Section 405 outlines the requirements for concrete quality, mixing, and placing, emphasizing the need for specified compressive strength and durability. It details the procedures for selecting concrete proportions based on field experience or trial mixtures, as well as testing and acceptance criteria for concrete strength. The section also includes guidelines for evaluating low-strength test results and ensuring structural integrity.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
12 views
SECTION 405
Section 405 outlines the requirements for concrete quality, mixing, and placing, emphasizing the need for specified compressive strength and durability. It details the procedures for selecting concrete proportions based on field experience or trial mixtures, as well as testing and acceptance criteria for concrete strength. The section also includes guidelines for evaluating low-strength test results and ensuring structural integrity.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 16
SECTION 405 - CONCRETE
QUALITY, MIXING AND PLACING
405.1 Notations f'c = specified compressive strength of concrete, MPa f'cr = required average compressive strength of concrete used as the basis for selection of concrete proportions, MPa fct = average splitting tensile strength of lightweight aggregate concrete, MPa s = standard deviation, MPa ss = sample standard deviation, MPa 405.2 General 405.2.1 Concrete shall be proportioned to provide an average compressive strength, f’cr as prescribed in Section 405.4.2, as well as satisfy the durability criteria of Section 404. Concrete shall be produced to minimize frequency of strengths below f'c as prescribed in Section 405.7.3.3. For concrete designed and constructed in accordance with the Code, fc′ shall not be less than 17 MPa. 405.2.2 Requirements for f'c shall be based on tests of cylinders made and tested as prescribed in Section 405.7.3. 405.2.3 Unless otherwise specified, f'c shall be based on 28- day tests. If other than 28 days, test age for f'c shall be as indicated in design drawings or specifications. 405.2.4 Where design criteria in Sections 408.7.1, 412.3.4(4), and 422.6.6, provide for use of a splitting tensile strength value of concrete, laboratory tests shall be made in accordance with Specification for Lightweight Aggregates for Structural Concrete (ASTM C 330) to establish value of fct corresponding to specified values of f'c. 405.2.5 Splitting tensile strength tests shall not be used as a basis for field acceptance of concrete. 405.2.6 Steel fiber-reinforced concrete shall conform to ASTM C1116. The minimum fc′ for steel fiber-reinforced concrete shall conform to 405.2.1. 405.3 Selection of Concrete Proportions 405.3.1Proportions of materials for concrete shall be established to provide: 1. Workability and consistency to permit concrete to be worked readily into forms and around reinforcement under conditions of placement to be employed without segregation or excessive bleeding. CHAPTER 4 - Concrete 4-21 National Structural Code of the Philippines 6th Edition Volume 1 2. Resistance to special exposures as required by Section 404. 3. Conformance with strength test requirements of Section 405.7. 405.3.2 Where different materials are to be used for different portions of proposed work, each combination shall be evaluated. 405.3.3 Concrete proportions, including water-cementitious materials ratio, shall be established on the basis of field experience and/or trial mixtures with materials to be employed (see Section 405.4), except as permitted in Section 405.5 or required by Section 404. 405.4 Proportioning on the Basis of Field Experience and Trial Mixtures, or Both 405.4.1 Sample Standard Deviation 405.4.1.1 Where a concrete production facility has test records not more than 12 months old, a sample standard deviation, ss, shall be established. Test records from which a standard deviation ss, is calculated: 1. Must represent materials, quality control procedures and conditions similar to those expected, and changes in materials and proportions within the test records shall not have been more restricted than those for proposed work. 2. Must represent concrete produced to meet a specified strength or strengths f'c within 7 MPa of that specified for proposed work. 3. Must consist of at least 30 consecutive tests or two groups of consecutive tests totaling at least 30 tests as defined in Section 405.7.2.4, except as provided in Section 405.4.1.2. 405.4.1.2 Where a concrete production facility does not have test records meeting requirements of Section 405.4.1.1(3), but does have test records not more than 12 months old based on 15 to 29 consecutive tests, a standard sample deviation ss, shall be established as the product of the calculated sample standard deviation and the modification factor of Table 405-1. To be acceptable, test records shall meet the requirements of Section 405.4.1.1, Items 1 and 2, and represent only a single record of consecutive tests that span a period of not less than 45 calendar days. Table 405-1 Modification Factor for Standard Deviation When Less Than 30 Tests are Available Number of Tests 1 Modification Factor for Standard Deviation2 Less than 15 Use Table 405-2 15 1.16 20 1.08 25 1.03 30 or more 1.00 1 Interpolate for intermediate number of tests. 2 Modified standard deviation to be used to determine required average strength f'cr from Section 405.4.2.1 405.4.2 Required Average Strength 405.4.2.1 Required average compressive strength f'cr used as the basis for selection of concrete proportions shall be the larger of Equation (405-1) or (405-2) using the sample standard deviation, ss, calculated in accordance with Section 405.4.1.1 or 405.4.1.2. f'c ≤ 35MPa: f'cr = f'c + 1.34 ss (405-1) f'cr = f'c + 2.33 ss – 3.5 (405-2) Use the larger value computed from Eq. 405-1 and 405-2, or: f'c >35MPa: f'cr = f'c + 1.34 ss (405-1) f'cr = 0.90 f'c + 2.33 ss (405-3) Use the larger value computed from Eq. 405-1 and 405-3. 405.4.2.2 When a concrete production facility does not have field strength test records for calculation of standard deviation meeting requirements of Section 405.4.1.1 or 405.4.1.2, required average strength f'cr shall be determined from Table 405-2 and documentation of average strength shall be in accordance with requirements of Section 405.4.3. Table 405-2 Required Average Compressive Strength When Data are not Available to Establish a Standard Deviation Specified Compressive Strength, f'c, MPa Required Average Compressive Strength, f'cr, MPa Less than 21 MPa f'c + 7.0 21 ≤ f'c ≤ 35 f'c + 8.3 Over 35 1.10f'c + 5.0 4-22 CHAPTER 4 - Concrete Association of Structural Engineers of the Philippines 405.4.3 Documentation of Average Strength. Documentation that proposed concrete proportions will produce an average compressive strength equal to or greater than required average compressive strength (see Section 405.4.2) shall consist of a field strength test record, several strength test records, or trial mixtures. 405.4.3.1 When test records in accordance with Sections 405.4.1.1 and 405.4.1.2, are used to demonstrate that proposed concrete proportions will produce the required average strength f'cr (see Section 405.4.2), such records shall represent materials and conditions similar to those expected. Changes in materials, conditions and proportions within the test records shall not have been more restricted than those for proposed work. For the purpose of documenting average strength potential, test records consisting of less than 30 but not less than 10 consecutive tests may be used, provided test records encompass a period of time not less than 45 days. Required concrete proportions may be established by interpolation between the strengths and proportions of two or more test records each of which meets other requirements of this section. 405.4.3.2 When an acceptable record of field test results is not available, concrete proportions established from trial mixtures meeting the following restrictions shall be permitted: 1. Combination of materials shall be those for proposed work. 2. Trial mixtures having proportions and consistencies required for proposed work shall be made using at least three different water-cementitious materials ratios or cementitious materials contents that will produce a range of strengths encompassing the required average strength f'cr, and meet the durability requirements of Section 404. 3. Trial mixtures shall be designed to produce a slump within ±20 mm of maximum permitted, and for airentrained concrete, within ±0.5 percent of maximum allowable air content, or within the tolerance specified for the proposed Work. 4. For each water-cementitious materials ratio or cementitious materials content, at least three test cylinders for each test age shall be made and cured in accordance with "Method of Making and Curing Concrete Test Specimens in the Laboratory" (ASTM C 192). Cylinders shall be tested at 28 days or at test age designated for determination of f'c. 5. From results of cylinder tests, a curve shall be plotted showing relationship between water-cementitious materials ratio or cementitious materials content and compressive strength at designated test age. 6. Maximum water-cementitious materials ratio or minimum cementitious materials content for concrete to be used in proposed work shall be that shown by the curve to produce the average strength required by Section 405.4.2, unless a lower water-cementitious materials ratio or higher strength is required by Section 404. 405.5 Proportioning without Field Experience or Trial Mixtures 405.5.1 If data required by Section 405.4 are not available, concrete proportions shall be based upon other experience or information, if approved by the engineer. The required average compressive strength f'cr of concrete produced with materials similar to those proposed for use shall be at least 8.5 MPa greater than the specified compressive strength, f'c. This alternative shall not be used for specified compressive strength greater than 35 MPa. 405.5.2 Concrete proportioned by Section 405.5 shall conform to the durability requirements of Section 404 and to compressive strength test criteria of Section 405.7. 405.6 Average Strength Reduction As data become available during construction, it shall be permitted to reduce the amount by which f'cr must exceed the specified value of f'c, provided: 1. Thirty or more test results are available and average of test results exceeds that required by Section 405.4.2.1, using a sample standard deviation calculated in accordance with Section 405.4.1.1, or 2. Fifteen to 29 test results are available and average of test results exceeds that required by Section 405.4.2.1, using a sample standard deviation calculated in accordance with Section 405.4.1.2, and 3. Special exposure requirements of Section 404 are met. 405.7 Evaluation and Acceptance of Concrete 405.7.1 Concrete shall be tested in accordance with the requirements of Section 405.7.2 through 405.7.5. Qualified field testing technicians shall perform tests on fresh concrete at the job site, prepare specimens required for curing under field conditions, prepare specimens required for testing in the laboratory, and record the temperature of the fresh concrete when preparing specimens for strength tests. Qualified laboratory technicians shall perform all required laboratory tests. CHAPTER 4 - Concrete 4-23 National Structural Code of the Philippines 6th Edition Volume 1 405.7.2 Frequency of Testing 405.7.2.1 Samples for strength tests of each class of concrete placed each day shall be taken not less than once a day, or not less than once for each 120 m3 of concrete, or not less than once for each 500 m2 of surface area for slabs or walls. 405.7.2.2 On a given project, if the total volume of concrete is such that the frequency of testing required by Section 405.7.2.1 would provide less than five strength tests for a given class of concrete, tests shall be made from at least five randomly selected batches or from each batch if fewer than five batches are used. 405.7.2.3 When total quantity of a given class of concrete is less than 40 m3, strength tests are not required when evidence of satisfactory strength is submitted to and approved by the engineer. 405.7.2.4 A strength test shall be the average of the strengths of two cylinders made from the same sample of concrete and tested at 28 days or at test age designated for determination of f'c. 405.7.3 Laboratory-Cured Specimens 405.7.3.1 Samples for strength tests shall be taken in accordance with "Method of Sampling Freshly Mixed Concrete" (ASTM C 172). 405.7.3.2 Cylinders for strength tests shall be molded and laboratory cured in accordance with "Practice for Making and Curing Concrete Test Specimens in the Field" (ASTM C 31M) and tested in accordance with "Test Method for Compressive Strength of Cylindrical Concrete Specimens" (ASTM C 39M). 405.7.3.3 Strength level of an individual class of concrete shall be considered satisfactory if both the following requirements are met: 1. Every arithmetic average of any three consecutive strength tests (see Section 405.7.2.4) equals or exceeds f'c ; 2. No individual strength test (average of two cylinders) falls below f'c by more than 3.5 MPa, when f’c is 35 MPa or less; or by more than 0.10f’c when f’c is more than 35 MPa. 405.7.3.4 If either of the requirements of Section 405.7.3.3 are not met, steps shall be taken to increase the average of subsequent strength test results. Requirements of Section 405.7.5 shall be observed if the requirement of Item 2 of Section 405.7.3.3 is not met. 405.7.4 Field-Cured Specimens 405.7.4.1 If required by the engineer-of-record, results of strength tests of cylinders cured under field conditions shall be provided. 405.7.4.2 Field-cured cylinders shall be cured under field conditions, in accordance with "Practice for Making and Curing Concrete Test Specimens in the Field" (ASTM C 31M). 405.7.4.3 Field-cured test cylinders shall be molded at the same time and from the same samples as laboratory-cured test cylinders. 405.7.4.4 Procedures for protecting and curing concrete shall be improved when strength of field-cured cylinders at test age designated for determination of f'c is less than 85 percent of that of companion laboratory-cured cylinders. The 85 percent limitation shall not apply if field-cured strength exceeds f'c by more than 3.5 MPa. 405.7.5 Investigation of Low-Strength Test Results 405.7.5.1 If any strength test (see Section 405.7.2.4) of laboratory-cured cylinders falls below specified values of f'c by more than 3.5 MPa (see Section 405.7.3.3, Item 2) or if tests of field-cured cylinders indicate deficiencies in protection and curing (see Section 405.7.4.4), steps shall be taken to ensure that load-carrying capacity of the structure is not jeopardized. 405.7.5.2 If the likelihood of low-strength concrete is confirmed and calculations indicate that load-carrying capacity is significantly reduced, tests of cores drilled from the area in question in accordance with "Method of Obtaining and Testing Drilled Cores and Sawed Beams of Concrete" (ASTM C 42M) shall be permitted. In such cases, three cores shall be taken for each strength test more than 3.5 MPa below specified value of f'c. 405.7.5.3 If concrete in the structure will be dry under service conditions, cores shall be air dried (temperatures 15ºC to 25ºC, relative humidity less than 60 percent) for seven days before test and shall be tested dry. If concrete in the structure will be more than superficially wet under service conditions, cores shall be immersed in water for at least 40 hours and be tested wet. 405.7.5.4 Concrete in an area represented by core tests shall be considered structurally adequate if the average of three cores is equal to at least 85 percent of f'c and if no single core is less than 75 percent of f'c. Additional testing of cores extracted from locations represented by erratic core strength results shall be permitted. 4-24 CHAPTER 4 - Concrete Association of Structural Engineers of the Philippines 405.7.5.5 If criteria of Section 405.7.5.4 are not met, and if structural adequacy remains in doubt, the engineer of record shall be permitted to order a strength evaluation in accordance with Section 420 for the questionable portion of the structure, or take other appropriate action. 405.7.6 Steel Fiber-Reinforced Concrete 405.7.6.1 Acceptance of steel fiber-reinforced concrete used in beams in accordance with 411.6.6.1(6) shall be determined by testing in accordance with ASTM C1609. In addition, strength testing shall be in accordance with 405.7.1. 405.7.6.2 Steel fiber-reinforced concrete shall be considered acceptable for shear resistance if conditions (1), (2), and (3) are satisfied: 1. The weight of deformed steel fibers per cubic meter of concrete is greater than or equal to 60 kg. 2. The residual strength obtained from flexural testing in accordance with ASTM C1609 at a mid-span deflection of 1/300 of the span length is greater than or equal to 90 percent of the measured first-peak strength obtained from a flexural test or 90 percent of the strength corresponding to fr from Eq. (409-10), whichever is larger; and 3. The residual strength obtained from flexural testing in accordance with ASTM C1609 at a mid-span deflection of 1/150 of the span length is greater than or equal to 75 percent of the measured first-peak strength obtained from a flexural test or 75 percent of the strength corresponding to fr from Eq. (409-10), whichever is larger. 405.8 Preparation of Equipment and Place of Deposit 405.8.1 Preparation before concrete placement shall include the following: 1. All equipment for mixing and transporting concrete shall be clean; 2. All debris shall be removed from spaces to be occupied by concrete; 3. Forms shall be properly coated; 4. Masonry filler units that will be in contact with concrete shall be well drenched; 5. Reinforcement shall be thoroughly clean of deleterious coatings; 6. Water shall be removed from place of deposit before concrete is placed unless a tremie is to be used or unless otherwise permitted by the engineer; 7. All laitance and other unsound material shall be removed before additional concrete is placed against hardened concrete. 405.9 Mixing 405.9.1 All concrete shall be mixed until there is a uniform distribution of materials and shall be discharged completely before mixer is recharged. 405.9.2 Ready-mixed concrete shall be mixed and delivered in accordance with requirements of "Specifications for Ready-Mixed Concrete" (ASTM C 94M) or "Specifications for Concrete Made by Volumetric Batching and Continuous Mixing" (ASTM C 685M). 405.9.3 Job-mixed concrete shall be mixed in accordance with the following: 1. Mixing shall be done in a batch mixer of an approved type; 2. Mixer shall be rotated at a speed recommended by the manufacturer; 3. Mixing shall be continued for at least 1-1/2 minutes 4. After all materials are in the drum, unless a shorter time is shown to be satisfactory by the mixing uniformity tests of "Specifications for Ready-Mixed Concrete" (ASTM C 94M); 5. Materials handling, batching and mixing shall conform to applicable provisions of "Specifications for Ready- Mixed Concrete" (ASTM C 94M); 6. A detailed record shall be kept to identify: a. Number of batches produced; b. Proportions of materials used; c. Approximate location of final deposit in structure; d. Time and date of mixing and placing. 405.10 Conveying 405.10.1 Concrete shall be conveyed from mixer to place of final deposit by methods that will prevent separation or loss of materials. 405.10.2 Conveying equipment shall be capable of providing a supply of concrete at site of placement without separation of ingredients and without interruptions sufficient to permit loss of plasticity between successive increments. CHAPTER 4 - Concrete 4-25 National Structural Code of the Philippines 6th Edition Volume 1 405.11 Depositing 405.11.1 Concrete shall be deposited as nearly as practicable in its final position to avoid segregation due to re-handling or flowing. 405.11.2 Concreting shall be carried on at such a rate that concrete is at all times plastic and flows readily into spaces between reinforcement. 405.11.3 Concrete that has partially hardened or been contaminated by foreign materials shall not be deposited in the structure. 405.11.4 Re-tempered concrete or concrete that has been remixed after initial set shall not be used unless approved by the engineer-of-record. 405.11.5 After concreting is started, it shall be carried on as a continuous operation until placing of a panel or section, as defined by its boundaries or predetermined joints, is completed, except as permitted or prohibited by Section 406.4. 405.11.6 Top surfaces of vertically formed lifts shall be generally level. 405.11.7 When construction joints are required, joints shall be made in accordance with Section 406.4. 405.11.8 All concrete shall be thoroughly consolidated by suitable means during placement and shall be thoroughly worked around reinforcement and embedded fixtures and into corners of forms. 405.12 Curing 405.12.1 Concrete (other than high-early-strength) shall be maintained above 10ºC and in a moist condition for at least the first seven days after placement, except when cured in accordance with Section 405.12.3. 405.12.2 High-early-strength concrete shall be maintained above 10ºC and in a moist condition for at least the first three days, except when cured in accordance with Section 405.12.3. 405.12.3 Accelerated Curing 405.12.3.1 Curing by high-pressure steam, steam at atmospheric pressure, heat and moisture or other accepted processes, may be employed to accelerate strength gain and reduce time of curing. 405.12.3.2 Accelerated curing shall provide a compressive strength of concrete at the load stage considered at least equal to required design strength at that load stage. 405.12.3.3 Curing process shall be such as to produce concrete with a durability at least equivalent to the curing method of Section 405.12.1 or 405.12.2. 405.12.4 When required by the engineer, supplementary strength tests in accordance with Section 405.7.4 shall be performed to assure that curing is satisfactory. 405.13 Hot Weather Requirements During hot weather, proper attention shall be given to ingredients, production methods, handling, placing, protection and curing to prevent excessive concrete temperatures or water evaporation that may impair required
Investigation of The Physical-Mechanical Properties and Durability of High-Strength Concrete With Recycled PET As A Partial Replacement For Fine Aggregates