Republic-Fire-Rated-Doors

The document outlines the basic requirements and classifications for fire doors based on their location and fire ratings, detailing maximum glass area allowed for each type. It also provides information on the types of fire door openings, the importance of compliance with Underwriters Laboratories and Warnock Hersey standards, and suggested procedures for selecting fire doors and frames. Additionally, it specifies guidelines for fire doors with glass, including size limitations and installation requirements.

Uploaded by

Ahmar Khateeb
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
16 views14 pages

Republic-Fire-Rated-Doors

The document outlines the basic requirements and classifications for fire doors based on their location and fire ratings, detailing maximum glass area allowed for each type. It also provides information on the types of fire door openings, the importance of compliance with Underwriters Laboratories and Warnock Hersey standards, and suggested procedures for selecting fire doors and frames. Additionally, it specifies guidelines for fire doors with glass, including size limitations and installation requirements.

Uploaded by

Ahmar Khateeb
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 14

BASIC FIRE DOOR REQUIREMENTS

TECHNICAL DATA
SHEET NO. 401

Fire door openings are classified by their locations in the building. The location determines the length of exposure
protection required, based on the potential fire hazard of that particular area. The six opening classifications are shown
below along with the six door ratings and the maximum amount of glass in square inches allowed for each door.

Label
Maximum
Classification Location In Building
Glass Area
3 100 square inches
3 hour rated opening (Class A). Openings are in walls separating
HOUR per leaf.
buildings or dividing a single building into fire areas. Doors for these
RATING See note 1.
openings require a fire protection rating of 3 hours.

1 1/2 hour rated opening (Class B). Openings are in enclosures of


vertical communication through buildings. These could be stairwells
1-1/2 or elevator shafts. While not a means of vertical communication, 100 square inches
HOUR per leaf.
boiler room doors are generally categorized as Class “B” openings.
RATING See note 2.
Door for these areas require a fire protection rating of 1 1/2 hours,
and glass areas may not exceed 100 square inches per individual
door leaf except as noted below.

3/4 hour rated opening (Class C). Openings are in corridors and
1296 square inches
3/4 room partitions. Doors for these areas require a fire protection rating per light. Neither
HOUR of 3/4 hour, and the glass area cannot exceed 1296 square inches dimension to exceed
RATING per light with no dimension exceeding 54 inches except as noted 54”. See note 2.
below.
1 1/2 hour rated opening (Class D). Openings are in exterior walls
1-1/2 which are subject to severe fire exposure from the outside of the
HOUR See note 3.
building. Doors for these areas require a fire protection rating of 1 1/2
RATING hours.

3/4 hour rated opening (Class E). Openings are in exterior walls
which are subject to moderate or light fire exposure from the outside 1296 square inches
3/4 of the building. A typical example would be a door leading to an per light. Neither
HOUR exterior fire escape. Doors for these openings require a fire dimension to exceed
RATING protection rating of 3/4 hour with glass areas not exceeding 1296 54”. See note 3.
square inches per light with no dimension exceeding 54 inches.

20 minute fire rated door frame assemblies are normally found in 1296 square inches
interior partitions and are intended for installation with 20 minutes fire per light. Neither
20 rated doors of the single swing, swing in pairs, or double egress dimension to exceed
MINUTE types. 54”. See note 2.
Revised 9/14

Note 1. 100 square inches when using Firelite glass. Neither dimension exceeding 33”.
Note 2. Except when using Pemko fire glazing compound. See U.L. procedure or consult factory.
Note 3. Consult with local authority having jurisdiction for allowable glass.

Republic Doors and Frames


155 Republic Drive • McKenzie, Tennessee 38201 • (731) 352-3383
TYPES OF FIRE DOOR OPENINGS
TECHNICAL DATA
SHEET NO. 402

Republic provides a comprehensive line of 1-3/8” and 1-3/4” thick labeled doors and frames to meet
every requirement for fire protection. The construction conforms to fire door procedure whether the
doors are furnished with labels or not. Since label requirements vary throughout the country, local
authorities having jurisdiction regarding the use of label opening should be consulted during the design
and planning stages.

Underwriters Laboratories (UL)

Doors and frames approved by the Underwriters Laboratories, Inc. have been investigated, fire tested in
accordance with UL10B, UL10C, UBC7-2 and ASTM E-152 and produced under the Underwriters
Laboratory factory inspection and labeling service program. The attachment of the Underwriters
Laboratories Listing or Classification mark indicates that the material has been constructed to comply
with the manufacturing specifications as described in the Underwriters Laboratories Follow-Up Service
Procedures Program.

Warnock Hersey (WH)

Doors and frames bearing the Warnock Hersey Label have been successfully fire tested in accordance
with UL10B, UL10C, UBC7-2 and ASTM E-152. The Warnock Hersey Listing or Classification mark
indicates that the material has been constructed to comply with the manufacturing specifications as
described in Warnock Hersey’s Follow-Up Service Procedures Program.
Revised 9/14

Republic Doors and Frames


155 Republic Drive • McKenzie, Tennessee 38201 • (731) 352-3383
SUGGESTED PROCEDURES FOR THE
SELECTION OF FIRE DOORS & FRAMES TECHNICAL DATA
SHEET NO. 403

A. Determine the appropriate building code.

B. Check and fulfill the fire insurance company’s requirement for the specific building.

C. Establish which label (UL or WH) is acceptable to local authorities having jurisdiction (LAHJ).

D. Basic Fire Door Requirements--


Use this checklist:
1. A fire door must have a Classification mark attached. (metal or mylar)
2. A fire door frame must have a Listing Mark on the hinge jamb - one on each hinge jamb of a double opening.
A fire door frame may be embossed with a UL Listing Mark if acceptable with the LAHJ.
3. A fire door must be self-closing and self-latching.
4. Door closers or UL Listed spring hinges are required on all fire doors.
5. An automatic closing door must have a separate, Listed, fail-safe-door-holder/release device or a hold-open
mechanism which may be an integral part of the basic closing device, provided the hold-open mechanism is
released by one or a combination of automatic fire detectors acceptable to the authority having jurisdiction.
6. A fire door must be free of any obstructions which would prevent the door from operating properly, i.e. wedge
door stops, chains, hook-backs, etc.
7. Only listed fire door hardware shall be used.
8. A fire door must have steel hinges.
9. A pair of doors must have an overlapping steel astragal for 3 hour rated locations.
10. A pair of doors may be furnished without an astragal for 1-1/2 hour and 3/4 hour locations providing the
opening meets one of the following:
a. Each leaf is equipped with a vertical rod exit device or rim exit device (with hardware mullion).
b. The door leaves have one mortise and one vertical rod exit device with open or closed back strike.
c. The active door leaf has a mortise or cylindrical lock with open or closed back strike; inactive door has
flush bolts.
11. Fire doors with glass lites:
a. Reinforcement channel must be provided except as noted on Tech Data Sheet 404.
b. Glass frame and glazing bead must be steel.
c. Glass must be 1/4” thick wire glass or other UL Listed glazing material.
d. Maximum allowable glass area (subject to approval of LAHJ):
•3 hours, 100 sq. in. per door leaf (Firelite)
•1-1/2 hours, 100 square inches per door leaf
•3/4 hour, 1296 square inches per door lite
12. Fire doors with fusible link louvers:
a. A Listed louver must be used. Door may be furnished with louver installed at door manufacturer’s
plant or cutout reinforced and labeled for field installation.
b. Louvers can be furnished in 1-3/4”, 1-1/2 hour and 3/4 hour label flush doors only (no louver
and glass lite combinations permitted).
c. Maximum door size with louver is 3’6” x 7’2”.
d. Only one louver per door leaf. Maximum louver size is 24” x 24”.
e. Louvers are not permitted to be installed in doors with Fire Exit Device Hardware.

E. For maximum fire protection, NFPA-80 should be used as a guideline.


Revised 9/14

Republic Doors and Frames


155 Republic Drive • McKenzie, Tennessee 38201 • (731) 352-3383
FIRE DOORS WITH GLASS
TECHNICAL DATA
SHEET NO. 404

6” minimum 6” minimum 6” minimum


6” minimum

6” minimum to 6” minimum to 6” minimum to


6” minimum to
exposed glass exposed glass exposed glass
exposed glass

Multiple lights
permitted in 3/4 hr.
& 20 minute
labeled doors only

VISION GLASS NARROW GLASS HALF GLASS FULL GLASS

MAXIMUM
DOOR TYPE SIZE VISION GLASS NARROW GLASS HALF GLASS FULL GLASS

DE 820 3072 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. 3/4 Hr., 20 Min. 20 Min Without Hose Stream
DE 818 3072 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. 3/4 Hr., 20 Min. 20 Min Without Hose Stream
DM 820 3072 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. 3/4 Hr., 20 Min. 20 Min Without Hose Stream
DL/DE 420 3072 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. 3/4 Hr., 20 Min. 20 Min Without Hose Stream
DL/DE 418 40100 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. 3/4 Hr., 20 Min. 20 Min Without Hose Stream
DL/DE 416 40100 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. 3/4 Hr., 20 Min. 20 Min Without Hose Stream
DL/DE 420 (Insulated) 3072 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. 3/4 Hr., 20 Min. Not Available
DL/DE 418 (Insulated) 4080 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. 3/4 Hr., 20 Min. Not Available
DL/DE 416 (Insulated) 4080 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. 3/4 Hr., 20 Min. Not Available
DL/DE 420 (Temp. Rise) 3072 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. Not Available Not Available
DL/DE 418 (Temp. Rise) 4080 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. Not Available Not Available
DL/DS 418 50100 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. 3/4 Hr., 20 Min. Not Available
DL/DS 416 50100 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. 3/4 Hr., 20 Min. Not Available
DM 420 3072 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. 3/4 Hr., 20 Min. 20 Min Without Hose Stream
DM 418 4070 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. 3/4 Hr., 20 Min. 20 Min Without Hose Stream
UNIFIT™ 4080 3 Hr., 1-1/2 Hr., 3/4 Hr., 20 Min. 3, 1-1/2 Hr., 3/4 Hr., 20 Min. 3/4 Hr., 20 Min. 20 Min Without Hose Stream

• Vision Glass - exposed glass area is not to exceed 100 square inches with no dimension exceeding 33”.
• 3-hour doors with light must incorporate Firelight or Firelight Plus glazing.
• Narrow Glass - exposed glass area is not to exceed 100 square inch with no dimension exceeding 33”.
• Half Glass - exposed glass area is not to exceed 1296 square inch with no dimension exceeding 54”.
• Full Glass - exposed glass area is not to exceed 2994 square inch with the width not to exceed 35-13/16”
and the height not to exceed 85-5/8”.
Revised 9/14

• Doors may be provided for Listed glass kits to be installed at the job site. A supplemental marking is
required specifying which manufacturer’s glass kit is to be used. Reinforcing channels must be provided
unless All Metal Stamping Model No. 110UL kit or Anemostat Listed kit with HM clips is used.
• Other approved glass kits for use in RBP doors are manufactured by Leslie-Locke and Air Louver.
• See Technical Data Sheet 405 for Unifit™ door limitations.

Republic Doors and Frames


155 Republic Drive • McKenzie, Tennessee 38201 • (731) 352-3383
LABELED DOOR SIZES AND TYPES
TECHNICAL DATA
SHEET NO. 405

Single Doors
• Doors may be fabricated from
Door Type Maximum Size Rating Available
cold rolled or galvanized steel. DE 820 3072 ( 914 x 2184) 1 1/2 Hr., 3/4 Hr., 20 Min.
• 20 gage, 18 gage or 16 gage DE 818 3072 ( 914 x 2184) 1 1/2 Hr., 3/4 Hr., 20 Min.
“Unifit” Doors can be labeled after DM 820 3072 ( 914 x 2184) 1 1/2 Hr., 3/4 Hr., 20 Min.
the appropriate preparations are DE & DL 420 4080 (1219 x 2438) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
added by an authorized U.L. or DE & DL 418 40100 (1219 x 3048) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
W.H. warehouse or distributor. DE & DL 416 40100 (1219 x 3048) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
Maximum size 20 gage Unifit door DE 414 40100 (1219 x 3048) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
is 3072. DE 420 (Insulated) 3072 ( 914 x 2184) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
DE & DL 418 (Insulated) 4080 (1219 x 2438) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
• DE 418 and 420 Doors may be
DE & DL 416 (Insulated) 4080 (1219 x 2438) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
full flush or (6) panel embossed design. Six DE & DL 420 (Temp. Rise) 3072 ( 914 x 2184) 3 Hr., 1 1/2 Hr., 3/4 Hr.
panel doors are available as insulated only. DE & DL 418 (Temp. Rise) 4080 (1219 x 2438) 3 Hr., 1 1/2 Hr., 3/4 Hr.
DS 418 4080 (1219 x 2438) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
DS 416 50100 (1524 x 3048) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
DS 414 50100 (1224 x 3048) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
DM 420 4070 (1219 x 2134) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
DM 418 4070 (1219 x 2134) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
UNIFIT™ 4080 (1219 x 2438) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.

Dutch Doors • Dutch Doors must have an


astragal attached to the top leaf.
• A half shelf is optional.
Door Type Maximum Size Rating Available • Lock provision may be for either
DL 420 3072 (914 x 2184) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min. cylindrical or mortise lock sets.
DL 418 4072 (1219 x 2184) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min. • Louvers are not permitted.
DE 420 3072 (914 x 2184) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min. • Glass lights are permitted in 1-1/2
DE 418 4072 (1219 x 2184) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min. hr., 3/4 hr. and 20 min. rated doors.

• Surface mounted or concealed Double Egress Doors


vertical rod device hardware is
required on each leaf.
Door Type Maximum Size Rating Available
• All series doors exceeding 1 1/2
DM 418 8080 (2438 x 2438) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
hr. rating require an astragal. DE & DL 420 8080 (2438 x 2438) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
• Glass lights are permitted up to DE & DL 418 8080 (2438 x 2438) 1 1/2 Hr., 3/4 Hr., 20 Min.
100 sq. in. of exposed glass per DE & DL 416 8080 (2438 x 2438) 1 1/2 Hr., 3/4 Hr., 20 Min.
leaf in 1 1/2 hr. rated doors and DE 418 (Insulated) 8080 (2438 x 2438) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
1296 sq. in. of exposed glass DE 420 (Insulated) 8080 (2438 x 2438) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
per light in 3/4 hr. rated doors.

Doors with Fusible Link Louvers


Revised 9/14

Door Type Maximum Size Label Available


DM 420 3072 (914 x 2184) 1 1/2 Hr., 3/4 Hr. • Maximum louver size: one 24”
DL 418 3672 (914 x 2184) 1 1/2 Hr., 3/4 Hr. (610) x 24” (610) per door leaf.
DE & DL 420 3072 (1067 x 2184) 1 1/2 Hr., 3/4 Hr.
Not available with glass lites or
DE & DL 418 3672 (1067 x 2184) 1 1/2 Hr., 3/4 Hr.
DE 416 3672 (1067 x 2184) 1 1/2 Hr., 3/4 Hr.
fire exit hardware.

Republic Doors and Frames


155 Republic Drive • McKenzie, Tennessee 38201 • (731) 352-3383
LABELED DOOR SIZES AND TYPES
(CONTINUED) TECHNICAL DATA
SHEET NO. 405a

Pairs of Doors without Astragal

Mortise and vertical rod Surface or concealed vertical rod


exit devices with open exit device on each leaf (two
or closed back strike active leaves) or rim exit device
with hardware mullion (two
active leaves).

Door Type Maximum Size Rating Available


DM 420 8070 (2438 x 2134) 1 1/2 Hr., 3/4 Hr., 20 Min.
DM 418 8070 (2438 x 2134) 1 1/2 Hr., 3/4 Hr., 20 Min.
DE & DL 418 80100 (2438 x 3048) 1 1/2 Hr., 3/4 Hr., 20 Min.
DE & DL 416 80100 (2438 x 3048) 1 1/2 Hr., 3/4 Hr., 20 Min.
DS 418 80100 (2438 x 3048) 1 1/2 Hr., 3/4 Hr., 20 Min.
Mortise or cylindrical DS 416 80100 (2438 x 3048) 1 1/2 Hr., 3/4 Hr., 20 Min.
lock with open or DE 420 (Temp. Rise) 6072 (1829 x 2184) 1 1/2 Hr., 3/4 Hr.
DE 418 (Temp. Rise) 8072 (2438 x 2184) 1 1/2 Hr., 3/4 Hr.
closed back strike and
DE & DL 418 (Insulated) 8080 (2438 x 2438) 1 1/2 Hr., 3/4 Hr., 20 Min.
flush bolts DE & DL 416 (Insulated) 8080 (2438 x 2438) 1 1/2 Hr., 3/4 Hr., 20 Min.
UNIFIT™ 8080 (2438 x 2438) 1 1/2 Hr., 3/4 Hr., 20 Min.

Pairs of Doors with Astragal


Door Type Maximum Size Rating Available
DE 820 6072 (1829 x 2184) 1 1/2 Hr., 3/4 Hr., 20 Min.
DE 818 6072 (1829 x 2184) 1 1/2 Hr., 3/4 Hr., 20 Min.
DM 820 6072 (1829 x 2184) 1 1/2 Hr., 3/4 Hr., 20 Min.
Mortise or cylindrical DE & DL 420 8080 (2438 x 2438) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
lock with open or DE & DL 418 80100 (2438 x 3048) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
closed back strike and DE & DL 416 80100 (2438 x 3048) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
DE 414 80100 (2438 x 3048) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
flush bolts
DE & DL 420 (Insulated) 6072 (1829 x 2184) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
DE & DL 418 (Insulated) 8080 (2438 x 2438) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
DE & DL 416 (Insulated) 8080 (2438 x 2438) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
DE 420 (Temp. Rise) 6072 (1829 x 2184) 3 Hr., 1 1/2 Hr., 3/4 Hr.
DE 418 (Temp. Rise) 8080 (2438 x 2438) 3 Hr., 1 1/2 Hr., 3/4 Hr.
DS 418 80100 (2438 x 3048) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
DS 416 80100 (2438 x 3048) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
Revised 9/14

DM 420 8070 (2438 x 2134) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
DM 418 8070 (2438 x 2134) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.
UNIFIT™ 8080 (2438 x 2438) 3 Hr., 1 1/2 Hr., 3/4 Hr., 20 Min.

Note: See Technical Data Sheet 405 for Unifit™ door limitations.

Republic Doors and Frames


155 Republic Drive • McKenzie, Tennessee 38201 • (731) 352-3383
LABELED FRAME SIZES AND TYPES
TECHNICAL DATA
SHEET NO. 406

Three Transom and


Sided Sidelight
Frames Frame
• Universal (ME) Frame
• Labeled frames may be of 16 gage, 14 gage, or 12 gage steel. (12 gage
must be welded)
• Maximum door opening size: 40100 single, 80100 double.
• Maximum rating: 3 hours.
• Jamb Depths:
• Labeled frames may be of 16, 14 or 12 gage steel.
3” (76) to 20” (508) Sgl. Rabbet
• Maximum frame size: 12’0” (3658) x 10’0” (3048) or 10’0” (3048) x 12’0” (3658)
4 1/2” (114) to 20” (508) Dbl. Rabbet
for masonry installations and 12’0” (3658) x 10’0” (3048) for drywall installations.
• Removable Fire Rated/UL approved hardware mullion permitted (up to
• Maximum door opening size: 4080 single, 8080 double.
three hour rating).
• Jamb Depth: 4 3/4” (121) to 20” (508).
• Anchors may be shipped loose for up to 3 hr. frames, single or double
• Maximum exposed glass size: 1296 sq. in. with a maximum exposed width of 54”
opening.
(1372).
• Based on welded construction.
• Maximum exposed panel size: 1296 sq. in. with a maximum transom width of
39” (991) and with a maximum height of 36” (914).
• Maximum rating: 1 1/2 hr. with panels, 3/4 hr. with glass for masonry or drywall
• Drywall (MH) Frame.
installations.
• Labeled frames shall be of 16 or 14 gage steel.
• A stop height of 5/8” (16) is required for a maximum exposed glass of 1296 sq.
• Maximum door opening size:
in. When using special glazing compound 4704 sq. in.
4090 single, 8090 double.
• A stop height of 5/8” (16) is required for panels.
• Maximum rating: 1 1/2 hours.
• Each jamb shall be provided with a sill anchor and (2) jamb anchors for heights
• Jamb Depths:
up to and including 60” (1524) and an additional anchor for each additional 30”
3” (76) to 15” (381) Sg. Rabbet
(762) of fraction thereof.
4 1/2” (114) to 15” (381) Dbl. Rabbet
• Welded only
• Based on knockdown construction.

Double Egress
Multiple
Frames
Opening
• Labeled frames may be of 16 gage or 14 gage steel.
Frame • Maximum door opening size: 8090.
• Maximum rating: 3 hours.
• Labeled frames may be of 16 gage, 14 gage or 12 gage steel. • A supplemental marking that reads: “Double egress fire doors by Republic
• Jamb Depth: 4 3/4” (121) to 20” (508). Builders Products” is required to be placed next to the U.L. Listing mark.
• Maximum door opening size: 4080. • Frames may also be used with 20 minute or 3/4 hour clasified wood doors.
Revised 9/14

• Maximum frame size: These frames require a supplemental marking that reads: “For use with clasified
98” (2489) high x 152” (3861) wide. double egress 20 minute or 3/4 hour doors” placed next to the U.L. Listing mark.
• Maximum Rating: 1 1/2 hours.
• Welded only.

Republic Doors and Frames


155 Republic Drive • McKenzie, Tennessee 38201 • (731) 352-3383
LABELED FRAME SIZES AND TYPES
(CONTINUED) TECHNICAL DATA
SHEET NO. 406a

Borrowed Light Frame


Typical Elevation Transom Frames
• Labeled frames may be of 16 gage or 14 gage or 12 gage Transom Frame Without Transom Bar
steel. Wood Panel
• Maximum size: 9’4” (2845) wide x 8’10” (2692) high.
• Jamb Depth: 4 3/4” (121) to 20” (508). • Labeled frames may be of 16 gage, 14 gage or 12 gage steel.
• Face Dimensions: 1” (25) minimum - 2” (51) maximum. • Maximum frame opening size: 4’0” (1219) x 11’0” (3353).
• Maximum Rating: 3/4 hour. • Maximum door size: 4080.
• Maximum Exposed Glass: 2650 sq. in. with a maximum exposed width of 53” • Maximum panel height: 48 1/2” (1232)-
(1346) and maximum expanded height of 50” (1270). • Jamb Depth: 4 1/2” (114) thru 20” (508).

• A stop height of 5/8”(16) is required for a maximum exposed glass of up to • Maximum rating: 1 1/2 hour.
• Requires a supplemental marking that specifies:
2650 sq. in.
“FOR USE ONLY WITH A CLASSIFIED TRANSOM PANEL AND ANY
• Fire window frames are intended for installation in masonry walls or for
CLASSIFIED FIRE DOOR HAVING A RATING UP TO 1 1/2 HOURS.”
installation in walls utilizing wood/steel studs.
• Each jamb shall be provided with a sill anchor and a jamb anchor for each
30” (762) of height or fraction thereof. An intermediate base anchor is
required for frames over 4’0” (1219) wide. Transom Frame With Transom Bar
Hollow Metal
• Must be welded. Panel
• Labeled frames may be of 16 gage, 14 gage or 12 gage steel.
20 Minute Frame • Maximum frame opening size: 4’0” (1219) x 11’0” (3353).
• Maximum door size: 4080.
with Lights • Maximum panel height: 4’0” (1219).
• Jamb Depth: 4 1/2” (114) thru 20” (508).
• Maximum rating: 3 hours.
• Twenty minute type door frame with lights, fire tested without hose stream, for
• Maximum panel height: 34” (864)
walls at least 3 1/2” (89) thick.
*Fixed mullion unit must be welded.
• ME/SE Series profile may be 12 gage, 14 gage or 16 gage steel.
• MH/SH Series profile may be 16 gage or 14 gage steel.
• Mitered corner connections are standard. 12 gage will be coped.
• Jamb Depth:
ME/SE profile - Sgl. Rbt. 3” (76) to 20” (508).
Transom Frame Without Transom Bar
Dbl. Rbt. 4 1/2” (114) to 20” (508).
MH/SH profile -Sgl. Rbt. 3 1/2” (89) to 15” (381).
Dbl. Rbt. 4 1/2” (114) to 15” (381). • Labeled frames may be of 16 gage, 14 gage or 12 gage steel.
• Labeled panels may be of 18 or 20 ga. steel.
• The overall frame size shall not exceed 158 in. (4013) (13ft. 2 in.) in width and
• Maximum frame opening size: 4’0” (1219) x 11’0” (3353). Hollow Metal
139 in. (3531) (11 ft. 7 in.) in height. Panel
• Maximum door size: 4080 single.
• The maximum size opening for the individual transom lights or sidelights shall
• Jamb Depth: 4 1/2” (114) thru 20” (508).
not exceed 5268 inches in area, and the maximum width or height of the
• Maximum rating: 3 hours.
individual light shall not exceed 109 3/4 inches (2788). • Astragal required at bottom of panel for 3 hour rating.
• 5/8” (16) glazing bead. • Maximum panel height: 34” (864).
Revised 9/14

• Also available for borrowed lights.


*Must be welded.

Republic Doors and Frames


155 Republic Drive • McKenzie, Tennessee 38201 • (731) 352-3383
LABELED FRAME SIZES AND TYPES
(CONTINUED) TECHNICAL DATA
SHEET NO. 406b

1 1/2 Hour Transom Sidelite Frames


With Firelite or Firelite Plus Glass

• Maximum door size 8080.


• ME/SE series profile may be 16 gage or 14 gage steel.
• MH/SH series profile may be 16 gage steel.
• Jamb depth ME/SE profile single rabbet 3” to 20”, double
rabbet 5 3/4” to 20”.
• Jamb depth MH/SH profile single rabbet 3 1/2” to 15”, double
rabbet 4 1/2” to 15”.
• The overall frame size shall not exceed 122” (10’2”) in width
and 121” (10’1”) in height.
• The maximum size opening for the individual transom lights
or sidelights shall not exceed 2627 sq. in. and the maximum
width and height of the individual lights shall not exceed 54”
and 77 3/4” respectively.
• 5/8” high glazing bead.
• Welded construction only.
• Only labeled sealant or 100% silicone sealant may be used
as a glazing compound for installing Firelite.
• All types of anchors are approved. Masonry anchors may be
loose or welded. Drywall anchors must be welded. All frames
exceeding 8’ x 9’ must have anchors welded in place.
• Also available for borrowed light frames.
• Face Dimensions: Refer to U.L. or W.H. procedure manual or
contact factory.
Revised 9/14

Republic Doors and Frames


155 Republic Drive • McKenzie, Tennessee 38201 • (731) 352-3383
LABELED ANCHOR DETAILS
TECHNICAL DATA
SHEET NO. 407

Wood/Steel Prepared Sill Anchor


Masonry Type
Stud Type Opening Type Type

Wire Masonry Wood Steel/Stud Twist in Prepared One Piece Sill Anchor
Anchor Anchor Opening Anchor Welded On
(Shipped Loose) (Shipped Loose)

Tee Masonry Steel Stud Welded On Drywall Sill Anchor


Anchor Anchor Prepared Opening Anchor
(Shipped Loose)

MH
Intermediate
Anchor

Welded On Masonry Wood/Steel Stud Snap-in Prepared


Anchor Adjustable Anchor Opening Anchor
Revised 9/14

(Shipped Loose)

UL and WARNOCK HERSEY


1. ME Frames are not required to have welded anchors.
2. MH Frames over 7’2” must have a welded intermediate anchor.
3. ME or MH anchors can be shipped loose.

Republic Doors and Frames


155 Republic Drive • McKenzie, Tennessee 38201 • (731) 352-3383
LABELED FRAME CORNER CONSTRUCTION
TECHNICAL DATA
SHEET NO. 408

NOTE: Labeled frames over 7’2” and


all double frames require 2 - #8 x 1/2
Self Tapping Screws to each corner. Drywall Frame
Mitered

Welded
Frame

Non-Handed
Frame
Revised 9/14

Republic Doors and Frames


155 Republic Drive • McKenzie, Tennessee 38201 • (731) 352-3383
LABELED TRANSOM FRAME & SIDELIGHT
FRAME CONSTRUCTION TECHNICAL DATA
SHEET NO. 409

Transom Frame or Mullion Head


Sidelight Frame Head Detail
Jamb Detail

Transom Bar or Sidelight Base


Sidelight Bar Mullion Detail
Jamb Detail

Mullion Sidelight Sidelight Base


Bar Detail Jamb Detail
Revised 9/14

Republic Doors and Frames


155 Republic Drive • McKenzie, Tennessee 38201 • (731) 352-3383
U.L. LABELED DE SERIES - 1-3/4”
TEMPERATURE RISE DOOR TECHNICAL DATA
SHEET NO. 410

Republic U.L. Labeled Temperature Rise Door is of steel-covered composite fire door construction and
fabricated of 20 or 18 gage steel panels bonded to a mineral fiber board core. The temperature
developed on the unexposed face of the door after the first 30 minutes of a fire test did not exceed 250o
Fahrenheit above the ambient temperature.

Minutes

5 15 30
2000

1550
1500
Unexposed
Degrees Fahrenheit

Exposed Surface 1399


Surface to Fire
to Fire
1000
1000

500

Time Temperature Curve


(Exposed Surface to Fire)
250o Maximum
Temperature Rise

DE Series Doors shall have lock edge non-beveled and reinforced with a continuous 14 gage channel.
Reinforcements for mortise or cylindrical locks shall be of a integral type and in accordance with ANSI
A115 Standards.

Hinge edge is non-beveled and reinforced with a continuous 10 gage channel, projection welded at
maximum 5” on centers.

Doors shall have a flush top and inverted bottom 16 gage channel projection welded at maximum 2-1/2”
on centers.

Doors are thoroughly cleaned, phosphatized and receive one coat of force-cured prime paint.

Doors are individually packaged, completely covering the door to prevent damage to door or finish. The
doors should be stored in an upright position, under cover at the building site on wood sills, or in a
manner that will prevent rust or damage.
Revised 9/14

Glass lights are permitted in doors with up to a maximum of 100 square inches of glass area per leaf.

Republic Doors and Frames


155 Republic Drive • McKenzie, Tennessee 38201 • (731) 352-3383
U.L. LABELED DE SERIES - 1-3/4” TEMPERATURE RISE
DOOR CONSTRUCTION DETAILS TECHNICAL DATA
SHEET NO. 411

16 gage flush
top continuous closer reinforcement
steel channel when specified

Mineral Fiberboard Steel Panel


Core

16 gage steel cylindrical lock


reinforcement with provisions
for Gov’t Series 160 or 161
cylindrical lock sets (2-3/4”
7’-11-5/8” max.

backset) and ANSI A115.2 lock


front (1-1/2” x 2-1/4”)

25 1/2"

16 gage mortise lock


reinforcement with provisions
for Gov’t Series 86 mortise
lockset and ANSI A115.1 lock
front (1-1/4” x 8”)
Continuous 10 gage steel channel
reinforcement compatible with 4-
1/12” x 4-1/2” full mortise template
type hinges

21 1/2"

3’-11-3/4” Max. per leaf


Steel Panel
Revised 9/14

For Standard Hardware Locations


Continuous inverted
16 gage steel channel refer to Technical Data Sheet No. 502.

Republic Doors and Frames


155 Republic Drive • McKenzie, Tennessee 38201 • (731) 352-3383