WTC WT6000 trainning program
WTC WT6000 trainning program
TRAINING PROGRAM
1
"top mount" designed for
robot controller panels
2
INSIDE THE WELD CONTROL
CIOM
Control transformer
120 circuit Breaker
Main circuit Breaker
Isolation contactor
Gen 6 Inverter
Gen 6 Timer
3
CIOM (Cabinet I/O Module)
4
5
Control transformer
Steps down line voltage to 120V and
24V for the cabinet power.
6
Main circuit Breaker
Interrupts customer supplied line
voltage and is upstream of the
inverter.
7
Isolation contactor
Device placed downstream of the
inverter, used to interrupt current to
the customer supplied weld
transformer.
8
Gen 6 Inverter
Converts 3-phase AC to MFDC
current.
Gen 6 Timer
Brains of weld control and
Ethernet/DeviceNet
communications
9
ENET IP
EtherNet/IP (EIP)is used for I/O communication between the weld timer and other
EtherNet enabled devices (e.g. a Robot or PLC). Also used to communicate with Weld
Gateway and RAFT Gateway networking software.
ENET EtherNet is used for Standard EtherNet communications.
The welding transformer for MFDC must be matched for the weld
current requirement - depends on the applied voltage and circuit
resistance.
Incoming
Three Phase
AC
Stage 1
Full Wave
Rectification
Stage 2
High Frequency
AC
Stage 3
DC Current
Output
Entry phase rotation to control
circuit breaker is not relevant.
(ABC) or (ACB)
Control
Insulated Gate Bipolar System
Transistors
(IGBT) act as switches
to produce a 1000 Hz
bipolar square wave.
Reference Inverter System Diagram
Diodes
Diodes in inverter applications have similar
characteristics to those of thyristors
(SCRs). They can be constructed in such
a way that any heat generated in the silicon
can be removed quickly. They are typically
used for line voltage rectification and are
subject to similar conditions as would be
found in an AC welding.
Capacitors
Capacitors are a vital component in inverter controls. They
serve as a power reservoir lowering the peak demand on
the rectifier diodes and absorbing any voltage overshoot
caused by AC line and weld load inductances.
380VAC to 537VDC
400VAC to 565VDC
480VAC to 679VDC
575VAC to 813VDC
IGBTs
the windings
the iron core
and the secondary diodes.
The core and winding determine how much current you can deliver, which
varies with the duty cycle at which you are using it.
Corrective Action 1:
• Ensure the master controller (i.e. robot, PLC, etc.) is
maintaining the Weld Initiate bit HIGH during the
time function #61 is monitoring the bit.
Weld Initiate Not Present Fault
Description 2:
• Occurs when the Weld Initiate bit goes LOW before
function #50 (TURN ON WELD COMPLETE) is
executed in the weld schedule.
Corrective Action 2:
• Ensure the master controller (i.e. robot, PLC, etc.) is
maintaining the Weld Initiate bit HIGH until function
#50 is executed in the weld schedule.
Control Stop Fault
Description:
• Occurs when the Control Stop bit goes LOW anytime during
the execution of the weld sequence. This bit is normally
maintained HIGH.
Corrective Actions:
• Ensure the Control Stop pushbutton is pulled out and +24VDC is on Pins 6
and 7 of the LIO connector on the processor module (1CPU). This is the
Control Stop hard-wired input.
• Investigate why the master EtherNet IP controller (i.e. robot, PLC, etc.)
turned the Control Stop input bit LOW during the weld sequence.
Look at safety gates, light screens, robot E-Stop, master E-Stop, etc.
Light screens can be localized to just the loading station or may cover
an entire cell.
Stepper Approaching Max Fault
Description 1:
• Occurs at the 1st weld of step 2 in the stepper
program, if the Remaining Tip Dresses Count has
decremented to 0.
Corrective Action:
• Indicates the final step in the stepper program has
begun and End of Stepper is approaching.
Stepper Approaching Max Fault
Description 2:
• Occurs at the 1st weld of step 5 in the stepper
program, if the Remaining Tip Dresses Count is > 0.
Corrective Action:
• Indicates the final step in the stepper program has
begun and End of Stepper is approaching.
Stepper Approaching Max Fault
Description 3:
• Occurs at the 1st weld of step 5 in the stepper
program, if the tip dress function is disabled in the
Setup Parameters.
Corrective Action:
• Indicates the final step in the stepper program has
begun and End of Stepper is approaching.
End of Stepper Fault
Descriptions:
• Occurs at the first weld of step 3 in the stepper program, if the Remaining
Tip Dresses Count has decremented to 0.
NOTE: The first 40 welds will be an ALERT. If the stepper program is not
reset by the 41st weld, it will change to a FAULT.
• Occurs at the last weld of step 5 in the stepper program, if the Remaining
Tip Dresses Count is > 0.
• Occurs at the last weld of step 5 in the stepper program, if the tip dress
function is disabled in the Setup Parameters.
NOTE: The first 40 welds will be an ALERT. If the stepper program is not
reset by the 41st weld, it will change to a FAULT.
Corrective Action:
• Reset the stepper program and replace the weld caps on the gun.
High Current Limit Fault
Description 1:
• Occurs when the weld processor detects that the
current passed during the weld sequence exceeded
the value programmed into the HIGH CURRENT LIMIT
WINDOW % in the Setup Parameters.
Corrective Action 1:
• Ensure the percentage value programmed into HIGH
CURRENT LIMIT WINDOW % in the Setup Parameters
is correct for the welding application.
High Current Limit Fault
Description 2:
• Occurs when the weld processor detects that the current passed
during the weld sequence exceeded the HI value programmed
into function #76 (SEC. CURR LIMITS: HI = nnnn0 LOW = nnnn0) or
function #84 (CURRENT WINDOW: HI= nn% LOW= nn%) in the
weld schedule (if used).
• Ensure the percentage value programmed into HIGH CURRENT L
Corrective Action 2:
• Ensure the HI value programmed into function #76 (SEC. CURR
LIMITS: HI = nnnn0 LOW = nnnn0) or function #84 (CURRENT
WINDOW: HI= nn% LOW= nn%) in the weld schedule is
correct for the welding application (if used).
High Current Limit Fault
Description 3:
• Occurs if the Transformer Turns Ratio is set too low for
the welding application.
Corrective Action 3:
• Ensure the value programmed into the Transformer
Turns Ratio in either function #90 (TRANSFORMER
TURNS RATIO nnn :1) or the Setup Parameters
matches the turns ratio stated on the serial tag affixed
to the welding transformer.
High Current Limit Fault
Description 4:
• May occur if there is insufficient gun pressure, poor
part fit-up or loose connections in the secondary
circuit. All of these conditions may cause expulsion or
exploding welds.
Corrective Action 4:
• Ensure gun pressure is correct for the welding application.
• Check for proper part fit-up and correct as required.
• Periodically inspect weld tooling (transformer secondary circuit)
for loose connections and correct as required.
Low Current Limit Fault
Description 1:
• Occurs when the weld processor detects that the
current passed during the weld sequence was less
than the value programmed into the LOW CURRENT
LIMIT WINDOW % in the Setup Parameters.
Corrective Action 1:
• Ensure the percentage value programmed into LOW
CURRENT LIMIT WINDOW % in the Setup Parameters
is correct for the welding application.
Low Current Limit Fault
Description 2:
• Occurs when the weld processor detects that the current
passed during the weld sequence was less than the LOW
value programmed into function #76 (SEC. CURR LIMITS: HI =
nnnn0 LOW = nnnn0) or function #84 (CURRENT WINDOW:
HI= nn% LOW= nn%) in the weld schedule (if used).
Corrective Action 2:
• Ensure the LOW value programmed into function #76 (SEC.
CURR LIMITS: HI = nnnn0 LOW = nnnn0) or function #84
(CURRENT WINDOW: HI= nn% LOW= nn%) in the weld
schedule is correct for the welding application (if used).
Low Current Limit Fault
Description 3:
• Occurs if the Transformer Turns Ratio is set too high
for the welding application.
Corrective Action 3:
• Ensure the value programmed into the Transformer
Turns Ratio in either function #90 (TRANSFORMER
TURNS RATIO nnn :1) or the Setup Parameters matches
the turns ratio stated on the serial tag affixed to the
welding transformer.
Low Current Limit Fault
Description 4:
• May occur when mechanical issues exist in the weld
transformer secondary circuit (weld tooling).
Corrective Action 4:
• Typical issues include:
Bad jumper cables or leaf shunts
Bad part fit-up
Contaminated weld caps
Insulation from sealer, tape or labels on the part
Gun sticking or not closing properly
Loose or open secondary diodes in the welding transformer
Loose or bad primary cables
Extended Weld Fault
Description:
• Occurs when either function #94 (EXTEND WELD IF LOW
CURRENT LIMIT FAULT) or #95 (EXTEND WELD IF CURRENT LESS
THAN nnnn0) is used in the weld schedule and the condition is
true. This typically occurs when the required current cannot be
achieved.
Corrective Action:
• See corrective action for LOW CURRENT LIMIT FAULT. Also,
ensure the value programmed into function #95 is correct for
the welding application.
Extended Weld Fault
Additional Comments:
• If the extend weld (re-weld) is successful, an EXTENDED WELD
(ALERT) will occur and the Weld Complete bit will go HIGH. If the
extend weld (re-weld) is unsuccessful, both an EXTENDED WELD
ALERT and a LOW CURRENT LIMIT FAULT will occur and the Weld
Complete bit will stay LOW.
• This fault must be set to (ALERT) for the Weld Complete bit to go
HIGH after a successful extend weld (re-weld). Otherwise, if set
to (FAULT), the Weld Complete bit will stay LOW.
Isolation Contactor Off When Needed Fault
Description:
• Occurs when the isolation contactor is not energized when
required by the weld schedule.
Corrective Actions:
• Ensure function #52 (TURN ON ISOLATION CONTACTOR) is in the weld
schedule and inserted before the squeeze function.
• Inspect isolation contactor for damage. The auxiliary contactor block may be
defective. Replace the entire isolation contactor or the auxiliary contact block
as required.
• If the isolation contactor is not defective, the solid state relay that drives the
isolation contactor coil may be shorted. Replace the solid state relay.
Isolation Contactor Error - Breaker Tripped Fault
Description:
• Occurs when the weld processor detects the isolation contactor is energized
(closed) when it should be de-energized (open). When this fault occurs, the
weld processor activates the shunt-trip mechanism on the circuit breaker.
Corrective Actions:
• Typically, this fault is caused by a defective auxiliary contact block on the
isolation contactor. The contacts can be cleaned by removing the auxiliary
block, manually moving the aux contact up and down a few times and then
reseating. If this does not resolve the problem, replace the auxiliary contact
block.
• Inspect isolation contactor for damage. The high current contacts maybe
frozen shut. If so, replace isolation contactor.
• If the isolation contactor is not defective, the solid state relay that drives the
isolation contactor coil may be shorted. Replace the CIOM.
High C-Factor Limit Fault
Description:
• Occurs when function #97 (C-FACTOR LIMIT: HI=nnnn LO=nnnn)
is used in the weld schedule and the C-Factor value calculated by
the weld processor exceeds the high limit value programmed in
the function.
Corrective Actions:
• Ensure the "HI" value programmed into function #97 is correct
for the welding application.
• High C-Factor Limit usually indicates current shunting in the
secondary circuit. Typically this is caused by a build-up of
expulsion slag across the gun pinch-point, the part shorting to
the electrode arms or shorting caused by broken leaf shunts.
Low C-Factor Limit Fault
Description:
• Occurs when function #97 (C-FACTOR LIMIT: HI=nnnn LO=nnnn)
is used in the weld schedule and the C-Factor value calculated by
the weld processor is less than the low limit value programmed
in the function.
Corrective Actions:
• Ensure the "LO" value programmed into function #97 is correct for the
welding application.
• Low C-Factor Limit usually indicates an increase in the resistance of the
secondary circuit. This can be caused by frayed or open welding cables. If
water-cooled cables are used (braided copper inside rubber jacket), the
frayed or open cable may not be externally visible and the cable resistance
will need to be checked with a Micro-Ohm Meter.
Low C-Factor Limit Fault
Troubleshooting:
• For all secondary issues, a standard multimeter (Fluke) can not measure the
resistance of the electrode arms (weld tip to transformer connection point).
This resistance is usually in the range of 50-150µΩ and a standard
multimeter and test lead set can only measure to a minimum of
approximately 0.3Ω. Therefore, a Micro-Ohm Meter is required to measure
this resistance.
• In MFDC applications, the welding transformer has diodes in its secondary.
With the gun closed and an insulator between the tips, take a standard
multimeter (in Diode Check Mode) and place the leads across the weld tips.
The multimeter should measure between 0.25V and 0.3V in one direction
and 1.7V and OL (over range) in the other. If the meter measures 0.00V,
either the transformer diodes are shorted or a short exists elsewhere in the
weld tooling (secondary circuit).
System Cooling Fault
Descriptions:
• Occurs when the System Cooling bit goes LOW anytime during
the execution of the weld sequence. This bit is normally
maintained HIGH.
• Occurs when function #79 (WAIT nnnn MS FOR SYSTEM
COOLING) is used in the weld schedule and the System Cooling
bit does not go HIGH within the amount of time programmed in
the function.
Corrective Actions:
• Identify and correct any water flow issues.
• Note: The inverter chill plate temperature can be seen in the
Display Mode screen of the DEP-300s.
Weld Interruption Fault
Descriptions:
• Occurs when the Weld / No Weld bit goes LOW while the weld control is
passing current during the execution of a weld schedule.
• Occurs when the circuit breaker on the weld cabinet is switched OFF while
the weld control is passing current during the execution of a weld schedule.
The fault will appear when the circuit breaker is switched back ON and the
weld processor re-initializes.
I/O Fault
Description:
• Occurs when either an EtherNet IP network communication
timeout occurs.
Corrective Actions:
• Water Cooled Inverter: Ensure the cooling water inlet
temperature is < 95 F (35 C).
• Air Cooled Inverter: Ensure the ambient air temperature around
the weld cabinet does not exceed 104 F (40 C).
• Note: The inverter chill plate temperature can be seen in the
Display Mode screen of the DEP-300s.
Output Ground Fault
Description:
• Occurs when a current imbalance exists between the two output
terminals of the inverter assembly.
Corrective Action:
• Identify and correct the unidirectional current path (shunting) to
ground between the output of the inverter assembly and the
primary of the welding transformer.
Typical problem areas include the rubber boot connectors at
the base of the robot, junction box on the robot and the
primary of the welding transformer.
IGBT Saturation Fault
Description:
• Occurs when the weld processor detects an instantaneous over-
current event, which exceeds the design rating of the IGBT
modules within the inverter assembly. This can be caused by
either a short across the welding transformer primary cables or
a defective inverter assembly.
Corrective Action:
• Use troubleshooting method described in Low Current Limit
Fault. Replace shorted primary cables and/or replace defective
Minipak enclosure.
IGBT Power Supply Fault
Description:
• Occurs when the IGBT Gate Board within the inverter assembly
has failed. This fault is monitored continuously.
Corrective Action:
• Replace defective Inverter.
Bus Charging Fault
Description:
• Occurs when the weld processor has detected the DC bus within
the inverter assembly did not charge correctly (either too slow
or too quickly). This fault is monitored continuously.
Corrective Action:
• Try resetting the circuit breaker on weld control cabinet. If
problem persists, replace defective Inverter.
AC Line Phase Fault
Description:
Occurs when the weld processor detects a line phase is either
incorrect or missing. This fault is monitored continuously.
Corrective Action:
Correct power problem or replace / install missing phase.
Secondary Current Sensor Fault
Description:
Occurs at the initiation of a weld schedule, when the weld
processor does not detect a proper connection to the secondary
current monitoring coil when it should.
This fault will only occur when the weld processor is configured to
either the (PRI/SEC) or (SEC/SEC) Firing Monitoring Mode in the
Setup Parameters.
Corrective Action:
The secondary current coil is either improperly connected to the
weld processor or it is bad. If proper connection has been verified
and the fault still persists, replace the coil with a known good one.
Current Regulation Fault
Description:
Occurs when the inverter reaches its maximum IGBT on-time rating
before the target secondary current is achieved. Thus, whatever
current level is achieved at max IGBT on-time, is what will be
delivered to the welding transformer.
PRESSURE NOT ACHIEVED
Occurs when function #74 (WAIT nnn MS FOR PRESSURE ACHIEVED) is
used in the weld schedule and the programmed pressure is not achieved
within the amount of time programmed in the function.
Check for mechanical problems with the weld gun related to air pressure, e.g.
water in air lines, pressure regulator set too low, etc.
SECONDARY DIODE
Occurs when the weld processor has detected a shorted secondary diode within the
welding transformer.
With the gun closed and an insulator between the tips, take a standard multimeter
(in Diode Check Mode) and place the leads across the weld tips. The multimeter
should measure between 0.25V and 0.3V in one direction and about .7V and in the
other. If the meter measures 0.00V, the secondary diodes are shorted and the
transformer must be replaced.
MedWeld 6000 Weld Cabinet Safety Concerns
What is a weld schedule
A weld schedule is a list of commands that the control is to execute. For example, to
perform a simple spot weld, you might use a weld schedule consisting of the following
functions:
Delay functions all have the same effect on the weld schedule.
They cause the control to wait for the amount of time specified.
During these functions, weld current does not flow and I/O status is not changed.
The time for these delays may be extended in such case where additional de-bounce time is
required for activation of I/O devices.
(Different names are assigned for describing the reasons for a delay).
Extend Function
75: EXTEND UNTIL NO INITIATE
This function is used to latch in the handshaking between the Series 6000 control and
the robot or automation control.
Normally, the schedule is programmed as follows after the weld function:
There is a fault conditions associated with re-welding. Each time the weld is extended; there
is an "EXTEND WELD" which can be set as a FAULT or ALERT. The normal setting is
ALERT. Also, there is a FAULT condition associated with EXCESSIVE REWELDS that can
be set up to detect if the control performs a high rate of extended welds.
99: GOTO SEQ#nnn (nnn = 1-255)
This function defines the length of a weld impulse. It tells the weld processor that the next
function in the schedule should be a pulsation weld (providing heat times followed by
cool times in repetitive fashion, rather than just heat cycles).
When this function appears before any weld function(s), the control displays IMP
(impulse) rather than MS (milliseconds) to indicate the weld control will do a pulsation
weld.
Pulsation welding provides a specified number of impulses
Input Monitoring Functions
These functions require specific inputs.
Before programming these functions, check the packet of drawings that came with your
Series 6000 for I/O availability.
61: ABORT IF NO INITIATE nnnn MSEC
65: WAIT nnnn MS INP #n TO BE 0 (0=OFF 1=ON)
66: WAIT FOR INPUT #n TO BE 0 (0=OFF 1=ON)
67: EXTEND WHILE INPUT #n IS 0 (0=OFF 1=ON)
68: WAIT nnnn MS FOR PRESSURE SWITCH INPUT
69: WAIT FOR PRESSURE SWITCH INPUT
70: WAIT nnnn MS FOR WELD PROCEED INPUT
71: WAIT FOR WELD PROCEED INPUT
79: WAIT nnnn MS FOR SYSTEM COOLING
85: WAIT FOR NO INITIATE IF FAULT
These functions allow the control to react to inputs coming to the control from welding
machines and automation equipment. Special sequencing for seam welding and other
applications can be solved using these functions. For example, varying the current
intensity of a seam welding process around corners can be solved by using function #67
following a weld current function.
Output Functions
These functions require specific outputs. Before programming these functions, check the
packet of drawings that came with your Series 6000 for I/O availability.
50: TURN ON WELD COMPLETE
51: TURN OFF WELD COMPLETE
52: TURN ON ISOLATION CONTACTOR
53: TURN OFF ISOLATION CONTACTOR
54: TURN ON VALVE #n (n = 1-6)
55: TURN OFF VALVE #n (n=1-6)
56: SET PRESSURE #nn (n=01-15)
58: TURN ON WELD IN PROGRESS
59: TURN OFF WELD IN PROGRESS
63: TURN ON OUTPUT #n
64: TURN OFF OUTPUT #n
These functions allow the control to turn outputs on or off within a weld schedule. Even
though these functions are available, certain versions of the software do NOT allow
inserting or deleting the following functions from a weld schedule using the DEP
Overide Functions
Overriding Setup Parameter Functions
76: SEC. CURR LIMITS: HI=nnnn0 LOW=nnnn0
77: ISOLATION CONTACTOR DELAY = nn SEC.
84: CURRENT WINDOW HI=nn% LO=nn%
90: TRANSFORMER TURNS RATIO nnn:1 (nnn=1-256)
97: C-FACTOR LIMIT: HI=nnn LO=nnn
The functions above allow setting programming limits that are unique to a given weld
schedule. The new limits override the limits programmed in the setup parameters,
and apply only to the weld schedule where they appear. They also take priority over
any other limits established
Process Weld Faults Function
Process Weld Faults
78: PROCESS WELD FAULTS
This function sets the Series 6000 timer to indicate any faults that may have been
generated so far in the schedule. The control normally processes all fault conditions at
the end of the weld schedule. This function allows forcing the control to process fault
conditions before it completes the weld schedule and before it activates the WELD
COMPLETE output .
Repeat Function
Weld functions provide a specified amount of weld current for the number of cycles
programmed. The weld function you select also tells the weld processor the type of
firing mode to use to control the energy provided to a weld. Specify weld current as
either:
A percentage of maximum available current, or
By the amount of secondary current desired.
These functions tell the control how to compensate for changes in the welding
environment:
%I determines the inverter firing point to achieve a set percentage of the maximum rated
inverter current.
Automatic Current Compensation. ACC monitors the current during each millisecond. It
compensates for changes detected during the millisecond firing point, to maintain
secondary current at the level programmed.
While the weld function used in the weld schedule will determine how weld current is
applied, the inverter setup parameters and firing modes determine how weld energy is
regulated, and when fault conditions will be generated.
Slope Current Functions
Either function (40 or 45) will fire for the time specified. For example, the function 40
SLOPE 200 MS 45% I TO 65% I tells the control to fire one millisecond at 45% of
the maximum available current. Then, over the next 199 milliseconds, it gradually
increases the heat provided to 65%.
I/O Needed
Input - Binary Selects
These inputs select the schedule to be initiated (1 - 255). The schedule is selected by a
combination of these inputs. Each input has a weighted value (1, 2, 4, 8, 16, 32, 64 or 128).
The schedule initiated is the one selected by adding the weighted values of the active
inputs. For example, to initiate schedule #4, activate BINARY SELECT Input #4. To
initiate schedule #7, activate BINARY SELECT inputs #1, #2 and #4 (because 1 + 2 + 4 = 7).
I/O Needed
Input - Isolation Contactor Saver
CSVR
This input tells the weld processor to enable the isolation contactor delay timer. The delay
timer (), holds the isolation contactor closed after a weld schedule is completed, to
prevent it from dropping out between welds. If this input is active at the end of a
schedule, the weld processor will hold the isolation contactor closed for the amount of
time programmed. If this input is not active, the isolation contactor will drop out at the
end of the weld schedule. However, if this input drops out during the delay time, the
remaining time on the delay timer is aborted and the isolation contactor is immediately
opened.
I/O Needed
Input - Fault Reset
FR
This input allows the control to remotely reset all faults.
This output indicates that one or more of the 32 steppers has arrived to the last weld of a
stepper. It is normally OFF. It turns ON to indicate the condition. The End of Stepper is
usually set up as a Fault condition. The End of Stepper will activate a Fault. In most recent
software, the End of Stepper will continue to a maximum of 40 welds before causing a
Fault thus allowing a robot to finish its welding cycle on a part.
This output is the invert of the Alert condition. It is normally ON. It turns OFF to indicate
an alert condition. Alert conditions are usually less serious than faults and normally serve
to warn the operator that maintenance is required. The weld control will automatically
reset the Alert condition upon a Fault Reset input, the execution of a weld schedule, or
upon a reset from a programming device. Programming of conditions as being an Alert is
done in the setup parameters.
I/O Needed
Output - No Fault
NFLT
This output is the invert of the Fault condition. This output is normally ON to indicate that
no fault conditions exist. If the control shuts down as the result of a fault condition, this
output will be turned OFF. The weld control will automatically reset the Fault condition
upon a Fault Reset input or upon a reset from a programming device. In some versions,
the Fault will inhibit the initiation of weld schedules so a fault reset would be required in
such case. Programming of conditions as being a Fault is done in the setup parameters.
I/O Needed
Output - No Control Stop
NCS
This output is ON to indicate that the control is not in control stop. If the timer detects a
control stop condition, this output will go OFF.
WMO
This output is used to indicate to robot or automation controls that the weld control is in
WELD MODE.
I/O Needed
Output - Steppers are Reset
SRST
This output indicates that all steppers in the timer have been reset. Usually, this output is
used for handshaking purposes with a robot to confirm that the robot initiated stepper
reset has been accomplished. The output will be ON when all steppers are on the first
weld of step #1. As soon as one of the steppers have advanced, the output will be OFF.
This output is used to handshake with the robot or automation to indicate that welding is
complete without fault. This output turned on and off by the weld control in response to .
This output is used to handshake with the robot or automation to indicate that welding is
occuring. This output turned on and off by the weld control in response to .
Stepper Profile Step 1 = + 00% + 1000 A after 0100 welds
Step 2 = + 00% + 0500 A after 0100 welds
Current Regulation mode Step 3 = + 00% + 0200 A after 0100 welds
Step 4 = + 00% + 0100 A after 0100 welds
Step 5 = + 00% + 0050 A after 0100 welds
1 Step 1 = +00% + 1000 A after 0100 welds
Stepper Profile
12000
11500
11000
10500
1
10000
9500
9000
24
48
72
96
120
144
168
192
216
240
264
288
312
336
360
384
408
432
456
480
Weld
11500
Tip Dress Remain > 0
11000 2
10500
10000
9500
9000
24
48
72
96
120
144
168
192
216
240
264
288
312
336
360
384
408
432
456
480
Weld
Stepper Profile
11500 3
11000
Tip Dress Remain > 0
10500
10000
9500
9000
24
48
72
96
120
144
168
192
216
240
264
288
312
336
360
384
408
432
456
480
Weld
11500
11000
Tip Dress Remain > 0
10500
10000
9500
9000
24
48
72
96
120
144
168
192
216
240
264
288
312
336
360
384
408
432
456
480
Weld
12000
11500
11000
10500
10000
9500
9000
24
48
72
96
120
144
168
192
216
240
264
288
312
336
360
384
408
432
456
480
Weld
Stepper Profile
80
70
60
50 1
40
30
20
10
0
23
46
69
92
115
138
161
184
207
230
253
276
299
322
345
368
391
414
437
460
483
Weld
Stepper Profile
Tip Dress Request
80
70
60 2
Stepper Profile
Tip Dress Request
80
70
3
60
50 Tip Dress Remain > 0
40
30
20
10
0
23
46
69
92
115
138
161
184
207
230
253
276
299
322
345
368
391
414
437
460
483
Weld
Stepper Profile
End of Stepper
80
70
60
50
40
30
20
10
0
23
46
69
92
115
138
161
184
207
230
253
276
299
322
345
368
391
414
437
460
483
Weld
12000
11500
11000
10500
1
10000
9500
9000
24
48
72
96
120
144
168
192
216
240
264
288
312
336
360
384
408
432
456
480
Weld
12000
11500
11000 2
10500
10000
9500
9000
24
48
72
96
120
144
168
192
216
240
264
288
312
336
360
384
408
432
456
480
Weld
11000
Tip Dress Remain > 0
10500
10000
9500
9000
24
48
72
96
120
144
168
192
216
240
264
288
312
336
360
384
408
432
456
480
Weld
11000
2
Tip Dress Remain Count Decrease
10500
If count still > 0, stepper will continue towards step 3
10000
9500
9000
24
48
72
96
120
144
168
192
216
240
264
288
312
336
360
384
408
432
456
480
Weld
11500
11000 2
Tip Dress Remain Count Decrease
10500
11500 3
11000
If Tip Dress Remain Count is decreased to 0,
10500 End of Stepper is activated at start of Step 3
10000 1st 40 welds will be ALERT then
9500 FAULT will occur on 41st weld if Stepper is not
reset
9000
24
48
72
96
120
144
168
192
216
240
264
288
312
336
360
384
408
432
456
480
Weld
The weld control unit has many steppers that can be assigned to a weld
schedule. Press F1 to select the stepper (example Stpr#24) for which you
want to review status.
Stepper Status
From this status screen, you can Advance the stepper by activating the F3
key
Software overview
• View Data
Weld, Steppers and Active Faults
• Reset Faults and Steppers
• Programming
Setup Parameters
Faults Severity
Operating Parameters
• Weld Schedules
Inserting / Editing Instructions
weld Instructions
Delay Instructions
Input & Output Monitoring
• Steppers
Counts and Boosts
The WTC EDEP ( Ethernet Data Entry Panel) Is a compact programming
device. That communicates with the weld timers though the local or the EIP
Ethernet Ports on the timer and also by the Serial Port on the timer.
The EDEP allows you to program weld schedules, Set-up parameters,
networking and a stepper profile then download the information to the weld
control. It also receives and displays the weld control weld summary data,
Stepper data, Active Faults and view the I/O
When the EDEP is plug in to the local port on the timer the EDEP will only
look for IP address 89.89.200.250. It will only communicate with the timer
which the EDEP is plug into.
If the local IP address is changed the EDEP will not communicates with the
timer. Local IP address does not need to be changed with the EDEP.
To communicates to the timer remotely though the EIP board the timer must
be set up with the IP address and subnet mask will cover this in the program
section there is no limit of timers that this EDEP can talk to.
There is no reason for you as a customer to need to used that serial port
(9 pin D shell type connector) unless both Ethernet ports not communicating
EDEP Display
IP Address for the timer you are commutating with
The welder ID
if there are active faults or alerts
The Key Pad
The EDEP provides push button keys to request status displays or making programming
changes.
The 5 “soft” keys F1
through F5 perform
different functions based
Leds 1 through 5 do nothing
on the mode you are in.
The symbols are only used up and down arrow keys
with the shift key pressed. scroll up and down
they are used for the letters to though the display
Program the timer ID.
Left and Right arrow keys
When the Shift key is light it move the cursor within a
allows you to used the top display
lettering in blue on the press
key the number keys 0 – 9 are
used to enter new values.
Power key is for the EDEP
only will not effect the weld Press the Enter key to
timer. place a new value into the
ESC key is used to undo EDEP memory. You must
unsaved data during DOWNLOAD your
programming changes
137
Power Up
The EDEP requires power from the timer when the EDEP is plug into the local Ethernet
port on the timer. The power comes from the CNMN1 the 9pin connector. Both the cables
have to be plug into the timer for the EDEP to work and have power.
If you are using the EDEP in a remotely you will still have to get power to the
EDEP with the cable that is provided with the EDEP.
When you are trying to talk to the timer remotely remember you will need to program the
EDEP IP address and subnet mask to talk to the timers. when you plug in the switch for
communication you will also need to have a plug for the power.
** The customer that is you, will need to provide the IP addresses and subnet mask all WTC
products will be set the EIP standard defaults.**
There are different cables for the EDEP One for communication locally and different one
for remotely.
When you apply power and plug in the EDEP you will have select local or global Ethernet.
That will be determined by where you plug in the cable.
Remember if the EDEP is plug in to the timer then you want local Ethernet.
If the EDEP is communicating remotely then you will want to select Global Ethernet.
Previous will let you look up to the last 30 weld Reset takes you to most resent weld
F5 Faults
Page 1 Page 2
F2, F5 Program Mode Page 2
F1 EIP Options setup the commutation to be able to talk to the weld timer by EIP
F2 Welder ID is where you can give your timer a Alfa numeric ID
F3 were you can set the date time and set defaults values
F4 Local Ethernet will change the setting talking to the EDEP only there is no
needed to change it and the only way to change it is by using serial communication.
F5 more takes you back to the first page of the Program menu
EIP Options
New timers are not set up to commutate you will need to Program the weld timer.
The IP Address and sub net Mask are set by the customer. Also If used by the customer you
will have to set the Gateway and Name Server.
Input and Output Instance are set and should be programmed. They can not be
programmed by the EDEP unless you reload defaults.
Mac Address is the hardware ID and can not be changed.
You will have to set the DHCP most of the time it will need to be changed to off.
The DHCP will set the retry and is only used when DHCP is turned on.
Port Mode should be set to auto. If the mode does not match the
with the Robot or PLC the timer will not talk.
If you set it to auto then it will match
what the robot is set to.
The other options are 10 half and 100 full
Programming EIP Options
To Program the data use the arrow keys to move the cursor to area you need to edit Type in
the new data and press enter. Finish changing all of the data on the screen
Then you need to press the F2 for download
You must download and cycle power to the timer before the date will take effect.
F3 Reload for EIP Options
(off) means will we not do any thing
(clear I/O) will erase all programmed I/O
(I/O default) will reset all the I/O back to factory setting
(EIP Factory Default) will reset all your EIP setting back to original setting meaning that
you will have to reprogram all the data in the EIP screen including the DHCP.