Check the supply voltage is correct before connecting the instrument. Flashing Anti-short cycle delay enabled
Do not expose to water or moisture: use the controller only within the operating limits avoiding ON Defrost enabled
sudden temperature changes with high atmospheric humidity to prevent formation of
condensation Flashing Drip time in progress
Warning: disconnect all electrical connections before any kind of maintenance. ON An alarm is occurring
Fit the probe where it is not accessible by the End User. The instrument must not be opened.
ON Continuous cycle is running
In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.r.l.”
(see address) with a detailed description of the fault. ON Energy saving enbled
Consider the maximum current which can be applied to each relay (see Technical Data). °C/°F ON Measurement unit
Ensure that the wires for probes, loads and the power supply are separated and far enough °C/°F Flashing Programming phase
from each other, without crossing or intertwining.
In case of applications in industrial environments, the use of mains filters (our mod. FT1) in 5. MAX & MIN TEMPERATURE MEMORIZATION
parallel with inductive loads could be useful.
Room
Evap.
Label Name Range °C/°F
Set Set point LS÷US -5.0 ---
9 10 11 12 Hy Differential 0,125.5°C/ 1 255°F 2.0 Pr1
8(3)A250V 8(3)A250V LS Minimum set point -50°CSET/-58°FSET -50.0 Pr2
US Maximum set point SET110°C/ SET 230°F 110 Pr2
Ot Thermostat probe calibration -1212°C /-120120°F 0.0 Pr1
1 2 3 4 5 6 7 8
P2P Evaporator probe presence n=not present; Y=pres. Y Pr1
Hot Key/IV Probe
N.C. OE Evaporator probe calibration -1212°C /-120120°F 0.0 Pr2
Def Comp TTL or X-REPoutput
P3P Third probe presence n=not present; Y=pres. n Pr2
Line O3 Third probe calibration -1212°C /-120120°F 0 Pr2
9-40Vdc supply: connect to the terminals 7 and 8. P4P Fourth probe presence n=not present; Y=pres. n Pr2
12Vac/dc supply: connect to the terminals 7 and 8. O4 Fourth probe calibration -1212°C /-120120°F 0 Pr2
24Vac/dc supply: connect to the terminals 7 and 8. OdS Outputs delay at start up 0÷255 min 0 Pr2
120Vac supply: connect to the terminals 7 and 8.
AC Anti-short cycle delay 0 50 min 1 Pr1
rtr P1-P2 percentage for regulation 0 ÷ 100 (100=P1 , 0=P2) 100 Pr2
16.2 XR40CX – 20A COMPRESSOR
CCt Continuos cycle duration 0.0÷24.0h 0.0 Pr2
CCS Set point for continuous cycle (-55.0÷150,0°C) (-67÷302°F) -5 Pr2
Room
Evap.