PCS-9611S Feeder Relay

The PCS-9611S Feeder Relay is a multifunctional protection, control, and monitoring unit designed for various electrical systems, offering features like selectable protection curves, comprehensive event recording, and multiple protection functions including overcurrent and undervoltage protection. It supports both single-phase and three-phase operations, allowing for flexible application in different scenarios. The device is equipped with high sampling rates and advanced configuration tools to ensure reliable performance and investment security.

Uploaded by

Nima dawa Sherpa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
76 views6 pages

PCS-9611S Feeder Relay

The PCS-9611S Feeder Relay is a multifunctional protection, control, and monitoring unit designed for various electrical systems, offering features like selectable protection curves, comprehensive event recording, and multiple protection functions including overcurrent and undervoltage protection. It supports both single-phase and three-phase operations, allowing for flexible application in different scenarios. The device is equipped with high sampling rates and advanced configuration tools to ensure reliable performance and investment security.

Uploaded by

Nima dawa Sherpa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

PCS S Series www.nrec.

com/en

PCS-9611S Feeder Relay


Table of Contents >
• Selectable IEC, ANSI inverse-time characteristic curves that can be
defined by users, and the inverse-time drop-out curve selection is
supported.

• Overvoltage and undervoltage protection support single phase and


three phase operation criteria setting, phase voltage and phase-to-
Overview 001
phase voltage measurement mode are selectable, which can be for
various applications. NR’s New-generation IED 001
• Highlights
Complete event recording function is provided: 001
64 latest protection
operation reports, 1024 latest supervision records, 1024 latest control
Product Family 002
operation records, 1024 latest user operation records and 1024 latest
records of time tagged sequence of event (SOE) can be recorded.
Application Scenario 002
Device List 002
Functions Function Matrix 003
Protection functions
• Line Protection
Phase Overcurrent Protection (50/51P) 006
PCS-9611S is a protection, control and monitoring unit for various
primary equipments (such as overhead line, underground cable,
PCS-902S
The device can Line Distance
provide six stages Relay protection
of phase overcurrent 011
with independent logic. Each stage can be independently set
capacitor and transformer etc.) on solidly grounded, impedance PCS-931S Line Differential Relay 032
as definite-time characteristics or inverse-time characteristics.
grounded, Peterson coil grounded and ungrounded system. With its PCS-9611S
The dropout characteristics can beFeeder Relay dropout,
set as immediate 054
flexibility and the powerful PCS-Studio configuration tool, the PCS-9611S
offers future-oriented system solutions with high investment security and
PCS-9613S
definite-time dropout Differential
or inverse-time dropout.Relay
Users can 080
choose
whether it is blocked by the voltage control element, direction
low operating costs.
Transformer Protection
control element, or harmonic control element, users can also 105
choose whether it is controlled by cold load pickup. The direction
PCS-978S Transformer Relay 109
control element can be set as no direction, forward direction and
PCS-9671S Transformer Relay 130
Busbar
3VTs
reverse direction. The phase overcurrent protection picks up when
the current exceeds the current threshold value, and operates
52

27P 59P 59Q VTS 59G 81U 81O 81R 25 79


Busbar Protection 149
after a certain time delay, once the fault disappears, the phase
1VT

PCS-915SC
overcurrent Centralized
protection will dropout. Busbar Relay 153
PCS-915SD Distributed Busbar Relay 168
67P 32R 21L

3CTs
•Earth Fault Overcurrent Protection (50/51G)
*
The device can provide six stages of earth fault overcurrent

*
1CT
50P 51P 49 CTS 50BF 51Q 46BC 50L/NL
Bay Control Unit 191
protection with independent logic. Each stage can be independently
set as definite-time characteristics
PCS-9705S Bayor inverse-time
Control Unit characteristics.
194
50G 51G SOTF 67G 37 64REF

1CT The dropout characteristics can be set as immediate dropout,


*

51SEF 60/59 60/50 67SEF FR Capacitor Protection


definite-time dropout or inverse-time dropout. Users can choose 219
1VT
whether it is blocked by the direction control element or the
PCS-9631S Capacitor Relay 223
harmonic control element, users can also choose whether it is
Load
controlled by cold load pickup. The direction control element can
Stability Control System 247
be set as no direction, forward direction and reverse direction. The
PCS-994S Frequency
zero-sequence andby
current used Voltage Controller
earth fault 250
overcurrent protection
Features can be calculated zero-sequence current or the measured zero-

• Fully integrates multi functions into one device and can realize the
Measurement and Recording
sequence current, it can operate to trip or alarm, and it can be 269
enabled or blocked by the external binary
PCS-221S input. Unit
Merging 272
protection and monitoring function of feeder and capacitor etc.

• Comprehensive functionality includes phase overcurrent protection,


• PCS-996S-G
Another Phasor
Group of Earth FaultData Concentrator
Overcurrent 294
Protection (A.50/51G)

earth fault overcurrent protection, negative-sequence overcurrent The device can provide six stages of another group of earth fault
protection, sensitive earth fault protection, overvoltage protection, Auxiliary Software
overcurrent protection with independent logic. Each stage can 312
be independently set as definite-time characteristics or inverse-
undervoltage protection, frequency protection, reverse power PCS-Studio Configuration Tool 312
protection, undercurrent protection, breaker failure protection, time characteristics. The dropout characteristics can be set as
PCS-Torch MOT Tool 312
immediate dropout, definite-time dropout or inverse-time dropout.
undercurrent protection etc. The breaker failure, reclosing, measuring,
monitoring and control function are supported. The high sampling The protection fixedly adopts the measured residual current, the
rate of recording is up to 9.6kHz. calculated residual current is not supported. It can operate to trip
or alarm, it can be enabled or blocked by the external binary input.
• The overcurrent protection is combined with harmonic blocking and
cold load pickup logic, which can prevent mal-operation affected by • Negative-sequence Overcurrent Protection (50/51Q)
inrush current while the transformer is no-load energized. The device can provide two stages of negative-sequence

034 PCS S Series Protection Automation Control


PCS S Series www.nrec.com/en

Table of Contents >


overcurrent protection with independent logic. Each stage can overvoltage protection will operate to remove the device from the
be independently set as definite-time characteristics or inverse- system after a time delay. In addition, the overvoltage protection
time characteristics. The dropout characteristics can be set as also provides the alarm function, prompting the overvoltage
immediate dropout, definite-time dropout or inverse-time dropout. of the system, it allows users to find the cause timely, and
For a double-circuit or a ring network line, the negative-sequence preventing further deterioration of the fault. Each stage of phase
fault current may have different flow direction. Considering Overview
overvoltage protection can be independently set as definite- 001
the protection selectivity, the negative-sequence overcurrent time characteristics or inverse-time characteristics. The dropout
protection can be blocked by the direction control element.
NR’s New-generation IED 001
characteristics can be set as immediate dropout and definite-
Negative-sequence overcurrent current can operate to trip or time dropout. Highlights 001
alarm, it can be enabled or blocked by the external binary input.
Users can select phase voltage or phase-to-phase voltage for
• Broken Conductor Protection (46BC)
Product Family
the protection calculation.
002
Broken-conductor fault mainly is single-phase broken or two- Application Scenario 002
“1-out-of-3” or “3-out-of-3” logic can be selected for the protection
phases broken. According to the ratio of negative-sequence Device
criterion. (1-out-of-3 means any of three phase List
voltages,002
3-out-
current to positive-sequence current (I2/I1), it is used to judge
Function Matrix 003
of-3 means all three phase voltages).
whether there is a broken-conductor fault. Negative-sequence
current under normal operating condition (i.e. unbalance current) • Residual Overvoltage Protection (59G)
is due to CT error and unbalance load, so the ratio of negative-
Line Protection
The device can provide two stages of residual overvoltage
006
sequence current to positive-sequence current (amplitude) is PCS-902S
protection with independent Line Distance
logic. When theRelay 011
residual voltage
relative steady. The value with margin can then be used as the is greaterPCS-931S
than the voltage
Linethreshold, the residual
Differential Relayovervoltage
032
setting of broken conductor protection. It is mainly used to detect protection will operate to remove the device from the system
PCS-9611S Feeder Relay 054
after a time delay. In addition, the residual overvoltage protection
broken-conductor fault and CT circuit failure as well.
PCS-9613S
also provides the Differential
alarm function, Relay
it prompt that 080
there is an earth
• Sensitive Earth Fault Protection (50/51SEF)
fault leading to residual voltage generation, it allows users to find
The device can provide six stages of sensitive earth fault
Transformer Protection 105
the cause timely, and preventing further deterioration of the fault.
protection with independent logic. Each stage can be
The dropout characteristics of residual overvoltage
PCS-978S Transformer Relay protection
109
independently set as definite-time characteristics or inverse-
can be set as immediate dropout and definite-time dropout.
time characteristics. The dropout characteristics can be set PCS-9671S Transformer Relay 130
as immediate dropout, definite-time dropout or inverse-time • Negative-sequence Overvoltage Protection (59Q)
dropout. Users can choose whether it is blocked by the direction Busbar Protection
This device provides two stages of negative-sequence 149
control element. The direction control element can be set as overvoltage protection. If the negative-sequence voltage is
PCS-915SC Centralized Busbar Relay 153
no direction, forward direction and reverse direction. The zero- larger than the predefined setting, this protection will operate.
sequence current used by sensitive earth fault protection is the ThePCS-915SD
negative-sequenceDistributed
overvoltageBusbar Relay
protection 168with
can operate
measured zero-sequence current from the high-precision CT. a definite-time limit, and the supported dropout characteristics
Sensitive earth fault protection can operate to trip or alarm, it can Bay Control Unit
include instantaneous dropout and definite-time dropout. 191
be enabled or blocked by the external binary input.

PCS-9705S Bay Control Unit
Positive-sequence Overvoltage Protection (59Pos)
194
The sensitive earth fault protection can be used to accomplish This device provides one stage of positive-sequence overvoltage
the function of high impedance restricted earth fault protection.
Capacitor Protection
protection. If the positive-sequence voltage is larger than the
219
Once it is used as high impedance restricted earth fault PCS-9631S
pre-defined setting, Capacitor
this protection Relay
will operate. 223
The positive-
protection, the direction control element should be disabled, and sequence overvoltage protection can operate with a definite-
it will not be controlled by voltage element. Stability Control System
time limit, and the supported dropout characteristics include 247
instantaneous
PCS-994S dropout and
Frequency anddefinite-time dropout.
Voltage Controller 250
• RMS Overcurrent Protection (50/51R)
The device can provide two stages of RMS overcurrent • Phase Undervoltage Protection (27P)
protection with independent logic. When the fault current with Measurement and
The device can provide Recording
two stages 269
of phase undervoltage
more harmonic components is generated in the system, the PCS-221S
protection with independent logic. Merging Unit drops
When the voltage 272 in
amplitude is larger than the current threshold of RMS overcurrent the system and it is lower than the voltage threshold, phase
PCS-996S-G Phasor Data Concentrator 294
protection, the RMS overcurrent protection will operate. undervoltage protection will operate.

The operating characteristics of RMS overcurrent protection Auxiliary Software 312


Taking into account that the role of undervoltage protection is
is definite-time characteristics. The dropout characteristics to remove the running device from the system, but in order to
PCS-Studio Configuration Tool 312
can be set as immediate dropout or definite-time dropout. prevent that undervoltage protection is always operating when
RMS overcurrent current can operate to trip or alarm, it can be
PCS-Torch
it is not charged, the breaker MOT check
closed position Tool criterion
312 is
enabled or blocked by the external binary input. added, users can choose to detect the breaker position, current
or no-check as the releasing condition for the protection.
• Phase Overvoltage Protection (59P)
The device can provide two stages of phase overvoltage In addition, the undervoltage protection also provides the alarm
protection with independent logic. When a high voltage occurs function, prompting the voltage drop of the system, it allows users
in the system, it is greater than the voltage threshold, phase to find the cause timely, and preventing further deterioration of

2021 Catalog 035


PCS S Series www.nrec.com/en

Table of Contents >


the fault. Each stage of phase undervoltage protection can be equipment, the single-phase criterion or three-phase criterion
independently set as definite-time characteristics or inverse- can be selected. The position of circuit breaker, the load
time characteristics. The dropout characteristics can be set as current also can be taken as the enabling conditions for the
instantaneous dropout and definite-time dropout. undercurrent protection. The undercurrent protection is with
Users can select phase voltage or phase-to-phase voltage for definite-time operation characteristic and instantaneous dropout
the protection calculation. Overview
characteristic. Undercurrent protection can operate to trip or 001
alarm, it can be enabled or blocked by the external binary input.
“1-out-of-3” or “3-out-of-3” logic can be selected for the protection NR’s New-generation IED 001
criterion. (1-out-of-3 means any of three phase voltages, 3-out- • Breaker Failure Protection (50BF)
of-3 means all three phase voltages).
Highlights 001
According to the tripping information from the device and the
auxiliary information (the current and the position) of target circuit
• Overfrequency Protection (81O) Product Family 002
breaker, breaker failure protection constitutes the criterion to
This device can provide six stages of overfrequency protection.
Application
discriminate whether the target circuit failsScenario 002
to open. If the criterion
If the system frequency is greater than the predefined setting,
is confirmed, breaker failure protection will operate
Device List to 002
trip the
this protection will operate for removing some part of active
target circuit breaker with the re-trip time delay, trip it again with
power supplies from the system. The overfrequency protection Function Matrix 003
the first time delay and trip the adjacent circuit breakers with
is with independent definite time delay characteristic and with
the second time delay. As a special backup protection, breaker
instantaneous dropout characteristic. Line Protection 006
failure protection can quickly isolate the fault, reduce the affected
• Underfrequency Protection (81U) range by thePCS-902S Linestability
fault, keep system Distance Relay generators,
and prevent 011
This device provides six stages of underfrequency protection. transformers and other
PCS-931S primary
Line equipment
Differential from seriously
Relay 032
If the system frequency is less than the predefined setting, this damaged.
protection will operate for shedding some part of loads from
PCS-9611S Feeder Relay 054
• Switch-on-to-Fault Protection (SOTF)
the system. The underfrequency protection is with independent PCS-9613S Differential Relay 080
The device can provide one stage of phase overcurrent SOTF
definite time delay characteristic and with instantaneous dropout
characteristic. Transformer Protection
protection and one stage of earth fault overcurrent SOTF
105
protection. The SOTF protection is with definite time delay
• Frequency Rate-of-change Protection (81R) PCS-978S
characteristic and Transformer
instantaneous Relay users
dropout characteristic, 109can
This device can provide six stages of frequency rate-of-change choose whetherPCS-9671S Transformer
it is blocked by Relayelement.
the harmonic control 130
protection. If the system frequency rate-of-change is greater than
The SOTF protection must be initiated by auto-reclosing signal
the predefined setting, this protection will operate. The frequency Busbar Protection 149
or the condition that the circuit breaker is open, the initiating
rate-of-change protection is with independent definite time delay
PCS-915SC
time Centralized
can be set by the setting. AfterBusbar Relay condition
the acceleration 153 is
characteristic and with instantaneous dropout characteristic.
satisfied, the SOTF protection will operate with a time delay.
PCS-915SD Distributed Busbar Relay 168
• Reverse Power Protection (32R)
In order to improve the reliability, phase overcurrent SOTF
This device can provide two stages of reverse power protection.
Bay Control Unit
protection can select phase voltage element, phase-to-phase 191
If the reverse power is detected and it is greater than the
voltage element, zero-sequenceBay
PCS-9705S voltage element
Control and negative-
Unit 194
predefined setting, the reverse power protection will operate.
sequence voltage element as auxiliary criterion.
The reverse power protection is with independent definite time
delay characteristic and with definite time delay or instantaneous • Capacitor Protection
Thermal Overload Protection (49) 219
dropout characteristic. PCS-9631S
The device provides two stagesCapacitor Relay protection,
of thermal overload 223
one stage for alarm purpose and the other stage for trip purpose.
• Cold Load Pickup Logic (CLP)
The cold load pickup (CLP) logic which is included within this
Stability Control System
The device provides two thermal overload calculation methods: 1) 247
relay serves to either inhibit the selected protective elements for PCS-994S Frequency
only calculated and
by current; Voltage
2) for Controller
the scenario 250
with oil temperature
an appointed duration, or to raise the settings of the selected measurement function, calculate the temperature difference
protective elements. Therefore, it allows the protection settings Measurement and Recording
between the equipment (such as transformer windings) and the 269
to be set closer to the load profile by automatically increasing oil, and then plus the oil temperature measured by the sensor, to
PCS-221S Merging Unit 272
them following circuit energization. The CLP logic thus provides obtain the final temperature.
PCS-996S-G Phasor Data Concentrator 294
stability, whilst maintaining protection during starting.
• Restricted Earth Fault Protection (64REF)
If the CLP logic operates, the CLP settings are enabled for the Auxiliary Software
The difference between current differential protection and REF 312
overcurrent protection and the earth fault overcurrent protection protection is that the first one is based on adjusted phase current
PCS-Studio Configuration Tool 312
respectively. After the drop-out time delay of the CLP logic has balance and the latter is based on balance of calculated residual
elapsed, the normal protection settings are applied. And if a fast current and residual currentPCS-Torch
from neutralMOT Tool 312
point CT.
resetting signal is received, the normal protection settings are
Each side of transformer can be equipped with one group of
applied after the pre-defined short resetting time delay.
REF protection, i.e., for a three-winding transformer, up to three
• Undercurrent Protection (37) groups of REF protection can be equipped, and this device
The device can provide one stage of undercurrent protection can support only one group of REF protection. REF protection
for tripping purpose or alarm purpose. For different protected is not affected by inrush current and the tap of transformer.

036 PCS S Series Protection Automation Control


PCS S Series www.nrec.com/en

Table of Contents >


CT transient detection function based on the ratio of residual time characteristics. The drop-out characteristics can be set as
current to positive current is adopted to eliminate the influence of instantaneous drop-out, definite-time drop-out or inverse-time
difference of transient characteristic to REF protection. drop-out. Another group of phase overcurrent protection picks
up when the current exceeds the current threshold value, and
In order to ensure the selectivity of restricted earth fault
operates after a certain time delay, once the fault disappears,
protection, direction criterion is also available.
Overview
another group of phase overcurrent protection will drop-out. 001
CT circuit supervision for REF protection is divided into two
• Distance ProtectionNR’s
(21L) New-generation IED 001
kinds: differential CT circuit abnormality without the pickup of the
Up to 6 zones distance protection with settable direction are
fault detector and differential CT circuit failure with the pickup of Highlights 001
supplied. Each zone includes three independent phase-to-phase
the fault detector.
measuring loops as well as three independent phase-to-ground
• Arc Flash Protection (50L/NL)
Product Family
measuring loops. Both mho and quadrilateral characteristics
002
The device can support up to 4 channels of arc flash signals, Application
are available for different application. Scenario distance
Phase-to-ground 002
each channel is composed of arc sensor and optical fiber, it is element should be compensated byDevice zero-sequence
List current
002
combined with the auxiliary fault current criterion. The arc sensor of local line. Each zone can select forward direction, reverse
type is point sensor, and the connector between the optical fiber
Function Matrix 003
direction and non direction.
and the device is ST type connector. Because the arc energy for
a busbar fault is mainly concentrated within the ultraviolet light
Line Protection
Load encroachment can distinguish effectively between heavily 006
loaded line and faulty line, and the risk of encroachment of the
range of 300~400nm (namometer), the arc sensor of the device PCS-902S Line Distance Relay 011
load impedance into the tripping characteristics of the distance
adopts ultraviolet light sensor, the sensor can ensure the reliable
protectionPCS-931S Line Differential Relay 032
can be excluded.
detection of arc signal and effectively prevent the adverse effects
of interference light.
PCS-9611S Feeder Relay
Power swing blocking and releasing can prevent distance
054
protection fromPCS-9613S Differential
undesired operation Relayswing,
during power 080even
• Current Unbalance Protection (60/50)
if measured impedance reaches into the operation area of
This device can provide two stages of current unbalance
Transformer Protection
distance protection. Moreover, distance protection can operate 105
protection. If the unbalance current is greater than the
reliably when aPCS-978S
fault occurs during power swing.
Transformer Relay 109
predefined setting, this protection will operate. The current
unbalance protection is with independent definite time delay PCS-9671S
Based on distance Transformer
protection characteristics,Relay 130can
faulty phase
characteristic and with definite time delay or instantaneous be identified correctly.
dropout characteristic.

Busbar Protection
Fault Location (FL)
149
• Voltage Unbalance Protection (60/59) PCS-915SC
Single-end Centralized
fault location Busbar for
function is available Relay
the device.153
Fault
This device can provide two stages of voltage unbalance location element picks up after the device
PCS-915SD Distributed Busbar Relay 168 operates to trip when
protection. If the unbalance voltage is greater than the there is a fault in the line. Fault location element can be activated
predefined setting, this protection will operate. The voltage Bay Control Unit
only after the distance protection, phase overcurrent protection191
unbalance protection is with independent definite time delay or earth fault overcurrent protection operates to trip. Once
characteristic and with definite time delay or instantaneous
PCS-9705S Bay Control Unit 194
any of phase overcurrent protection or earth fault overcurrent
dropout characteristic. protection operates, fault distance calculation starts after 25ms.
Capacitor Protection 219
The premise of fault location is to select the faulty phase. After
• Automatic Reclosure (79)
selecting the faultPCS-9631S
phase, calculateCapacitor
the fault Relay 223
distance according
AR can be used with either integrated device or external device.
to the fault type.
When AR is used with integrated device, the internal protection
logic can initiate AR, moreover, a tripping contact from external
Stability Control System 247
device can be connected to the device via input signal to initiate Control Frequency
PCS-994S functionsand Voltage Controller 250
integrated AR. • Switchgear control
Measurement and Recording 269
When AR is used as an independent device, it can be initiated • Double point status synthesis
by operating signal of protections. The device can output PCS-221S Merging Unit 272
• Remote/Local control mode switch
some configurable output signals (such as, contact signals or PCS-996S-G Phasor Data Concentrator 294
digital signal, for example, GOOSE signal) to initiate external • Interlocking logic for control
AR or block external AR. The contact signals includes tripping Auxiliary Software 312
• Direct control
signal, blocking AR signal and protection operating signal, etc,.
PCS-Studio Configuration Tool 312
According to requirement, these contacts can be selectively • Closing synchronism check with voltage selection
connected to external AR and the device can be set as one-shot PCS-Torch MOT Tool 312
• Switchgear trip counter
or multi-shot AR.

• Another Group of Phase Overcurrent Protection (S2.50/51P)


Measurement and metering
The device can provide six stages of another group of phase
overcurrent protection with independent logic. Each stage can • U, I, P, Q, Cos
be independently set as definite-time characteristics or inverse- • Positive, negative and zero sequences

2021 Catalog 037


PCS S Series www.nrec.com/en

Table of Contents >


• Max.15th harmonics ₒₒ IEC 62439 Parallel Redundancy Protocol (PRP)

• Energy metering (active and reactive energies for import and ₒₒ IEC 62439 High-availability Seamless Ring (HSR)
export) Redundancy Protocol

• Power Quality Supervision (PQS) with Total Harmonic Distortion ₒₒ IEEE 802.1w Rapid Spanning Tree Protocol (RSTP)
(THD), deviation and unbalance
• Support for digital substation Overview 001
• DC analogue outputs (4~20mA, 0~10V, 0~5V or 0~20mA) NR’s
ₒₒ Extendable quantity New-generation
of communication IED
interfaces 001
ₒₒ Support of IEC 61850 MMS Server Highlights 001
Synchrophasor measurement
• The integrated Phasor Measurement Unit (PMU) function of Product Family
ₒₒ Support of IEC 61850-8-1 GOOSE
002
synchrophasor measurement is compatible with IEEE C37.118- ₒₒ Support of IEC 61850-9-2LE SV
Application Scenario 002
2005, IEEE C37.118.1-2011, IEEE C37.118.2-2011 and IEEE
C37.118.1a-2014.
• Device
Up to four 10Base-T/100Base-TX copper List
Ethernet ports 002
• Function
Up to four 100Base-FX optical Ethernet portsMatrix 003
• Supporting time synchronization by IRIG-B signal
• Two RS-485 serial ports for communication or printer
• Supporting P Class or M Class measurement (user selectable) Line Protection 006
• One RS-485/TTL serial port for clock synchronization
• Measurement of three-phase and single-phase voltage and PCS-902S Line Distance Relay 011
current • One BNCPCS-931S
port for clock synchronization
Line Differential Relay 032
• Measurement of positive/negative/zero-sequence voltage and PCS-9611S Feeder Relay 054
current User Interfaces
PCS-9613S Differential Relay 080
• Friendly HMI interface with LCD, easy-to-use keypad aids simple
• Calculation of active power, reactive power, system frequency,
and rate-of-change of frequency (ROCOF) Transformer Protection
navigation and set-point adjustment 105
• Push buttonsPCS-978S Transformer
for open/close, Relay between
switch for selection 109
• Measurement of up to 32 binary status (user configurable)
local and remote control, and user's login and logout authority
• Output of synchrophasor with timestamp, support of multiple
PCS-9671S Transformer Relay 130
management
protocols (TCP, TCP-UDP, UDP) and multiple data rates for
maximum 4 clients (PDC)
• Busbar Protection
4 Programmable operator pushbuttons with user-configurable149
labels
PCS-915SC Centralized Busbar Relay 153
Supervision functions • Up PCS-915SD
to 15/18 (6U, Distributed
1/3 × 19" orBusbar
6U, 1/2Relay 168
× 19" chassis)
programmable target LEDs with user-configurable labels
• VT circuit supervision
• Bay Control Unit
1 RS-232 rear port for printer (by jumper) 191
• CT circuit supervision
PCS-9705S Bay Control Unit 194
• Language switchover—English+ selected language
• Self-diagnostic

• DC power supply supervision


• Capacitor Protection
Configuration tool—PCS-Studio 219
PCS-9631S Capacitor Relay 223
• System frequency supervision
Additional functions
• Event recorder including 1024 disturbance items, 1024 change- • Stability Control System
User programmable logic 247
of-state events, 1024 supervision events, 256 control logs and PCS-994S Frequency and Voltage Controller 250
• Fault location
1024 device logs.

• Disturbance recorder including 64 disturbance records with Measurement


• Fault phase selection and Recording 269
waveforms (The file format of disturbance recorder is compatible • PCS-221S
System phase sequences Merging
rotation function (ABCUnit
or ACB)272
with international COMTRADE file).
• PCS-996S-G
Clock synchronizationPhasor Data Concentrator 294
• Single line diagram representation in display ₒₒ IRIG-B: IRIG-B via RS-485 differential level, TTL level, BNC or
Auxiliary Software
optical fiber interface 312
Communication functions PCS-Studio Configuration Tool 312
ₒₒ PPS: Pulse per second (PPS) via RS-485 differential level or
• Support of various protocols binary input PCS-Torch MOT Tool 312
ₒₒ Modbus
ₒₒ IEEE1588: Clock message based on IEEE1588 via Ethernet
ₒₒ DNP3
network
ₒₒ IEC 60870-5-103
ₒₒ SNTP (PTP): Unicast (point-to-point) SNTP mode via Ethernet
ₒₒ IEC 61850 Ed1 & Ed2 network

038 PCS S Series Protection Automation Control


PCS S Series www.nrec.com/en

Table of Contents >


ₒₒ SNTP (BC): Broadcast SNTP mode via Ethernet network 5. Push buttons with configurable labels for user-programmable
functions
ₒₒ Message (IEC103/Modbus/DNP3): Clock messages through
IEC103 protocol, Modbus protocol and DNP3 protocol 6. Front RJ45 multiplex port for debugging

7. Push button for target reset of all signals


• Cyber security
ₒₒ NERC CIP Overview
8. Two LED indictors for device running status 001
ₒₒ IEC 62351 9. Up to 18 (6U, 1/2 ×NR’s
19")/15New-generation IED 001
(6U, 1/3 × 19") programmable target
LEDs with user-configurable labels Highlights 001
ₒₒ IEC 62443
Product Family 002
ₒₒ IEEE 1686 Rear Panel Application Scenario 002
Device List 002
Front Panel Function Matrix 003
3 3

4 1 Line Protection
2
4 1 006
2
8 8
PCS-902S Line Distance Relay 011

1
3 1 PCS-931S Line Differential Relay 032
9 9 PCS-9611S Feeder Relay 054
4
2
5 PCS-9613S Differential
5 Relay 080
2

5 5 6
Transformer Protection 6
105
7
PCS-978S Transformer Relay 109
6
6 7 3 4 PCS-9671S
1. Current and voltage Transformer
analog inputs Relay 130

Busbar Protection
2. Power supply and binary I/O 149
1. Local LCD screen for device status and information display
PCS-915SC
3. Copper Ethernet portCentralized Busbar Relay 153
2. Easy-to-use keypad aiding simple navigation and set-point PCS-915SD
4. Fiber-optic Distributed
Ethernet port Busbar Relay 168
adjustment
5. RS-232 or RS-485 serial port
3. Push buttons for opening/closing operation and switching of local/ Bay Control Unit 191
6. Debug port
remote control mode PCS-9705S Bay Control Unit 194
4. Push button for user login/logout of authority management
Capacitor Protection 219
PCS-9631S Capacitor Relay 223

Stability Control System 247


PCS-994S Frequency and Voltage Controller 250

Measurement and Recording 269


PCS-221S Merging Unit 272
PCS-996S-G Phasor Data Concentrator 294

Auxiliary Software 312


PCS-Studio Configuration Tool 312
PCS-Torch MOT Tool 312

2021 Catalog 039