SE QUEDA
CONTIGO
OWNER’S MANUAL
CONTROL PANEL AND ACCESORIES
FORT MODULAR AIR-COOLED SCREW CHILLERS
IMPORTADO POR:
AIR TECNIA SA DE CV
RUFINA 34 COL TACUBAYA CIUDAD MEXICO,
MEXICO
High Prestige HVAC
IMPORTANTE:
Lea con atención este manual antes de instalar o hacer funcionar la nueva unidad de aire acondicionado.
Asegúrese de guardar este manual para su consulta posterior.
[email protected]
Tel. +52 998 251 0602
www.hprestige.com
To Users
Thank you for selecting HPS’s product. Please read this instruction manual carefully before installing
and using the product, so as to master and correctly use the product. In order to guide you to correctly
install and use our product and achieve expected operating effect, we hereby instruct as below:
(1) This instruction manual is a universal manual, some functions are only applicable to particular product.
All the illustrations and information in the instruction manual are only for reference.
(2) In order to make the product better, we will continuously conduct improvement and innovation. We
have the right to make necessary revision to the product from time to time due to the reason of sales
or production, and reserve the right to revise the contents without further notice.
(3) For personal injury or property loss and damage caused by improper operation such as improper
installation and debugging, unnecessary maintenance, violation of related national laws and rules and
industrial standard, and violation of this instruction manual, etc., we will bear no liability.
(4) The final right to interpret for this instruction manual belongs to High Prestige Systems (HPS).
Contents
Safety Notices (Please be sure to abide)................................................................ 1
1 General.................................................................................................................... 2
2 Connection between Modules............................................................................... 2
2.1 DIP Switch Address Setting............................................................................................... 2
2.2 Connection Instructions..................................................................................................... 2
3 Connection of the Remote Monitoring System................................................... 2
3.1 Modbus Address Setting................................................................................................... 2
3.2 Baud Rate Setting............................................................................................................. 3
3.3 Connection Instructions of the Remote Monitoring.......................................................... 5
Control Panel and Accessories for Modular Air-cooled Screw Chillers
Safety Notices (Please be sure to abide)
(1) All modules shall be powered with one power supply.
(2) Do not expose the control panel to the moist pace or direct sunlight.
(3) When the air conditioning system is installed where vulnerable to the electromagnetic interference, the
communication line of the control panel shall be the shielded twisted pair.
(4) Be sure the communication line is placed to the correct port, otherwise it would cause communication
fault.
(5) Do not strike or frequently disassemble/reassemble the control panel.
(6) Do not operate the control panel with wet hands.
The pictures covered in this manual may not be completely the same with those of the real images.
This product is subject to any necessary modification by the manufacturer duo to sales or fabrication
change anytime without advanced notice.
1
1 General
The modular air-cooled screw chiller generally consists of 1~4 single modules (based on the actual load
demand) as well as control and accessories herein.
Control and accessories includes one control panel and two pieces of communication lines for each
module.
The control panel is intended to control the module and display the module data, and also provide a
Modbus RS485 interface which is capable of integrating the module with the building management system
or remote monitoring system. See the operation manual of the control panel of the modular air-cooled
screw chillers for more details.
Two communication lines are used to connect the remote monitoring system.
2 Connection between Modules
2.1 DIP Switch Address Setting
Each module shall have a unique address which is defined as per the setting of its DIP switch shown in
the figure below.
Module 1 Module 2 Module 3 Module 4
2.2 Connection Instructions
Follow the steps stated below for the internal connection as shown in the figure below.
Step 1: Connect the communication line of module 1 from its main board CN25 to its control panel CN1.
Step 2: Connect the communicaton line of module 1 from its main board CN33 to CN25 on module 2.
Step 3: Connect the communicaton line of module 2 from its main board CN33 to CN25 on module 3.
Step 4: Connect the next module in the same way.
To
connect
the next
module
Main Board 1 Main Board 2 Main Board 3
3 Connection of the Remote Monitoring System
3.1 Modbus Address Setting
Each single unit is an object for communication in the remote monitoring system and is distinguished
from each other by a specific modbus address which can be set through the control panel ranging from
1~255 as stated below.
2
Control Panel and Accessories for Modular Air-cooled Screw Chillers
Step 1: After the control panel is power on, press the “Menu” button to access to the menu page, and
then on the menu page select “User Setting” by pressing the ▲/▼ button and then press the “OK” button.
Later, a prompt dialog box will pop up, telling “Please input the password”. Once the password is identified,
it will access to the page as shown below.
Step 2: Select the option of “Modbus Address” by pressing the ▲/▼ button and then press the “OK”
button to access to the setting page where it is allowed to set the Modbus address by pressing the ▲/▼
button. After that, press the “OK”button to finish this setting. The setting page is as shown in the figure
below.
3.2 Baud Rate Setting
Three baud rates, 4800, 9600 and 19200 are supported for the remote monitoring system. The default
is 9600. During installation, it is allowed to set the baud rate through the control panel. Unless otherwise
specified, all control panels shall be set to the same baud rate following the steps stated below.
Step 1: After the control panel is power on, press the “Menu” button to access to the menu page, and
then on the menu page select “Factory Setting” by pressing the ▲/▼ button and then press the “OK”button.
Later, a prompt dialog box will pop up, telling “Please input the password”.
3
Factory Parameter
Factory Parameter Setting:
Please input password: 0 *****
Exit Enter
Press <▲▼> to adjust and <ENTER> to switch. Menu
Step 2: Modify the password number by pressing the he ▲/▼ button and move the cursor by pressing
the “OK” button. Once the password numbers are all input and identified, it will access to the first page of
“Factory Setting” as shown in the figure below.
200kPa
Step 3: Select the option of “Baud Rate”by pressing the ▲/▼ button as shown in the figure below.
Step 4: Press the “OK” button to access to the setting page and set it as expected by pressing the ▲/▼
button. After that, press the “OK” button to finish this setting. The setting page is as shown in the figure
below.
4
Control Panel and Accessories for Modular Air-cooled Screw Chillers
3.3 Connection Instructions of the Remote Monitoring
Structure Diagram of the Patches Boards for Communication between the BASes and the Units
L5 L5 L5
CN25 CN25 CN25
L1 L1 L1
Main Baord 2 Main Board 3
Main Board 1
CN 2
Patch Board 1 Patch Board 2 Patch Board 3
To connect the
next patch
board
L2 L2 L2
CN 7
L3 CN 11
RS485/RS232 Repeater
L4
PC
Figure 16 BAS Connection Diagram of the Air-cooled Screw Chiller
Communication Lines Descriptions
Material: Class 5 twisted pairs, AWG24, 8m, each piece for each control panel.
L1(Standard) Line end: Four-cord socket
Usage: It is used to connect the wired controller and the patch board for BAS control.
5
HIGH PRESTIGE SYSTEMS
E-mail: [email protected] www.hprestige.com