Customer: Routine Test Report

The test report certifies that the LTB145D1/B(CSB0 & Avatar) breaker and FSA1 mechanism passed all routine tests as per IEC62271-100 standards on April 5, 2024. The report includes detailed results on resistance, operational tests, and various settings, confirming compliance with technical specifications. All tests were approved by the quality department of Hitachi Energy High Voltage Switchgear Company Limited.

Uploaded by

Nguyễn Quý
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
33 views15 pages

Customer: Routine Test Report

The test report certifies that the LTB145D1/B(CSB0 & Avatar) breaker and FSA1 mechanism passed all routine tests as per IEC62271-100 standards on April 5, 2024. The report includes detailed results on resistance, operational tests, and various settings, confirming compliance with technical specifications. All tests were approved by the quality department of Hitachi Energy High Voltage Switchgear Company Limited.

Uploaded by

Nguyễn Quý
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 15

ROUTINE Page 1 of 15

TEST REPORT
Breaker LTB145D1/B(CSB0 & Avatar) Order No: 502893565
Mechanism: FSA1 Serial No: 1361845910-002

Customer
HITACHI ENERGY VIETNAM

Customer reference Country

Reference Project
502893565

Breaker type Serial number


LTB145D1/B(CSB0 & Avatar) 1361845910-002

Mechanism type Serial number


FSA1 1361845910-002-A1

Standard Test completed


IEC62271-100 4/5/2024

We hereby certify that the above objects have passed all routine tests in accordance with the
standard referred to in above and with the terms of the contract.

Hitachi Energy High Voltage Switchgear Company Limited,Beijing


Quality Department

........................................................... Date: 4/5/2024


mj

Test witnessed by

........................................................... .............................................................

........................................................... .............................................................

...........................................................
ROUTINE Page 2 of 15
TEST REPORT
Breaker LTB145D1/B(CSB0 & Avatar) Order No: 502893565
Mechanism: FSA1 Serial No: 1361845910-002

Rated data
Rated filling pressure for operation: 0.70 MPa(abs)

Check of rating plates Approved: mj

MECHANISM RESULTS

Resistance in ohms of auxiliary circuits


Description Mechanism No. Mechanism No. Mechanism No.
1361845910-002-A1
Closing coil 1 27 - -
Opening coil 1 27 - -
Opening coil 2 28 - -
Antipumping relay 1 7390 - -
Density blocking relay 1 7470 - -
Density blocking relay 2 7500 - -
Heater anticondense 722 - -
Heater total 232 - -

All resistances checked Approved mj


ROUTINE Page 3 of 15
TEST REPORT
Breaker LTB145D1/B(CSB0 & Avatar) Order No: 502893565
Mechanism: FSA1 Serial No: 1361845910-002

Check of Approved
Wiring acc. To circuit diagram mj
Local/remote operation mj
Blocking relays mj
Extra relays mj
On-line-motor starter does not trip for 10 consecutive operations mj
Auxiliary contacts mj
Thermostat settings mj
Counter mj
All adjustments and paint marking mj

Settings
Description Unit Mech. 1 Mech. 2 Mech. 3
Thermostat °C 10.0 - -
Close spring setting mm 90.0 - -
Trip spring setting mm 76.0 - -

Approved: mj

Spring charge at nominal voltage


Description Unit Mech. 1 Mech. 2 Mech. 3
Charging time s 10.5 - -
Motor current A 9.0 - -

Approved: mj

Lowest operating voltage


Description Unit Mech. 1 Mech. 2 Mech. 3
Close coil 1 VDC 46 - -
Trip coil 1 VDC 40 - -
Trip coil 2 VDC 36 - -

Approved: mj

Power frequency test of auxiliary circuits


1 second 50 Hz 2.5 kV Approved: mj
1 second 50 Hz 2.0 kV,motor Approved: -
ROUTINE Page 4 of 15
TEST REPORT
Breaker LTB145D1/B(CSB0 & Avatar) Order No: 502893565
Mechanism: FSA1 Serial No: 1361845910-002

POLE RESULTS

Resistance in main circuit


Phase Unit Part 1 Part 2
A µOhm 33
B µOhm 33
C µOhm 33
Approved: mj

Power frequency test


60 seconds 50 Hz breaking unit 260 kV Approved: mj
60 seconds 50 Hz to earth: 260 / kV Approved: mj

Overpressure test on each pole


10 minutes duration 1.15 MPa(abs) Approved: mj

Tightness test on each pole Approved: mj

OPERATING TEST

Test assumptions
Technical provision: 1HYB600092CN
Fill pressure: 0.70 MPa(abs)

Operations Voltage Motor Close 1 Close 2 Trip 1 Trip 2 Trip 3


level VDC VDC VDC VDC VDC VDC
5 Close and Open Min 94 94 77 77
5 Close and Open Max 121 121 121 121
5 Close and Open Nom 110 110 110 110
5 Close-Open Nom 110 110 110 110
5 Open-0.3s-Close Nom 110 110 110 110

Operating test
At least 25 operations as above Approved: mj
Stored energi test O – 0.3s- CO- 3min- CO Approved: -
ROUTINE Page 5 of 15
TEST REPORT
Breaker LTB145D1/B(CSB0 & Avatar) Order No: 502893565
Mechanism: FSA1 Serial No: 1361845910-002

Test Samples
Oper. Oper. Volt Cc Tc Operation times Cont. Cont. Cont. Over Re- Damp Time
No. Level phase stroke speed speed travel bounce time difference
A B C 1 2 a b
ms ms ms mm m/s m/s mm mm ms ms ms
Close 5 Min. 1 - 54.7 54.5 55.7 84.9 2.1 8.7 2.3 12.7 -30.1
Open 6 Min. - 1 35.9 34.7 34.5 84.7 2.5 3.8 1.2 18.6 -15.6 24.7
Close 15 Max. 1 - 52.3 52.2 53.3 84.9 2.1 8.6 2.3 12.4 -30.0
Open 16 Max. - 1 31.6 30.4 30.3 84.7 2.5 3.8 1.4 18.5 -15.6 20.4
Close 25 Nom. 1 - 53.4 53.4 54.5 84.8 2.1 8.4 1.7 13.1 -30.4
Open 26 Nom. - 1 32.5 31.2 31.0 84.8 2.4 3.4 1.3 19.9 -15.9 25.2
Open 41 Nom. - 2 32.8 31.6 31.3 84.8 2.4 3.4 1.3 19.8 -16.0 25.4

Oper. Oper. Volt Cc Tc Interval times 1 Interval times 2 Time


No. Level phase phase difference
A B C A B C a b
ms ms ms ms ms ms ms
C-O 31 Nom. 1 1 52.2 51.3 49.9 13.2 -30.6
O-C-O 37 Nom. 1 1 270.2 271.2 272.8 51.5 50.7 49.1 -15.9 25.5
ROUTINE Page 6 of 15
TEST REPORT
Breaker LTB145D1/B(CSB0 & Avatar) Order No: 502893565
Mechanism: FSA1 Serial No: 1361845910-002

Main Test sequence Close Min. Operation No 5

140

A1
120
B1
C1
1a
100

1b

80
mm

60

40

20

T1
0

2
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil 1 Trip coil -
94 VDC 94 VDC -
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 54.7 (0.0 - 75.0)
B1 54.5 (0.0 - 75.0)
C1 55.7 (0.0 - 75.0)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 67.4 12.7
1b 24.6 -30.1
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 2.1 (1.9 - 2.1)
Contact Stroke mm 84.9 (84.0 - 87.0)
OverTravel mm 8.7 (0.0 - 10.0)
Rebounce mm 2.3
ROUTINE Page 7 of 15
TEST REPORT
Breaker LTB145D1/B(CSB0 & Avatar) Order No: 502893565
Mechanism: FSA1 Serial No: 1361845910-002

Main Test sequence Open Min. Operation No 6

140

120 A1
B1
C1
100 1a
1b
T1
80
mm

60

40

20

2
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil - Trip coil 1
94 VDC - 77 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 35.9 (31.0 - 34.9)
B1 34.7 (31.0 - 34.9)
C1 34.5 (31.0 - 34.9)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 20.3 -15.6
1b 60.6 24.7
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 2.5 (2.2 - 2.6)
Contact Stroke mm 84.7 (84.0 - 87.0)
OverTravel mm 3.8 (0.0 - 7.0)
Rebounce mm 1.2
Damping time ms 18.6 (15.0 - 27.0)
ROUTINE Page 8 of 15
TEST REPORT
Breaker LTB145D1/B(CSB0 & Avatar) Order No: 502893565
Mechanism: FSA1 Serial No: 1361845910-002

Main Test sequence Close Max. Operation No 15

140

A1
120
B1
C1
1a
100

1b

80
mm

60

40

20

T1
0

2
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil 1 Trip coil -
121 VDC 121 VDC -
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 52.3 (0.0 - 75.0)
B1 52.2 (0.0 - 75.0)
C1 53.3 (0.0 - 75.0)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 64.7 12.4
1b 22.3 -30.0
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 2.1 (1.9 - 2.1)
Contact Stroke mm 84.9 (84.0 - 87.0)
OverTravel mm 8.6 (0.0 - 10.0)
Rebounce mm 2.3
ROUTINE Page 9 of 15
TEST REPORT
Breaker LTB145D1/B(CSB0 & Avatar) Order No: 502893565
Mechanism: FSA1 Serial No: 1361845910-002

Main Test sequence Open Max. Operation No 16

140

120 A1
B1
C1
100 1a
1b
T1
80
mm

60

40

20

2
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil - Trip coil 1
121 VDC - 121 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 31.6 (31.0 - 34.9)
B1 30.4 (31.0 - 34.9)
C1 30.3 (31.0 - 34.9)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 16.0 -15.6
1b 52.0 20.4
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 2.5 (2.2 - 2.6)
Contact Stroke mm 84.7 (84.0 - 87.0)
OverTravel mm 3.8 (0.0 - 7.0)
Rebounce mm 1.4
Damping time ms 18.5 (15.0 - 27.0)
ROUTINE Page 10 of 15
TEST REPORT
Breaker LTB145D1/B(CSB0 & Avatar) Order No: 502893565
Mechanism: FSA1 Serial No: 1361845910-002

Main Test sequence Close Nom. Operation No 25

140

A1
120
B1
C1
1a
100

1b

80
mm

60

40

20

T1
0

2
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil 1 Trip coil -
110 VDC 110 VDC -
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 53.4 (0.0 - 75.0)
B1 53.4 (0.0 - 75.0)
C1 54.5 (0.0 - 75.0)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 66.5 13.1
1b 23.0 -30.4
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 2.1 (1.9 - 2.1)
Contact Stroke mm 84.8 (84.0 - 87.0)
OverTravel mm 8.4 (0.0 - 10.0)
Rebounce mm 1.7
ROUTINE Page 11 of 15
TEST REPORT
Breaker LTB145D1/B(CSB0 & Avatar) Order No: 502893565
Mechanism: FSA1 Serial No: 1361845910-002

Main Test sequence Open Nom. Operation No 26

140

120 A1
B1
C1
100 1a
1b
T1
80
mm

60

40

20

2
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil - Trip coil 1
110 VDC - 110 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 32.5 (31.0 - 34.9)
B1 31.2 (31.0 - 34.9)
C1 31.0 (31.0 - 34.9)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 16.6 -15.9
1b 57.7 25.2
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 2.4 (2.2 - 2.6)
Contact Stroke mm 84.8 (84.0 - 87.0)
OverTravel mm 3.4 (0.0 - 7.0)
Rebounce mm 1.3
Damping time ms 19.9 (15.0 - 27.0)
ROUTINE Page 12 of 15
TEST REPORT
Breaker LTB145D1/B(CSB0 & Avatar) Order No: 502893565
Mechanism: FSA1 Serial No: 1361845910-002

Main Test sequence Close-Open Nom. Operation No 31

140

120 A1
B1
C1
100 1a
1b

80
mm

60

40

20

T1
0

2
A

Ic1
0

0 20 40 60 80 100 120 140 160 180 200 220 240


ms

Operation data
Motor Close coil 1 Trip coil 1
110 VDC 110 VDC 110 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 53.5 (0.0 - 75.0) 52.2 (0.0 - 60.0)
B1 53.5 (0.0 - 75.0) 51.3 (0.0 - 60.0)
C1 54.6 (0.0 - 75.0) 49.9 (0.0 - 60.0)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 66.7 27.3 13.2
1b 22.9 106.8 -30.6
ROUTINE Page 13 of 15
TEST REPORT
Breaker LTB145D1/B(CSB0 & Avatar) Order No: 502893565
Mechanism: FSA1 Serial No: 1361845910-002

Main Test sequence Open-0.3s-Close-Open Nom. Operation No 37

140

120 A1
B1
C1
100 1a
1b
T1
80
mm

60

40

20

2
A

Ic1
0

0 50 100 150 200 250 300 350 400 450 500


ms

Operation data
Motor Close coil 1 Trip coil 1
110 VDC 110 VDC 110 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 32.9 (31.0 - 34.9) 270.2 51.5 (0.0 - 60.0)
B1 31.8 (31.0 - 34.9) 271.2 50.7 (0.0 - 60.0)
C1 31.4 (31.0 - 34.9) 272.8 49.1 (0.0 - 60.0)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 17.0 299.2 26.5 -15.9
1b 58.4 214.8 104.9 25.5
ROUTINE Page 14 of 15
TEST REPORT
Breaker LTB145D1/B(CSB0 & Avatar) Order No: 502893565
Mechanism: FSA1 Serial No: 1361845910-002

Main Test sequence Open Nom. Operation No 41

140

120 A1
B1
C1
100 1a
1b
T1
80
mm

60

40

20

2
A

Ic1
0

0 20 40 60 80 100 120 140


ms

Operation data
Motor Close coil - Trip coil 2
110 VDC - 110 VDC
Contact times in ms
Main Contact time Close/Open interval Close/Open interval
A1 32.8 (31.0 - 34.9)
B1 31.6 (31.0 - 34.9)
C1 31.3 (31.0 - 34.9)
Aux. Contact time Close/Open Close/Open Aux-Main
1a 16.8 -16.0
1b 58.2 25.4
Travel parameters
Description Unit T1 Limits
Travel speed 1 m/s 2.4 (2.2 - 2.6)
Contact Stroke mm 84.8 (84.0 - 87.0)
OverTravel mm 3.4 (0.0 - 7.0)
Rebounce mm 1.3
Damping time ms 19.8 (15.0 - 27.0)
ROUTINE Page 15 of 15
TEST REPORT
Breaker LTB145D1/B(CSB0 & Avatar) Order No: 502893565
Mechanism: FSA1 Serial No: 1361845910-002

Free Test Spring charge Nom. Mechanism No 1 Operation No 1


40

35

30

25

20
A

15

10

Im1
0

0 1 2 3 4 5 6 7 8 9 10 11 12
s

Operation data
Motor Close coil 1 Trip coil -
110 VDC 110 VDC -

Spring charge for mechanism 1


Description Unit Result Limits
Charge current A 9.0
Charge time s 10.5 (0.0 - 15.0)