WP Selectivity Analysis Low Voltage Power Distribution Systems Fuses Circuit Breaker White Paper
WP Selectivity Analysis Low Voltage Power Distribution Systems Fuses Circuit Breaker White Paper
Marcelo Valdes, PE, Cindy Cline, Steve Hansen, and Tom Papallo
© 2009 IEEE. Reprinted from the record of the I & CPS Technical Conference in Calgary in May
2009.
This material is posted here with permission of the IEEE. Such permission of the IEEE does not in
any way imply IEEE endorsement of any of Ferraz Shawmut’s products or services. Personal use of
this material is permitted. However, permission to reprint/republish this material for advertising or
promotional purposes, or for creating new collective works for resale or redistribution to servers or
lists or to reuse any coprighted component of this work in other works must be obtained from the
IEEE by writing to [email protected].
By choosing to view this document, you agree to all provisions of the copyright laws protecting it.
Page 1 of 10 Preprint for Peer Review
Abstract – Interest in complete overcurrent device selectivity selectivity. The more common solutions for complete selectivity
has increased due to the addition of selectivity requirements to are fully fused systems where circuit sizes and fuse types are
articles 700, 701, and 708 of the National Electrical Code selected to maximize selectivity, and the use of low-voltage
(NFPA70). Many users, both commercial and industrial, use power circuit breakers without instantaneous protection in low-
fuses and circuit breakers simultaneously. Traditional Time- voltage switchgear to achieve better selectivity at the main
Current Curve (TCC) analysis is known to not fully equipment level. Neither of these solutions may yield the most
communicate fuse selectivity; hence fuse manufacturers size- or cost-efficient initial-cost solution nor the best solution
publish device ratio guidelines for selection of fuse type and from a safety and maintenance perspective, but they may be the
sizes. Recent publications of selectivity tables by circuit only perceived solution for a user designing for maximum
manufacturers also demonstrate that traditional TCCs are often selectivity. Furthermore, over the years many existing facilities
insufficient to fully communicate circuit breaker selectivity. have accumulated a variety of device types. Increasing interest
Traditional TCCs can lead to incorrect conclusions regarding in arc-flash protection may drive facility engineers to closely
circuit breaker fuse selectivity, indicating more or less scrutinize the protection and selectivity achieved by their existing
selectivity than may be possible. The authors will describe distribution systems in order to achieve maximum possible
various methods for assessment of selectivity in systems using protection at the least sacrifice to system reliability.
both fuses and circuit breakers together, with either device on
the line side. The methods will demonstrate that selectivity B. Conventional Selectivity Assessment Using Time-Current
above what TCCs demonstrate may be possible if devices are Curves and Fuse Ratios
selected correctly, and that traditional TCC analysis, can also
incorrectly demonstrate more selectivity than a more thorough Traditional assessment of selectivity is based on the use of
analysis would predict. The methods lend themselves to time-current curve (TCC) overlays. These have proven to be a
analysis that a power system engineer can perform with useful tool to evaluate selectivity over the long-time and short-
published information or information that may be requested time operating ranges of the various types of overcurrent
from manufacturers. devices. For circuit breakers, the curves are also used to
Index Terms – Selectivity, Low-Voltage Fuses, Circuit document the operation of overcurrent devices in the
Breakers, Current Limiting. instantaneous range. However, when overcurrent devices
operate faster than about one cycle, the TCC is a limited tool for
I. INTRODUCTION accurately predicting device behavior. In systems where at least
one device can operate in less than one cycle or the devices
A. Impetus for Total Selectivity in Mixed Circuit Breaker and interact with each other, the RMS-drawn TCC may not be an
Fuse Systems accurate representation of device performance. When there is
device interaction, a time-current curve that predicts how one
In 2005 the NFPA added the following requirement to article device operates in isolation may no longer describe how the
700.27, Emergency Systems, of NFPA 70-National Electrical device operates as part of a system. This is one reason why
Code (NEC) [1]: “Emergency system(s) overcurrent devices TCCs are not usually drawn below 0.01 seconds and why
shall be selectively coordinated with all supply-side overcurrent coordination studies often reflect the peak or RMS equivalent of
protective devices.” The same requirement was added in the the fully asymmetric peak current on the time-current curve.
2005 edition to article 701.18[2], Legally Mandated Standby Molded-case circuit breakers [5] usually are drawn showing
Systems and in 2008 to the new article 708.54[3], Coordination. instantaneous clearing times of 1.5 cycles or less. Over much of
Though local and state jurisdictions are interpreting these the instantaneous range these devices may be significantly
requirements differently, many of the interpretations require that faster than 1.5 cycles and may exhibit current-limiting behavior
substantial portions of the power distribution system provide even if not marked as UL 489 current-limiting circuit breakers.
complete selectivity up to calculated bolted fault values for both Furthermore, though the TCC may be labeled in RMS amperes,
utility and emergency generations sources. Similar requirements the circuit breaker’s instantaneous trip system may be sensitive
have existed previously in NEC article 620.62[4]. to peak amperes. That implies that faults of equal RMS value
Traditional power distribution system design often ignored but different power factors or closing angles [6] will be sensed by
selective performance to such high levels of fault current due to the circuit breaker trip system differently. Fuses are energy-
considerations of safety, equipment, or conductor protection and based devices and hence they may also be affected by fault
the real or perceived difficulty in achieving such high levels of current asymmetry.
selective behavior. However, the stricter interpretations of the It is important to understand whether time-coordination
new NEC requirements do not allow for these considerations. studies are designed to determine selectivity or nonselectivity.
Also, in many industrial and critical commercial systems it is not Protective devices should reliably be as or more selective than
unusual for designers to desire and design for higher levels of indicated by analysis. However, a determination of lack of
selectivity need not be as reliable. In other words, devices that minimum level, not an average or maximum level. If published
seem not to be selective by analysis may be selective under data are to be used for selectivity analysis, it is important to
some circumstances, but devices determined to be selective by know if the data are minimum, maximum, or average for the
the same analysis should be reliably selective under all parameter considered. In time-current curves, tolerance in time
reasonably expected conditions. and current are demonstrated by the band’s width. When the
time-current curve is shown as a line, it must be labeled as
C. Fuse Operation either a maximum or minimum characteristic. Other data, such
as let-through tables or melt-energy tables, may not clearly
The UL 248-1 definition of current-limiting fuse is, “A fuse identify whether the data are average, minimum, or maximum.
that, within a specified overcurrent range, limits the clearing time All analyses must take tolerance into account.
at rated voltage to an interval equal to or less than the first major
or symmetrical current loop duration; and limits the peak current D. Fuse Peak Let-Through Current (Ip)
to a value less than the available peak current.” UL 248, Low
Voltage Fuses, defines fuse performance by class including the The di/dt at the initiation of the fault is the primary external
maximum allowable peak let-through current (Ip), maximum factor determining the peak let-through current, Ip, passed by the
2
allowable clearing I t, and the maximum allowable threshold fuse. Higher di/dt will result in higher peak current let-through.
ratio. Threshold current is defined by UL 248 as “The lowest The maximum possible fuse Ip occurs at the maximum
prospective RMS symmetrical current above which a fuse is prospective fault current. Fuse Ip graphs are readily available
current limiting.” UL 248 defines threshold ratio as “The from fuse manufacturers. Figure 2 represents the Ip of a 100 A
threshold current divided by the fuse current rating. “ Class J fuse (AJT100). The uppermost diagonal line, labeled as
Fuses are thermal energy–sensitive devices. If the fuse 2.3x RMS, represents the peak available current, assuming a
element reaches its design melting temperature, it will melt. For power factor of 15%. The red line represents the maximum Ip of
each fuse design, there is a minimum melting energy that is the AJT100 fuse.
determined by the element material (typically copper or silver)
2
and by the minimum element cross-section. I t is a measure of
thermal energy under fault conditions represented by equation
(1) and defined in section V. Figure 1 depicts a current-limiting
Let-Through Current, kA peak
fuse element.
that must be maintained between upstream and downstream breaker will react differently than if the prospective fault current
fuses to assure selectivity under all overcurrent conditions. was not being affected by the current-limiting device. The same
effect that creates the dynamic system that impairs engineered
E. Circuit Breakers series-rated systems can create a combination of devices with
desirable selective behavior, not evident from traditional time-
Two different types of physical mechanisms may cause current curve analysis.
current-limiting behavior in circuit breakers. The more limited
behavior in most molded-case circuit breakers not designed to II. CURRENT-LIMITING FUSE ABOVE NONCURRENT-
optimize current-limiting behavior derives from traditional contact LIMITING CIRCUIT BREAKER
arm construction. Magnetic repulsion forces are created at the
point where the contacts touch due to the constriction of current. When a circuit breaker does not provide current-limiting
The constriction is caused by the contact material’s inherent behavior, an upstream fuse will be subject to the full magnitude
roughness, which leads to conduction at only a few spots on the of the fault current for the time shown on the circuit breaker’s
contact’s surface. As the current flows toward those spots on time-current curve. For this combination of devices the
both contact surfaces, repulsive forces are created across the traditional time-current curve is a suitable analytical tool to
contacts. Mechanism spring forces should keep the contacts determine selectivity. If the fuse curve crosses the instantaneous
closed for currents within the circuit breaker’s operating range. foot of the circuit breaker curve, it is likely that the pair is more
At currents above the circuit breaker’s maximum instantaneous selective than the curve overlay shows, due to the conservative
pickup, the repulsive forces may start to overcome the spring manner in which most circuit breaker curves are drawn. This is
forces and the contacts may part temporarily, causing an arc particularly true for circuit breakers with high withstand levels
voltage to develop. This action is called contact popping. The above the intersection of the fuse curve and the circuit breaker’s
popping will have a current- and energy-limiting effect prior to withstand rating. Popping behavior may provide some current-
the contact’s being driven to full opening by the magnetic or limiting behavior that may help provide additional selectivity.
electronic unlatching mechanism. Popping does not normally
cause contacts to latch open and is power factor and closing III. NONCURRENT-LIMITING CIRCUIT BREAKER ABOVE
angle dependent, so the limitation caused by the popping is not CURRENT-LIMITING FUSE
normally shown on circuit breaker let-through curves or time-
current curves. Many circuit breakers employ magnetic trips or simple
A second design common in circuit breakers specifically digital electronic trips. For this kind of sensing the instantaneous
designed to be current limiting is the reverse-current loop shown trip may be described as peak sensing. Because they are peak
in Figure 3. In this design, current is routed through parallel sensing, the trips are sensitive to the peak let-through of the
contact arms so that opposing magnetic forces are formed. overcurrent device below. Peak-sensing trips are set to the
During high fault-current conditions, the magnetic repulsion nominal RMS current setting times √2. This comes from the ratio
forces quickly climb to values that force the contacts to of peak to RMS for a symmetrical sine wave. The analysis to
overcome the spring forces holding them together, so they part determine selectivity is based on a comparison of the peak let-
from each other very quickly. This is described as blowing the through current of the downstream device versus the pickup
contacts open. setting of the upstream device in peak amperes, for a given
value of available RMS fault current.
Figure 4 shows a simple system composed of a circuit
breaker above a fused switch. The minimum setting for the
upstream circuit breaker to reliably predict selective behavior at
maximum available fault current is determined from the
downstream fuse’s peak let-through characteristics at the
expected maximum fault current. Figure 5 shows the peak let-
through current for several current-limiting fuses. The uppermost
diagonal line represents the prospective peak current available
at the fuse’s 15% test power factor. The lower diagonal line, √2
times RMS, is the range of available instantaneous pickup
settings for circuit breakers. If the available bolted fault current
Fig 3. Circuit breaker reverse-current loop. (Ibf) at the fuse is 50,000 A, the 200 A class J fuse shown in
Figure 4 will let through a peak current of ~14,000 A. Dividing
Before the magnetic trip or other instantaneous trip initiates
the peak let-through current by the square root of 2 provides a
action to unlatch the circuit breaker, the repulsion forces may
value of ~10,000 A RMS. If the circuit breaker is set above
cause significant popping. The combination of forces acting
10,000 A, the pair will be reliably selective. For a 601 Class L
directly on the contact arms and the instantaneous trip
fuse with 62,000 A available, the circuit breaker’s trip setting
mechanism creates the circuit breaker’s instantaneous and
must be above 22,000 A to reliably maintain full selectivity.
current-limiting characteristics.
These derivations are shown on Figure 5 by the dashed line
Because of these various mechanisms, circuit breakers are
pairs drawn vertically up to the peak let-through curves and
sensitive to the peak current and peak energy delivered over the
down from the √2 diagonal line.
first few milliseconds of a fault. Circuit breakers also limit the
energy they allow to flow through the first few milliseconds of a
fault and up to complete interruption. This creates the possibility
that overcurrent devices above or below a current-limiting circuit
guidelines for current-limiting fuses. However, there is little current. This also shows that the clearing time is also reduced to
information in the industry that indicates what selectivity is far less that the 0.025 s of the static TCC.
possible between these two types of current-limiting devices,
other than what may be shown by traditional time-current curve
analysis. This section presents the reasons why this selectivity is
possible and a technique to evaluate it for circuit breaker above
fuse combinations.
Figure 8 shows an upstream fuse and downstream current-
limiting circuit breaker. Overlaying the time-current curve of the
current-limiting circuit breaker and the melting time of the fuse is
the traditional way to analyze these devices. Figure 8 also
shows the time-current curve overlay for a 1600 A class L fuse
and a 250 A current-limiting circuit breaker.
2
Fig. 9. Let-through peak and I t energy waverform.
achieve selectivity above a smaller and faster fuse. This reduced in the series circuit, the series circuit available current, Isf, has to
let-through current becomes the prospective fault current for the be 90 kA.
upstream fuse, shown by the lower darker line in Figure 10. After
converting the let-through current to a RMS value by dividing by
the square root of 2, we may refer to it as the effective RMS
current available to the fuse, Ie. A third designation, Isf, is used in
the analysis of the devices in series. Isf is the prospective fault
current that is required to generate the effective RMS of the
series combination.
2
Fig. 11. Half-cycle available I t based on prospective fault
current, Ibf, and effective fault current.
2
D. Fuse Response to I t
2
Fuses respond to the I t thermal energy flowing through the
2
Fig. 10. Peak and effective let-through current. fuse element. When the I t thermal energy is sufficient to melt
the current-carrying element, the fuse starts to interrupt the fault
The data for Isf are generated, with Isf as the dependent current. The energy required to accomplish this is called the pre-
variable and Ie as the independent variable. This may also be arc energy or melting energy. Figure 12 shows the minimum
2 2
considered a reverse let-through curve, with both terms melting I t of the fuse as a function of Ibf and Isf. The I t melt
expressed in RMS current, where the RMS prospective is a values are unchanged but are shifted to the effective RMS let-
function of the peak-current let-through by the smaller current- through current Isf. This shifts the melt curve from the bolted fault
limiting device. The data may be curve-fitted to create the current to the series fault current.
equation for Isf = f(Ie). Equation 2 is the fit of the data. The fuse will melt at a specific level of energy based on
prospective fault current. By shifting the prospective fault current
I sf = .746 − 0.149 I e + 0.0967 I e2 + 3 * 10−16 e I e from Ibf to Isf, the “apparent” energy required increases. The
(2) fuse’s melt-energy characteristic, inclusive of the current-limiting
Equation 2 is the system’s available fault current shifted by effect of the downstream circuit breaker, is represented by the
the peak let-through characteristics of the smaller downstream fuse-melting energy as a function of Isf. The graph demonstrates
current-limiting circuit breaker. Equation 2 is used to calculate that in a system able to deliver a 50 kA bolted fault current, the
2 2
the larger system fault current needed to produce the RMS fuse alone will melt at an I t of 2.2 million A s. But in the series
prospective current that determines the upstream fuse’s combination, which is arrived at by the Isf transform of the
2 2
performance. This equation can be used to shift the current axis current, the fuse apparent I t melt energy is 2.8 million A s. This
2
in an I t melting curve of the upstream fuse to properly is because for 50 kA available fault current, the downstream
demonstrate the current the upstream fuse will see. It shifts the circuit breaker will only let through the equivalent of a 23 kA
current of a circuit’s characteristic from the Ibf current to the Isf fault.
current needed to create the same let-through. Figure 11 shows
2
the half-cycle I t as a function of Ibf and Isf. For example, for the
2 2
half-cycle I t to reach a value of 5 million A s, the bolted fault
2
current has to be 14 kA. But for the I t to reach the same value
1600 A Class L Fuse Melt Energy as used is the current- and energy-limiting characteristics of the
function of Ibf and shifted to Isf circuit breaker and the pre-arc melt energy of the fuse. Fuse
manufacturers do not commonly publish the pre-arc melt-energy
curves for their fuses, but it may be available upon request.
I2t Melt as f(Isf)
Fuse Melt Energy in Million A2s
required analytical tool. Note that the time the fuse takes to open
is not part of the analysis. It is the energy the fuse lets through in
the process that matters.
Transition Region
Fully Current-
Limiting Region
breaker, as shown in Figure 13. The example analysis shown incorrect. Second, nontraditional measures, such as peak
2
previously indicated that a 250 A current-limiting molded-case currents and I t, can reliably be used to perform selectivity
circuit breaker should be selective with a 1600 A class L fuse. studies rather than solely using time. Third and most important,
The overlay of characteristics shown in Figure 13 demonstrates the limiting and trip-commit behavior of devices developed
that potential lack of selective performance occurs at high fault individually can be analytically combined for series
currents in the range of 90 to 100 kA. Without shifting the fuse combinations. This enables analysis of the series performance
melt-energy curve by the transform of the circuit breaker’s let- of the near-infinite combinations of upstream and downstream
through, peak current selectivity may be limited to 65 kA. With devices. The demonstrated methods can provide the industry
the curve shift, selectivity should be at least 95 kA. Three-phase with provable techniques to improve analysis of system reliability
short-circuit tests where performed at 100 kA with a 20% power and protection using devices and information available to the
factor. Ten tests were done at various closing angles (closing industry today.
angle is a measurement of the angular difference between when
the fault is initiated and the voltage on phase A of the test Main Advanced
circuit). In all ten cases the circuit breaker interrupted with no Current Conventional Current
apparent damage to the fuse. Impedance tests on the fuses pre Limiting Fuse Circuit Breaker Limiting
and post testing indicated no changes in fuse resistance. Feeder Circuit Breaker
[4] Ed Larsen, “A New Approach to Low-Voltage Circuit in mechanical engineering. He started with GE in 1986 in the
Breaker short-circuit selective coordination”, IEEE Industrial and New Product Development department. He has also worked on
Commercial Power Systems Conference Record, May 2008. circuit breaker and electrical distribution system projects for
several other major manufacturers, returning to GE in 1997. He
IX. VITAE is currently manager of the Innovation Engineering organization
for GE’s Power Distribution and control products business. He is
Cindy Cline graduated from Michigan Technological the holder of 35 US and international patents and has co-
University in 1983 with a BSEE in power systems and authored several papers for IEEE forums on selectivity, power
machinery. She has held engineering and management systems protection, and arc flash related topics.
positions with Ferraz Shawmut and formerly for LCI. Cindy is Marcelo E. Valdes graduated from Cornell University in1977
currently Manager, Applications Engineering for Ferraz with a BS in electrical engineering. He has been with GE for
Shawmut. Her responsibilities include application engineering, over 31 years, in field engineering, sales, marketing, and
finding solutions to difficult protection applications, technical application engineering. He is currently the manager of
support, technical seminars and training, product safety, and Application Engineering for GE’s Electrical Distribution Business
leading Ferraz Shawmut’s Applications Engineering team. She in Plainville, Connecticut, where he provides application
is currently a member of IEEE. Cindy has published several engineering and strategic product planning leadership. Mr.
papers and articles on overcurrent protection, ac/dc power- Valdes is past chair of the IEEE Power and Industrial
conversion systems, and fuse performance. Applications Engineering chapter in San Jose, CA, and the
Steve Hansen graduated from Iowa State University in 1973 Industrial Applications chapter in San Francisco, CA. He is a
with a BS in engineering operations. He has held field and registered Professional Electrical Engineer in California. Mr.
management positions with Ferraz Shawmut and Rockwell Valdes has authored and co-authored several technical papers
Automation. Steve is presently senior field engineer for Ferraz for IEEE and other engineering forums, and has several pending
Shawmut. His responsibilities include application engineering, patents in the field of power systems protection and circuit
technical training, product safety, major account development, breaker trip systems. Currently Mr. Valdes is a member of
and standards development. An active member of NFPA and several IEEE standard working groups, including the working
IEEE, Mr. Hansen serves on various IEEE working groups group editing the revision of the IEEE Color Books into a new
involving safety and arc flash, including IEEE P1683 and IEEE format, a new recommended practice for safe power distribution
1584. Mr. Hansen has been a member and chair of various system design. He is currently vice chair of IEEE P1683,
NEMA and UL committees in the area of fuse standards, Standard for Safe Motor Control Centers and leader of the
including NEMA 5FU, UL STP198(currently 248), and STP347. project to write the “Recommended Practice for Bus and
Mr. Hansen has published several papers in the area of Switchgear Protection” (P3004.11) derived from the present
overcurrent protection, safety, and overcurrent protective device IEEE Buff book. Mr. Valdes is also involved in various other
coordination. IEEE working groups.
Tom Papallo graduated from the University of Connecticut
in 1986 with a BS degree and in 1989 with an MS degree, both