Adjustments for REC 473NT1/94 Settings

The document details the configuration and operational settings for the REC 473NT1/94 recloser used at the Ninh Thuận 1 substation, including protection settings for overcurrent and ground fault conditions. It outlines the parameters for various protective functions, including time delays, pickup values, and operational modes. The adjustments are made to align with actual operational requirements and ensure effective protection of the electrical system.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
52 views6 pages

Adjustments for REC 473NT1/94 Settings

The document details the configuration and operational settings for the REC 473NT1/94 recloser used at the Ninh Thuận 1 substation, including protection settings for overcurrent and ground fault conditions. It outlines the parameters for various protective functions, including time delays, pickup values, and operational modes. The adjustments are made to align with actual operational requirements and ensure effective protection of the electrical system.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

TỔNG CÔNG TY ĐIỆN LỰC MIỀN NAM

CÔNG TY ĐIỆN LỰC NINH THUẬN

PHIẾU CHỈNH ĐỊNH RECLOSER REC 473NT1/94


THUỘC ĐIỆN LỰC THUẬN NAM
Mô tả chung
Thuộc trạm 110/22kV: NINH THUẬN 1 Kiểu bảo vệ: Bảo vệ quá dòng (F50/51, F50/51N)
Phát tuyến: 473NT1 Hãng sản xuất: ENTEC
Chỉ danh Recloser: REC 473NT1/94 Nước sản xuất Hàn Quốc
Loại tủ điều khiển: EVRC2A-NT610 Năm lắp đặt: 2021

Nguyên tắc hoạt động của các chức năng bảo vệ chính của Recloser
Ngưỡng chỉnh định
Tác động
Chức Thời gian trễ (Cảnh báo hoặc cắt MC tại chỗ, liên
Cấp bảo vệ Giá trị động…)
năng (s)
450A
51 I> IEC-VI Theo đặc tuyến phụ thuộc Cắt REC 473NT1/94
TMS = 0,28
50-1 I>> 3400A 0 Cắt REC 473NT1/94
50-2 I>>> 4500A 0 Cắt REC 473NT1/94
180A
51N Io> IEC-VI Theo đặc tuyến phụ thuộc Cắt REC 473NT1/94
TMS = 0,35
50N-1 Io>> 3300A 0 Cắt REC 473NT1/94
50N-2 Io>>> 4000A 0 Cắt REC 473NT1/94
79 ON 5,0s
Trip to
2
Lockout
Cắt REC 473NT1/94
46BC ON 3,0s (I2/I1) ≥ 30%
Imin = 50A
Imax = 450A

Nguyên nhân chỉnh định: Thay đổi trị bảo vệ phù hợp với vận hành thực tế

Phạm vi thay đổi: ☐ Chức năng x Ngưỡng chỉnh định ☐ Tín hiệu ☐ Tác động

Người lập phiếu: Trần Hữu Ngọc


Phó Giám đốc
Công ty Điện lực
Điện thoại/Fax: 0905.142.405
Ninh Thuận
Ngày ban hành: 13/03/2025
Nguyễn Hữu Tiên

Trang 1 / 6
BẢNG SETTING RECLOSER REC 473NT1/94
THUỘC ĐIỆN LỰC THUẬN NAM

Settings Value Range


Unit Step Help Comment
(EVRC2A-NT610) (Group1) Min Max
RECLOSER
AUTO RECLOSING
FUNCTION
Reclose Fun 1: ENABLE 0 1 1 0: DISABLE 1: ENABLE
OPERATIONS-PHASE
Lockout Shots 2 1 5 1
Sh1 Fast Active 1: YES 0 1 1 0: NO 1: YES
Sh2 Fast Active 1: YES 0 1 1 0: NO 1: YES
Sh3 Fast Active 0: NO 0 1 1 0: NO 1: YES
OPERATIONS-GROUND
Lockout Shots 2 1 5 1
Sh1 Fast Active 1: YES 0 1 1 0: NO 1: YES
Sh2 Fast Active 1: YES 0 1 1 0: NO 1: YES
Sh3 Fast Active 0: NO 0 1 1 0: NO 1: YES
OPERATIONS-SEF
Lockout Shots 2 1 5 1
OPERATIONS-NEG SEQ'
INTERVALS-PHASE/NEG SEQ'
Reclose 1 5,0 s 0,1 1800 0,01
Reclose 2 - s 1 1800 0,01
INTERVALS-GROUND
Reclose 1 5,0 s 0,1 1800 0,01
Reclose 2 - s 1 1800 0,01
INTERVALS-SEF
INTERVALS-OTHERS
Reset T(A.R) 30 s 0,1 600 0,01
Reset T(L.O) 10 s 0,1 600 0,01
Reclose Wait 60 s 0,1 600 0,01 0: OFF
TIME OC-PHA
(+)/ (-) PHASE FAST
Function 2:TR&AL 0 3 1 0:DISABLE 1:TRIP 2:TR&AL 3:ALARM
Pickup 450 A 10 1600 1
Curve 16:[ IEC-VI] 1 62 1 11:[ IEC-NI] 16:[ IEC-VI] 49: [ DEF-1s]
Time Dial 0,28 0,01 15 0,01
Time Add. 0 s 0 600 0,01
M.R.T 0 s 0 10 0,01
Reset Method 0 0 1 1 0: INST 1: LINEAR
Low Set DT 0: OFF s 0,01 600 0,01 0: OFF
(+)/ (-) PHASE DELAY
TIME OC-GND
(+)/ (-) GROUND FAST
Function 2:TR&AL 0 3 1 0:DISABLE 1:TRIP 2:TR&AL 3:ALARM
Pickup 180 A 10 1600 1
Curve 16:[ IEC-VI] 1 62 1 11:[ IEC-NI] 16:[ IEC-VI] 49: [ DEF-1s]
Time Dial 0,35 0,01 15 0,01
Time Add. 0 s 0 600 0,01
M.R.T 0 s 0 10 0,01
Reset Method 0 0 1 1 0: INST 1: LINEAR
Low Set DT 0: OFF s 0,01 600 0,01 0: OFF
(+)/ (-) GROUND DELAY
TIME OC-NEQ

Trang 2 / 6
Settings Value Range
Unit Step Help Comment
(EVRC2A-NT610) (Group1) Min Max
(+)/ (-)NEG SEQ' FAST
Function 0:DISABLE 0 3 1 0:DISABLE 1:TRIP 2:TR&AL 3:ALARM
(+)/ (-)NEG SEQ' DELAY
Function 0:DISABLE 0 3 1 0:DISABLE 1:TRIP 2:TR&AL 3:ALARM
INST OC-PHA (Instantanenous overcurrent phase)
(+)/ (-) INST OC-PHA
Function 1: ENABLE 0 1 1 0: DISABLE 1: ENABLE
Pickup 3400 A 10 20000 1
Time Delay 0 s 0 600 0,01
Active Shot 1 1 5 1
INST OC-GND (Instantanenous overcurrent ground)
(+)/ (-) INST OC-GND
Function 1: ENABLE 0 1 1 0: DISABLE 1: ENABLE
Pickup 3300 A 10 20000 1
Time Delay 0 s 0 600 0,01
Active Shot 1 1 5 1
INST OC-SEF (Instantanenous overcurrent SEF)
(+)/ (-) INST OC-SEF
Function 0:DISABLE 0 3 1 0:DISABLE 1:TRIP 2:TR&AL 3:ALARM
INST OC-NEQ (Instantanenous overcurrent NEQ)
(+)/ (-) INST OC-NEQ
Function 0: DISABLE 0 1 1 0: DISABLE 1: ENABLE
INST OCL-PHA (Instantanenous overcurrent lockout phase)
(+)/ (-)INST OCL-PHA
Function 1: ENABLE 0 1 1 0: DISABLE 1: ENABLE
Pickup 4500A A 10 20000 1
Time Delay 0 s 0 600 0,01
Active Shot 1 1 5 1
INST OCL-GND (Instantanenous overcurrent lockout ground)
(+)/ (-) INST OCL-GND
Function 1: ENABLE 0 1 1 0: DISABLE 1: ENABLE
Pickup 4000A A 10 20000 1
Time Delay 0 s 0 600 0,01
Active Shot 1 1 5 1
INST OCL-NEQ (Instantanenous overcurrent lockout NEQ)
(+)/ (-)INST OCL-NEQ
Function 0: DISABLE 0 1 1 0: DISABLE 1: ENABLE
INRUSH RES'/CLPU
INRUSH RESTRAINT-FUNCTION
Phase 1: ENABLE 0 1 1 0: DISABLE 1: ENABLE
Ground 1: ENABLE 0 1 1 0: DISABLE 1: ENABLE
SEF 0: DISABLE 0 1 1 0: DISABLE 1: ENABLE
Neg Seq' 0: DISABLE 0 1 1 0: DISABLE 1: ENABLE
INRUSH RESTRAINT-PICKUP CURRENT
Phase 450 A 10 20000 1
Ground 180 A 10 20000 1
INRUSH RESTRAINT-RESTORE MIN. TIME
P-Function 0: DISABLE 0 1 1 0: DISABLE 1: ENABLE
G-Function 0: DISABLE 0 1 1 0: DISABLE 1: ENABLE
RMT Time - s 0,01 600 0,01
INRUSH RES' RESET
P-Reset I 450 A 10 1600 1
G-Reset I 180 A 10 1600 1
Reset Time 2 s 0,01 600 0,01

Trang 3 / 6
Settings Value Range
Unit Step Help Comment
(EVRC2A-NT610) (Group1) Min Max
INRUSH RESTRAINT-PHASE CURVE
Curve 16: [ IEC-VI] 1 62 1 11: [ IEC-NI] 16: [ IEC-VI]…
Time Dial 0,1 s 0,01 15 0,01
Time Add. 0 s 0 600 0,01
M.R.T 0 s 0 10 0,01
Reset Method 0 0 1 1 0: INST 1: LINEAR
INRUSH RESTRAINT-GROUND CURVE
Curve 16:[ IEC-VI] 1 62 1 11: [ IEC-NI] 16: [ IEC-VI]…
Time Dial 0,3 s 0,01 15 0,01
Time Add. 0 s 0 600 0,01
M.R.T 0 s 0 10 0,01
Reset Method 0 0 1 1 0: INST 1: LINEAR
INRUSH RESTRAINT-NEG SEQ' CURVE
INRUSH RESTRAINT-OTHERS
Outage Time 2 s 0,01 600 0,01
Make Use 'I' 1: YES 0 1 1 0: NO 1: YES
COLD LOAD PICKUP
Function 0: DISABLE 0 1 1 0: DISABLE 1: ENABLE
HARMONIC BLOCK
2ND BLOCKING
Function 0: DISABLE 0 1 1 0: DISABLE 1: ENABLE
5TH BLOCKING
Function 0: DISABLE 0 1 1 0: DISABLE 1: ENABLE
DIRECTION
PHASE
Type 0: NONE 0 2 1 0: NONE 1: FORWARD 2: REVERSE
GROUND
Type 0: NONE 0 2 1 0: NONE 1: FORWARD 2: REVERSE
SEF
NEG SEQ'
BROKEN CONDUCT
BROKEN CONDUCT
Function 1: ENABLE 0 1 1 0: DISABLE 1: ENABLE
Pickup(I2/I1) 30 % 1 100 1
Min.I 50 A 1 630 1 0: OFF
Time Delay 3 s 0 600 0,01
Max.I 450 A 10 1600 1 0: OFF
VOLTAGE
UNDER VOLT1
Function 0: DISABLE 0 3 1 0:DISABLE 1:TRIP 2:TR&AL 3:ALARM
UNDER VOLT2
Function 0: DISABLE 0 3 1 0:DISABLE 1:TRIP 2:TR&AL 3:ALARM
UV RESTORATION
Function 0: DISABLE 0 1 1 0: DISABLE 1: ENABLE
OVER VOLT1
Function 0: DISABLE 0 3 1 0:DISABLE 1:TRIP 2:TR&AL 3:ALARM
OVER VOLT2
Function 0: DISABLE 0 3 1 0:DISABLE 1:TRIP 2:TR&AL 3:ALARM
NEUTRAL OVERVOLT1
Function 0: DISABLE 0 3 1 0:DISABLE 1:TRIP 2:TR&AL 3:ALARM
NEUTRAL OVERVOLT2
Function 0: DISABLE 0 3 1 0:DISABLE 1:TRIP 2:TR&AL 3:ALARM
OV RESTORATION
Function 0: DISABLE 0 1 1 0: DISABLE 1: ENABLE

Trang 4 / 6
Settings Value Range
Unit Step Help Comment
(EVRC2A-NT610) (Group1) Min Max
FREQUENCY
UNDER FREQUENCY1
Function 0: DISABLE 0 1 1 0: DISABLE 1: ENABLE
UNDER FREQUENCY2
Function 0: DISABLE 0 1 1 0: DISABLE 1: ENABLE
OVER FREQUENCY1
Function 0: DISABLE 0 1 1 0: DISABLE 1: ENABLE
OVER FREQUENCY2
Function 0: DISABLE 0 1 1 0: DISABLE 1: ENABLE
FREQUENCY DECAY
Function 0: DISABLE 0 1 1 0: DISABLE 1: ENABLE
AUTO RESTORATION
Function 0: DISABLE 0 1 1 0: DISABLE 1: ENABLE
POWER
FUNCTION
Function 0: DISABLE 0 3 1 0:DISABLE 1:TRIP 2:TR&AL 3:ALARM
FORWARD POWER
Pickup1 0 MW 0 300 0,01 0: OFF
Pickup2 0 MW 0 300 0,01 0: OFF
DIRECTION POWER
Min.Power1 0 MW -300 300 0,01 0: OFF
Min.Power2 0 MW -300 300 0,01 0: OFF
DEMAND
PHASE
Function 0: DISABLE 0 1 1 0: DISABLE 1: ENABLE
GROUND
Function 0: DISABLE 0 1 1 0: DISABLE 1: ENABLE
NEG SEQ
Function 0: DISABLE 0 1 1 0: DISABLE 1: ENABLE
ACTIVE POWER
Function 0: DISABLE 0 1 1 0: DISABLE 1: ENABLE
REACTIVE POWER
Function 0: DISABLE 0 1 1 0: DISABLE 1: ENABLE
Z0 ADMITTANCE-
Z0 ADMITTANCE
Function 0: DISABLE 0 1 1 0: DISABLE 1: ENABLE
HOTLINE TAG
PHASE
Curve 16:[ IEC-VI] 1 62 1 49: [ DEF-1S]
Time Dial 0,28 0,01 15 0,01
Time Add. 0 s 0 600 0,01
M.R.T 0 s 0 10 0,01
Reset Method 0 0 1 1 0: INST 1: LINEAR
GROUND
Curve 16:[ IEC-VI] 1 62 1 49: [ DEF-1S]
Time Dial 0,35 0,01 15 0,01
Time Add. 0 s 0 600 0,01
M.R.T 0 s 0 10 0,01
Reset Method 0 0 1 1 0: INST 1: LINEAR
SEF
NEG SEQ'
USER CURVE
OTHERS
OTHERS

Trang 5 / 6
Settings Value Range
Unit Step Help Comment
(EVRC2A-NT610) (Group1) Min Max
Seq'Coordinate' 0: OFF 0 1 1 0: OFF 1: ON
SECTIONALIZER
PICKUP CURRENT
Phase 0: OFF A 10 1600 1 0: OFF
Ground 0: OFF A 10 1600 1 0: OFF
SEF 0: OFF A 0,1 160 0,1 0: OFF
Neg Seq' 0: OFF A 10 1600 1 0: OFF
INRUSH DURATION T
AUTO SECTION
MONITORING
PHASE DIFFERENCE
Function 0: DISABLE 0 1 1 0: DISABLE 1: ENABLE
Dead Line Lv 0,5 xVT 0,1 1,4 0,01
Live Line Lv 0,8 xVT 0,1 1,4 0,01
Max Volt Diff 0,1 xVT 0,1 1,4 0,01
Max Angle Diff 30 deg 1 100 1
Max Freq. Diff 2,00 Hz 0,01 5 0,01
Check Phase 0: ALL 0 3 1 0: ALL 1: A 2: B 3: C
Time Delay 1 s 0 600 0,01
SYNCHRO' CHECK
Function 0: DISABLE 0 1 1 0: DISABLE 1: ENABLE
Max. Volt 1,2 xVT 0,1 1,4 0,01
Min. Volt 0,3 xVT 0,1 1,4 0,01
Max Volt Diff 0,1 xVT 0,1 1,4 0,01
Angle Diff1 30 deg 20 80 0,1 0: OFF
Angle Diff2 30 deg 20 80 0,1 0: OFF
Slip Freq. 0,1 Hz 0,5 5 0,1
Sync Phase 4: AB 1 6 1 0: NONE 1: A 2: B 3: C 4: AB 5: BC 6: CA
Compens' Angle 0 deg 0 330 30
Load-V Factor 1 0,5 2 0,01
Closing Time 1000 ms 0 600 0,1
CL Wait Time 1000 s 1 600 1
OPEN PHASE
Function 0: DISABLE 0 1 1 0: DISABLE 1: ENABLE
LIVE LINE BLOCK
Function 0: DISABLE 0 1 1 0: DISABLE 1: ENABLE
FAULT LOCATOR
Function 0: DISABLE 0 1 1 0: DISABLE 1: ENABLE
Feeder Length 0 km 1 99,9 0,1
Z0(Real) 0,00 ohm 0,01 99,99 0,01
Z1(Real) 0,00 ohm 0,01 99,99 0,01
Z0(Imag) 0,00 ohm 0,01 99,99 0,01
Z1(Imag) 0,00 ohm 0,01 99,99 0,01
LOAD CURR' ALARM
Function 0: DISABLE 0 1 1 0: DISABLE 1: ENABLE
POWER FACTOR
Function 0: DISABLE 0 1 1 0: DISABLE 1: ENABLE

Trang 6 / 6