(TDB) 2024 VRF Duct For Europe (R410A, 50Hz) - Ver.1.0 - 231018
(TDB) 2024 VRF Duct For Europe (R410A, 50Hz) - Ver.1.0 - 231018
Technical
Data Book
Duct for Europe
(R410A, 50Hz)
Model: AM160DNMPKH/EU
History
Model Names
AM 160 D N M P K H / EU
AM VRF P Premium
N Indoor Unit(NASA)
M MSP Duct
Features & Benefits
Duct
Capacity (kW)
16.0
Image
Contents
1. Specification 8
2. Summary Table 9
3. Capacity Table 10
4. Dimensional Drawing 11
5. Center of Gravity 12
6. Electrical Wiring Diagram 13
7. Sound Data 14
8. Fan Characteristics 16
9. Piping Diagram 17
10. Installation 18
1. Specification
Duct
Type Duct S
Model Name AM160DNMPKH/EU
Power Supply Φ, #, V, Hz 1,2,220-240,50
kW 16.0
Cooling
Btu/h 54,600
Performance Capacity
kW 18.0
Heating
Btu/h 61,400
Cooling 300.0
Power Input W
Heating 300.0
Cooling 2.5
Power Current Input A
Heating 2.5
MCA 3.60
Current A
MFA 15
Type - F&T
Fin - Al
Heat exchanger Material
Tube - Cu
Fin Treatment - Green Hydrophile
Type - Sirocco Fan
Quantity EA 3
m³/min 45.00/35.00/25.00
Fan Air Flow Rate H/M/L
l/s 750/583/417
㎜Aq 0/5.2/15
External Pressure Min/Std/Max
Pa 0.00/51.00/147.10
Type - BLDC
Fan Motor
Output x n W 350
Type Flare connection
Liquid Pipe
Φ, ㎜ (inch) 9.52 (3/8)
Piping
Type Flare connection
Connections Gas Pipe
Φ, ㎜ (inch) 15.88 (5/8)
Drain Pipe Φ,mm VP25 (OD 32,ID 25)
Wiring Min. ㎟ 0.75
Communication
connections Remark - F1,F2
Type - R410A
Refrigerant
Control Method - EEV INCLUDED
Sound Pressure Level H/M/L dB(A) 43/39/35
Sound Level
Sound Power Level Cooling 65
Net Weight kg 44.6
Shipping Weight kg 51.1
Dimensions
Net Dimensions (W×H×D) mm 1,300x300x700
Shipping Dimensions (W×H×D) mm 1,529x370x779
Casing Material - GI Steel plate
External Model - -
Internal Model - Built In
Additional Drain Pump
Accessories Max. lifting Height
㎜ / Liter/h 750 / 24
/ Displacement
Air Filter - -
NOTE
• Specification may be subject to change without prior notice.
1) Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°C DB, 19°C WB, Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB, Outdoor temperature 7°C DB, 6°C WB
- Equivalent refrigerant piping length 7.5m, Level differences 0m
2) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
3) Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level, - Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level, - Reference power : 1pW, - Measured according to ISO 3741
5) Select wire size based on the value of MCA
2. Summary Table
Duct
Performance Characteristics
Electrical Characteristics
Model Code Power Supply (Φ, #, V, Hz) Power Input (W) Current Input (A) MCA (A) MFA (A) FLA (A)
NOTE
• MCA : Minimum circuit amperes
• MFA: Maximum fuse amperes
• FLA: Full load amperes
• Select wire size based on the value of MCA
3. Capacity Table
Duct
AM160DNMPKH/EU
NOTE
The performance table shows the average value of each conditions.
4. Dimensional Drawing
Duct
AM160DNMPKH/EU
(Unit: mm)
Drain pipe connection (Without drain pump) VP25 (OD 32, ID 25)
(Unit: mm)
Model A B C D E F
AM160DNMPKH/EU 700 [27-9/16] 265 [10-7/16] 1300 [51-3/16] 625 [24-39/64] 300 [11-13/16] 150 [5-15/16]
6. Electrical Wiring Diagram
Duct
AM160DNMPKH/EU
F100/F101 Fuse M-BLDC Motor for indoor Fan DISPLAY LED display
Contact output port Contact output port for EEPROM SUB PBA
ERROR CHECK COMP CHECK EEPROM
for error check compressor operation check
DISCHARGE TEMP Thermistor (DISCHARGE_10Kohm) EVA IN TEMP Thermistor (EVA IN_10Kohm) EVA OUT TEMP Thermistor (EVA OUT_10Kohm)
EEV Electronic expansion valve EXTERNAL CTRL Input port for external contact control
NOTE
• This wiring diagram applies only to the Indoor unit.
• Symbols show as follow :
BLK: black, RED: red, BLU: blue, WHT white, YEL: yellow, BRN: brown, SKY: skyblue: GRN: green
• For connection wiring indoor-outdoor transmission F1-F2, indoor-wired remote controller transmission F3-F4.
• Protective earth(screw), : connector, : The wire quantity
7. Sound Data
Duct
Unit: dB(A)
Discharge Suction
Model High Mid Low
Duct Duct AM160DNMPKH/EU 43 39 35
2m 2m
1.5m
Microphone
• NR Curve
1) AM160DNMPKH/EU
70 70
65 65
60 60
Sound Pressure Level (dB)
55 NR 60 55
50 NR 55 50
45 NR 50 45
40 40
NR 45
35 35
NR 40
30 30
NR 35
25 25
NR 30
20 20
NR 25
15 15
NR 20
10 10
Hearing threshold NR 15
5 5
0 0
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency(Hz)
NOTE
• Specifications may be subject to change without prior notice.
- Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A weighted sound pressure level
- Reference acoustic pressure 0 dB = 20μPa
7. Sound Data
Duct
• NR Curve
AM160DNMPKH/EU
90 90
85 85
80 80
75 75
Sound Power Level (dB)
70 70
65 65
60 60
55 NR 60
55
50 NR 55
50
45 NR 50
45
40 40
NR 45
35 35
NR 40
30 30
NR 35
25 25
NR 30
20 20
NR 25
15 15
NR 20
10 10
5 NR 15 5
0 0
125 250 500 1000 2000 4000 8000 A
Octave Band Center Frequency(Hz)
8. Fan Characteristics
Duct
1) AM160DNMPKH/EU
External Static Pressure(mmAq) Option Code External Static Pressure(mmAq) Option Code
1 2
0≤SP≤5.2 010054-1E54B9-20A0A0-331120 5.2<SP≤8 010054-1E580A-20A0A0-331120
19 19
18 18
17 17
16 16
HIGH
15 15
14 14
13 13
HIGH 12
12
11 11
10 10
MIDDLE
9 9
MIDDLE Upper limit of
8 8
external 2
7 Upper limit of 7
external static pressure
6 6
static pressure 1
5 5
LOW LOW
4 4
3 3
2 Lower limit of 2
Lower limit of
external 1
external
1
static pressure static pressure
0 0
20 25 30 35 40 45 50 55 60 20 25 30 35 40 45 50 55 60
External Static Pressure(mmAq) Option Code External Static Pressure(mmAq) Option Code
3 4
8<SP≤12 010054-1E583C-20A0A0-331120 12<SP≤14 010054-1E586D-20A0A0-331120
19
HIGH 19
18
18
17
17
16 HIGH
16
External Static Pressure [mmAq]
15
15
14
14 4
13 MIDDLE
13
MIDDLE Upper limit of
12
Upper limit of 3 12
11
external
external 11
static pressure
10
static pressure 10
9 9
8 8
7 7 Lower limit of
6 LOW external
6
LOW static pressure
5 5
4 4
3 Lower limit of 3
2 external 2
1 static pressure 1
0 0
20 25 30 35 40 45 50 55 60 20 25 30 35 40 45 50 55 60
18
17
HIGH
16
5
External Static Pressure [mmAq]
15
14
MIDDLE Upper limit of
13
external
12 static pressure
11
10
7
LOW
6 Lower limit of
5 external
4 static pressure
3
0
20 25 30 35 40 45 50 55 60
Filter
Filter
(T_II)
Thermistor-RoomAirout
Termistor - IDU Heat Exchanger In (T_AO)
Gas pipe
connection port
ØB
Refrigerant flow
Cooling Heating
Unit : mm (inch)
Model A B
AM160DNMDKH1TK 9.52 (3/8) 15.88 (5/8)
10. Installation
Duct
Indoor Unit
• There must be no obstacles near the air inlet and outlet.
• Install the indoor unit on a ceiling that can support its weight.
• Maintain sufficient clearance around the indoor unit.
• Make sure that the water dripping from the drain hose runs away correctly and safely.
• The indoor unit must be installed in this way, that they are out of public access. (Not touchable by the users)
• After connecting a chamber, insulate the connection part between the indoor unit and the chamber with t10 or thicker
insulation. Otherwise, there can be air leak or dew from the connection part.
• Rigid wall without vibration.
• Where it is not exposed to direct sunshine.
• Where the air filter can be removed and cleaned easily.
20mm or more
Unit Width(W)
20mm or more
“A”=W+100mm “B”=500mm
• You must have 20mm or more space between the ceiling and the bottom of indoor unit. Otherwise, the noise from the
vibration of indoor unit may bother the user.When the ceiling is under construction, the hole for check-up must be made to
take service, clean and repair the unit.
• It is possible to install the unit at an height of between 2.2~2.5m from the ground, if the unit has a duct with a well defined
lenght (300mm or more), to avoid fan motor blower contact.
• If you install the cassette or duct type indoor unit on the ceiling with humidity over 80%, you must apply extra
• 10mm of polyethylene foam or other insulation with similar material on the body of the indoor unit.
Insulation Guide
• I nsulate the end of the pipe and some curved area by using separate insulator.
• I nsulate the discharge and suction part at the same time when you insulate connection duct.
• If the humidity is over 80%, it is required to add 10mm polyethylene foam or other similar insulation to the indoor unit when
installing belt or pipe type indoor unit on the ceiling.
D B
Back
Front
A C
10. Installation
Duct
• Insulate the end of the pipe and some curved area by using separate insulator.
• Insulate the discharge and suction part at the same time when you insulate connection duct.
• If the humidity is over 80%, it is required to add 10mm polyethylene foam or other similar insulation to the indoor unit
when installing belt or pipe type indoor unit on the ceiling.
Drainpipe Connection
Without the drain pump
1 Install horizontal drainpipe with a slope of 1/100 or more and fix it by hanger space of 1.0~1.5m.
2 Install U-trap at the end of the drainpipe to prevent a nasty smell to reach the indoor unit.
3 Do not install the drainpipe to upward position. It may cause water flow back to the unit.
1~1.5m
Hanger
Flexible hose
Horizontal drainpipe
Ceiling more than 1/100 slope
1 The drain pipe should be installed within 300mm to 550mm from the flexible hose and then lift down 20mm or more.
2 Install horizontal drainpipe with a slope of 1/100 or more and fix it by hanger space of 1.0~1.5m.
3 Install the air vent in the horizontal drainpipe to prevent water flow back to the indoor unit.
NOTE
• You may not need to install it if there were proper slope in the horizontal drainpipe.
4 The flexible hose should not be installed upward position, it may cause water flow back to the indoor unit.
Ceiling
10. Installation
Duct
Centralized Drainage
Without the drain pump
1 Install horizontal drainpipe with a slope of 1/100 or more and fix it by hanger space of 1.0~1.5m.
2 Install U-trap at the end of the drainpipe to prevent a nasty smell to reach the indoor unit.
100mm or more
Horizontal drainpipe
Ceiling more than 1/100 slope
1 Install main air vent at the front of the farthest indoor unit from the main drain when installed indoor units are more than 3.
2 You may need to install individual air vent to prevent water flow back at the top of each indoor unit drainpipe.
Hanger 1~1.5m
Main air vent
Individual
air vent
550mm or
less
1 pour water into the base pan in the indoor unit as shown in figure.
2 Confirm that the water flows out through the drain hose.
Outdoor Unit
Wired Remote
Control
220-240V~
or
MCCB+ ELCB
ELB
V1 V2
EEV kit
L N
n Coef×35.6×Lk×ik
Σ( ) < 10% of input voltage[V]
k=1 1000×Ak
• coef: 1.55
• Lk: Distance among each indoor unit[m], Ak: Power cable specification[mm²]
ik: Running current of each unit[A]
10. Installation
Duct
Example of Installation
− Total power cable length L = 100(m), Running current of each units 1[A]
− Total 10 indoor units were installed
n Coef×35.6×Lk×ik
Σ( ) < 10% of input voltage[V]
k=1 1000×Ak
• Calculation
− Installing with 1 sort wire.
2.5[mm²] 2.5[mm²] 2.5[mm²]
-2.2[V] -2.0[V]
208.8[V](Within 198V~242V)
220[V]
-(2.2+2.0+1.8+1.5+1.3+1.1+0.9+0.7+0.4+0.2)=-11.2[V] it's okay
-1.4[V] -1.2[V]
209.5[V](Within 198V~242V)
220[V]
-(1.4+1.2+1.8+1.5+1.3+1.1+0.9+0.7+0.4+0.2)=-10.5[V] it's okay
Rating current
CAUTION
• Select the power cable in accordance with relevant local and national regulations.
• Wire size must comply with local and national code.
• For the power cable, use the grade of H07RN-F or H05RN-F materials.
• You should connect the power cable into the power cable terminal and fasten it with a clamp.
• The unbalanced power must be maintained within 10% of supply rating among whole indoor units.
• If the power is unbalanced greatly, it may shorten the life of the condenser. If the unbalanced power is exceeded over 10% of
supply rating, the indoor unit is protected, stopped and the error mode indicates.
• To protect the product from water and possible shock, you should keep the power cable and the connection cord of the indoor
and outdoor units in the iron pipe.
• Connect the power cable to the auxiliary circuit breaker.
• An all pole disconnection from the power supply must be incorporated in the fixed wiring(≥3mm).
• You must keep the cable in a protection tube.
• Keep distances of 50mm or more between power cable and communication cable.
• Maximum length of power cables are decided within 10% of power drop. If it exceeds, you must consider another power
supplying method.
• The circuit breaker(ELCB or MCCB+ELB) should be considered more capacity if many indoor units are connected from one
breaker.
• Use round pressure terminal for connections to the power terminal block.
• For wiring, use the designated power cable and connect it firmly, then secure to prevent outside pressure being exerted on the
terminal board.
• Use an appropriate screwdriver for tightening the terminal screws. A screwdriver with a small head will strip the head and
make proper tightening impossible.
• Over-tightening the terminal screws may break them.
• See the table below for tightening torque for the terminal screws.
Tightening torque
N•m kgf•cm
M3.5 0.8~1.0 8.0~10.0
M4 1.2~1.5 12.0~14.7
2023.10
Ver.1.0
Samsung Electronics Co., LTD.
Head Office (Suwon Korea) 129, Samsung-Ro, Yeongtong-Gu, Suwon City, Gyeonggi-Do, Korea 16677
Website : www.samsung.com, https://partnerhub.samsung.com Email : [email protected]
Images and data in this book may subject to change without prior notice.