TECHNICAL DATA
SHEET NO. 401
Fire door openings are classified by their locations in the building. The location determines the length of exposure
protection required, based on the potential fire hazard of that particular area. The six opening classifications are shown
below along with the six door ratings and the maximum amount of glass in square inches allowed for each door.
Label
Maximum
Classification Location In Building
Glass Area
3 100 square inches
3 hour rated opening (Class A). Openings are in walls separating
HOUR per leaf.
buildings or dividing a single building into fire areas. Doors for these
RATING See note 1.
openings require a fire protection rating of 3 hours.
3/4 hour rated opening (Class C). Openings are in corridors and
1296 square inches
3/4 room partitions. Doors for these areas require a fire protection rating per light. Neither
HOUR of 3/4 hour, and the glass area cannot exceed 1296 square inches dimension to exceed
RATING per light with no dimension exceeding 54 inches except as noted 54”. See note 2.
below.
1 1/2 hour rated opening (Class D). Openings are in exterior walls
1-1/2 which are subject to severe fire exposure from the outside of the
HOUR See note 3.
building. Doors for these areas require a fire protection rating of 1 1/2
RATING hours.
3/4 hour rated opening (Class E). Openings are in exterior walls
which are subject to moderate or light fire exposure from the outside 1296 square inches
3/4 of the building. A typical example would be a door leading to an per light. Neither
HOUR exterior fire escape. Doors for these openings require a fire dimension to exceed
RATING protection rating of 3/4 hour with glass areas not exceeding 1296 54”. See note 3.
square inches per light with no dimension exceeding 54 inches.
20 minute fire rated door frame assemblies are normally found in 1296 square inches
interior partitions and are intended for installation with 20 minutes fire per light. Neither
20 rated doors of the single swing, swing in pairs, or double egress dimension to exceed
MINUTE types. 54”. See note 2.
Revised 9/14
Note 1. 100 square inches when using Firelite glass. Neither dimension exceeding 33”.
Note 2. Except when using Pemko fire glazing compound. See U.L. procedure or consult factory.
Note 3. Consult with local authority having jurisdiction for allowable glass.
Republic provides a comprehensive line of 1-3/8” and 1-3/4” thick labeled doors and frames to meet
every requirement for fire protection. The construction conforms to fire door procedure whether the
doors are furnished with labels or not. Since label requirements vary throughout the country, local
authorities having jurisdiction regarding the use of label opening should be consulted during the design
and planning stages.
Doors and frames approved by the Underwriters Laboratories, Inc. have been investigated, fire tested in
accordance with UL10B, UL10C, UBC7-2 and ASTM E-152 and produced under the Underwriters
Laboratory factory inspection and labeling service program. The attachment of the Underwriters
Laboratories Listing or Classification mark indicates that the material has been constructed to comply
with the manufacturing specifications as described in the Underwriters Laboratories Follow-Up Service
Procedures Program.
Doors and frames bearing the Warnock Hersey Label have been successfully fire tested in accordance
with UL10B, UL10C, UBC7-2 and ASTM E-152. The Warnock Hersey Listing or Classification mark
indicates that the material has been constructed to comply with the manufacturing specifications as
described in Warnock Hersey’s Follow-Up Service Procedures Program.
Revised 9/14
B. Check and fulfill the fire insurance company’s requirement for the specific building.
C. Establish which label (UL or WH) is acceptable to local authorities having jurisdiction (LAHJ).
Multiple lights
permitted in 3/4 hr.
& 20 minute
labeled doors only
MAXIMUM
DOOR TYPE SIZE VISION GLASS NARROW GLASS HALF GLASS FULL GLASS
DE 820 3072 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. 3/4 Hr., 20 Min. 20 Min Without Hose Stream
DE 818 3072 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. 3/4 Hr., 20 Min. 20 Min Without Hose Stream
DM 820 3072 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. 3/4 Hr., 20 Min. 20 Min Without Hose Stream
DL/DE 420 3072 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. 3/4 Hr., 20 Min. 20 Min Without Hose Stream
DL/DE 418 40100 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. 3/4 Hr., 20 Min. 20 Min Without Hose Stream
DL/DE 416 40100 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. 3/4 Hr., 20 Min. 20 Min Without Hose Stream
DL/DE 420 (Insulated) 3072 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. 3/4 Hr., 20 Min. Not Available
DL/DE 418 (Insulated) 4080 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. 3/4 Hr., 20 Min. Not Available
DL/DE 416 (Insulated) 4080 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. 3/4 Hr., 20 Min. Not Available
DL/DE 420 (Temp. Rise) 3072 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. Not Available Not Available
DL/DE 418 (Temp. Rise) 4080 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. Not Available Not Available
DL/DS 418 50100 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. 3/4 Hr., 20 Min. Not Available
DL/DS 416 50100 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. 3/4 Hr., 20 Min. Not Available
DM 420 3072 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. 3/4 Hr., 20 Min. 20 Min Without Hose Stream
DM 418 4070 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. 3/4 Hr., 20 Min. 20 Min Without Hose Stream
UNIFIT™ 4080 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. 3/4 Hr., 20 Min. 20 Min Without Hose Stream
• Vision Glass - exposed glass area is not to exceed 100 square inches with no dimension exceeding 33”.
• 3-hour doors with light must incorporate Firelight or Firelight Plus glazing.
• Narrow Glass - exposed glass area is not to exceed 100 square inch with no dimension exceeding 33”.
• Half Glass - exposed glass area is not to exceed 1296 square inch with no dimension exceeding 54”.
• Full Glass - exposed glass area is not to exceed 2994 square inch with the width not to exceed 35-13/16”
and the height not to exceed 85-5/8”.
Revised 9/14
• Doors may be provided for Listed glass kits to be installed at the job site. A supplemental marking is
required specifying which manufacturer’s glass kit is to be used. Reinforcing channels must be provided
unless All Metal Stamping Model No. 110UL kit or Anemostat Listed kit with HM clips is used.
• Other approved glass kits for use in RBP doors are manufactured by Leslie-Locke and Air Louver.
• See Technical Data Sheet 405 for Unifit™ door limitations.
Single Doors
• Doors may be fabricated from
Door Type Maximum Size Rating Available
cold rolled or galvanized steel. DE 820 3072 ( 914 x 2184) 1 1/2 Hr., 3/4 Hr., 20 Min.
• 20 gage, 18 gage or 16 gage DE 818 3072 ( 914 x 2184) 1 1/2 Hr., 3/4 Hr., 20 Min.
“Unifit” Doors can be labeled after DM 820 3072 ( 914 x 2184) 1 1/2 Hr., 3/4 Hr., 20 Min.
the appropriate preparations are DE & DL 420 4080 (1219 x 2438) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
added by an authorized U.L. or DE & DL 418 40100 (1219 x 3048) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
W.H. warehouse or distributor. DE & DL 416 40100 (1219 x 3048) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
Maximum size 20 gage Unifit door DE 414 40100 (1219 x 3048) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
is 3072. DE 420 (Insulated) 3072 ( 914 x 2184) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
DE & DL 418 (Insulated) 4080 (1219 x 2438) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
• DE 418 and 420 Doors may be
DE & DL 416 (Insulated) 4080 (1219 x 2438) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
full flush or (6) panel embossed design. Six DE & DL 420 (Temp. Rise) 3072 ( 914 x 2184) 3 Hr., 1 1/2 Hr., 3/4 Hr.
panel doors are available as insulated only. DE & DL 418 (Temp. Rise) 4080 (1219 x 2438) 3 Hr., 1 1/2 Hr., 3/4 Hr.
DS 418 4080 (1219 x 2438) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
DS 416 50100 (1524 x 3048) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
DS 414 50100 (1224 x 3048) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
DM 420 4070 (1219 x 2134) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
DM 418 4070 (1219 x 2134) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
UNIFIT™ 4080 (1219 x 2438) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
DM 420 8070 (2438 x 2134) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
DM 418 8070 (2438 x 2134) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
UNIFIT™ 8080 (2438 x 2438) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
Note: See Technical Data Sheet 405 for Unifit™ door limitations.
Double Egress
Multiple
Frames
Opening
• Labeled frames may be of 16 gage or 14 gage steel.
Frame • Maximum door opening size: 8090.
• Maximum rating: 3 hours.
• Labeled frames may be of 16 gage, 14 gage or 12 gage steel. • A supplemental marking that reads: “Double egress fire doors by Republic
• Jamb Depth: 4 3/4” (121) to 20” (508). Builders Products” is required to be placed next to the U.L. Listing mark.
• Maximum door opening size: 4080. • Frames may also be used with 20 minute or 3/4 hour clasified wood doors.
Revised 9/14
• Maximum frame size: These frames require a supplemental marking that reads: “For use with clasified
98” (2489) high x 152” (3861) wide. double egress 20 minute or 3/4 hour doors” placed next to the U.L. Listing mark.
• Maximum Rating: 1 1/2 hours.
• Welded only.
• A stop height of 5/8”(16) is required for a maximum exposed glass of up to • Maximum rating: 1 1/2 hour.
• Requires a supplemental marking that specifies:
2650 sq. in.
“FOR USE ONLY WITH A CLASSIFIED TRANSOM PANEL AND ANY
• Fire window frames are intended for installation in masonry walls or for
CLASSIFIED FIRE DOOR HAVING A RATING UP TO 1 1/2 HOURS.”
installation in walls utilizing wood/steel studs.
• Each jamb shall be provided with a sill anchor and a jamb anchor for each
30” (762) of height or fraction thereof. An intermediate base anchor is
required for frames over 4’0” (1219) wide. Transom Frame With Transom Bar
Hollow Metal
• Must be welded. Panel
• Labeled frames may be of 16 gage, 14 gage or 12 gage steel.
20 Minute Frame • Maximum frame opening size: 4’0” (1219) x 11’0” (3353).
• Maximum door size: 4080.
with Lights • Maximum panel height: 4’0” (1219).
• Jamb Depth: 4 1/2” (114) thru 20” (508).
• Maximum rating: 3 hours.
• Twenty minute type door frame with lights, fire tested without hose stream, for
• Maximum panel height: 34” (864)
walls at least 3 1/2” (89) thick.
*Fixed mullion unit must be welded.
• ME/SE Series profile may be 12 gage, 14 gage or 16 gage steel.
• MH/SH Series profile may be 16 gage or 14 gage steel.
• Mitered corner connections are standard. 12 gage will be coped.
• Jamb Depth:
ME/SE profile - Sgl. Rbt. 3” (76) to 20” (508).
Transom Frame Without Transom Bar
Dbl. Rbt. 4 1/2” (114) to 20” (508).
MH/SH profile -Sgl. Rbt. 3 1/2” (89) to 15” (381).
Dbl. Rbt. 4 1/2” (114) to 15” (381). • Labeled frames may be of 16 gage, 14 gage or 12 gage steel.
• Labeled panels may be of 18 or 20 ga. steel.
• The overall frame size shall not exceed 158 in. (4013) (13ft. 2 in.) in width and
• Maximum frame opening size: 4’0” (1219) x 11’0” (3353). Hollow Metal
139 in. (3531) (11 ft. 7 in.) in height. Panel
• Maximum door size: 4080 single.
• The maximum size opening for the individual transom lights or sidelights shall
• Jamb Depth: 4 1/2” (114) thru 20” (508).
not exceed 5268 inches in area, and the maximum width or height of the
• Maximum rating: 3 hours.
individual light shall not exceed 109 3/4 inches (2788). • Astragal required at bottom of panel for 3 hour rating.
• 5/8” (16) glazing bead. • Maximum panel height: 34” (864).
Revised 9/14
Wire Masonry Wood Steel/Stud Twist in Prepared One Piece Sill Anchor
Anchor Anchor Opening Anchor Welded On
(Shipped Loose) (Shipped Loose)
MH
Intermediate
Anchor
(Shipped Loose)
Welded
Frame
Non-Handed
Frame
Revised 9/14
Republic U.L. Labeled Temperature Rise Door is of steel-covered composite fire door construction and
fabricated of 20 or 18 gage steel panels bonded to a mineral fiber board core. The temperature
developed on the unexposed face of the door after the first 30 minutes of a fire test did not exceed 250o
Fahrenheit above the ambient temperature.
Minutes
5 15 30
2000
1550
1500
Unexposed
Degrees Fahrenheit
500
DE Series Doors shall have lock edge non-beveled and reinforced with a continuous 14 gage channel.
Reinforcements for mortise or cylindrical locks shall be of a integral type and in accordance with ANSI
A115 Standards.
Hinge edge is non-beveled and reinforced with a continuous 10 gage channel, projection welded at
maximum 5” on centers.
Doors shall have a flush top and inverted bottom 16 gage channel projection welded at maximum 2-1/2”
on centers.
Doors are thoroughly cleaned, phosphatized and receive one coat of force-cured prime paint.
Doors are individually packaged, completely covering the door to prevent damage to door or finish. The
doors should be stored in an upright position, under cover at the building site on wood sills, or in a
manner that will prevent rust or damage.
Revised 9/14
Glass lights are permitted in doors with up to a maximum of 100 square inches of glass area per leaf.
16 gage flush
top continuous closer reinforcement
steel channel when specified
25 1/2"
21 1/2"