The XR40CX digital controller is designed for medium to low temperature refrigeration units, featuring defrost management and various control functions. It includes multiple commands for temperature monitoring, defrost initiation, and alarm settings, as well as safety precautions and installation guidelines. The manual provides detailed instructions for operating the controller, including key combinations for programming and accessing hidden menus.

Uploaded by

pratama
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
17 views4 pages

XR40CX_GB

The XR40CX digital controller is designed for medium to low temperature refrigeration units, featuring defrost management and various control functions. It includes multiple commands for temperature monitoring, defrost initiation, and alarm settings, as well as safety precautions and installation guidelines. The manual provides detailed instructions for operating the controller, including key combinations for programming and accessing hidden menus.

Uploaded by

pratama
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

4.

FRONT PANEL COMMANDS


Digital controller with defrost management
XR40CX
CONTENTS
1. GENERAL WARNING__________________________________________________________1
2. GENERAL DESCRIPTION ______________________________________________________1
3. CONTROLLING LOADS________________________________________________________1
4. FRONT PANEL COMMANDS ___________________________________________________1
5. MAX & MIN TEMPERATURE MEMORIZATION _____________________________________1
6. MAIN FUNCTIONS ____________________________________________________________1
7. PARAMETERS _______________________________________________________________2 : To display target set point; in programming mode it selects a parameter or confirm an
8. DIGITAL INPUT (ENABLED WITH P3P = N)________________________________________3 operation.
9. TTL SERIAL LINE – FOR MONITORING SYSTEMS _________________________________3 (DEF) To start a manual defrost
10. X-REP OUTPUT – OPTIONAL___________________________________________________3
11. INSTALLATION AND MOUNTING ________________________________________________3 (UP): To see the max. stored temperature; in programming mode it browses the parameter
12. ELECTRICAL CONNECTIONS __________________________________________________3 codes or increases the displayed value.
13. HOW TO USE THE HOT KEY ___________________________________________________3
(DOWN) To see the min stored temperature; in programming mode it browses the parameter
14. ALARM SIGNALS _____________________________________________________________3
codes or decreases the displayed value.
15. TECHNICAL DATA ____________________________________________________________3
16. CONNECTIONS ______________________________________________________________3 To switch the instrument off, if onF = oFF.
17. DEFAULT SETTING VALUES ___________________________________________________4
Not enabled.
1. GENERAL WARNING
KEY COMBINATIONS:
1.1 PLEASE READ BEFORE USING THIS MANUAL +  To lock & unlock the keyboard.
 This manual is part of the product and should be kept near the instrument for easy and quick + To enter in programming mode.
reference.
 The instrument shall not be used for purposes different from those described hereunder. It + To return to the room temperature display.
cannot be used as a safety device.
 Check the application limits before proceeding. 4.1 USE OF LEDS
 Dixell Srl reserves the right to change the composition of its products, even without notice,
ensuring the same and unchanged functionality. Each LED function is described in the following table.
LED MODE FUNCTION
1.2 SAFETY PRECAUTIONS ON Compressor enabled

 Check the supply voltage is correct before connecting the instrument. Flashing Anti-short cycle delay enabled
 Do not expose to water or moisture: use the controller only within the operating limits avoiding ON Defrost enabled
sudden temperature changes with high atmospheric humidity to prevent formation of
condensation Flashing Drip time in progress
 Warning: disconnect all electrical connections before any kind of maintenance. ON An alarm is occurring
 Fit the probe where it is not accessible by the End User. The instrument must not be opened.
ON Continuous cycle is running
 In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.r.l.”
(see address) with a detailed description of the fault. ON Energy saving enbled
 Consider the maximum current which can be applied to each relay (see Technical Data). °C/°F ON Measurement unit
 Ensure that the wires for probes, loads and the power supply are separated and far enough °C/°F Flashing Programming phase
from each other, without crossing or intertwining.
 In case of applications in industrial environments, the use of mains filters (our mod. FT1) in 5. MAX & MIN TEMPERATURE MEMORIZATION
parallel with inductive loads could be useful.

2. GENERAL DESCRIPTION 5.1 HOW TO SEE THE MIN TEMPERATURE


Model XR40CX, format 32 x 74 mm, is microprocessor based controller, suitable for applications on 1. Press and release the n key.
medium or low temperature refrigerating units. It has 2 relay outputs to control compressor and 2. The “Lo” message will be displayed followed by the minimum temperature recorded.
defrost, which can be either electrical or reverse cycle (hot gas). It is also provided with three NTC or 3. By pressing the n key again or by waiting 5s the normal display will be restored.
PTC probe inputs, the first one for temperature control, the second one, to be located onto the
evaporator, to control the defrost termination temperature, the third one, optional, to connect to the 5.2 HOW TO SEE THE MAX TEMPERATURE
HOT KEY terminals to signal the condenser temperature alarm or to display a temperature. The
digital input can operate as fourth temperature probe. 1. Press and release the o key.
The HOT KEY output allows to connect the unit, by means of the external module XJ485-CX, to a 2. The “Hi” message will be displayed followed by the maximum temperature recorded.
network line ModBUS-RTU compatible such as the dIXEL monitoring units of X-WEB family. It 3. By pressing the o key again or by waiting 5s the normal display will be restored.
allows to program the controller by means the HOT KEY programming keyboard.
The instrument is fully configurable through special parameters that can be easily programmed 5.3 HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED
through the keyboard. 1. Hold press the SET key for more than 3s, while the max. or min temperature is displayed. (rSt
message will be displayed)
3. CONTROLLING LOADS 2. To confirm the operation the “rSt” message starts blinking and the normal temperature will be
displayed.
3.1 COMPRESSOR
The regulation is performed according to Temper. 6. MAIN FUNCTIONS
the temperature measured by the
thermostat probe with a positive
SET
6.1 HOW TO SEE THE SETPOINT
differential from the set point: if the 1. Push and immediately release the SET key: the display will show the Set
temperature increases and reaches set point value;
Time
point plus differential the compressor is 2. Push and immediately release the SET key or wait for 5 seconds to
started and then turned off when the Compr.
ON
display the probe value again.
temperature reaches the set point value
again.
6.2 HOW TO CHANGE THE SETPOINT
In case of fault in the thermostat probe the start and stop of the compressor are timed through 1. Push the SET key for more than 2 seconds to change the Set point value;
parameters “COn” and “COF”. 2. The value of the set point will be displayed and the “°C” or “°F” LED starts blinking;
3. To change the Set value push the o or n arrows within 10s.
3.2 DEFROST 4. To memorise the new set point value push the SET key again or wait 10s.
Two defrost modes are available through the “tdF” parameter: defrost through electrical heater (tdF =
EL) and hot gas defrost (tdF = in). Other parameters are used to control the interval between 6.3 HOW TO START A MANUAL DEFROST
defrost cycles (IdF), its maximum length (MdF) and two defrost modes: timed or controlled by the Push the DEF key for more than 2 seconds and a manual defrost will start.
evaporator’s probe (P2P).
At the end of defrost dripping time is started, its length is set in the FSt parameter. With FSt =0 the
dripping time is disabled.
6.4 HOW TO CHANGE A PARAMETER VALUE
To change the parameter’s value operate as follows:

1592020040 XR40CX GB m&M r1.1 22.06.2012 XR40CX 1/4


1. Enter the Programming mode by pressing the Set + n keys for 3s (the “°C” or “°F” LED starts DISPLAY
blinking). CF Temperature measurement unit: °C=Celsius; °F=Fahrenheit. WARNING: When the
2. Select the required parameter. Press the “SET” key to display its value measurement unit is changed the SET point and the values of the parameters Hy, LS, US, Ot,
3. Use “UP” or “DOWN” to change its value. ALU and ALL have to be checked and modified if necessary).
4. Press “SET” to store the new value and move to the following parameter. rES Resolution (for °C): (in = 1°C; dE = 0.1 °C) allows decimal point display.
To exit: Press SET + UP or wait 15s without pressing a key. Lod Instrument display: (P1; P2, P3, P4, SET, dtr): it selects which probe is displayed by the
NOTE: the set value is stored even when the procedure is exited by waiting the time-out to expire. instrument: P1 = Thermostat probe; P2 = Evaporator probe; P3 = Third probe(only for model
with this option enabled); P4 = Fourth probe, SET = set point; dtr = percentage of visualization.
6.5 THE HIDDEN MENU rEd X- REP display (optional): (P1; P2, P3, P4, SET, dtr): it selects which probe is displayed by
The hidden menu Includes all the parameters of the instrument. X- REP: P1 = Thermostat probe; P2 = Evaporator probe; P3 = Third probe(only for model with
this option enabled); P4 = Fourth probe, SET = set point; dtr = percentage of visualization.
6.5.1 HOW TO ENTER THE HIDDEN MENU
dLy Display delay: (0 ÷20.0m; risul. 10s) when the temperature increases, the display is updated of
1. Enter the Programming mode by pressing the Set + n keys for 3s (the “°C” or “°F” LED starts 1 °C/1°F after this time.
blinking). dtr Percentage of the second and first probe for visualization when Lod = dtr (0÷100; 100 =
2. Released the keys, then push again the Set+n keys for more than 7s. The Pr2 label will be P1, 0 = P2 ): if Lod = dtr it allows to set the visualization according to the percentage of the
displayed immediately followed from the HY parameter. first and second probe, as for the following formula (dtr(P1-P2)/100 + P2).
NOW YOU ARE IN THE HIDDEN MENU.
DEFROST
3. Select the required parameter.
4. Press the “SET” key to display its value dFP Probe selection for defrost termination: nP = no probe; P1 =thermostat probe; P2 =
5. Use o or n to change its value. evaporator probe; P3 =configurable probe; P4 = Probe on Hot Key plug.
6. Press “SET” to store the new value and move to the following parameter. tdF Defrost type: EL = electrical heater; in = hot gas
To exit: Press SET + o or wait 15s without pressing a key. dtE Defrost termination temperature: (-50÷50 °C/
NOTE1: if none parameter is present in Pr1, after 3s the “noP” message is displayed. Keep the keys -58÷122°F) (Enabled only when EdF=Pb) sets the temperature measured by the evaporator
pushed till the Pr2 message is displayed. probe, which causes the end of defrost.
NOTE2: the set value is stored even when the procedure is exited by waiting the time-out to expire. IdF Interval between defrost cycles: (0÷120h) Determines the time interval between the
beginning of two defrost cycles.
6.5.2 HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THE MdF (Maximum) length for defrost: (0÷255min) When P2P = n, (not evaporator probe: timed
FIRST LEVEL AND VICEVERSA. defrost) it sets the defrost duration, when P2P = y (defrost end based on temperature) it sets
Each parameter present in the HIDDEN MENU can be removed or put into “THE FIRST LEVEL” (user the maximum length for defrost.
level) by pressing “SET + n ”. dSd Start defrost delay: ( 0÷99min) This is useful when different defrost start times are necessary
In HIDDEN MENU when a parameter is present in First Level the decimal point is on. to avoid overloading the plant.
dFd Temperature displayed during defrost: (rt = real temperature; it = temperature at defrost
6.6 HOW TO LOCK THE KEYBOARD start; SEt = set point; dEF = “dEF” label)
dAd MAX display delay after defrost: (0÷255min). Sets the maximum time between the end of
1. Keep pressed for more than 3 s the UP + DOWN keys.
defrost and the restarting of the real room temperature display.
2. The “POF” message will be displayed and the keyboard will be locked. At this point it will be Fdt Drip time: (0120 min) time interval between reaching defrost termination temperature and the
possible only to see the set point or the MAX o Min temperature stored restoring of the control’s normal operation. This time allows the evaporator to eliminate water
3. If a key is pressed more than 3s the “POF” message will be displayed. drops that might have formed due to defrost.
dPo First defrost after start-up: (y = immediately; n = after the IdF time)
6.7 TO UNLOCK THE KEYBOARD dAF Defrost delay after continuous cycle: (023.5h) time interval between the end of the fast
Keep pressed together for more than 3s the o and n keys, till the “Pon” message will be freezing cycle and the following defrost related to it.
displayed. ALARMS
ALC Temperature alarms configuration: (Ab; rE)
6.8 THE CONTINUOUS CYCLE Ab= absolute temperature: alarm temperature is given by the ALL or ALU values. rE =
When defrost is not in progress, it can be activated by holding the “o ” key pressed for about 3 temperature alarms are referred to the set point. Temperature alarm is enabled when the
seconds. The compressor operates to maintain the “ccS” set point for the time set through the “CCt” temperature exceeds the “SET+ALU” or “SET-ALL” values.
parameter. The cycle can be terminated before the end of the set time using the same activation key ALU MAXIMUM temperature alarm: (SET÷110°C; SET÷230°F) when this temperature is reached
“o ” for 3 seconds. the alarm is enabled, after the “ALd” delay time.
ALL Minimum temperature alarm: (-50.0 ÷ SET°C; -58÷230°F when this temperature is reached
the alarm is enabled, after the “ALd” delay time.
6.9 THE ON/OFF FUNCTION AFH Differential for temperature alarm recovery: (0,1÷25,5°C; 1÷45°F) Intervention differential for
With “onF = oFF”, pushing the ON/OFF key, the instrument is switched off. The “OFF” recovery of temperature alarm.
message is displayed. In this configuration, the regulation is disabled. ALd Temperature alarm delay: (0÷255 min) time interval between the detection of an alarm
To switch the instrument on, push again the ON/OFF key. condition and alarm signalling.
dAO Exclusion of temperature alarm at startup: (from 0.0 min to 23.5h) time interval between the
WARNING: Loads connected to the normally closed contacts of the relays are always detection of the temperature alarm condition after instrument power on and alarm signalling.
supplied and under voltage, even if the instrument is in stand by mode. CONDENSER TEMPERATURE ALARM (detected by the fourth probe)
7. PARAMETERS AP2 Probe selection for temperature alarm of condenser: nP = no probe; P1 =thermostat probe;
P2 = evaporator probe; P3 =configurable probe; P4 = Probe on Hot Key plug.
REGULATION AL2 Low temperature alarm of condenser: (-55÷150°C) when this temperature is reached the LA2
Hy Differential: (0,1 ÷ 25,5°C / 1÷255 °F) Intervention differential for set point. Compressor Cut IN is alarm is signalled, possibly after the Ad2 delay.
Set Point + differential (Hy). Compressor Cut OUT is when the temperature reaches the set Au2 High temperature alarm of condenser: (-55÷150°C) when this temperature is reached the
point. HA2 alarm is signalled, possibly after the Ad2 delay.
LS Minimum set point: (- 50°C÷SET/-58°F÷SET): Sets the minimum value for the set point. AH2 Differential for temperature condenser alarm recovery: (0,1÷25,5°C; 1÷45°F)
US Maximum set point: (SET÷110°C/ SET÷230°F). Set the maximum value for set point. Ad2 Condenser temperature alarm delay: (0÷255 min) time interval between the detection of the
Ot Thermostat probe calibration: (-12.0÷12.0°C; -120÷120°F) allows to adjust possible offset of condenser alarm condition and alarm signalling.
the thermostat probe. dA2 Condenser temperature alarm exclusion at start up: (from 0.0 min to 23.5h, res. 10min)
P2P Evaporator probe presence: n= not present: the defrost stops by time; y= present: the defrost bLL Compressor off with low temperature alarm of condenser: n = no: compressor keeps on
stops by temperature. working; Y = yes, compressor is switched off till the alarm is present, in any case regulation
OE Evaporator probe calibration: (-12.0÷12.0°C; -120÷120°F). allows to adjust possible offset of restarts after AC time at minimum.
the evaporator probe. AC2 Compressor off with high temperature alarm of condenser: n = no: compressor keeps on
P3P Third probe presence (P3): n= not present:, the terminal operates as digital input.; y= working; Y = yes, compressor is switched off till the alarm is present, in any case regulation
present:, the terminal operates as third probe. restarts after AC time at minimum.
O3 Third probe calibration (P3): (-12.0÷12.0°C; -120÷120°F). allows to adjust possible offset of DIGITAL INPUT
the third probe. i1P Digital input polarity: oP: the digital input is activated by opening the contact; CL: the digital
P4P Fourth probe presence: (n = Not present; y = present). input is activated by closing the contact.
o4 Fourth probe calibration: (-12.012.0°C) allows to adjust possible offset of the fourth probe. i1F Digital input configuration: EAL = external alarm: “EA” message is displayed; bAL = serious
OdS Outputs activation delay at start up: (0÷255min) This function is enabled at the initial start up alarm “CA” message is displayed. PAL = pressure switch alarm, “CA” message is displayed;
of the instrument and inhibits any output activation for the period of time set in the parameter. dor = door switch function; dEF = activation of a defrost cycle; AUS =not enabled; Htr = kind of
AC Anti-short cycle delay: (0÷50 min) minimum interval between the compressor stop and the action inversion (cooling – heating); FAn = not set it; ES = Energy saving.
following restart. did: (0255 min) with i1F= EAL or i1F = bAL digital input alarm delay: delay between the
rtr Percentage of the second and first probe for regulation (0÷100; 100 = P1, 0 = P2 ): it detection of the external alarm condition and its signalling.
allows to set the regulation according to the percentage of the first and second probe, as for the with i1F= dor: door open signalling delay
following formula (rtr(P1-P2)/100 + P2). with i1F = PAL: time for pressure switch function: time interval to calculate the number of
CCt Compressor ON time during continuous cycle: (0.0÷24.0h; res. 10min) Allows to set the the pressure switch activation.
length of the continuous cycle: compressor stays on without interruption for the CCt time. Can be nPS Pressure switch number: (0 15) Number of activation of the pressure switch, during the “did”
used, for instance, when the room is filled with new products. interval, before signalling the alarm event (I2F= PAL).
CCS Set point for continuous cycle: (-50÷150°C) it sets the set point used during the continuous If the nPS activation in the did time is reached, switch off and on the instrument to
cycle. restart normal regulation.
COn Compressor ON time with faulty probe: (0÷255 min) time during which the compressor is odc Compressor status when open door: no; Fan = normal; CPr; F_C = Compressor OFF.
active in case of faulty thermostat probe. With COn=0 compressor is always OFF. rrd Outputs restart after doA alarm: no = outputs not affected by the doA alarm; yES = outputs
COF Compressor OFF time with faulty probe: (0÷255 min) time during which the compressor is restart with the doA alarm;
OFF in case of faulty thermostat probe. With COF=0 compressor is always active. HES Temperature increase during the Energy Saving cycle : (-30,0°C30,0°C/-22÷86°F) it sets
the increasing value of the set point during the Energy Saving cycle.

1592020040 XR40CX GB m&M r1.1 22.06.2012 XR40CX 2/4


OTHER power connections. Do not exceed the maximum current allowed on each relay, in case of heavier
Adr Serial address (1÷244): Identifies the instrument address when connected to a ModBUS loads use a suitable external relay.
compatible monitoring system.
PbC Type of probe: it allows to set the kind of probe used by the instrument: PbC = PBC probe, ntc 12.1 PROBE CONNECTION
= NTC probe. The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid
onF on/off key enabling: nu = disabled; oFF = enabled; ES = not set it. infiltration. It is recommended to place the thermostat probe away from air streams to correctly
dP1 Thermostat probe display measure the average room temperature. Place the defrost termination probe among the evaporator
dP2 Evaporator probe display fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during
dP3 Third probe display- optional. defrost, to prevent premature defrost termination.
dP4 Fourth probe display.
rSE Real set point: (readable only), it shows the set point used during the energy saving cycle or 13. HOW TO USE THE HOT KEY
during the continuous cycle.
rEL Software release for internal use.
Ptb Parameter table code: readable only.
13.1 HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD)
1. Program one controller with the front keypad.
8. DIGITAL INPUT (ENABLED WITH P3P = N) 2. When the controller is ON, insert the “Hot key” and push o key; the "uPL" message
appears followed a by flashing “End”
The free voltage digital input is programmable in different configurations by the “i1F” parameter.
3. Push “SET” key and the End will stop flashing.
4. Turn OFF the instrument remove the “Hot Key”, then turn it ON again.
8.1 DOOR SWITCH INPUT (i1F = dor)
It signals the door status and the corresponding relay output status through the “odc” parameter: no, NOTE: the “Err” message is displayed for failed programming. In this case push again o key if you
Fan = normal (any change); CPr, F_C = Compressor OFF. want to restart the upload again or remove the “Hot key” to abort the operation.
Since the door is opened, after the delay time set through parameter “did”, the door alarm is enabled,
the display shows the message “dA” and the regulation restarts is rtr = yES. The alarm stops as 13.2 HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY
soon as the external digital input is disabled again. With the door open, the high and low temperature
alarms are disabled. (DOWNLOAD)
1. Turn OFF the instrument.
8.2 GENERIC ALARM (i1F = EAL) 2. Insert a programmed “Hot Key” into the 5 PIN receptacle and then turn the Controller ON.
3. Automatically the parameter list of the “Hot Key” is downloaded into the Controller memory,
As soon as the digital input is activated the unit will wait for “did” time delay before signalling the the “doL” message is blinking followed a by flashing “End”.
“EAL” alarm message. The outputs status don’t change. The alarm stops just after the digital input is 4. After 10 seconds the instrument will restart working with the new parameters.
de-activated. 5. Remove the “Hot Key”..
8.3 SERIOUS ALARM MODE (i1F = bAL) NOTE the message “Err” is displayed for failed programming. In this case turn the unit off and then
When the digital input is activated, the unit will wait for “did” delay before signalling the “CA” alarm on if you want to restart the download again or remove the “Hot key” to abort the operation.
message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated. 14. ALARM SIGNALS
Message Cause Outputs
8.4 PRESSURE SWITCH (i1F = PAL) “P1” Room probe failure Compressor output acc. to par. “Con” and “COF”
If during the interval time set by “did” parameter, the pressure switch has reached the number of “P2” Evaporator probe failure Defrost end is timed
activation of the “nPS” parameter, the “CA” pressure alarm message will be displayed. The “P3” Third probe failure Outputs unchanged
compressor and the regulation are stopped. When the digital input is ON the compressor is always “P4” Fourth probe failure Outputs unchanged
OFF.
“HA” Maximum temperature alarm Outputs unchanged.
If the nPS activation in the did time is reached, switch off and on the instrument to restart
normal regulation. “LA” Minimum temperature alarm Outputs unchanged.
"HA2" Condenser high temperature It depends on the “Ac2” parameter
8.5 START DEFROST (i1F = dFr) "LA2" Condenser low temperature It depends on the “bLL” parameter
“dA” Door open Compressor according to rrd
It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation
“EA” External alarm Output unchanged.
will restart only if the digital input is disabled otherwise the instrument will wait until the “MdF” safety
time is expired. “CA” Serious external alarm (i1F=bAL) All outputs OFF.
“CA” Pressure switch alarm (i1F=PAL) All outputs OFF
8.6 INVERSION OF THE KIND OF ACTION: HEATING-COOLING (i1F = Htr)
This function allows to invert the regulation of the controller: from cooling to heating and viceversa.
14.1 ALARM RECOVERY
Probe alarms P1”, “P2”, “P3” and “P4” start some seconds after the fault in the related probe; they
8.7 ENERGY SAVING (i1F = ES) automatically stop some seconds after the probe restarts normal operation. Check connections before
The Energy Saving function allows to change the set point value as the result of the SET+ HES replacing the probe.
(parameter) sum. This function is enabled until the digital input is activated. Temperature alarms “HA”, “LA” “HA2” and “LA2” automatically stop as soon as the temperature
returns to normal values.
8.8 DIGITAL INPUTS POLARITY Alarms “EA” and “CA” (with i1F=bAL) recover as soon as the digital input is disabled.
Alarm “CA” (with i1F=PAL) recovers only by switching off and on the instrument.
The digital input polarity depends on the “i1P” parameter.
i1P=CL: the input is activated by closing the contact. 14.2 OTHER MESSAGES
i1P=OP: the input is activated by opening the contact
Pon Keyboard unlocked.
9. TTL SERIAL LINE – FOR MONITORING SYSTEMS PoF Keyboard locked
noP In programming mode: none parameter is present in Pr1
The TTL serial line, available through the HOT KEY connector, allows by means of the external On the display or in dP2, dP3, dP4: the selected probe is nor enabled
TTL/RS485 converter, XJ485-CX, to connect the instrument to a monitoring system ModBUS-RTU noA None alarm is recorded.
compatible such as the X-WEB500/3000/300.

10. X-REP OUTPUT – OPTIONAL 15. TECHNICAL DATA


Housing: self extinguishing ABS.
As optional, an X-REP can be connected to the instrument, trough the HOY KEY
Case: XR40CX frontal 32x74 mm; depth 60mm;
connector. The X-REP output EXCLUDES the serial connection.
Mounting: XR40CX panel mounting in a 71x29mm panel cut-out
To connect the X-REP to the Protection: IP20; Frontal protection: XR40CX IP65
instrument the following connectors
Connections: Screw terminal block  2,5 mm2 wiring.
must be used CAB-51F(1m), CAB-
Power supply: according to the model: 12Vac/dc, ±10%; 24Vac/dc, ±10%; 230Vac 10%,
52F(2m), CAB-55F(5m),
50/60Hz, 110Vac 10%, 50/60Hz
Power absorption: 3VA max
11. INSTALLATION AND MOUNTING Display: 3 digits, red LED, 14,2 mm high; Inputs: Up to 4 NTC or PTC probes.
Instrument XR40CX shall be mounted on vertical panel, in a 29x71 Digital input: free voltage contact
mm hole, and fixed using the special bracket supplied. Relay outputs: compressor SPST 8(3) A, 250Vac; or 20(8)A 250Vac
The temperature range allowed for correct operation is 060 °C. defrost: SPDT 8(3) A, 250Vac
Avoid places subject to strong vibrations, corrosive gases, Data storing: on the non-volatile memory (EEPROM).
excessive dirt or humidity. The same recommendations apply to Kind of action: 1B; Pollution grade: 2;Software class: A.;
probes. Let air circulate by the cooling holes. Rated impulsive voltage: 2500V; Overvoltage Category: II
Operating temperature: 0÷60 °C;Storage temperature: -30÷85 °C.
Relative humidity: 2085% (no condensing)
Measuring and regulation range: NTC probe: -40÷110°C (-40÷230°F);
PTC probe: -50÷150°C (-58÷302°F)
12. ELECTRICAL CONNECTIONS Resolution: 0,1 °C or 1°C or 1 °F (selectable); Accuracy (ambient temp. 25°C): ±0,7 °C ±1 digit
The instrument is provided with screw terminal block to connect cables with a cross section up to 2,5
mm2. Before connecting cables make sure the power supply complies with the instrument’s 16. CONNECTIONS
requirements. Separate the probe cables from the power supply cables, from the outputs and the The X-REP output excludes the TTL output.. It’s present in the following codes:
XR40CX- xx2xx, XR40CX –xx3xx;

1592020040 XR40CX GB m&M r1.1 22.06.2012 XR40CX 3/4


16.1 XR40CX – 8A COMPRESSOR
17. DEFAULT SETTING VALUES

Room
Evap.
Label Name Range °C/°F
Set Set point LS÷US -5.0 ---
9 10 11 12 Hy Differential 0,125.5°C/ 1 255°F 2.0 Pr1
8(3)A250V 8(3)A250V LS Minimum set point -50°CSET/-58°FSET -50.0 Pr2
US Maximum set point SET110°C/ SET  230°F 110 Pr2
Ot Thermostat probe calibration -1212°C /-120120°F 0.0 Pr1
1 2 3 4 5 6 7 8
P2P Evaporator probe presence n=not present; Y=pres. Y Pr1
Hot Key/IV Probe
N.C. OE Evaporator probe calibration -1212°C /-120120°F 0.0 Pr2
Def Comp TTL or X-REPoutput
P3P Third probe presence n=not present; Y=pres. n Pr2
Line O3 Third probe calibration -1212°C /-120120°F 0 Pr2
9-40Vdc supply: connect to the terminals 7 and 8. P4P Fourth probe presence n=not present; Y=pres. n Pr2
12Vac/dc supply: connect to the terminals 7 and 8. O4 Fourth probe calibration -1212°C /-120120°F 0 Pr2
24Vac/dc supply: connect to the terminals 7 and 8. OdS Outputs delay at start up 0÷255 min 0 Pr2
120Vac supply: connect to the terminals 7 and 8.
AC Anti-short cycle delay 0  50 min 1 Pr1
rtr P1-P2 percentage for regulation 0 ÷ 100 (100=P1 , 0=P2) 100 Pr2
16.2 XR40CX – 20A COMPRESSOR
CCt Continuos cycle duration 0.0÷24.0h 0.0 Pr2
CCS Set point for continuous cycle (-55.0÷150,0°C) (-67÷302°F) -5 Pr2
Room
Evap.

COn Compressor ON time with faulty probe 0  255 min 15 Pr2


COF Compressor OFF time with faulty probe 0  255 min 30 Pr2
9 10 11 12 CF Temperature measurement unit °C  °F °C Pr2
8(3)A250V 20(8)A250V rES Resolution in=integer; dE= dec.point dE Pr1
Lod Probe displayed P1;P2 P1 Pr2
rEd2 X-REP display P1 - P2 - P3 - P4 - SEt - dtr P1 Pr2
1 2 3 4 5 6 7 8 dLy Display temperature delay 0 ÷ 20.0 min (10 sec.) 0 Pr2
Hot Key/IV probe dtr P1-P2 percentage for disply 1 ÷ 99 50 Pr2
N.C. TTL or X-REP output
Def Comp tdF Defrost type EL=el. heater; in= hot gas EL Pr1
Line dFP Probe selection for defrost termination nP; P1; P2; P3; P4 P2 Pr2
9-40Vdc supply: connect to the terminals 7 and 8. dtE Defrost termination temperature -50  50 °C 8 Pr1
12Vac/dc supply: connect to the terminals 7 and 8. IdF Interval between defrost cycles 1  120 ore 6 Pr1
24Vac/dc supply: connect to the terminals 7 and 8. MdF (Maximum) length for defrost 0  255 min 30 Pr1
120Vac supply: connect to the terminals 7 and 8. dSd Start defrost delay 0÷99min 0 Pr2
dFd Displaying during defrost rt, it, SEt, DEF it Pr2
dAd MAX display delay after defrost 0 ÷ 255 min 30 Pr2
Fdt Draining time 0÷120 min 0 Pr2
dPo First defrost after startup n=after IdF; y=immed. n Pr2
dAF Defrost delay after fast freezing 0 ÷ 23h e 50’ 0.0 Pr2
ALc Temperat. alarms configuration rE= related to set;
Ab Pr2
Ab = absolute
ALU MAXIMUM temperature alarm Set110.0°C; Set÷230°F 110 Pr1
ALL Minimum temperature alarm -50.0°CSet/ -58°FSet -50.0 Pr1
AFH Differential for temperat. alarm recovery (0,1°C÷25,5°C) (1°F÷45°F) 1 Pr2
ALd Temperature alarm delay 0  255 min 15 Pr2
dAO Delay of temperature alarm at start up 0  23h e 50’ 1.3 Pr2
AP2 Probe for temperat. alarm of condenser nP; P1; P2; P3; P4 P4 Pr2
AL2 Condenser for low temperat. alarm (-55 ÷ 150°C) (-67÷ 302°F) -40 Pr2
AU2 Condenser for high temperat. alarm (-55 ÷ 150°C) (-67÷ 302°F) 110 Pr2
AH2 Differ. for condenser temp. alar. recovery [0,1°C ÷ 25,5°C] [1°F ÷ 45°F] 5 Pr2
Ad2 Condenser temperature alarm delay 0 ÷ 254 (min.) , 255=nU 15 Pr2
dA2 Delay of cond. temper. alarm at start up 0.0 ÷ 23h 50’ 1,3 Pr2
Compr. off for condenser low
n Pr2
bLL temperature alarm n(0) - Y(1)
Compr. off for condenser high
n Pr2
AC2 temperature alarm n(0) - Y(1)
i1P Digital input polarity oP=opening;CL=closing cL Pr1
i1F Digital input configuration EAL, bAL, PAL, dor; dEF; Htr,
EAL Pr1
AUS
did Digital input alarm delay 0÷255min 5 Pr1
Nps Number of activation of pressure switch 0 ÷15 15 Pr2
odc Compress status when open door no; Fan; CPr; F_C no Pr2
rrd Regulation restart with door open alarm n–Y y Pr2
HES Differential for Energy Saving (-30°C÷30°C) (-54°F÷54°F) 0 Pr2
Adr Serial address 0÷247 1 Pr2
PbC Kind of probe Ptc; ntc ntc Pr2
onF on/off key enabling nu, oFF; ES nu Pr1
dP1 Room probe display -- -- Pr2
dP2 Evaporator probe display -- -- Pr2
dP3 Third probe display -- -- Pr1
dP4 Fourth probe display -- -- Pr1
rSE Valore set operativo actual set -- Pr1
rEL Software release -- -- Pr2
Ptb Map code -- -- Pr2
2 Only for models XR40CX–xx2xx, XR40CX–xx3xx;

1592020040 XR40CX GB m&M r1.1 22.06.2012 XR40CX 4/4