01. Bảng chỉnh định REC 473NT1-93-A01 (Cooper FXD) Mới

The document details the settings and operational parameters for the REC 473NT1/93/A01 recloser used at the Ninh Thuận 1 substation. It includes information on overcurrent protection settings, operational sequences, and adjustments made to align with practical operations. The document is issued by the Southern Power Corporation and includes contact details for the responsible personnel.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
76 views6 pages

01. Bảng chỉnh định REC 473NT1-93-A01 (Cooper FXD) Mới

The document details the settings and operational parameters for the REC 473NT1/93/A01 recloser used at the Ninh Thuận 1 substation. It includes information on overcurrent protection settings, operational sequences, and adjustments made to align with practical operations. The document is issued by the Southern Power Corporation and includes contact details for the responsible personnel.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

TỔNG CÔNG TY ĐIỆN LỰC MIỀN NAM

CÔNG TY ĐIỆN LỰC NINH THUẬN

PHIẾU CHỈNH ĐỊNH RECLOSER REC 473NT1/93/A01


THUỘC ĐIỆN LỰC THUẬN NAM

Mô tả chung
Thuộc trạm 110/22kV: NINH THUẬN 1 Kiểu bảo vệ: Bảo vệ quá dòng (F50/51, F50/51N)
Phát tuyến: 473NT1 Hãng sản xuất: COOPER
Chỉ danh Recloser: REC 473NT1/93/A01 Nước sản xuất Trung Quốc
Loại tủ điều khiển: Cooper FXD Năm lắp đặt: 2014

Nguyên tắc hoạt động của các chức năng bảo vệ chính của Recloser

Ngưỡng chỉnh định


Tác động
Chức Thời gian trễ
Cấp bảo vệ Giá trị (Cảnh báo hoặc cắt MC tại chỗ, liên động…)
năng (s)
450A
51 I> IEC-VI Theo đặc tuyến phụ thuộc Cắt REC 473NT1/93/A01
TMS = 0,28
50-1 I>> 3420A 0 Cắt REC 473NT1/93/A01
50-2 I>>> 4500A 0 Cắt REC 473NT1/93/A01
180A
51N Io> IEC-VI Theo đặc tuyến phụ thuộc Cắt REC 473NT1/93/A01
TMS = 0,35
50N-1 Io>> 3330A 0 Cắt REC 473NT1/93/A01
50N-2 Io>>> 4000A 0 Cắt REC 473NT1/93/A01
79 ON 5,0s
Trip to
2
Lockout

Nguyên nhân chỉnh định: Thay đổi trị bảo vệ phù hợp với vận hành thực tế

Phạm vi thay đổi: ☐ Chức năng x Ngưỡng chỉnh định ☐ Tín hiệu ☐ Tác động

Người lập phiếu: Trần Hữu Ngọc


Phó Giám đốc
Công ty Điện lực
Điện thoại/Fax: 0905.142.405
Ninh Thuận

Ngày ban hành: 13/03/2025


Nguyễn Hữu Tiên

Trang 1 / 6
BẢNG SETTING RECLOSER REC 473NT1/93/A01
THUỘC ĐIỆN LỰC THUẬN NAM

Parameters Value Value


Unit Range
(Cooper - FXD) (Normal) (Alter #1)
Overcurrent Protection
Phase
Enable Phase Trip Enable Enable Disable/ Enable
Min Trip Current 450 #N/A A 10,00 3200,00
Overcurrent Alarm 450 #N/A A 5,00 3200,00
Alarm Time Delay 10000 10000 ms 0 3600000
Ground
Enable Ground Enable Enable Disable/ Enable
Min Trip Current 180 #N/A A 10,00 3200,00
Overcurrent Alarm 180 #N/A A 5,00 3200,00
Alarm Time Delay 10000 10000 ms 0 3600000
Negative Sequence
Enable Negative Sequence Disable Disable Disable/ Enable

TCC1 Phase
...IEC-INVERSE/ IEC-VERY INV/ IEC-EXTREME
Curve Type IEC-VERY INV #N/A
INV/ IEC-D/ IEC-E…
Time Mult Enable Enabe Enabe Disable/ Enable
Time Multiplier 0,28 #N/A 0.10 25.00
Time Adder Enable Disable Disable Disable/ Enable
Time Adder 0 0 ms 0 30000
MRTA Enable Disable Disable Disable/ Enable
Minimum Response Time
10 10 ms 10 1000
Adder
Hight Current Trip Enable Enabe Enabe Disable/ Enable
Hight Current Trip
7,60 #N/A 1.00 32.00
Multiplier
Hight Current Trip Delay 10 #N/A ms 10 150

TCC1 Ground
...IEC-INVERSE/ IEC-VERY INV/ IEC-EXTREME
Curve Type IEC-VERY INV #N/A
INV/ IEC-D/ IEC-E…
Time Mult Enable Enabe Enabe Disable/ Enable
Time Multiplier 0,35 #N/A 0.10 25.00
Time Adder Enable Disable Disable Disable/ Enable
Time Adder 0 0 ms 0 30000
MRTA Enable Disable Disable Disable/ Enable
Minimum Response Time 10 10 ms 10 1000
Hight Current Trip Enable Enabe Enabe Disable/ Enable
Hight Current Trip 18,50 #N/A 1.00 32.00
Hight Current Trip Delay 10 #N/A ms 10 150

TCC2 Phase

TCC2 Ground

Reclosing
Phase
Open Interval #1 5000 3000 ms 300 3600000
Open Interval #2 - #N/A ms 300 3600000
Ground
Open Interval #1 5000 3000 ms 300 3600000
Open Interval #2 - #N/A ms 300 3600000

Trang 2 / 6
Parameters Value Value
Unit Range
(Cooper - FXD) (Normal) (Alter #1)
Above Min Trip Drop 60 60 s 0 300
Reset Target After Rec 3000 3000 ms 3000 3600000
Reset Time 180000 180000 ms 200 3600000

Operations Sequence
Phase
Operation #1 TCC1 TCC1 TCC1/ TCC2
Operation #2 TCC1 TCC1 TCC1/ TCC2
Operation #3 - #N/A TCC1/ TCC2
Ground
Operation #1 TCC1 TCC1 TCC1/ TCC2
Operation #2 TCC1 TCC1 TCC1/ TCC2
Operation #3 - #N/A TCC1/ TCC2
Sequence Coord
Enable Sequence Coord Disable Enable Disable/ Enable
Sequence Coord Max ope 1 1 1/2/3
Number Of Trip Operation 2 #N/A 1/2/3/ 4

Hot line Tag


Phase
Delay 0 0 ms 0 100000
Ground
Delay 0 0 ms 0 100000

Hight Current Lockout (HCL)


Phase
Enable HCL Op1 Enable #N/A Disable/ Enable
Enable HCL Op2 - #N/A Disable/ Enable
Hight Current Lockout 4500A #N/A A 20 20000
Ground
Enable HCL Op1 Enable #N/A Disable/ Enable
Enable HCL Op2 - #N/A Disable/ Enable
Hight Current Lockout 4000A #N/A A 20 20000

Cold load pickup (CLPU)


Enable Cold load pickup Enable Enable Disable/ Enable
Phase
Min Trip Current 450 #N/A A 10,00 3200
...IEC-INVERSE/ IEC-VERY INV/ IEC-EXTREME
TCC IEC-VERY INV #N/A
INV/ IEC-D/ IEC-E…
CLPU Mult Enable Enable Enable Disable/ Enable
Time Multiplier 0,10 #N/A 0.10 25.00
CLPU Add Enable Disable Enable Disable/ Enable
Time Adder 0 0 ms 0 30000
CLPU MRTA Enable Disable Enable Disable/ Enable
Minimum Response Time 10 10 ms 10 1000
CLPU HCT Enable Disable Enable Disable/ Enable
Hight Current Trip - #N/A 1.00 32.00
Hight Current Trip Delay 10 10 ms 10 150
CLPU HCL Enable Disable Disable Disable/ Enable
Hight Current lockout - - A 20 20000
Ground
Min Trip Current 180 #N/A A 10,00 3200
...IEC-INVERSE/ IEC-VERY INV/ IEC-EXTREME
TCC IEC-VERY INV #N/A
INV/ IEC-D/ IEC-E…
CLPU Mult Enable Enable Enable Disable/ Enable
Time Multiplier 0,30 #N/A 0.10 25.00
CLPU Add Enable Disable Enable Disable/ Enable
Time Adder 0 0 ms 0 30000

Trang 3 / 6
Parameters Value Value
Unit Range
(Cooper - FXD) (Normal) (Alter #1)
CLPU MRTA Enable Disable Enable Disable/ Enable
Minimum Response Time 10 10 ms 10 1000
CLPU HCT Enable Disable Enable Disable/ Enable
Hight Current Trip - #N/A 1.00 32.00
Hight Current Trip Delay 10 10 ms 10 150
CLPU HCL Enable Disable Disable Disable/ Enable
Hight Current lockout - - A 20 20000

CLPU Operations to lockout 1 1 1/ 2/ 3/ 4


CLPU Reclose Intervals - - ms 300 3600000
CLPU Activation Time 3000 3000 ms 0 3600000

Sensitive Earth
Enable Sensitive Earth Disable Disable Disable/ Enable

Low Set
Phase
Enable Low Set Phase Disable Disable Disable/ Enable
Min Trip Current 500 - A 10.00 1600.00
Min Trip Delay 1000 - ms 0 100000
Ground
Enable Low Set Phase Disable Disable Disable/ Enable
Min Trip Current 150 - A 10.00 1600.00
Min Trip Delay 1000 - ms 0 100000
Neg Seq
Enable Low Set Phase Disable Disable Disable/ Enable
Min Trip Current - - A 10.00 1600.00
Min Trip Delay - - ms 0 100000

VOLTAGE
Comm Voltage Enable Disable Disable Disable/ Enable
UNDER VOLTAGE
Level 1 Enable Disable Disable Disable/ Enable
Level 1 Pickup - - kV
Level 1 Time Delay - - ms 0 3600000
Level 2 Enable Disable Disable Disable/ Enable
Level 2 Pickup - - kV 0 200
Level 2 Time Delay - - ms 0 3600000
Level 3 Enable Disable Disable Disable/ Enable
Level 3 Pickup - - kV 0 200
Level 3 Time Delay - - ms 0 3600000
Three Phase/ Any Single Phase/ Single Phase With 3-
Overvoltage Trip Mode - -
Phase Inhibit
OVER VOLTAGE
Level 1 Enable Disable Disable Disable/ Enable
Level 1 Pickup - - kV 0 200
Level 1 Time Delay - - ms 0 3600000
Level 2 Enable Disable Disable Disable/ Enable
Level 2 Pickup - - kV 0 200
Level 2 Time Delay - - ms 0 3600000
Level 3 Enable Disable Disable Disable/ Enable
Level 3 Pickup - - kV 0 200
Level 3 Time Delay - - ms 0 3600000
AUTO RESTORATION FROM UNDER/ OVER LOADSHED
Enable Restoration Disable Disable Disable/ Enable
Mode - - Three Phase/ Any Single Phase
Voltage Hight Limit - - kV 0 200
Voltage Low Limit - - kV 0 200

Trang 4 / 6
Parameters Value Value
Unit Range
(Cooper - FXD) (Normal) (Alter #1)
Schedule Time - - ms 100 3600000
Transient Time - - ms 100 3600000
Abort Time - - ms 100 3600000
Supervision Using Disable Disable Disable/ Enable
UNDER VOLTAGE ALARM
Volt Alarm Enable Disable Disable Disable/ Enable
Alarm Pickup - - kV 0.00 200.00
Alarm Time Delay - - ms 0 3600000
Alarm Mode - - Three Phase/ Any Single Phase
OVER VOLTAGE ALARM
Volt Alarm Enable Disable Disable
Alarm Pickup - - kV 0.00 200.00
Alarm Time Delay - - ms 0 3600000
Alarm Mode - - Three Phase/ Any Single Phase

FREQUENCY
Comm Frequency Enable Disable Disable Disable/ Enable
Minimum Voltage - - kV 0 200
Level 1 Enable Disable Disable Disable Enable
Level 1 Pickup - - Hz 46 64
Level 1 Delay - - ms 0 3600000
Level 2 Enable Disable Disable Disable Enable
Level 2 Pickup - - Hz 46 64
Level 2 Delay - - ms 0 3600000
Level 3 Enable Disable Disable Disable Enable
Level 3 Pickup - - Hz 46 64
Level 3 Delay - - ms 0 3600000
Level 4 Enable Disable Disable Disable Enable
Level 4 Pickup - - Hz 46 64
Level 4 Delay - - ms 0 3600000
Level 5 Enable Disable Disable Disable Enable
Level 5 Pickup - - Hz 46 64
Level 5 Delay - - ms 0 3600000
Level 6 Enable Disable Disable Disable Enable
Level 6 Pickup - - Hz 46 64
Level 6 Delay - - ms 0 3600000
AUTO RESTORATION FROM UNDER FREQUENCY
Enable Restoration Disable Disable Disable Enable
Schedule Time - - ms 100 3600000
Transient Time - - ms 100 3600000
Abort Time - - ms 100 3600000
High Limit Frequency - - Hz 46 64
Low Limit Frequency - - Hz 46 64
Supervision Using
Disable Disable Disable/ Enable
Volatage & Freq
Enable Load Supervision Disable Disable Disable/ Enable
Supervision pickupp - - A 0 3200

DIRECTIONAL
PHASE
Directional Type No supervision No supervision No supervision/ Forward/ Reverse
Maximum Torque Angle - - Degrees 0 90
Torque Angle Width - - Degrees 0 90
GROUND
Directional Type No supervision No supervision No supervision/ Forward/ Reverse
Maximum Torque Angle - - Degrees 0 90
Torque Angle Width - - Degrees 0 90
NEGATIVE SEQUENCE

Trang 5 / 6
Parameters Value Value
Unit Range
(Cooper - FXD) (Normal) (Alter #1)
Directional Type No supervision No supervision No supervision/ Forward/ Reverse
Maximum Torque Angle - - Degrees 0 90
Torque Angle Width - - Degrees 0 90

Trang 6 / 6