350ÌA 1 000 V
DS2 350ÌA
INDUSTRIAL SOCKET
OUTLET DS2
IP66 95 mm² (1) METAL IK10 -40 °C 2 PIL. EMC
IP67 95-120 mm² (2)
+60 °C
(1) Flexible wiring (min.-max.).
(2) Stranded wiring (min.-max.). OTHER FEATURES
Pilot wiring 2,5 mm²
* See our cable AMPLIFIER lugs for sections bigger than 95 mm² (flexible) or 120 mm² (stranded).
Padlocking system is
standard.
SOCKET-OUTLET
female INLET male
DS2 DS2
Each socket-outlet 220-250 V AC 380-440 V AC 3P+N+E+2 pilots 3924017240 3928017240
and each inlet should be 380-400 V AC 660-690 V AC 3P+N+E+2 pilots 3924197240 3928197240
connected to a wall box, 왘 Other currents, voltages, frequencies are available (see page 14).
a sleeve, a handle or a
spacer to ensure correct
operation of the closing
mechanism.
92
350ÌA DS2
Cable outer Ø
OPTIONS Cable section Reference HANDLE Reference
(min./max.)
SAFETY HASP FOR UP TO 6 PADLOCKS METAL HANDLE WITH INTEGRATED CABLE CLAMP
40-50 mm 5K6P0D50
399A541
51-60 mm 5K6P0D60
ALLEN-SCREW LOCKING LATCH
61-70 mm 5K6P0D70
Direct latch locking, no padlocking option. Ref. socket + 22
71-80 mm 5K6P0D80
INLET CAP IP66/IP67
81-90 mm 5K6P0D90
392A426 METAL HANDLE METRIC THREAD ENTRY
(WITHOUT CABLE GLAND)
IP40 SELF RETURNING LID (MANUAL CLOSING) M40 5K6P0M40L
Socket-outlet
M50 5K6P0M50L
ref.+R
ELECTROMAGNETIC COMPATIBILITY (EMC) NEW M63 5K6P0M63L
Please order a metal threaded d accessory
M75 5K6P0M75L
herewith, together with a EMC cable gland to
be found on page 318.
METAL HANDLE METRIC THREAD ENTRY
CABLE AMPLIFIER LUGS (WITHOUT CABLE GLAND) - LARGE SIZE
Flexible 120 mm2 M63 796P0M63
392A277150
Stranded 150 mm2
M75 796P0M75
Flexible 150 mm2
392A277185
Stranded 185 mm2
SPACERS (BETWEEN THE WALL BOX OR PANEL) SLEEVE Reference
METAL SLEEVE
Depth 68 mm 5K7M0-68
60° 597M6
Depth 115 mm 5K7M0-115
PADLOCKING/ELECTRO-MECHANICAL INTERLOCKING Cable
BOXES Reference
outer Ø
Socket-outlet reference+MIL. METAL BOX (+ EARTHING WIRE) + METAL SLEEVE
Check out the details on page 312 +ÌCORNET
60° M63 597E6M63
60° M75 597E6M75
STAINLESS STEEL (+ EARTHING WIRE) + METAL SLEEVE +
METAL CABLE GLAND (+ EARTHING WIRE)
70° 35-46 mm 577C763M
70° 48-65 mm 577C775M
ELECTRICAL INTERLOCKING TYPICAL WIRING DIAGRAM OF THE DS2
At this level of power, it is not possible to break directly under load. Electrical CONTROL CIRCUIT
interlocking with a switch or a pilot controlled contactor is required. PLUG SOCKET-OUTLET CONTACTOR
L1 L1
Boxes with the following equipment are available upon request:
• circuit breaker or differential switch, L2 L2
• contactor, L3 L3
• fuses, PILOT CIRCUIT COIL
• loop-out enclosures, COIL SUPPLY
• terminals for single pole cables... FUSE
PILOT
CONTACTS
93
350ÌA DS2
DRAWINGS
AND DIMENSIONS
INLET
C A
A B C
420 188 217
COUPLER SOCKET
C A
A B C D
503 188 375 327
94
350ÌA DS2
WALL BOX MOUNTED SOCKET-OUTLET 70°
A E1
E2
A B C D E1 E2
206 784 375 651 240 190
PANEL MOUNTED SOCKET-OUTLET 60°
C1
A E
D E
C2
A B C1 C2 D E
255 474 180 375 180 165
95