k8ds PH - n190 E1 01 - csm1020920 321132
k8ds PH - n190 E1 01 - csm1020920 321132
Ordering Information
List of Models
Function Rated input voltage* Relay output Model
Phase sequence and phase 3-phase, 3-wire 200 to 480
SPDT × 1 K8DS-PH1
loss monitoring VAC
* The power supply voltage is the same as the rated input voltage.
1
K8DS-PH
Ratings and Specifications
Ratings
Rated input voltage 3-phase, 200 to 480 VAC (3-wire)
Input load Approx. 2.7 VA
Phase sequence 0.1 s±0.05 s
Operating time
Phase loss 0.1 s max. (when the voltage changes rapidly from 100% to 0% of rated voltage)
Reset method Automatic reset
Indicators Power (PWR): Green, Relay output (RY): Yellow
Output relays One SPDT relay (NC operation)
Rated load
Resistive load
5 A at 250 VAC
5 A at 30 VDC
Output relay ratings Maximum switching capacity: 1,250 VA, 150 W
Minimum load: 5 VDC, 10 mA (reference values)
Mechanical life: 10 million operations min.
Electrical life: 5 A at 250 VAC or 30 VDC:50,000 operations
3 A at 250 VAC/30 VDC:100,000 operations
Ambient operating temperature −20 to 60°C (with no condensation or icing)
Storage temperature −25 to 65°C (with no condensation or icing)
Ambient operating humidity 25% to 85% (with no condensation)
Storage humidity 25% to 85% (with no condensation)
Altitude 2,000 m max.
Terminal screw tightening torque 0.49 to 0.59 N·m
Recommended wire
Solid wire: 2.5 mm2
Twisted wires: AWG16, AWG18
Note: 1. Ferrules with insulating sleeves must be used with twisted wires.
Terminal wiring method 2. Two wires can be twisted together.
Recommended ferrules
Al 1,5-8BK (for AWG16) manufactured by Phoenix Contact
Al 1-8RD (for AWG18) manufactured by Phoenix Contact
Al 0,75-8GY (for AWG18) manufactured by Phoenix Contact
Case color N1.5
Case material PC and ABS, UL 94 V-0
Weight Approx. 60 g
Mounting Mounts to DIN Track.
Dimensions 17.5 × 80 × 74 mm (W×D×H)
2
K8DS-PH
Specifications
Input voltage range 200 to 480 VAC
Input frequency 50/60 Hz (no presumed range)
Overload capacity Continuous 500 V
80%±10% of rated input
Calculation Formula
Phase loss detection level
= 1 − ((Highest phase-to-phase voltage − Lowest phase-to-phase voltage)/Average three-
phase phase-to-phase voltage)
EN 60947-5-1
Conforming standards
Installation environment (pollution level 2, installation category III)
Applicable
EMC EN 60947-5-1
standards
UL 508 (Recognition), Korean Radio Waves Act (Act 10564),
Safety standards
CSA: C22.2 No.14, CCC: GB14048.5
20 MΩ min.
Insulation resistance Between external terminals and case
Between input terminals and output terminals
2,000 VAC for one minute
Dielectric strength Between external terminals and case
Between input terminals and output terminals
1,500 V power supply terminal common/normal mode
Noise immunity
Square-wave noise of ±1 µs/100 ns pulse width with 1-ns rise time
Frequency: 10 to 55 Hz, acceleration 50 m/s2
Vibration resistance
10 sweeps of 5 min each in X,Y, and Z directions
Shock resistance 100 m/s2, 3 times each in 6 directions along 3 axes
Degree of protection Terminals: IP20
70
60
Ambient temperature [°C]
50
40
30
20
10
0 5 10 15 20 25 30 35 40 45 50
Distance between products d [mm]
Test method
Sample: K8DS-PH
Distance between products: 0, 5, and 10 mm min.
3
K8DS-PH
Connections
Terminal Diagram
Control Output
Input Voltages
Relay output L1 L2 L3
250 VAC, 5 A (resistive load)
30 VDC, 5 A (resistive load)
L1 L2 L3
3-phase,
3-wire
power
supply
Phase-to-phase voltage:
Relay Output 200 to 480 VAC
14 12 11
14 12 11
Wiring Example
L1
3-phase L2
Motor
voltage
L3
L1 L2 L3
Power supply
AC/DC
14 12 11
Timing Charts
●Phase Sequence and Phase Loss Operation
Diagram
Phase Loss Operation Phase Sequence Operation
L2 L1 L3 L1
L1
L1 L3 L2 L2
Input L2
L3 L2 L1 L3
L3
Relay 11-14
4
K8DS-PH
Nomenclature
Front
Terminal block ●Indicators
(See notes 1 and 2.)
Item Meaning
Power indicator
L1 L2 L3 Lit when power is being supplied*.
(PWR: Green)
Relay status indi-
cator Lit when relay is operating (normally lit).
(RY: Yellow)
* This indicator uses the input across L2 and L3 as the internal power
Power indicator
supply. It will not light unless there is an input across L2 and L3.
Note: 1. Use either a solid wire of 2.5 mm2 maximum or a ferrule with
Relay status indicator insulating sleeve for the terminal connection.
The length of the exposed current-carrying part inserted into
the terminal must be 8 mm or less to maintain dielectric
strength after connection.
For 2.5 mm2 or For ferrules with
smaller solid wires an insulation sleeve.
8 mm max. 8 mm max.
14 12 11 Recommended ferrules
Phoenix Contact
• Al 1,5-8BK (for AWG16)
• Al 1-8RD (for AWG18)
• Al 0,75-8GY (for AWG18)
2. Tightening torque: 0.49 to 0.59 N·m
Operation Methods
Connections
●Input
Connect using L1, L2, and L3.
Make sure the phase sequence is wired correctly. The Unit will not
operate normally if the phase sequence is incorrect.
●Outputs
Terminals 11, 12, and 14 are the output terminals SPDT.
* Use the recommended ferrules if you use twisted wires.
L1 L2 L3
Voltage input
L1
L2
L3
14
11
Signal output
12 Relay signal
output
Load
5
K8DS-PH
Dimensions (Unit: mm)
45 80
44
69
15 25 25 25 25 15 (5)* 1
10 10
1,000 (500)*
*Dimensions in parentheses are for the PFP-50N.
6
K8DS-PH
Q Checking Operation Q Is it possible to detect phase losses for motor loads while
the motor is operating?
Phase Sequence
Switch the wiring, as shown by the dotted lines in the Phase loss can be detected while the motor is operating.
connection diagram, to reverse the phase sequence and However, the detection conditions depend on the load
check that the K8DS operates. conditions that are shown in the following figure. Understand
Phase Loss these characteristics when using this feature.
Create a phase loss for any input phase and check that the
K8DS operates. Normally, three-phase motors will continue to rotate even if
one phase is open. The three-phase voltage will be induced
Connection Diagram at the motor terminals. The diagram shows voltage induction
at the motor terminals when phase R has been lost with a
3φ,
200 VAC
load applied to a three-phase motor. The horizontal axis
L1 L1 shows the motor load as a percentage of the rated load, and
the vertical axis shows voltage as a percentage of the rated
L2 L2
voltage. The solid line in the this graph shows the voltage that
L3 L3
is induced at the motor terminals when a phase loss occurs
while the motor is operating under various loads. The figure
below shows how a phase loss that occurs while the motor is
operating causes an imbalance in the voltage across each
Q Can phase loss be detected on the load side?
motor terminal. The K8DS-PH1 detects phase loss when the
In principle, phase loss cannot be detected on the load side motor is operating when the voltage is unbalanced.
because the K8DS-PH measures three-phase voltage to (Detection occurs when the imbalance is 80% of the
determine phase loss. maximum phase). The K8DS-PH1 cannot detect phase loss
with light motor loads because the voltage imbalance is too
small. The detectable range is shown by the diagonal lines.
100
95
90 VST
85
80
VTR
75
70
Detectable
65 area
60
55
50
45 VRS
0 10 20 30 40 50 60 70 80 90 100 110
Motor load (as a percentage of rated load)
Note: For phase loss of phase R. VST, VTR, and VRS indicate the motor
terminal voltage at phase loss.
7
K8DS-PH
Safety Precautions
Be sure to read the precautions for all models in the website at the following URL: http://www.ia.omron.com/.
Warning Indications
WARNING
Indicates a potentially hazardous situation
which, if not avoided, will result in minor or
Electrical shock may occasionally cause serious injury.
WARNING moderate injury, or may result in serious
Confirm that the input voltage is OFF before starting any
injury or death. Additionally there may be
wiring work and wire all connections correctly.
significant property damage.
Indicates a potentially hazardous situation
CAUTION which, if not avoided, may result in minor or
moderate injury or in property damage.
Precautions for Safe Supplementary comments on what to do or
CAUTION
Use avoid doing, to use the product safely.
Precautions for Supplementary comments on what to do or Electrical shock may cause minor injury.
Correct Use avoid doing, to prevent failure to operate, Do not touch terminals while electricity is being supplied.
malfunction, or undesirable effects on
product performance.
There is a risk of minor electrical shock, fire, or device failure.
Meaning of Product Safety Symbols Do not allow any pieces of metal, conductors, or cutting chips
that occur during the installation process to enter the product.
Used for general prohibitions for which there is no There is a risk of minor electrical shock, fire, or device failure.
specific symbol. Do not disassemble, modify, repair, or touch the inside of the
product.
Used for general mandatory action precautions for Use of excessive torque may damage the terminal screws.
which there is no specified symbol. Tighten terminal screws to the specified torque of 0.49 to
0.59 N·m.
Use of the product beyond its life may result in contact welding
or burning. Make sure to consider the actual operating
conditions and use the product within its rated load and
electrical life count. The life of the output relay varies
significantly with the switching capacity and switching
conditions.
8
K8DS-PH
9
MEMO
10
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have
any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing
by Omron). Omron disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE
PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL
SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products
or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at Omron’s election,
to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the
non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price
of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other
claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored,
installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by
Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or
unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system
assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in
writing, are not to be construed as an amendment or addition to the above warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is
not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system,
or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with
respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it
to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice
to change part numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be
assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to
confirm actual specifications of purchased Product.
OMRON ASIA PACIFIC PTE. LTD. OMRON (CHINA) CO., LTD. © OMRON Corporation 2014 All Rights Reserved.
No. 438A Alexandra Road # 05-05/08 (Lobby 2), Room 2211, Bank of China Tower, In the interest of product improvement,
Alexandra Technopark, 200 Yin Cheng Zhong Road, specifications are subject to change without notice.
Singapore 119967 PuDong New Area, Shanghai, 200120, China CSM_1_1_0314
Tel: (65) 6835-3011/Fax: (65) 6835-2711 Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200 Cat. No. N190-E1-01 0513
0314 (0314)
Mouser Electronics
Authorized Distributor
Omron:
K8DS-PH1 200/480VAC