(TDB) 2024 VRF Duct For Europe (R410A, 50Hz) - Ver.1.0 - 231018

The document provides technical data for the AM160DNMPKH/EU ducted indoor unit designed for VRF systems in Europe, highlighting its features, specifications, and performance characteristics. Key benefits include its compact design for easy installation, energy efficiency through a Smart Inverter System, and simple servicing with 3-way access. The document also includes detailed specifications such as power input, cooling and heating capacities, and sound levels.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
93 views24 pages

(TDB) 2024 VRF Duct For Europe (R410A, 50Hz) - Ver.1.0 - 231018

The document provides technical data for the AM160DNMPKH/EU ducted indoor unit designed for VRF systems in Europe, highlighting its features, specifications, and performance characteristics. Key benefits include its compact design for easy installation, energy efficiency through a Smart Inverter System, and simple servicing with 3-way access. The document also includes detailed specifications such as power input, cooling and heating capacities, and sound levels.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 24

VRF

Technical
Data Book
Duct for Europe
(R410A, 50Hz)

Model: AM160DNMPKH/EU
History

Version Modification Date Remark


Ver. 1.0 Release Duct TDB for Europe 23.10.11 -
Nomenclature
Indoor Unit

Model Names

AM 160 D N M P K H / EU

(1) (2) (3) (4) (5) (6) (7) (8) Buyer

(1) Classification (6) Feature

AM VRF P Premium

(2) Capacity (7) Rating Voltage

x 1/10 kW (3 digits) K 220~240V, 50/60Hz, 1Ø

(3) Version (8) Mode

D 2024 H Heat Pump(R410A)

(4) Product Type

N Indoor Unit(NASA)

(5) Product Notation

M MSP Duct
Features & Benefits
Duct

Install anywhere and maintain easily


Small & lightweight
Fit your air conditioner into even the smallest spaces. A lightweight and compact Slim Fit design is 30%
smaller and 42% lighter than conventional air conditioners*. It makes it much easier to handle and set
up, and means it can be installed almost anywhere in a building with little difficulty.

* Based on internal testing compared to competing air conditioners.

Simple set up, automatically even cooling


Auto ESP Adjustment
Enjoy maximum comfort and efficiency with
minimum effort. The Auto ESP Adjustment
automatically optimizes the air volume and
pressure and minimizes noise, ensuring
consistent cooling and heating in any
situation. The external static pressure (ESP)
can also be adjusted using a remote control.
Features & Benefits
Duct

Simple to service in various locations


3-way Service Access
Install your ducted air conditioner in various locations, but still enjoy easy access for servicing. It can be
accessed from three directions–top, side and bottom–using an easy to remove Slide Fit cover. So it’s
simple to maintain wherever it’s installed in, which saves you time and money.

World-class energy efficiency & savings


Smart Inverter System

Save money without sacrificing performance


with its outstanding energy efficiency,
earning it a Top-level Energy Efficiency
Ratio. A large Sirocco Fan with aerodynamic
blades and a DC Fan Motor expels more air,
with less noise*. And the Twin Rotary BLDC
Compressor is quieter and more reliable.

* Based on internal testing compared to conventiona


air conditioners. Results may vary depending on
environmental factors and individual use.
Line-up
Indoor unit

Capacity (kW)

16.0

Image
Contents

1. Specification 8
2. Summary Table 9
3. Capacity Table 10
4. Dimensional Drawing 11
5. Center of Gravity 12
6. Electrical Wiring Diagram 13
7. Sound Data 14
8. Fan Characteristics 16
9. Piping Diagram 17
10. Installation 18
1. Specification
Duct

Type Duct S
Model Name AM160DNMPKH/EU
Power Supply Φ, #, V, Hz 1,2,220-240,50
kW 16.0
Cooling
Btu/h 54,600
Performance Capacity
kW 18.0
Heating
Btu/h 61,400
Cooling 300.0
Power Input W
Heating 300.0
Cooling 2.5
Power Current Input A
Heating 2.5
MCA 3.60
Current A
MFA 15
Type - F&T
Fin - Al
Heat exchanger Material
Tube - Cu
Fin Treatment - Green Hydrophile
Type - Sirocco Fan
Quantity EA 3
m³/min 45.00/35.00/25.00
Fan Air Flow Rate H/M/L
l/s 750/583/417
㎜Aq 0/5.2/15
External Pressure Min/Std/Max
Pa 0.00/51.00/147.10
Type - BLDC
Fan Motor
Output x n W 350
Type Flare connection
Liquid Pipe
Φ, ㎜ (inch) 9.52 (3/8)
Piping
Type Flare connection
Connections Gas Pipe
Φ, ㎜ (inch) 15.88 (5/8)
Drain Pipe Φ,mm VP25 (OD 32,ID 25)
Wiring Min. ㎟ 0.75
Communication
connections Remark - F1,F2
Type - R410A
Refrigerant
Control Method - EEV INCLUDED
Sound Pressure Level H/M/L dB(A) 43/39/35
Sound Level
Sound Power Level Cooling 65
Net Weight kg 44.6
Shipping Weight kg 51.1
Dimensions
Net Dimensions (W×H×D) mm 1,300x300x700
Shipping Dimensions (W×H×D) mm 1,529x370x779
Casing Material - GI Steel plate
External Model - -
Internal Model - Built In
Additional Drain Pump
Accessories Max. lifting Height
㎜ / Liter/h 750 / 24
/ Displacement
Air Filter - -

NOTE
• Specification may be subject to change without prior notice.
1) Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°C DB, 19°C WB, Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB, Outdoor temperature 7°C DB, 6°C WB
- Equivalent refrigerant piping length 7.5m, Level differences 0m
2) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
3) Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level, - Reference acoustic pressure 0 dB = 20uPa
4) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level, - Reference power : 1pW, - Measured according to ISO 3741
5) Select wire size based on the value of MCA
2. Summary Table
Duct

Performance Characteristics

Nominal Capacity [kW] Sound Static Pressure


Fan Sound Power
Model Code Airflow [CMM] Pressure (Min/Std/Max)
Cooling Sensible Heating Speed [dBA]
[dBA] [mmAq]
16.0 12.1 18.0 High 45.0 43 65
AM160DNMPKH/EU 12.8 9.7 15.9 Mid 35.0 39 - 0 / 5.2 / 15
9.1 6.9 13.4 Low 25.0 35 -

Electrical Characteristics

Model Code Power Supply (Φ, #, V, Hz) Power Input (W) Current Input (A) MCA (A) MFA (A) FLA (A)

AM160DNMPKH/EU 1,2,220~240,50 300.0 2.5 3.60 15 2.88

NOTE
• MCA : Minimum circuit amperes
• MFA: Maximum fuse amperes
• FLA: Full load amperes
• Select wire size based on the value of MCA
3. Capacity Table
Duct

AM160DNMPKH/EU

Cooling TC: Total Capacity, SHC: Sensible Heat Capacity


Indoor temperature
Outdoor 20(℃,DB) 23(℃,DB) 26(℃,DB) 27(℃,DB) 28(℃,DB) 30(℃,DB) 32(℃,DB)
Air Temp. 14(℃,WB) 16(℃,WB) 18(℃,WB) 19(℃,WB) 20(℃,WB) 22(℃,WB) 24(℃,WB)
(℃,DB) TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-5 11.1 9.6 13.0 10.9 15.0 11.8 16.0 12.1 16.7 12.2 17.9 12.3 19.2 12.2
-4 11.1 9.6 13.0 10.9 15.0 11.8 16.0 12.1 16.7 12.2 17.9 12.3 19.2 12.2
-2 11.1 9.6 13.0 10.9 15.0 11.8 16.0 12.1 16.7 12.2 17.9 12.3 19.2 12.2
0 11.1 9.6 13.0 10.9 15.0 11.8 16.0 12.1 16.7 12.2 17.9 12.3 19.2 12.2
2 11.1 9.6 13.0 10.9 15.0 11.8 16.0 12.1 16.7 12.2 17.9 12.3 19.2 12.2
4 11.1 9.6 13.0 10.9 15.0 11.8 16.0 12.1 16.7 12.2 17.9 12.3 19.2 12.2
6 11.1 9.6 13.0 10.9 15.0 11.8 16.0 12.1 16.7 12.2 17.9 12.3 19.2 12.2
8 11.1 9.6 13.0 10.9 15.0 11.8 16.0 12.1 16.7 12.2 17.9 12.3 19.2 12.2
10 11.1 9.6 13.0 10.9 15.0 11.8 16.0 12.1 16.7 12.2 17.9 12.3 19.2 12.2
12 11.1 9.6 13.0 10.9 15.0 11.8 16.0 12.1 16.6 12.1 17.8 12.2 19.1 12.1
14 11.1 9.6 13.0 10.9 15.0 11.8 16.0 12.1 16.6 12.1 17.8 12.2 19.1 12.1
16 11.1 9.6 13.0 10.9 15.0 11.8 16.0 12.1 16.6 12.1 17.8 12.2 19.0 12.0
18 11.1 9.6 13.0 10.9 15.0 11.8 16.0 12.1 16.6 12.1 17.7 12.1 19.0 12.0
20 11.1 9.6 13.0 10.9 15.0 11.8 16.0 12.1 16.6 12.1 17.7 12.1 18.9 11.9
21 11.1 9.6 13.0 10.9 15.0 11.8 16.0 12.1 16.6 12.1 17.7 12.1 18.9 11.9
23 11.1 9.6 13.0 10.9 15.0 11.8 16.0 12.1 16.6 12.1 17.7 12.1 18.9 11.9
25 11.1 9.6 13.0 10.9 15.0 11.8 16.0 12.1 16.6 12.1 17.7 12.1 18.9 11.9
27 11.1 9.6 13.0 10.9 15.0 11.8 16.0 12.1 16.6 12.1 17.7 12.1 18.9 11.9
29 11.1 9.6 13.0 10.9 15.0 11.8 16.0 12.1 16.6 12.1 17.7 12.1 18.9 11.9
31 11.1 9.6 13.0 10.9 15.0 11.8 16.0 12.1 16.6 12.1 17.7 12.1 18.9 11.9
33 11.1 9.6 13.0 10.9 15.0 11.8 16.0 12.1 16.6 12.1 17.7 12.1 18.9 11.9
35 11.1 9.6 13.0 10.9 15.0 11.8 16.0 12.1 16.6 12.1 17.7 12.1 18.9 11.9
37 11.1 9.6 13.0 10.9 15.0 11.8 16.0 12.1 16.6 12.1 17.6 12.0 18.6 11.8
39 11.1 9.6 13.0 10.9 15.0 11.8 16.0 12.1 16.5 12.0 17.3 11.8 18.2 11.5
42 11.1 9.6 13.0 10.9 14.9 11.7 15.8 12.0 16.2 11.9 16.9 11.5 17.7 11.2
44 11.1 9.6 13.0 10.9 14.5 11.3 15.3 11.5 15.8 11.5 16.2 11.1 17.1 10.9
46 11.1 9.6 12.9 10.8 14.2 11.2 14.7 11.2 15.3 11.2 15.8 10.8 16.7 10.5
48 11.0 9.5 12.7 10.6 13.9 11.0 14.4 10.9 15.0 11.0 15.3 10.4 16.1 10.2
50 11.0 9.5 12.7 10.6 13.9 11.0 14.4 10.9 15.0 11.0 15.2 10.3 16.0 10.1

Heating TC: Total Capacity


Indoor temperature (℃,DB)
Outdoor Air Temp.
14(℃,DB) 16(℃,DB) 18(℃,DB) 20(℃,DB) 22(℃,DB) 24(℃,DB) 27(℃,DB)
(℃)
TC TC TC TC TC TC TC
DB WB kW kW kW kW kW kW kW
-25 -25.1 10.4 10.4 10.4 10.4 10.2 10.2 10.1
-22 -22.2 10.6 10.6 10.6 10.5 10.5 10.4 10.4
-19.8 -20 10.7 10.7 10.7 10.6 10.6 10.5 10.4
-18.8 -19 10.9 10.9 10.9 10.7 10.7 10.5 10.4
-16.7 -17 11.6 11.5 11.3 10.9 10.8 10.6 10.5
-14.7 -15 12.2 12.2 11.8 11.5 11.1 10.8 10.6
-12.6 -13 12.6 12.5 12.3 12.0 11.7 11.4 10.9
-10.5 -11 13.2 13.1 12.9 12.7 12.5 12.3 11.8
-9.5 -10 13.6 13.3 13.2 12.9 12.8 12.6 12.2
-8.5 -9.1 13.7 13.6 13.4 13.3 13.1 12.7 12.3
-7 -7.6 14.1 14.0 13.7 13.6 13.3 12.9 12.5
-5 -5.6 14.9 14.7 14.5 14.3 13.8 13.5 13.1
-3 -3.7 15.9 15.5 15.3 15.1 14.5 14.0 13.5
0 -0.7 16.4 16.2 16.0 15.8 15.1 14.4 13.8
3 2.2 17.2 17.0 16.8 16.5 15.9 15.2 14.5
5 4.1 18.1 17.8 17.6 17.2 16.2 15.2 14.5
7 6 18.8 18.6 18.2 18.0 16.7 15.2 14.5
9 7.9 19.4 19.1 18.6 18.0 16.7 15.2 14.5
11 9.8 20.0 19.7 18.8 18.0 16.7 15.2 14.5
13 11.8 20.5 20.3 19.1 18.0 16.7 15.2 14.5
15 13.7 21.2 20.8 19.4 18.0 16.7 15.2 14.5
18 16.6 21.2 20.9 19.4 18.0 16.8 15.3 14.6
20 18.5 21.3 20.9 19.6 18.1 16.8 15.3 14.6
22 20.4 21.4 21.0 19.6 18.2 16.9 15.4 14.6
24 22.4 21.5 21.0 19.7 18.2 16.9 15.4 14.7

NOTE
The performance table shows the average value of each conditions.
4. Dimensional Drawing
Duct

AM160DNMPKH/EU
(Unit: mm)

No. Name Description

Liquid pipe connection Ø9.52 (3/8)

Gas pipe connection Φ15.88 (5/8)

Drain pipe connection (Without drain pump) VP25 (OD 32, ID 25)

Drain pipe connection (With drain pump) -

Power & Communication Conduits -

Air discharge grille flange -

Air suction flange -

8 Hook Use M8~M10 bolt(4ea)


5. Center of Gravity
Duct

(Unit: mm)

Model A B C D E F

AM160DNMPKH/EU 700 [27-9/16] 265 [10-7/16] 1300 [51-3/16] 625 [24-39/64] 300 [11-13/16] 150 [5-15/16]
6. Electrical Wiring Diagram
Duct

AM160DNMPKH/EU

F100/F101 Fuse M-BLDC Motor for indoor Fan DISPLAY LED display

Contact output port Contact output port for EEPROM SUB PBA
ERROR CHECK COMP CHECK EEPROM
for error check compressor operation check

SUB PBA for wired remote Contact output port Thermistor


2WIRE-SUB VENTILATOR ROOM TEMP
control communication for Ventilator control (ROOM_10Kohm)

DISCHARGE TEMP Thermistor (DISCHARGE_10Kohm) EVA IN TEMP Thermistor (EVA IN_10Kohm) EVA OUT TEMP Thermistor (EVA OUT_10Kohm)

EEV Electronic expansion valve EXTERNAL CTRL Input port for external contact control

NOTE
• This wiring diagram applies only to the Indoor unit.
• Symbols show as follow :
BLK: black, RED: red, BLU: blue, WHT white, YEL: yellow, BRN: brown, SKY: skyblue: GRN: green
• For connection wiring indoor-outdoor transmission F1-F2, indoor-wired remote controller transmission F3-F4.
• Protective earth(screw), : connector, : The wire quantity
7. Sound Data
Duct

Sound pressure level

Unit: dB(A)
Discharge Suction
Model High Mid Low
Duct Duct AM160DNMPKH/EU 43 39 35
2m 2m
1.5m

Microphone

• NR Curve
1) AM160DNMPKH/EU
70 70
65 65
60 60
Sound Pressure Level (dB)

55 NR 60 55
50 NR 55 50
45 NR 50 45
40 40
NR 45
35 35
NR 40
30 30
NR 35
25 25
NR 30
20 20
NR 25
15 15
NR 20
10 10
Hearing threshold NR 15
5 5
0 0
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency(Hz)

NOTE
• Specifications may be subject to change without prior notice.
- Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A weighted sound pressure level
- Reference acoustic pressure 0 dB = 20μPa
7. Sound Data
Duct

Sound Power level

NOTE Unit: dB(A)

• Specifications may be subject to change without prior notice Model Power


- Sound power level is an absolute value that a sound source AM160DNMPKH/EU 65
generates.
- dBA = A-weighted sound power level.
- Reference power : 1pW.
- Measured according to ISO 3741.

• NR Curve
AM160DNMPKH/EU
90 90
85 85
80 80
75 75
Sound Power Level (dB)

70 70
65 65
60 60
55 NR 60
55
50 NR 55
50
45 NR 50
45
40 40
NR 45
35 35
NR 40
30 30
NR 35
25 25
NR 30
20 20
NR 25
15 15
NR 20
10 10
5 NR 15 5
0 0
125 250 500 1000 2000 4000 8000 A
Octave Band Center Frequency(Hz)
8. Fan Characteristics
Duct

1) AM160DNMPKH/EU

External Static Pressure(mmAq) Option Code External Static Pressure(mmAq) Option Code
1 2
0≤SP≤5.2 010054-1E54B9-20A0A0-331120 5.2<SP≤8 010054-1E580A-20A0A0-331120

19 19

18 18

17 17

16 16
HIGH

External Static Pressure [mmAq]


External Static Pressure [mmAq]

15 15

14 14

13 13
HIGH 12
12

11 11

10 10
MIDDLE
9 9
MIDDLE Upper limit of
8 8
external 2
7 Upper limit of 7
external static pressure
6 6
static pressure 1
5 5
LOW LOW
4 4

3 3

2 Lower limit of 2
Lower limit of
external 1
external
1
static pressure static pressure
0 0
20 25 30 35 40 45 50 55 60 20 25 30 35 40 45 50 55 60

Air Flow Rate [CMM] Air Flow Rate [CMM]

External Static Pressure(mmAq) Option Code External Static Pressure(mmAq) Option Code
3 4
8<SP≤12 010054-1E583C-20A0A0-331120 12<SP≤14 010054-1E586D-20A0A0-331120
19
HIGH 19
18
18
17
17
16 HIGH
16
External Static Pressure [mmAq]

External Static Pressure [mmAq]

15
15
14
14 4
13 MIDDLE
13
MIDDLE Upper limit of
12
Upper limit of 3 12
11
external
external 11
static pressure
10
static pressure 10
9 9
8 8
7 7 Lower limit of
6 LOW external
6
LOW static pressure
5 5
4 4
3 Lower limit of 3
2 external 2
1 static pressure 1
0 0
20 25 30 35 40 45 50 55 60 20 25 30 35 40 45 50 55 60

Air Flow Rate [CMM] Air Flow Rate [CMM]

External Static Pressure(mmAq) Option Code


5
14<SP≤15 010054-1E589E-20A0A0-331120
19

18

17
HIGH
16
5
External Static Pressure [mmAq]

15

14
MIDDLE Upper limit of
13
external
12 static pressure
11

10

7
LOW
6 Lower limit of
5 external
4 static pressure
3

0
20 25 30 35 40 45 50 55 60

Air Flow Rate [CMM]


9. Piping Diagram
Duct

EEV included Model

Filter

Electronic Expansion Valve


- Indoor (E_ID)

Filter
(T_II)
Thermistor-RoomAirout
Termistor - IDU Heat Exchanger In (T_AO)

Thermistor- Indoor Room


(T-IR)
Heat Exchanger - Indoor unit
(HX_ID)

Liquid pipe Motor for Indoor Fan


connection port (IFM)
ØA Thermistor - IDU Heat Exchanger Out
(T_IO)

Gas pipe
connection port
ØB

Refrigerant flow
Cooling Heating

Unit : mm (inch)
Model A B
AM160DNMDKH1TK 9.52 (3/8) 15.88 (5/8)
10. Installation
Duct

Indoor Unit
• There must be no obstacles near the air inlet and outlet.
• Install the indoor unit on a ceiling that can support its weight.
• Maintain sufficient clearance around the indoor unit.
• Make sure that the water dripping from the drain hose runs away correctly and safely.
• The indoor unit must be installed in this way, that they are out of public access. (Not touchable by the users)
• After connecting a chamber, insulate the connection part between the indoor unit and the chamber with t10 or thicker
insulation. Otherwise, there can be air leak or dew from the connection part.
• Rigid wall without vibration.
• Where it is not exposed to direct sunshine.
• Where the air filter can be removed and cleaned easily.

Space requirements for installation & service


• C
 onstruction Standard for Inspection Hole.
1) In case, the ceiling is textile, Inspection hole dose not need.
2) In case, the ceiling is plaster board, Inspection hole depends on Inside height of the ceiling.
a. Height is more than 0.5m : Only “B” [Inspection for PBA] is applied.
b. Height is less than 0.5m : Both “A” & ”B” are applied.
c. “A” & ”B” are inspection holes.
Unit Depth(D)

20mm or more

Unit Width(W)
20mm or more
“A”=W+100mm “B”=500mm

• You must have 20mm or more space between the ceiling and the bottom of indoor unit. Otherwise, the noise from the
vibration of indoor unit may bother the user.When the ceiling is under construction, the hole for check-up must be made to
take service, clean and repair the unit.
• It is possible to install the unit at an height of between 2.2~2.5m from the ground, if the unit has a duct with a well defined
lenght (300mm or more), to avoid fan motor blower contact.
• If you install the cassette or duct type indoor unit on the ceiling with humidity over 80%, you must apply extra
• 10mm of polyethylene foam or other insulation with similar material on the body of the indoor unit.

Insulation Guide
• I nsulate the end of the pipe and some curved area by using separate insulator.
• I nsulate the discharge and suction part at the same time when you insulate connection duct.
• If the humidity is over 80%, it is required to add 10mm polyethylene foam or other similar insulation to the indoor unit when
installing belt or pipe type indoor unit on the ceiling.
D B
Back

Front

A C
10. Installation
Duct

Indoor unit A B C D Front / Back

Insulate the front and


back side in proper size
AM160DNMPKH/EU 1300x700x300 1300x300 1300x300 700x300 700x300 at the same time when
insulating the suction
duct and discharge duct.

• Insulate the end of the pipe and some curved area by using separate insulator.
• Insulate the discharge and suction part at the same time when you insulate connection duct.
• If the humidity is over 80%, it is required to add 10mm polyethylene foam or other similar insulation to the indoor unit
when installing belt or pipe type indoor unit on the ceiling.

Drainpipe Connection
Without the drain pump

1 Install horizontal drainpipe with a slope of 1/100 or more and fix it by hanger space of 1.0~1.5m.
2 Install U-trap at the end of the drainpipe to prevent a nasty smell to reach the indoor unit.
3 Do not install the drainpipe to upward position. It may cause water flow back to the unit.

1~1.5m
Hanger

Flexible hose

Horizontal drainpipe
Ceiling more than 1/100 slope

With the drain pump

1 The drain pipe should be installed within 300mm to 550mm from the flexible hose and then lift down 20mm or more.
2 Install horizontal drainpipe with a slope of 1/100 or more and fix it by hanger space of 1.0~1.5m.
3 Install the air vent in the horizontal drainpipe to prevent water flow back to the indoor unit.

NOTE
• You may not need to install it if there were proper slope in the horizontal drainpipe.

4 The flexible hose should not be installed upward position, it may cause water flow back to the indoor unit.

Air vent 1~1.5m


200mm
300mm or less or more Hanger
20mm
or more
Flexible hose
Within
300~550mm
Horizontal drainpipe
more than 1/100 slope

Ceiling
10. Installation
Duct

Centralized Drainage
Without the drain pump

1 Install horizontal drainpipe with a slope of 1/100 or more and fix it by hanger space of 1.0~1.5m.
2 Install U-trap at the end of the drainpipe to prevent a nasty smell to reach the indoor unit.
100mm or more

Horizontal drainpipe
Ceiling more than 1/100 slope

With the drain pump

1 Install main air vent at the front of the farthest indoor unit from the main drain when installed indoor units are more than 3.
2 You may need to install individual air vent to prevent water flow back at the top of each indoor unit drainpipe.

Hanger 1~1.5m
Main air vent
Individual
air vent
550mm or
less

Main drainpipe Centralized horizontal drainpipe


(more than 1/100 slope)

Testing the drainage


Prepare a little water about 2 liter.

1 pour water into the base pan in the indoor unit as shown in figure.
2 Confirm that the water flows out through the drain hose.

Power and communication cable connection


1 Before wiring work, you must turn off all power source.
2 Indoor unit power should be supplied through the breaker( ELCB or MCCB+ELB ) separated by the outdoor power.
ELCB:Earth Leakage Circuit Breaker
MCCB:Molded Case Circuit Breaker
ELB:Earth Leakage Breaker
3 The power cable should be used only copper wires.
4 Connect the power cable{1(L), 2(N)} among the units within maximum length and communication cable(F1, F2) each.
5 Connect F3, F4(for communication) when installing the wired remote control.
10. Installation
Duct

Outdoor Unit

Wired Remote
Control

220-240V~
or
MCCB+ ELCB
ELB

V1 V2

EEV kit
L N

Indoor Unit 1 Indoor Unit 2 Indoor Unit 3 N L N L N L

 ELCB : Essential Installation


WARNING :
Power off before connecting any wires;
Indoor PBA will be damaged while V1,V2,F3,F4 short each Indoor Unit 4 Indoor Unit 5 Indoor Unit 6
other.  Ceiling, wall-mounted indoor unit.

Specification of electronic wire


Power supply MCCB ELB or ELCB Power cable Earth cable Communication cable
Max : 242V X A, 30mmA
XA 2.5mm² 2.5mm² 0.75~1.5mm²
Min : 198V 0.1 s

• Decide the capacity of ELCB(or MCCB+ELB) by below formula.


• Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord.
(Code designation IEC:60245 IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC 66 / CENELEC: H07RN-F )

The capacity of ELCB(or MCCB+ELB) X [A] = 1.25 X 1.1 X ΣAi

− X : The capacity of ELCB(or MCCB+ELB).


− ΣAi : Sum of Rating currents of each indoor unit.
− Refer to each installation manual about the rating current of indoor unit.
• Decide the power cable specification and maximum length within 10% power drop among indoor units.

n Coef×35.6×Lk×ik
Σ( ) < 10% of input voltage[V]
k=1 1000×Ak

• coef: 1.55
• Lk: Distance among each indoor unit[m], Ak: Power cable specification[mm²]
ik: Running current of each unit[A]
10. Installation
Duct

Example of Installation

− Total power cable length L = 100(m), Running current of each units 1[A]
− Total 10 indoor units were installed

10[A] 9[A] 1[A]


ELCB
or MCCB+
ELB
Indoor unit1 Indoor unit2 Indoor unit10

0[m] 10[m] 20[m] 100[m]

• Apply following equation.

n Coef×35.6×Lk×ik
Σ( ) < 10% of input voltage[V]
k=1 1000×Ak

• Calculation
− Installing with 1 sort wire.
2.5[mm²] 2.5[mm²] 2.5[mm²]

-2.2[V] -2.0[V]
208.8[V](Within 198V~242V)
220[V]
-(2.2+2.0+1.8+1.5+1.3+1.1+0.9+0.7+0.4+0.2)=-11.2[V] it's okay

− Installing with 2 different sort wire.

4.0[mm²] 4.0[mm²] 2.5[mm²]

-1.4[V] -1.2[V]
209.5[V](Within 198V~242V)
220[V]
-(1.4+1.2+1.8+1.5+1.3+1.1+0.9+0.7+0.4+0.2)=-10.5[V] it's okay

Rating current

Unit Model Rating current

AM*DNMPKH* *160* 2.45A


10. Installation
Duct

CAUTION
• Select the power cable in accordance with relevant local and national regulations.
• Wire size must comply with local and national code.
• For the power cable, use the grade of H07RN-F or H05RN-F materials.
• You should connect the power cable into the power cable terminal and fasten it with a clamp.
• The unbalanced power must be maintained within 10% of supply rating among whole indoor units.
• If the power is unbalanced greatly, it may shorten the life of the condenser. If the unbalanced power is exceeded over 10% of
supply rating, the indoor unit is protected, stopped and the error mode indicates.
• To protect the product from water and possible shock, you should keep the power cable and the connection cord of the indoor
and outdoor units in the iron pipe.
• Connect the power cable to the auxiliary circuit breaker.
• An all pole disconnection from the power supply must be incorporated in the fixed wiring(≥3mm).
• You must keep the cable in a protection tube.
• Keep distances of 50mm or more between power cable and communication cable.
• Maximum length of power cables are decided within 10% of power drop. If it exceeds, you must consider another power
supplying method.
• The circuit breaker(ELCB or MCCB+ELB) should be considered more capacity if many indoor units are connected from one
breaker.
• Use round pressure terminal for connections to the power terminal block.
• For wiring, use the designated power cable and connect it firmly, then secure to prevent outside pressure being exerted on the
terminal board.
• Use an appropriate screwdriver for tightening the terminal screws. A screwdriver with a small head will strip the head and
make proper tightening impossible.
• Over-tightening the terminal screws may break them.
• See the table below for tightening torque for the terminal screws.

Tightening torque
N•m kgf•cm
M3.5 0.8~1.0 8.0~10.0
M4 1.2~1.5 12.0~14.7
2023.10
Ver.1.0
Samsung Electronics Co., LTD.