Product datasheet
Specifications
voltage measurement relay RM4-U -
range 1..100 V - 24..240 V AC DC
RM4UA32MW
Discontinued on: 01 November 2020
Discontinued
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product Harmony Relay
Product or component type Industrial measurement and control relays
Relay type Voltage measurement relay
Relay name RM4U
Relay monitored parameters Overvoltage or undervoltage detection
Time delay Adjustable 0.05...30 s
Power consumption in VA 1.5…3.3 VA AC
Measurement range 1...10 V voltage AC 50/60 Hz
10...100 V voltage AC 50/60 Hz
5...50 V voltage AC 50/60 Hz
1...10 V voltage DC
10...100 V voltage DC
5...50 V voltage DC
Contacts type and composition 2 C/O
Complementary
Maximum switching voltage 440 V AC
[Us] rated supply voltage 24...240 V AC 50/60 Hz +/- 5 %
24...240 V DC
Maximum power consumption in 1.2 W DC
W
Output contacts 2 C/O
Internal input resistance 112000 Ohm
225000 Ohm
23000 Ohm
Permissible continuous 300 V
overload 90 V
150 V
Permissible non repetitive 100 A for <= 1 s
overload 200 A for <= 1 s
400 A for <= 1 s
Setting accuracy of the +/-5 %
switching threshold
Switching threshold drift <= 0.06 % per degree centigrade depending permissible ambient air temperature
<= 0.5 % within the supply voltage range (0.85...1.1 Un)
Setting accuracy of time delay 10 P
11 Jul, 2023 1
Time delay drift <= 0.07 % per degree centigrade depending on the rated operational temperature
<= 0.5 % within the supply voltage range (0.85...1.1 Un)
Hysteresis 5…30 % adjustable of voltage threshold setting
Quality labels CE
Overvoltage category III conforming to IEC 60664-1
[Ui] rated insulation voltage 500 V conforming to IEC
Operating voltage tolerance 0.85...1.1 Uc
Supply disconnection value > 0.1 Uc
Operating position Any position without derating
Connections - terminals Screw terminals, 2 x 1.5 mm²flexible with cable end
Screw terminals, 2 x 2.5 mm²flexible without cable end
Tightening torque 0.6…1.1 N.m
Mechanical durability 30000000 cycles
[Ith] conventional free air 8A
thermal current
[Ie] rated operational current 2 A at 70 °C 24 V DC-13 conforming to IEC 60947-5-1/1991
2 A at 70 °C 24 V DC-13 conforming to VDE 0660
3 A at 70 °C 115 V AC-15 conforming to IEC 60947-5-1/1991
3 A at 70 °C 115 V AC-15 conforming to VDE 0660
3 A at 70 °C 24 V AC-15 conforming to IEC 60947-5-1/1991
3 A at 70 °C 24 V AC-15 conforming to VDE 0660
3 A at 70 °C 250 V AC-15 conforming to IEC 60947-5-1/1991
3 A at 70 °C 250 V AC-15 conforming to VDE 0660
0.1 A at 70 °C 250 V DC-13 conforming to IEC 60947-5-1/1991
0.1 A at 70 °C 250 V DC-13 conforming to VDE 0660
0.3 A at 70 °C 115 V DC-13 conforming to IEC 60947-5-1/1991
0.3 A at 70 °C 115 V DC-13 conforming to VDE 0660
Switching capacity in mA 10 mA at 12 V
Switching voltage 250 V AC
Contacts material 90/10 silver nickel contacts
Number of cables 2
Height 78 mm
Width 22.5 mm
Depth 80 mm
Terminals description ISO n°1 (15-16-18)OC
(25-26-28)OC
(C-B1-B2-B3)CO
(A1-A2)CO
Output relay state Tripped if A measured > A set
9 mm pitches 2.5
Product weight 0.168 kg
Compatibility code RM4
Environment
Electromagnetic compatibility Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2
Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2
Standards EN/IEC 60255-6
Product certifications GL
CSA
UL
Directives 73/23/EEC - low voltage directive
89/336/EEC - electromagnetic compatibility
Ambient air temperature for -40…85 °C
storage
2
11 Jul, 2023
Ambient air temperature for -20…65 °C
operation
Relative humidity 15…85 % 3K3 conforming to IEC 60721-3-3
Vibration resistance 0.35 ms (f= 10…55 Hz) conforming to IEC 60068-2-6
Shock resistance 15 gn for 11 ms conforming to IEC 60068-2-27
IP degree of protection IP20 (terminals) conforming to IEC 60529
IP50 (casing) conforming to IEC 60529
Pollution degree 3 conforming to IEC 60664-1
Dielectric test voltage 2.5 kV
Non-dissipating shock wave 4.8 kV
Resistance to electrostatic 6 kV contact conforming to IEC 61000-4-2 level 3
discharge 8 kV air conforming to IEC 61000-4-2 level 3
Resistance to electromagnetic 10 V/m conforming to IEC 61000-4-3 level 3
fields
Resistance to fast transients 2 kV conforming to IEC 61000-4-4 level 3
Protection against electric 2 kV: level 3 conforming to IEC 61000-4-5
shocks
Disturbance radiated/ CISPR 11 group 1 - class A
conducted CISPR 22 - class A
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Contractual warranty
Warranty 18 months
11 Jul, 2023 3
Product datasheet RM4UA32MW
Dimensions Drawings
Voltage Measurement Relays
Dimensions
4
11 Jul, 2023
Product datasheet RM4UA32MW
Mounting and Clearance
Voltage Measurement Relays
Rail mounting
Screw fixing
11 Jul, 2023 5
Product datasheet RM4UA32MW
Connections and Schema
Voltage Measurement Relays
RM4UA01 and RM4UA02 Wiring Diagram
A1-A2 Supply voltage
B1, B2, B3, C Voltages to be measured (see table below)
Connection and current values to be measured
RM4UA•1 B1-C 0.05…0.5 V
B2-C 0.3…3 V
B3-C 0.5…5 V
RM4UA•2 B1-C 1…10 V
B2-C 5…50 V
B3-C 10…100 V
RM4UA03 Wiring Diagram
A1-A2 Supply voltage
B2, B3, C Voltages to be measured (see table below)
Connection and current values to be measured
B2-C 30…300 V
B3-C 50…500 V
RM4UA31 and RM4UA32 Wiring Diagram
A1-A2 Supply voltage
B1, B2, B3, C Voltages to be measured (see table below)
Connection and current values to be measured
RM4UA•1 B1-C 0.05…0.5 V
B2-C 0.3…3 V
B3-C 0.5…5 V
RM4UA•2 B1-C 1…10 V
B2-C 5…50 V
B3-C 10…100 V
6
11 Jul, 2023
RM4UA33 Wiring Diagram
A1-A2 Supply voltage
B2, B3, C Voltages to be measured (see table below)
Connection and current values to be measured
B2-C 30…300 V
B3-C 50…500 V
11 Jul, 2023 7
Product datasheet RM4UA32MW
Connections and Schema
Voltage Measurement Relays
Application Scheme
Example: overspeed monitoring (undervoltage function)
(1) Tachogenerator
(2) Overspeed
8
11 Jul, 2023
Product datasheet RM4UA32MW
Performance Curves
Electrical Durability and Load Limit Curves
AC Load
Curve 1: Electrical durability of contacts on resistive load in millions of operating cycles
X Current broken in A
Y Millions of operating cycles
Curve 2: Reduction factor k for inductive loads (applies to values taken from durability Curve 1)
X Power factor on breaking (cos φ)
Y Reduction factor K
DC Load
Load limit curve
X Current in A
Y Voltage in V
1 L/R = 20 ms
2 L/R with load protection diode
3 Resistive load
11 Jul, 2023 9
Product datasheet RM4UA32MW
Technical Description
Function Diagram
Overvoltage Control
Function “>”
Legend
t Time delay
U A1-A2 Supply voltage
US1 Setting voltage threshold
US2 Voltage measured
15-18, 15-16; 25-28, 25-26 Output relays connections
Relay status: black color = energized.
10
11 Jul, 2023
Product datasheet RM4UA32MW
Technical Description
Function Diagram
Undervoltage Control
Function “<”
Legend
t Time delay
U A1-A2 Supply voltage
US1 Setting voltage threshold
US2 Voltage measured
15-18, 15-16; 25-28, 25-26 Output relays connections
Relay status: black color = energized.
Recommended replacement(s)
RM4UA32MW is replaced by:
Modular 1-phase voltage control relay, 8 A, 2 CO, 1…100 V AC/DC, 24…240 V AC/
1x DC
RM22UA32MR
11 Jul, 2023 11