Data Sheet Zonecheck
OVERVIEW
A Zonecheck unit incorporates an approved flow-switch with a testing pump and circulation loop. When the pump is
activated via the local key-switch, water is circulated across the flow-switch at a flow equivalent to one sprinkler head in
operation (required by code standards). The Key-switch is used to activate the Zonecheck test and indicate flow-switch
activation as well as the local valve-status. 060a
Zonecheck is simple and sustainable solution for performing sprinkler system flow-switch tests. Zonecheck does not
initiate the fire pump which eases co-ordination and labour whilst also reducing the risk of false alarms.
Specifications
Be
for
an e initia
d iso
lat ting a
e an flo
y ala w-sw
rm
s. Onitch tes
ce t
tes cont
t is ac
comp t ap Key
pr
let opria -sw
e ret te
urn fire
to sa
itch
Pum
Ru p ‘st an fety
nni
ng Flow-s db perso
y’ po nn
Ac witch sit el
tiva ion
ted Val .
Gr Stan
ve
ou Fau
testp
lt
db
y
22
0V
50 AC~
Hz
ZC Se
KY lf
SE test
+4
4 (0
)18
89
27
1271
inf
o@
proje
ctfi Tes
t gui
re.
[Link] de.
Proje
ct
Fir
e Pr
od
ucts
Ltd
ZONECHECK FLOW-SWITCH
Working pressure rating Water, 12 bar (175 psi) max Type Potter VSR-EU
Operating temp range 0°C - 49°C (32°F – 120°F) Contact rating 10A@125/250VAC
Pipe diameter 50/65/80/100/150/200mm (2-8“) 2.0A@30VDC
Approvals LPCB, UL, FM and VdS IP rating IP54
IP rated IP54 Time delay 0-30s
KEY-SWITCH PUMP
Voltage 230v 50Hz Type Wilo Para
Internal consumption 7.5W max Operating voltage 230v 50Hz
Amps 0.88A Amps 0.82A
LED indication Pump running Max power rating 75W
Flow-switch activated IP Rating IPX4D
Valve fault
Max key-switch group size 25
Max group cable length 300m
Product code (Order No.) ZCKYSE
Spare key set (Order No.) ZC-ALKK
ØMM A B C D
Dimensions 50 (2”)
65 (2 ½”)
210
215
66
66
145
155
116
124
80 (3”) 220 85 165 130
100 (4”) 225 85 170 140
150 (6”) 250 115 195 170
200 (8”) 275 150 225 195
*Please leave a minimum of 160mm above the face flow-switch and pump head
for access and maintenance.
B A 450mm
Orientation
Zonecheck can be installed both horizontally and vertically. Please check the
directional arrows on the pump casting before installing. Pump flow should be
opposite to the sprinkler systems flow.
When installing horizontally the flow-switch must face upwards and can not be
installed facing sidewards or below the pipe.
Left hand and right hand models are designed for when Zonecheck is installed
along walls and space is limited.
(SIDE VIEW) (VIEW FROM ABOVE)
LEFT RIGHT
HAND HAND
Wiring
Typical fire-alarm/flow-switch connections (Typical 1/Typical 2). Exact wiring
required depends on type of fire panel used. Refer to specific fire-alarm panel
instructions for further information/guidance.
Resistors sized according to specific alarm-panel requirements.
(x) = fire/alarm resistor (usually 1Ω)
(y) = end of line resistor (usually 470Ω)
Up to 25 Zonechecks can be tested simultaneously when the Zonecheck units
are wired in parallel via ‘group’ by turning the master key-switch to ‘Group Test’.
POWER SUPPLY
POWER SUPPLY KEY-SWITCH
GROUND GROUND
L N L N
MAINS IN PUMP OUT
KEY-SWITCH
MALE-FEMALE
CONNECTORS
FLOW-
(SUPPLIED)
SWITCH VALVE GROUP
1 2 1 2 + -
KEY-SWITCH
GROUPING
OPTIONAL ZONECHECK
FIRE ALARM/ MONITORED VALVE/ PUMP
INTERFACE ISOLATION VALVE
DEVICE
FIRE ALARM/
INTERFACE DEVICE
y
KEY-SWITCH
FLOW-SWITCH
(TYPICAL 1)
N/O COM COM N/O
y x
FLOW-SWITCH
(TYPICAL 2)
N/O COM COM N/O
Designed and manufactured in the
100% water saving Remote testing No water discharge UK by Project Fire Products Ltd.
+44(0)1889 271271
info@[Link]
Approved Simplified testing method Code compliant
[Link]
Zonecheck® is a registered trademark.
Sustainable testing LPCB VdS FM UL © Project Fire Products Ltd. 2023.
Energy efficient
PROJECT FIRE®