Paquete 25TON TRANE

The document provides an overview of the Voyager™ packaged cooling units with electric heat, detailing their features, benefits, and application considerations. It emphasizes the units' reliability, ease of installation, and advanced control systems, making them suitable for light commercial applications. The document also includes technical specifications, performance data, and guidelines for selection and installation.

Uploaded by

Luis Oropeza
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
99 views72 pages

Paquete 25TON TRANE

The document provides an overview of the Voyager™ packaged cooling units with electric heat, detailing their features, benefits, and application considerations. It emphasizes the units' reliability, ease of installation, and advanced control systems, making them suitable for light commercial applications. The document also includes technical specifications, performance data, and guidelines for selection and installation.

Uploaded by

Luis Oropeza
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 72

Packaged Cooling with

Electric Heat Rooftop Units

Voyager™
12½ - 25 Tons - 60 Hz

December 2003 RT-PRC002-EN


Introduction

VoyagerTM . . . a proven performer built to For contractors, Voyager saves time and
provide ultimate indoor comfort. money, increasing their ability to win
Voyager continues to provide the highest jobs. It meets engineer’s design criteria
standards in quality and reliability, and offers solutions to cover many
comfort, ease of service, and the special applications. And, of course,
performance of Trane light commercial Voyager carries the Trane reputation for
products. excellence, quality and reliability.

© 2003 American Standard Inc. All rights reserved RT-PRC002-EN


Contents

Introduction 2
Features and Benefits 4

Application Considerations 8

Selection Procedure 9
Model Number Description 10
General Data 11

Performance Data 15
Cooling Performance 15
Fan Performance 21
Heat Performance 34
Controls 35
Electric Power 36
Dimension and Weights 54

Mechanical Specifications 65

RT-PRC002-EN 3
Features and
Benefits

Weather Tight Top and Cabinet • Actual shipping tests were performed Conversionless Units
• Voyager units incorporate either a one to determine packaging requirements. • The dedicated design units (either
piece top or the Trane-Tite-Top (T3). Units were test shipped around the downflow or horizontal) require no
Each part of the top (either two or three country to determine the best panel removal or alteration time to
pieces) overlaps in such a way that packaging. Factory shake and drop convert in the field — a major cost
water cannot leak into the unit. These tests were used as part of the package savings during installation.
overlapped edges are gasketed and design process to help assure that the
sealed to ensure superior water unit arrives at the job site in top • Horizontal units come complete with
condition. duct flanges so the contractor doesn’t
integrity. have to field fabricate them. These duct
• Quick- Access (12½-25 tons) panels • Rigging tests include lifting a unit into flanges are a time and cost saver.
reduce the number of possible water the air and letting it drop one foot,
entry points. assuring that the lifting lugs and rails U-shaped Airflow
hold up under stress.
• For added water integrity, Voyager has • U-shaped airflow allows for improved
a raised 11/8" lip around the supply and • We perform a 100% coil leak test at the static capabilities.
return of the downflow units to prevent factory. The evaporator and condenser
water from blowing into the ductwork. coils are leak tested at 200 psig and
pressure tested to 450 psig.
Quality And Reliability Testing • All parts are inspected at the point of
• The fan and idler arm assembly final assembly. Sub-standard parts are
designs have been tested to over identified and rejected immediately.
300,000 cycles each. Our combined • Every unit receives a 100% unit run test
cycle testing is now over 7,000,000 before leaving the production line to
cycles. make sure it lives up to rigorous Trane
• All of Voyager’s designs were requirements.
rigorously rain tested at the factory to
ensure water integrity. We test designs at our factory not on
our customers!

4 RT-PRC002-EN
Features and
Benefits

• Eliminates the need for field-installed


components with its built-in anti-short-
cycle timer, time delay relay and
minimum ‘’on’’ time controls. These
controls are factory tested to assure
proper operation.
• Requires no special tools to run the unit
through its paces during testing. Simply
place a jumper between Test 1 and Test
2 terminals on the Low VoltageTerminal
Board and the unit will stage through its
operational steps.The unit
ReliaTel™ automatically returns control after 60
minutes to the zone sensor after
Several years ago, Trane was the first to stepping through the test mode a single
introduce ReliaTel into the Light time, even if the jumper is left on the
Commercial Market. That design, along unit.
with immeasurable experience, has
provided the technology for Trane’s • As long as the unit has power and the
second-generation ReliaTel LED is lit, the ReliaTel is operational.
microprocessor controls. The light indicates that the ReliaTel is
functioning properly.
ReliaTel: • Features expanded diagnostic
• Provides unit control for heating, capabilities when used with Trane’s
cooling, and ventilating by utilizing Integrated ComfortTM Systems.
input from sensors that measure • As an energy benefit, softens electrical
outdoor and indoor temperature. ‘’spikes’’ by staging on fans,
compressors and heaters.
• Improves quality and reliability
through the use of time-tested • The Intelligent Fallback or Adaptive
microprocessor controls and logic. Control is a benefit to the building
occupant. If a component goes astray,
• Prevents the unit from short cycling, the unit will continue to operate at
considerably improving compressor predetermined temperature set points.
life.
• Intelligent Anticipation is a standard
• Ensures that the compressor will run feature of the ReliaTel. Functioning
for a specific amount of time, which constantly, the ReliaTel and zone
allows oil to return for better sensors work together in harmony, to
lubrication, enhancing the reliability of provide tight comfort control.
the compressor.
• Reduces the number of components
required to operate the unit, thereby
reducing possibilities for component
failure.

RT-PRC002-EN 5
Features and
Benefits

Easy Access Low Voltage Terminal Board


Voyager’s Low Voltage Terminal Board is
external to the electrical control cabinet.
It is extremely easy to locate and attach
the thermostat wire. This is another cost
and time saving installation feature.

Standardized Components
• Components are placed in the same Low Voltage Connections
location on all Voyager units.
Familiarize yourself with one Voyager The wiring of the low voltage
and you are familiar with every connections to the unit and the zone
Voyager. sensors is as simple as 1-1, 2-2, and 3-3.
This simplified system makes it easy for
• ReliaTel can fit all Voyager Packaged the installer to wire.
Gas/Electrics, Cooling with Electric Quick-Adjust Idler Arm
Heat, and Heat Pump models. This Colored And Numbered Wiring
provides standardization of parts for You save time and money tracing wires With the Quick-Adjust Idler Arm, the belt
the contractors. Less money is tied up and diagnosing the unit. and sheaves on all 12½-25 tons can be
in inventory using the ReliaTel. quickly adjusted without moving the
VariTrac™ mounted fan motor. The result is a major
• Contractors/owners can stock fewer When Trane’s changeover VAV System savings in time and money.
parts due to standardized components for light commercial applications is
throughout Voyager units. coupled with Voyager, it provides the
Single Side Service latest in technological advances for
Single side service is standard on all comfort management systems and can
Voyager 12½-25 tons. allow thermostat control in every zone
served by VariTrac.
Quick-Access Panels On The 12½-25 Tons
Remove three or fewer screws for access
to the standardized internal components
and wiring.
VariTrac

6 RT-PRC002-EN
Features and
Benefits

Capacity Modulation Flexible Applications Factory Built Roof Curbs


• The 12½-25 tons have dual • Only three roof curbs for the entire Available for the downflow units.
compressors. Voyager line simplifies curb selection. Zone Sensors
Compressors • Airflow is outstanding. The Voyager can Available in programmable, automatic
• Voyager utilizes the best compressor replace an older machine with old and manual styles.
technology available to achieve the ductwork and, in many cases, improve
the comfort through better air The following options round out the
highest possible performance. The complete line of Voyager accessories:
dual compressor models are distribution.
outstanding for humidity control, light • A wide variety of Factory Installed — 0 - 25% manual outside air hood
load cooling conditions and system Options (FIOPs) are available. — Motorized outside air for 12½-25 tons
back-up applications. Trane Communication Interface (TCI) One Of Our Finest Assets:
Low Ambient Cooling Available factory or field installed. This Trane Sales Representatives are a
All Voyager 12½-25 tons have cooling module, when applied with the Micro, Support group that can assist you with:
capabilities down to 0°F as standard. easily interfaces with Trane’s Integrated — Product
ComfortTM System. — Application
Power Exhaust Option — Service
This option is available on the 12½-25 Single Point Power — Training
tons downflow units. It provides exhaust A single electrical connection powers the — Special Applications
of the return air, when using a downflow unit. — Specifications
economizer, to maintain proper building Sloped Drain Pans — Computer Programs and much more
pressurization. Great for relieving most Voyager has the features and benefits
building overpressurization problems. Standard on every unit.
that make it first class in the light
CO2 Sensing Downflow And Horizontal Economizers commercial rooftop market. Designed
The CO2 sensor has the ability to monitor The economizers come with three with input from field contractors and
space occupancy levels within the control options — dry bulb is standard, engineers, its U-shaped airflow
building by measuring the parts per enthalpy and differential enthalpy are performance is outstanding.
million of CO2 (Carbon Dioxide) in the air. optional. If all of your customers knew about
As the CO2 levels increase, the outside air High Static Drive Accessory Voyager, all would insist on it.
damper modulates to meet the CO2
space ventilation requirements.The CO2 Available on many models, this high
sensor kit is available as a field installed static drive accessory extends the
accessory. capability of the standard motor. Avoid
expensive motors and operating costs
Ventilation Override Accessory by installing this optimized sheave
With the Ventilation Override Accessory accessory.
installed, the unit can be set to transition
to up to 3 different pre-programmed
sequences for Smoke Purge,
Pressurization, and Exhaust. The
transition occurs when a binary input on
the RTOM is closed (shorted). This would
typically be a hard wired relay output
from a smoke detector of fire control
panel.The ventilation override kit is
available as a field installed accessory.

ReliaTel

RT-PRC002-EN 7
Application
Considerations

Application of this product should be Power Exhaust Accessory


within the cataloged airflow and cooling The power exhaust accessory is
considerations. available on all 12½-25 ton downflow
units. This accessory can be field
Low Ambient Cooling installed and will assist in relieving
This Voyager line features, as standard, building pressurization.
low ambient cooling down to 0°F.
Contact your local Trane Representative Condensate Trap
for more assistance with low ambient The evaporator is a draw-thru
cooling applications. configuration. A trap must be field
provided prior to start-up on the cooling
Barometric Relief cycle.
This product line offers an optional
barometric relief damper included in the Clearance Requirements
downflow economizer accessory. This The recommended clearances identified
accessory consists of gravity dampers with unit dimensions should be
which open with increased pressure. As maintained to assure adequate
the building air pressure increases, the serviceability, maximum capacity and
pressure in the unit return air section peak operating efficiency. Actual
also increases, opening the dampers clearances which appear inadequate
and relieving the conditioned space. should be reviewed with the local Trane
sales personnel.
NOTE: THE EFFECTIVENESS OF
BAROMETRIC RELIEF DAMPER Unit Pitch
DURING ECONOMIZING OPERATION
IS SYSTEM RELATED. These units have sloped condensate
drain pans. Units must be installed level,
PRESSURE DROP OF THE RETURN AIR any unit slope must be toward access
SYSTEM SHOULD BE CONSIDERED TO side of unit.
CONTROL BUILDING PRESSURIZA-
TION.

8 RT-PRC002-EN
Selection
Procedure

Cooling Capacity To Find Capacity at Intermediate Step 5


Conditions Not in the Table If the performance will not meet the
Step 1
When the design conditions are required load of the building -total or
Calculate the building’s total and sensible
between two numbers that are in the sensible cooling load, try a selection at
cooling loads at design conditions. Use
capacity table, interpolation is required the next higher size unit.
the Trane calculation methods or any
other standard accepted method. to approximate the capacity. Note: Heating Capacity
Extrapolation outside of the table
Factors used in unit selection: conditions is not recommended. Step 1
A Calculate the building heating load
Total Cooling Load: 180 MBh Step 4 using the Trane calculation form or other
B In order to select the correct unit which standard accepted method.
Sensible Cooling Load: 129 MBh meets the building’s requirements, the
C fan motor heat must be deducted from Step 2
Airflow: 6000 cfm the gross cooling capacity. The amount Size the system heating capacity to
D of heat that the fan motor generates is match the calculated building heating
Electrical Characteristics: 460/60/3 dependent on the effort by the motor - load. The following are building heating
E cfm and static pressure. To determine the requirements:
Summer Design Conditions: Entering total unit static pressure you add the A
Evaporator Coil: 80 DB, 67 WB Outdoor external static pressure to the additional Total heating load of 115.0 MBH
Ambient: 95 DB static related by the added features: B
F 6000 cfm
External Static (duct system) C
External Static Pressure: 0.49 in. wg 0.49 wg
G 460 volt/3 phase Power Supply
Rooftop - downflow configuration Standard Filter 1 in. 0.10 wg
H from Table PD - 26 The electric heat accessory capacities
Accessories are listed in Table PD - 27. From the table,
• Roof curb a 36 kw heater will deliver 122.94 MBH
Economizer 0.04 wg
• Economizer at 480 volts. In order to determine
• Electric Heat (100% Return Air) from Table PD-26 capacity at 460 volts, the heater voltage
I correction factor from Table PD - 28 must
Heating be used. Therefore, 122.94 MBH x .94
• Capacity 115 MBh Electric Heater Size 36 kw 0.07 wg (voltage correction factor) = 115.6 MBH.
• 460 volt/3 phase Electric Heat —at 6000 from Table PD - 26
cfm
Air Delivery Selection
Total Static Pressure 0.60 wg
Step 2 External static pressure drop through
As a starting point, a rough the air distribution system has been
determination must be made of the size Note: The Evaporator Fan Performance calculated to be 0.50 inches of water.
of the unit. The final selection will be Table PD - 12 has already accounted for From Table PD - 26 static pressure drop
made after examining the performance the pressure drop for standard filters and through the economizer is 0.04 and the
at the given conditions. Divide the total wet coils (see note belowTable PD - 12). 36 kw heater is 0.07 inches of water
cooling load by nominal BTUH per ton Therefore, the actual total static pressure (0.49 + 0.04 + 0.07). Enter Table PD - 12
(12 MBh per ton); then round up to the is 0.60 -0.10 (from Table PD - 26) = 0.50 for a TCD180B4 at 6000 cfm and 0.50
nearest unit size. wg. static pressure.The standard motor at
With 6000 cfm and 0.50 wg. 777 rpm will give the desired airflow at a
180 MBh / 12 MBh = 15.0 Tons Table PD - 12 shows 2.56 bhp for this rated bhp of 2.71.
unit. Note below the table gives a
Step 3 formula to calculate Fan Motor Heat,
Table PD - 2 shows that a TCD180b4 has 3.15 x bhp = MBH.
a gross cooling capacity of 184 MBh and 3.15 x 2.56 = 8.06 MBH.
130 MBh sensible capacity at 6000 cfm
and 95 DB outdoor ambient with 80 DB, Now subtract the fan motor heat from
67 WB air entering the evaporator. the gross cooling capacity of the unit:
NetTotal Cooling Capacity
= 184 MBH - 8.06 = 175.9 MBH.
Net Sensible Cooling Capacity
= 130 MBH - 8.06 = 121.9 MBH.

RT-PRC002-EN 9
Model
Number
Description

Packaged Cooling with Electric Heat Unit Typical Model Nomenclature

T C D 1 5 0 C 3 0 0 A A
1 2 3 4 5 6 7 8 9 10 11 12

Digits 1, 2 - Product Type Digit 7- Major Development Sequence


TC = Packaged Cooling, Electric
Digit 8 - Electrical Characteristics
Heat
TF = With Factory Installed 3 = 208-230/60/3
Options 4 = 460/60/3
W= 575/60/3
Digit 3 - Airflow Configuration K = 380/60/3

D = Downflow
H = Horizontal Digit 9, 10 - Factory-Installed Options
00 = No Factory-installed Options
Digits 4, 5, 6 - Nominal Gross Cooling 0A = Factory-installed Economizer
Capacity (MBh) 0B = Oversized Motor
0C = Downflow Economizer and
150 = 12½ Tons Standard Efficiency Oversized Motor
151 = 12½ Tons High Efficiency 0F = Trane Communications Interface
180 = 15 Tons Standard Efficiency (TCI)
181 = 15 Tons High Efficiency 0G = Downflow Economizer and TCI
210 = 17½ Tons Standard Efficiency 0H = TXV/Face-Split Evaporator
211 = 17½ Tons High Efficiency 0J = Oversized Motor and TXV/Face-Split
240 = 20 Tons Standard Efficiency Evaporator
241 = 20 Tons High Efficiency 0K = Downflow Economizer, Oversized
300 = 25 Tons Standard Efficiency Motor, and TXV/Face-Split Evaporator
301 = 25 Tons High Efficiency 0L = Downflow Economizer and TXV/Face-
Split Evaporator

Digit 11- Minor Design Sequence

Digit 12- Service Digit

10 RT-PRC002-EN
General (12½, 15 Ton)
Data Standard Efficiency

Table GD - 1— General Data


12½ Ton Downflow and Horizontal Units 15 Ton Downflow and Horizontal Units
TC*150D3, D4, DW, DK TC*180B3, B4, BW, BK
Cooling Performance1
Gross Cooling Capacity 150,000 182,000
EER2 9.8 9.9
Nominal CFM / ARI Rated CFM 5,000/4,400 6,000/5,300
ARI Net Cooling Capacity 142,000 174,000
Integrated Part Load Value3 10.5 10.2
System Power (KW) 14.49 17.57
Compressor
No./Type 2/Climatuff® Scroll 2/Trane 3-D® Scroll/Climatuff® Scroll
Sound Rating (BELS)4 9.2 9.2
Outdoor Coil — Type Hi-Performance Hi-Performance
Tube Size (in.) O.D. .375 .375
Face Area (sq ft) 24.18 27.12
Rows/FPI 2/16 3/16
Indoor Coil — Type Hi-Performance Hi-Performance
Tube Size (in.) .375 .375
Face Area (sq ft) 17.5 17.5
Rows/FPI 2/15 2/15
Refrigerant Control Short Orifice Short Orifice
Drain Connection No./Size (in.) 1/1.00 NPT 1/1.00 NPT
Outdoor Fan — Type Propeller Propeller
No. Used/Diameter (in.) 2/26 2/26
Drive Type/No. Speeds Direct/1 Direct/1
CFM 10,600 10,200
No. Motors/HP 2/.50 2/.50
Motor RPM 1,100 1,100
Indoor Fan — Type FC Centrifugal FC Centrifugal
No. Used 1 1
Diameter x Width (in.) 15 x 15 15 x 15
Drive Type/No. Speeds Belt/1 Belt/1
No. Motors 1 1
Motor HP (Standard/Oversized) 3.0/5.0 3.0/5.0
Motor RPM (Standard/Oversized) 1,740/3,450 1,740/3,450
Motor Frame Size (Standard/Oversized) 145T/145T 145T/145T
Filters — Type Furnished6 Throwaway Throwaway
(No.) Size Recommended (in.)
Downflow (2) 20 x 20 x 2, (4) 20 x 25 x 2 (2) 20 x 20 x 2, (4) 20 x 25 x 2
Horizontal (2) 20 x 20 x 2, (4) 20 x 25 x 2 (2) 20 x 20 x 2, (4) 20 x 25 x 2
Refrigerant Charge (Lbs of R-22)5 9.3/9.4/Circuit 17.5/9.5/Circuit
NOTES:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity
is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment
certification program, which is based on ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb
at ARI rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Optional 2 inch pleated filters are also available.
7. For 380V/60Hz units, the oversized motor is used as the standard motor. Refer to oversized motor data.

*Indicates both downflow and horizontal units.

RT-PRC002-EN 11
General (17½, 20, 25 Ton)
Data Standard Efficiency

Table GD - 2 — General Data


17½ Ton 20 Ton 25 Ton
Downflow and Horizontal Units Downflow and Horizontal Units Downflow and Horizontal Units
TC*210C3, C4, CW, CK TC*240B3, B4, BW, BK TC*300B3, B4, BW, BK
Cooling Performance1
Gross Cooling Capacity 210,000 242,000 290,000
EER2 9.8 9.7 9.7
Nominal CFM / ARI Rated CFM 7,000/5,800 8,000/7,000 10,000/8,750
ARI Net Cooling Capacity 196,000 232,000 272,000
Integrated Part Load Value3 10.0 10.0 9.8
System Power (KW) 20.0 23.91 28.05
Compressor
No./Type 2/Trane 3-D® Scroll/Climatuff® Scroll 2/Trane 3-D®Scroll 2/Trane 3-D Scroll
Sound Rating (BELS)4 9.4 9.4 9.4
Outdoor Coil — Type Hi-Performance Hi-Performance Hi-Performance
Tube Size (in.) O.D. .375 .375 .375
Face Area (sq ft) 27.12 35.30 36.43
Rows/FPI 3/16 3/16 2/16
Indoor Coil — Type Hi-Performance Hi-Performance Hi-Performance
Tube Size (in.) .375 .375 .375
Face Area (sq ft) 17.50 26.00 26.00
Rows/FPI 4/15 2/15 3/15
Refrigerant Control Short Orifice Short Orifice Short Orifice
Drain Connection No./Size (in.) 1/1.00 NPT 1/1.00 NPT 1/1.00 NPT
Outdoor Fan — Type Propeller Propeller Propeller
No. Used/Diameter (in.) 2/26 2/26 2/28
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1
CFM 13,400 14,600 16,700
No. Motors/HP 2/1.0 2/1.0 2/1.0
Motor RPM 1,125 1,125 1,125
Indoor Fan — Type FC Centrifugal FC Centrifugal FC Centrifugal
No. Used 1 1 1
Diameter x Width (in.) 15 x 15 18 x 18 18 x 18
Drive Type/No. Speeds Belt / 1 Belt / 1 Belt / 1
No. Motors 1 1 1
Motor HP (Standard/Oversized) 5.0/7.5 5.0/7.5 7.5/NA
Motor RPM (Standard/Oversized) 3,450/3,470 3,450/3,470 3,470/NA
Motor Frame Size (Standard/Oversized) 145T/184T 145T/184T 184T/NA
Filters — Type Furnished7 Throwaway Throwaway Throwaway
(No.) Size Recommended (in.)
Downflow (2) 20 x 20 x 2, (4) 20 x 25 x 2 (4) 20 x 20 x 2, (4) 20 x 25 x 2 (4) 20 x 20 x 2, (4) 20 x 25 x 2
Horizontal (2) 20 x 20 x 2, (4) 20 x 25 x 2 (8) 20 x 25 x 2 (8) 20 x 25 x 2
Refrigerant Charge (Lbs of R-22)5 21.0/14.3/Circuit6 18.9/21.0/Circuit 17.0/Circuit

NOTES:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is
net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. 17½ - 20 ton models are certified in accordance with the Unitary
Large Equipment certification program, which is based on ARI Standard 340/360-93. 25 ton model ratings shown are tested in accordance with ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb
at ARI rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Refrigerant charge for horizontal models is 21.5/14.5 per circuit.
7. Optional two inch pleated filters are also available.
8. For 380V/60Hz units, the oversized motor is used as the standard motor. Refer to oversized motor data.

*Indicates both downflow and horizontal units.

12 RT-PRC002-EN
General (12½, Ton)
Data High Efficiency

Table GD - 3 — General Data


12½ Ton
Downflow and Horizontal Models
TC*151C3,C4,CW
Cooling Performance1
Gross Cooling Capacity 154,000
EER2 11.3
Nominal CFM / ARI Rated CFM 5,000/4,400
ARI Net Cooling Capacity 146,000
Integrated Part Load Value 3 11.5
System Power KW 12.92
Compressor
No./Type 2/Copeland Scroll
Sound Rating (BELS)4 9.2
Outdoor Coil — Type Hi-Performance
Tube Size (in.) O.D. 0.375
Face Area (sq ft) 27.12
Rows/FPI 3/16
Indoor Coil — Type Hi-Performance
Tube Size (in.) 0.375
Face Area (sq ft) 17.50
Rows/FPI 3/15
Refrigerant Control Short Orifice9
Drain Connection No./Size (in.) 1/1.0 NPT
Outdoor Fan — Type Propeller
No. Used/Diameter (in.) 2/26
Drive Type/No. Speeds Direct/1
CFM 10,400
No. Motors/HP 2/.50
Motor RPM 1100
Indoor Fan — Type FC Centrifugal
No. Used 1
Diameter x Width (in.) 15 x 15
Drive Type/No. Speeds BELT/1
No. Motors 1
Motor HP (Standard/Oversized) 3.0/5.0
Motor RPM
(Standard/Oversized) 1740/3450
Motor Frame Size
(Standard/Oversized) 145T/145T
Filters — Type/Furnished? Throwaway/Yes8
(No.) Size Recommended (in.) (2)20 X 20 X 2/
(4)20 X 25 X 2
Refrigerant Charge (Lbs of R-22) 5/Circuit 15.0/13.89

NOTES:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity
is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment
certification program, which is based on ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb
at ARI rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Face area for Indoor Coil on horizontal models is 12.36.
7. Horizontal models have 4 - 20 x 25 x 2 filters.
8. Optional two inch pleated filters are also available for 12½ ton models.
9. TXV/Face-Split Option (Downflow Only) TCD151C3,4,W (Refrigerant Control): Expansion Valve; (Refrigerant Charge): 13.4/12.0.

*Indicates both downflow and horizontal units.

RT-PRC002-EN 13
General (15, 17½, 20, 25 Ton)
Data High Efficiency

Table GD - 4 — General Data


15 Ton 17½ Ton 20 Ton 25 Ton
Downflow and Horizontal Models
TC*181C3,C4,CW TC*211C3,C4,CW TC*241C3,C4,CW TC*301C3,C4,CW
Cooling Performance1
9
Gross Cooling Capacity 189,000 220,000 268,000 300,00011
EER2 11.58 11.0 10.6 10.411
Nominal CFM / ARI Rated CFM 6,000/5,300 7,000/6,200 8,000/7,000 10,000/8,750
ARI Net Cooling Capacity 180,000 208,000 250,0009 278,000
Integrated Part Load Value3 13.3 12.0 11.2 11.011
System Power KW 15.658 18.91 23.589 26.7311
Compressor
No./Type Trane 3-D®Scroll/Climatuff® Scroll 2/Trane3-D Scroll/Copeland Scroll 2/Trane 3-D Scroll/Copeland Scroll 2/Trane 3-D Scroll
Sound Rating (BELS)4 9.2 9.4 9.4 9.4
Outdoor Coil — Type Hi-Performance Hi-Performance Hi-Performance Hi-Performance
Tube Size (in.) O.D. 0.375 0 .375 0.375 0.375
Face Area (sq ft) 35.30 35.30 35.30 35.30
Rows/FPI 3/16 3/16 3/16 3/16
Indoor Coil — Type Hi-Performance Hi-Performance Hi-Performance Hi-Performance
Tube Size (in.) 0.375 0.375 0.375 0.375
Face Area (sq ft) 26.00 26.000 26.00 26.00
Rows/FPI 3/15 4/15 4/15 4/15
Refrigerant Control Short Orifice8 Short Orifice Short Orifice9 Short Orifice11
Drain Connection No./Size (in.) 1/1.0 NPT 1 /1.0 NPT 1/1.0 NPT 1/1.0 NPT
Outdoor Fan — Type Propeller Propeller Propeller Propeller
No. Used/Diameter (in.) 2/26 2/26 2/26 2/26
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1
CFM 11,000 12,800 13,700 13,700
No. Motors/HP 2/.50 2/1.00 2/1.00 2/1.00
Motor RPM 1100 1125 1125 1125
Indoor Fan — Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
No. Used 1 1 1 1
Diameter x Width (in.) 18 x 18 18 x 18 18 x 18 18 x 18
Drive Type/No. Speeds BELT/1 BELT/1 BELT/1 BELT/1
No. Motors 1 1 1 1
Motor HP (Standard/Oversized) 3.0/5.0 5.0/7.5 5.0/7.5 7.5/NA
Motor RPM
(Standard/Oversized) 1740/3450 3450/3470 3450/3470 3470/NA
Motor Frame Size
(Standard/Oversized) 145T/145T 145T/184T 145T/184T 184T/NA
Filters — Type Furnished7 Throwaway Throwaway Throwaway Throwaway
(No.) Size Recommended (in.) (4/4)20 X 20 X 2/20 X 25 X 26 (4/4)20 X 20 X 2/20 X 25 X 26 (4/4)20 X 20 X 2/20 X 25 X 26 (4/4)20X20X2/20X25X26
Refrigerant Charge (Lbs of R-22) 5 / Circuit 25/138 25.7/12.510 21.8/21.89 24.5/24.511

NOTES:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is
net and includes the effect of fan motor heat. 15 - 20 ton models are certified in accordance with the Unitary Large Equipment certification program, which is based on
ARI Standard 340/360-93. 25 ton model ratings shown are tested in accordance with ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb
at ARI rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Horizontal models have 8 - 20 x 25 x 2 filters.
7. Optional two inch pleated filters are also available.
8. TXV/Face-Split Option (Downflow Only) TCD181C3,4,W (EER):11.4; (System Power kW): 15.79; (Refrigerant Control): Expansion Valve; (Refrigerant Charge): 26.0/12.0
9. TXV/Face-Split Option (Downflow Only) TCD241C3,4,W (Gross Cooling Capacity):259,000; (ARI Net Cooling Capacity): 244,000; (System Power kW): 23.02;
(Refrigerant Control): Expansion Valve; (Refrigerant Charge): 21.5/22.2
10. TXV/Face-Split Option (Downflow Only) TCD211C3,4,W Refrigerant Charge): 27.0/10.0
11. TXV/Face-Split Option (Downflow Only) TCD301C3,4,W (EER): 10; (Gross Cooling Capacity): 294,000; (ARI Net Cooling Capacity): 272,000; (IPLV): 10.6; System Power kW):
27.2; Refrigerant Control: Expansion Valve; (Refrigerant Charge): 21.0/23.0

*Indicates both downflow and horizontal units.

14 RT-PRC002-EN
Performance (12½, 15 Ton)
Data Standard Efficiency

Table PD-1 — Gross Cooling Capacities (MBH) 12½ Ton Three Phase TC*150D3, D4, DW, DK
Ambient Temperature
85 95 105 115
Enter
Dry Entering Wet Bulb
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 135.0 108.0 153.0 86.0 162.0 59.3 126.0 103.0 146.0 82.0 158.0 56.7 116.0 98.2 138.0 77.7 152.0 53.8 106.0 93.1 127.0 80.0 145.0 50.5
4500 80 136.0 128.0 154.0 105.0 163.0 79.5 127.0 123.0 147.0 101.0 159.0 76.5 117.0 117.0 138.0 97.0 153.0 73.2 110.0 110.0 128.0 92.2 145.0 69.6
85 142.0 142.0 154.0 123.0 164.0 95.9 135.0 135.0 147.0 120.0 159.0 94.2 127.0 127.0 138.0 116.0 153.0 91.7 120.0 120.0 128.0 111.0 146.0 88.5
90 150.0 150.0 155.0 142.0 166.0 112.0 144.0 144.0 148.0 139.0 161.0 111.0 137.0 137.0 139.0 136.0 154.0 109.0 130.0 130.0 130.0 130.0 146.0 107.0
75 139.0 114.0 155.0 89.8 163.0 60.4 129.0 109.0 149.0 85.4 159.0 57.9 120.0 104.0 141.0 89.5 154.0 55.0 109.0 98.9 131.0 85.1 147.0 51.6
5000 80 140.0 136.0 156.0 109.0 164.0 81.3 130.0 130.0 149.0 106.0 160.0 79.1 123.0 123.0 141.0 102.0 155.0 75.8 115.0 115.0 131.0 97.5 147.0 72.2
85 147.0 147.0 157.0 129.0 166.0 98.2 141.0 141.0 150.0 126.0 161.0 96.8 133.0 133.0 141.0 123.0 155.0 94.8 125.0 125.0 131.0 118.0 148.0 91.9
90 155.0 155.0 158.0 148.0 167.0 115.0 149.0 149.0 151.0 147.0 163.0 115.0 143.0 143.0 143.0 143.0 157.0 114.0 135.0 135.0 135.0 135.0 149.0 111.0
75 142.0 120.0 157.0 91.3 164.0 61.5 132.0 115.0 151.0 88.8 160.0 59.0 122.0 110.0 143.0 84.2 155.0 56.1 112.0 104.0 133.0 89.9 148.0 52.9
5500 80 143.0 143.0 158.0 112.0 165.0 82.0 135.0 135.0 152.0 110.0 161.0 80.4 127.0 127.0 143.0 107.0 156.0 78.3 119.0 119.0 134.0 102.0 149.0 74.7
85 152.0 152.0 159.0 133.0 167.0 99.9 145.0 145.0 152.0 132.0 163.0 99.1 138.0 138.0 144.0 129.0 157.0 97.4 130.0 130.0 134.0 125.0 150.0 95.0
90 159.0 159.0 160.0 154.0 169.0 118.0 153.0 153.0 153.0 153.0 164.0 118.0 147.0 147.0 147.0 147.0 158.0 117.0 140.0 140.0 140.0 140.0 151.0 116.0
75 145.0 125.0 158.0 93.3 165.0 62.5 135.0 120.0 153.0 91.2 161.0 60.1 125.0 115.0 145.0 87.3 156.0 57.2 115.0 110.0 136.0 82.8 149.0 54.0
6000 80 147.0 147.0 159.0 115.0 166.0 82.9 140.0 140.0 153.0 114.0 162.0 81.7 132.0 132.0 145.0 111.0 157.0 79.3 123.0 123.0 136.0 107.0 150.0 76.5
85 155.0 155.0 161.0 137.0 168.0 101.1 149.0 149.0 154.0 137.0 164.0 101.0 142.0 142.0 146.0 135.0 158.0 99.8 134.0 134.0 137.0 131.0 151.0 97.8
90 161.0 161.0 162.0 159.0 170.0 120.0 156.0 156.0 156.0 156.0 166.0 121.0 150.0 150.0 150.0 150.0 160.0 121.0 143.0 143.0 143.0 143.0 152.0 119.0
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity

Table PD-2 — Gross Cooling Capacities (MBH) 15 Ton Three Phase TC*180B3, B4, BW, BK
Ambient Temperature
85 95 105 115
Enter.
Dry Entering Wet Bulb
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 168.0 133.0 188.0 106.0 198.0 73.0 157.0 128.0 181.0 101.0 194.0 70.4 147.0 122.0 172.0 97.0 187.0 67.3 137.0 117.0 162.0 92.1 179.0 63.2
5400 80 168.0 156.0 188.0 128.0 199.0 97.3 155.0 155.0 181.0 125.0 195.0 94.3 149.0 143.0 172.0 120.0 188.0 90.8 140.0 137.0 162.0 115.0 179.0 86.7
85 174.0 174.0 189.0 150.0 200.0 117.0 166.0 166.0 182.0 147.0 196.0 115.0 158.0 158.0 172.0 143.0 189.0 113.0 150.0 150.0 162.0 138.0 180.0 110.0
90 184.0 184.0 190.0 172.0 202.0 136.0 177.0 177.0 183.0 170.0 197.0 135.0 170.0 170.0 170.0 170.0 190.0 133.0 162.0 162.0 165.0 157.0 181.0 131.0
75 172.0 140.0 190.0 110.0 199.0 74.3 161.0 134.0 184.0 106.0 195.0 71.7 151.0 129.0 175.0 101.0 189.0 68.7 140.0 124.0 165.0 96.1 181.0 64.9
6000 80 169.0 169.0 191.0 133.0 200.0 99.4 164.0 157.0 184.0 130.0 196.0 97.2 155.0 151.0 176.0 126.0 190.0 93.8 145.0 145.0 165.0 121.0 182.0 89.9
85 181.0 181.0 192.0 156.0 202.0 119.0 173.0 173.0 185.0 154.0 198.0 118.0 165.0 165.0 176.0 151.0 191.0 116.0 157.0 157.0 166.0 146.0 183.0 113.0
90 189.0 189.0 193.0 179.0 204.0 140.0 183.0 183.0 183.0 183.0 199.0 139.0 176.0 176.0 178.0 171.0 193.0 138.0 168.0 168.0 170.0 166.0 184.0 136.0
75 176.0 147.0 192.0 112.0 200.0 75.5 165.0 141.0 186.0 110.0 196.0 73.0 154.0 136.0 178.0 105.0 190.0 69.8 144.0 130.0 168.0 99.8 182.0 66.1
6600 80 178.0 171.0 193.0 136.0 201.0 101.0 169.0 165.0 187.0 135.0 197.0 98.8 160.0 159.0 178.0 131.0 191.0 96.1 150.0 150.0 168.0 127.0 183.0 92.6
85 185.0 185.0 194.0 161.0 203.0 122.0 179.0 179.0 188.0 160.0 199.0 121.0 171.0 171.0 179.0 158.0 193.0 119.0 163.0 163.0 169.0 153.0 185.0 116.0
90 193.0 193.0 193.0 193.0 205.0 143.0 188.0 188.0 188.0 188.0 201.0 143.0 181.0 181.0 182.0 178.0 195.0 142.0 173.0 173.0 174.0 174.0 186.0 140.0
75 179.0 152.0 194.0 114.0 201.0 76.7 168.0 147.0 188.0 112.0 197.0 74.2 158.0 142.0 180.0 109.0 191.0 71.0 142.0 142.0 170.0 103.0 183.0 67.2
7200 80 182.0 177.0 195.0 140.0 202.0 103.0 173.0 172.0 189.0 139.0 198.0 100.0 164.0 164.0 181.0 136.0 192.0 97.6 155.0 155.0 171.0 132.0 184.0 94.4
85 189.0 189.0 196.0 166.0 204.0 125.0 183.0 183.0 190.0 166.0 200.0 123.0 176.0 176.0 182.0 164.0 194.0 121.0 167.0 167.0 167.0 167.0 186.0 119.0
90 197.0 197.0 197.0 197.0 206.0 146.0 192.0 192.0 193.0 187.0 202.0 146.0 185.0 185.0 186.0 184.0 196.0 146.0 177.0 177.0 177.0 177.0 188.0 144.0
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

*Indicates both downflow and horizontal units.

RT-PRC002-EN 15
Performance (17½, 20 Ton)
Data Standard Efficiency

Table PD-3 — Gross Cooling Capacities (MBH) 17½ Ton Three Phase TC*210C3, C4, CW, CK
Ambient Temperature
85 95 105 115
Enter
Dry Entering Wet Bulb
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 195.0 171.0 213.0 127.0 224.0 83.3 182.0 164.0 206.0 124.0 219.0 80.1 169.0 158.0 195.0 119.0 213.0 76.1 155.0 151.0 181.0 113.0 204.0 71.8
6300 80 200.0 200.0 214.0 157.0 226.0 114.0 191.0 191.0 207.0 156.0 221.0 112.0 180.0 180.0 196.0 153.0 214.0 110.0 168.0 168.0 183.0 147.0 205.0 106.0
85 211.0 211.0 217.0 188.0 229.0 140.0 204.0 204.0 209.0 188.0 223.0 139.0 195.0 195.0 199.0 186.0 216.0 139.0 184.0 184.0 187.0 182.0 206.0 137.0
90 219.0 219.0 220.0 217.0 230.0 164.0 214.0 214.0 214.0 214.0 225.0 167.0 207.0 207.0 207.0 207.0 218.0 169.0 198.0 198.0 198.0 198.0 208.0 168.0
75 199.0 181.0 215.0 131.0 225.0 84.7 187.0 176.0 208.0 129.0 221.0 81.4 174.0 169.0 198.0 125.0 215.0 77.7 160.0 160.0 185.0 119.0 206.0 73.4
7000 80 206.0 206.0 217.0 164.0 228.0 116.0 198.0 198.0 210.0 164.0 222.0 114.0 188.0 188.0 200.0 162.0 216.0 113.0 176.0 176.0 187.0 157.0 207.0 110.0
85 216.0 216.0 220.0 197.0 230.0 144.0 210.0 210.0 213.0 198.0 225.0 144.0 202.0 202.0 204.0 198.0 218.0 145.0 192.0 192.0 192.0 192.0 209.0 144.0
90 224.0 224.0 224.0 224.0 233.0 172.0 219.0 219.0 219.0 219.0 227.0 173.0 212.0 212.0 212.0 212.0 221.0 177.0 204.0 204.0 204.0 204.0 211.0 177.0
75 203.0 191.0 217.0 135.0 226.0 86.1 192.0 187.0 211.0 138.0 222.0 82.9 178.0 178.0 201.0 131.0 216.0 79.2 165.0 165.0 188.0 126.0 208.0 75.0
7700 80 211.0 211.0 219.0 169.0 229.0 118.0 204.0 204.0 212.0 171.0 224.0 117.0 194.0 194.0 203.0 170.0 218.0 116.0 183.0 183.0 191.0 167.0 209.0 114.0
85 220.0 220.0 222.0 203.0 232.0 147.0 214.0 214.0 216.0 207.0 226.0 148.0 207.0 207.0 207.0 207.0 220.0 150.0 197.0 197.0 197.0 197.0 211.0 150.0
90 226.0 226.0 226.0 226.0 235.0 176.0 223.0 223.0 222.0 222.0 229.0 179.0 216.0 216.0 216.0 216.0 223.0 184.0 208.0 208.0 208.0 208.0 214.0 186.0
75 206.0 199.0 218.0 138.0 227.0 87.8 195.0 195.0 212.0 143.0 223.0 84.3 183.0 183.0 203.0 136.0 217.0 80.6 171.0 171.0 190.0 132.0 209.0 76.5
8400 80 214.0 214.0 221.0 174.0 230.0 120.0 208.0 208.0 214.0 178.0 226.0 120.0 199.0 199.0 205.0 178.0 219.0 119.0 188.0 188.0 194.0 176.0 211.0 117.0
85 222.0 222.0 224.0 210.0 233.0 150.0 217.0 217.0 218.0 215.0 228.0 151.0 211.0 211.0 211.0 211.0 222.0 155.0 202.0 202.0 202.0 202.0 213.0 156.0
90 229.0 229.0 229.0 229.0 236.0 181.0 225.0 225.0 225.0 225.0 231.0 184.0 220.0 220.0 219.0 219.0 225.0 190.0 212.0 212.0 212.0 212.0 216.0 193.0
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity

Table PD-4 — Gross Cooling Capacities (MBH) 20 Ton Three Phase TC*240B3, B4, BW, BK
Ambient Temperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 223.0 180.0 251.0 143.0 265.0 97.7 209.0 173.0 242.0 137.0 260.0 94.3 195.0 165.0 228.0 130.0 252.0 90.3 180.0 158.0 212.0 135.0 241.0 85.5
7200 80 226.0 214.0 252.0 173.0 267.0 131.0 208.0 208.0 242.0 169.0 261.0 127.0 197.0 197.0 228.0 162.0 253.0 122.0 186.0 186.0 213.0 155.0 242.0 117.0
85 235.0 235.0 253.0 204.0 268.0 158.0 224.0 224.0 242.0 200.0 262.0 156.0 213.0 213.0 229.0 194.0 253.0 153.0 201.0 201.0 214.0 188.0 242.0 149.0
90 248.0 248.0 255.0 234.0 271.0 185.0 239.0 239.0 245.0 232.0 264.0 185.0 228.0 228.0 228.0 228.0 255.0 183.0 217.0 217.0 217.0 217.0 243.0 179.0
75 229.0 190.0 255.0 148.0 267.0 99.4 215.0 183.0 246.0 142.0 262.0 96.1 200.0 175.0 233.0 136.0 254.0 92.2 185.0 168.0 218.0 129.0 244.0 87.1
8000 80 228.0 228.0 256.0 180.0 268.0 134.0 217.0 217.0 246.0 176.0 264.0 131.0 205.0 205.0 233.0 171.0 255.0 127.0 193.0 193.0 218.0 164.0 245.0 121.0
85 243.0 243.0 257.0 212.0 271.0 162.0 233.0 233.0 247.0 210.0 265.0 161.0 222.0 222.0 234.0 206.0 257.0 158.0 210.0 210.0 220.0 199.0 245.0 155.0
90 255.0 255.0 259.0 245.0 273.0 190.0 247.0 247.0 247.0 247.0 267.0 191.0 237.0 237.0 237.0 237.0 258.0 190.0 226.0 226.0 226.0 226.0 247.0 187.0
75 234.0 199.0 257.0 151.0 268.0 101.0 220.0 192.0 249.0 147.0 263.0 97.9 205.0 184.0 237.0 141.0 256.0 93.7 190.0 177.0 222.0 134.0 246.0 88.6
8800 80 236.0 236.0 259.0 185.0 270.0 136.0 224.0 224.0 249.0 183.0 265.0 134.0 212.0 212.0 237.0 178.0 257.0 130.0 200.0 200.0 222.0 172.0 247.0 126.0
85 250.0 250.0 260.0 220.0 273.0 165.0 240.0 240.0 251.0 219.0 267.0 165.0 229.0 229.0 239.0 216.0 259.0 163.0 217.0 217.0 225.0 210.0 248.0 160.0
90 260.0 260.0 263.0 254.0 275.0 194.0 253.0 253.0 253.0 253.0 270.0 196.0 244.0 244.0 244.0 244.0 261.0 196.0 233.0 233.0 233.0 233.0 250.0 194.0
75 238.0 208.0 259.0 154.0 269.0 103.0 224.0 201.0 251.0 151.0 265.0 99.6 209.0 193.0 240.0 146.0 257.0 95.1 194.0 186.0 225.0 139.0 248.0 89.2
9600 80 242.0 242.0 261.0 190.0 271.0 137.0 231.0 231.0 252.0 189.0 266.0 136.0 219.0 219.0 240.0 185.0 259.0 133.0 206.0 206.0 226.0 180.0 249.0 129.0
85 254.0 254.0 263.0 227.0 274.0 167.0 246.0 246.0 254.0 227.0 269.0 168.0 236.0 236.0 243.0 225.0 261.0 167.0 224.0 224.0 229.0 220.0 251.0 165.0
90 264.0 264.0 264.0 264.0 277.0 198.0 258.0 258.0 258.0 258.0 272.0 201.0 249.0 249.0 249.0 249.0 263.0 202.0 239.0 239.0 239.0 239.0 252.0 201.0
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

*Indicates both downflow and horizontal units.

16 RT-PRC002-EN
Performance (25 Ton)
Data Standard Efficiency

Table PD-5— Gross Cooling Capacities (MBH) 25 Ton Three Phase TC*300B3, B4, BW, BK
Ambient Temperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 266 224 299 174 319 118 247 215 285 167 309 113 228 205 266 172 297 108 209 196 244 163 280 99.9
80 270 268 300 215 321 161 252 252 285 209 311 155 237 237 266 200 297 149 221 221 244 190 280 142
9000 85 286 286 301 255 323 196 272 272 286 250 312 194 256 256 267 242 298 189 240 240 246 233 281 183
90 301 301 304 295 326 232 289 289 289 289 314 231 275 275 275 275 300 229 259 259 259 259 282 224
75 272 237 303 180 322 120 253 227 290 174 312 115 234 218 271 165 300 109 214 208 249 156 284 102
80 277 277 304 223 324 171 262 262 290 219 314 161 246 246 271 211 301 155 229 229 249 201 284 147
10000 85 294 294 306 266 327 208 282 282 291 263 316 200 266 266 273 257 302 197 249 249 253 248 285 192
90 308 308 310 309 329 239 297 297 297 297 318 240 284 284 284 284 304 239 268 268 268 268 286 235
75 275 243 305 183 323 122 256 233 291 177 314 117 236 223 273 188 301 111 216 214 251 178 285 103
80 282 282 306 227 325 174 267 267 292 223 315 162 250 250 273 216 302 157 233 233 251 206 286 150
10500 85 298 298 308 272 328 216 286 286 294 270 317 203 270 270 276 264 304 200 253 253 256 255 286 196
90 312 312 311 311 330 256 301 301 301 301 320 244 288 288 288 288 306 244 273 273 272 272 288 241
75 278 248 306 185 324 123 258 239 293 181 315 118 239 229 275 172 302 113 217 217 253 184 286 104
80 286 286 308 231 325 160 271 271 294 228 316 163 254 254 276 221 304 160 237 237 253 212 287 153
11000 85 301 301 310 277 327 224 289 289 296 276 319 205 274 274 278 271 305 204 257 257 257 257 288 200
90 314 314 314 314 330 266 304 304 304 304 321 248 291 291 291 291 307 249 276 276 276 276 289 246
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
4. Table is for 460 volt capacity. For capacity at 230 volt, multiply table capacity by 101%.

RT-PRC002-EN 17
Performance (12½ Ton)
Data High Efficiency

Table PD-6 — Gross Cooling Capacities (MBH) 12½ Ton Three Phase TC*151C3, C4, CW
Ambient Temperature
85 95 105 115
Enter
Dry Entering Wet Bulb
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 137.0 116.0 157.0 90.2 166.0 60.8 127.0 110.0 151.0 87.1 163.0 58.5 116.0 105.0 140.0 82.3 158.0 55.8 106.0 99.7 128.0 80.6 152.0 52.8
4500 80 140.0 139.0 158.0 111.0 167.0 82.9 130.0 130.0 151.0 109.0 164.0 80.8 122.0 122.0 141.0 104.0 159.0 77.8 114.0 114.0 128.0 98.5 152.0 74.6
85 149.0 149.0 158.0 132.0 169.0 100.0 142.0 142.0 151.0 131.0 165.0 99.4 133.0 133.0 141.0 126.0 159.0 98.2 125.0 125.0 130.0 121.0 152.0 96.0
90 158.0 158.0 160.0 153.0 170.0 118.0 152.0 152.0 154.0 152.0 166.0 118.0 145.0 145.0 145.0 145.0 160.0 118.0 137.0 137.0 137.0 137.0 153.0 117.0
75 141.0 123.0 159.0 93.4 167.0 61.6 131.0 117.0 154.0 90.9 164.0 59.4 120.0 112.0 144.0 86.6 159.0 56.8 109.0 107.0 132.0 81.0 153.0 53.7
5000 80 145.0 145.0 160.0 116.0 168.0 84.1 136.0 136.0 154.0 114.0 165.0 82.4 128.0 128.0 144.0 110.0 161.0 80.9 119.0 119.0 132.0 105.0 154.0 77.5
85 155.0 155.0 161.0 138.0 170.0 103.0 148.0 148.0 155.0 138.0 166.0 102.0 140.0 140.0 145.0 135.0 161.0 102.0 131.0 131.0 134.0 129.0 154.0 100.0
90 162.0 162.0 163.0 160.0 172.0 121.0 157.0 157.0 157.0 157.0 168.0 122.0 151.0 151.0 151.0 151.0 163.0 123.0 143.0 143.0 143.0 143.0 155.0 122.0
75 145.0 129.0 161.0 95.8 168.0 62.6 134.0 124.0 156.0 94.4 165.0 60.4 123.0 119.0 147.0 90.4 161.0 57.8 112.0 112.0 135.0 85.1 154.0 54.6
5500 80 150.0 150.0 162.0 119.0 169.0 85.2 142.0 142.0 156.0 119.0 167.0 84.0 133.0 133.0 147.0 116.0 162.0 82.4 124.0 124.0 135.0 111.0 155.0 80.1
85 158.0 158.0 163.0 143.0 172.0 104.0 153.0 153.0 157.0 144.0 168.0 104.0 146.0 146.0 149.0 143.0 163.0 105.0 137.0 137.0 137.0 137.0 156.0 104.0
90 165.0 165.0 165.0 165.0 173.0 123.0 161.0 161.0 161.0 161.0 170.0 126.0 156.0 156.0 156.0 156.0 164.0 127.0 149.0 149.0 149.0 149.0 157.0 127.0
75 148.0 136.0 162.0 97.9 168.0 63.5 137.0 131.0 157.0 97.1 166.0 61.4 126.0 125.0 150.0 94.3 162.0 58.9 116.0 116.0 138.0 89.0 155.0 55.6
6000 80 154.0 154.0 163.0 123.0 170.0 86.2 147.0 147.0 158.0 124.0 168.0 85.8 138.0 138.0 150.0 122.0 162.0 83.3 128.0 128.0 138.0 117.0 156.0 82.2
85 161.0 161.0 165.0 147.0 172.0 106.0 157.0 157.0 160.0 150.0 169.0 106.0 151.0 151.0 152.0 150.0 164.0 107.0 142.0 142.0 142.0 142.0 158.0 107.0
90 167.0 167.0 167.0 167.0 174.0 126.0 164.0 164.0 164.0 164.0 171.0 128.0 159.0 159.0 159.0 159.0 166.0 131.0 153.0 153.0 153.0 153.0 159.0 132.0
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity

*Indicates both downflow and horizontal units.

18 RT-PRC002-EN
Performance (15, 17½ Ton)
Data High Efficiency

Table PD-7 — Gross Cooling Capacities (MBH) 15 Ton Three Phase TC*181C3, C4, CW
Ambient Temperature
85 95 105 115
Enter.
Dry Entering Wet Bulb
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 172 144 194 112 205 75.2 159 138 185 107 200 71.9 147 131 172 101 193 68 130 130 158 97 183 63.4
5400 80 175 169 195 138 207 103 164 162 186 134 202 99.7 153 153 173 128 194 95.4 142 142 158 122 183 90.5
85 185 185 196 164 209 126 176 176 186 161 203 124 165 165 174 156 195 122 155 155 155 155 184 117
90 195 195 195 195 211 149 188 188 190 184 204 148 178 178 179 179 196 147 168 168 167 167 184 144
75 177 153 197 116 207 76 164 147 189 112 202 73.2 151 140 176 106 195 69.3 138 131 162 99.8 185 64.8
6000 80 181 180 198 144 209 105 170 170 189 142 204 103 159 159 177 136 196 99.4 148 148 162 130 186 94.6
85 192 192 199 172 211 129 183 183 190 171 206 129 173 173 173 173 197 127 162 162 162 162 186 124
90 201 201 200 200 214 153 194 194 195 194 208 155 185 185 185 185 199 154 175 175 175 175 187 152
75 181 162 198 123 208 76.6 168 155 191 117 204 74.4 152 152 180 111 197 70.6 142 139 165 105 187 66.2
6600 80 186 186 200 151 210 107 177 177 192 148 206 105 166 166 180 144 198 102 154 154 166 137 188 98.6
85 197 197 202 179 213 131 189 189 194 180 208 132 179 179 183 173 199 132 168 168 170 166 189 129
90 204 204 205 202 215 157 199 199 199 199 209 159 191 191 191 191 201 160 181 181 181 181 190 160
75 184 170 200 127 209 79.1 168 168 193 121 206 76.4 156 156 182 116 198 71.9 145 145 168 110 189 67.4
7200 80 191 191 202 153 211 108 182 182 194 154 207 107 171 171 183 151 199 105 159 159 169 145 190 102
85 200 200 204 185 214 134 194 194 194 194 209 136 185 185 187 181 201 135 174 174 174 174 191 134
90 207 207 208 207 217 160 203 203 203 203 211 163 195 195 195 195 203 166 186 186 186 186 192 167
NOTES:
1 All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table PD-8 — Gross Cooling Capacities (MBH)17½ Ton Three Phase TC*211C3, C4, CW
Ambient Temperature
85 95 105 115
Enter
Dry Entering Wet Bulb
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 200.0 169.0 224.0 130.0 233.0 86.2 184.0 162.0 215.0 125.0 231.0 83.3 169.0 154.0 199.0 118.0 226.0 79.3 147.0 147.0 180.0 113.0 214.0 74.2
6300 80 202.0 202.0 225.0 161.0 236.0 118.0 190.0 190.0 216.0 158.0 234.0 117.0 177.0 177.0 200.0 151.0 227.0 112.0 164.0 164.0 181.0 142.0 214.0 107.0
85 216.0 216.0 227.0 191.0 239.0 143.0 206.0 206.0 217.0 190.0 236.0 146.0 193.0 193.0 202.0 184.0 228.0 144.0 180.0 180.0 185.0 176.0 215.0 139.0
90 227.0 227.0 230.0 221.0 242.0 169.0 220.0 220.0 220.0 220.0 239.0 175.0 209.0 209.0 209.0 209.0 229.0 174.0 196.0 196.0 195.0 195.0 217.0 171.0
75 205.0 180.0 226.0 134.0 234.0 87.6 190.0 172.0 219.0 131.0 233.0 84.8 174.0 164.0 204.0 124.0 228.0 80.8 155.0 155.0 184.0 116.0 218.0 76.0
7000 80 210.0 210.0 228.0 167.0 237.0 119.0 198.0 198.0 220.0 167.0 236.0 120.0 185.0 185.0 205.0 160.0 229.0 117.0 171.0 171.0 186.0 152.0 218.0 112.0
85 223.0 223.0 230.0 199.0 241.0 145.0 215.0 215.0 222.0 202.0 238.0 150.0 202.0 202.0 209.0 197.0 231.0 150.0 188.0 188.0 191.0 189.0 219.0 147.0
90 232.0 232.0 233.0 230.0 244.0 173.0 227.0 227.0 227.0 227.0 241.0 180.0 218.0 218.0 218.0 218.0 232.0 182.0 205.0 205.0 204.0 204.0 221.0 181.0
75 210.0 190.0 228.0 138.0 235.0 88.9 195.0 183.0 222.0 137.0 234.0 86.0 179.0 175.0 208.0 130.0 229.0 82.4 161.0 161.0 188.0 122.0 220.0 77.7
7700 80 217.0 217.0 231.0 173.0 239.0 120.0 206.0 206.0 223.0 174.0 237.0 121.0 192.0 192.0 209.0 169.0 231.0 121.0 178.0 178.0 190.0 161.0 221.0 116.0
85 228.0 228.0 232.0 206.0 242.0 148.0 221.0 221.0 226.0 211.0 240.0 153.0 210.0 210.0 214.0 209.0 234.0 156.0 196.0 196.0 195.0 195.0 222.0 154.0
90 235.0 235.0 235.0 235.0 245.0 176.0 232.0 232.0 232.0 232.0 243.0 185.0 224.0 224.0 224.0 224.0 235.0 189.0 213.0 213.0 212.0 212.0 224.0 191.0
75 214.0 200.0 230.0 141.0 236.0 90.3 200.0 193.0 224.0 141.0 235.0 87.4 181.0 181.0 211.0 136.0 230.0 83.8 166.0 166.0 191.0 128.0 222.0 79.2
8400 80 222.0 222.0 232.0 177.0 239.0 133.0 213.0 213.0 226.0 181.0 238.0 123.0 199.0 199.0 213.0 178.0 233.0 124.0 184.0 184.0 194.0 170.0 223.0 121.0
85 231.0 231.0 234.0 211.0 243.0 149.0 226.0 226.0 229.0 220.0 241.0 155.0 216.0 216.0 216.0 216.0 235.0 161.0 203.0 203.0 202.0 202.0 224.0 162.0
90 238.0 238.0 238.0 238.0 246.0 178.0 235.0 235.0 235.0 235.0 244.0 189.0 229.0 229.0 229.0 229.0 237.0 195.0 219.0 219.0 219.0 219.0 227.0 199.0
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity

*Indicates both downflow and horizontal units.

RT-PRC002-EN 19
Performance (20, 25 Ton)
Data High Efficiency

Table PD-9 — Gross Cooling Capacities (MBH) 20 Ton Three Phase TC*241C3, C4, CW
Ambient Temperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 246 205 273 158 284 105 228 196 263 152 280 101 208 186 246 145 273 96.5 191 176 222 136 261 91.5
7200 80 250 245 274 192 287 142 232 232 264 190 283 141 216 216 246 183 274 135 201 201 223 172 261 130
85 263 263 275 227 290 171 251 251 265 228 285 173 236 236 248 221 275 170 219 219 225 211 262 168
90 274 274 278 262 293 201 266 266 268 265 288 206 254 254 254 254 277 205 239 239 237 237 262 205
75 253 218 275 163 285 107 234 209 267 159 282 103 214 199 252 152 275 98.3 194 189 228 142 266 93.6
8000 80 257 257 277 199 289 144 243 243 268 199 285 143 227 227 252 194 277 140 210 210 228 184 266 136
85 270 270 279 236 292 174 261 261 270 240 288 177 247 247 255 237 278 177 230 230 232 226 266 177
90 280 280 282 273 295 205 274 274 274 274 291 212 264 264 264 264 280 214 250 250 248 248 267 218
75 258 230 278 167 287 109 240 221 270 164 284 105 219 211 256 159 277 100 199 199 232 149 269 95.5
8800 80 264 264 280 204 290 155 252 252 271 208 287 145 236 236 257 205 279 144 218 218 233 195 269 141
85 276 276 282 244 293 177 268 268 274 250 290 181 256 256 260 251 281 182 240 240 238 238 269 185
90 285 285 286 281 297 209 280 280 280 280 293 217 271 271 271 271 283 221 258 258 258 258 271 229
75 262 240 280 169 288 110 246 233 273 169 285 106 225 223 260 166 278 102 205 205 236 156 271 97.1
9600 80 270 270 282 209 291 161 260 260 274 215 288 147 245 245 261 215 281 147 226 226 237 205 271 146
85 280 280 284 250 295 179 274 274 277 260 291 184 263 263 265 263 282 186 248 248 246 246 272 193
90 288 288 288 288 298 212 284 284 284 284 294 222 276 276 276 276 285 228 264 264 265 265 275 240
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table PD-10 — Gross Cooling Capacities (MBH)25 Ton Three PhaseTC*301C3, C4, CW
Ambient Temperature (F)
85 95 105 115
Enter.
Dry Entering Wet Bulb (F)
CFM Bulb 61 67 73 61 67 73 61 67 73 61 67 73
Airflow (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 277 243 306 187 316 117 258 234 295 178 314 115 238 224 276 169 305 110 218 214 253 163 292 104
9000 80 284 284 307 225 321 169 269 269 295 225 317 161 252 252 277 217 307 158 235 235 254 207 293 151
85 300 300 309 269 325 198 289 289 298 271 320 202 273 273 280 266 308 201 256 256 259 256 293 198
90 312 312 313 312 329 236 305 305 305 305 321 240 293 293 293 293 310 245 277 277 277 277 295 244
75 284 258 310 188 319 121 264 249 299 185 316 117 244 239 282 178 308 112 224 224 259 168 295 106
10000 80 294 294 310 233 323 175 280 280 300 236 319 170 263 263 283 230 309 163 245 245 260 221 296 158
85 307 307 313 280 327 202 298 298 303 286 322 207 284 284 287 284 312 208 267 267 267 267 297 208
90 318 318 318 318 331 241 312 312 312 312 324 248 301 301 301 301 314 255 287 287 287 287 299 257
75 286 265 311 190 320 122 267 256 300 189 316 118 247 246 284 182 309 113 228 228 261 172 296 107
10500 80 297 297 312 237 324 178 285 285 302 241 320 174 267 267 285 237 310 165 249 249 262 227 298 162
85 310 310 315 285 328 204 302 302 305 293 323 210 289 289 289 289 313 212 272 272 272 272 299 213
90 320 320 320 320 332 244 314 314 314 314 325 251 305 305 305 305 316 260 292 292 292 292 301 264
75 289 272 312 192 321 123 270 264 302 192 317 119 249 249 286 186 309 114 231 231 263 176 297 108
11000 80 300 300 313 240 324 181 289 289 304 246 321 177 272 272 287 243 311 170 253 253 265 234 299 165
85 312 312 316 289 329 205 305 305 307 299 324 212 293 293 293 293 314 215 276 276 276 276 300 217
90 322 322 321 321 332 246 317 317 317 317 326 255 308 308 308 308 317 265 295 295 295 295 303 270
NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

20 RT-PRC002-EN
Performance (12½ Ton)
Data Standard Efficiency

Table PD-11 — Evaporator Fan Performance — 12½Ton — TC*150D


External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Field 3 HP Standard Motor & Sheaves
Supplied Low Static Drive
4000 — — — — — — 565 0.93 599 1.03 632 1.15 663 1.27 695 1.38 727 1.48 757 1.59
4500 — — — — 571 1.10 603 1.21 634 1.31 665 1.43 694 1.56 723 1.69 750 1.82 778 1.94
5000 547 1.18 581 1.30 613 1.42 643 1.54 672 1.67 700 1.78 727 1.91 755 2.05 781 2.19 806 2.34
5500 595 1.55 627 1.68 656 1.81 685 1.94 711 2.08 737 2.21 763 2.34 788 2.47 813 2.62 837 2.77
6000 643 1.99 673 2.12 701 2.26 727 2.41 752 2.56 777 2.71 801 2.85 825 2.99 848 3.13 871 3.27

Table PD-11 — Evaporator Fan Performance — 12½ Ton — TC*150D — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Sheaves 3 HP Standard Motor & High Static Drive Accessory
4000 786 1.70 813 1.81 841 1.91 867 2.02 893 2.12 919 2.22 943 2.32 966 2.41 989 2.50 1011 2.60
4500 806 2.06 834 2.19 861 2.31 886 2.43 911 2.56 935 2.67 960 2.79 983 2.90 1005 3.02 1028 3.13
5000 830 2.48 856 2.62 882 2.76 907 2.89 931 3.02 955 3.16 977 3.30 1001 3.44 1022 3.56 1045 3.70
5500 861 2.93 884 3.10 906 3.25 930 3.41 953 3.56 976 3.70 999 3.86 1021 4.00 1043 4.15 1064 4.31
6000 894 3.43 916 3.61 938 3.79 959 3.97 980 4.15 1000 4.31 1019 4.46 1040 4.62 1061 4.78 1082 4.95
5 HP Oversize Motor & Sheaves
For Standard Evaporator Fan Speed (RPM), reference Table PD-22.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-24.

5 HP Oversize Motor & Field Supplied Drive


NOTES:
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters
No accessories or options are included in pressure drop data. Trane’s factory supplied motors, in commercial equipment, are definite
Refer to Table PD-26 to determine add’l static pressure drop purpose motors, specifically designed and tested to operate reliably and
due to other options/accessories. continuously at all cataloged conditions. Using the full horsepower range
1. Field Supplied Fan Sheave BK90 Required. Field Supplied Belt may be necessary. of our fan motors as shown in our tabular data will not result in nuisance
2. 5 HP Oversized Motor with Field Supplied Motor Sheave IVL40 Required. Field tripping or premature motor failure. Our product’s warranty will not be
Supplied Belt may be necessary. affected.
3. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to
“Motor & Sheave/Fan Speed” tables to determine operating range.

RT-PRC002-EN 21
Performance (15Ton)
Data Standard Efficiency

Table PD-12 — Evaporator Fan Performance — 15 Ton — TC*180B


External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Field 3 HP Standard Motor & Sheaves
Supplied Low Static Drive (1)
4800 — — 563 1.17 596 1.29 626 1.41 656 1.52 685 1.63 714 1.76 742 1.90 768 2.04 794 2.18
5400 585 1.47 618 1.60 648 1.72 676 1.86 703 1.99 729 2.12 756 2.25 782 2.38 807 2.52 832 2.68
6000 643 1.99 673 2.12 701 2.26 727 2.41 752 2.56 777 2.71 801 2.85 825 2.99 848 3.13 871 3.27
6600 701 2.61 729 2.76 755 2.91 780 3.07 804 3.23 827 3.39 849 3.56 871 3.72 892 3.88 914 4.03
7200 760 3.35 786 3.52 810 3.69 834 3.85 856 4.02 878 4.20 899 4.38 919 4.56 939 4.74 959 4.91
(2) 5 HP Oversized Motor & Sheaves

Table PD-12 — Evaporator Fan Performance — 15 Ton — TC*180B — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Sheaves 3 HP Standard Motor & High Static Drive Accessory
4800 819 2.30 844 2.43 871 2.57 898 2.70 923 2.83 946 2.96 970 3.09 994 3.23 1018 3.39 1041 3.54
5400 855 2.84 878 3.00 901 3.15 923 3.29 945 3.43 969 3.58 993 3.73 1016 3.88 1038 4.03 1060 4.17
6000 894 3.43 916 3.61 938 3.79 959 3.97 980 4.15 1000 4.31 1019 4.46 1040 4.62 1061 4.78 1082 4.95
6600 935 4.18 956 4.34 977 4.51 997 4.70 1018 4.90 1037 5.10 1056 5.30 1075 5.49 1093 5.67 — —
7200 979 5.08 999 5.25 1018 5.41 1038 5.58 1057 5.77 — — — — — — — — — —

5 HP Oversized Motor & Sheaves 5 HP OS Motor & Field Supplied Drive (3)
For Standard Evaporator Fan Speed (RPM), reference Table PD-22. Trane’s factory supplied motors, in commercial equipment, are
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-23. definite purpose motors, specifically designed and tested to
For Oversized Evaporator Fan Speed (RPM), reference Table PD-24. operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown in our
NOTES:
tabular data will not result in nuisance tripping or premature motor
Fan motor heat (MBH) = 3.15 x Fan BHP
failure. Our product’s warranty will not be affected.
Data includes pressure drop due to wet coils and filters
No accessories or options are included in pressure drop data.
Refer to Table PD-26 to determine add’l static pressure drop
due to other options/accessories.
1. Field Supplied Fan Sheave BK105 Required. Field Supplied Belt
may be necessary.
2. 5 HP Oversized Motor with Field Supplied Fan Sheave BK160
Required.
Field Supplied Belt may be necessary.
3. 5 HP Oversized Motor with Field Supplied Motor Sheave IVP50
Required. Field Supplied Belt may be necessary.
4. For 380V/60 Hz units, the oversized motor is used as the standard
motor. Refer to “Motor & Sheave/Fan Speed” tables to determine
operating range.

22 RT-PRC002-EN
Performance (17½Ton)
Data Standard Efficiency

Table PD-13 — Evaporator Fan Performance — 17½ Ton — TC*210C


External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Standard Motor with Low Static Drive Accessory
5600 — — — — 735 2.34 759 2.46 783 2.60 807 2.74 830 2.89 852 3.03 875 3.18 898 3.33
6300 765 2.96 788 3.10 810 3.23 831 3.36 852 3.50 874 3.65 895 3.81 917 3.97 937 4.13 956 4.29
7000 845 4.02 866 4.18 886 4.33 906 4.48 925 4.62 944 4.77 963 4.93 982 5.10 1002 5.29 1021 5.47
7700 925 5.32 944 5.49 963 5.66 982 5.82 999 5.98 1016 6.14 1033 6.30 1050 6.47 1069 6.66 1086 6.86
8400 1006 6.87 1024 7.06 1041 7.24 1058 7.42 1075 7.60 1091 7.78 1107 7.95 1122 8.13 1138 8.31 1154 8.50
7.5 HP Oversize Motor & Sheaves

5 HP Standard Motor & Sheaves

Table PD-13 — Evaporator Fan Performance — 17½ Ton — TC*210C — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Standard Motor & Sheaves
5600 923 3.50 946 3.68 968 3.85 989 4.03 1011 4.21 1033 4.39 1056 4.58 1078 4.77 1099 4.96 1122 5.18
6300 976 4.46 997 4.63 1019 4.82 1040 5.00 1060 5.19 1079 5.39 1100 5.60 1118 5.79 1138 6.00 1157 6.20
7000 1039 5.65 1057 5.82 1074 6.00 1092 6.19 1111 6.39 1130 6.59 1150 6.80 1168 7.01 1186 7.22 1205 7.46
7700 1104 7.06 1122 7.26 1138 7.46 1154 7.66 1170 7.84 1186 8.05 1202 8.25 1220 8.47 — — — —
8400 — — — — — — — — — — — — — — — — — — — —

For Standard Evaporator Fan Speed (RPM), reference Table PD-22. 7.5 HP Oversive Motor & Sheaves
For Standard Motor & Low Static Drive Accessory Fan Speed (RPM), reference Table PD-25.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-24.
NOTE: Trane’s factory supplied motors, in commercial equipment, are
Fan motor heat (MBH) = 3.15 x Fan BHP definite purpose motors, specifically designed and tested to operate
Data includes pressure drop due to wet coils and filters reliably and continuously at all cataloged conditions. Using the full
No accessories or options are included in pressure drop data. horsepower range of our fan motors as shown in our tabular data will
Refer to Table PD-26 to determine add’l static pressure drop not result in nuisance tripping or premature motor failure. Our
due to other options/accessories. product’s warranty will not be affected.
1. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor &
Sheave/Fan Speed” tables to determine operating range.

*Indicates both downflow and horizontal units.

RT-PRC002-EN 23
Performance (20 Ton)
Data Standard Efficiency

Table PD-14 — Evaporator Fan Performance — 20 Ton — TC*240B


External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Standard Motor & Field Supplied 5 HP Standard Motor & Sheaves
Low Static Drive (1)
6400 — — 514 1.69 546 1.88 574 2.05 599 2.21 624 2.37 648 2.54 671 2.71 695 2.90 720 3.11
7200 527 2.08 562 2.29 592 2.50 619 2.71 644 2.91 667 3.09 689 3.26 711 3.45 732 3.64 752 3.83
8000 578 2.79 610 3.03 639 3.26 666 3.50 690 3.73 712 3.96 733 4.16 753 4.35 773 4.55 792 4.75
8800 629 3.65 659 3.93 687 4.18 712 4.43 736 4.69 758 4.96 778 5.20 797 5.43 816 5.65 834 5.86
9600 681 4.67 709 4.99 735 5.27 759 5.54 782 5.82 804 6.11 824 6.39 843 6.67 861 6.92 878 7.16
5 HP Standard Motor & Sheaves (2) 7.5 HP Oversized Motor & Sheaves

Table PD-14 — Evaporator Fan Performance — 20 Ton — TC*240B — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Standard Motor & Sheaves 5 HP Standard Motor & High Static Drive Accessory
6400 744 3.32 768 3.52 790 3.72 811 3.91 833 4.13 855 4.36 877 4.59 897 4.82 917 5.05 936 5.29
7200 773 4.04 795 4.27 817 4.50 839 4.74 860 4.96 880 5.19 898 5.41 917 5.64 937 5.88 957 6.14
8000 811 4.96 830 5.18 848 5.40 867 5.64 887 5.90 907 6.16 927 6.42 946 6.68 964 6.93 982 7.18
8800 852 6.08 869 6.30 887 6.53 904 6.77 921 7.01 938 7.26 955 7.52 973 7.81 991 8.09 — —
9600 895 7.40 911 7.63 928 7.86 944 8.11 960 8.36 976 8.61 — — — — — — — —
7.5 HP Oversized Motor & Sheaves
For Standard Evaporator Fan Speed (RPM), reference Table PD-22. Trane’s factory supplied motors, in commercial equipment, are
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-23. definite purpose motors, specifically designed and tested to operate
For Oversized Evaporator Fan Speed (RPM), reference Table PD-24. reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will
NOTES:
not result in nuisance tripping or premature motor failure. Our
Fan motor heat (MBH) = 3.15 x Fan BHP
product’s warranty will not be affected.
Data includes pressure drop due to wet coils and filters
No accessories or options are included in pressure drop data.
Refer to Table PD-26 to determine add’l static pressure drop
due to other options/accessories.
1. Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may be
necessary.
2. 7.5 HP Standard Motor with Field Supplied Motor Sheave IVP50 Required.
Field Supplied Belt may be necessary.
3. For 380V/60 Hz units, the oversized motor is used as the standard motor.
Refer to “Motor & Sheave/Fan Speed” tables to determine operating
range.

*Indicates both downflow and horizontal units.

24 RT-PRC002-EN
Performance (25 Ton)
Data Standard Efficiency

Table PD-15 — Evaporator Fan Performance — 25 Ton — TC*300B


External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
7.5 HP Standard Motor & Low Static Drive Accessory 7.5 HP Standard Motor & Sheaves
7000 — — — — 593 2.42 619 2.62 643 2.80 667 2.98 690 3.16 712 3.35 733 3.53 754 3.73
7500 — — 595 2.66 624 2.88 649 3.10 673 3.31 695 3.50 717 3.68 738 3.88 759 4.08 779 4.28
8000 595 2.92 627 3.16 655 3.39 679 3.63 702 3.86 724 4.07 745 4.28 766 4.48 786 4.68 805 4.90
8500 628 3.47 659 3.73 686 3.97 710 4.23 732 4.47 754 4.71 774 4.94 794 5.15 813 5.36 832 5.58
9000 661 4.08 691 4.36 717 4.62 741 4.89 763 5.15 784 5.41 803 5.66 822 5.89 841 6.12 859 6.35
9500 695 4.76 723 5.06 749 5.34 772 5.62 794 5.90 814 6.18 833 6.45 852 6.71 870 6.95 887 7.19
10000 729 5.52 755 5.84 781 6.13 804 6.42 825 6.72 844 7.01 863 7.31 881 7.59 899 7.86 916 8.11
10500 762 6.35 788 6.69 812 7.00 835 7.31 856 7.62 875 7.93 894 8.24 911 8.54 — — — —
11000 796 7.27 821 7.63 844 7.96 867 8.3 887 8.60 — — — — — — — — — —

7.5 HP Standard Motor & Sheaves 7.5 HP Standard Motor & High Static Drive Accessory

Table PD-15 — Evaporator Fan Performance — 25 Ton — TC*300B — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
7.5 HP Standard Motor & Sheaves
7000 776 3.95 798 4.18 820 4.40 841 4.62 862 4.84
7500 798 4.48 818 4.71 839 4.95 860 5.19 880 5.42
8000 824 5.11 842 5.32 860 5.55 880 5.80 899 6.06
8500 850 5.81 868 6.03 885 6.26 902 6.49 920 6.74
9000 877 6.58 894 6.81 911 7.05 928 7.29 944 7.53
9500 904 7.43 921 7.67 938 7.92 954 8.17 970 8.42
10000 933 8.36 949 8.62 — — — — — —
10500 — — — — — — — — — —
11000 — — — — — — — — — —

7.5 HP Oversized Motor & High Static Drive Accessory


For Standard Evaporator Fan Speed (RPM), reference Trane’s factory supplied motors, in commercial
Table PD-22. equipment, are definite purpose motors, specifically
For Standard Motor & High Static Drive Accessory Fan designed and tested to operate reliably and
Speed (RPM), reference Table PD-23. continuously at all cataloged conditions. Using the full
For Standard Motor & Low Static Drive Accessory Fan horsepower range of our fan motors as shown in our
Speed (RPM), reference Table PD-25. tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will
not be affected.
NOTES:
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters
No accessories or options are included in pressure drop
data. Refer to Table PD-26 to determine add’l static pressure
drop due to other options/accessories.
1. For 380V/60 Hz units, the oversized motor is used as the
standard motor. Refer to “Motor & Sheave/Fan Speed”
tables to determine operating range.

*Indicates both downflow and horizontal units.

RT-PRC002-EN 25
Performance (12½ Ton)
Data High Efficiency

Table PD-16 — Evaporator Fan Performance — 12½Ton — TCD151C


External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Field 3 HP Standard Motor & Drive
Supplied Low Static Drive (1)
4000 — — — — 549 0.91 596 1.07 638 1.22 677 1.37 713 1.52 746 1.66 778 1.80 809 1.94
4500 — — 528 0.95 580 1.15 626 1.33 668 1.51 706 1.68 741 1.85 775 2.02 806 2.18 836 2.34
5000 503 0.96 562 1.20 613 1.42 657 1.63 698 1.83 735 2.03 770 2.23 803 2.42 835 2.60 864 2.79
5500 540 1.22 597 1.49 646 1.74 689 1.98 729 2.21 766 2.43 800 2.65 833 2.86 864 3.07 893 3.28
6000 578 1.53 633 1.82 680 2.10 722 2.37 761 2.62 797 2.87 831 3.12 863 3.36 893 3.59 922 3.82
5 HP Oversized
Motor & Drive

3 HP Standard Motor & High


Static Drive Accessory

Table PD-16 — Evaporator Fan Performance — 12½ Ton — TCD151C — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard 3 HP Standard Motor & High Static Drive Accessory
Motor & Drive
4000 838 2.08 865 2.21 892 2.35 918 2.48 943 2.61 967 2.73 990 2.87 1013 3.01 1035 3.17 1057 3.33
4500 865 2.50 892 2.66 919 2.81 944 2.97 969 3.12 993 3.27 1016 3.42 1039 3.57 1061 3.72 1082 3.85
5000 893 2.97 920 3.15 946 3.32 971 3.50 996 3.67 1020 3.85 1043 4.02 1065 4.19 1087 4.36 1108 4.52
5500 921 3.49 948 3.69 974 3.89 999 4.09 1023 4.28 1047 4.48 1070 4.67 1092 4.86 1114 5.05 1135 5.24
6000 950 4.05 977 4.28 1002 4.50 1027 4.72 1051 4.94 1075 5.16 1098 5.38 1120 5.59 — — — —
5 HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-22. Trane’s factory supplied motors, in commercial equipment, are
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-23. definite purpose motors, specifically designed and tested to operate
For Oversized Evaporator Fan Speed (RPM), reference Table PD-24. reliably and continuously at all cataloged conditions. Using the full
NOTE: horsepower range of our fan motors as shown in our tabular data will
Fan motor heat (MBH) = 3.15 x Fan BHP not result in nuisance tripping or premature motor failure. Our
Data includes pressure drop due to wet coils and filters product’s warranty will not be affected.
No accessories or options are included in pressure drop data.
Refer to Table PD-26 to determine add’l static pressure drop
due to other options/accessories.
1. Field Supplied Fan Sheave BK115 Required. Field Supplied
Belt may be necessary.

26 RT-PRC002-EN
Performance (12½ Ton)
Data High Efficiency

Table PD-17 — Evaporator Fan Performance — 12½Ton — TCH151C


External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Field Supplied Low Static Drive (1) 3 HP Standard Motor & Drive
4000 — — — — 510 0.98 541 1.10 572 1.22 602 1.35 631 1.48 659 1.62 687 1.76 714 1.91
4500 — — 521 1.17 551 1.29 579 1.42 607 1.56 635 1.68 662 1.82 688 1.98 713 2.13 738 2.28
5000 534 1.40 566 1.54 593 1.67 620 1.81 645 1.95 671 2.11 696 2.25 720 2.40 744 2.56 767 2.73
5500 581 1.83 611 1.99 637 2.13 661 2.28 685 2.43 709 2.59 732 2.76 754 2.92 777 3.08 799 3.25
6000 628 2.34 657 2.51 682 2.68 704 2.83 727 3.00 749 3.16 770 3.33 791 3.52 812 3.70 833 3.87
5 HP Oversized Motor& Drive

Table PD-17 — Evaporator Fan Performance — 12½ Ton — TCH151C — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Drive 3 HP Standard Motor & High Static
Drive Accessory
4000 740 2.07 766 2.23 791 2.38 814 2.54 838 2.70 860 2.86 883 3.02 905 3.19 926 3.37 948 3.55
4500 763 2.44 787 2.61 811 2.78 835 2.96 858 3.13 880 3.31 901 3.48 922 3.66 943 3.84 963 4.02
5000 790 2.90 812 3.07 835 3.24 857 3.42 879 3.61 901 3.81 922 4.00 942 4.20 962 4.39 982 4.59
5500 820 3.43 842 3.61 862 3.80 883 3.98 904 4.17 924 4.37 944 4.57 964 4.78 984 4.99 1003 5.20
6000 853 4.04 874 4.23 893 4.43 913 4.63 932 4.83 951 5.03 970 5.24 988 5.45 1007 5.66 — —
5 HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-22. Trane’s factory supplied motors, in commercial equipment, are
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-23. definite purpose motors, specifically designed and tested to operate
For Oversized Evaporator Fan Speed (RPM), reference Table PD-24. reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
NOTE: will not result in nuisance tripping or premature motor failure. Our
Fan motor heat (MBH) = 3.15 x Fan BHP product’s warranty will not be affected.
Data includes pressure drop due to wet coils and filters
No accessories or options are included in pressure drop data.
Refer to Table PD-26 to determine add’l static pressure drop
due to other options/accessories.
1. Field Supplied Fan Sheave BK115 Required. Field Supplied Belt
may be necessary.

RT-PRC002-EN 27
Performance (15 Ton)
Data High Efficiency

Table PD-18 — Evaporator Fan Performance — 15 Ton — TC*181C


External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Field 3 HP Standard Motor & Drive
Supplied Low Static Drive (1)
4800 — — 444 0.84 472 0.99 503 1.14 535 1.29 566 1.44 598 1.60 629 1.77 658 1.94 684 2.11
5400 445 1.04 474 1.19 506 1.33 536 1.47 564 1.62 592 1.78 621 1.95 648 2.12 676 2.30 704 2.49
6000 479 1.38 513 1.55 543 1.72 571 1.87 597 2.03 623 2.19 648 2.36 673 2.55 699 2.74 723 2.93
6600 519 1.79 552 1.98 580 2.17 606 2.35 632 2.52 656 2.69 679 2.87 702 3.05 725 3.25 748 3.46
7200 560 2.28 591 2.49 618 2.70 643 2.91 667 3.09 690 3.27 712 3.46 734 3.65 755 3.85 776 4.06
3 HP Standard Motor & Drive 5 HP Oversized Motor& Drive

Table PD-18 — Evaporator Fan Performance — 15 Ton — TC*181C — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Drive 3 HP Standard Motor & High
Static Drive Accessory
4800 710 2.29 735 2.48 760 2.68 785 2.88 809 3.09 832 3.29 854 3.49 876 3.69 898 3.90 919 4.10
5400 730 2.68 755 2.88 778 3.07 800 3.28 823 3.49 845 3.71 867 3.94 889 4.17 910 4.40 931 4.62
6000 749 3.13 774 3.34 798 3.56 821 3.77 842 3.99 863 4.20 884 4.43 904 4.66 924 4.90 944 5.15
6600 771 3.7 794 3.88 816 4.09 839 4.32 862 4.56 884 4.80 904 5.03 924 5.27 943 5.51 961 5.75
7200 797 4.29 818 4.51 839 4.74 860 4.96 881 5.20 902 5.45 923 5.70 — — — — — —
5 HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-22. Trane’s factory supplied motors, in commercial equipment, are
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-23. definite purpose motors, specifically designed and tested to operate
For Oversized Evaporator Fan Speed (RPM), reference Table PD-24. reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will
NOTE:
not result in nuisance tripping or premature motor failure. Our
Fan motor heat (MBH) = 3.15 x Fan BHP
product’s warranty will not be affected.
Data includes pressure drop due to wet coils and filters
No accessories or options are included in pressure drop data.
Refer to Table PD-26 to determine add’l static pressure drop
due to other options/accessories.
1. Field Supplied Fan Sheave BK120 Required. Field Supplied Belt may
be necessary. Field Supplied Belt may be necessary.

*Indicates both downflow and horizontal units.

28 RT-PRC002-EN
Performance (17½ Ton)
Data High Efficiency

Table PD-19 — Evaporator Fan Performance — 17½ Ton — TC*211C


External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Standard Motor & Field 5 HP Standard Motor & Drive
Supplied Low Static Drive (1)
5600 — — — — 518 1.45 547 1.60 575 1.75 602 1.91 629 2.08 656 2.26 683 2.43 710 2.63
6300 — — 532 1.76 561 1.94 588 2.10 614 2.26 639 2.43 663 2.60 687 2.79 711 2.99 735 3.19
7000 546 2.11 578 2.31 606 2.52 631 2.71 655 2.89 678 3.07 701 3.25 723 3.44 744 3.64 766 3.85
7700 594 2.75 625 2.98 651 3.21 675 3.43 698 3.64 720 3.84 741 4.03 761 4.23 782 4.44 801 4.65
8400 642 3.52 671 3.78 697 4.03 720 4.27 741 4.51 762 4.73 782 4.95 802 5.16 821 5.38 840 5.60

5 HP Standard Motor & High


Static Drive Accessory

Table PD-19— Evaporator Fan Performance — 17½ Ton — TC*211C — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Standard Motor & Drive 5 HP Standard Motor & High Static Drive Accessory
5600 736 2.83 761 3.03 785 3.23 807 3.43 829 3.64 851 3.86 872 4.09 893 4.32 914 4.56 935 4.80
6300 759 3.38 783 3.59 807 3.82 830 4.04 853 4.27 874 4.49 894 4.72 913 4.95 933 5.19 952 5.43
7000 788 4.07 810 4.29 831 4.51 852 4.74 874 4.97 895 5.22 917 5.47 937 5.72 957 5.97 975 6.22
7700 821 4.87 841 5.10 861 5.34 881 5.59 900 5.83 919 6.07 939 6.32 958 6.58 978 6.85 997 7.12
8400 858 5.82 876 6.06 894 6.30 912 6.55 930 6.81 949 7.08 967 7.34 984 7.60 1002 7.87 — —
7.5 HP Oversized Motor & Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-22. Trane’s factory supplied motors, in commercial equipment, are
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-23. definite purpose motors, specifically designed and tested to operate
For Oversized Evaporator Fan Speed (RPM), reference Table PD-24. reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
NOTE: will not result in nuisance tripping or premature motor failure. Our
Fan motor heat (MBH) = 3.15 x Fan BHP product’s warranty will not be affected.
Data includes pressure drop due to wet coils and filters
No accessories or options are included in pressure drop
data. Refer to Table PD-26 to determine add’l static
pressure drop due to other options/accessories.
1. Field Supplied Fan Sheave BK190 Required. Field
Supplied Belt may be necessary.

*Indicates both downflow and horizontal units.

RT-PRC002-EN 29
Performance (20 Ton)
Data High Efficiency

Table PD-20 — Evaporator Fan Performance — 20 Ton — TC*241C


External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Standard Motor & Field Supplied 5 HP Standard Motor & Drive
Low Static Drive (1)
6400 506 1.64 540 1.84 570 2.03 595 2.19 620 2.34 644 2.51 669 2.69 693 2.89 717 3.09 741 3.29
7200 560 2.28 592 2.50 620 2.72 646 2.92 668 3.10 690 3.27 711 3.45 733 3.65 755 3.86 777 4.08
8000 616 3.07 645 3.31 672 3.56 696 3.80 719 4.02 739 4.22 759 4.41 778 4.60 797 4.81 817 5.03
8800 671 4.04 698 4.29 724 4.55 747 4.83 769 5.10 790 5.34 808 5.56 826 5.77 844 5.98 861 6.20
9600 728 5.19 753 5.46 776 5.74 799 6.04 820 6.34 840 6.63 859 6.90 876 7.14 893 7.37 909 7.59
(2) 7.5 HP Oversized Motor & Drive

Table PD-20 — Evaporator Fan Performance — 20 Ton — TC*241C — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Standard Motor & Drive 5 HP Standard Motor & High Static Drive Accessory
6400 765 3.49 788 3.70 810 3.91 832 4.12 854 4.34 875 4.57 896 4.80 916 5.04 936 5.29 955 5.54
7200 799 4.31 820 4.53 841 4.76 862 4.99 883 5.22 902 5.46 922 5.69 942 5.94 961 6.19 980 6.44
8000 837 5.26 857 5.51 876 5.76 896 6.01 915 6.26 934 6.52 953 6.77 971 7.03 989 7.29 — —
8800 879 6.43 897 6.67 915 6.93 933 7.19 951 7.46 969 7.74 986 8.01 — — — — — —
9600 925 7.83 941 8.07 958 8.32 974 8.58 — — — — — — — — — — — —
7.5 HP Oversized Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-22. Trane’s factory supplied motors, in commercial equipment, are
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-23. definite purpose motors, specifically designed and tested to operate
For Oversized Evaporator Fan Speed (RPM), reference Table PD-24. reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
NOTES:
will not result in nuisance tripping or premature motor failure. Our
Fan motor heat (MBH) = 3.15 x Fan BHP
product’s warranty will not be affected.
Data includes pressure drop due to wet coils and filters
No accessories or options are included in pressure drop data.
1. Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may
be necessary.
2. 7.5 HP Standard Motor with Field Supplied Motor Sheave 1VP50
Required. Field Supplied Belt may be necessary.

*Indicates both downflow and horizontal units.

30 RT-PRC002-EN
Performance (25 Ton)
Data High Efficiency

Table PD-21 — Evaporator Fan Performance — 25 Ton — TC*301C


External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
7.5 HP Standard Motor & Low Static Drive Accessory 7.5 HP Standard Motor & Drive
7000 — — — — 608 2.54 633 2.73 656 2.89 678 3.06 700 3.25 723 3.44 745 3.65 768 3.87
7500 — — 611 2.78 640 3.02 665 3.24 687 3.43 708 3.61 729 3.79 749 3.98 770 4.19 792 4.41
8000 616 3.07 645 3.31 672 3.56 696 3.80 719 4.02 739 4.22 759 4.41 778 4.60 797 4.81 817 5.03
8500 650 3.66 678 3.90 704 4.16 728 4.43 750 4.68 771 4.90 790 5.10 808 5.31 826 5.52 844 5.74
9000 685 4.31 712 4.56 737 4.83 760 5.12 782 5.39 802 5.65 821 5.88 839 6.09 856 6.30 873 6.53
9500 721 5.04 746 5.30 770 5.58 792 5.88 814 6.18 834 6.46 853 6.72 870 6.96 887 7.18 903 7.41
10000 756 5.85 780 6.12 803 6.41 825 6.72 846 7.04 866 7.35 884 7.64 902 7.90 918 8.14 934 8.38
10500 791 6.74 814 7.03 836 7.33 858 7.64 878 7.98 898 8.31 916 8.62 — — — — — —
11000 827 7.71 849 8.02 870 8.33 891 8.63 — — — — — — — — — — — —
7.5 HP Standard Motor & Drive

Table PD-21 — Evaporator Fan Performance — 25 Ton — TC*301C — Continued


External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
7.5 HP Standard Motor & Drive
7000 790 4.09 812 4.31 833 4.53 854 4.76 875 4.99
7500 813 4.65 833 4.88 854 5.12 874 5.36 894 5.59
8000 837 5.26 857 5.51 876 5.76 896 6.01 915 6.26
8500 863 5.97 881 6.21 900 6.46 919 6.73 937 6.99
9000 890 6.76 908 7.00 925 7.25 943 7.52 961 7.79
9500 919 7.64 936 7.88 952 8.13 969 8.40 985 8.67
10000 949 8.62 — — — — — — — —
10500 — — — — — — — — — —
11000 — — — — — — — — — —

Trane’s factory supplied motors, in commercial


7.5 HP Standard Motor & High Static Drive Accessory equipment, are definite purpose motors,
specifically designed and tested to operate reliably
and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors
For Standard Evaporator Fan Speed (RPM), reference Table PD-22. as shown in our tabular data will not result in
For Standard Motor & High Static Drive Accessory Fan Speed nuisance tripping or premature motor failure. Our
(RPM), reference Table PD-23. product’s warranty will not be affected.
For Standard Motor & Low Static Drive Accessory Fan Speed
(RPM), reference Table PD-25.

NOTE:
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters
No accessories or options are included in pressure drop data.
Refer to Table PD-26 to determine add’l static pressure drop
due to other options/accessories.

*Indicates both downflow and horizontal units.

RT-PRC002-EN 31
Performance (12½-25 Ton)
Data

Table PD-22— Standard Motor & Drive/Fan Speed (Rpm)


Unit 6Turns 5Turns 4Turns 3Turns 2Turns 1Turn
Tons Model No. Open Open Open Open Open Open Closed
12½ TC*150D3,4,W, YC*151C3,4,W 640 680 720 760 800 840 NA
TC*150DK 705 756 806 857 907 957 NA
TC*180B3,4,W 679 721 764 806 849 891 NA
15 TC*180BK N/A 680 733 785 837 889 941
TC*181C3,4,W 560 600 640 680 720 760 NA
TC*210C3,4,W 869 923 978 1032 1087 1141 NA
17½ TC*210CK 869 924 978 1032 1087 1141 NA
TC*211C3,4,W 615 659 703 747 791 835 NA
20 TC*240B3,4,W,TC*241C3,4,W 615 659 703 747 791 835 NA
TC*240BK 590 627 664 701 738 775 NA
25 TC*300B3,4,W,TC*301C3,4,W 705 742 779 817 854 891 NA
TC*300BK 701 738 775 812 849 886 NA
Factory set at 3 turns open.

Table PD-23— Standard Motor & High Static Drive Accessory/Fan Speed (Rpm)
Unit 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn
Tons Model No. Open Open Open Open Open Open Closed
12½ TC*151C3,4,W 807 857 908 958 1009 1059 NA
TC*180B3,4,W 806 849 891 934 976 1019 NA
15
TC*181B3,4,W 640 680 720 760 800 840 NA
17½ TC*211C3,4,W 835 879 923 967 1011 1055 NA
20 TC*240B/241C3,4,W 835 879 923 967 1011 1055 NA
25 TC*300B/301C3,4,W 816 853 890 928 965 1002 NA

Table PD-24— Oversized Motor & Drive/Fan Speed (Rpm)


Unit 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn
Tons Model No. Open Open Open Open Open Open Closed
12½ TC*150D,151C3,4,W 869 923 978 1032 1087 1141 NA
TC*180B3,4,W 806 856 907 957 1008 1058 NA
15
TC*181C3,4,W 705 755 806 856 907 957 NA
17½ TC*210C3,4,W 949 1008 1068 1127 1187 1246 NA
TC*211C3,4,W 816 853 890 928 965 1002 NA
20 TC*240B3,4,W,TYC*241C3,4,W 816 853 890 928 965 1002 NA

Table PD-25 — Standard Motor & Low Static Fan Drive


Unit 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn
Tons Model No. Open Open Open Open Open Open Closed
17½ TC*210C3,4,W 705 755 806 856 907 957 NA
25 TC*300B3,4,W,301C3,4,W 594 631 668 705 742 779 NA

*Indicates both downflow and horizontal units.

32 RT-PRC002-EN
Performance (12½-25 Ton)
Data

Table PD-26 — Static Pressure Drops Through Accessories (Inches Water Column)
Economizer with Electric Heater
Unit Standard 2 Inch OA/RA Dampers2 Accessory (KW)3
Tons Model No. CFM Filters1 Pleated Filters4 100% OA 100% RA 5-12 14-23 36 54 72
TC*150D 4000 .05 .08 .19 .02 — .03 .03 .04 —
12½ TC*151C 5000 .07 .11 .26 .03 — .04 .05 .06 —
6000 .10 .15 .33 .04 — .06 .07 .09 —
4800 .07 .10 .25 .03 — .04 .04 .05 —
TC*180B 6000 .10 .15 .33 .04 — .06 .07 .08 —
7200 .15 .19 .40 .05 — .09 .10 .12 —
15 4800 .04/.03 .07/.06 .14 .03 — 04 .04 .05 —
TCD/TCH181C 6000 .06/.05 .10/.09 .20 .04 — 06 .07 .08 —
7200 .09/.07 .13/.11 .27 .05 — 09 .10 .12 —
5600 .09 .13 .30 .04 — — .06 .07 —
TC*210C 7000 .14 .18 .39 .05 — — .10 .11 —
8400 .20 .24 .47 .06 — — .15 .17 —
17½ 5600 .06/.05 .09/.08 .18 .04 — — .05 .06 .07
TCD/TCH211C 7000 .09/.07 .13/.11 .26 .04 — — .08 .09 .11
8400 .12/.10 .17/.14 .35 .06 — — .12 .13 .16
6400 .07 .11 .22 .04 — — .06 .08 .09
TCD240B 8000 .11 .15 .32 .05 — — .10 .12 .14
TCD241C 9600 .16 .20 .44 .07 — — .14 .17 .20
20 6400 .06 .10 .22 .04 — — .06 .08 .09
TCH240B 8000 .09 .13 .32 .05 — — .10 .12 .14
TCH241C 9600 .13 .17 .44 .07 — — .14 .17 .20
7000 .09 .13 .26 .04 — — .08 .10 .11
TCD300B 9000 .14 .18 .40 .07 — — .13 .15 .18
TCD301C 11000 .21 .25 .57 .10 — — .18 .22 .26
25 7000 .07 .11 .26 .04 — — .08 .10 .11
TCH300B 9000 .11 .15 .40 .07 — — .13 .15 .18
TCH301C 11000 .17 .22 .60 .10 — — .18 .22 .26

NOTES:
1. Tested with: 2” filters 12½-25 tons
2. OA = Outside Air and RA = Return Air.
3. Nominal KW ratings at 240, 480, 600 volts.
4. Difference in pressure drop should be considered when utilizing optional 2” pleated filters.

*Indicates both downflow and horizontal units.

RT-PRC002-EN 33
Performance (12½-25 Ton)
Data

Table PD-27 — Auxiliary Electric Heat Capacity


Total2 Stage1 Stage 2
Unit KW MBH No. of KW MBH KW MBH
Tons Model No. Input1 Output1 Stages Input1 Output1 Input1 Output1
18.00 61.47 1 18.00 61.47 — —
TC*150D3,D4,DW,DK 27.004 92.15 2 9.00 30.72 18.00 61.43
12½-15 TC*180B3,B4,BW,BK 36.00 122.94 2 18.00 61.47 18.00 61.47
TC*151 or 181C3,C4,CW 54.00 184.41 2 36.00 122.94 18.00 61.47
TC*210C3,C4,CW,CK 36.00 122.94 2 18.00 61.47 18.00 61.47
17½, 20, 25 240, 300B3,B4,BW,BK 54.00 184.41 2 36.00 122.94 18.00 61.47
TC*211, 241, 301C3,C4,CW 72.003 245.88 2 36.00 122.94 36.00 122.94
NOTES:
1. Does not include indoor fan power or heat. 2

3. Not available on TC*210C.


(
2. Heaters are rated at 240v, 480v. and 600v. For other than rated voltage, CAP =
Voltage
Rated Voltage )
x rated cap.

4. 27KW heater can be used with TCD181C4, TCD211C4, TCD241C4 andTCD301C4 only. Cannot be used with oversized motor.

Table PD-28 — Electric Heater Voltage


Correction Factors (Applicable to Auxiliary
Heat Capacity)
Nominal Distribution Capacity
Voltage Voltage Multiplier
208 0.75
240 230 0.92
240 1.00
440 0.84
480 460 0.94
480 1.00
540 0.81
600 575 0.92
600 1.00

Table PD-29 — Air Temperature Rise Across Electric Heaters (Degree F)


12½ Ton 15 Ton 17½ Ton 20 Ton 25 Ton
5000 CFM 6000 CFM 7000 CFM 8000 CFM 9000 CFM
Three Phase Three Phase Three Phase Three Phase Three Phase
TC*150 TC*180 TC*210 TC*240 TC*300
KW Stages TC*151 TC*181 TC*211 TC*241 TC*301
9.00 1 — — — — —
17.30 1 — — — — —
18.00 1 11.4 9.5 — — —
27.00 2 — 14.22 12.221 10.72 9.52
36.00 2 22.8 19.0 16.3 14.2 12.6
54.00 2 34.1 28.5 24.4 21.3 19.0
72.002 2 — — 32.5 28.5 25.3

For minimum design airflow, see airflow performance table for each unit.
To calculate temp rise at different air flow, use following formula:
KW x 3413
Temp. Rise across Elect. Htr =
1.08 x CFM

NOTES:
1. Not available on TC*210 model.
2. 27KW heater can be used with TCD181C4, TCD211C4, TCD241C4 andTCD301C4 only. Cannot be used with oversized motor.

34 RT-PRC002-EN
Controls

Field Installed Control Options Digital Display Zone Sensor CO2 Sensing —The CO2 sensor has the
The Digital LCD (Liquid Crystal Display) ability to monitor space occupancy levels
Zone Sensors zone sensor has the look and functionality within the
Zone sensors are the building occupant’s of standard zone building by
comfort control devices.They replace the sensors.This measuring the
conventional electro-mechanical sensor includes a parts per million
thermostats.The following zone sensor digital display of of CO2 (Carbon
options are available for Voyager units set point Dioxide) in the air.
with the ReliaTel™ control: adjustment and As the CO2 levels
Manual Changeover space temperature increase, the
Heat, Cool or Off in F (Fahrenheit) or outside air
System Switch. Fan C (Celsius). damper
Auto or Off Switch. Includes FAN and modulates to
One temperature SYSTEM buttons meet the CO2 space ventilation
setpoint lever. (supports the requirements.The CO2 sensor kit is
service functions of available as a field installed accessory.
the standard Economizer Controls
sensor). E-squared memory stores last The standard equipment offering is a
programmed set points. Requires 24 VAC fixed dry bulb changeover control. In
(Volts AC).This sensor should be utilized addition, there are two optional controls,
Manual/Automatic Changeover with ReliaTel controls.
Auto, Heat, Cool or Off System Switch. Enthalpy and Differential Enthalpy
Fan Auto or Off Control.
Programmable Night Setback
Switch.Two Enthalpy Control
Auto or manual changeover with seven-
temperature Replaces the dry bulb control with a wet
day programming. Keyboard selection
setpoint levers. bulb changeover controller which has a
Optional Status fully adjustable set point. Enthalpy control
Indication LED lights, offers a higher level of comfort control,
System On, Heat, along with energy savings potential, than
Cool, or Service. the standard dry bulb control. This is due
to the additional wet bulb sensing
capability.
Differential Enthalpy
Replaces the standard dry bulb control
Remote Sensor with two enthalpy sensors that compare
Sensor(s) available total heat content of the indoor air and
for all zone sensors to of Heat, Cool, Fan, Auto, or On. All outdoor air to determine the most
provide remote programmable sensors have System On, efficient air source.This control option
sensing capabilities. Heat, Cool, Service LED/indicators as offers the highest level of comfort control,
standard. Night Setback Sensors have plus energy efficiency, available.
one (1) Occupied, one (1) Un-occupied, Remote Potentiometer
and two (2) Override programs per day. Minimum position setting of economizer
can be remotely adjusted with this
accessory.
Integrated
ComfortTM Differential Pressure Switches
System This factory or field-installed option
Dual Thermistor Remote Zone Sensor Sensor(s) allows individual fan failure and dirty filter
This sensor will allow the customer to available with indication. The fan failure switch will
reduce the total number of remote optional disable all unit functions and “flash” the
sensors to obtain space temperature temperature Service LED on the zone sensor. The dirty
averaging. This sensor should be utilized adjustment and filter switch will light the Service LED on
with ReliaTel controls. override buttons the zone sensor and will allow continued
to provide central unit operation.
control through a Trane Communication Interface (TCI)
Trane Integrated This factory or field-installed micro-
Comfort system. processor interface allows the unit to
communicate toTrane’s Integrated
Comfort system.
RT-PRC002-EN 35
Electrical (Standard
Data Efficiency)

Table ED-1 — Unit Wiring Standard Efficiency


Standard Indoor Fan Motor Oversize Indoor Fan Motor
Unit Minimum Maximum Fuse Minimum Maximum Fuse
Unit Operating Circuit Size Or Maximum Circuit Size Or Maximum
Tons Model No. Voltage Range Ampacity2 Circuit Breaker1 Ampacity2 Circuit Breaker1
TC*150D3 187-253 63 80 69 80
12½ TC*150D4 414-506 33 40 36 40
TC*150DW 518-633 26 30 28 35
TC*150DK 342-418 43 50 – –
TC*180B3 187-253 78 90 84 100
15 TC*180B4 414-506 39 50 42 50
TC*180BW 517-633 31 40 33 40
TC*180BK 342-418 50 60 – –
TC*210C3 187-253 88 100 96 125
17½ TC*210C4 414-506 44 50 47 60
TC*210CW 517-633 35 45 38 45
TC*210CK 342-418 57 70 – –
TC*240B3 187-253 100 125 107 125
20 TC*240B4 414-506 50 60 54 60
TC*240BW 517-633 40 45 43 50
TC*240BK 342-418 65 80 – –
TC*300B3 187-253 118 150 – –
25 TC*300B4 414-506 58 70 – –
TC*300BW 517-633 46 50 – –
TC*300BK 342-418 70 80 – –

NOTE:
1. HACR breaker per NEC.
2. Values do not include power exhaust accessory.

*Indicates both downflow and horizontal units.

36 RT-PRC002-EN
Electrical
Data (High Efficiency)

Table ED-2 — Unit Wiring High Efficiency


Standard Indoor Fan Motor Oversize Indoor Fan Motor
Unit Minimum Maximum Fuse Minimum Maximum Fuse
Unit Operating Circuit Size Or Maximum Circuit Size Or Maximum
2 1 2
Tons Model No. Voltage Range Ampacity Circuit Breaker Ampacity Circuit Breaker1
TC*151C3 187-253 64 80 70 90
12½ TC*151C4 414-506 31 40 34 40
TC*151CW 517-633 25 30 28 35
TC*181C3 187-253 74 90 80 100
15 TC*181C4 414-506 36 50 38 50
TC*181CW 517-633 29 40 31 40
TC*211C3 187-253 91 110 98 125
17½ TC*211C4 414-506 44 60 48 60
TC*211CW 517-633 35 45 38 50
TC*241C3 187-253 99 125 107 125
20 TC*241C4 414-506 50 60 54 60
TC*241CW 517-633 40 50 43 50
TC*301C3 187-253 120 150 N/A N/A
25 TC*301C4 414-506 58 70 N/A N/A
TC*301CW 517-633 47 60 N/A N/A

NOTE:
1. HACR breaker per NEC.
2. Values do not include power exhaust accessory.

Table ED-3— Unit Wiring — TXV/Face-Split Evaporator Coil Option (Downflow Only) — High Efficiency
Standard Indoor Fan Motor Oversize Indoor Fan Motor
Unit Minimum Maximum Fuse Minimum Maximum Fuse
Unit Operating Circuit Size Or Maximum Circuit Size Or Maximum
Tons Model No. Voltage Range Ampacity2 Circuit Breaker1 Ampacity2 Circuit Breaker1
TCD151C3 187-253 59 70 65 80
12½ TCD151C4 414-506 30 35 32 40
TCD151CW 517-633 24 30 26 30
TCD181C3 187-253 74 90 80 90
15 TCD181C4 414-506 37 50 39 50
TCD181CW 517-633 30 40 32 40
TCD211C3 187-253 91 125 99 125
17½ TCD211C4 414-506 45 60 49 60
TCD211CW 517-633 36 45 39 50
TCD241C3 187-253 99 125 107 125
20 TCD241C4 414-506 51 60 54 70
TCD241CW 517-633 40 50 43 50
TCD301C3 187-253 117 150 N/A N/A
25 TCD301C4 414-506 57 70 N/A N/A
TCD301CW 517-633 46 50 N/A N/A
NOTE:
1. HACR breaker per NEC.
2. Values do not include power exhaust accessory.

*Indicates both downflow and horizontal units.

RT-PRC002-EN 37
Electrical
Data

Table ED-4 — Electrical Characteristics — Power Exhaust Accessory


Accessory
Accessory Operating Amps
Tons Model Number Voltage Phase HP RPM FLA LRA
12½1, 2 BAYPWRX019 208-230 1 3/4 1040 6.6 13.5
15, 17½ BAYPWRX020 460 1 3/4 1040 3.2 8.4
20, 25 BAYPWRX021 575 1 3/4 1040 2.1 5.2

NOTES:
1. 12½ Ton Standard Unit.
2. 12½ Ton High Efficiency Unit.

38 RT-PRC002-EN
Electrical
Data

Table ED-5 — Unit Wiring With Electric Heat (Single Point Connection) — Standard Efficiency

Standard Indoor Motor Oversize Indoor Motor


To Use Heater Heater Control Max Fuse Size or Max Fuse Size or
Tons With Model No. KW Rating1 Stages MCA Max Circuit Breaker2 MCA Max Circuit Breaker2
208/230 Volts Three Phase
AYDHTRF318A 13.5/18.0 1 63/68 80/80 69/76 80/80
12½ TCD150D3 AYDHTRF336A 27.0/36.0 2 108/122 110/125 115/130 125/150
AYDHTRF354A 40.5/54.0 2 154/176 175/200 162/184 175/200
AYDHTRK318A 13.5/18.0 1 78/78 100/100 84/84 100/100
15 TCD180B3 AYDHTRK336A 27.0/36.0 2 108/122 110/125 115/130 125/150
AYDHTRK354A 40.5/54.0 2 154/176 175/200 162/184 175/200
AYDHTRL336A 27.0/36.0 2 115/130 125/150 125/139 125/150
17½ TCD210C3
AYDHTRL354A 40.5/54.0 2 162/184 175/200 171/193 175/200
AYDHTRL336A 27.0/36.0 2 115/130 125/150 125/139 125/150
20 TCD240B3 AYDHTRL354A 40.5/54.0 2 162/184 175/200 171/193 175/200
AYDHTRK372A 54.0/72.0 2 209/238 225/250 218/247 225/250
AYDHTRL336A 27.0/36.0 2 125/139 150/150 — —
25 TCD300B3 AYDHTRL354A 40.5/54.0 2 171/193 175/200 — —
AYDHTRK372A 54.0/72.0 2 218/247 225/250 — —
460 Volts Three Phase
AYDHTRL418A 18.0 1 34 40 37 40
12½ TCD150D4 AYDHTRK436A 36.0 2 61 70 64 70
AYDHTRK454A 54.0 2 88 90 91 100
AYDHTRL418A 18.0 1 39 50 42 50
15 TCD180B4 AYDHTRK436A 36.0 2 61 70 64 70
AYDHTRK454A 54.0 2 88 90 91 100
AYDHTRL436A 36.0 2 64 70 68 70
17½ TCD210C4
AYDHTRL454A 54.0 2 91 100 95 100
AYDHTRL436A 36.0 2 64 70 68 70
20 TCD240B4 AYDHTRL454A 54.0 2 91 100 95 100
AYDHTRK472A 72.0 2 118 125 123 125
AYDHTRL436A 36.0 2 68 70 — —
25 TCD300B4 AYDHTRL454A 54.0 2 95 100 — —
AYDHTRK472A 72.0 2 123 125 — —
575 Volts Three Phase
AYDHTRKW18A 18.0 1 27 30 30 35
12½ TCD150DW AYDHTRMW36A 36.0 2 49 50 51 60
AYDHTRKW54A 54.0 2 70 70 73 80
AYDHTRKW18A 18.0 1 31 40 33 40
15 TCD180BW AYDHTRMW36A 36.0 2 49 50 51 60
AYDHTRKW54A 54.0 2 70 70 73 80
AYDHTRMW36A 36.0 2 51 60 55 60
17½ TCD210CW
AYDHTRLW54A 54.0 2 73 80 77 80
AYDHTRMW36A 36.0 2 51 60 55 60
20 TCD240BW AYDHTRLW54A 54.0 2 73 80 77 80
AYDHTRKW72A 72.0 2 95 100 98 100
AYDHTRMW36A 36.0 2 55 60 — —
25 TCD300BW AYDHTRLW54A 54.0 2 77 80 — —
AYDHTRKW72A 72.0 2 98 100 — —
NOTES:
1. Heater kw ratings are at 208/240 for 208/230V unit, 480V for 460 unit and 600V for 575 unit.
2. HACR type circuit breaker per NEC.

RT-PRC002-EN 39
Electrical
Data

Table ED-5 — Unit Wiring With Electric Heat (Single Point Connection) — Standard Efficiency continued

Standard Indoor Motor Oversize Indoor Motor


To Use Heater Heater Control Max Fuse Size or Max Fuse Size or
Tons With Model No. KW Rating1 Stages MCA Max Circuit Breaker2 MCA Max Circuit Breaker2
380 Volts Three Phase
AYDHTRE418A 11.3 1 43 50 — —
12½ TCD150D4 AYDHTRE436A 22.6 2 55 60 — —
AYDHTRE454A 33.8 2 76 80 — —
AYDHTRE418A 11.3 1 50 60 — —
15 TCD180B4 AYDHTRE436A 22.6 2 55 60 — —
AYDHTRE454A 33.8 2 76 80 — —
AYDHTRG436A 22.6 2 60 70 — —
17½ TCD210C4
AYDHTRG454A 33.8 2 81 90 — —
AYDHTRG436A 22.6 2 65 80 — —
20 TCD240B4 AYDHTRG454A 33.8 2 81 90 — —
AYDHTRH472A 45.1 2 103 110 — —
AYDHTRG436A 22.6 2 70 80 — —
25 TCD300B4 AYDHTRG454A 33.8 2 81 90 — —
AYDHTRH472A 45.1 2 103 100 — —
NOTES:
1. Heater kw ratings are at 380V for 380 unit.
2. HACR type circuit breaker per NEC.

40 RT-PRC002-EN
Electrical
Data

Table ED-6 — Unit Wiring With Electric Heat (Single Point Connection) — Standard Efficiency

Standard Indoor Motor Oversize Indoor Motor


To Use Heater Heater Control Max Fuse Size or Max Fuse Size or
Tons With Model No. KW Rating1 Stages MCA Max Circuit Breaker2 MCA Max Circuit Breaker2
208/230 Volts Three Phase
AYHHTRN318A 13.5/18.0 1 63/68 80/80 69/76 80/80
12½ TCH150D3 AYHHTRN336A 27.0/36.0 2 108/122 110/125 115/130 125/150
AYHHTRN354A 40.5/54.0 2 154/176 175/200 162/184 175/200
AYHHTRN318A 13.5/18.0 1 78/78 100/100 84/84 100/100
15 TCH180B3 AYHHTRP336A 27.0/36.0 2 108/122 110/125 115/130 125/150
AYHHTRP354A 40.5/54.0 2 154/176 175/200 162/184 175/200
AYHHTRQ336A 27.0/36.0 2 115/130 125/150 125/139 125/150
17½ TCH210C3
AYHHTRQ354A 40.5/54.0 2 162/184 175/200 171/193 175/200
AYHHTRN336A 27.0/36.0 2 115/130 125/150 125/139 125/150
20 TCH240B3 AYHHTRN354A 40.5/54.0 2 162/184 175/200 171/193 175/200
AYHHTRN372A 54.0/72.0 2 209/238 225/250 218/247 225/250
AYHHTRN336A 27.0/36.0 2 132/139 150/150 — —
25 TCH300B3 AYHHTRN354A 40.5/54.0 2 171/193 175/200 — —
AYHHTRN372A 54.0/72.0 2 218/247 225/250 — —
460 Volts Three Phase
AYHHTRN418A 18.0 1 34 40 37 40
12½ TCH150D4 AYHHTRN436A 36.0 2 61 70 64 70
AYHHTRP454A 54.0 2 88 90 91 100
AYHHTRN418A 18.0 1 37 50 42 50
15 TCH180B4 AYHHTRP436A 36.0 2 61 70 64 70
AYHHTRP454A 54.0 2 88 90 91 100
AYHHTRQ436A 36.0 2 64 70 68 70
17½ TCH210C4
AYHHTRQ454A 54.0 2 91 100 95 100
AYHHTRN436A 36.0 2 64 70 68 70
20 TCH240B4 AYHHTRN454A 54.0 2 91 100 95 100
AYHHTRN472A 72.0 2 118 125 123 125
AYHHTRN436A 36.0 2 68 70 — —
25 TCH300B4 AYHHTRN454A 54.0 2 95 100 — —
AYHHTRN472A 72.0 2 123 125 — —
575 Volts Three Phase
AYHHTRNW18A 18.0 1 27 30 30 35
12½ TCH150DW AYHHTRPW36A 36.0 2 49 50 51 60
AYHHTRPW54A 54.0 2 70 70 73 80
AYHHTRNW18A 18.0 1 31 40 33 40
15 TCH180BW AYHHTRPW36A 36.0 2 49 50 51 60
AYHHTRPW54A 54.0 2 70 70 73 80
AYHHTRPW36A 36.0 2 51 60 55 60
17½ TCH210CW AYHHTRQW54A 54.0 2 73 80 77 80
AYHHTRMW36A 36.0 2 51 60 55 60
20 TCH240BW AYHHTRNW54A 54.0 2 73 80 77 80
AYHHTRNW72A 72.0 2 95 100 98 100
AYHHTRMW36A 36.0 2 55 60 — —
25 TCH300BW AYHHTRNW54A 54.0 2 77 80 — —
AYHHTRNW72A 72.0 2 98 100 — —
NOTES:
1. Heater kw ratings are at 208/240 for 208/230V unit, 480V for 460 unit and 600V for 575 unit..
2. HACR type circuit breaker per NEC.

RT-PRC002-EN 41
Electrical
Data

Table ED-6 — Unit Wiring With Electric Heat (Single Point Connection) — Standard Efficiency continued

Standard Indoor Motor Oversize Indoor Motor


To Use Heater Heater Control Max Fuse Size or Max Fuse Size or
Tons With Model No. KW Rating1 Stages MCA Max Circuit Breaker2 MCA Max Circuit Breaker2
380 Volts Three Phase
AYHHTRK418A 11.3 1 43 50 — —
12½ TCH150DK AYHHTRK436A 22.6 2 55 60 — —
AYHHTRK454A 33.8 2 76 80 — —
AYHHTRK418A 11.3 1 50 60 — —
15 TCH180BK AYHHTRK436A 22.6 2 55 60 — —
AYHHTRK454A 33.8 2 76 80 — —
AYHHTRL436A 22.6 2 60 70 — —
17½ TCH210CK
AYHHTRL454A 33.8 2 81 90 — —
AYHHTRR436A 22.6 2 65 80 — —
20 TCH240BK AYHHTRR454A 33.8 2 81 90 — —
AYHHTRR472A 45.1 2 103 110 — —
AYHHTRR436A 22.6 2 70 80 — —
25 TCH300BK AYHHTRR454A 33.8 2 81 90 — —
AYHHTRR472A 45.1 2 103 100 — —
NOTES:
1. Heater kw ratings are at 380V for 380 unit.
2. HACR type circuit breaker per NEC.

42 RT-PRC002-EN
Electrical
Data

Table ED-7 — Unit Wiring With Electric Heat (Single Point Connection) — High Efficiency
Standard Indoor Motor Oversize Indoor Motor
To Use Heater Heater Control Max Fuse Size or Max Fuse Size or
Tons With Model No. KW Rating Stages MCA Max Circuit Breaker1 MCA Max Circuit Breaker2
208/230 Volts Three Phase
AYDHTRK318A 13.5/18.0 1 64/68 80/80 70/76 90/90
12½ TCD151C3 AYDHTRK336A 27.0/36.0 2 108/122 110/125 115/130 125/150
AYDHTRK354A 40.5/54.0 2 154/176 175/200 162/184 175/200
AYDHTRK318A 13.5/18.0 1 74/74 100/100 80/80 100/100
15 TCD181C3 AYDHTRK336A 27.0/36.0 2 108/122 110/125 115/130 125/150
AYDHTRK354A 40.5/54.0 2 154/176 175/200 162/184 175/200
AYDHTRL336A 27.0/36.0 2 115/130 125/150 125/139 125/150
17½ TCD211C3 AYDHTRL354A 40.5/54.0 2 162/184 175/200 171/193 175/200
AYDHTRK372A 54.0/72.0 2 209/238 225/250 218/247 225/250
AYDHTRL336A 27.0/36.0 2 115/130 125/150 125/139 125/150
20 TCD241C3 AYDHTRL354A 40.5/54.0 2 162/184 175/200 171/193 175/200
AYDHTRK372A 54.0/72.0 2 209/238 225/250 218/247 225/250
AYDHTRL336A 27.0/36.0 2 125/139 150/150 — —
25 TCD301C3 AYDHTRL354A 40.5/54.0 2 171/193 175/200 — —
AYDHTRK372A 54.0/72.0 2 218/247 225/250 — —

460 Volts Three Phase


AYDHTRL418A 18.0 1 34 40 37 40
12½ TCD151C4 AYDHTRK436A 36.0 2 61 70 64 70
AYDHTRK454A 54.0 2 88 90 91 100
AYDHTRL418A 18.0 1 36 50 38 50
AYDHTRK427A 27.0 2 47 50 — —
15 TCD181C4 AYDHTRK436A 36.0 2 61 70 64 70
AYDHTRK454A 54.0 2 88 90 91 100
AYDHTRL427A 27.0 2 51 60 — —
AYDHTRL436A 36.0 2 64 70 68 70
17½ TCD211C4 AYDHTRL454A 54.0 2 91 100 95 100
AYDHTRK472A 72.0 2 118 125 123 125
AYDHTRL427A 27.0 2 51 60 — —
AYDHTRL436A 36.0 2 64 70 68 70
20 TCD241C4 AYDHTRL454A 54.0 2 91 100 95 100
AYDHTRK472A 72.0 2 118 125 123 125
AYDHTRL436A 36.0 2 68 70 — —
AYDHTRL427A 27.0 2 58 70 — —
25 TCD301C4 AYDHTRL454A 54.0 2 95 100 — —
AYDHTRK472A 72.0 2 123 125 — —

575 Volts Three Phase


TCD151CW AYDHTRKW18A 18.0 1 27 30 30 35
12½ TCD151CW AYDHTRMW36A 36.0 2 49 50 51 60
TCD151CW AYDHTRKW54A 54.0 2 70 70 73 80
TCD181CW AYDHTRKW18A 18.0 1 29 40 31 40
15 TCD181CW AYDHTRMW36A 36.0 2 49 50 31 40
TCD181CW AYDHTRKW54A 54.0 2 70 70 73 80
TCD211CW AYDHTRMW36A 36.0 2 51 60 55 60
17½ TCD211CW AYDHTRLW54A 54.0 2 73 80 77 80
TCD211CW AYDHTRKW72A 72.0 2 95 100 98 100
TCD241CW AYDHTRMW36A 36.0 2 51 60 55 60
20 TCD241CW AYDHTRLW54A 54.0 2 73 80 77 80
TCD241CW AYDHTRKW72A 72.0 2 95 100 98 100
TCD301CW AYDHTRMW36A 36.0 2 55 60 — —
25 TCD301CW AYDHTRLW54A 54.0 2 77 80 — —
TCD301CW AYDHTRKW72A 72.0 2 98 100 — —
NOTES:
1. HACR type circuit breaker per NEC.
2. Values do not include power exhaust accessory.

RT-PRC002-EN 43
Electrical
Data

Table ED-8 — Unit Wiring With Electric Heat (Single Point Connection) — High Efficiency
Standard Indoor Motor Oversize Indoor Motor
To Use Heater Heater Control Max Fuse Size or Max Fuse Size or
Tons With Model No. KW Rating Stages MCA Max Circuit Breaker1 MCA Max Circuit Breaker2
208/230 Volts Three Phase
AYHHTRN318A 13.5/18.0 1 64/68 80/80 70/76 90/90
12½ TCH151C3 AYHHTRP336A 27.0/36.0 2 108/122 110/125 115/130 125/150
AYHHTRP354A 40.5/54.0 2 154/176 175/200 162/184 175/200
AYHHTRM318A 13.5/18.0 1 74/74 100/100 80/80 100/100
15 TCH181C3 AYHHTRM336A 27.0/36.0 2 108/122 110/125 115/130 125/150
AYHHTRM354A 40.5/54.0 2 154/176 175/200 162/184 175/200
AYHHTRN336A 27.0/36.0 2 115/130 125/150 125/139 125/150
17½ TCH211C3 AYHHTRN354A 40.5/54.0 2 162/184 175/200 171/193 175/200
AYHHTRN372A 54.0/72.0 2 209/238 225/250 218/247 225/250
AYHHTRN336A 27.0/36.0 2 115/130 125/150 125/139 125/150
20 TCH241C3 AYHHTRN354A 40.5/54.0 2 162/184 175/200 171/193 175/200
AYHHTRN372A 54.0/72.0 2 209/238 225/250 218/247 225/250
AYHHTRN336A 27.0/36.0 2 125/139 150/150 — —
25 TCH301C3 AYHHTRN354A 40.5/54.0 2 171/193 175/200 — —
AYHHTRN372A 54.0/72.0 2 218/247 225/250 — —

460 Volts Three Phase


AYHHTRN418A 18.0 1 34 40 37 40
12½ TCH151C4 AYHHTRP436A 36.0 2 61 70 64 70
AYHHTRP454A 54.0 2 88 90 91 100
AYHHTRM418A 18.0 1 36 50 38 50
15 TCH181C4 AYHHTRM436A 36.0 2 61 70 64 70
AYHHTRM454A 54.0 2 88 90 91 100
AYHHTRN436A 36.0 2 64 70 68 70
17½ TCH211C4 AYHHTRN454A 54.0 2 91 100 95 100
AYHHTRN472A 72.0 2 118 125 123 125
AYHHTRN436A 36.0 2 64 70 68 70
20 TCH241C4 AYHHTRN454A 54.0 2 91 100 95 100
AYHHTRN472A 72.0 2 118 125 123 125
AYHHTRN436A 36.0 2 68 70 — —
25 TCH301C4 AYHHTRN454A 54.0 2 95 100 — —
AYHHTRN472A 72.0 2 123 125 — —

575 Volts Three Phase


AYHHTRNW18A 18.0 1 27 30 30 35
12½ TCH151CW AYHHTRPW36A 36.0 2 49 50 51 60
AYHHTRPW54A 54.0 2 70 70 73 80
AYHHTRMW18A 18.0 1 29 40 31 40
15 TCH181CW AYHHTRMW36A 36.0 2 49 50 31 40
AYHHTRMW54A 54.0 2 70 70 73 80
AYHHTRMW36A 36.0 2 51 60 55 60
17½ TCH211CW AYHHTRNW54A 54.0 2 73 80 77 80
AYHHTRNW72A 72.0 2 95 100 98 100
AYHHTRMW36A 36.0 2 51 60 55 60
20 TCH241CW AYHHTRNW54A 54.0 2 73 80 77 80
AYHHTRNW72A 72.0 2 95 100 98 100
AYHHTRMW36A 36.0 2 55 60 — —
25 TCH301CW AYHHTRNW54A 54.0 2 77 80 — —
AYHHTRNW72A 72.0 2 98 100 — —
NOTES:
1. HACR type circuit breaker per NEC.
2. Values do not include power exhaust accessory.

44 RT-PRC002-EN
Electrical
Data

Table ED-9— Unit Wiring With Electric Heat (Single Point Connection) — TXV/Face-Split Evaporator Coil Option
(Downflow Only) High Efficiency
Standard Indoor Motor Oversize Indoor Motor
To Use Heater Heater Control Max Fuse Size or Max Fuse Size or
Tons With Model No. KW Rating Stages MCA Max Circuit Breaker2 MCA Max Circuit Breaker1,2
208/230 Volts Three Phase
AYDHTRK318A 13.5/18.0 1 61/68 70/70 68/76 80/80
12½ TCD151C3 AYDHTRK336A 27.0/36.0 2 108/122 110/125 115/130 125/150
AYDHTRK354A 40.5/54.0 2 154/176 175/200 162/184 175/200
AYDHTRK318A 13.5/18.0 1 74/74 100/100 80/80 90/90
15 TCD181C3 AYDHTRK336A 27.0/36.0 2 108/122 110/125 115/130 125/150
AYDHTRK354A 40.5/54.0 2 154/176 175/200 162/184 175/200
AYDHTRL336A 27.0/36.0 2 115/130 125/150 125/139 125/150
17½ TCD211C3 AYDHTRL354A 40.5/54.0 2 162/184 175/200 171/193 175/200
AYDHTRK372A 54.0/72.0 2 209/238 225/250 218/247 225/250
AYDHTRL336A 27.0/36.0 2 115/130 125/150 125/139 125/150
20 TCD241C3 AYDHTRL354A 40.5/54.0 2 162/184 175/200 171/193 175/200
AYDHTRK372A 54.0/72.0 2 209/238 225/250 218/247 225/250
AYDHTRL336A 27.0/36.0 2 125/139 150/150 — —
25 TCD301C3 AYDHTRL354A 40.5/54.0 2 171/193 175/200 — —
AYDHTRK372A 54.0/72.0 2 218/247 225/250 — —

460 Volts Three Phase


AYDHTRL418A 18.0 1 34 35 37 40
12½ TCD151C4 AYDHTRK436A 36.0 2 61 70 64 70
AYDHTRK454A 54.0 2 88 90 91 100
AYDHTRL418A 18.0 1 37 50 39 50
AYDHTRK427A3 27.0 2 47 50 — —
15 TCD181C4 AYDHTRK436A 36.0 2 61 70 64 70
AYDHTRK454A 54.0 2 88 90 91 100
AYDHTRL427A3 27.0 2 51 60 — —
AYDHTRL436A 36.0 2 64 70 68 70
17½ TCD211C4 AYDHTRL454A 54.0 2 91 100 95 100
AYDHTRK472A 72.0 2 118 125 123 125
AYDHTRL427A3 27.0 2 51 60 — —
AYDHTRL436A 36.0 2 64 70 68 70
20 TCD241C4 AYDHTRL454A 54.0 2 91 100 95 100
AYDHTRK472A 72.0 2 118 125 123 125
AYDHTRL427A3 27.0 2 57 70 — —
AYDHTRL436A 36.0 2 68 70 — —
25 TCD301C4 AYDHTRL454A 54.0 2 95 100 — —
AYDHTRK472A 72.0 2 123 125 — —
575 Volts Three Phase
AYDHTRKW18A 18.0 1 27 30 30 30
12½ TCD151CW AYDHTRMW36A 36.0 2 49 50 51 60
AYDHTRKW54A 54.0 2 70 70 73 80
AYDHTRKW18A 18.0 1 30 40 32 40
15 TCD181CW AYDHTRMW36A 36.0 2 49 50 51 60
AYDHTRKW54A 54.0 2 70 70 73 80
AYDHTRMW36A 36.0 2 51 60 55 60
17½ TCD211CW AYDHTRLW54A 54.0 2 73 80 77 80
AYDHTRKW72A 72.0 2 95 100 98 100
AYDHTRMW36A 36.0 2 51 60 55 60
20 TCD241CW AYDHTRLW54A 54.0 2 73 80 77 80
AYDHTRKW72A 72.0 2 95 100 98 100
AYDHTRMW36A 36.0 2 55 60 — —
25 TCD301CW AYDHTRLW54A 54.0 2 77 80 — —
AYDHTRKW72A 72.0 2 98 100 — —
NOTES:
1. HACR type circuit breaker per NEC. 2. Values do not include power exhaust accessory. 3. Do not use with oversized motor.

RT-PRC002-EN 45
Electrical
Data

Table ED-10 — Electrical Characteristics — Evaporator Fan Motor — 60 Cycle


Standard Evaporator Fan Motor Oversized Evaporator Fan Motor
Unit Amps Amps
Tons Model No. No. Volts Phase HP FLA LRA No. Volts Phase HP FLA LRA
TC*150D3, TC*151C3 1 208-230 3 3.00 10.6 81.0 1 208-230 3 5.00 16.7 109.8
12½ TC*150D4, TC*151C4 1 460 3 3.00 4.8 40.5 1 460 3 5.00 7.6 54.9
TC*150DW, TC*151CW 1 575 3 3.00 3.9 31.0 1 575 3 5.00 6.1 41.6
TC*150DK 1 380 3 5.0 9.2 66.5 — — — — — —
TC*180B3, TC*181C3 1 208-230 3 3.00 10.6 81.0 1 208-230 3 5.00 16.7 109.8
15 TC*180B4, TC*181C4 1 460 3 3.00 4.8 40.5 1 460 3 5.00 7.6 54.9
TC*180BW, TC*181CW 1 575 3 3.00 3.9 31.0 1 575 3 5.00 6.1 41.6
TC*180BK 1 380 3 5.0 9.2 66.5 — — — — — —
TC*210C3, TC*211C3 1 208-230 3 5.00 16.7 109.8 1 208-230 3 7.50 17.6 120.4
17½ TC*210C4, TC*211C4 1 460 3 5.00 7.6 54.9 1 460 3 7.50 8.6 74.0
TC*210CW, TC*211CW 1 575 3 5.00 6.1 41.6 1 575 3 7.50 7.0 60.0
TC*210CK 1 380 3 7.5 13.3 83.5 — — — — — —
TC*240B3, TC*241C3 1 208-230 3 5.00 16.7 109.8 1 208-230 3 7.50 17.6 120.4
20 TC*240B4, TC*241C4 1 460 3 5.00 7.6 54.9 1 460 3 7.50 8.6 74.0
TC*240BW, TC*241CW 1 575 3 5.00 6.1 41.6 1 575 3 7.50 7.0 60.0
TC*240BK 1 380 3 7.5 13.3 83.5 — — — — — —
TC*300B3, TC*301C3 1 208-230 3 7.50 17.6 120.4 — — — — — —
25 TC*300B4, TC*301C4 1 460 3 7.50 8.6 74.0 — — — — — —
TC* 300BW, TC*301CW 1 575 3 7.50 7.0 60.0 — — — — — —
TC*300BK 1 380 3 7.5 13.3 83.5 — — — — — —

*Indicates both downflow and horizontal units.

46 RT-PRC002-EN
Electrical (Standard
Data Efficiency)

Table ED-11— Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — Standard Efficiency
Compressor Motors Condenser Fan Motors
Unit Amps1 Amps1
Tons Model No. No. Volts Phase HP2 RPM RLA LRA No. Phase HP FLA LRA
TC*150D3 2 208-230 3 6.00 3450 20.4 156 2 1 .50 3.2 8.8
TC*150D4 2 460 3 6.00 3450 10.8 75 2 1 .50 1.6 3.8
12½ TC*150DW 2 575 3 6.00 3450 8.3 54 2 1 .50 1.3 3.2
TC*150DK 2 380 3 6.0 3450 13.1 70 2 1 .50 1.9 5.2
TC*180B3 2 208-230 3 9.30/5.10 3450 31.9/20.7 253/128 2 1 .50 3.2 8.8
15 TC*180B4 2 460 3 9.30/5.10 3450 16.3/10.0 113/63 2 1 .50 1.6 3.8
TC*180BW 2 575 3 9.30/5.10 3450 13.1/7.4 85/49 2 1 .50 1.3 3.2
TC*180BK 2 380 3 9.3/5.1 3450 19.7/12.1 125/64 2 1 .50 1.9 5.2
TC*210C3 2 208-230 3 9.3/6.0 3450 31.5/20.8 253/156 2 1 1.00 5.5 18.3
17½ TC*210C4 2 460 3 9.3/6.0 3450 15.9/10.0 113/75 2 1 1.00 2.9 9.3
TC*210CW 2 575 3 9.3/6.0 3450 12.8/8.2 85/54 2 1 1.00 2.0 5.7
TC*210CK 2 380 3 9.3/6.0 3450 19.2/12.1 125/70 2 1 1.00 3.5 8.5
TC*240B3 2 208-230 3 9.30 3450 31.7 253 2 1 1.00 5.5 18.3
20 TC*240B4 2 460 3 9.30 3450 16.2 113 2 1 1.00 2.9 9.3
TC*240BW 2 575 3 9.30 3450 13.0 85 2 1 1.00 2.0 5.7
TC*240BK 2 380 3 9.3 3450 19.6 125 2 1 1.00 3.5 8.5
TC*300B3 2 208-230 3 10.00 3450 36.6 278 2 1 1.00 5.5 18.3
25 TC*300B4 2 460 3 10.00 3450 17.9 124 2 1 1.00 2.9 9.3
TC*300BW 2 575 3 10.00 3450 14.9 92 2 1 1.00 2.0 5.7
TC*300BK 2 380 3 10.0 3450 21.7 137 2 1 1.00 3.5 8.5

NOTES:
1. Amp draw for each motor; multiply value by numbers of motors to determine total amps.
2. HP for each compressor.

*Indicates both downflow and horizontal units.

RT-PRC002-EN 47
Electrical
Data (High Efficiency)

Table ED-12 — Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — High Efficiency
Compressor Motors Condenser Fan Motors
Unit Amps1 Amps1
Tons Model No. No. Volts Phase HP2 RPM RLA LRA No. Phase HP FLA LRA
TC*151C3 2 208-230 3 5.70 3450 20.7 156 2 1 .50 3.2 8.8
12½ TC*151C4 2 460 3 5.70 3450 10.0 75 2 1 .50 1.6 3.8
TC*151CW 2 575 3 5.70 3450 8.2 54 2 1 .50 1.3 3.2
TC*181C3 2 208-230 3 9.30/4.50 3450 31.5/16.9 253/124 2 1 .50 3.2 8.8
15 TC*181C4 2 460 3 9.30/4.50 3450 15.1/8.2 113/59.6 2 1 .50 1.6 3.8
TC*181CW 2 575 3 9.30/4.50 3450 12.1/6.6 85/49.4 2 1 .50 1.3 3.2
TC*211C3 2 208-230 3 10.0/5.70 3450 33.3/20.7 278/156 2 1 1.00 5.5 18.3
17½ TC*211C4 2 460 3 10.0/5.70 3450 16.3/10.0 124/75 2 1 1.00 2.9 9.3
TC*211CW 2 575 3 10.0/5.70 3450 13.2/8.2 92/54 2 1 1.00 2.0 5.7
TC*241C3 2 208-230 3 9.30 3450 31.6 253 2 1 1.00 5.5 18.3
20 TC*241C4 2 460 3 9.30 3450 16.1 113 2 1 1.00 2.9 9.3
TC*241CW 2 575 3 9.30 3450 12.9 85 2 1 1.00 2.0 5.7
TC*301C3 2 208-230 3 10.00 3450 37.6 278 2 1 1.00 5.5 18.3
25 TC*301C4 2 460 3 10.00 3450 18.3 124 2 1 1.00 2.9 9.3
TC*301CW 2 575 3 10.00 3450 14.9 92 2 1 1.00 2.0 5.7

NOTES:
1. Amp draw for each motor; multiply value by numbers of motors to determine total amps.
2. HP for each compressor.

Table ED-13 — Electrical Characteristics — Compressor Motor And Condenser Motor — 60 Cycle — TXV/Face-Split Evaporator Coil Option
(Downflow Only) – High Efficiency
Compressor Motors Condenser Fan Motors
Unit Amps1 Amps1
2
Tons Model No. No. Volts Phase HP RPM RLA LRA No. Phase HP FLA LRA
TCD151C3 2 208-230 3 5.7 3450 18.6 156/156 2 1 .50 3.2 8.8
12½ TCD151C4 2 460 3 5.7 3450 9.4 75/75 2 1 .50 1.6 3.8
TCD151CW 2 575 3 5.7 3450 7.4 54/54 2 1 .50 1.3 3.2
TCD181C3 2 208-230 3 9.30/4.50 3450 32.1/16.4 253/124 2 1 .50 3.2 8.8
15 TCD181C4 2 460 3 9.30/4.50 3450 15.6/8.7 113/59.6 2 1 .50 1.6 3.8
TCD181CW 2 575 3 9.30/4.50 3450 12.3/7.4 85/49.4 2 1 .50 1.3 3.2
TCD211C3 2 208-230 3 10.00/5.7 3450 34.8/19.5 278/156 2 1 1.00 5.5 18.3
17½ TCD211C4 2 460 3 10.00/5.7 3450 17.0/10.3 124/75 2 1 1.00 2.9 9.3
TCD211CW 2 575 3 10.00/5.7 3450 13.8/8.1 92/54 2 1 1.00 2.0 5.7
TCD241C3 2 208-230 3 9.0/9.3 3500/3450 30.4/32.6 225/253 2 1 1.00 5.5 18.3
20 TCD241C4 2 460 3 9.0/9.3 3500/3450 16.1/16.8 114/113 2 1 1.00 2.9 9.3
TCD241CW 2 575 3 9.0/9.3 3500/3450 12.5/13.4 80/85 2 1 1.00 2.0 5.7
TCD301C3 2 208-230 3 10.00 3450 36.2 278 2 1 1.00 5.5 18.3
25 TCD301C4 2 460 3 10.00 3450 17.7 124 2 1 1.00 2.9 9.3
TCD301CW 2 575 3 10.00 3450 14.3 92 2 1 1.00 2.0 5.7
NOTES:
1. Amp draw for each motor; multiply value by numbers of motors to determine total amps.
2. HP for each compressor.

*Indicates both downflow and horizontal units.

48 RT-PRC002-EN
Jobsite
Connections

DISCONNECT Zone Sensors —Typical Number Of Wires


SWITCH A— Manual Changeover ...................................... 4
(BY OTHERS)
Manual/Auto Changeover ............................. 5
Manual/Auto Changeover with
Status Indication LED’s .......................... 10
ZONE SENSORS Programmable Night Setback with
Status Indication LED’s ............................ 7
ROOFTOP
UNIT B— 3 Power Wires + 1 Ground Wire (three phase)
2 Power Wires + 1 Ground Wire (single phase)

For specific wiring information, see the installation instructions.


All wiring except power wires is low voltage.
All customer supplied wiring to be copper and must conform to NEC or CEC and local electrical codes. Wiring shown dotted is to be furnished and installed by the customer.

RT-PRC002-EN 49
Typical (12½-25 Ton)
Wiring

50 RT-PRC002-EN
Typical (12½-25 Ton)
Wiring

Typical wiring diagram. For specific


wiring, see individual Service Facts.

RT-PRC002-EN 51
Typical (12½-25 Ton)
Wiring

52 RT-PRC002-EN
Typical (12½-25 Ton)
Wiring

RT-PRC002-EN 53
Dimensional (12½ Ton) High Efficiency
Data (12½, 15, 17½ Ton) Std.
Efficiency

All dimensions are in inches.

NOTE:
Duct flanges mount 7-7/16" down
inside the curb on the 1½" curb
flanges. See recommended duct
dimensions on the next page.
Roofcurb is intended for
downflow use only.

Downflow Unit Clearance

54 RT-PRC002-EN
Dimensional (12½ Ton) High Efficiency
Data (12½, 15, 17½ Ton) Std.
Efficiency

All dimensions are in inches.


1"
Downflow Duct Connections — Field Fabricated
17 7/8"

59 7/16"

26 5/16"
52 1/2" 1"

1 1\2"
PERIMETER
14 1/16" CURB FLANGE
N
7 7/16"
T UR
RE

LY
PP
SU

NOTE:
Duct flanges mount 7-7/16" down
inside the curb on the 1½" curb
flanges.
Roofcurb is intended for
downflow use only.

Horizontal Unit Supply/Return and Unit Clearance

RT-PRC002-EN 55
Dimensional (15-25 Ton) High Efficiency
Data (20, 25 Ton) Std. Efficiency

All dimensions are in inches.

NOTE:
Duct flanges mount 7-7/16" down
inside the curb on the 1½" curb
flanges. See recommended duct
dimensions on the next page.
Downflow Unit Clearance
Roofcurb is intended for
downflow use only.

56 RT-PRC002-EN
Dimensional (15-25 Ton) High Efficiency
Data (20, 25 Ton) Std. Efficiency

All dimensions are in inches. 1"


Downflow Duct Connections — Field Fabricated
19 5/16"

73 7/16"

26 5/16"
66 1/2" 1"

1 1\2"
PERIMETER
14 1/16" CURB FLANGE
N
7 7/16"
T UR
RE
Y
PPL
SU

NOTE:
Duct flanges mount 7-7/16" down
inside the curb on the 1½" curb
flanges.
Roofcurb is intended for
downflow use only.

Horizontal Unit Supply/Return and Unit Clearance

RT-PRC002-EN 57
Dimensional (12½-25 Ton)
Data Accessories

All dimensions are in inches.

Note:
When applying economizer to horizontal units,
connecting ductwork must be run full size to
allow proper operation of Economizer Damper.

Table DD-1
Unit
Model # A B1 C2
1
TC*150, 151-180, 210 17 /2 53¾ 36
TC*181, 211-301 191/2 64¾ 39

NOTES:
1. Horizontal dimension only. Downflow economizer is width of
end panel.
2. Power exhaust is applied on downflow economizer only.

58 RT-PRC002-EN
Dimensional Factory Installed
Data Options (FIOPS)

All dimensions are in inches.

Table DD-2
Unit
Model # A B C
TCD150, 151, 180, 210 423/8 483/8 31
TCD181, 211-301 291/2 56 381/2

RT-PRC002-EN 59
Dimensional Factory Installed
Data Options (FIOPS)

Disconnect Switch
or Circuit Breaker
Fan Failure Switch

Clogged Filter Switch


Powered Or Unpowered
Convenience Outlet

Trane Communication Interface


Hinged Access Door
Black Epoxy Coated
Outdoor Coils

Hinged Access Door

Through the Base


Electrical

High Pressure Cut Out

Supply and/or Return


Smoke Detectors

60 RT-PRC002-EN
Dimensional (12½-25 Ton)
Data

Table DD-3 — Standard Efficiency Units


Condensate Condensate Drain Location
Tons Downflow Only Drain Size Downflow Horizontal
A B C D F G H E J E K
12½, 15, 17½ 267/16 221/2 1811/16 41/4 41/4 627/16 5411/16 1 NPT — 255/8 — 6
20, 25 267/16 283/4 1915/16 41/4 41/4 765/16 6811/16 1 NPT — 263/4 — 53/8

Table DD-4 — High Efficiency Units


Condensate Condensate Drain Location
Tons Downflow Only Drain Size Downflow Horizontal
A B C D F G H E J E K
12½ 267/16 221/2 1811/16 41/4 41/4 627/16 5411/16 1 NPT — 255/8 — 6
15-25 267/16 283/4 1915/16 41/4 41/4 765/16 6811/16 1 NPT — 263/4 — 53/8

RT-PRC002-EN 61
Weights (12½-25 Ton)

Table W-1 — Accessory Net Weights (Lbs)1, 7


Oversized High5 Low5
Economizer Outside Air Damper Power Roof Motor Static Static
Model No. Net Manual Motorized Exhaust4 Curb4 Adder Drive Drive
TCD150D,180B
TCD121,151C, TCD210C 65 32 60 95 205 5 2 2
TCD240B
TCD181,211,241C 80 32 75 95 235 5 2 —
TCD300B.301C 80 32 75 95 235 N/A N/A 2
TCH150D, 180B, 210C
TCH121,151C 50 32 60 — — 5 2 2
TCH240B
TCH181,211,241C 65 32 75 — — 5 2 —
TCH300B,301C 65 32 75 — — N/A N/A 2

Table W-1 Continued


Electric Heaters
Unit All Zone 6-23 KW 27-36 KW 54 KW 72 KW
Model No. Sensors 240/480V2 3 240/480V2 3 240/480V2 3 240/480V2 3
TCD150D, 180B, 210C 1 28/216 31/27 38/32 —
TCD121,151,181C
TCD240B 1 — 33/27 40/32 43/34
TCD211,241C
TCD300B,301C 1 — 33/27 40/32 43/34
TCH150D, 180B, 210C 1 28/216 31/27 38/32 —
TCH121,151,181C
TCH240B 1 — 33/27 40/32 43/34
TCH211, 241C
TCH300B, 301C 1 — 33/27 40/32 43/34

NOTES:
1. Net weight should be added to unit weight when ordering factory installed accessories.
2. For 600V heaters net weights are same as 480V heaters.
3. To estimate shipping weight add 5 lbs to net weight.
4. Downflow only.
5. Not available on all models (See Fan Performance tables for specific models).
6. 9 - 23 KW Heaters not available for TC*210C.
7. TC150-300 factory installed options for economizers, multiply net capacity x .99, EER x .97. For oversized motors, multiply net capacity x .98, EER x .93.
This is provided in compliance with ARI certification program.

62 RT-PRC002-EN
Weights

Table W-2 — Maximum Unit And Corner Weights (Lbs) And Center Of Gravity Dimensions (In.)
Unit Maximum Weights (Lbs) Corner Weights (Lbs)1 Center of Gravity (In.)
Tons Model No. Shipping2 Net A B C D Length Width
12½ TC*150D/TC*151C 1687/1776 1319/1408 446/474 339/349 230/248 303/337 46/45 29/30
15 TC*180B/TC*181C 1866/2297 1498/1838 547/627 358/461 234/317 359/431 42/52 28/35
17½ TC*210C/TC*211C 2022/2380 1654/1921 565/643 425/495 285/341 378/442 46/53 29/35
20 TC*240B/TC*241C 2372/2470 1913/2011 679/692 482/523 312/343 440/453 51/53 34/34
25 TC*300B/ TC*301C 2365/2475 1906/2016 661/695 507/524 320/343 418/454 53/53 33/34

NOTES:
1. Corner weights are given for information only. 12½-25 ton models must be supported continuously by a curb or equivalent frame support.
2. Weights are approximate. Horizontal and downflow unit and corner weights may vary slightly.

*Indicates both downflow and horizontal units.

RT-PRC002-EN 63
Weights

Table W-3 — Factory Installed Options (FIOPS) Net Weights (Lbs)1,2,3


Model
Accessory Number Weight
FIYHEMT003-005 49
High Efficiency Motors
FIYHEMT006-008 36
Hinged Doors FIYHNGE004-009 27
Powered Convenience Outlet FIYCOPO201-205 38
Through the Base Electrical FIYTBUE206-216 23
FIYGARD001,002,004 38
Tool-less Hail Guard
FIYGARD003,005 43
FIYUCB4030-4150 5
Unit Mounted Circuit Breaker
FIYUCB3175-3250 10
Unit Mounted Disconnect FIYUDC4150,6100 5
FIYUDC3250 10

NOTES:
1. Weights for FIOP accessories not listed are <5 lbs.
2. Net weight should be added to unit weight when ordering factory installed accessories.
3. See Table W-1 for standard factory installed economizer, electric heater and oversized motor.

64 RT-PRC002-EN
Mechanical
Specifications

General UnitTop Indoor Fan


The units shall be dedicated downflow The top cover shall be one piece, or Units shall have belt driven, FC,
or horizontal airflow. The operating where seams exist, double hemmed and centrifugal fans with adjustable motor
range shall be between 115°F and 0°F in gasket sealed to prevent water leakage. sheaves. 12½-25 ton units shall have an
cooling as standard from the factory for Filters adjustable idler-arm assembly for quick
all units. Cooling performance shall be Two inch standard filters shall be factory adjustment of fan belts and motor
rated in accordance with ARI testing supplied on all units. An optional 2” sheaves. All motors shall be thermally
procedures. All units shall be factory pleated filter shall be available for 12½-25 protected. Oversized motors will be
assembled, internally wired, fully ton models. available for high static operations. All
charged with R-22, and 100 percent run indoor fan motors meet the U.S. Energy
tested to check cooling operation, fan Compressors Policy Act of 1992 (EPACT).
and blower rotation, and control 12½ to 25 ton standard and high
efficiency units shall have direct-drive, Controls
sequence before leaving the factory.
Wiring internal to the unit shall be hermetic, scroll type compressors with Unit shall be completely factory wired
colored and numbered for simplified centrifugal type oil pumps. Motor shall with necessary controls and contactor
identification. Units shall be UL listed be suction gas-cooled and shall have a pressure lugs or terminal block for power
and labeled, classified in accordance to voltage utilization range of plus or minus wiring. Units shall provide an external
UL 1995/CAN/CSA No. 236-M90 for 10 percent of unit nameplate voltage. location for mounting a fused disconnect
Central Cooling Air Conditioners. Internal overloads shall be provided with device. ReliaTel shall be provided for all
Canadian units shall be CSA Certified. the scroll compressors. All models (with 24 volt control functions.The resident
the exception of 12½ ton standard control algorithms shall make all heating,
Casing efficiency) have crankcase heaters. cooling, and/or ventilating decisions in
Unit casing shall be constructed of zinc response to electronic signals from
coated, heavy gauge, galvanized steel. Refrigerant Circuits
sensors measuring indoor and outdoor
Exterior surfaces shall be cleaned, Each refrigerant circuit shall have
temperatures.The control algorithm
phosphatized, and finished with a independent fixed orifice expansion
maintains accurate temperature control,
weather-resistant baked enamel finish. devices or thermal expansion valve,
minimizes drift from set point, and
Unit’s surface shall be tested 500 hours service pressure ports, and refrigerant
provides better building comfort. A
in a salt spray test in compliance with line filter driers factory-installed as
centralized control shall provide anti-short
ASTM B117. Cabinet construction shall standard. An area shall be provided for
cycle timing and time delay between
allow for all maintenance on one side replacement suction line driers.
compressors to provide a higher level of
of the unit. Service panels shall have Evaporator and Condenser Coils machine protection.
lifting handles and be removed and Internally finned, 3/8" copper tubes
reinstalled by removing not more than mechanically bonded to a configured Accessories
three screws on the 12½-25 ton units aluminum plate fin shall be standard. Electric Heaters
while providing a water and air tight Coils shall be leak tested at the factory to Electric heat modules shall be available
seal. All exposed vertical panels and ensure the pressure integrity. The for installation within basic unit. Electric
top covers in the indoor air section evaporator coil and condenser coil shall heater elements shall be constructed of
shall be insulated with a 1/2 inch, 1 be leak tested to 200 psig and pressure heavy-duty nickel chromium elements
pound density matt-faced, fire- tested to 450 psig. On all dual internally delta connected for 240 volt,
resistant, permanent, odorless, glass compressor models, the evaporator coil wye connected for 480 and 600 volt.
fiber material. The base of the shall be intermingled or face-split Staging shall be achieved through
downflow unit shall be insulated with configuration. ReliaTel. Each heater package shall have
1/2 inch, 1 pound density foil-faced, automatically reset high limit control
Outdoor Fans
closed-cell material. The downflow operating through heating element
The outdoor fan shall be direct-drive,
unit’s base pan shall have no contactors. All heaters shall be
statically and dynamically balanced,
penetrations within the perimeter of individually fused from the factory, where
draw-through in the vertical discharge
the curb other than the raised 11/8 inch required, and shall meet all NEC and CEC
position.The fan motor(s) shall be
high supply/return openings to provide requirements when properly installed.
permanently lubricated and shall have
an added water integrity precaution, if Power assemblies shall provide single-
built-in thermal overload protection.
the condensate drain backs up. The point connection. Electric heat modules
base of the unit shall have provisions shall be UL listed or CSA certified.
for forklift and crane lifting.

RT-PRC002-EN 65
Mechanical
Specifications

Roof Curb - Downflow High Static Drive CO2 Sensing


The roof curb shall be designed to mate Field installed high static drive option shall The CO2 sensor has the ability to monitor
with the downflow unit and provide allow the standard motor to operate with space occupancy levels within the
support and a water tight installation improved external static capabilities. building by measuring the parts per
when installed properly.The roof curb (See Fan Performance tables). million of CO2 (Carbon Dioxide) in the air.
design shall allow field-fabricated Low Static Drive As the CO2 levels increase, the outside air
rectangular supply/return ductwork to be Field installed low static drive option shall damper modulates to meet the CO2
connected directly to the curb. Curb allow the standard motor to operate at space ventilation requirements.The CO2
design shall comply with NRCA lower static performance. (See Fan accessory kit is available as a field
requirements. Curb shall be shipped Performance tables). installed accessory.
knocked down for field assembly and Ventilation Override Accessory
shall include wood nailer strips. Oversized Motors
Factory or field installed oversized With the Ventilation Override Accessory
Economizer - Downflow motors shall be available for high static installed, the unit can be set to transition
This accessory shall be either field or applications. up to 3 different pre-programmed
factory installed.The assembly includes sequences for Smoke Purge,
fully modulating 0-100 percent motor and Control Options Pressurization, and Exhaust.The
dampers, barometric relief, minimum transition occurs when a binary input on
position setting, preset linkage, wiring Trane Communication Interface (TCI) the RTOM is closed (shorted).This would
harness with plug, and fixed dry bulb This option shall be provided to interface typically be a hard wired relay output
control.The barometric relief damper with the Trane Integrated ComfortTM from a smoke detector or fire control
shall be standard with the downflow System. panel.The ventilation override kit is
economizer and shall provide a pressure available as a field installed accessory.
operated damper that shall be gravity Zone Sensors
This option shall be provided to interface Digital Display Zone Sensor
closing and shall prohibit entrance of The Digital LCD (Liquid Crystal Display)
outside air during the equipment “off” with the ReliaTel™ equipped Voyagers
and shall be available in either manual, zone sensor has the look and functionality
cycle. Solid state enthalpy and differential of standard zone sensors.This sensor
enthalpy control shall be factory supplied, automatic programmable with night
setback, with system malfunction lights, includes a digital display of set point
field installed option. adjustment and space temperature in F
or remote sensor options.
Economizer - Horizontal (Fahrenheit) or C (Celsius). Includes FAN
This accessory shall be field installed only. Differential Pressure Switches and SYSTEM buttons (supports the
The horizontal economizer shall be These field installed options allow for service functions of the standard sensor).
available and contain the same features individual fan failure and dirty filter E-squared memory stores last
as the downflow economizer with the indication.The fan failure switch will programmed set points. Requires 24 VAC
exception of barometric relief. disable all unit functions and “flash” the (Volts AC).This sensor should be utilized
Service LED on the zone sensor.The dirty with ReliaTel™ controls.
Remote Potentiometer filter switch will light the Service LED on
The minimum position setting of the the zone sensor and will allow continued Dual Thermistor Remote Zone Sensor
economizer shall be adjusted with this unit operation. This sensor will allow the customer to
accessory. reduce the total number of remote
LonTalk® Communications Interface sensors to obtain space temperature
Powered Exhaust The LonTalk Communications Interface,
The field installed powered exhaust shall averaging. This sensor should be utilized
when installed in a Voyager unit, allows with ReliaTel controls.
provide exhaust of return air, when using the unit to communicate as aTracer™
an economizer, to maintain better building LCI-V device or directly with generic
pressurization. LonTalk Network Building Automation
Manual Outside Air Damper System Controls.
Field installed rain hood and screen shall
provide up to 25 percent outside air.
Motorized Outside Air Dampers
Manually set outdoor air dampers shall
provide up to 50 percent outside air. Once
set, outdoor air dampers shall open to set
position when indoor fan starts.The
damper shall close to the full closed
position when indoor fan shuts down.

66 RT-PRC002-EN
Mechanical
Specifications

Additional Factory Installed Powered or Unpowered Convenience Trane Communications Interface (TCI)
Options (FIOPS) Outlet An option for a factory installedTrane
This option is a GFCI, 120v/15amp, 2 plug, Communication Interface is available to
Electric Heaters convenience outlet, either powered or allow twisted wire pair communication
Factory installed and wired electric unpowered. When the convenience outlet with an Integrated Comfort ™ System.
heaters are available for all 3 phase is powered, a service receptacle Order this option when a combination of
horizontal and downflow 12½ - 25 ton disconnect will be available.The TCI and oversized motor is desired.
models. If ordering theThrough the Base convenience outlet is powered from the
Electrical option with an Electric Heater, Discharge Air Sensing Kit
line side of the disconnect or circuit This kit provides true discharge air
the heater must be factory installed breaker, and therefore will not be sensing in heating models.This sensor is
Through the Base Electrical With affected by the position of the disconnect a status indicator readable through
Disconnect Switch or circuit breaker.This option can only be Tracer™ orTracker™. The kit is functional
Factory installed 3-pole, molded case, ordered when theThrough the Base only with the ReliaTel Options Module.
disconnect switch with provisions for Electrical with either the Disconnect
through the base electrical connections Switch or Circuit Breaker option is Coil Guards
are available.The disconnect switch will ordered.This option is available on all Quality, tooless hail/coil guards shall be
be installed in the unit in a water tight 12½ -25 ton downflow models. either factory or field-installed for
enclosure with access through a swinging condenser coil protection.
Clogged Filter/Fan Failure Switch
door. Factory wiring will be provided from A dedicated differential pressure switch is High Efficiency Motors
the switch to the unit high voltage available to achieve active fan failure This option is available with efficiency
terminal block.The switch will be UL/CSA indication and/or clogged filter indication. ratings from 86.5 up to 91.0. Not available
agency recognized. Note:The disconnect These indications will be registered with for all models.
switch will be sized per NEC and UL either a zone sensor with status indication Supply and/or Return Air Smoke
guidelines but will not be used in place of lights or an Integrated Comfort™ System. Detector
unit overcurrent protection.This option is With this option installed, if smoke is
available on all 12½-25 ton downflow Reference or Comparative Enthalpy
Reference or Comparative Enthalpy detected, all unit operation will be shut
models. down. Reset will be manual at the unit.
option shall be available when a factory
Through the Base Electrical with Circuit installed Downflow Economizer is Return Air Smoke Detectors require
Breaker ordered.This option is available on all minimum allowable airflow when used
This option is a factory installed, thermal 12½-25 ton downflow models. with certain models. See the Installation,
magnetic, molded case, HACR Circuit Operation, and Maintenance (IOM)
Breaker with provisions for through the High Pressure Cutout manual for the models affected and the
base electrical connections.The circuit This option is offered for units that do not minimum allowable airflow required.This
breaker will be installed in a water tight have High Pressure cutout as standard. option is available on all 12½-25 ton
enclosure in the unit with access through The units with High Pressure Cutout as downflow models.
a swinging door. Factory wiring will be standard are TC*180-301B,C.
Black Epoxy Coated Condenser Coil
provided from the switch to the unit high Hinged Access Doors The coil provides corrosion protection to
voltage terminal block.The circuit breaker Sheet metal hinges are available factory condenser coils for seacoast application.
will provide overcurrent protection, be installed on the Filter/Evaporator Access The protection is a factory applied
sized per NEC and UL guidelines, and be Door and the Compressor/Control Access thermoset vinyl coating, bonded to
agency recognized by UL/CSA.This option Door.This option is available on all 12½- normal aluminum fin stock.The uniform
is available on all 12½-25 ton downflow 25 ton downflow models. thickness of the bonded vinyl layer
models. exhibits excellent corrosion protection in
salt spray tests performed in accordance
with ASTM B117.

RT-PRC002-EN 67
Mechanical
Specifications

Frostat
This factory or field installed option is to
be utilized as a safety device. The Frostat
opens when temperatures on the
evaporator coil fall below 10°F. The
temperature will need to rise to 50°F
before closing.This option should be
utilized in low airflow or high outside air
applications.
Novar Unit Controls
Novar rooftop unit controls will be factory
installed and tested.The Novar electronic
thermostat module will interface to the
unit microprocessor and will control the
unit to the desired stage of cooling or
heating.The Novar electronic thermostat
module will monitor the following unit
information: fan failure status, cooling
stage 1 on status, cooling stage 2 on
status, heating on status, clogged filter
status or unit shutdown status, and
discharge air temperature. The Novar
electronic thermostat module will have
the ability to enable the unit mounted
economizer.
Novar Return Air Sensor
This option, when used in conjunction
with Novar Controls, will contain a factory
provided wired zone temperature sensor
located in the return air stream.
Through the Base Utilities Access
An electrical service entrance shall be
provided allowing electrical access for
both control and main power connections
inside the curb and through the base of
the unit. Option will allow for field
installation of liquid-tight conduit and an
external field installed disconnect switch.
Two Inch Permanent Filters
Optional two inch permanent filters shall
be available for 12½-25 ton models.
Thermal Expansion Valve/Face-Split
Evaporator Coil Option
All units shall have a short orifice
refrigerant control metering device. For
more exact refrigerant flow, when using
units in low airflow or high outside air
applications, aThermal Expansion Valve
option shall be available.This option
includes a face-split evaporator coil which
increases part load and latent capacity.

68 RT-PRC002-EN
RT-PRC002-EN 69
70 RT-PRC002-EN
RT-PRC002-EN 71
*High Efficiency Units only

Literature Order Number RT-PRC002-EN


File Number PL-UN-RT-TCD/TCH12½-25TONS-PRC002-EN-12-03
Supersedes RT-PRC002-EN 10-03