Bus Bar Calculation For 4000a, 65ka
Bus Bar Calculation For 4000a, 65ka
Ref: Industrial Power Engineering and application Handbook (as applicable for IEC,ANSI,NEMA,ISO and IS)
Example 28.2
2
100 = (1.166/100) x ( 65000/A) x (1+ 0.00363 x 85) x 1
A= 812 mm² for Aluminium
812mm² Minimum size of conductor for a required fault level 65KA for 1 Sec.
B. THERMAL RATING:
DERATING FACTOR ON ACCOUNT OF HIGHER AMBIENT
TEMPERATURE Or RESTRICTED TEMPERATURE RISE
( Ref: Industrial Power Engineering and application Handbook Cheptor No. 28,
Figure No.28.7, Table No.28.3 and Page No. 870/871)
( Ref: Industrial Power Engineering and application Handbook Table No.28.6 and Page No. 874)
Page 1 of 2
AC Current rating for 3bars of Al. Flats 150x6mm considered = 3975A
Therefore Current rating for Two pair 3bars of Al. Flats 150x6mm considered = 3975A x 2=7950Amp.
Therefore busbar and its arrangement is suitable for Connected load 3150A and a fault level of 65kA for 1 sec.
50 + (3150Amp. / 4690Amp.)ª x35 =65˙ C which is within the limit of 85˙ C [50+35].
Summary: Hence the designed bus bar for BUS DUCT is OK & within the safe limit.
Page 2 of 2