Hitachi VRF SetFree FSN2 Indoor
Hitachi VRF SetFree FSN2 Indoor
Models
Indoor Units
In-the-Ceiling Type
RPI-0.8FSN2 RPI-1.0FSN2 RPI-1.5FSN2
Technical Catalogue RPI-2.0FSN2 RPI-2.5FSN2 RPI-3.0FSN2
RPI-4.0FSN2 RPI-5.0FSN2
for Indoor Unit RPI-8FSN RPI-10FSN
4-Way Cassette Type
RCI-1.0FSN2 RCI-1.5FSN2 RCI-2.0FSN2
RCI-2.5FSN2 RCI-3.0FSN2 RCI-4.0FSN2
RCI-5.0FSN2
2-Way Cassette Type
RCD-1.0FSN2 RCD-1.5FSN2 RCD-2.0FSN2
RCD-2.5FSN2 RCD-3.0FSN2 RCD-4.0FSN2
RCD-5.0FSN2
Wall Type
RPK-1.0FSNSM2 RPK-1.5FSNSM2 RPK-2.0FSNSM2
RPK-2.5FSNSM2 RPK-3.0FSNSM2 RPK-4.0FSNSM2
Floor Type
RPF-1.0FSN2E RPF-1.5FSN2E
Floor Concealed Type
RPFI-1.0FSN2E RPFI-1.5FSN2E
Ceiling Type
RPC-2.0FSN2 RPC-2.5FSN2 RPC-3.0FSN2
RPC-4.0FSN2 RPC-5.0FSN2
System Equipment
Total Heat Exchangers
KPI-2521 KPI-5021 KPI-8021 KPI-10021
TIP No 1:
TIP No 2:
Take advantage
of diversity factor
will reduce your
initial capital as
well as ongoing
running cost.
TIP No 3:
TIP No 4:
TIP No 5:
Having minimum
Change Over box in same
zone will prevent units
from fighting against each
others and save energy.
TIP No 6:
Unbalanced selection
will cause small unit
starve from Refrigerant
and run longer than
it should be.
CONTENTS
Technical Data
Items Page
1. Features 1-5
1.1 System Features 1-5
1.2 Features on Indoor Unit 1-12
1.2.1 In-the-Ceiling Type 1-12
1.2.2 4-Way Cassette Type 1-13
1.2.3 2-Way Cassette Type 1-16
1.2.4 Wall Type 1-18
1.2.5 Floor Type 1-20
1.2.6 Floor Concealed Type 1-20
1.2.7 Ceiling Type 1-21
1.3 Features on Total Heat Exchangers 1-22
1.4 Features on Optional Liquid Crystal Remote Control Switch,
Wireless Remote Control Switch, Half Size Remote Control Switch, 1-23
7-Day Timer and Central Stations
1.4.1 Lineup 1-23
1.4.2 Liquid Crystal Remote Control Switch, PC-AR (Optional) 1-23
1.4.3 Wireless Remote Control Switch, PC-LH3A (Optional) 1-25
1.4.4 Half Size Remote Control Switch, PC-ARH (Optional) 1-26
1.4.5 7-Day Timer, PSC-A1T (Optional) 1-27
1.4.6 Central Station, PSC-5S (Optional) and PSC-A64S (Optional) 1-28
1.4.7 Centralized ON/OFF Controller, PSC-A16RS (Optional) 1-30
2. General Data 1-31
3. Dimensional Data 1-43
3.1 Dimensional Data for Indoor Units 1-43
3.2 Dimensional Data for Total Heat Exchangers 1-56
4. Selection Data 1-57
4.1 Operation Space 1-57
4.2 Selection Guide 1-60
4.3 Sensible Heat Factor (SHF) 1-62
4.4 Fan Performance 1-63
4.5 Model Selection of Total Heat Exchangers 1-68
5. Electrical Data 1-72
6. Sound Data 1-74
7. Working Range 1-87
iv
CONTENTS
Technical Data
Items Page
8. Optional Accessories 1-88
8.1 for Control Systems 1-88
8.1.1 Liquid Crystal Remote Control Switch (PC-AR) 1-88
8.1.2 Wireless Remote Control Switch (PC-LH3A) 1-88
8.1.3 Half Size Remote Control Switch (PC-ARH) 1-88
8.1.4 7-Day Timer (PSC-A1T) 1-88
8.1.5 Central Station (PSC-5S and PSC-A64S) 1-89
8.1.6 Centralized ON/OFF Controller (PSC-A16RS) 1-93
8.1.7 Receiver Kit (PC-ALH, PC-ALHD, PC-ALHP and PC-ALHZ) 1-93
8.1.8 Remote Control Cable <for PC-AR>
1-93
(PRC-5K, PRC-10K and PRC-15K)
8.1.9 3P Connector Cable (PCC-1A) 1-93
8.1.10 Remote Sensor (THM-R2A) 1-93
8.2 for Indoor Units 1-94
8.2.1 for In-the-Ceiling Type 1-94
8.2.2 for 4-Way Cassette Type 1-98
8.2.3 for 2-Way Cassette Type 1-109
9. Component Data 1-117
10. Control System 1-124
10.1 Refrigeration Cycle 1-124
10.2 System Control 1-130
10.2.1 Control in a Room 1-130
10.2.2 Group Control from a Remote Place 1-131
10.2.3 Control in a Room/Control from a Remote Place 1-131
10.3 Standard Operation Sequence 1-132
10.4 Safety and Control Device Setting 1-138
10.5 Optional Dip Switch Setting for Capacity Adjustment 1-138
10 6 Electrical
10.6 El t i l Wiring
Wi i Diagram
Di 1-139
1 139
11. Miscellaneous Notes 1-149
12. Standard Specifications 1-151A-B-C
1-151
v
CONTENTS
Installation and Operation
Page
vi
CONTENTS
Installation and Operation
Items Page
11. Installation of Optional Air Panel 2-103
11.1 Air Panel for 4-Way Cassette Type: P-N23WA 2-103
11.2 Air Panel for 2-Way Cassette Type: P-N23DWA and P-N46DWA 2-108
12. Installation of Optional Controller 2-113
12.1 Remote Control Switch : PC-AR 2-114
12.2 Wireless Remote Control Switch: PC-LH3A 2-132
12.3 7-Day Timer : PSC-A1T 2-137
12.4 Central Station: PSC-5S 2-151
12.5 Central Station: PSC-A64S 2-169
12.6 Centralized ON/OFF Controller: PSC-A16RS 2-192
12.7 Wireless Receiver Kit: PC-ALH (for 4-Way Cassette Type) 2-204
12.8 Wireless Receiver Kit: PC-ALHD, PC-ALHP and PC-ALHZ
(for 2-Way Cassette Type, Ceiling Type, In-the-Ceiling Type, 2-210
Floor Type, Floor Concealed Type and Wall Type)
13. Total Heat Exchanger 2-220
13.1 Safety Summary 2-220
13.2 Structure 2-220
13.3 Transportation and Handling 2-221
13.4 Installation 2-221
13.5 Electrical Wiring 2-225
13.6 Test Run 2-232
13.7 Safety and Control Device Setting 2-232
14. Maintenance 2-233
15. Operation 2-234
15.1 Remote Control Switch 2-234
15.2 Before Operation 2-236
15.3 Operation Method 2-236
15.4 Setting of Automatic Swing Louver Direction 2-237
15.5 Automatic Control 2-244
15.6 Identifying of Indoor Units Installed Side by Side 2-245
15.7 Filter Cleaning 2-246
15.8 Filter and Element Cleaning for Total Heat Exchanger 2-249
15.9 Replacing Batteries for Wireless Remote Control Switch 2-250
16. Troubleshooting 2-251
16.1 Initial Troubleshooting 2-251
16.2 Troubleshooting by Alarm Code 2-252
16.3 Troubleshooting in Check Mode by Remote Control Switch 2-254
16.4 Self-Checking of PCB using Remote Control Switch 2-260
16.5 Self-Checking of Remote Control Switch 2-262
vii
TECHNICAL DATA
GENERAL DATA
2. General Data
1-31
GENERAL DATA
1-32
GENERAL DATA
1-33
GENERAL DATA
1-34
GENERAL DATA
1-35
GENERAL DATA
1-36
GENERAL DATA
1-37
GENERAL DATA
NOTES:
1. The nominal capacity is the combined capacity of the HITACHI standard SET-FREE system, and is based on the JIS standard B8616.
Cooling Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
Outdoor Air Inlet Temperature: 35oC DB (95oF DB)
Heating Operation Conditions
Indoor Air Inlet Temperature: 20oC DB (68oF DB)
Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Length: 7.5 Meters Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1 meter beneath the unit and 1 meter from inlet grille.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
1-38
GENERAL DATA
1-39
GENERAL DATA
1-40
GENERAL DATA
1-41
GENERAL DATA
1-42
DIMENSIONAL DATA
3. Dimensional Data
3.1 Dimensional Data for Indoor Units
In-the-Ceiling Type
Models: RPI-0.8FSN2, RPI-1.0FSN2, RPI-1.5FSN2, RPI-2.0FSN2, RPI-2.5FSN2, RPI-3.0FSN2,
RPI-4.0FSN2 and RPI-5.0FSN2
Unit: mm
l - 6
b (Around the Flange)
40 a
e c x 300 = d
300 4 - 40 x 12
20
x
m
22
n
Viewed from A
22
30
120
20
300 l - 6
e c x 300 = d (Around the Flange) Drain Pipe Connection Drain Pipe Connection
(2.0 to 5.0HP Standard Position) (VP25) (0.8 to 1.5HP with Drain-Up
Mechanism)
Refrigerant Gas Pipe Connection
(With i Flare Nut)
Air Outlet
Refrigerant Liquid Pipe Connection
2xv=w
a 75 (Electrical Control Box) (With h Flare Nut) u 45
2x90=180
220
A
q
90
v
r
97
p
23
35
s
t
48.5 f j (Refrigerant Gas Pipe Connection) 246 (Refrigerant Liquid Pipe Connection)
90 (Drain Pipe Connection) 321 (Refrigerant Gas Pipe Connection)
k (Refrigerant Liquid Pipe Connection) 377 (Drain Pipe Connection: 2.0 to 5.0HP)
402 (Drain Pipe Connection: 0.8 to 1.5HP)
Dimension a b c d e f g h i j k
HP
0.8 650 730 1 300 215 553 583 6.35 12.7 70 92
1.0 650 730 1 300 215 553 583 6.35 12.7 70 92
1.5 650 730 1 300 215 553 583 6.35 12.7 70 92
2.0 900 980 2 600 190 803 833 6.35 15.88 77 92
2.5 900 980 2 600 190 803 833 9.53 15.88 77 95
3.0 650 730 1 300 215 553 583 9.53 15.88 77 95
4.0 900 980 2 600 190 803 833 9.53 15.88 (19.05)*1 81 95
5.0 1300 1380 3 900 240 1203 1233 9.53 15.88 (19.05)*1 81 95
*1: In case of using R407C or R22, use 19.05
Dimension l m n p q r s t u v w x
HP
0.8 10 676 720 23 270 182 222 43 220 100 200 226
1.0 10 676 720 23 270 182 222 43 220 100 200 226
1.5 10 676 720 23 270 182 222 43 220 100 200 226
2.0 12 676 720 23 270 182 222 43 220 100 200 226
2.5 12 676 720 23 270 182 222 43 220 100 200 226
3.0 10 756 800 103 350 204 244 123 300 140 280 306
4.0 12 756 800 103 350 204 244 123 300 140 280 306
5.0 14 756 800 103 350 204 244 123 300 140 280 306
1-43
DIMENSIONAL DATA
In-the-Ceiling Type
Models: RPI-8FSN and RPI-10FSN
Unit: mm
50 x 20 = 1000
1250 (Unit)
1372
Air Intake Side
50
25
2, 3 10 15
(170)
102
100
23
78
420 1034 (for Suspension Bolts) 60 340
(Duct Size <outer size>) (Duct Size <outer size>)
1124
340
44
420
470
327
20
20
35
30
164
105
41
Min. 20
Switch Box
JISC8336-1985
(Field-Supplied)
20 20
Min. 20
Service Space
1 : Secure the service space of false ceiling
for cleaning the heat exchanger.
2 : Use the air filter (field-supplied) at the intake side.
And secure the service space for the air filter.
730
3 : Use the canvas duct between the indoor unit and duct
for duct connection in order to eliminate vibration.
800 (at intake and discharge sides)
0
~20
200 150
~30 Dim.
0
0 a b
50 135 HP Ref.
450 50 1
R410A 19.05 9.53
8.0
450
R22, R407C (*) 25.4 12.7
R410A 22.2 9.53
Service Access Panel 10.0
R22, R407C (*) 28.6 12.7
(*): In case of using R22 or R407C, use the accessory adaptor.
1-44
DIMENSIONAL DATA
Unit: mm
20
5 Drain Pipe Connection VP25
6 Wiring Hole for Conduit Tube 32.5 Knockout Hole
7 Wiring Hole 30 x 39 Hole
860~910
760 11 Supply Duct Connection 150 x 400 Knockout Hole
840
25 (Liquid Pipe)
24 (Drain Pipe)
Dimension a b
HP
1.0 12.7 6.35
B 1.5 12.7 6.35
20
C
248
36
31
127 (Liquid Pipe)
102
118 (Drain Pipe)
37
102 (Gas Pipe)
A
Air Inlet Grille
7 6 Optional Air Panel
Optional 12 13 (Field-Supplied) 10
In case of using this,
cut the insulation material 385 30
along to the line indicated 220 100
46
opening position.
2 1
120 7 6 In case of using this,
cut the insulation material
145
150
along to the line indicated
opening position.
5
25
10
25
9-M4 75 135 135 75
127 85
31
150
950
25
10
20 20 10
Viewed from A
Wall Mounting Embedding Cable 9-M4 75 135 135 75
in the Wall (for Self-Tapping Screw)
Mounting for Remote Control Switch (Optional) Enlarged View of E
Min.
Min.
Min.
100
100
100
Service Space
Min.
Min.
100
100
1-45
DIMENSIONAL DATA
20
5 Drain Pipe Connection VP25
6 Wiring Hole for Conduit Tube 32.5 Knockout Hole
7 Wiring Hole 30 x 39 Hole
860~910
10 Supply Duct Connection 150 x 385 Knockout Hole
760
840
11 Supply Duct Connection 150 x 400 Knockout Hole
25 (Liquid Pipe)
24 (Drain Pipe)
18 (Gas Pipe)
Dimension a b
HP
3.0 15.88 9.53
B
20
C
298
127 (Liquid Pipe)
36
31
102
118 (Drain Pipe)
102 (Gas Pipe)
37
A
Air Inlet Grille
7 6 Optional Air Panel
Optional 12 13 (Field-Supplied) 10
In case of using this, 385 30
cut the insulation material 220 100
96
along to the line indicated
opening position.
2 1
120 7 6 In case of using this,
cut the insulation material
145
150
along to the line indicated
opening position.
5
25
10
25
9-M4 75 135 135 75
127 85
31
400 50
Switch Box In case of using this, 11
JISC8336-1985 220 100
96
150
950
20 20
Viewed from A
25
10
Embedding Cable 10
Wall Mounting
in the Wall 9-M4 75 135 135 75
Mounting for Remote Control Switch (Optional) (for Self-Tapping Screw)
Enlarged View of E
Service Space
Min.
Min.
Min.
100
100
100
Min.
Min.
100
100
1-46
DIMENSIONAL DATA
20
5 Drain Pipe Connection VP25
620
670
8 9 Suspension Bolt 4-M10 or W3/8
10 Electrical Control Box
11 Supply Duct Connection 2-150 x 400
12 Remote Control Switch (PC-AR) Optional
Min. 0.75mm2, Field-Supplied
20
50
298
B E
125
55
1 120 10
150
180
15
15
30
90
Enlarged View of D
2
11 In case of using 11 ,
Cut out the insulation
1 9-M4 material along this line.
1100 (for Self-Tapping Screw)
50
400 170
Viewed from A Viewed from B
120 120 120 35
55
70
180
150
Surroundings
in the ceiling 30 185 185
MIN.
500
MIN. MIN.
100 500
3000
MIN.
MIN.
500
Switch Box
JISC8336-1985
(Field-Supplied)
MIN.
500
Separated Installation Closed Installation Mounting for Remote Control Switch (Optional)
1-47
DIMENSIONAL DATA
Unit: mm
20
5 Drain Pipe Connection VP25
6 Wiring Hole for Conduit Tube 32.5
7 Wiring Hole 30 x 39 Hole
8 Suspension Bracket
9 Suspension Bolt 4-M10 or W3/8
540
620
670
10 Electrical Control Box
11 Supply Duct Connection 2-150 x 610
12 Remote Control Switch (PC-AR) Optional
13 Shielded Twist-Pair Cable for PC-AR Min. 0.75mm2, Field-Supplied
*1: In case of using R407C or R22, use 19.05.
20
8
95 (Gas Pipe) 410
95 (Liquid Pipe)
5 4 285
3
25 (Drain Pipe) 205
9
D
298
260
B E
125
115
50
30
445
A
10-M4
Optional 12 13 (Field-Supplied) (for Self-Tapping Screw)
170 610
140 180 160
70
55
10
1 120
180
150
30
15
15
180 180 140
11 In case of using 11 ,
710
70
Piping Connection
150
Surroundings
15
MIN.
110
in the ceiling
500
MIN. MIN.
3000
MIN.
100 500
MIN.
500
90 20 20
MIN. MIN. MIN.
MIN.
MIN.
MIN.
500
500
Separated Installation Closed Installation Mounting for Remote Control Switch (Optional)
Viewed from B
Service Space
NOTE:
1. Distance between the wall and panel edge must
be a min. 1500mm to prevent short circuiting.
1-48
DIMENSIONAL DATA
Wall Type
Models: RPK-1.0FSNSM2 and RPK-1.5FSNSM2
Unit: mm
60
5
5
47 Auto Louver 47
Receiver Part
1 10 Option
125
540 120 56
(PC-AR) (PC-LH3A)
410
480 108
5 4 3
Viewed from A
28
15 35 27 24 20
20 50 20 20 20 20 20 20
20 25 25 25 30 25 25 25
280
20
45
45
20
20x3=6
60 5 38 38 5 115
20 20
65 530 10
780
Min. 150
8 9 7
Switch Box
JISC8336-1985
(Field-Supplied)
20 20
Min. 1000
Unit: mm
Mounting for Remote Control Switch (Option)
(In case of using PC-AR)
Service Space
1-49
DIMENSIONAL DATA
Wall Type
Model: RPK-2.0FSNSM2
Unit: mm
6 6
295
60
60
5
5
47 47
1 Auto Louver
Indication Part Receiver Part 10 Option
A
4 3 125
P a
Pipe Diameter a
5
15.88 440 470
12.7 410
Gas Pipe Connection
550 150
(15.88)
20 20 20 20
295
48.5
20 30 30 40 40 30 30 20 12 8.5 150
45 49
80
45
15
15x4=60
1030
Switch Box
JISC8336-1985
(Field-Supplied)
1-50
DIMENSIONAL DATA
Wall Type
Models: RPK-2.5FSNSM2, RPK-3.0FSNSM2 and RPK-4.0FSNSM2
Unit: mm
Mark Name Remark
1 Air Outlet
2 Air Inlet
1140 3 Refrigerant Gas Pipe Connection with 15.88 Flare Nut
4 Refrigerant Liquid Pipe Connection with 9.53 Flare Nut
Piping
5 Drain Pipe Connection VP16
6 Wiring and Piping Hole Knockout Hole
Piping Piping 7 Wiring and Piping Hole 80 Knockout Hole
8 Wiring and Piping Hole 80 Knockout Hole
9 Suspension Bracket
Remote Control Switch Wired PC-AR
10
(Option) Wireless PC-LH3A
2
2
1150
245
6 6
333
70
70
8
8
60 Auto Louver 60
1
Indication Part Receiver Part
10 Option
A
4 5
125
120 56
(PC-AR) (PC-LH3A)
550
3
572
654 141
Viewed from A
565 433.6
780
660
560
105 100 250 100 105 87
20x5 28 50x4 50x4
20
25
40 20
20
229
20
221
333
141
20
10
60
93
42
42
7
300 300
58 141
8 Outline of the Unit
9
1150
Flange Part for
Min. 100
Switch Box
JISC8336-1985
(Field-Supplied)
20 20
Min. 100 Min. 200
Min. 1000
1-51
DIMENSIONAL DATA
Floor Type
Models: RPF-1.0FSN2E and RPF-1.5FSN2E
Unit: mm
30
168
157
40
163 220
156
52
133
182
630
529
388
260
134
103
315
630
85
220
220
b c
140
b c For Bolt d 228
a 2-12, 15x18 a a
Location of Fixing Holes on Location of Fixing Holes
Location of Fixing Holes on Wall
Floor for Wood Screws (4-M5) on Floor for Bolts (2-M8)
Ceiling
1000
Min.
630
Min. Min.
Wall 300 a 300 Wall
Service Access
Dimension a b c d
HP
1.0 1045 754 217 732
1.5 1170 879 217 857
1-52
DIMENSIONAL DATA
Unit: mm
220
220
122 50
72
13 64 133
19
52
620
315
529
388
52
260
134
114
100
25 55
36 b 85 60
a 103
103
315
620
85
220
220
138
b c b c d 77
a a a
620
640
Dimension a b c d
HP
1.0 863 754 66 732
1.5 988 879 66 857
1-53
DIMENSIONAL DATA
Ceiling Type
Models: RPC-2.0FSN2, RPC-2.5FSN2 and RPC-3.0FSN2
Unit: mm
370
9 3 Cut out the resin along this line.
110 92
27
70
12 (Field-Supplied)
110
148
11 Optional
280
670
120
4-12
(Hole for Suspension Bolt)
(50) b (50) 10
a
Max.50
Suspension Bolt Length 4 8
1 38
Suspension Bracket
52
216
210
160
12
12
70 c 70 118 74
Left Side
Switch Box
JISC8336-1985
176
(Field-Supplied)
20 20
in the Wall
2
205 Refrigerant Gas Piping 156
with 15.88 Flare Nut
5 Cut out the resin along this line. 7
d Refrigerant Liquid Piping 106
with e Flare Nut
67
40
130
104
40
Piping Position 6 9
MIN.40
500
300
MIN.400 4 Hole for Refrigerant Piping
for Right Side Arrangement
Separated Installation 5 Hole for Refrigerant Piping Hole for Rear Side Arrangement
VP20
6 Drain Piping Connection
(for Rear Right Side Arrangement)
VP20
7 Hole for Drain Piping
(for Rear Left Side Arrangement)
MIN. MIN. Knockout Hole
MIN.40 300 300 8 Hole for Drain Piping
for Left Side Arrangement
Closed Installation 9 Wiring Hole for Conduit Tube 26.5 Hole
10 Suspension Bracket
Service Space
11 Remote Control Switch (PC-AR) Optional
12 Shielded Twist-Pair Cable for PC-AR Min. 0.75mm2, Field-Supplied
Dimension a b c d e
HP
2.0 1100 1000 960 200 6.35
2.5 1320 1220 1180 195 9.53
3.0 1320 1220 1180 195 9.53
1-54
DIMENSIONAL DATA
Ceiling Type
Models: RPC-4.0FSN2 and RPC-5.0FSN2
Unit: mm
280
9 3 Cut out the resin
110 92
along this line.
27
70
12 (Field-Supplied)
110
147
11 Optional
280
670
120
4-12
(Hole for Suspension Bolt)
(50) b (50)
a 10
1 4 8
38 Max.50
Suspension Bracket Suspension Bolt Length
276
270
52
160
12
12
70 c 70 118 74
Left Side
Switch Box
JISC8336-1985
176
(Field-Supplied)
20 20
in the Wall
2 210 Refrigerant Gas Piping with 15.88 (*1) Flare Nut 156
40
130
104
MIN.
3 Hole for Refrigerant Piping Hole for Upper Side Arrangem
500
Dimension a b c
HP
4.0 1320 1220 1180
5.0 1580 1480 1440
1-55
DIMENSIONAL DATA
Unit: mm
EA RA
(Exhaust Air) (Return Air)
(Standard Position)
D
A
OA SA
115
(Outside Air) (Supply Air)
(Standard Position)
10
22
Min.600
K
150 to 250
C
Air Supply Fan
Service Access
Panel Position
Electrical Control Box
Service Cover
K
Suspension Bracket
H
Air Filters
1-56
SELECTION DATA
4. Selection Data
4.1 Operation Space
In-the-Ceiling Type
Models: RPI-0.8FSN2, RPI-1.0FSN2, RPI-1.5FSN2, RPI-2.0FSN2, RPI-2.5FSN2, RPI-3.0FSN2,
RPI-4.0FSN2 and RPI-5.0FSN2
Electrical Box Service Access
Door (Min. 450)
Service Space
100 Rear Side of False Ceiling 600
In case that the
1000
ceiling board can
Min.
not be detected
400
Rear Side
for servicing,
prepare a service
access door
below the indoor
275
1000
Min.
View from Bottom Min.
Min. 600
600
View from Top
Service Space
Min. 20
730
800
0
~20
200 150
~30
0
0
135
Min. 20
450 50
50
Service Access Panel Ceiling
Secure the service space
450 of false ceiling for cleaning
the heat exchanger. * Prepare the Service Access Panel for service.
Service Access Panel * In case that the ceiling board is not be detachable
for servicing, prepare a service access panel below
the indoor unit for removing the indoor unit.
Unit: mm
1500
1500
1500
Min.
Min.
Min.
1500
1500
Min.
Min.
Min.
1-57
SELECTION DATA
Service
Min. 1500 Access Min. 1500 10 to 20mm
Service
Panel Access 298mm
Min. Panel Unit Height
Min.
1500 in False Celling
1500
Min.
1500 Unit Height in False Celling
Min.
1500
Min. 1500
Min. 3000
Service Min. 100
Access Min. 500
Piping Connection Side Min. Panel
Separated Installation 1500
Piping
Min. Connection
1500 Side
Min. 1500 Min. 500
Min. 500
Min. 1000
Piping Connection Side
Closed Installation of Two Units Service Space
Distance from Wall Side
Wall Type
Models: RPK-1.0FSNSM2 and RPK-1.5FSNSM2 Model: RPK-2.0FSNSM2
Unit: mm
Min.
150
Min.
150
Unit: mm
Min.
Min.
1000
100
1000
Min.
Min.
Min.
100 Min.
100 100
Unit: mm
100
1000
Min.
Min.
Min.
100 200
1-58
SELECTION DATA
Floor Type
Models: RPF-1.0FSN2E and RPF-1.5FSN2E
Ceiling
1000
Min.
Wall Wall
630
Floor
Min. 300 1170 (1.5HP) Min. 300
1045 (1.0HP)
620
640
Floor Floor
Min. Min. Min. Min.
240 901 (1.5HP) 240 240 901 (1.5HP) 240
776 (1.0HP) 776 (1.0HP)
Service Space
Ceiling Type
Models: RPC-2.0FSN2, RPC-2.5FSN2, RPC-3.0FSN2, RPC-4.0FSN2 and RPC-5.0FSN2
(mm)
Min. 500
Min. 8
EA RA
150 to 250
OA SA
Min. 600
450
Service Access
Door (450 x 450)
450
1-59
SELECTION DATA
SHF
Model
Hi Me Lo
RPI-0.8FSN2 0.73 0.71 0.68
RPI-1.0FSN2 0.73 0.71 0.68
RPI-1.5FSN2 0.74 0.71 0.67
RPI-2.0FSN2 0.73 0.70 0.66
RPI-2.5FSN2 0.70 0.68 0.66
RPI-3.0FSN2 0.71 0.67 0.63
RPI-4.0FSN2 0.69 0.67 0.64
RPI-5.0FSN2 0.73 0.68 0.65
RPI-8FSN 0.72 - -
RPI-10FSN 0.71 - -
RCI-1.0FSN2 0.85 0.83 0.81
RCI-1.5FSN2 0.81 0.77 0.72
RCI-2.0FSN2 0.74 0.71 0.69
RCI-2.5FSN2 0.74 0.70 0.68
RCI-3.0FSN2 0.74 0.67 0.65
RCI-4.0FSN2 0.72 0.71 0.68
RCI-5.0FSN2 0.70 0.66 0.64
RCD-1.0FSN2 0.81 0.76 0.75
RCD-1.5FSN2 0.73 0.70 0.68
RCD-2.0FSN2 0.74 0.70 0.67
RCD-2.5FSN2 0.70 0.69 0.67
RCD-3.0FSN2 0.69 0.69 0.67
RCD-4.0FSN2 0.70 0.68 0.66
RCD-5.0FSN2 0.69 0.67 0.65
RPK-1.0FSNSM2 0.78 0.74 0.71
RPK-1.5FSNSM2 0.73 0.72 0.70
RPK-2.0FSNSM2 0.69 0.68 0.67
RPK-2.5FSNSM2 0.71 0.69 0.68
RPK-3.0FSNSM2 0.74 0.70 0.69
RPK-4.0FSNSM2 0.71 0.69 0.68
RPF-1.0FSN2E 0.73 0.69 0.65
RPF-1.5FSN2E 0.73 0.69 0.65
RPFI-1.0FSN2E 0.73 0.69 0.65
RPFI-1.5FSN2E 0.73 0.69 0.65
RPC-2.0FSN2 0.74 0.71 0.68
RPC-2.5FSN2 0.72 0.69 0.67
RPC-3.0FSN2 0.71 0.68 0.66
RPC-4.0FSN2 0.73 0.70 0.68
RPC-5.0FSN2 0.70 0.68 0.66
1-62
SELECTION DATA
130 130
120 120
110 110
EXTERNAL STATIC PRESSURE (Pa)
90 90
80 80 Hi
Hi
70 70
60 Me 60
Me Hi
50 50
Lo Hi
Me
40 40 Lo Me
30 Lo 30
Me Hi Hi
Lo Me
20 20
Lo
Lo
10 10
0 0
2 3 4 5 6 7 8 9 10 11 5 6 7 8 9 10 11 12 13 14
AIR VOLUME (m3/min) AIR VOLUME (m3/min)
The setting of Normal, High Static Pressure,and Low Static Pressure Mode The setting of Normal, High Static Pressure,and Low Static Pressure Mode
can be changed by Remote Control Switch. can be changed by Remote Control Switch.
RPI-2.0FSN2 RPI-2.5FSN2
130 130
120 120
110 110
EXTERNAL STATIC PRESSURE (Pa)
100 100
90 90
80 Hi 80 Hi
70 70
60 60
Me Me
Hi Hi
50 50
40 40 Me
Lo Me Lo
30 30
Hi Me Hi
Lo Lo
Me
20 20
Lo Lo
10 10
0 0
7 8 9 10 11 12 13 14 15 16 8 9 10 11 12 13 14 15 16 18
AIR VOLUME (m3/min) AIR VOLUME (m3/min)
The setting of Normal, High Static Pressure,and Low Static Pressure Mode The setting of Normal, High Static Pressure,and Low Static Pressure Mode
can be changed by Remote Control Switch. can be changed by Remote Control Switch.
1-63
SELECTION DATA
PI-3.0FSN2 RPI-4.0FSN2
320 320
: Normal Mode (at shipping) : Normal Mode (at shipping)
300 : High Static Pressure Mode 300 : High Static Pressure Mode
: Low Staitc Pressue Mode : Low Staitc Pressue Mode
280 280
260 260
240 240
220 220
200 200
180 180
Hi Hi
160 160
140 140
Me Hi
120 Hi
120
Me
Me 100
100 Me
Lo
80 Lo
80
Lo Hi
60 60
Lo Me Hi
Me
40 40
Lo
Lo
20 20
0 0
11 12 13 14 15 16 17 18 19 20 13 15 17 19 21 23 25 27 29 31
AIR VOLUME (m3/min) AIR VOLUME (m3/min)
The setting of Normal, High Static Pressure, and Low Static Pressure Mode The setting of Normal, High Static Pressure,and Low Static Pressure Mode
can be changed by Remote Control Switch. can be changed by Remote Control Switch.
PI-5.0FSN2
320
: Normal Mode (at shipping)
300 : High Static Pressure Mode
: Low Staitc Pressue Mode
280
260
240
220
EXTERNAL STATIC PRESSURE (Pa)
200
180
Hi
160
140
120 Hi
Me
100
80 Lo Me
60
Lo Hi
Me
40
Lo
20
0
23 25 27 29 31 33 35 37 39 41
AIR VOLUME (m3/min)
The setting of Normal, High Static Pressure,and Low Static Pressure Mode
can be changed by Remote Control Switch.
1-64
SELECTION DATA
RPI-8FSN
High Static Pressure Setting: 220Pa (at shipping) High Static Pressure Setting: 260Pa (at shipping)
Low Static Pressure Setting: 110Pa
Low Static Pressure Setting: 130Pa
380V/50Hz
380V/60Hz 415V/50Hz
350 350
300 300
250 250
Lower Limit of Air Volume
150 150
100 100
50 50
0 0
40 45 50 55 60 65 70 75 40 45 50 55 60 65 70 75
3
AIR VOLUME (m /min) AIR VOLUME (m3/min)
The setting of High Static Pressure and Low Static Pressure Mode can be The setting of High Static Pressure and Low Static Pressure Mode can be
changed by changing the position of the connector inside of the indoor unit. changed by changing the position of the connector inside of the indoor unit.
RPI-10FSN
High Static Pressure Setting: 220Pa (at shipping) High Static Pressure Setting: 260Pa (at shipping)
Low Static Pressure Setting: 110Pa
Low Static Pressure Setting: 130Pa
380V/50Hz
380V/60Hz 415V/50Hz
350 350
300 300
EXTERNAL STATIC PRESSURE (Pa)
250 250
Upper Limit of Air Volume
200 200
150 150
100 100
50 50
0 0
55 60 65 70 75 80 85 90 55 60 65 70 75 80 85 90
3
AIR VOLUME (m /min) AIR VOLUME (m3/min)
The setting of High Static Pressure and Low Static Pressure Mode can be The setting of High Static Pressure and Low Static Pressure Mode can be
changed by changing the position of the connector inside of the indoor unit. changed by changing the position of the connector inside of the indoor unit.
1-65
SELECTION DATA
KPI-2521
Fan Performance and Heat Exchange Efficiency Curve Fan Performance and Heat Exchange Efficiency Curve
70 70
150
150 200 Duct
200 Duct Length
Length
40m
Hi
External Static Pressure (Pa)
0
0 0 50 100 150 200 250 300 350 400
0 50 100 150 200 250 300 350 400
3
Air Volume (m /h) Air Volume (m /h) 3
KPI-5021
Fan Performance and Heat Exchange Efficiency Curve Fan Performance and Heat Exchange Efficiency Curve
Model: KPI-5021
Heat Exchange Efficiency (%)
80
Temperature Exchange
80 400 Efficiency
70
60 300
Total Heat Exchanger Efficiency
50 250 (Cooling Operation)
Total Heat Exchange Efficiency
200 (Cooling Operation)
Duct 50 250
Length 200
External Static Pressure (Pa)
200 Duct
Hi Hi
60m 200
Length
External Static Pressure (Pa)
60m
150 50m
50m
Me 40m
150
Lo Me 40m
100
30m Lo
100
30m
20m
50 20m
50
10m
10m
0
0 100 200 300 400 500 600 700 0
0 100 200 300 400 500 600 700
Air Volume (m3/h) Air Volume (m3/h)
1-66
SELECTION DATA
KPI-8021
Fan Performance and Heat Exchange Efficiency Curve Fan Performance and Heat Exchange Efficiency Curve
Heat Exchange Efficiency (%)
80 600
70 500 70 500
Total Heat Exchanger Efficiency
(Heating Operation) Total Heat Exchange Efficiency
(Heating Operation)
60 400 60 400
Total Heat Exchanger Efficiency
(Cooling Operation) Total Heat Exchange Efficiency
(Cooling Operation)
Duct
Length Hi
Hi
Me 60m 60m
100
40m 100 Me
40m
20m 20m
0 0
0 200 400 600 800 1000 1200 0 200 400 600 800 1000 1200
Do not use the condition that the External Static Do not use the condition that External Static
Pressure is under than 29Pa. Pressure is under than 29Pa.
KPI-10021
Fan Performance and Heat Exchange Efficiency Curve Fan Performance and Heat Exchange Efficiency Curve
Heat Exchange Efficiency (%)
80 600
80 600
Hi 80m Me
External Static Pressure (Pa)
Lo 80m
200 Lo
60m 200
60m
Me
40m
100 40m
100
20m
20m
0
0 200 400 600 800 1000 1200 1400 0
0 200 400 600 800 1000 1200 1400
3
Air Volume (m /h) Air Volume (m3/h)
Do not use the condition that the External Static Do not use the condition that External Static
Pressure is under than 49Pa. Pressure is under than 49Pa.
1-67
ELECTRICAL DATA
5. Electrical Data
< 50 Hz >
Indoor Unit
Unit Main Power Applicable Voltage Indoor Fan Motor
Model
VOL PH HZ Maximum Minimum PH RNC IPT
RPI-0.8FSN2 0.5/0.5 0.10/0.11
RPI-1.0FSN2 0.5/0.5 0.10/0.11
RPI-1.5FSN2 0.7/0.7 0.14/0.15
RPI-2.0FSN2 0.7/0.7 0.14/0.15
220/240 1 50 264 198 1
In-the-Ceiling RPI-2.5FSN2 0.7/0.7 0.14/0.15
Type RPI-3.0FSN2 0.9/0.9 0.19/0.20
RPI-4.0FSN2 1.3/1.4 0.28/0.31
RPI-5.0FSN2 1.9/2.0 0.40/0.46
RPI-8FSN 1.6/1.6 0.99/0.99
380/415 3 50 456 342 3
RPI-10FSN 2.0/2.0 1.23/1.23
RCI-1.0FSN2 0.2/0.2 0.03/0.03
RCI-1.5FSN2 0.2/0.2 0.03/0.03
RCI-2.0FSN2 0.2/0.2 0.04/0.04
4-Way
RCI-2.5FSN2 220/240 1 50 264 198 1 0.3/0.3 0.06/0.06
Cassette Type
RCI-3.0FSN2 0.4/0.3 0.07/0.07
RCI-4.0FSN2 0.7/0.6 0.13/0.13
RCI-5.0FSN2 0.8/0.8 0.16/0.16
RCD-1.0FSN2 0.2/0.2 0.05/0.06
RCD-1.5FSN2 0.3/0.4 0.07/0.08
RCD-2.0FSN2 0.3/0.4 0.07/0.08
2-Way
RCD-2.5FSN2 220/240 1 50 264 198 1 0.4/0.5 0.09/0.11
Cassette Type
RCD-3.0FSN2 0.5/0.6 0.11/0.13
RCD-4.0FSN2 0.6/0.6 0.12/0.14
RCD-5.0FSN2 0.8/0.9 0.18/0.20
RPK-1.0FSNSM2 0.2/0.2 0.03/0.03
RPK-1.5FSNSM2 0.3/0.3 0.03/0.03
RPK-2.0FSNSM2 0.3/0.3 0.03/0.03
Wall Type 220/240 1 50 264 198 1
RPK-2.5FSNSM2 0.3/0.3 0.04/0.04
RPK-3.0FSNSM2 0.3/0.3 0.04/0.04
RPK-4.0FSNSM2 0.5/0.5 0.06/0.06
RPF-1.0FSN2E 0.2/0.2 0.04/0.04
Floor Type 220/240 1 50 264 198 1
RPF-1.5FSN2E 0.2/0.2 0.05/0.05
Floor RPFI-1.0FSN2E 0.2/0.2 0.04/0.04
220/240 1 50 264 198 1
Concealed Type RPFI-1.5FSN2E 0.2/0.2 0.05/0.05
RPC-2.0FSN2 0.4/0.4 0.08/0.09
RPC-2.5FSN2 0.5/0.5 0.09/0.12
Ceiling Type RPC-3.0FSN2 220/240 1 50 264 198 1 0.5/0.5 0.09/0.12
RPC-4.0FSN2 0.8/1.0 0.17/0.22
RPC-5.0FSN2 0.9/1.0 0.18/0.22
VOL: Rated Unit Power Supply Voltage (Plated)(V) RNC: Running Current (A)
PH: Phase () IPT: Input (kW)
HZ: Frequency (Hz)
1-72
ELECTRICAL DATA
< 60 Hz >
Indoor Unit
Unit Main Power Applicable Voltage Indoor Fan Motor
Model
VOL PH HZ Maximum Minimum PH RNC IPT
RPI-0.8FSN2 0.6 0.12
RPI-1.0FSN2 0.6 0.12
RPI-1.5FSN2 0.8 0.16
RPI-2.0FSN2 0.8 0.16
220 1 60 242 198 1
In-the-Ceiling RPI-2.5FSN2 0.8 0.16
Type RPI-3.0FSN2 1.2 0.26
RPI-4.0FSN2 1.5 0.32
RPI-5.0FSN2 2.3 0.49
RPI-8FSN 1.9 1.14
380 3 60 418 342 3
RPI-10FSN 2.3 1.41
RCI-1.0FSN2 0.2 0.03
RCI-1.5FSN2 0.2 0.03
RCI-2.0FSN2 0.2 0.04
4-Way
RCI-2.5FSN2 220 1 60 242 198 1 0.3 0.06
Cassette Type
RCI-3.0FSN2 0.4 0.07
RCI-4.0FSN2 0.7 0.13
RCI-5.0FSN2 0.8 0.16
RCD-1.0FSN2 0.2 0.05
RCD-1.5FSN2 0.4 0.08
RCD-2.0FSN2 0.4 0.08
2-Way
RCD-2.5FSN2 220 1 60 242 198 1 0.5 0.11
Cassette Type
RCD-3.0FSN2 0.6 0.13
RCD-4.0FSN2 0.7 0.14
RCD-5.0FSN2 1.2 0.24
RPK-1.0FSNSM2 0.2 0.03
RPK-1.5FSNSM2 0.3 0.03
RPK-2.0FSNSM2 0.3 0.03
Wall Type 220 1 60 242 198 1
RPK-2.5FSNSM2 0.3 0.04
RPK-3.0FSNSM2 0.3 0.04
RPK-4.0FSNSM2 0.5 0.06
RPF-1.0FSN2E 0.2 0.04
Floor Type 220 1 60 242 198 1
RPF-1.5FSN2E 0.2 0.05
Floor RPFI-1.0FSN2E 0.2 0.04
220 1 60 242 198 1
Concealed Type RPFI-1.5FSN2E 0.2 0.05
RPC-2.0FSN2 0.4 0.09
RPC-2.5FSN2 0.7 0.15
Ceiling Type RPC-3.0FSN2 220 1 60 242 198 1 0.7 0.15
RPC-4.0FSN2 0.9 0.20
RPC-5.0FSN2 0.9 0.20
VOL: Rated Unit Power Supply Voltage (Plated)(V) RNC: Running Current (A)
PH: Phase () IPT: Input (kW)
HZ: Frequency (Hz)
1-73
SOUND DATA
6. Sound Data
In-the-Ceiling Type
Model: RPI-0.8FSN2 Power Supply: 220V, 50/60Hz Model: RPI-1.0FSN2 Power Supply: 220V, 50/60Hz
Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit
90 90
Noise Criteria Curve Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
70 NC-70 70 NC-70
60 NC-60 60 NC-60
50 NC-50 50 NC-50
40 NC-40 40 NC-40
Hi Hi
30 NC-30 30 NC-30
Me Me
Lo Lo
20 Approximate 20 Approximate
NC-2 NC-2
Threshold of 0 Threshold of 0
Hearing for Hearing for
Continuous Noise Continuous Noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Central Frequency (Cycle per Second) Central Frequency (Cycle per Second)
Model: RPI-1.5FSN2 Power Supply: 220V, 50/60Hz Model: RPI-2.0FSN2 Power Supply: 220V, 50/60Hz
Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit
90 90
Noise Criteria Curve Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
80 80
70 NC-70 70 NC-70
60 NC-60 60 NC-60
50 NC-50 50 NC-50
40 NC-40 40 NC-40
Hi Hi
30 NC-30 30 NC-30
Me Me
Lo Lo
20 Approximate 20 Approximate
NC-2 NC-20
Threshold of 0 Threshold of
Hearing for Hearing for
Continuous Noise Continuous Noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Central Frequency (Cycle per Second) Central Frequency (Cycle per Second)
1-74
SOUND DATA
Model: RPI-2.5FSN2 Power Supply: 220V, 50/60Hz Model: RPI-3.0FSN2 Power Supply: 220V, 50/60Hz
Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit
90 90
Noise Criteria Curve Noise Criteria Curve
80 80
70 NC-70
70
NC-70
60 NC-60 60 NC-6
0
50 NC-50 50 NC-5
0
Hi
40 NC-40 40 NC-4
0
Me
Hi
30 NC-30 30 NC-3
0
Lo Me
Lo
20 Approximate
NC-2 20 Approximate NC-
20
Threshold of 0 Threshold of
Hearing for Hearing for
Continuous Noise Continuous Noise
10
10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Central Frequency (Cycle per Second) Central Frequency (Cycle per Second)
Model: RPI-4.0FSN2 Power Supply: 220V, 50-60Hz Model: RPI-5.0FSN2 Power Supply: 220V, 50/60Hz
Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit
90 90
Noise Criteria Curve Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
80 80
70 NC-70 70 NC-70
60 NC-60 60 NC-60
50 NC-50 50 NC-50
Hi Hi
Me
40 NC-40 40 NC-40
Me
30 NC-30 30 NC-30
Lo Lo
20 Approximate 20 Approximate
NC-2 NC-2
Threshold of 0 Threshold of 0
Hearing for Hearing for
Continuous Noise Continuous Noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Central Frequency (Cycle per Second) Central Frequency (Cycle per Second)
1-75
SOUND DATA
Model: RPI-8FSN Power Supply: 380V, 50/60Hz Model: RPI-8FSN Power Supply: 415V, 50Hz
Measurement Point: 1.5 Meter Beneath the Unit Measurement Point: 1.5 Meter Beneath the Unit
220Pa 260Pa
110Pa 130Pa
90 90
Noise Criteria Curve Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
NC-70 NC-70
70 70
60 NC-6 60 NC-6
0 0
50 NC-5 50 NC-5
0 0
40 NC-4 40 NC-4
0 0
30 NC-3 30 NC-3
0 0
Approximate
20 NC-
20 20 Approximate NC-
20
Threshold of Threshold of
Hearing for Hearing for
Continuous Noise Continuous Noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Central Frequency (Cycle per Second) Central Frequency (Cycle per Second)
Model: RPI-10FSN Power Supply: 380V, 50/60Hz Model: RPI-10FSN Power Supply: 415V, 50Hz
Measurement Point: 1.5 Meter Beneath the Unit Measurement Point: 1.5 Meter Beneath the Unit
220Pa 260Pa
110Pa 130Pa
90 90
Noise Criteria Curve Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
Octave Sound Pressure Level (dB: Overall C Scale)
80 80
NC-70 NC-70
70 70
60 NC-6 60 NC-6
0 0
50 NC-5 50 NC-5
0 0
40 NC-4 40 NC-4
0 0
30 NC-3 30 NC-3
0 0
20 Approximate NC-
20 20 Approximate NC-
20
Threshold of Threshold of
Hearing for Hearing for
Continuous Noise Continuous Noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Central Frequency (Cycle per Second) Central Frequency (Cycle per Second)
NOTES:
1. The sound pressure level is based on following conditions, 1.5 Meter Beneath the Unit.
2. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in
the field.
1-76
SOUND DATA
Model: RCI-1.0FSN2 Power Supply: 220-240V/220V, 50/60Hz Model: RCI-1.5FSN2 Power Supply: 220-240V/220V, 50/60Hz
Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit
90 90
Noise Criteria Curve Noise Criteria Curve
80 80
NC-70 NC-70
70 70
60 NC-6 60 NC-6
0 0
50 NC-5 50 NC-5
0 0
40 NC-4 40 NC-4
0 0
Hi Hi
Me
30 NC-3 30 NC-3
0 0
Me
Lo
Approximate
20 NC-
20 20 Approximate NC-
20
Threshold of Threshold of Lo
Hearing for Hearing for
Continuous Noise Continuous Noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Central Frequency (Cycle per Second) Central Frequency (Cycle per Second)
Model: RCI-2.0FSN2 Power Supply: 220-240V/220V, 50/60Hz Model: RCI-2.5FSN2 Power Supply: 220-240V/220V, 50/60Hz
Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit
90 90
Noise Criteria Curve Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
Octave Sound Pressure Level (dB: Overall C Scale)
80 80
NC-70 NC-70
70 70
60 NC-6 60 NC-6
0 0
50 NC-5 50 NC-5
0 0
Hi
40 NC-4 40 NC-4
0 0
Me
30 NC-3 30 NC-3
0 0
Hi
Me
Approximate
20 Approximate NC- 20 NC-
Threshold of Lo 20 Threshold of 20
Hearing for Hearing for
Continuous Noise Continuous Noise Lo
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Central Frequency (Cycle per Second) Central Frequency (Cycle per Second)
1-77
SOUND DATA
Model: RCI-3.0FSN2 Power Supply: 220-240V/220V, 50/60Hz Model: RCI-4.0FSN2 Power Supply: 220-240V/220V, 50/60Hz
Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit
90 90
Noise Criteria Curve Noise Criteria Curve
80 80
NC-70 NC-70
70 70
60 NC-6 60 NC-6
0 0
Hi
50 NC-5 50 NC-5
0 0
Hi
40 NC-4 40 NC-4
0 0
Me
Me
30 NC-3 30 NC-3
0 0
Approximate
20 Approximate NC-
20 20 NC-
20
Threshold of Threshold of
Hearing for Hearing for
Continuous Noise Lo Continuous Noise
Lo
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Central Frequency (Cycle per Second) Central Frequency (Cycle per Second)
80
NC-70
70
60 NC-6
0
Hi
50 NC-5
0
Me
40 NC-4
0
30 NC-3
0
Lo
20 Approximate NC-
20
Threshold of
Hearing for
Continuous Noise
10
63 125 250 500 1000 2000 4000 8000
1-78
SOUND DATA
Model: RCD-1.0FSN2 Power Supply: 220V, 50/60Hz Model: RCD-1.5FSN2 Power Supply: 220V, 50/60Hz
Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit
90 90
Noise Criteria Curve Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
NC-70 70 NC-70
70
60 NC-60 60 NC-60
50 NC-50 50 NC-50
Hi Hi
40 NC-40 40 NC-40
Me Me
30 NC-30 30 NC-30
20 Approximate 20 Approximate
NC-2
Threshold of NC-2 Threshold of 0
0
Hearing for
Lo Hearing for Lo
Continuous Noise Continuous Noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Central Frequency (Cycle per Second) Central Frequency (Cycle per Second)
Model: RCD-2.0FSN2 Power Supply: 220V, 50/60Hz Model: RCD-2.5FSN2, RCD-3.0FSN2 Power Supply: 220V, 50/60Hz
Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit
90 90
Noise Criteria Curve Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
80 80
70 NC-70 70 NC-70
60 NC-60 60 NC-60
50 NC-50 50 NC-50
Hi
Hi Me
40 NC-40 40 NC-40
Me
30 NC-30 30 NC-30
20 Approximate 20 Approximate
Threshold of NC-2 Threshold of NC-2
0 0
Lo Lo
Hearing for Hearing for
Continuous Noise Continuous Noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Central Frequency (Cycle per Second) Central Frequency (Cycle per Second)
1-79
SOUND DATA
Model: RCD-4.0FSN2 Power Supply: 220V, 50/60Hz Model: RCD-5.0FSN2 Power Supply: 220V, 50/60Hz
Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit
90 90
Noise Criteria Curve Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
NC-70 70 NC-70
70
60 NC-60 60 NC-60
Hi
50 NC-50 50 NC-50
Hi Me
Me
40 NC-40 40 NC-40
30 NC-30 30 NC-30
Lo
Lo
20 Approximate NC-2 20 Approximate NC-2
Threshold of 0 Threshold of 0
Hearing for Hearing for
Continuous Noise Continuous Noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Central Frequency (Cycle per Second) Central Frequency (Cycle per Second)
1-80
SOUND DATA
Wall Type
80 80
NC-70 NC-70
70 70
60 NC-6 60 NC-6
0 0
50 NC-5 50 NC-5
0 0
NC-4
Me NC-4
40 0 40 0
Hi Hi
30 NC-3 30 NC-3
0 0
Lo Me Lo
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Central Frequency (Cycle per Second) Central Frequency (Cycle per Second)
80 80
NC-70 NC-70
70 70
NC-6 60 NC-6
60 0 0
NC-5 50 NC-5
50 0 0
Hi
Hi
NC-4 40 NC-4
40 0 0
Me
NC-3 Me
30 0 30 NC-3
Lo 0
Lo
Approximate
20 Approximate 20 Threshold of
Threshold of NC-
NC- Hearing for 20
Hearing for 20
Continuous Noise Continuous Noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Central Frequency (Cycle per Second) Central Frequency (Cycle per Second)
1-81
SOUND DATA
Model: RPK-4.0FSNSM2
Power Supply: 220V, 50/60Hz
Measurement Point: 1 Meter Beneath the Unit and
1 Meter From Discharge Grille
90
Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
80
NC-70
70
60 NC-6
0
50 Hi NC-5
0
40 NC-4
0
Me
NC-3
0
30
Lo
Approximate NC-
20 20
Threshold of
Hearing for
Continuous Noise
10
63 125 250 500 1000 2000 4000 8000
1-82
SOUND DATA
Floor Type
Model: RPF-1.0FSN2E Power Supply: 220V, 50/60Hz Model: RPF-1.5FSN2E Power Supply: 220V, 50/60Hz
Measurement Point: 1.5 Meter from the Unit Measurement Point: 1.5 Meter from the Unit
1.5 Meter from Floor Level 1.5 Meter from Floor Level
Noise Criteria Curve Noise Criteria Curve
Hi/Me/Lo: 35/32/29 dBA Hi/Me/Lo: 38/35/31 dBA
80 80
Octave Sound Pressure Level (dB: Overall C Scale)
60 60
50 50
40 40
30 30
20 20
Approximate Approximate
Threshold of Threshold of
Hearing for Hearing for
Continuous Noise Continuous Noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Central Frequency (Cycle per Second) Central Frequency (Cycle per Second)
Model: RPFI-1.0FSN2E Power Supply: 220V, 50/60Hz Model: RPFI-1.5FSN2E Power Supply: 220V, 50/60Hz
Measurement Point: 1.5 Meter from the Unit Measurement Point: 1.5 Meter from the Unit
1.5 Meter from Floor Level 1.5 Meter from Floor Level
Noise Criteria Curve Noise Criteria Curve
Hi/Me/Lo: 35/32/29 dBA Hi/Me/Lo: 38/35/31 dBA
80 80
Octave Sound Pressure Level (dB: Overall C Scale)
70 70
60
60
50 50
40 40
30 30
20 20
Approximate Approximate
Threshold of Threshold of
Hearing for Hearing for
Continuous Noise Continuous Noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Central Frequency (Cycle per Second) Central Frequency (Cycle per Second)
1-83
SOUND DATA
Ceiling Type
Model: RPC-2.0FSN2 Power Supply: 220V, 50/60Hz Model: RPC-2.5FSN2, RPC-3.0FSN2 Power Supply: 220V, 50/60Hz
Measurement Point: 1 Meter Beneath the Unit and Measurement Point: 1 Meter Beneath the Unit and
90 1 Meter From Discharge Grille 90 1 Meter From Discharge Grille
Noise Criteria Curve Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
70 NC-70 70 NC-70
60 NC-60 60 NC-60
50 NC-50 50 NC-50
40 NC-40 40 NC-40
Hi Hi
30 NC-30 30 NC-30
Me Me
Lo Lo
20 Approximate NC-2 20 Approximate NC-2
Threshold of 0 Threshold of 0
Hearing for Hearing for
Continuous Noise Continuous Noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Central Frequency (Cycle per Second) Central Frequency (Cycle per Second)
Model: RPC-4.0FSN2 Power Supply: 220V, 50/60Hz Model: RPC-5.0FSN2 Power Supply: 220V, 50/60Hz
Measurement Point: 1 Meter Beneath the Unit and Measurement Point: 1 Meter Beneath the Unit and
90
1 Meter From Discharge Grille 1 Meter From Discharge Grille
90
Noise Criteria Curve Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
80 80
NC-70 70 NC-70
70
60 NC-60 60 NC-60
50 50
NC-50 NC-50
Hi Hi
40 40 NC-40
NC-40
30 NC-30 30 NC-30
Me Me
Lo Lo
20 Approximate 20 Approximate
NC-2 NC-2
Threshold of 0 Threshold of 0
Hearing for Hearing for
Continuous Noise Continuous Noise
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Central Frequency (Cycle per Second) Central Frequency (Cycle per Second)
1-84
SOUND DATA
Total Heat Exchangers
Model: KPI-2521 Power Supply: 220-240V/50Hz Model: KPI-5021 Power Supply: 220-240V/50Hz
Measurement Point: 1.5 Meter Beneath the Unit Measurement Point: 1.5 Meter Beneath the Unit
and with a Sound-Proof Duct and with a Sound-Proof Duct
90 90
Noise Criteria Curve Noise Criteria Curve
80 80
Octave Sound Pressure Level (dB: Overall C Scale)
60 NC-6
0 60 NC-6
0
NC-5 NC-5
50 0 50 0
NC-4
40 0 40 NC-4
0
30 NC-3
0 30 NC-3
0
Hi
Me
Lo Me Hi
20 NC-
20 20
Lo NC-20
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Central Frequency (Cycle per Second) Central Frequency (Cycle per Second)
Model: KPI-8021 Power Supply: 220-240V/50Hz Model: KPI-10021 Power Supply: 220-240V/50Hz
Measurement Point: 1.5 Meter Beneath the Unit Measurement Point: 1.5 Meter Beneath the Unit
and with a Sound-Proof Duct and with a Sound-Proof Duct
90 90
Noise Criteria Curve Noise Criteria Curve
80 80
Octave Sound Pressure Level (dB: Overall C Scale)
NC-70 NC-70
70 70
60 NC-6
0 60 NC-6
0
50 NC-5 50 NC-5
0 0
40 NC-4
0 40 NC-4
0
Hi
Lo
30 NC-3
0 30 NC-3
0
Lo Me
Hi
Me NC-
20
20 20
NC-20
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Central Frequency (Cycle per Second) Central Frequency (Cycle per Second)
NOTES:
1. The sound pressure level is based on following conditions, 1.5 Meter Beneath the Unit. (Total heat exchange mode)
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in
the field.
2. The sound pressure level emitted from the air outlet to the duct is higher than the values indicated in the GENERAL
DATA table by 5 to 6 dB(A) approximately. It is recommended that a sound-proof duct.
1-85
SOUND DATA
Model: KPI-2521 Power Supply: 220V/60Hz Model: KPI-5021 Power Supply: 220V/60Hz
Measurement Point: 1.5 Meter Beneath the Unit Measurement Point: 1.5 Meter Beneath the Unit
and with a Sound-Proof Duct and with a Sound-Proof Duct
90 90
Noise Criteria Curve Noise Criteria Curve
70 NC-70 70 NC-70
60 NC-6 60 NC-6
0 0
50 NC-5 50 NC-5
0 0
40 Hi NC-4 40 NC-4
0 0
Hi
Me
Me
30 NC-30 30 NC-30
Lo
Lo
20 NC-2 20 NC-2
0 0
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Central Frequency (Cycle per Second)
Central Frequency (Cycle per Second)
Model: KPI-8021 Power Supply: 220V/60Hz Model: KPI-10021 Power Supply: 220V/60Hz
Measurement Point: 1.5 Meter Beneath the Unit Measurement Point: 1.5 Meter Beneath the Unit
and with a Sound-Proof Duct and with a Sound-Proof Duct
90 90
Noise Criteria Curve Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
80 80
Octave Sound Pressure Level (dB: Overall C Scale)
70 NC-70 70 NC-70
60 NC-6 60 NC-6
0 0
50 NC-5 50 NC-5
0 0
40 NC-4 40 NC-4
0 0
Hi
Hi
30 NC-30 30 NC-30
Me
Lo
Lo
Me
20 20 NC-2
0
NC-20
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Central Frequency (Cycle per Second) Central Frequency (Cycle per Second)
NOTES:
1. The sound pressure level is based on following conditions, 1.5 Meter Beneath the Unit. (Total heat exchange mode)
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in
the field.
2. The sound pressure level emitted from the air outlet to the duct is higher than the values indicated in the GENERAL
DATA table by 5 to 6 dB(A) approximately. It is recommended that a sound-proof duct.
1-86
ctrical Wiring Diagram
ELECTRICAL WIRING DIAGRAM (FOR MODELS: RPI-0.8FSN2, RPI-1.0FSN2, RPI-1.5FSN2, RPI-2.0FSN2, RPI-2.5FSN2, RPI-3.0FSN2, RPI-4.0FSN2 AND RPI-5.0FSN2)
CONTROL SYSTEM
1-139
ELECTRICAL WIRING DIAGRAM (FOR MODELS: RPI-8FSN AND RPI-10FSN)
CONTROL SYSTEM
1-140
ELECTRICAL WIRING DIAGRAM (FOR MODELS: RCI-1.0FSN2, RCI-1.5FSN2, RCI-2.0FSN2, RCI-2.5FSN2, RCI-3.0FSN2, RCI-4.0FSN2 AND RCI-5.0FSN2)
CONTROL SYSTEM
1-141
ELECTRICAL WIRING DIAGRAM (FOR MODELS: RCD-1.0FSN2, RCD-1.5FSN2, RCD-2.0FSN2, RCD-2.5FSN2, RCD-3.0FSN2, RCD-4.0FSN2 AND RCD-5.0FSN2)
CONTROL SYSTEM
1-142
ELECTRICAL WIRING DIAGRAM (FOR MODELS: RPK-1.0FSNSN2 AND RPK-1.5FSNSM2)
CONTROL SYSTEM
1-143
ELECTRICAL WIRING DIAGRAM (FOR MODELS: RPK-2.0FSNSM2)
CONTROL SYSTEM
1-144
ELECTRICAL WIRING DIAGRAM (FOR MODELS: RPK-2.5FSNSM2, RPK-3.0FSNSM2 AND RPK-4.0FSNSM2)
CONTROL SYSTEM
1-145
ELECTRICAL WIRING DIAGRAM (FOR MODELS: RPF-1.0FSN2E, RPF-1.5FSN2E, RPFI-1.0FSN2E AND RPFI-1.5FSN2E)
for Communication
2 wire RCS (PC-AR)
Main Switch
1N~
220/240V
50Hz (3N~)
for RCS
1N~
220V/60Hz
(3N~)
SK1
C55
P
THM5 Gas Pipe Thermistor On PCB
(17G )
L1 Y52H
YH2 TF Transformer
C16 YME YLO YSLO YH1
YME Relay for ME Fan Motor Tap DC Coil
RSW2
YLO Relay for LO Fan Motor Tap DC Coil
DSW4 DSW5
PCN2
IC1 YSLO Relay for SLO Fan Motor Tap DC Coil
EFR1
DSW3
YH1 Relay for Hi Fan Motor Tap DC Coil
DSW6 RSW1
DSW7 Terminals
PCN7
1-146
ELECTRICAL WIRING DIAGRAM (FOR MODELS: RPC-2.0FSN2, RPC-2.5FSN2, RPC-3.0FSN2, RPC-4.0FSN2 AND RPC-5.0FSN2)
CONTROL SYSTEM
1-147
MISCELLANEOUS NOTES
Special Notes
1. Provide a service access door near the unit 10. During heating operation, the outdoor heat
piping connection part on the false ceiling for the exchanger produces condensate dew or
cassette type units. melting water from frost.
2. Consider the air distribution from the unit to the Install the outdoor unit where drainage of
space of the room, and select a suitable location such water is convenient, or provide a drain
so that uniform air temperature in the room can passage.
be obtained. 11. Heating Performance: The heating capacity
Cassette and Ceiling Types - Avoid unit normally decreases when outdoor temperatures
installation in a room where the ceiling height decrease. Therefore, provide an auxiliary
(distance between the floor to the false ceiling) heating unit if outdoor temperatures are very
exceeds three meters. If the indoor unit is low.
installed in a room with a ceiling of higher than 3 12. In the case that an outdoor temperature is
meters, it is recommended that an air circulation low and humidity is high, the outdoor heat
fan be installed separately to obtain uniform air exchanger will covered with frost, resulting in
temperature in the room, especially during the lower heating capacity. In order to remove
heating operation. the frost, the unit is automatically changed to
3. Check to ensure that the ceiling slab is strong the defrosting mode. During this defrosting
enough and that the false ceiling is flat and level. operation, the unit is stopped for approximately
4. Avoid obstacles which may restrict the air intake 3 to 10 minutes.
or the discharge flow. 13. As this unit is of heat pump type by circulating
5. Do not install the unit in a machinery shop or hot air in the whole room space, it takes time to
kitchen where vapor from oil or its mist can enter heat up the room temperature.
to the unit. 14. The operating sound data is based on an
The oil will deposit on the heat exchanger, anechoic chamber. Therefore, the actual
thereby reducing the unit performance, and may operating sound will be higher due to reflected
deform, in the worst case, break the plastic parts sound from the floor and wall.
of the unit. 15. In the case that the unit is operated for a long
6. Pay attention to the following points when the time higher than the indoor temperature of
unit is installed in a hospital or other facilities 27oCDB or the humidity of 80%, dewing may
where electromagnetic wave is radiated from occur on the cabinets resulting in dew drops. If
medical equipment. dewing, it is required to add thermal insulator
(A) Do not install the unit where the on the cabinets.
electromagnetic wave is directly radiated to 16. Provide snow-protection hoods to prevent the
the electrical box, remote control cable or outdoor heat exchanger from snow clogging.
remote control switch. If the unit is operated in an are where it snows
(B) Install the unit and component as far as heavily, provide a base under the outdoor
practical (at least three meters) from the unit which should be 50cm higher than the
electromagnetic wave radiator. presumable maximum snow height.
(C) Prepare a steel box and install the remote 17. It is recommended that periodical service and
control switch in it. Prepare a steel conduit maintenance be performed by authorized
pipe and wire the remote control cable in it. service engineers before air conditioning
And then, connect earth wire with the box seasons, in order to avoid performance
and the pipe. decrease due to dust or dirt.
18. This heat pump air conditioner has been
(D) Install a noise filter when the power supply
designed for normal air conditioning for men.
emits harmful noise.
Do not apply to other purposes such as for
7. Do not install the units in an acid or alkaline food, animals, plants, high precision machines
environment due to the corrosive action on the or work of art. Also do not apply to vehicles
heat exchanger. In the case that outdoor units or vessels. It will results in water leakage or
are installed near the sea, it is recommended electrical leakage.
that optional corrosion-resistant type outdoor 19. It is recommended that the system be installed
unit be used. by authorized engineers. If not, it may cause
8. Do not install the units in a flammable water leakage, electric shock or fire.
environment due to the danger of an explosion. 20. In a place where fibers or dusts are floating, the
9. Regarding cassette type indoor units, consider air filter or heat exchangers or the drain pipe
the direct and reflected sound level, when may be clogged, resulting in water leakage
selecting the unit for spaces where extremely from the drain pan.
low sound is required.
1-149
MISCELLANEOUS NOTES
Use tools and measuring instruments only for the new refrigerant which is directly touch to refrigerant.
: Interchangeability is available with current R22 : only for Refrigerant R410A (No Interchangeability with R22)
: Prohibited : only for Refrigerant R407C (No Interchangeability with R22)
Interchangeability
Reason of Non-Interchangeability and Attention
Measuring Instrument and Tool with R22 Use
(: Strictly Required)
R410A R407C
Pipe Cutter Cutting Pipe
-
Chamfering Reamer Removing Burrs
Flaring Tool * The flaring tools for R407C are applicable to R22. Flaring for Tubes
* If using flaring tube, make dimension of tube larger Dimensional Control
Extrusion
- for R410A. for Extruded Portion
Adjustment Gauge
* In case of material 1/2H, flaring is not available. of Tube after Flaring
* In case of material 1/2H, bending is not available. Bending
Pipe Bender
Use elbow for bend and braze.
* In case of material 1/2H, expanding of tube is not Expanding Tubes
Refrigerant Expanding Tool
available. Use socket for connecting tube.
Pipe
* For 12.7, 15.88, spanner size is up 2mm. Connection of
Torque Wrench
* For 6.35, 9.53, 19.05, spanner size is the same. Flare Nut
Brazing Tool * Perform correct brazing work. Brazing for Tubes
* Strict Control against Contamin Prevention from
Nitrogen Gas (Blow nitrogen during brazing.) Oxidation during
Brazing
* Use a synthetic oil which is equivalent to the oil used Applying Oil to
Lubrication Oil
in the refrigeration cycle. the Flared Surface
(for Flare Surface)
* Synthetic oil absorbs moisture quickly.
* Check refrigerant cylinder color. Refrigerant Charging
Refrigerant
Liquid refrigerant charging is required regarding
Cylinder
zeotoropic refrigerant.
The current ones are applicable. However, it is Vacuum Pumping
Vacuum Pump
required to mount a vacuum pump adapter which
Adapter for can prevent from reverse flow when a vacuum pump
Vacuum Pump stops, resulting in no reverse oil flow.
* No interchangeability is available due to higher Vacuum Pumping,
Vacuum pressures when compared with R22. Vacuum Holding,
Manifold Valve
Drying Do not use current ones to the different refrigerant. Refrigerant Charging
If used, mineral oil will flow into the cycle and cause and Check of
Refrigerant
sludges, resulting in clogging or compressor failure. Pressures
Charge
Charging Hose Connection diameter is different; R410A: UNF1/2,
R407C: UNF7/16.
Charging Cylinder * Use the weight scale. -
Measuring
Weight Scale - Instrument for
Refrigerant Charging
Refrigerant Gas * The current gas leakage detector (R22) is not Gas Leakage Check
Leakage Detector applicable due to different detecting method.
: Interchangeability with R407C.
1-150
STANDARD SPECIFICATIONS
1-151 A
STANDARD SPECIFICATIONS
to be de-frosted where necessary. Coil shall be within 300mm. The cabinet shall include indoor
cleaned, dehydrated and pressure tested at factory coils, piping, supply air fan, drain pump, electronic
and shall be charged with correct refrigerant charge expansion valve, control circuit board, accessories
before shipment. and electrical connections mounted within an
Clearance shall be provided around units for condenser insulated enclosure. Facial Panel shall be either a
air flow and maintenance access. Hot discharge air four-way or a two-way air distribution type, impact
shall not be short-circuited to condenser intake. resistant, stain resistant and washable decoration
panel. The supply air is distributed via motorized
CH Change Over Box louvers which can be horizontally and vertically
Cabinet - The cabinet shall be compact, light adjusted from 0° to 90°. Access panels shall be
weight, constructed from galvanized sheet complete easily removed and sized to provide adequate
with high density foam insulation suitable for indoor access to interior for routine inspection and
installation. All fasteners exposed to the weather shall maintenance, and shall be air tight. The cabinet is
be galvanized steel. The sheet metal cabinet shall be to be insulated for thermal & acoustic performance,
housing expansion valves, refrigeration control solenoid using polyethylene insulation.
valves, control circuit board and other electric controls Evaporator Coil - Shall be manufactured
interfacing Hitachi H-Link network. Access panel shall by Hitachi, and shall be direct expansion type
be provided for routine inspection and maintenance. manufactured from inner grooved copper tubes
Changeover box shall be capable of control refrigerant expanded into aluminum fins to form a mechanical
flow for either one unit or a group of up to 8 units. bond. Coil shall be pressure tested at factory
It shall have 2 incoming gas pipes (low pressure and and shall be charged with dry air or dry nitrogen
high pressure) and 1 outgoing gas pipe. Liquid pipe before shipment.
shall not be run through changeover box to save Condensate Drain Pan - Shall be sized and
on pipe joints. sloped to catch all condensate, and to allow it to
Ducted Indoor Unit RPI SERIES drain away freely, and shall be constructed to be
Cabinet - Shall be fabricated using galvanized steel corrosion resistant. A condensate pan with drain
with high density foam insulation. The cabinet shall connections shall be provided under the coil.
include indoor coils, piping, supply air fan, motor, The unit shall also include a built-in, automatic
electronic expansion valve, control circuit board, condensate lift mechanism that will be able to
accessories and electrical connections mounted raise drain water 850mm above the condensate
within an insulated enclosure with four brackets to pan. The lift mechanism shall be equipped with
accommodate suspension. Access panels shall be a positive acting liquid level sensor to shut down
easily removed and sized to provide adequate access the indoor unit if liquid level in the drain pan
to interior for routine inspection and maintenance, reaches maximum level.
and shall be air tight. The cabinet is to be insulated Evaporator Fan - Shall be direct drive turbo
for thermal & acoustic performance, using fan, minimum 3 speeds. Indoor turbo fan shall
polyethylene insulation. be statically and dynamically self balanced and
Evaporator Coil - Shall be manufactured by Hitachi, shall be driven by high efficient DC fan motor with
and shall be direct expansion type manufactured from permanently lubricated bearings.
inner grooved copper tubes expanded into aluminum The four-way indoor unit shall have an adjustable
fins to form a mechanical bond. Coil shall be pressure air outlet system offering 4-way airflow, 3-way
tested at factory and shall be charged with dry air or airflow, or 2-way airflow with switches that can be
dry nitrogen before shipment. set to provide optimum airflow based on ceiling
Condensate Drain Pan - Shall be sized and height and number of outlets used.
sloped to catch all condensate, and to allow it to Wall Mounted Indoor Unit RPK SERIES
drain away freely, and shall be constructed to be
corrosion resistant. Cabinet - Shall be fabricated with high strength
moulded plastic and sufficient insulation and shall
Evaporator Fan - Shall be direct drive centrifugal be suitable to be mounted firmly on the factory
fan, minimum 3 speeds. Indoor centrifugal fan shall be supplied mounting template. It Shall include indoor
statically and dynamically self balanced and shall be coils, piping, supply air fan, motor, electronic
driven by high efficient DC fan motor with permanently expansion valve, control circuit board, accessories
lubricated bearings. Fan curves showing the airflow and electrical connections within an insulated
limits, available external static, and input power for enclosure. Front panel shall be easily removed
each fan speed are to be documented within the to provide access to interior of unit for routine
manufacturer’s standard literature. inspection and maintenance.
Cassette Indoor Unit RCI/RCD SERIES Evaporator Coil - Shall be manufactured
Cabinet - Shall be fabricated using galvanized steel by Hitachi, and shall be direct expansion type
coated with high density foam insulation with unit height manufactured from inner grooved copper tubes
1-151 B
STANDARD SPECIFICATIONS
expanded into aluminum fins to form a mechanical Condensate Drain Pan - Shall be sized and
bond. Coil shall be pressure tested at factory and sloped to catch all condensate, and to allow it to
shall be charged with dry air or dry nitrogen drain away freely, and shall be constructed to be
before shipment. corrosion resistant.
Condensate Drain Pan - Shall be sized and Evaporator Fan - Shall be sirocco type fan direct
sloped to catch all condensate, and to allow it to driven by single phase motor with permanently
drain away freely, and shall be constructed to be lubricated bearings, minimum 3 speeds. Indoor sirocco
corrosion resistant. fan shall be statically and dynamically balanced.
Evaporator Fan - Shall be tangential type fan Control
direct driven by single phase motor with permanently General - shall consist of Hitachi local control,
lubricated bearings, minimum 3 speeds. Indoor central control, central on/off control, schedule timer,
tangential fan shall be statically and dynamically web based CS Net and Open interface including
balanced. Bacnet and Lonworks gateway.
Under ceiling Mounted Indoor Unit RPC SERIES Wiring - Shall be no-polar 2 conductor, twisted
Cabinet - Shall be fabricated with galvanised steel shielded pair and shall be wired in daisy chain
with white power coating and sufficient insulation and configuration from outdoor units to changeover boxes
shall be suitable to be mounted firmly under ceiling. and from changeover box to indoor units. Control
It Shall include indoor coils, piping, supply air fan, wiring for central control, schedule timer, CS net
motor, electronic expansion valve, control circuit shall be installed in daisy chain from outdoor units to
board, accessories and electrical connections within outdoor units and to these controls.
an insulated enclosure. Front panel shall be easily Local Remote Control - shall be LCD wired remote
removed to provide access to interior of unit control PC-AR OR PC-ART with weekly timer function.
for routine inspection and maintenance.
General: Provide microprocessor controller with the
Evaporator Coil - Shall be manufactured by Hitachi, following functions:
and shall be direct expansion type manufactured from
- Power ON/OFF switch.
inner grooved copper tubes expanded into aluminum
fins to form a mechanical bond. Coil shall be pressure - Mode selector switch:
tested at factory and shall be charged with dry air or DEHUMIDIFY - COOL - HEAT - AUTO
dry nitrogen before shipment. - Temperature settings
Condensate Drain Pan - Shall be sized and - Evaporator fan speed selector
sloped to catch all condensate, and to allow it to - Indicating lamps, LEDs or LCD display for unit
drain away freely, and shall be constructed to be operating or fault
corrosion resistant. - Self diagnosis functions
Evaporator Fan - Shall be sirocco type fan - Group control up to 16 units by one single control
direct driven by single phase motor with permanently Central Control - shall be LCD wired control or web
lubricated bearings, minimum 3 speeds. Indoor based as listed,
sirocco fan shall be statically and dynamically
- Schedule timer: PSC-A1T (weekly timer with
balanced.
3 programs/day, winter and summer schedule)
Floor Mounted Indoor Unit RPF/RPFI SERIES - Central on/off control: PSC-A16RS (up to 16 groups
Cabinet - Shall be fabricated with galvanised or 160 units collectively on/off control)
steel for floor concealed type and galvanised steel - Central station control: PSC-A64S OR PSC-5S
with white power coating for floor exposed type (up to 64 groups or 160 units collectively control)
and sufficient insulation and shall be suitable to
- Web based control: PSC-6WTX (up to 64 groups or
be mounted firmly on the floor. It Shall include
1024 units collectively control over net)
indoor coils, piping, supply air fan, motor, electronic
expansion valve, control circuit board, accessories Quality assurance
and electrical connections within an insulated The complete VRF system shall be designed
enclosure. Front panel shall be easily removed within the guarantee working range published in the
to provide access to interior of unit for routine technical literature and installed within guide line of
inspection and maintenance. manufacturer published technical literature and shall
Evaporator Coil - Shall be manufactured by Hitachi, be commissioned and certified by factory trained
and shall be direct expansion type manufactured from technicians or factory trained agents.
inner grooved copper tubes expanded into aluminum The complete system shall be complete assembled
fins to form a mechanical bond. Coil shall be pressure and tested in ISO9001 and ISO14001 certified
tested at factory and shall be charged with dry air or manufacturing facilities and shall be tested to comply
dry nitrogen before shipment. with current Australian safety and EMC standards.
1-151 C
IMPORTANT NOTICE
CAUTION
• Use shielded wires of operation line between the indoor unit and the outdoor unit.
And connect the shielded part to the earth screw in the electrical box of the indoor unit as shown in the Fig. 1.
(Example: RPI-8FSN)
Protect the earth wire not to contact
with the live part.
TB2
A B 1 2
Shielded
DO NOT connect the wiring Part
to these terminals. (TB1-1,2)
Power
Source