PowerProtect DD - Data Domain Field Component Replacement-Replacement Procedures - DD6400-1
PowerProtect DD - Data Domain Field Component Replacement-Replacement Procedures - DD6400-1
Topic
Data Domain Field Component Replacement
Selections
Replacement Procedures: DD6400
If you find any errors in this procedure or have comments regarding this application, send
email to [email protected]
Copyright © 2024 Dell Inc. or its subsidiaries. All Rights Reserved. Dell Technologies, Dell, EMC, Dell EMC and other
trademarks are trademarks of Dell Inc. or its subsidiaries. Other trademarks may be trademarks of their respective owners.
The information in this publication is provided “as is.” Dell Inc. makes no representations or warranties of any kind with
respect to the information in this publication, and specifically disclaims implied warranties of merchantability or fitness for a
particular purpose.
Use, copying, and distribution of any software described in this publication requires an applicable software license.
This document may contain certain words that are not consistent with Dell's current language guidelines. Dell plans to
update the document over subsequent future releases to revise these words accordingly.
This document may contain language from third party content that is not under Dell's control and is not consistent with
Dell's current guidelines for Dell's own content. When such third party content is updated by the relevant third parties, this
document will be revised accordingly.
Dell Technologies – Restricted Use – Confidential & Subject to NDA
Page 1 of 181
Contents
Preliminary Activity Tasks ...................................................................................................3
Read, understand, and perform these tasks.................................................................................................3
Page 2 of 181
Preliminary Activity Tasks
This section may contain tasks that you must complete before performing this procedure.
3. Table 1 lists tasks, cautions, warnings, notes, and/or knowledgebase (KB) solutions that you need to
be aware of before performing this activity. Read, understand, and when necessary perform any
tasks contained in this table and any tasks contained in any associated knowledgebase solution.
Table 1 List of cautions, warnings, notes, and/or KB solutions related to this activity
• Use caution when extending the controller from the rack. Pull the controller out of the rack slowly and
verify that it has been securely installed in the rails.
Page 3 of 181
Dell Technologies – Restricted Use – Confidential & Subject to NDA
Page 4 of 181
DD6400 FRU Procedures
Page 5 of 181
Dell EMC PowerProtect DD6400
System Maintenance and Upgrade Guide
May 2024
Rev. 04
Page 6 of 181
Notes, cautions, and warnings
NOTE: A NOTE indicates important information that helps you make better use of your product.
CAUTION: A CAUTION indicates either potential damage to hardware or loss of data and tells you how to avoid
the problem.
WARNING: A WARNING indicates a potential for property damage, personal injury, or death.
© 2021 - 2024 Dell Inc. or its subsidiaries. All rights reserved. Dell Technologies, Dell, and other trademarks are trademarks of Dell Inc. or its
subsidiaries. Other trademarks may be trademarks of their respective owners.
Page 7 of 181
Contents
Figures..........................................................................................................................................8
Tables.......................................................................................................................................... 12
Contents 3
Page 8 of 181
Extend the system from the cabinet............................................................................................................................40
Remove the system cover.............................................................................................................................................. 40
Remove the cooling fan....................................................................................................................................................41
Install the cooling fan........................................................................................................................................................ 41
Install the system cover...................................................................................................................................................42
Slide the system into the cabinet..................................................................................................................................43
Verify the replacement fan............................................................................................................................................. 44
4 Contents
Page 9 of 181
Remove an expansion card from an expansion card riser........................................................................................ 71
Install expansion card into expansion card riser.........................................................................................................73
Install the system cover...................................................................................................................................................75
Slide the system into the cabinet.................................................................................................................................. 76
Reconnect and power on the system...........................................................................................................................77
Verify the PCIe HBA replacement................................................................................................................................. 77
Contents 5
Page 10 of 181
Chapter 13: Replace the system board....................................................................................... 104
Verify the status of the system board....................................................................................................................... 105
Shut down and disconnect the system......................................................................................................................105
Remove a PSU................................................................................................................................................................. 105
Extend the system from the cabinet.......................................................................................................................... 106
Remove the system cover.............................................................................................................................................107
Removing the air shroud................................................................................................................................................ 107
Remove the cooling fan assembly............................................................................................................................... 108
Remove expansion card risers......................................................................................................................................109
Remove expansion card riser 1............................................................................................................................... 109
Remove expansion card riser 2............................................................................................................................... 110
Remove expansion card riser 3................................................................................................................................ 111
Remove the memory module......................................................................................................................................... 112
Remove processor and heat sink module................................................................................................................... 112
Remove the system board............................................................................................................................................. 113
Install the system board..................................................................................................................................................114
Install a processor and heat sink module.................................................................................................................... 114
Install the memory module............................................................................................................................................. 115
Installing the new TPM................................................................................................................................................... 116
Install expansion card riser 1.......................................................................................................................................... 117
Install expansion card riser 2......................................................................................................................................... 118
Install expansion card riser 3......................................................................................................................................... 118
Install the cooling fan assembly.................................................................................................................................... 119
Installing the air shroud.................................................................................................................................................. 120
Install the system cover.................................................................................................................................................. 121
Install the PSU.................................................................................................................................................................. 122
Slide the system into the cabinet................................................................................................................................ 123
Reconnect and power on the system......................................................................................................................... 124
Restoring the Service Tag by using the Easy Restore feature.............................................................................124
Enter the system Service Tag by using System Setup.......................................................................................... 125
Import server profile....................................................................................................................................................... 125
Upgrade the identity module firmware.......................................................................................................................125
Bring up the existing file system..................................................................................................................................126
6 Contents
Page 11 of 181
Remove the system board.............................................................................................................................................139
Install the system board................................................................................................................................................. 139
Install expansion card riser 1......................................................................................................................................... 140
Install expansion card riser 2..........................................................................................................................................141
Install expansion card riser 3..........................................................................................................................................141
Installing the air shroud.................................................................................................................................................. 142
Install the cooling fan assembly....................................................................................................................................143
Install the system cover................................................................................................................................................. 144
Install the hard drive....................................................................................................................................................... 145
Install the front bezel......................................................................................................................................................146
Install the PSU..................................................................................................................................................................146
Install the system in the cabinet.................................................................................................................................. 147
Reconnect and power on the system.........................................................................................................................149
Verify the system and perform a system headswap...............................................................................................150
Verify the system............................................................................................................................................................ 150
Contents 7
Page 12 of 181
Figures
1 Maintenance connections...................................................................................................................................... 15
2 Drive fault LED.......................................................................................................................................................... 17
3 Removing the front bezel....................................................................................................................................... 19
4 Removing a hard drive............................................................................................................................................ 19
5 Removing the drive from the drive carrier........................................................................................................ 20
6 Installing a drive into the drive carrier................................................................................................................. 21
7 Installing a hard drive.............................................................................................................................................. 22
8 Installing the front bezel........................................................................................................................................ 22
9 Drive fault LED......................................................................................................................................................... 23
10 Drive fault LED......................................................................................................................................................... 24
11 Removing the front bezel...................................................................................................................................... 26
12 Removing a hard drive............................................................................................................................................26
13 Removing the drive from the drive carrier........................................................................................................ 27
14 Installing a drive into the drive carrier................................................................................................................ 28
15 Installing a hard drive.............................................................................................................................................. 29
16 Installing the front bezel........................................................................................................................................ 29
17 Drive fault LED......................................................................................................................................................... 30
18 Drive fault LED.......................................................................................................................................................... 31
19 Removing the front bezel...................................................................................................................................... 33
20 Removing a hard drive............................................................................................................................................33
21 Removing the drive from the drive carrier........................................................................................................ 34
22 Installing a drive into the drive carrier................................................................................................................ 35
23 Installing a hard drive.............................................................................................................................................. 36
24 Installing the front bezel........................................................................................................................................ 36
25 Drive fault LED......................................................................................................................................................... 37
26 Extend the system from the cabinet.................................................................................................................. 40
27 Remove the system cover......................................................................................................................................41
28 Removing cooling fan.............................................................................................................................................. 41
29 Installing cooling fan................................................................................................................................................42
30 Slide the system into the cabinet........................................................................................................................ 43
31 PSU LED.................................................................................................................................................................... 45
32 Remove the power supply unit.............................................................................................................................46
33 Install the PSU.......................................................................................................................................................... 47
34 Extend the system from the cabinet................................................................................................................... 51
35 Remove the system cover..................................................................................................................................... 51
36 Removing the air shroud........................................................................................................................................ 52
37 Removing expansion card riser 2......................................................................................................................... 53
38 Removing the network daughter card................................................................................................................53
39 Installing the network daughter card.................................................................................................................. 54
40 Installing expansion card riser 2........................................................................................................................... 54
8 Figures
Page 13 of 181
41 Installing the air shroud.......................................................................................................................................... 55
42 Slide the system into the cabinet........................................................................................................................ 56
43 Power button............................................................................................................................................................ 57
44 Network daughter card.......................................................................................................................................... 57
45 NIC LEDs....................................................................................................................................................................58
46 Extend the system from the cabinet................................................................................................................... 61
47 Remove the system cover......................................................................................................................................61
48 Removing the air shroud........................................................................................................................................ 62
49 Removing a memory module................................................................................................................................. 63
50 Installing a memory module................................................................................................................................... 64
51 Installing the air shroud.......................................................................................................................................... 64
52 Slide the system into the cabinet........................................................................................................................ 66
53 Slot numbering......................................................................................................................................................... 69
54 Extend the system from the cabinet.................................................................................................................. 70
55 Remove the system cover......................................................................................................................................71
56 Removing the expansion card from expansion card riser 1............................................................................72
57 Removing the expansion card from expansion card riser 2...........................................................................72
58 Removing the expansion card from expansion card riser 3...........................................................................73
59 Installing expansion card into expansion card riser 1....................................................................................... 74
60 Installing expansion card into expansion card riser 2...................................................................................... 74
61 Installing expansion card into expansion card riser 3...................................................................................... 75
62 Slide the system into the cabinet........................................................................................................................ 76
63 Power button............................................................................................................................................................ 77
64 Extend the system from the cabinet.................................................................................................................. 80
65 Remove the system cover......................................................................................................................................81
66 Removing the NVRAM module from expansion card riser 1..........................................................................82
67 NVRAM module........................................................................................................................................................ 82
68 Installing the NVRAM module in expansion card riser 1................................................................................. 83
69 Slide the system into the cabinet........................................................................................................................ 84
70 Extend the system from the cabinet.................................................................................................................. 88
71 Remove the system cover.....................................................................................................................................89
72 TPM location.............................................................................................................................................................89
73 Installing the TPM................................................................................................................................................... 90
74 Slide the system into the cabinet......................................................................................................................... 91
75 Extend the system from the cabinet.................................................................................................................. 94
76 Remove the system cover.....................................................................................................................................95
77 Removing the air shroud........................................................................................................................................ 95
78 Installing the air shroud........................................................................................................................................ 100
79 Slide the system into the cabinet.......................................................................................................................102
80 Remove the power supply unit........................................................................................................................... 106
81 Extend the system from the cabinet.................................................................................................................106
82 Remove the system cover................................................................................................................................... 107
83 Removing the air shroud...................................................................................................................................... 108
Figures 9
Page 14 of 181
84 Removing the cooling fan.................................................................................................................................... 109
85 Removing expansion card riser 1......................................................................................................................... 110
86 Removing expansion card riser 2......................................................................................................................... 111
87 Removing expansion card riser 3......................................................................................................................... 111
88 Removing a memory module................................................................................................................................ 112
89 Removing the system board.................................................................................................................................113
90 Installing system board.......................................................................................................................................... 114
91 Installing a memory module.................................................................................................................................. 116
92 TPM location............................................................................................................................................................ 116
93 Installing the TPM................................................................................................................................................... 117
94 Installing expansion card riser 1........................................................................................................................... 117
95 Installing expansion card riser 2.......................................................................................................................... 118
96 Installing expansion card riser 3.......................................................................................................................... 119
97 Installing the cooling fan assembly.................................................................................................................... 120
98 Installing the air shroud......................................................................................................................................... 121
99 Install the PSU........................................................................................................................................................ 123
100 Slide the system into the cabinet.......................................................................................................................123
101 Release and extend system from cabinet......................................................................................................... 131
102 Removing system from rails................................................................................................................................ 132
103 Remove the power supply unit........................................................................................................................... 133
104 Removing the front bezel.....................................................................................................................................133
105 Removing a hard drive.......................................................................................................................................... 134
106 Removing the system cover................................................................................................................................135
107 Removing the cooling fan.................................................................................................................................... 135
108 Removing the air shroud...................................................................................................................................... 136
109 Removing expansion card riser 1........................................................................................................................ 137
110 Removing expansion card riser 2........................................................................................................................138
111 Removing expansion card riser 3........................................................................................................................138
112 Removing the system board................................................................................................................................139
113 Installing system board......................................................................................................................................... 140
114 Installing expansion card riser 1.......................................................................................................................... 140
115 Installing expansion card riser 2.......................................................................................................................... 141
116 Installing expansion card riser 3..........................................................................................................................142
117 Installing the air shroud.........................................................................................................................................143
118 Installing the cooling fan assembly.....................................................................................................................144
119 Installing a hard drive............................................................................................................................................ 145
120 Installing the front bezel.......................................................................................................................................146
121 Install the PSU.........................................................................................................................................................147
122 Pull out the intermediate rail................................................................................................................................147
123 Attach the inner rails to the system.................................................................................................................. 148
124 Install system into the extended rails................................................................................................................ 148
125 Slide system into the rack....................................................................................................................................149
126 Power button.......................................................................................................................................................... 149
10 Figures
Page 15 of 181
127 Removing the front bezel.................................................................................................................................... 153
128 Installing the front bezel.......................................................................................................................................154
129 Extend the system from the cabinet.................................................................................................................156
130 Sliding rail assembly - 2U systems..................................................................................................................... 157
131 CMA arm and separator....................................................................................................................................... 157
132 Release and extend system from cabinet........................................................................................................ 158
133 Removing system from rails................................................................................................................................ 158
134 Removing the rails................................................................................................................................................. 159
135 Remove the original CMA bracket..................................................................................................................... 159
136 Attach outer CMA bracket to the rails............................................................................................................. 160
137 Attach inner CMA bracket to the rails...............................................................................................................161
138 Installing the rear end of the rail........................................................................................................................ 162
139 Installing the front end of the rail.......................................................................................................................162
140 Installing screws..................................................................................................................................................... 163
141 Pull out the intermediate rail............................................................................................................................... 163
142 Attach the inner rails to the system.................................................................................................................. 164
143 Install system into the extended rails................................................................................................................164
144 Slide system into the rack....................................................................................................................................165
145 Install the seperator...............................................................................................................................................165
146 Install the arm......................................................................................................................................................... 166
147 Close the arm.......................................................................................................................................................... 166
148 Slide the system into the cabinet.......................................................................................................................167
149 Power button.......................................................................................................................................................... 167
150 Slot numbering........................................................................................................................................................168
151 Extend the system from the cabinet.................................................................................................................170
152 Remove the system cover................................................................................................................................... 170
153 Installing expansion card into expansion card riser 1...................................................................................... 171
154 Installing expansion card into expansion card riser 2.....................................................................................172
155 Installing expansion card into expansion card riser 3.....................................................................................172
156 Slide the system into the cabinet.......................................................................................................................173
157 Power button...........................................................................................................................................................174
Figures 11
Page 16 of 181
Tables
1 Communications settings....................................................................................................................................... 15
2 Component characteristics.................................................................................................................................... 16
3 Front disk slot numbers.......................................................................................................................................... 18
4 Front disk slot numbers..........................................................................................................................................25
5 Front disk slot numbers..........................................................................................................................................32
6 Fan locations............................................................................................................................................................. 40
7 NIC LED states.........................................................................................................................................................58
8 Memory mapping..................................................................................................................................................... 59
9 Slot assignments......................................................................................................................................................69
10 Slot assignments.................................................................................................................................................... 168
12 Tables
Page 17 of 181
1
FRU and Upgrade Overview
The tool, safety, and connection information in this chapter applies to all component replacement procedures for the
PowerProtect system. Verify that the required tools are available, review the safety information, and connect to the system
before proceeding.
This chapter contains the following information:
Topics:
• Tools and supplies needed
• Safety overview
• Establish a serial management connection to the PowerProtect system
• Component characteristics
Page 18 of 181
Safety overview
CAUTION:
● If the system is used in a manner not specified by the manufacturer, the protection provided by the
equipment may be impaired.
● The RJ45 sockets on the motherboard, PCI cards, or I/O modules are for Ethernet connection only and must
not be connected to a telecommunications network.
CAUTION: Improper installation on the rails may damage the rails or cause the system to fall when extended.
When extending the system from the rack, pull outward slowly and verify the system is properly installed on the
rails.
Review this list of important safety recommendations.
● All plug-in modules and blank plates are part of the fire enclosure and must be removed only when a replacement can be
added immediately. The system must not be run without all parts in place.
● A DD6400 system must be operated only from a power supply input voltage range of 100–240 VAC and 50–60 Hz.
● The system is intended to operate with all installed power supplies working as intended.
● Provide a suitable power source with electrical overload protection.
● A safe electrical earth connection must be provided to each power cord. Check the grounding of the power sources before
applying power.
● The plug on each power supply cord is used as the main device to disconnect power from the system. Ensure that the
socket outlets are located near the equipment and are easily accessible.
● Permanently unplug the unit if you think it is damaged in any way and before moving the system. To completely remove
system power, you must disconnect all power supplies.
● The power connections must always be disconnected prior to removal or replacement of a power supply module from any of
the components in the system.
● A faulty power supply module should be replaced within 24 hours.
● Do not lift system components by yourself. A DD6400 system weighs up to 72.91 lbs (33.1 kg).
CAUTION: PowerProtect systems are heavy. Use at least two people or a mechanical lift to move any system.
● To comply with applicable safety, emission, and thermal requirements, covers must not be removed and all bays must be
fitted with plug-in modules.
● For ESD protection, Dell EMC recommends that you wear a suitable antistatic wrist or ankle strap. Observe all conventional
ESD precautions when handling plug-in modules and components.
Safety instructions
WARNING: Whenever you need to lift the system, get others to assist you. To avoid injury, do not attempt to lift
the system by yourself.
WARNING: Opening or removing the system cover while the system is powered on may expose you to a risk of
electric shock.
CAUTION: Do not operate the system without the cover for a duration exceeding five minutes. Operating the
system without the system cover can result in component damage.
CAUTION: Many repairs may only be done by a certified service technician. You should only perform
troubleshooting and simple repairs as authorized in your product documentation, or as directed by the online or
telephone service and support team. Damage due to servicing that is not authorized by Dell is not covered by
your warranty. Read and follow the safety instructions that are shipped with your product. Always use a static
mat and anti-static wristband while working on components inside the system.
NOTE: It is recommended that you always use an anti-static mat and an anti-static wristband while working on components
inside the system.
CAUTION: To ensure proper operation and cooling, all bays in the system and system fans must be always
populated with a component or a blank.
Page 19 of 181
Establish a serial management connection to the
PowerProtect system
About this task
The PowerProtect system supports a direct serial connection, or Serial over LAN (SOL). Both methods cannot be enabled at the
same time. The serial port and Ethernet ports are located on the back of the system.
The serial and Ethernet ports are located on the lower left-hand side of the system.
CAUTION: Enabling SOL disables the serial console. If SOL is enabled on the PowerProtect DD controller and the
controller subsequently requires servicing, disable SOL and enable the serial console port to prevent confusion
and unnecessary troubleshooting should service personnel attempt to use the serial port to access the system.
1. Ethernet port
2. Serial port (COM 1)
Steps
Verify whether the system uses a serial connection or SOL, and follow one of the procedures below as required.
Page 20 of 181
Establish an SOL connection
Prerequisites
The system must be configured to accept SOL connections. The Hardware Overview and Installation Guide for this system
provides instructions to configure the system for SOL.
Steps
1. Open an SSH shell.
2. Run the following command to connect to iDRAC.
ssh <iDRAC-IP-address> -l <iDRAC-username>.
3. Log in with the credentials for the iDRAC username.
4. Run one of the following commands to initiate the SOL session.
● console com2
● connect
Component characteristics
The following table lists the replaceable components, whether the component is hot-swappable, and whether the procedure can
be completed by a customer (CRU), or a Dell or partner technician (FRU):
DIMM N CRU
Network daughter card N CRU
PCIe HBA N CRU
Rail kit N CRU
NVRAM N FRU
TPM N FRU
System board N FRU
CPU/heatsink N FRU
Chassis N FRU
The following table lists the available upgrades, whether they can be performed with the system powered on, and whether the
procedure is a CRU or a FRU.
Page 21 of 181
2
Replace an Operating System Disk
Complete the following procedure to replace a disk mounted in the front of the chassis.
This CRU can be completed with the system powered on.
After replacing the disk, it takes approximately 2 hours for the disk rebuild process to complete.
NOTE: This is an estimate, and the rebuild may take significantly longer depending on the amount of activity on the system.
Topics:
• Identify a failed OS disk
• Remove the front bezel to access front panel hard drives
• Remove a hard drive
• Removing the drive from the drive carrier
• Installing a drive into the drive carrier
• Install the hard drive
• Install the front bezel
• Verify the replacement data disk
Steps
1. Verify the drive fault LED on the left control panel at the front of the system is illuminated solid amber.
Page 22 of 181
2. Run the alerts show current command to identify the location of the failed disk. Record the slot number of the failed
disk.
CAUTION: The physical labeling of the disks on the system chassis, and the disk numbering in do not match.
The physical labeling starts with Disk 0, and starts with Disk 1.
NOTE: The sample output below only includes the alert object and alert message. It does not include the columns for
the alert ID, post time, severity, and alert class which are part of the actual output.
3. Match the slot number of the failed disk from the alerts show current output to the physical location of the disk.
NOTE: Although the physical slots are numbered starting from 0, the software identifies the slots starting at 1.
The following table maps the slot number to the physical location of the disk.
4. Run the disk beacon command on the failed disk to illuminate the LED.
Steps
1. Unlock the bezel by using the bezel key.
2. Press the release button, and pull the left end of the bezel.
3. Unhook the right end, and remove the bezel.
Page 23 of 181
Figure 3. Removing the front bezel
Prerequisites
Follow the safety guidelines listed in Safety instructions.
Steps
1. Press the release button to open the hard drive release handle.
2. Holding the handle, slide the hard drive out of the hard drive slot.
3. If you are not replacing the hard drive immediately, insert a hard drive blank in the empty hard drive slot to maintain proper
system cooling.
Page 24 of 181
Removing the drive from the drive carrier
Steps
1. Using a Phillips #1 screwdriver, remove the screws from the slide rails on the drive carrier.
NOTE: If the hard drive or SSD carrier has Torx screw, use Torx 6 (for 2.5-inch drive) or Torx 8 (for 3.5-inch drive)
screwdriver to remove the drive.
Page 25 of 181
Figure 6. Installing a drive into the drive carrier
Prerequisites
Follow the safety guidelines listed in Safety instructions.
Steps
1. Press the release button on the front of the hard drive to open the release handle.
2. Insert the hard drive into the hard drive slot and slide until the hard drive connects with the backplane.
3. Close the hard drive release handle to lock the hard drive in place.
Page 26 of 181
Figure 7. Installing a hard drive
Steps
1. Align and insert the right end of the bezel onto the system.
2. Press the release button and fit the left end of the bezel onto the system.
3. Lock the bezel by using the key.
Page 27 of 181
Verify the replacement data disk
About this task
The system reports the state of a replacement disk drive depending on the history of the disk. Use the disk show state
command to display the state of all disk drives.
A replacement disk drive that is inserted into the system is recognized as a failed disk drive and is noted as failed when first
installed. An auto-spare process should change the status to spare in a few minutes.
Steps
1. Verify the drive fault LED on the left control panel at the front of the system is off.
The 'storage add force' command will make the disk available to the
filesystem. Any existing data on this will be lost.
Are you sure? (yes|no) [no]: yes
6. Run the disk show state command to verify the disk rebuild status.
Page 28 of 181
3
Replace a Cache Tier Disk
Complete the following procedure to replace a Cache Tier disk mounted in the front of the chassis.
This CRU can be completed with the system powered on.
Cache Tier disks are not RAID protected, so no disk rebuild is required.
Topics:
• Identify a failed Cache Tier disk
• Remove the front bezel to access front panel hard drives
• Remove a hard drive
• Removing the drive from the drive carrier
• Installing a drive into the drive carrier
• Install the hard drive
• Install the front bezel
• Verify the replacement drive
Steps
1. Verify the drive fault LED on the left control panel at the front of the system is illuminated solid amber.
2. Run the alerts show current command to identify the location of the failed disk. Record the slot number of the failed
disk.
Page 29 of 181
CAUTION: The physical labeling of the disks on the system chassis, and the disk numbering in DD OS do not
match. The physical labeling starts with Disk 0, and DD OS starts with Disk 1.
NOTE: The sample output below only includes the alert object and alert message. It does not include the columns for
the alert ID, post time, severity, and alert class which are part of the actual output.
3. Match the slot number of the failed disk from the alerts show current output to the physical location of the disk.
NOTE: Although the physical slots are numbered starting from 0, the software identifies the slots starting at 1.
The following table maps the slot number to the physical location of the disk.
4. Run the disk beacon command on the failed disk to illuminate the LED.
Steps
1. Unlock the bezel by using the bezel key.
2. Press the release button, and pull the left end of the bezel.
3. Unhook the right end, and remove the bezel.
Page 30 of 181
Figure 11. Removing the front bezel
Prerequisites
Follow the safety guidelines listed in Safety instructions.
Steps
1. Press the release button to open the hard drive release handle.
2. Holding the handle, slide the hard drive out of the hard drive slot.
3. If you are not replacing the hard drive immediately, insert a hard drive blank in the empty hard drive slot to maintain proper
system cooling.
Page 31 of 181
Removing the drive from the drive carrier
Steps
1. Using a Phillips #1 screwdriver, remove the screws from the slide rails on the drive carrier.
NOTE: If the hard drive or SSD carrier has Torx screw, use Torx 6 (for 2.5-inch drive) or Torx 8 (for 3.5-inch drive)
screwdriver to remove the drive.
Page 32 of 181
Figure 14. Installing a drive into the drive carrier
Prerequisites
Follow the safety guidelines listed in Safety instructions.
Steps
1. Press the release button on the front of the hard drive to open the release handle.
2. Insert the hard drive into the hard drive slot and slide until the hard drive connects with the backplane.
3. Close the hard drive release handle to lock the hard drive in place.
Page 33 of 181
Figure 15. Installing a hard drive
Steps
1. Align and insert the right end of the bezel onto the system.
2. Press the release button and fit the left end of the bezel onto the system.
3. Lock the bezel by using the key.
Page 34 of 181
Verify the replacement drive
Steps
1. Verify the drive fault LED on the left control panel at the front of the system is off.
Page 35 of 181
4
Replace a Data Disk
Complete the following procedure to replace a disk mounted in the front of the chassis.
This CRU can be completed with the system powered on.
After replacing the disk, it takes approximately 2 hours for the disk rebuild process to complete.
NOTE: This is an estimate, and the rebuild may take significantly longer depending on the amount of activity on the system.
Topics:
• Identify a failed data disk
• Remove the front bezel to access front panel hard drives
• Remove a hard drive
• Removing the drive from the drive carrier
• Installing a drive into the drive carrier
• Install the hard drive
• Install the front bezel
• Verify the replacement data disk
Steps
1. Verify the drive fault LED on the left control panel at the front of the system is illuminated solid amber.
Page 36 of 181
2. Run the alerts show current command to identify the location of the failed disk. Record the slot number of the failed
disk.
CAUTION: The physical labeling of the disks on the system chassis, and the disk numbering in do not match.
The physical labeling starts with Disk 0, and starts with Disk 1.
NOTE: The sample output below only includes the alert object and alert message. It does not include the columns for
the alert ID, post time, severity, and alert class which are part of the actual output.
3. Match the slot number of the failed disk from the alerts show current output to the physical location of the disk.
NOTE: Although the physical slots are numbered starting from 0, the software identifies the slots starting at 1.
The following table maps the slot number to the physical location of the disk.
4. Run the disk beacon command on the failed disk to illuminate the LED.
Steps
1. Unlock the bezel by using the bezel key.
2. Press the release button, and pull the left end of the bezel.
3. Unhook the right end, and remove the bezel.
Page 37 of 181
Figure 19. Removing the front bezel
Prerequisites
Follow the safety guidelines listed in Safety instructions.
Steps
1. Press the release button to open the hard drive release handle.
2. Holding the handle, slide the hard drive out of the hard drive slot.
3. If you are not replacing the hard drive immediately, insert a hard drive blank in the empty hard drive slot to maintain proper
system cooling.
Page 38 of 181
Removing the drive from the drive carrier
Steps
1. Using a Phillips #1 screwdriver, remove the screws from the slide rails on the drive carrier.
NOTE: If the hard drive or SSD carrier has Torx screw, use Torx 6 (for 2.5-inch drive) or Torx 8 (for 3.5-inch drive)
screwdriver to remove the drive.
Page 39 of 181
Figure 22. Installing a drive into the drive carrier
Prerequisites
Follow the safety guidelines listed in Safety instructions.
Steps
1. Press the release button on the front of the hard drive to open the release handle.
2. Insert the hard drive into the hard drive slot and slide until the hard drive connects with the backplane.
3. Close the hard drive release handle to lock the hard drive in place.
Page 40 of 181
Figure 23. Installing a hard drive
Steps
1. Align and insert the right end of the bezel onto the system.
2. Press the release button and fit the left end of the bezel onto the system.
3. Lock the bezel by using the key.
Page 41 of 181
Verify the replacement data disk
About this task
The system reports the state of a replacement disk drive depending on the history of the disk. Use the disk show state
command to display the state of all disk drives.
A replacement disk drive that is inserted into the system is recognized as a failed disk drive and is noted as failed when first
installed. An auto-spare process should change the status to spare in a few minutes.
Steps
1. Verify the drive fault LED on the left control panel at the front of the system is off.
The 'storage add force' command will make the disk available to the
filesystem. Any existing data on this will be lost.
Are you sure? (yes|no) [no]: yes
Enclosure Disk
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
--------- ----------------------------------------------
1 . . . . v . . . . . . .
2 . . . . . . . . . . . . . . .
--------- ----------------------------------------------
Page 42 of 181
Legend State Count
------ --------------- -----
. In Use Disks 26
v Available Disks 1
------ --------------- -----
Total 27 disks
6. Use the alerts show current (or alerts show current-detailed) command.
Page 43 of 181
5
Replace a Fan
CAUTION: Improper installation on the rails may damage the rails or cause the system to fall when extended.
When extending the system from the rack, pull outward slowly and verify the system is properly installed on the
rails.
The system contains fans in the front of the chassis.
Complete the following procedure to replace a failed fan.
This CRU can be completed with the system powered on.
Topics:
• Identify a failed fan
• Extend the system from the cabinet
• Remove the system cover
• Remove the cooling fan
• Install the cooling fan
• Install the system cover
• Slide the system into the cabinet
• Verify the replacement fan
Prerequisites
Establish a connection to the system as described in Establish a serial management connection to the PowerProtect system.
Steps
1. Use the alerts show current (or alerts show current-detailed) command that will include messages
indicating fan loss or fan failure.
NOTE: The sample output below only includes the alert object and alert message. It does not include the columns for
the alert ID, post time, severity, and alert class which are part of the actual output.
Replace a Fan 39
Page 44 of 181
System Board Fan6 medium OK
--------- ----------------- ------ ------
3. Record the number of the failed fan.
4. Map the number of the failed fan to the physical location of that fan.
The following table shows the physical layout of the fans as seen from the front of the system.
Steps
1. At the front of the cabinet, locate the two slam latches on the left and right sides of the system. Pull the slam latches up to
release the system from the cabinet. If the slam latches do not disengage, loosen the screw under each latch.
2. Using the slam latches, pull the system from the cabinet until the rails lock in the extended position.
40 Replace a Fan
Page 45 of 181
Figure 27. Remove the system cover
Steps
Press the release tab and lift the cooling fan out of the cooling fan assembly.
Steps
Holding the release tab, align the connector at the base of the cooling fan with the connector on the system board.
Replace a Fan 41
Page 46 of 181
Figure 29. Installing cooling fan
Steps
1. Align the tabs on the system cover with the guide slots on the system.
2. Push the system cover latch down.
The system cover slides forward, the tabs on the system cover engage with the guide slots on the system and the system
cover latch locks into place.
3. Using a flat or Phillips head screwdriver, rotate the latch release lock clockwise to the locked position.
42 Replace a Fan
Page 47 of 181
Slide the system into the cabinet
Steps
1. At the front of the cabinet, push the system inward until the lock levers click into place.
2. Push the blue slide release lock tabs forward on both rails and slide the system into the cabinet. The slam latches engage to
secure the system in the cabinet.
NOTE: Make sure the cables remain clear of the chassis as it slides back into place.
Replace a Fan 43
Page 48 of 181
Verify the replacement fan
Prerequisites
Establish a connection to the system as described in Establish a serial management connection to the PowerProtect system.
Steps
1. Use the enclosure show fans command to verify the status of the new fan.
44 Replace a Fan
Page 49 of 181
6
Replace a Power Supply
The system contains two power supply units (PSUs) in the rear of the chassis.
Complete the following procedure to replace a PSU.
This CRU can be performed with the system powered on.
Topics:
• Identify a failed PSU
• Remove a PSU
• Install the PSU
• Verify the replacement power supply
Prerequisites
Establish a connection to the system as described in Establish a serial management connection to the PowerProtect system.
Steps
1. Check the LED on the affected PSU. The PSU handle functions as the LED.
NOTE: If a PSU is found to be faulted, the LED blinks amber.
2. Enter the alerts show current command (or alerts show current-detailed) to display messages indicating
PSU failure. A sample output is shown.
NOTE: The sample output below only includes the alert object and alert message. It does not include the columns for
the alert ID, post time, severity, and alert class which are part of the actual output.
Page 50 of 181
# alerts show current
Object Message
--------- -----------------
Encl=1:PowerSupply=2 EVT-ENVIRONMENT-00026: Power supply has failed
--------- -----------------
3. Enter the enclosure show powersupply command to check the status of each power supply.
4. Map the number of the failed PSU to the physical location of that power supply.
As seen from the back of the system, both power supplies are on the right--hand side of the system. Power supply 1 is the
left-hand PSU, and power supply 2 is the right-hand PSU.
Remove a PSU
Prerequisites
Follow the safety guidelines listed in Safety instructions.
Steps
1. Disconnect the power cable from the power source and from the PSU you intend to remove, and then remove the cable
from the strap on the PSU handle.
2. Press the release latch and slide the PSU out of the system by using the PSU handle.
Page 51 of 181
Install the PSU
Prerequisites
Follow the safety guidelines listed in Safety instructions.
Steps
1. Verify that nothing has dropped into the empty PSU slot before installing the replacement PSU.
2. Slide the PSU into the system until the PSU is fully seated and the release latch snaps into place.
3. Connect the power cable to the PSU, and plug the cable into a power outlet.
CAUTION: When connecting the power cable to the PSU, secure the cable to the PSU with the strap.
NOTE: When installing, hot swapping, or hot adding a new PSU, wait for 15 seconds for the system to recognize the
PSU and determine its status. The PSU redundancy may not occur until discovery is complete. Wait until the new PSU is
discovered and enabled before you remove the other PSU. The PSU status indicator turns green to signify that the PSU
is functioning properly.
Prerequisites
Establish a connection to the system as described in Establish a serial management connection to the PowerProtect system.
Page 52 of 181
Steps
1. Enter the enclosure show powersupply command to check the status of each power supply.
2. Use the alerts show current (or alerts show current-detailed) command.
Page 53 of 181
7
Replace the Network Daughter Card
CAUTION: Improper installation on the rails may damage the rails or cause the system to fall when extended.
When extending the system from the rack, pull outward slowly and verify the system is properly installed on the
rails.
The system uses a network daughter card that contains 4 x 10 GbE ports. If a port fails, the whole card requires replacement.
Complete the following procedure to replace the network daughter card.
This CRU is not hot-swappable, and requires a system shutdown to replace.
Topics:
• Verify the status of the network daughter card
• Shut down and disconnect the system
• Extend the system from the cabinet
• Remove the system cover
• Removing the air shroud
• Remove expansion card riser 2
• Remove the network daughter card
• Install the network daughter card
• Install expansion card riser 2
• Installing the air shroud
• Install the system cover
• Slide the system into the cabinet
• Reconnect and power on the system
• Verify the replacement network daughter card
Prerequisites
Establish a connection to the system as described in Establish a serial management connection to the PowerProtect system.
Steps
1. Use the enclosure show io-cards command to check the status of the network daughter card. If the card has failed,
it will not appear in the command output.
2. If the network daughter card is visible in the output of the enclosure show io-cards command, use the alerts
show current command to look for alerts relating to one or more network interfaces that indicate a failure of the network
daughter card.
3. Verify the link and activity LEDs on the impacted port are off.
The network daughter card is located at the rear of the chassis, at the bottom.
Page 54 of 181
The ports are labeled ethMa, ethMb, ethMc, and ethMd from left to right.
Prerequisites
Establish a connection to the system.
Steps
1. Stop the system using the system poweroff command to allow the proper shut down of the file system and other system
components. The power down process takes approximately five minutes to complete. The system poweroff command
immediately turns the front panel blue LED to amber, and is complete when the front panel LED turns off.
NOTE: The system fans still run, and NIC port LEDs still flash after running the system poweroff command.
Steps
1. At the front of the cabinet, locate the two slam latches on the left and right sides of the system. Pull the slam latches up to
release the system from the cabinet. If the slam latches do not disengage, loosen the screw under each latch.
2. Using the slam latches, pull the system from the cabinet until the rails lock in the extended position.
Page 55 of 181
Figure 34. Extend the system from the cabinet
Page 56 of 181
Removing the air shroud
Steps
Hold the air shroud at both ends and lift it away from the system.
Steps
1. If installed, remove expansion cards installed on the riser.
2. Disconnect any cables connected to the riser.
3. To remove expansion card riser 2:
a. Using Phillips #2 screwdriver, loosen the screws that secure the riser to the system.
b. Press the release tab, and holding the riser by its edges, lift the riser from the riser connector on the system board.
Page 57 of 181
Figure 37. Removing expansion card riser 2
Page 58 of 181
2. Align the captive screws at the back-end of the card with the screw holes on the system board.
3. Press the touch points on the card until the card connector is firmly seated on the system board connector.
4. Using a Phillips #2 screwdriver, tighten the captive screws to secure the NDC to the system board.
Steps
To install expansion card riser 2:
a. Align the screw and tab on the riser with the screw hole and slot on the system.
b. Lower the riser into the system until the riser connector engages with the connector on the system board.
c. Using Phillips #2 screwdriver, tighten the screws to secure the riser to the system.
Page 59 of 181
Installing the air shroud
Steps
1. Align the tabs on the air shroud with the slots on the system.
2. Lower the air shroud into the system until it is firmly seated.
When firmly seated, the memory socket numbers marked on the air shroud align with the respective memory sockets.
Steps
1. Align the tabs on the system cover with the guide slots on the system.
2. Push the system cover latch down.
The system cover slides forward, the tabs on the system cover engage with the guide slots on the system and the system
cover latch locks into place.
3. Using a flat or Phillips head screwdriver, rotate the latch release lock clockwise to the locked position.
Page 60 of 181
Slide the system into the cabinet
Steps
1. At the front of the cabinet, push the system inward until the lock levers click into place.
2. Push the blue slide release lock tabs forward on both rails and slide the system into the cabinet. The slam latches engage to
secure the system in the cabinet.
NOTE: Make sure the cables remain clear of the chassis as it slides back into place.
Page 61 of 181
Reconnect and power on the system
This section describes the steps to reconnect and power on the system.
Steps
1. Use the cable labels to reconnect the cables in the same configuration as they were before starting the replacement
procedure.
CAUTION: When connecting SAS cables to the SAS cards, ensure there is sufficient slack in the cable to
avoid unnecessary strain on the cable connector and the SAS card when the controller is fully extended from
the rack.
5. If the system does not power on when the AC power cords were reconnected, press the power button on the right control
panel at the front of the system.
Steps
1. Verify the link and activity LEDs on all ports are lit on the active ports.
The network daughter card is located at the rear of the chassis, at the bottom.
Page 62 of 181
Figure 45. NIC LEDs
2. Use the enclosure show io-cards and net show settings commands to check the status of the network
daughter card. Verify the network daughter card appears in the list
3. Use the alerts show current (or alerts show current-detailed) command.
Page 63 of 181
8
Replace a DIMM
CAUTION: Improper installation on the rails may damage the rails or cause the system to fall when extended.
When extending the system from the rack, pull outward slowly and verify the system is properly installed on the
rails.
The following table lists the memory capacity and the number of DIMMs installed in the system.
Topics:
• Identify a failed DIMM
• Shut down and disconnect the system
• Extend the system from the cabinet
• Remove the system cover
• Removing the air shroud
• Remove the memory module
• Install the memory module
• Installing the air shroud
• Install the system cover
• Slide the system into the cabinet
• Reconnect and power on the system
• Verify the replacement DIMM
Prerequisites
Establish a connection to the system as described in Establish a serial management connection to the PowerProtect system.
Steps
1. Enter the alert show current command to display message indicating a DIMM failure. A sample output is shown.
Replace a DIMM 59
Page 64 of 181
DDFS will not be started.
Prerequisites
Establish a connection to the system as described in Establish a serial management connection to the PowerProtect system.
Steps
1. Stop the system using the system poweroff command to allow the proper shut down of the file system and other system
components. The power down process takes approximately five minutes to complete. The system poweroff command
immediately turns the front panel blue LED to amber, and is complete when the front panel LED turns off.
NOTE: The system fans still run, and NIC port LEDs still flash after running the system poweroff command.
Steps
1. At the front of the cabinet, locate the two slam latches on the left and right sides of the system. Pull the slam latches up to
release the system from the cabinet. If the slam latches do not disengage, loosen the screw under each latch.
2. Using the slam latches, pull the system from the cabinet until the rails lock in the extended position.
60 Replace a DIMM
Page 65 of 181
Figure 46. Extend the system from the cabinet
Replace a DIMM 61
Page 66 of 181
Removing the air shroud
Steps
Hold the air shroud at both ends and lift it away from the system.
Prerequisites
WARNING: Allow the memory modules to cool after you power off the system. Handle the memory modules by
the card edges and avoid touching the components or metallic contacts on the memory module.
CAUTION: To ensure proper system cooling, memory module blanks must be installed in any memory socket that
is not occupied. Remove memory module blanks only if you intend to install memory modules in those sockets.
Steps
1. Locate the appropriate memory module socket.
CAUTION: Handle each memory module only by the card edges, ensuring not to touch the middle of the
memory module or metallic contacts.
2. Push the ejectors outward on both ends of the memory module socket at the same time to release the memory module from
the socket.
3. Lift and remove the memory module from the system.
62 Replace a DIMM
Page 67 of 181
Figure 49. Removing a memory module
Prerequisites
CAUTION: To ensure proper system cooling, memory module blanks must be installed in any memory socket that
is not occupied. Remove memory module blanks only if you intend to install memory modules in those sockets.
Steps
1. Locate the appropriate memory module socket.
CAUTION: Handle each memory module only by the card edges, ensuring not to touch the middle of the
memory module or metallic contacts.
CAUTION: To prevent damage to the memory module or the memory module socket during installation, do
not bend or flex the memory module. You must insert both ends of the memory module simultaneously.
2. Open the ejectors on the memory module socket outward to allow the memory module to be inserted into the socket.
3. Align the edge connector of the memory module with the alignment key of the memory module socket, and insert the
memory module in the socket.
CAUTION: Do not apply pressure at the center of the memory module; apply pressure at both ends of the
memory module evenly.
NOTE: The memory module socket has an alignment key that enables you to install the memory module in the socket in
only one orientation.
4. Press the memory module with your thumbs until the socket levers firmly click into place.
Replace a DIMM 63
Page 68 of 181
Figure 50. Installing a memory module
Steps
1. Align the tabs on the air shroud with the slots on the system.
2. Lower the air shroud into the system until it is firmly seated.
When firmly seated, the memory socket numbers marked on the air shroud align with the respective memory sockets.
64 Replace a DIMM
Page 69 of 181
Install the system cover
Prerequisites
Follow the safety guidelines.
Ensure that all internal cables are routed correctly and connected, and that no tools or extra parts are left inside the system.
Steps
1. Align the tabs on the system cover with the guide slots on the system.
2. Push the system cover latch down.
The system cover slides forward, the tabs on the system cover engage with the guide slots on the system and the system
cover latch locks into place.
3. Using a flat or Phillips head screwdriver, rotate the latch release lock clockwise to the locked position.
Replace a DIMM 65
Page 70 of 181
Figure 52. Slide the system into the cabinet
NOTE: Make sure the cables remain clear of the chassis as it slides back into place.
Steps
1. Close the cable management arms.
2. Prepare the terminal session.
3. Reconnect the AC power cords to the power supplies.
NOTE: The system may not power on automatically after plugging in the AC power cords.
4. If the system does not power on when the AC power cords were reconnected, press the power button on the right control
panel at the front of the system.
66 Replace a DIMM
Page 71 of 181
Steps
1. Enter the system show meminfo command to see the top level summary. Confirm that the system reports the correct
amount of memory.
2. Enter the enclosure show memory command to verify all DIMMs are discovered.
NOTE: The DIMM part numbers and serial numbers are displayed by the command, but truncated from the sample
output below for readability.
Replace a DIMM 67
Page 72 of 181
9
Replace a PCIe HBA (SAS, FC, or NIC)
CAUTION: Improper installation on the rails may damage the rails or cause the system to fall when extended.
When extending the system from the rack, pull outward slowly and verify the system is properly installed on the
rails.
The system uses a variety of PCIe HBAs to provide network, FC, or storage connectivity. If a port fails, the whole card requires
replacement.
CAUTION: This procedure does not apply to replacing the NVRAM module.
Topics:
• Identify the failed PCIe HBA (SAS, FC, or NIC)
• Shut down and disconnect the system
• Extend the system from the cabinet
• Remove the system cover
• Remove an expansion card from an expansion card riser
• Install expansion card into expansion card riser
• Install the system cover
• Slide the system into the cabinet
• Reconnect and power on the system
• Verify the PCIe HBA replacement
Page 73 of 181
Figure 53. Slot numbering
2. Enter the enclosure show io-cards command to check the status of each HBA. Record the failed HBA.
Prerequisites
Establish a connection to the system.
Steps
1. Stop the system using the system poweroff command to allow the proper shut down of the file system and other system
components. The power down process takes approximately five minutes to complete. The system poweroff command
immediately turns the front panel blue LED to amber, and is complete when the front panel LED turns off.
NOTE: The system fans still run, and NIC port LEDs still flash after running the system poweroff command.
Page 74 of 181
Extend the system from the cabinet
Use this procedure to extend the system from the cabinet so that you can remove the system cover to access the internal FRU
components, or to remove the system from the cabinet.
Steps
1. At the front of the cabinet, locate the two slam latches on the left and right sides of the system. Pull the slam latches up to
release the system from the cabinet. If the slam latches do not disengage, loosen the screw under each latch.
2. Using the slam latches, pull the system from the cabinet until the rails lock in the extended position.
Page 75 of 181
Figure 55. Remove the system cover
NOTE: When removing an expansion card from riser 2 or 3, ensure that the PCIe card holder latch is closed.
Steps
1. If applicable, disconnect the cables from the expansion card.
2. Hold the expansion card by its edges, and pull the card until the card edge connector disengages from the expansion card
connector on the riser.
Page 76 of 181
Figure 56. Removing the expansion card from expansion card riser 1
Figure 57. Removing the expansion card from expansion card riser 2
Page 77 of 181
Figure 58. Removing the expansion card from expansion card riser 3
NOTE: When installing a card into riser 2 or 3, open the PCIe card holder latch.
Steps
1. Pull the expansion card latch.
2. If installed, remove the filler bracket.
NOTE: Store the filler bracket for future use. Filler brackets must be installed in empty expansion card slots to maintain
Federal Communications Commission (FCC) certification of the system. The brackets also keep dust and dirt out of the
system and aid in proper cooling and airflow inside the system.
3. Hold the card by its edges, and align the card edge connector with the expansion card connector on the riser.
4. Insert the card edge connector firmly into the expansion card connector until the card is fully seated.
5. Push the expansion card latch.
Page 78 of 181
Figure 59. Installing expansion card into expansion card riser 1
Page 79 of 181
Figure 61. Installing expansion card into expansion card riser 3
Steps
1. Align the tabs on the system cover with the guide slots on the system.
2. Push the system cover latch down.
The system cover slides forward, the tabs on the system cover engage with the guide slots on the system and the system
cover latch locks into place.
3. Using a flat or Phillips head screwdriver, rotate the latch release lock clockwise to the locked position.
Page 80 of 181
Slide the system into the cabinet
Steps
1. At the front of the cabinet, push the system inward until the lock levers click into place.
2. Push the blue slide release lock tabs forward on both rails and slide the system into the cabinet. The slam latches engage to
secure the system in the cabinet.
NOTE: Make sure the cables remain clear of the chassis as it slides back into place.
Page 81 of 181
Reconnect and power on the system
This section describes the steps to reconnect and power on the system.
Steps
1. Use the cable labels to reconnect the cables in the same configuration as they were before starting the replacement
procedure.
CAUTION: When connecting SAS cables to the SAS cards, ensure there is sufficient slack in the cable to
avoid unnecessary strain on the cable connector and the SAS card when the controller is fully extended from
the rack.
5. If the system does not power on when the AC power cords were reconnected, press the power button on the right control
panel at the front of the system.
Page 82 of 181
10
Replace an NVRAM module
CAUTION: Improper installation on the rails may damage the rails or cause the system to fall when extended.
When extending the system from the rack, pull outward slowly and verify the system is properly installed on the
rails.
The NVRAM module is located in slot 2.
CAUTION: This procedure does not apply to replacing the PCIe NIC, FC, or SAS module.
Steps
1. Check the status of the file system and disable it if necessary.
Page 83 of 181
CAUTION: If the file system is not shut down, you will not be able to erase the data from the NVRAM
and you will get a message such as **** This operation is not allowed when the filesystem
is enabled **** Error retrieving information (This operation is not allowed when the
filesystem is enabled).
a. Run the filesys status command to verify the state of the file system.
b. If the file system is enabled, run the filesys disable command to disable it.
# filesys disable
This action will disable the file system.
Applications may experience interruptions
while the file system is disabled.
Are you sure? (yes|no) [no]: yes
ok, proceeding.
Please wait............
The filesystem is now disabled.
2. Run the system erase nvram-flash command to erase the data on the NVRAM.
CAUTION: This command must be run by a qualified Dell EMC user with BASH access, otherwise the system
displays a message such as **** This command is not available for this user. The sysadmin
password is required to confirm the command.
ok, proceeding.
NOTE: If the command fails, skip it and continue with the NVRAM replacement.
CAUTION: After erasing the NVRAM data, the NVRAM module is unusable until it receives a new firmware
installation at the factory.
Steps
1. Stop the system using the system poweroff command to allow the proper shut down of the file system and other system
components. The power down process takes approximately five minutes to complete. The system poweroff command
immediately turns the front panel blue LED to amber, and is complete when the front panel LED turns off.
NOTE: The system fans still run, and NIC port LEDs still flash after running the system poweroff command.
Page 84 of 181
Extend the system from the cabinet
Use this procedure to extend the system from the cabinet so that you can remove the system cover to access the internal FRU
components, or to remove the system from the cabinet.
Steps
1. At the front of the cabinet, locate the two slam latches on the left and right sides of the system. Pull the slam latches up to
release the system from the cabinet. If the slam latches do not disengage, loosen the screw under each latch.
2. Using the slam latches, pull the system from the cabinet until the rails lock in the extended position.
Page 85 of 181
Figure 65. Remove the system cover
NOTE: This procedure describes and illustrates NVRAM module removal from slot 2 in expansion card riser 1.
Steps
1. If applicable, disconnect the cables from the expansion card in slot 1 (the top slot in riser 1).
2. Hold the expansion card by its edges, pull the card until the card edge connector disengages from the expansion card
connector on the riser, and place it on an ESD-safe surface.
3. Remove the NVRAM module from slot 2 (the middle slot in riser 1)
Page 86 of 181
Figure 66. Removing the NVRAM module from expansion card riser 1
NOTE: This procedure describes and illustrates NVRAM module installation in slot 2 in expansion card riser 1.
Steps
1. Pull the expansion card latch.
2. Hold the NVRAM module by its edges, and align the card edge connector with the expansion card connector in slot 2 on the
riser.
3. Insert the NVRAM module edge connector firmly into the expansion card connector until the card is fully seated.
4. If applicable, reinstall the expansion card removed from slot 1 on the riser.
5. If applicable, reconnect the cables from the expansion card in slot 1.
6. Push the expansion card latch.
Page 87 of 181
Figure 68. Installing the NVRAM module in expansion card riser 1
Steps
1. Align the tabs on the system cover with the guide slots on the system.
2. Push the system cover latch down.
The system cover slides forward, the tabs on the system cover engage with the guide slots on the system and the system
cover latch locks into place.
3. Using a flat or Phillips head screwdriver, rotate the latch release lock clockwise to the locked position.
Page 88 of 181
Slide the system into the cabinet
Steps
1. At the front of the cabinet, push the system inward until the lock levers click into place.
2. Push the blue slide release lock tabs forward on both rails and slide the system into the cabinet. The slam latches engage to
secure the system in the cabinet.
NOTE: Make sure the cables remain clear of the chassis as it slides back into place.
Page 89 of 181
Reconnect and power on the system
Steps
1. Use the cable labels to reconnect the cables in the same configuration as they were before starting the replacement
procedure.
CAUTION: When connecting SAS cables to the SAS cards, ensure there is sufficient slack in the cable to
avoid unnecessary strain on the cable connector and the SAS card when the controller is fully extended from
the rack.
5. If the system does not power on when the AC power cords were reconnected, press the power button on the right control
panel at the front of the system.
Steps
1. Run the alerts show current command to verify the system has cleared the NVRAM failure alert.
NOTE: It may take one to two minutes for the system to clear the alert.
2. Run the system show nvram command to verify the NVRAM appears.
NOTE: This command shows the charge level of the NVRAM battery. The battery must be at least 80% charged for the
file system to start.
# filesys enable
4. Run the filesys status command to verify the file system is enabled.
# filesys status
Page 90 of 181
5. Run the system show hardware command to verify the hardware configuration is the same as it was before replacing
the NVRAM module.
Page 91 of 181
11
Replace the Trusted Platform Module (TPM)
CAUTION: Improper installation on the rails may damage the rails or cause the system to fall when extended.
When extending the system from the rack, pull outward slowly and verify the system is properly installed on the
rails.
The PowerProtect system uses a TPM to secure the system.
Complete the following procedure to replace the TPM.
This FRU is not hot-swappable, and requires a system shutdown to replace.
Topics:
• Verify the status of the TPM
• Shut down and disconnect the system
• Extend the system from the cabinet
• Remove the system cover
• Locate the TPM
• Upgrading the Trusted Platform Module
• Install the system cover
• Slide the system into the cabinet
• Reconnect and power on the system
• Initializing the TPM 2.0 for TXT users
Prerequisites
Establish a connection to the system as described in Establish a serial management connection to the PowerProtect system.
Steps
Run the system show all command, and look for the line indicating the TPM. If it is not present, the TPM requires
replacement:
Steps
1. Stop the system using the system poweroff command to allow the proper shut down of the file system and other system
components. The power down process takes approximately five minutes to complete. The system poweroff command
immediately turns the front panel blue LED to amber, and is complete when the front panel LED turns off.
Page 92 of 181
NOTE: The system fans still run, and NIC port LEDs still flash after running the system poweroff command.
Steps
1. At the front of the cabinet, locate the two slam latches on the left and right sides of the system. Pull the slam latches up to
release the system from the cabinet. If the slam latches do not disengage, loosen the screw under each latch.
2. Using the slam latches, pull the system from the cabinet until the rails lock in the extended position.
Page 93 of 181
Figure 71. Remove the system cover
Page 94 of 181
Upgrading the Trusted Platform Module
About this task
CAUTION: If you are using the Trusted Platform Module (TPM) with an encryption key, you may be prompted
to create a recovery key during program or System Setup. Work with the customer to create and safely store
this recovery key. When replacing this system board, you must supply the recovery key when you restart your
system or program before you can access the encrypted data on your hard drives.
CAUTION: A TPM removed from a system board cannot be reinstalled on another system board. Once the TPM
plug-in module is installed, it is cryptographically bound to that specific system board.
Steps
1. Align the tabs on the system cover with the guide slots on the system.
Page 95 of 181
2. Push the system cover latch down.
The system cover slides forward, the tabs on the system cover engage with the guide slots on the system and the system
cover latch locks into place.
3. Using a flat or Phillips head screwdriver, rotate the latch release lock clockwise to the locked position.
Page 96 of 181
NOTE: Make sure the cables remain clear of the chassis as it slides back into place.
Steps
1. Use the cable labels to reconnect the cables in the same configuration as they were before starting the replacement
procedure.
CAUTION: When connecting SAS cables to the SAS cards, ensure there is sufficient slack in the cable to
avoid unnecessary strain on the cable connector and the SAS card when the controller is fully extended from
the rack.
5. If the system does not power on when the AC power cords were reconnected, press the power button on the right control
panel at the front of the system.
Page 97 of 181
12
Replace a CPU
CAUTION: Improper installation on the rails may damage the rails or cause the system to fall when extended.
When extending the system from the rack, pull outward slowly and verify the system is properly installed on the
rails.
Complete the following procedure to replace a CPU.
This FRU is not hot-swappable, and requires a system shutdown to replace.
Topics:
• Verify the status of the CPU
• Shut down and disconnect the system
• Extend the system from the cabinet
• Remove the system cover
• Removing the air shroud
• Remove processor and heat sink module
• Remove the processor from the processor and heat sink module
• Install the processor into a processor and heat sink module
• Install a processor and heat sink module
• Installing the air shroud
• Install the system cover
• Slide the system into the cabinet
• Reconnect and power on the system
• Verify the replacement CPU
Prerequisites
Establish a connection to the system as described in Establish a serial management connection to the PowerProtect system.
Steps
Use the enclosure show cpu command to verify a CPU failure.
Prerequisites
Establish a connection to the system as described in Establish a serial management connection to the PowerProtect system.
Replace a CPU 93
Page 98 of 181
Steps
1. Stop the system using the system poweroff command to allow the proper shut down of the file system and other system
components. The power down process takes approximately five minutes to complete. The system poweroff command
immediately turns the front panel blue LED to amber, and is complete when the front panel LED turns off.
NOTE: The system fans still run, and NIC port LEDs still flash after running the system poweroff command.
Steps
1. At the front of the cabinet, locate the two slam latches on the left and right sides of the system. Pull the slam latches up to
release the system from the cabinet. If the slam latches do not disengage, loosen the screw under each latch.
2. Using the slam latches, pull the system from the cabinet until the rails lock in the extended position.
94 Replace a CPU
Page 99 of 181
Figure 76. Remove the system cover
Replace a CPU 95
Steps
1. Using a Torx #T30 screwdriver, loosen the screws on the heat sink.
NOTE: Ensure that you loosen one screw before moving on to the next screw.
2. Pushing both blue retention clips simultaneously, lift the processor and heat sink module (PHM) out of the system.
3. Set the PHM aside with the processor side facing up.
Steps
1. Place the heat sink with the processor side facing up.
2. Insert a flat blade screwdriver into the release slot marked with a yellow label. Twist (do not pry) the screwdriver to break
the thermal paste seal.
3. Push the retaining clips on the processor bracket to unlock the bracket from the heat sink.
96 Replace a CPU
2. Flex the outer edges of the bracket around the processor ensuring that the processor is locked into the clips on the bracket.
NOTE: Ensure that pin 1 indicator on the bracket is aligned with the pin 1 indicator on the processor before placing the
bracket on the processor.
Replace a CPU 97
3. If you are using an existing heat sink, remove the thermal grease from the heat sink by using a clean lint-free cloth.
4. Use the thermal grease syringe included with your processor kit to apply the grease in a quadrilateral design on the top of
the processor.
CAUTION: Applying too much thermal grease can result in excess grease coming in contact with and
contaminating the processor socket.
NOTE: The thermal grease syringe is intended for single use only. Dispose the syringe after you use it.
5. Place the heat sink on the processor and push down until the bracket locks onto the heat sink.
NOTE:
● Ensure that the two guide pin holes on the bracket match the guide holes on the heat sink.
● Ensure that the pin 1 indicator on the heat sink is aligned with the pin 1 indicator on the bracket before placing the
heat sink onto the processor and bracket.
98 Replace a CPU
WARNING: The heat sink may be hot to touch for some time after the system has been powered down. Allow the
heat sink to cool before removing it.
Steps
1. Align the pin 1 indicator of the heat sink to the system board and then place the processor and heat sink module (PHM) on
the processor socket.
CAUTION: To avoid damaging the fins on the heat sink, do not press down on the heat sink fins.
NOTE: Ensure that the PHM is held parallel to the system board to prevent damaging the components.
2. Push the blue retention clips inward to allow the heat sink to drop into place.
3. Using the #Torx T30 screwdriver with adjustable torque, tighten one screw at a time.
NOTE: Ensure that the screw is tightened completely before moving onto the next screw.
NOTE: The processor and heat sink module retention screws should not be tightened to more than 0.13 kgf-m (1.35
N.m or 12 in-lbf).
Replace a CPU 99
Steps
1. Align the tabs on the air shroud with the slots on the system.
2. Lower the air shroud into the system until it is firmly seated.
When firmly seated, the memory socket numbers marked on the air shroud align with the respective memory sockets.
Steps
1. Align the tabs on the system cover with the guide slots on the system.
2. Push the system cover latch down.
The system cover slides forward, the tabs on the system cover engage with the guide slots on the system and the system
cover latch locks into place.
3. Using a flat or Phillips head screwdriver, rotate the latch release lock clockwise to the locked position.
NOTE: Make sure the cables remain clear of the chassis as it slides back into place.
Steps
1. Close the cable management arms.
2. Prepare the terminal session.
3. Reconnect the AC power cords to the power supplies.
NOTE: The system may not power on automatically after plugging in the AC power cords.
4. If the system does not power on when the AC power cords were reconnected, press the power button on the right control
panel at the front of the system.
Topics:
• Verify the status of the system board
• Shut down and disconnect the system
• Remove a PSU
• Extend the system from the cabinet
• Remove the system cover
• Removing the air shroud
• Remove the cooling fan assembly
• Remove expansion card risers
• Remove the memory module
• Remove processor and heat sink module
• Remove the system board
• Install the system board
• Install a processor and heat sink module
• Install the memory module
• Installing the new TPM
• Install expansion card riser 1
• Install expansion card riser 2
• Install expansion card riser 3
• Install the cooling fan assembly
• Installing the air shroud
• Install the system cover
• Install the PSU
• Slide the system into the cabinet
• Reconnect and power on the system
• Restoring the Service Tag by using the Easy Restore feature
• Enter the system Service Tag by using System Setup
• Import server profile
• Upgrade the identity module firmware
• Bring up the existing file system
Prerequisites
Establish a connection to the system as described in Establish a serial management connection to the PowerProtect system.
Steps
Prerequisites
Establish a connection to the system.
Steps
1. Stop the system using the system poweroff command to allow the proper shut down of the file system and other system
components. The power down process takes approximately five minutes to complete. The system poweroff command
immediately turns the front panel blue LED to amber, and is complete when the front panel LED turns off.
NOTE: The system fans still run, and NIC port LEDs still flash after running the system poweroff command.
Remove a PSU
Prerequisites
Follow the safety guidelines listed in Safety instructions.
Steps
1. Disconnect the power cable from the power source and from the PSU you intend to remove, and then remove the cable
from the strap on the PSU handle.
2. Press the release latch and slide the PSU out of the system by using the PSU handle.
Steps
1. At the front of the cabinet, locate the two slam latches on the left and right sides of the system. Pull the slam latches up to
release the system from the cabinet. If the slam latches do not disengage, loosen the screw under each latch.
2. Using the slam latches, pull the system from the cabinet until the rails lock in the extended position.
Steps
1. If installed, remove the expansion cards from the riser.
2. Disconnect any cables connected to the riser.
3. Press the release latches, and lift the riser from the riser connector on the system board.
Steps
1. If installed, remove expansion cards installed on the riser.
2. Disconnect any cables connected to the riser.
3. To remove expansion card riser 2:
a. Using Phillips #2 screwdriver, loosen the screws that secure the riser to the system.
b. Press the release tab, and holding the riser by its edges, lift the riser from the riser connector on the system board.
Steps
1. If installed, remove expansion cards installed on the riser.
2. Disconnect any cables connected to the riser.
3. Using Phillips #2 screwdriver, loosen the screw that secures the riser to the system.
4. Press the release tab, and holding the riser by its edges, lift the riser from the riser connector on the system board.
Prerequisites
WARNING: Allow the memory modules to cool after you power off the system. Handle the memory modules by
the card edges and avoid touching the components or metallic contacts on the memory module.
CAUTION: To ensure proper system cooling, memory module blanks must be installed in any memory socket that
is not occupied. Remove memory module blanks only if you intend to install memory modules in those sockets.
Steps
1. Locate the appropriate memory module socket.
CAUTION: Handle each memory module only by the card edges, ensuring not to touch the middle of the
memory module or metallic contacts.
2. Push the ejectors outward on both ends of the memory module socket at the same time to release the memory module from
the socket.
3. Lift and remove the memory module from the system.
Steps
1. Using a Torx #T30 screwdriver, loosen the screws on the heat sink.
NOTE: Ensure that you loosen one screw before moving on to the next screw.
2. Pushing both blue retention clips simultaneously, lift the processor and heat sink module (PHM) out of the system.
3. Set the PHM aside with the processor side facing up.
Steps
1. Disconnect all cables from the system board.
CAUTION: Take care not to damage the system identification button while removing the system board from
the chassis.
CAUTION: Do not lift the system board by holding a memory module, processor, or other components.
2. Holding the system board holder, pull the blue release pin, and slide the system board toward the front of the system to
disengage the connectors from the slots on the system.
3. Incline the system board at an angle, and lift the system board out of the system.
Steps
1. Unpack the replacement system board assembly.
CAUTION: Do not lift the system board by holding a memory module, processor, or other components.
CAUTION: Take care not to damage the system identification button while placing the system board into the
chassis.
2. Holding the system board holder and blue release pin, push the system board toward the back of the system until the release
pin clicks into place.
3. Reconnect all cables to the system board.
WARNING: The heat sink may be hot to touch for some time after the system has been powered down. Allow the
heat sink to cool before removing it.
Steps
1. Align the pin 1 indicator of the heat sink to the system board and then place the processor and heat sink module (PHM) on
the processor socket.
CAUTION: To avoid damaging the fins on the heat sink, do not press down on the heat sink fins.
NOTE: Ensure that the PHM is held parallel to the system board to prevent damaging the components.
2. Push the blue retention clips inward to allow the heat sink to drop into place.
3. Using the #Torx T30 screwdriver with adjustable torque, tighten one screw at a time.
NOTE: The processor and heat sink module retention screws should not be tightened to more than 0.13 kgf-m (1.35
N.m or 12 in-lbf).
Prerequisites
CAUTION: To ensure proper system cooling, memory module blanks must be installed in any memory socket that
is not occupied. Remove memory module blanks only if you intend to install memory modules in those sockets.
Steps
1. Locate the appropriate memory module socket.
CAUTION: Handle each memory module only by the card edges, ensuring not to touch the middle of the
memory module or metallic contacts.
CAUTION: To prevent damage to the memory module or the memory module socket during installation, do
not bend or flex the memory module. You must insert both ends of the memory module simultaneously.
2. Open the ejectors on the memory module socket outward to allow the memory module to be inserted into the socket.
3. Align the edge connector of the memory module with the alignment key of the memory module socket, and insert the
memory module in the socket.
CAUTION: Do not apply pressure at the center of the memory module; apply pressure at both ends of the
memory module evenly.
NOTE: The memory module socket has an alignment key that enables you to install the memory module in the socket in
only one orientation.
4. Press the memory module with your thumbs until the socket levers firmly click into place.
Steps
1. Align the guide rails on the riser with the standoffs on the side of the system.
2. Lower the riser into the system until the riser connector engages with the connector on the system board.
Steps
To install expansion card riser 2:
a. Align the screw and tab on the riser with the screw hole and slot on the system.
b. Lower the riser into the system until the riser connector engages with the connector on the system board.
c. Using Phillips #2 screwdriver, tighten the screws to secure the riser to the system.
Steps
1. Align the tab on the riser with the slot on the system, and guide rails on the riser with the standoffs on the side of the
system.
2. Lower the riser into the system until the riser edge connector engages with the connector on the system board.
The riser card edge engages with the riser guide on the system.
3. Using a Phillips #2 screwdriver, tighten the screw to secure the riser to the system.
Steps
1. Align the guide rails on the cooling fan assembly with the standoffs on the system.
2. Lower the cooling fan assembly into the system until the cooling fan connectors engage with the connectors on the system
board.
3. Press the release levers to lock the cooling fan assembly into the system.
Steps
1. Align the tabs on the air shroud with the slots on the system.
2. Lower the air shroud into the system until it is firmly seated.
When firmly seated, the memory socket numbers marked on the air shroud align with the respective memory sockets.
Steps
1. Align the tabs on the system cover with the guide slots on the system.
2. Push the system cover latch down.
The system cover slides forward, the tabs on the system cover engage with the guide slots on the system and the system
cover latch locks into place.
3. Using a flat or Phillips head screwdriver, rotate the latch release lock clockwise to the locked position.
Steps
1. Verify that nothing has dropped into the empty PSU slot before installing the replacement PSU.
2. Slide the PSU into the system until the PSU is fully seated and the release latch snaps into place.
3. Connect the power cable to the PSU, and plug the cable into a power outlet.
CAUTION: When connecting the power cable to the PSU, secure the cable to the PSU with the strap.
NOTE: When installing, hot swapping, or hot adding a new PSU, wait for 15 seconds for the system to recognize the
PSU and determine its status. The PSU redundancy may not occur until discovery is complete. Wait until the new PSU is
discovered and enabled before you remove the other PSU. The PSU status indicator turns green to signify that the PSU
is functioning properly.
NOTE: Make sure the cables remain clear of the chassis as it slides back into place.
Steps
1. Use the cable labels to reconnect the cables in the same configuration as they were before starting the replacement
procedure.
CAUTION: When connecting SAS cables to the SAS cards, ensure there is sufficient slack in the cable to
avoid unnecessary strain on the cable connector and the SAS card when the controller is fully extended from
the rack.
5. If the system does not power on when the AC power cords were reconnected, press the power button on the right control
panel at the front of the system.
Steps
1. Perform one of the following steps:
● Press Y to restore the Service Tag, license, and diagnostics information.
● Press N to navigate to the Dell Lifecycle Controller based restore options.
● Press F10 to restore data from a previously created Hardware Server Profile.
After the restore process is complete, the BIOS prompts to restore the system configuration data.
2. Perform one of the following steps:
● Press Y to restore the system configuration data.
● Press N to use the default configuration settings.
After the restore process is complete, the system restarts.
Steps
1. Press F2 to enter System Setup.
2. Click Service Tag Settings.
3. Enter the Service Tag.
NOTE: You can enter the Service Tag only when the Service Tag field is empty. Ensure that you enter the correct
Service Tag. After the Service Tag is entered, it cannot be updated or changed.
4. Click Ok.
5. Import your new or existing iDRAC Enterprise license.
For more information, see the Integrated Dell Remote Access Controller User's Guide for your version of iDRAC at Dell
Support.
Prerequisites
The system must support iDRAC9, and you need to know the first two digits of the iDRAC firmware version.
Prerequisites
The .pm firmware file must be on the local system you are using to connect to iDRAC.
Steps
1. Using your laptop, connect a USB port on laptop to the console port on the front of the PowerProtect system. Use the
default IP address 192.168.0.120.
2. Login with the user name root and the password calvin.
3. Select Maintenance > System Update > Manual Update.
4. Select Local for the location type.
5. Click Choose File to browse for the firmware file on the local system. Note the version number in the file name.
6. Click Upload to upload the file to the PowerProtect DD system.
7. Select the firmware file in the Upgrade Details area and click Install.
Next steps
After a system board replacement, all user-configured iDRAC settings and users are reset to the system defaults. Use the
record of those settings written down at the beginning of the system board replacement procedure to reconfigure iDRAC.
2. After verifying that the disks are visible to the destination system as foreign devices, run the following command in BASH
mode.
CAUTION: This command must be run by a qualified user with BASH access.
# system headswap
The system responds:
NOTE: This command might take 30 minutes or longer to complete, depending on the number of shelves and the
amount of data on the shelves. The system should reboot automatically to complete the headswap process.
4. If the system headswap command fails , run the following command in bash mode.
# dd_voltool –-headswap
5. Run the disk show state command to verify the system has updated the disk status.
The output should indicate that the data storage is in the In Use state.
6. Run the filesys status command to verify the status of the file system.
The system displays the message The filesystem is locked: Use 'filesys encryption unlock' to
enter the passphrase. if the file system is encrypted and locked.
7. If necessary, run the filesys encryption unlock command to unlock the file system.
The security officer must enter the system passphrase to unlock the file system.
8. Determine if the system time must be corrected. If it must be corrected:
CAUTION: The file system is disabled if the difference between the time on the system and the NTP time
is more than 60 seconds. KB article 497028 The Data Domain File System (DDFS) may be disabled if there
is a backwards jump in system time configured on the system , available from Dell Support, provides more
information.
a. Run the ntp status command and note the NTP status, time, and date.
# ntp status
Status Enabled
Current Clock Time Thu Feb 20 00:41:22.411 2020
Clock Last Synchronized Thu Feb 20 0 0:38:18.196 2020
Clock Last Synchronized With Time Server 10.173.240.1
# date
Thu Jan 01 00:31:33 PST 2017
c. If the NTP time and system time are not within 60 seconds of each other, run the ntp disable command to disable
NTP.
# ntp disable
# ntp enable
f. Run the alerts show current command to verify there are no active alerts on the system.
# filesys enable
NOTE: If the date and time were set backwards, an error message is logged in the messages.engineering log on
the system. This message identifies the change and notes that the file system is disabled. KB article 497028 The Data
Domain File System (DDFS) may be disabled if there is a backwards jump in system time configured on the system,
available from https://support.emc.com/, provides more information.
9. Run the system upgrade status to check the progress of the system upgrade and index rebuild.
NOTE:
● Only trained and qualified service engineer should be allowed to install or replace this equipment.
● Before removing the chassis, label all cables attached to the chassis so that the cables can be reconnected correctly
after the chassis replacement.
● During the procedure, wear a grounding wrist strap to avoid ESD damage to the equipment.
Place the current chassis and the new chassis on an ESD-free work surface that is large enough for the new and old systems to
be side-by-side on a table or counter top to ensure the correct placement of all components in the new chassis.
The system may take more than an hour to reboot after a chassis replacement due to automatic firmware updates on the new
chassis.
CAUTION: If any components are not fully seated, the system may not boot upon completion of the procedure.
When installing a component into the system, verify it is fully seated before proceeding to the next step.
Topics:
• Preliminary and troubleshooting steps
• Shut down and disconnect the system
• Remove the system from the cabinet
• Remove a PSU
• Remove the front bezel to access front panel hard drives
• Remove a hard drive
• Remove the system covers
• Remove the cooling fan assembly
• Removing the air shroud
• Remove expansion card risers
• Remove the system board
• Install the system board
• Install expansion card riser 1
• Install expansion card riser 2
• Install expansion card riser 3
• Installing the air shroud
• Install the cooling fan assembly
• Install the system cover
Steps
If the system is online, it is beneficial to run the following commands and save the output on the system that is to be replaced
before replacing the chassis. If the system is not online, skip this step and proceed with the procedure to replace the chassis.
Use this information to verify that the procedure has completed successfully:
NOTE:
● When you run these commands before and after the chassis replacement, the output should be the same. Save this
information in case any configuration problems are found after the procedure has completed.
● See the DD OS Command Reference Guide for detailed information about these commands.
Prerequisites
Establish a connection to the system.
Steps
1. Stop the system using the system poweroff command to allow the proper shut down of the file system and other system
components. The power down process takes approximately five minutes to complete. The system poweroff command
immediately turns the front panel blue LED to amber, and is complete when the front panel LED turns off.
NOTE: The system fans still run, and NIC port LEDs still flash after running the system poweroff command.
Steps
1. At the front of the cabinet, locate the two slam latches on left and right side of the system. Pull the slam latches up to
release the system from the cabinet. If the slam latches do not disengage, loosen the screw under each latch.
2. Using the slam latches, pull the system from the cabinet until the rails lock in the extended position.
3. Locate the lock levers on the sides of the inner rails (1). Unlock each lever by rotating it up to its release position (2). Grasp
the sides of the system (3) firmly and pull it forward until the standoffs are at the front of the J-slots in the rails. Lift the
system up and away from the rails.
4. Place the system on a suitable work surface. Ensure the work surface(s) is capable of supporting the weight.
Remove a PSU
Prerequisites
Follow the safety guidelines listed in Safety instructions.
Steps
1. Disconnect the power cable from the power source and from the PSU you intend to remove, and then remove the cable
from the strap on the PSU handle.
2. Press the release latch and slide the PSU out of the system by using the PSU handle.
Steps
1. Unlock the bezel by using the bezel key.
2. Press the release button, and pull the left end of the bezel.
3. Unhook the right end, and remove the bezel.
Prerequisites
Follow the safety guidelines listed in Safety instructions.
Steps
1. Press the release button to open the hard drive release handle.
2. Holding the handle, slide the hard drive out of the hard drive slot.
3. If you are not replacing the hard drive immediately, insert a hard drive blank in the empty hard drive slot to maintain proper
system cooling.
Prerequisites
Follow all safety guidelines.
Steps
1. Using a flat or a Phillips head screwdriver, rotate the latch release lock counter clockwise to the unlocked position.
2. Lift the latch till the system cover slides back and the tabs on the system cover disengage from the guide slots on the
system.
3. Hold the cover on both sides, and lift the cover away from the system.
Steps
1. If installed, remove the expansion cards from the riser.
2. Disconnect any cables connected to the riser.
3. Press the release latches, and lift the riser from the riser connector on the system board.
Steps
1. If installed, remove expansion cards installed on the riser.
2. Disconnect any cables connected to the riser.
3. To remove expansion card riser 2:
a. Using Phillips #2 screwdriver, loosen the screws that secure the riser to the system.
b. Press the release tab, and holding the riser by its edges, lift the riser from the riser connector on the system board.
Steps
1. If installed, remove expansion cards installed on the riser.
2. Disconnect any cables connected to the riser.
3. Using Phillips #2 screwdriver, loosen the screw that secures the riser to the system.
4. Press the release tab, and holding the riser by its edges, lift the riser from the riser connector on the system board.
Steps
1. Disconnect all cables from the system board.
CAUTION: Take care not to damage the system identification button while removing the system board from
the chassis.
CAUTION: Do not lift the system board by holding a memory module, processor, or other components.
2. Holding the system board holder, pull the blue release pin, and slide the system board toward the front of the system to
disengage the connectors from the slots on the system.
3. Incline the system board at an angle, and lift the system board out of the system.
Steps
1. Unpack the replacement system board assembly.
CAUTION: Do not lift the system board by holding a memory module, processor, or other components.
CAUTION: Take care not to damage the system identification button while placing the system board into the
chassis.
2. Holding the system board holder and blue release pin, push the system board toward the back of the system until the release
pin clicks into place.
3. Reconnect all cables to the system board.
Steps
1. Align the guide rails on the riser with the standoffs on the side of the system.
2. Lower the riser into the system until the riser connector engages with the connector on the system board.
Steps
To install expansion card riser 2:
a. Align the screw and tab on the riser with the screw hole and slot on the system.
b. Lower the riser into the system until the riser connector engages with the connector on the system board.
c. Using Phillips #2 screwdriver, tighten the screws to secure the riser to the system.
Steps
1. Align the tab on the riser with the slot on the system, and guide rails on the riser with the standoffs on the side of the
system.
2. Lower the riser into the system until the riser edge connector engages with the connector on the system board.
The riser card edge engages with the riser guide on the system.
3. Using a Phillips #2 screwdriver, tighten the screw to secure the riser to the system.
Steps
1. Align the tabs on the air shroud with the slots on the system.
2. Lower the air shroud into the system until it is firmly seated.
When firmly seated, the memory socket numbers marked on the air shroud align with the respective memory sockets.
Steps
1. Align the guide rails on the cooling fan assembly with the standoffs on the system.
2. Lower the cooling fan assembly into the system until the cooling fan connectors engage with the connectors on the system
board.
3. Press the release levers to lock the cooling fan assembly into the system.
Steps
1. Align the tabs on the system cover with the guide slots on the system.
2. Push the system cover latch down.
The system cover slides forward, the tabs on the system cover engage with the guide slots on the system and the system
cover latch locks into place.
3. Using a flat or Phillips head screwdriver, rotate the latch release lock clockwise to the locked position.
Prerequisites
Follow the safety guidelines listed in Safety instructions.
Steps
1. Press the release button on the front of the hard drive to open the release handle.
2. Insert the hard drive into the hard drive slot and slide until the hard drive connects with the backplane.
3. Close the hard drive release handle to lock the hard drive in place.
Steps
1. Align and insert the right end of the bezel onto the system.
2. Press the release button and fit the left end of the bezel onto the system.
3. Lock the bezel by using the key.
Steps
1. Verify that nothing has dropped into the empty PSU slot before installing the replacement PSU.
2. Slide the PSU into the system until the PSU is fully seated and the release latch snaps into place.
3. Connect the power cable to the PSU, and plug the cable into a power outlet.
CAUTION: When connecting the power cable to the PSU, secure the cable to the PSU with the strap.
NOTE: When installing, hot swapping, or hot adding a new PSU, wait for 15 seconds for the system to recognize the
PSU and determine its status. The PSU redundancy may not occur until discovery is complete. Wait until the new PSU is
discovered and enabled before you remove the other PSU. The PSU status indicator turns green to signify that the PSU
is functioning properly.
Steps
1. Pull the inner rails out of the rack until they lock into place.
2. Release the inner rail lock by pulling forward on the white tabs and sliding the inner rail out of the intermediate rails.
1. Intermediate rail
2. Inner rail
5. With the intermediate rails extended, install the system into the extended rails.
Steps
1. Use the cable labels to reconnect the cables in the same configuration as they were before starting the replacement
procedure.
CAUTION: When connecting SAS cables to the SAS cards, ensure there is sufficient slack in the cable to
avoid unnecessary strain on the cable connector and the SAS card when the controller is fully extended from
the rack.
5. If the system does not power on when the AC power cords were reconnected, press the power button on the right control
panel at the front of the system.
# system headswap
5. Log in again as sysadmin.
6. After the file system is up and running, verify the health of the file system by entering these two commands:
# filesys status
NOTE: If the output of this command shows that the file system is down, attempt to enable the file system using the
filesys enable command before entering the filesys show space command.
Steps
1. From the System Misconfigured menu, select Show Head Swap Menu > Do a Head Swap.
2. Select Yes at the confirmation prompt.
3. Run the disk rescan command to discover the disks.
a. If all of the disks are not listed, perform another rescan.
b. If all of the disks are still not listed, reboot the system.
# system headswap
This command returns the system back to its prior operational
conditions. The system will be rebooted before
resuming normal operations.
ok, proceeding.
sysadmin@dd6400-203#
Broadcast message from root (Fri Oct 1 11:46:08 2021):
Steps
1. Unlock the bezel by using the bezel key.
2. Press the release button, and pull the left end of the bezel.
3. Unhook the right end, and remove the bezel.
Steps
1. Align and insert the right end of the bezel onto the system.
2. Press the release button and fit the left end of the bezel onto the system.
3. Lock the bezel by using the key.
Prerequisites
Establish a connection to the system.
Steps
1. Stop the system using the system poweroff command to allow the proper shut down of the file system and other system
components. The power down process takes approximately five minutes to complete. The system poweroff command
immediately turns the front panel blue LED to amber, and is complete when the front panel LED turns off.
NOTE: The system fans still run, and NIC port LEDs still flash after running the system poweroff command.
Steps
1. At the front of the cabinet, locate the two slam latches on the left and right sides of the system. Pull the slam latches up to
release the system from the cabinet. If the slam latches do not disengage, loosen the screw under each latch.
2. Using the slam latches, pull the system from the cabinet until the rails lock in the extended position.
3. Locate the lock levers on the sides of the inner rails (1). Unlock each lever by rotating it up to its release position (2). Grasp
the sides of the system (3) firmly and pull it forward until the standoffs are at the front of the J-slots in the rails. Lift the
system up and away from the rails.
4. Place the system on a suitable work surface. Ensure the work surface(s) is capable of supporting the weight.
Steps
1. Open the front latch and disengage the rail from the flange.
2. Pull the entire rail forward to release the rear end of the rail from the flange.
Steps
1. Remove the two screws holding the CMA bracket to the rail.
Steps
1. Use the included screws to install the outer bracket to the rail.
2. Align the hole of the inner bracket and push down to attach it to the rail.
NOTE: Some pressure is required to push the inner bracket down and secure it. The bracket clicks when it locks in
place.
3. Repeat the preceding steps to attach the outer and inner brackets to the other rail.
Steps
1. Determine where to mount the system, and use masking tape or a felt-tip pen to mark the location at the front and back of
the cabinet.
NOTE: Install the left rail assembly first.
5. For the front end piece, rotate the latch outward and pull the rail forward until the pins slide into the flange, and release the
latch to secure the rail in place.
Steps
1. Align the screws with the designated U spaces on the front and rear rack flanges.
Ensure that the screw holes on the tab of the system retention bracket are seated on the designated U spaces.
Steps
1. Pull the inner rails out of the rack until they lock into place.
2. Release the inner rail lock by pulling forward on the white tabs and sliding the inner rail out of the intermediate rails.
1. Intermediate rail
2. Inner rail
5. With the intermediate rails extended, install the system into the extended rails.
2. Install the arm on the right side of the chassis, on top of the separator with the open side up.
3. Close the arm by connecting it to the bracket on the left side of the chassis.
NOTE: Make sure the cables remain clear of the chassis as it slides back into place.
Steps
1. Use the cable labels to reconnect the cables in the same configuration as they were before starting the replacement
procedure.
CAUTION: When connecting SAS cables to the SAS cards, ensure there is sufficient slack in the cable to
avoid unnecessary strain on the cable connector and the SAS card when the controller is fully extended from
the rack.
5. If the system does not power on when the AC power cords were reconnected, press the power button on the right control
panel at the front of the system.
CAUTION: A module that is hot-inserted into the system remains powered off until the next system reboot.
Topics:
• Adding a PCIe HBA
• Shut down and disconnect the system
• Extend the system from the cabinet
• Remove the system cover
• Install expansion card into expansion card riser
• Install the system cover
• Slide the system into the cabinet
• Reconnect and power on the system
• Configure the new PCIe HBA
Prerequisites
Establish a connection to the system.
Steps
1. Stop the system using the system poweroff command to allow the proper shut down of the file system and other system
components. The power down process takes approximately five minutes to complete. The system poweroff command
immediately turns the front panel blue LED to amber, and is complete when the front panel LED turns off.
NOTE: The system fans still run, and NIC port LEDs still flash after running the system poweroff command.
Steps
1. At the front of the cabinet, locate the two slam latches on the left and right sides of the system. Pull the slam latches up to
release the system from the cabinet. If the slam latches do not disengage, loosen the screw under each latch.
2. Using the slam latches, pull the system from the cabinet until the rails lock in the extended position.
NOTE: When installing a card into riser 2 or 3, open the PCIe card holder latch.
Steps
1. Pull the expansion card latch.
2. If installed, remove the filler bracket.
NOTE: Store the filler bracket for future use. Filler brackets must be installed in empty expansion card slots to maintain
Federal Communications Commission (FCC) certification of the system. The brackets also keep dust and dirt out of the
system and aid in proper cooling and airflow inside the system.
3. Hold the card by its edges, and align the card edge connector with the expansion card connector on the riser.
4. Insert the card edge connector firmly into the expansion card connector until the card is fully seated.
5. Push the expansion card latch.
Steps
1. Align the tabs on the system cover with the guide slots on the system.
2. Push the system cover latch down.
The system cover slides forward, the tabs on the system cover engage with the guide slots on the system and the system
cover latch locks into place.
NOTE: Make sure the cables remain clear of the chassis as it slides back into place.
Steps
1. Use the cable labels to reconnect the cables in the same configuration as they were before starting the replacement
procedure.
CAUTION: When connecting SAS cables to the SAS cards, ensure there is sufficient slack in the cable to
avoid unnecessary strain on the cable connector and the SAS card when the controller is fully extended from
the rack.
5. If the system does not power on when the AC power cords were reconnected, press the power button on the right control
panel at the front of the system.
Steps
1. Connect cables to the new HBA.
2. Use the system show hardware command and confirm that all PCIe HBAs appear.