Bảng chỉnh định REC 477NP-49 (Cài ngày 03-4-2025) Sửa lại

The document outlines the adjustment details for the REC 477NP/49 recloser at the Ninh Phuoc substation, including protection settings and operational parameters. It specifies the recloser's operational thresholds for overcurrent and ground fault protection, as well as the rationale for the adjustments made. The document also includes the contact information for the author and the date of issuance.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
19 views5 pages

Bảng chỉnh định REC 477NP-49 (Cài ngày 03-4-2025) Sửa lại

The document outlines the adjustment details for the REC 477NP/49 recloser at the Ninh Phuoc substation, including protection settings and operational parameters. It specifies the recloser's operational thresholds for overcurrent and ground fault protection, as well as the rationale for the adjustments made. The document also includes the contact information for the author and the date of issuance.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

TỔNG CÔNG TY ĐIỆN LỰC MIỀN NAM

CÔNG TY ĐIỆN LỰC NINH THUẬN

PHIẾU CHỈNH ĐỊNH RECLOSER REC 477NP/49


THUỘC ĐIỆN LỰC THUẬN NAM

Mô tả chung
Thuộc trạm 110/22kV: NINH PHƯỚC Kiểu bảo vệ: Bảo vệ quá dòng (F50/51, F50/51N)
Phát tuyến: 477NP Hãng sản xuất: BUHEUNG
Chỉ danh Recloser: REC 477NP/49 Nước sản xuất: Hàn Quốc
Loại tủ điều khiển: BR-10R Năm lắp đặt: 2025

Nguyên tắc hoạt động của các chức năng bảo vệ chính của Recloser

Ngưỡng chỉnh định


Tác động
Chức Thời gian trễ (Cảnh báo hoặc cắt MC tại chỗ, liên
Cấp bảo vệ Giá trị động…)
năng (s)
450A
51 I> IEC-VI Theo đặc tuyến phụ thuộc Cắt REC 477NP/49
TMS = 0,4
50-1 I>> 5400A 0 Cắt REC 477NP/49
50-2 I>>> 6000A 0 Cắt REC 477NP/49
280A
51N Io> IEC-VI Theo đặc tuyến phụ thuộc Cắt REC 477NP/49
TMS = 0,6
50N-1 Io>> 4800A 0 Cắt REC 477NP/49
50N-2 Io>>> 5500A 0 Cắt REC 477NP/49
79 ON 5,0s
Trip to
2
Lockout

Nguyên nhân chỉnh định: Thay đổi trị bảo vệ phù hợp với vận hành thực tế

Phạm vi thay đổi: ☐ Chức năng x Ngưỡng chỉnh định ☐ Tín hiệu ☐ Tác động

Người lập phiếu: Trần Hữu Ngọc


Phó Giám đốc
Công ty Điện lực
Điện thoại/Fax: 0905.142.405
Ninh Thuận

Ngày ban hành: 02/04/2025


Nguyễn Hữu Tiên

Trang 1 / 5
BẢNG SETTING RECLOSER REC 477NP/49
THUỘC ĐIỆN LỰC THUẬN NAM

Settings Value Range


Unit Step Help Comment
(BR-10R) (Group1) Min Max
GROUP
PHASE
Detection
Pickup 450 20 1120 1A
Directional Control 2: Bi-Dir 0 2 1 0: For 1: Rev 2: Bi-Dir
Directional Control block 1: Enable 0 1 1 0:Disable 1:Enable
V1 Voltage Threshold 0,20 pu 0,1 1 0,01
Maximum Torque Angle 135 degree 0 359 1
Operations
Lockout 2 1 4 1
Fast 2 0 4 1
Fast Curve
Type 16:[IEC-VI] 1 62 1 11:[IEC-NI] 16:[IEC-VI] 49: [DEF-1s]
Multiplier 0,40 0,05 2 0,01
Time Adder 0 s 0 1 0,01
Min. Response 0 s 0 1 0,01
Max. Response 0 s 0 180 0,1
Reset Time 0 s 0 180 0,01
Delay Curve
Type 16:[IEC-VI] 1 62 1 11:[IEC-NI] 16:[IEC-VI] 49: [DEF-1s]
Multiplier 0,40 0,05 2 0,01
Time Adder 0 s 0 1 0,01
Min. Response 0 s 0 1 0,01
Max. Response 0 s 0 180 0,1
Reset Time 0 s 0 180 0,01
High Current
Trip - Operation Count 1 1 4 1 0: OFF
Trip - Pickup 5400 A 50 10000 1
Trip - Response time 0 s 0 1 0,01
Lockout - Operation Count 1 1 4 1 0: OFF
Lockout - Pickup 6000 A 50 10000 1
Lockout – Response Time 0 s 0 1 0,01
Cold Load Pickup
Pickup Multiple 0: OFF 1 10 1 0: OFF
Restore Time - s 0 18000 1
Curve Type - 1 62 1 11:[IEC-NI] 16:[IEC-VI] 49: [DEF-1s]
Curve Multiplier - 0,05 2 0,01
Curve Time Adder 0 s 0 1 0,01
Curve Min.Response Time 0 s 0 1 0,01
GROUND
Detection
Pickup 280 20 1120 1A
Directional Control 2: Bi-Dir 0 2 1 0: For 1: Rev 2: Bi-Dir
Directional control block 1: Enable 0 1 1 0:Disable 1:Enable
V1 Voltage Threshold 0,20 pu 0,1 1 0,01
Maximum Torque Angle 135 degree 0 359 1
Operations
Lockout 2 1 4 1
Fast 2 0 4 1
Fast Curve
Type 16:[ IEC-VI] 1 62 1 11:[ IEC-NI] 16:[ IEC-VI] 49: [ DEF-1s]
Multiplier 0,60 0,05 2 0,01
Time Adder 0 s 0 1 0,01
Min. Response 0 s 0 1 0,01
Max. Response 0 s 0 180 0,1
Reset Time 0 s 0 180 0,01
Delay Curve
Type 16:[ IEC-VI] 1 62 1 11:[ IEC-NI] 16:[ IEC-VI] 49: [ DEF-1s]

Trang 2 / 5
Settings Value Range
Unit Step Help Comment
(BR-10R) (Group1) Min Max
Multiplier 0,60 0,05 2 0,01
Time Adder 0 s 0 1 0,01
Min. Response 0 s 0 1 0,01
Max. Response 0 s 0 180 0,1
Reset Time 0 s 0 180 0,01
High Current
Trip - Operation Count 1 1 4 1 0: OFF
Trip - Pickup 4800 A 50 10000 1
Trip - Response time 0 s 0 1 0,01
Lockout - Operation Count 1 1 4 1 0: OFF
Lockout - Pickup 5500 A 50 10000 1
Lockout – Response Time 0 s 0 1 0,01
Cold Load Pickup
Pickup Multiple 0: OFF 1 10 1 0: OFF
Restore Time - s 0 18000 1
Curve Type - 1 62 1 11:[IEC-NI] 16:[IEC-VI] 49: [DEF-1s]
Curve Multiplier - 0,05 2 0,01
Curve Time Adder 0 s 0 1 0,01
Curve Min.Response Time 0 s 0 1 0,01
COMMON
Cold Load Common
Natural time 15 s 0 18000 1
Loss of Load Diversity Time 3600 s 0 18000 1
Inrush
Detect Level 20 % 0 50 1 OFF, 0-50: 1%
Detect Time 0,02 s 0,02 1 0,01
Restrain Time 10 s 0 10 0,01
Reclose Interval
Time 1 5 s 0,5 180 0,1
Time 2 2 s 0,5 180 0,1
Time 3 15 s 0,5 180 0,1
Sequence Coordination
Active 0: NO 0 1 1 0: NO 1: YES
Mode Fast TCC 0 1 1 0: Fast TCC 1: Every TCC
Ground Trip Precedence
0: NO 0 1 1 0: NO 1: YES
Reset Time
Reclose Sequence 30 s 0,5 180 0,1
Lockout 3,00 s 0 180 1
SEF
Detection
Operation Mode 0: OFF 0 1 0 0: OFF 1: ON
NEGATIVE SEQUENCE
Detection
Operation Mode 0: OFF 0 1 0 0: OFF 1: ON
Directional Control 2: Bi-Dir 0 2 1 0: For 1: Rev 2: Bi-Dir
Directional control Block 0:Disable 0 1 1 0:Disable 1:Enable
I2 Pickup Current - A 5 690 1
V2 Voltage Threshold - pu 0,1 1 0,01
Maximum Torque Angle - degree 0 359 1
Operations
Lockout - 1 4 1
Fast - 0 4 1
Fast Curve
Definite Time OFF s 0,01 180 0,01 OFF, 0-180: 0,01s
Delay Curve
Definite Time OFF s 0,01 180 0,01 OFF, 0-180: 0,01s
Reclose Interval
Time 1 - s 1 62 1
Time 2 - s 0,05 2 0,01
Time 3 - s 0 1 0,01

Trang 3 / 5
Settings Value Range
Unit Step Help Comment
(BR-10R) (Group1) Min Max
UNBALANCE/LOSS
Voltage Unbalance
Operation Mode 0:Disable 0 1 1 0:Disable 1:Enable
Current Unbalance
Operation Mode 0:Disable 0 1 1 0:Disable 1:Enable
Loss Phase
Operation Mode 0:Disable 0 1 1 0:Disable 1:Enable
UNDER/OVER
Under Voltage Trip
Operation Mode 0:Disable 0 1 1 0:Disable 1:Enable
Over Voltage Trip
Operation Mode 0:Disable 0 1 1 0:Disable 1:Enable
Under Frequency Trip - 50Hz
Operation Mode 0:Disable 0 1 1 0:Disable 1:Enable
Over Frequency Trip - 50Hz
Operation Mode 0:Disable 0 1 1 0:Disable 1:Enable
GLOBAL
SYSTEM 1
System
Frequency 0: 50Hz Hz 20 1120 0: 50Hz 1:60Hz
Rate Voltage (P-P) 22000 V 500 40000 100
Primary Current 1000 A 100 2000 10
Source Selection 3: RST-Negative 0 3 1 0: ABC-Po 1: ABC-Ne 2: RST-Po 3: RST-Ne
Phase Rotation 0: ABC 0 1 1 0: ABC 1: ACB
Debounce
Delay Time for Switch Contacts 0,005 s 0,001 10 0,001
Delay Time for Contact 0,01 s 0,001 10 0,001
Delay Time for Door Contact 5 s 1 180 1
Pulse on Time
Open Time 0,07 s 0,03 10 0,01
Close Time 0,09 s 0,03 10 0,01
Control Key Time 0,5 s 0,05 5 0,01
Interrupting Time 25 ms 0 50 1
Demand Interval 15 minute 2 60 5
Battery Management
Automatic Test Period 180 hour 1 180 1 0: OFF
Low Battery Detection Level 22,00 V 21 24 0,1
Cutoff Level 21,5 V 20 23 0,1
Cutoff Delay Time 60 s 1 180 1
GPS
Use of GPS 0: Not Used 0 1 1 0: Not Used 1: Used
Low Battery Detection Level 00:00 minute -12H +12H 30
Live/Dead Live
Live Line Level 0,7 pu 0,3 0,8 0,01
Dead Line Level 0,3 pu 0,2 0,8 0,01
Delay Time 0,50 s 0,01 180 0,01
SYSTEM 2
Synchronism Check
Phase Difference 30 degree 1 90 1
Delay Time 0,5 s 0,1 180 0,1
Interlocking
Sync.Fail 0:Disable 0 1 1 0:Disable 1:Enable
Live Load 1:Enable 0 1 1 0:Disable 1:Enable
Duty Wear Monitor
VI Type 1: 16kA 0 1 1 0: 12,5kA 1: 16kA
Alarm Level 30 % 0 50 1
Operation Count 51 0 10000 1
Sag & Swell
Sag Level 0: OFF 0 1 0 0: OFF 1: ON
Swell Level 0: OFF 0 1 0 0: OFF 1: ON
THD Alarm

Trang 4 / 5
Settings Value Range
Unit Step Help Comment
(BR-10R) (Group1) Min Max
Voltage 0: OFF 0 1 0 0: OFF 1: ON
Current 0: OFF 0 1 0 0: OFF 1: ON
SYSTEM 3
Loop Control
Operating Mode 0: Feeder 0 2 1 0: Feeder 1: Mid-Point 2: Tie-Point
Used VT - Source 0: 3Phase 0 3 1 0: 3Phase 1:A-Phase 2: B-Phase 3: C-Phase
Used VT - Load 0: 3Phase 0 3 1 0: 3Phase 1:A-Phase 2: B-Phase 3: C-Phase
Feeding Direction 0: Both 0 2 1 0: Both 1: to Load 2: to Source
Deadbus Delay Time 30 s 0 1000 1
Voltage Regain Delay 10 s 0 180 1
Livebus Delay Time 10 s 0 180 1
Switch onto Fault Delay 30 s 0 180 1
Auto Open Delay 10 s 0 180 1
Return to Normal Setting Delay 10 s 0 180 1
Setting Group
Active 0: Group 1 0 3 1 0: Group 1 1: Group 2 2: Group 3 3: Group 4
Alternate Operating Delay Time 10 s 0 180 1
VT Fail Check
Mode 0:Disable 0 1 1 0:Disable 1:Enable
Distance to Fault
Operating Mode 0:Disable 0 1 1 0:Disable 1:Enable

Trang 5 / 5