II 2 GD Ex db IIC T* Gb Tamb -55°C to +**°C Ex tb IIIC T**°C Db IP66/67 Tamb -55°C to +**°C
SGS Fimko Oy Customer Reference No. 0676 Project File No. 22/0235
This document is issued by the Company subject to their General Conditions for Certification Services accessible at http://www.sgs.com/en/Terms-and-
Conditions.aspx . Attention is drawn to the limitation of liability, indemnification and jurisdiction issues defined therein. Any holder of this document is
advised that information contained herein reflects the Company’s findings at the time of their intervention only and within the limits of Client’s instructions,
if any. It does not necessarily indicate that the equipment may be used in particular industries or circumstances. The Company’s sole responsibility is to
its Client and this document does not exonerate parties to a transaction from exercising all their rights and obligations un der the transaction documents.
This document cannot be reproduced except in full, schedule included, without prior written approval of the Company. Any unauthorized alteration, forgery
or falsification of the content or appearance of this document is unlawful and offenders may be prosecuted to the fullest extent of the law .
SGS Fimko Oy
Takomotie 8
FI-00380 Helsinki, Finland
Telephone +358 (0)9 696 361
e-mail [email protected]
web site www.sgs.fi Mikko Välimäki
Business ID 0978538-5 Member of the SGS Group (SGA SA) SGS Fimko Oy
BAS-CERT-081 SGS Baseefa Limited is an associate of SGS Fimko OY Issue 3
Certificate Number
Issued 14 November 2023
Baseefa03ATEX0075X
Page 2 of 7
Issue 21
13 Schedule
14 Certificate Number Baseefa03ATEX0075X – Issue 21
15 Description of Product
The Range of SM87 Alarm Stations comprises a cylindrical enclosure a square base with an irregular shaped cover secured
by 4 off screws of grade A4-70 or A4-80 stainless steel. The base and cover may be manufactured from either aluminium or
stainless steel.
The cover is fitted with an actuator mechanism which may be operated by either a push button or break glass function
dependant on the external actuator assembly.
The units may be supplied by the manufacturer in an assembly of up to five interconnected enclosures using cable bushings
to EPS13ATEX1619U.
Type BGLD – A Breakglass unit with latching mechanism The interior of the enclosure comprises up to two micro-switches,
mounted on the inside of the cover, and up to twelve rail mounted terminals fitted to the enclosure base, and rated up to 24V,
2A.
Type LBGLD - A Breakglass unit with protective lift flap and latching mechanism. The interior and rating as per the Type
BGLD.
Type PBLD – A Push Button unit with latching mechanism. The interior and rating as per the Type BGLD.
Type PBMD – A Push button unit with momentary mechanism. The interior and rating as per the Type BGLD.
Type SM87 EOL Unit A – The interior comprises up to two micro-switches, mounted on the inside of the cover, and up to
twelve rail mounted terminals fitted to the enclosure base with the addition of an end of line module rated 24V 0.5A.
Type SM87 Addressable Unit B –The interior comprises up to two micro-switches, mounted on the inside of the cover and a
Servoteknikk addressable callpoint PCB, rated up to 24V 0.5A.
Type SM87 Addressable Unit G –The interior comprises up to two micro-switches, mounted on the inside of the cover and a
Tyco addressable callpoint PCB, rated up to 24V 0.5A.
Type SM87 Addressable Unit F – The interior comprises up to two micro-switches, mounted on the inside of the cover and
an Autronica addressable callpoint PCB, rated up to 24V 0.5A.
Type SM87 XP950 Module Unit – The interior comprises up to two micro-switches, mounted on the inside of the cover and
an Apollo PCB, rated up to 24V 1.0A.
Type SM87 Addressable Unit H - The interior comprises a Hochiki addressable callpoint PCB and up to 7 terminals rated at
up to 24V 0.2A.
Type SM87 Addressable Unit J - The interior comprises a Ziton addressable module, up to 5 terminals and 2 x 2.5W resistors
rated at up to 24V 0.1A, 7W.
Type SM87PBD MCR-CUBE EOL Unit – an SM87 Alarm Station with switches mounted on the underside of the cover and
an end of line (EOL) module and terminals mounted in the base, rated up to 24V, 0.5A.
Type SM87 Omron Relay Unit A – Type SM87 Alarm Station comprising an alternative interior which includes a relay
callpoint, Omron Type SPDT G2R and up to 6 Weidmuller AKZ 1.5 terminals, rated up to 24V, 2A.
Type SM87 Addressable Unit C - SM87 Alarm Station with switches mounted on the underside of the cover and an alternative
addressable printed circuit board (PCB) mounted in the base, rated up to 28V, 0.5A
Type SM87 Addressable Module G – with switches mounted on the underside of the cover and an alternative addressable
Tyco module mounted in the base, rated up to 24V, 0.02A.
Type SM87 Addressable Module I – with switches mounted on the underside of the cover and an alternative addressable
Apollo module mounted in the base, rated up to 24V, 0.02A.
Type SM87 Addressable Module K – with switches mounted on the underside of the cover and an alternative addressable
Tyco module mounted on the base, rated up to 24V, 0.1A.
Cable entry holes are provided as specified on the certified drawings for the accommodation of flameproof cable entry devices,
with or without the interposition of a flameproof thread adapter. Unused entries are to be fitted with suitable certified
flameproof stopping plugs.
The cable entry devices, thread adapters and stopping plugs shall be suitable for the equipment, the cable and the conditions
of use and shall be certified as Equipment (not a Component) under an EC Type Examination Certificate to Directive
2014/34/EU.
When used in an explosive dust atmosphere the cable entry devices shall maintain the ingress protection of the enclosure.
16 Report Number
See certificate history.
20 Certificate History
Certificate No. Date Comments
Baseefa03ATEX0075 09 May 2006 The release of the prime certificate. The associated test and
assessment against the requirements of EN 50014:1997 +
Amendments 1 & 2, EN 50018:2000 + Amendment 1, EN 50281-1-
1:1998 is documented in Test Report No. 02(C)0226.
Baseefa03ATEX0075/1 27 January 2004 Alternative arrangement comprising an SM87 Alarm Station with
switches mounted on the underside of the cover and an addressable
printed circuit board (PCB) mounted in the base.
In this form the unit is designated a SM87 ADDRESSABLE UNIT
B and is rated up to 24V, 0.5A with a revised Temperature
Classification of T85°C (Tamb = -55°C to +55°C) or T100°C (Tamb
= -55°C to +70°C).
No report.
Baseefa03ATEX0075/2 27 January 2004 Alternative arrangement comprising an SM87 Alarm Station with
switches mounted on the underside of the cover and an alternative
addressable printed circuit board (PCB) mounted in the base.
In this form the unit is designated a SM87 ADDRESSABLE UNIT
F and is rated up to 24V, 0.5A with a revised Temperature
Classification of T85°C (Tamb = -55°C to +55°C) or T100°C (Tamb
= -55°C to +70°C).
No report.
Baseefa03ATEX0075/3 29 January 2004 Alternative arrangement comprising an SM87 Alarm Station with
switches mounted on the underside of the cover and an alternative
addressable printed circuit board (PCB) mounted in the base.
In this form the unit is designated a SM87 ADDRESSABLE UNIT
G and is rated up to 24V, 0.5A with a revised Temperature
Classification of T85°C (Tamb = -55°C to +55°C) or T100°C (Tamb
= -55°C to +70°C).
No report.