Chapter 6 - Duct Design and Sizing
Chapter 6 - Duct Design and Sizing
1. Minor losses (Dynamic Losses in Fittings) such as elbows, connectors, dividers, …. Diameter
𝒇𝒇
inch mm
Whenever a change in area or direction occurs in a duct or when the flow is 4 10 0.035
divided or diverted into a branch, substantial losses in total pressure will occur. 6 15 0.028
8 20 0.023
These losses are usually of greater magnitude than the losses in the straight pipe 10 25 0.022
and are referred to as dynamic losses defined as: 12 30 0.019
𝐿𝐿𝑒𝑒 14 36 0.017
�
𝑉𝑉 2 𝐶𝐶𝑜𝑜 = 𝑓𝑓 ≡ Loss coefficient where
𝐶𝐶𝑜𝑜 � � ← (𝑖𝑖𝑖𝑖𝑖𝑖ℎ 𝑜𝑜𝑜𝑜 𝑤𝑤𝑤𝑤) 𝐷𝐷 16 40 0.016
4005
𝑉𝑉𝑉𝑉 ≡ 𝑃𝑃𝑑𝑑 = � 𝐿𝐿𝑒𝑒 ≡ Equivalent length (table 6.2) 20 50 0.015
� 2
𝑉𝑉
𝐶𝐶𝑜𝑜 � � ← (𝑃𝑃𝑃𝑃) 𝑓𝑓 ≡ The friction factor (table 6.1) 24 60 0.014
1.29
ASHRAE classified the fittings as either constant-flow (i.e. elbows or transitions) or as divided flow
(i.e. wye or tee). Tables 6.5 through 6.10 give "𝐶𝐶𝑜𝑜 " for different types of constant-flow fittings (see
bb). You may also consult ASHRAE codes for "𝐶𝐶𝑜𝑜 " for different fittings.
2. Major losses (pressure drop due to friction in duct, ∆𝑃𝑃𝑓𝑓 ):
This pressure loss can be found from Moody chart, however, ASHRAE prepared friction charts for
fully developed air flow in galvanized steel (Figures 6.3 and 6.4). These charts provide frictional
pressure drop per unit length of the duct.
Known specs:
• The fan specs are usually known before duct sizing. Meaning, 𝑆𝑆𝑆𝑆𝑓𝑓𝑓𝑓𝑓𝑓 is available from the catalogue.
• 𝑐𝑐𝑐𝑐𝑐𝑐 can be found from the cooling or heating loads.
• ∆𝑃𝑃𝑙𝑙𝑙𝑙𝑙𝑙𝑙𝑙𝑙𝑙𝑙𝑙 of all components of the system (coils, dampers, filters, …) are also known from manufacturers.
2
Thus, ∆𝑃𝑃𝑙𝑙𝑙𝑙𝑙𝑙𝑙𝑙𝑙𝑙𝑙𝑙 for the supply and return ducts can then be calculated:
𝑇𝑇𝑇𝑇𝑓𝑓𝑓𝑓𝑓𝑓 ≥ �∆𝑃𝑃𝑓𝑓,𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑 + ∑ ∆𝑃𝑃𝑙𝑙𝑙𝑙𝑙𝑙𝑙𝑙𝑙𝑙𝑙𝑙 � = ∆𝑃𝑃𝑓𝑓,𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑 + ∑ 𝑉𝑉𝑉𝑉𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓 + ∑ 𝑃𝑃𝑑𝑑,𝑒𝑒𝑒𝑒𝑒𝑒𝑒𝑒𝑒𝑒 + ∆𝑃𝑃𝑅𝑅𝑅𝑅𝑅𝑅𝑅𝑅𝑅𝑅𝑅𝑅 where
∆𝑃𝑃𝑓𝑓
∆𝑃𝑃𝑓𝑓,𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑 = � � 𝐿𝐿𝑒𝑒𝑒𝑒𝑒𝑒 where 𝐿𝐿𝑒𝑒𝑒𝑒𝑒𝑒 ≡ Effective length = 𝐿𝐿𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑 + 𝐿𝐿𝑒𝑒
𝐿𝐿
𝐿𝐿𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑 ≡ Actual duct length 𝐿𝐿𝑒𝑒 = equivalent length of fittings (table 6.2)
∆𝑃𝑃𝑓𝑓,𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑 = Frictional pressure drop due to friction in the duct (see tables 6-5 to 6-10).
Applications Methods 4
Equal Friction loss method.
Low and medium Velocity-reduction method
Pressure systems Balanced Capacity method AHU
Fan
(Equal pressure drop method)
large pressure system Static regain method
Figure A
4
∆𝑷𝑷𝒇𝒇
1. Equal Friction Loss Method, .
𝑳𝑳
It can be used for all types of systems including small, light commercial, as well as large VAV systems. It is
straightforward method and easy to use. It gives an automatic reduction of the air velocity throughout the
system, which remains in general within the noise limits of the application.
This method makes the frictional pressure loss per foot of duct length the same for the entire system. If the
layout is symmetrical (all runs from fan to diffuser are approximately the same length), this method will
produce a good balanced design. However, most duct systems have a variety of duct runs ranging from
long to short. The short runs will have to be dampered in order to balance the flow rate to avoid noise.
pressure loss in the longest run including all fittings and transitions.
Steps:
• Compute the flow rate in the main duct, 𝑄𝑄𝐴𝐴 : 𝑄𝑄𝐴𝐴 = ∑𝑁𝑁
𝑖𝑖=1 𝑄𝑄𝑖𝑖 = 𝑄𝑄1 + 𝑄𝑄2 + 𝑄𝑄3 + 𝑄𝑄4 + ⋯
• Determine ∆𝑃𝑃𝑓𝑓 ⁄𝐿𝐿 of the main duct from the chart. This pressure drop is equal for all ducts.
• Find the diameter of the trunk (duct A), 𝐷𝐷𝐴𝐴 , using one of the following options:
The friction chart
4 𝑄𝑄𝐴𝐴
𝑄𝑄𝐴𝐴 = 𝑉𝑉𝐴𝐴 𝐴𝐴𝐴𝐴 → 𝐷𝐷𝐴𝐴 = �
𝜋𝜋 𝑉𝑉𝐴𝐴
1.852 1⁄4.973
0.022243𝑄𝑄̇
The empirical Hazen-William equation: 𝐷𝐷𝑒𝑒𝑒𝑒,𝐴𝐴 = � �∆𝑃𝑃 ⁄𝐿𝐿𝐴𝐴� �
𝑓𝑓 𝐴𝐴
∆𝑃𝑃𝑓𝑓
• Find 𝐷𝐷𝑒𝑒𝑒𝑒 for all other ducts where = 𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐 for all ducts using the friction charts (fig. 6.3 or 6.4)
𝐿𝐿
Q̇1.852 Q̇1.852 Q̇1.852
or the empirical equation: � 4.973� = � 4.973� = � 4.973 � = ⋯
D D D eq eq eq
A B C
• Calculate the pressure drops for the longest and each run as:
∆𝑃𝑃𝑓𝑓 ∆𝑃𝑃𝑓𝑓
∆𝑃𝑃𝑓𝑓,𝐴𝐴 = � � . 𝐿𝐿 ; ∆𝑃𝑃𝑓𝑓,𝐵𝐵 = � � . 𝐿𝐿 ; …
𝐿𝐿 𝐴𝐴 𝐴𝐴 𝐿𝐿 𝐵𝐵 𝐵𝐵
• Estimate the minor losses (velocity pressure losses, 𝑉𝑉𝑉𝑉) in each duct run based on either:
– Fitting loss factor, Co, or
– Effective length method, 𝐿𝐿𝑒𝑒𝑒𝑒𝑒𝑒
5
• Determine the static head of the fan based on the highest pressure drop.
• Select a suitable fan for the index run (trunk) with the highest-pressure loss.
• Balance the total pressure loss of the ductwork by introducing Dampers to short runs
Note: Ductulator is a computer software that can be used for sizing Table A
∆𝑷𝑷𝒇𝒇 per 100 Feet of Duct
ducts if you know cfm & ∆𝑃𝑃𝑓𝑓 or 𝑉𝑉𝑎𝑎𝑎𝑎𝑎𝑎 in the trunk. Table A shows the System Type
(inch H2O column)
Supply run-outs 0.08 (19.93 Pa)
friction loss for sizing ducts in Ductulator. Supply plenum 0.05 (12.45 Pa)
Return ducts 0.02 (5.0 Pa)
Example:
The following figure shows a typical duct layout. Design the duct system using Equal friction loss method.
The air velocity in the main duct (A) is 8 m/s. Assume 𝐶𝐶𝑜𝑜 = 1.0 for the outlets (diffusers). Find the required
FTP and the amount of dampening in each duct.
Important note: it is assumed 𝐶𝐶𝑜𝑜 = 1.0 for the outlets, however, the correct values are found in chapter 8.
2 m3/s 2 1 m3/s 3
Return
D F
15 m
15 m 12 m 18 m
18 m 66mm
A C E
Fresh air
AHU
Outdoor
&
FAN
B 66mm
WYE 45° WYE 45° 90° Elbow
1 m3/s 1
Solution:
1. Compute 𝑄𝑄𝑡𝑡𝑡𝑡𝑡𝑡 of the main duct: 𝑄𝑄𝑡𝑡𝑡𝑡𝑡𝑡 = 𝑄𝑄𝐴𝐴 = 𝑄𝑄1 + 𝑄𝑄2 + 𝑄𝑄3 = 1 + 2 + 1 = 4 𝑚𝑚3 /𝑠𝑠 and V = 8 m/sec
𝑃𝑃𝑓𝑓,𝐴𝐴
2. in the main duct is found from the friction chart as:
𝐿𝐿
𝑃𝑃𝑓𝑓,𝐴𝐴 𝑃𝑃𝑓𝑓,𝐴𝐴
@ 𝑄𝑄 = 4 𝑚𝑚3 ⁄𝑠𝑠 = 4000 𝐿𝐿⁄𝑠𝑠 & 𝑉𝑉 = 8 𝑚𝑚/𝑠𝑠 → = 0.73 𝑃𝑃𝑃𝑃⁄𝑚𝑚 where is equal for all branches
𝐿𝐿 𝐿𝐿
3. Compute 𝐷𝐷′ 𝑠𝑠 =?
• 𝐷𝐷𝐴𝐴 =? can be calculated or read from the same figure:
𝑄𝑄 4
𝑄𝑄𝐴𝐴 = 𝑉𝑉𝐴𝐴 . 𝐴𝐴𝐴𝐴 → 𝐴𝐴 = = = 0.5 𝑚𝑚2 → 𝐷𝐷𝐴𝐴 = 0.798 𝑚𝑚 (or from chart, 𝐷𝐷𝐴𝐴 = 0.80 m)
𝑉𝑉 8
6
Friction loss, Pa/m
≈ 𝟎𝟎. 𝟕𝟕𝟕𝟕 𝑷𝑷𝑷𝑷⁄𝒎𝒎
∆𝑷𝑷𝒇𝒇,𝑨𝑨𝑨𝑨
𝑳𝑳
A C E
FAN B 66 m
m
• For supply ducts, an initial guess for the velocity is needed (taken from the table below). This
velocity should be fairly high because it will get progressively Recommended Velocity (m/s)
For supply and return - ASHRAE
smaller at the branch takeoffs. This is the reason it is called Residences Hotels Schools
Main supply 5 6 7.5
“velocity-reduction method”.
Main return 4 5 6
Steps of calculation: Branch supply 3 4 6
Branch return 3 4 5
1. Select velocities in the main and branch ducts from the table.
2. Find "𝐷𝐷" of the main and branches from 𝑐𝑐𝑐𝑐𝑐𝑐 or figures 6.3 or figure 6.4.
3. From "𝑉𝑉" & "𝐷𝐷" obtained, find ∆𝑃𝑃𝑓𝑓 ⁄𝐿𝐿 for the main and branch ducts from figures 6.3 or figure 6.4.
4. Find ∆𝑃𝑃 due to minor losses using ∑ 𝑉𝑉𝑉𝑉𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓 for all fittings.
5. Select a fan that can provide sufficient 𝑆𝑆𝑆𝑆 for the index run.
6. Balancing dampers have to be installed in each run. The damper in the index run is left completely
open, while the other dampers are throttled to reduce 𝑐𝑐𝑐𝑐𝑐𝑐 of each room to the required value.
Advantages and disadvantages of the velocity-reduction method:
It can be used for both supply and return air-ducts. However, selection of suitable velocities in different
duct runs requires experience. Wrong selection of velocities can lead to very large ducts, which leads to
occupying large space in the building and increases the cost. If your selection of velocities led to very small
ducts, it will result in large pressure drop and hence necessitates the selection of a large fan leading to
higher fan cost and running cost.
8
Example: Apply the “velocity-reduction” method to the previous example.
2 m3/s 2 1 m3/s 3
Return
D F
Outside Fresh air 15 m 12 m 18 m 66m
m
AHU A C E
+
FAN
B 66 m
m
90° Elbow
WYE 45° WYE 45°
Solution: 1 m3/s 1
1. Select the velocities: 𝑉𝑉 = 5 𝑚𝑚/𝑠𝑠 for the downstream branches while 𝑉𝑉𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚 remains 8 m/sec.
2. Find the diameters:
Segment A: 𝑄𝑄𝐴𝐴 = 4 𝑚𝑚3 /𝑠𝑠 & 𝑉𝑉𝐴𝐴 = 8𝑚𝑚/𝑠𝑠 → 𝐴𝐴𝐴𝐴 = 𝑄𝑄𝐴𝐴 ⁄𝑉𝑉𝐴𝐴 = 0.5 𝑚𝑚2 → 𝐷𝐷𝐴𝐴 = 0.798 𝑚𝑚
Segment B: 𝑄𝑄𝐵𝐵 = 1 𝑚𝑚3 /𝑠𝑠 & 𝑉𝑉𝐵𝐵 = 5𝑚𝑚/𝑠𝑠 → 𝐴𝐴𝐵𝐵 = 𝑄𝑄𝐵𝐵 ⁄𝑉𝑉𝐵𝐵 = 0.2 𝑚𝑚2 → 𝐷𝐷𝐵𝐵 = 0.505 𝑚𝑚
Segment C: 𝑄𝑄𝐶𝐶 = 3 𝑚𝑚3 /𝑠𝑠 & 𝑉𝑉𝐶𝐶 = 5𝑚𝑚/𝑠𝑠 → 𝐴𝐴𝐶𝐶 = 𝑄𝑄𝐶𝐶 ⁄𝑉𝑉𝐶𝐶 = 0.6 𝑚𝑚2 → 𝐷𝐷𝐶𝐶 = 0.874 𝑚𝑚
Segment D: 𝑄𝑄𝐷𝐷 = 2 𝑚𝑚3 /𝑠𝑠 & 𝑉𝑉𝐶𝐶 = 5𝑚𝑚/𝑠𝑠 → 𝐴𝐴𝐷𝐷 = 𝑄𝑄𝐷𝐷 ⁄𝑉𝑉𝐷𝐷 = 0.4 𝑚𝑚2 → 𝐷𝐷𝐷𝐷 = 0.714 𝑚𝑚
Segments E&F: 𝑄𝑄𝐸𝐸&𝐹𝐹 = 1 𝑚𝑚3 /𝑠𝑠 & 𝑉𝑉𝐸𝐸&𝐹𝐹 = 5𝑚𝑚/𝑠𝑠 → 𝐴𝐴𝐸𝐸&𝐹𝐹 = 𝑄𝑄𝐸𝐸&𝐹𝐹 ⁄𝑉𝑉𝐸𝐸&𝐹𝐹 = 0.2 𝑚𝑚2 → 𝐷𝐷𝐸𝐸&𝐹𝐹 = 0.505 𝑚𝑚
𝜌𝜌𝑉𝑉𝐷𝐷2 1.2×52
The velocity pressure drop from upstream to branch: 𝑉𝑉𝑉𝑉𝑏𝑏 = 𝐶𝐶𝑏𝑏 � � = 0.515 � � = 7.73 𝑃𝑃𝑃𝑃
2 2
𝜌𝜌𝑉𝑉𝐷𝐷2 1.2×52
The velocity pressure loss at the outlet 1: ∆𝑉𝑉𝑉𝑉𝑔𝑔𝑔𝑔𝑔𝑔𝑔𝑔𝑔𝑔(1) = 𝐶𝐶𝑒𝑒𝑒𝑒𝑒𝑒𝑒𝑒 � � = 1.0 � � = 15.0 𝑃𝑃𝑃𝑃
2 2
Therefore, ∆𝑷𝑷𝑨𝑨−𝑩𝑩 = 𝟏𝟏𝟏𝟏. 𝟑𝟑𝟑𝟑 + 𝟑𝟑. 𝟗𝟗𝟗𝟗 + 𝟏𝟏𝟏𝟏. 𝟎𝟎 + 𝟕𝟕. 𝟕𝟕𝟕𝟕 = 𝟑𝟑𝟑𝟑. 𝟏𝟏𝟏𝟏 𝑷𝑷𝑷𝑷
Section A-C-D:
∆𝑷𝑷𝑨𝑨−𝑪𝑪−𝑫𝑫 = ∆𝑃𝑃𝐴𝐴,𝑓𝑓 + ∆𝑃𝑃𝐶𝐶,𝑓𝑓 + ∆𝑃𝑃𝐷𝐷,𝑓𝑓 + ∆𝑃𝑃𝑢𝑢−𝐵𝐵 + ∆𝑃𝑃𝑢𝑢−𝐷𝐷 + ∆𝑃𝑃𝑒𝑒𝑒𝑒𝑒𝑒𝑒𝑒,𝑔𝑔𝑔𝑔𝑔𝑔𝑔𝑔𝑔𝑔(2) ≈ 51.41 𝑃𝑃𝑃𝑃
Section A-C-E-F:
∆𝑷𝑷𝑨𝑨−𝑪𝑪−𝑬𝑬−𝑭𝑭 = ∆𝑃𝑃𝐴𝐴,𝑓𝑓 + ∆𝑃𝑃𝐶𝐶,𝑓𝑓 + ∆𝑃𝑃𝐸𝐸,𝑓𝑓 + ∆𝑃𝑃𝐹𝐹,𝑓𝑓 + ∆𝑃𝑃𝑢𝑢−𝐷𝐷,𝐶𝐶 + ∆𝑃𝑃𝑢𝑢−𝐷𝐷,𝐸𝐸 + ∆𝑃𝑃𝑒𝑒𝑒𝑒𝑒𝑒𝑒𝑒𝑒𝑒 + ∆𝑃𝑃𝑒𝑒𝑒𝑒𝑒𝑒𝑒𝑒 ≈ 69.3 𝑃𝑃𝑃𝑃.
This is the “index run” where the total pressure 𝑭𝑭𝑭𝑭𝑭𝑭 = 𝟔𝟔𝟔𝟔. 𝟑𝟑 𝑷𝑷𝑷𝑷 = 𝟎𝟎. 𝟐𝟐𝟐𝟐𝟐𝟐 𝒊𝒊𝒊𝒊. 𝒘𝒘𝒘𝒘
4. Dampering (balancing):
Amount of dampering required at 1 = 𝐹𝐹𝐹𝐹𝐹𝐹 − ∆𝑃𝑃𝐴𝐴−𝐵𝐵 = 32.24 𝑃𝑃𝑃𝑃 = 0.13 𝑖𝑖𝑖𝑖. 𝑤𝑤𝑤𝑤
Amount of dampering required at 2 = 𝐹𝐹𝐹𝐹𝐹𝐹 − ∆𝑃𝑃𝐴𝐴−𝐶𝐶−𝐷𝐷 = 18.0 𝑃𝑃𝑃𝑃 = 0.072 𝑖𝑖𝑖𝑖. 𝑤𝑤𝑤𝑤
Notes: A damper is selected (purchased) based on its ∆𝑃𝑃 & 𝑉𝑉𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑 . It can be manual or motorized.
9
Conclusion and caution:
a) The Velocity method results in larger “D” due to the velocities selected in branches & downstream.
This leads to lower FTP (small fan).
b) The Equal Friction method results in smaller “D” but larger FTP (large fan).
c) The velocity reduction method requires less dampering at outlet 1 but more at outlet 2.
2
4
AHU 1 3
+
FAN
5
The main idea:
This method requires that the flow rate to each room be balanced. As a result, the loss in total pressure
automatically balances, regardless of the duct sizes. Hence, the loss in total pressure is required to be equal
for all duct runs starting from the fan to each outlet knowing cfm to each run. In general, each run has a
different 𝐿𝐿𝑒𝑒 resulting in different pressure loss per unit length for each run.
𝐿𝐿𝑒𝑒
∆𝑃𝑃𝑓𝑓 = ∆𝑃𝑃𝑓𝑓 (𝑐𝑐𝑐𝑐𝑐𝑐, 𝐿𝐿𝑒𝑒 ) = 𝑓𝑓 𝑃𝑃𝑉𝑉 = 𝑇𝑇𝑇𝑇1 − 𝑇𝑇𝑇𝑇2
𝐷𝐷
This equation states that for a given 𝐿𝐿𝑒𝑒 , "𝐷𝐷" can always be adjusted to obtain the necessary cfm (velocity)
that will produce the required loss in total pressure. Thus, the use of equivalent lengths for the fittings is the
only limitation of this method.
10
Solution:
1. Flow rates: 𝑄𝑄̇𝐵𝐵𝐵𝐵 = 0.2 + 1.1 = 1.3 𝑚𝑚3 /𝑠𝑠𝑠𝑠𝑠𝑠 and 𝑄𝑄̇𝐴𝐴𝐴𝐴 = 0.6 + 1.3 = 1.9 𝑚𝑚3 /𝑠𝑠𝑠𝑠𝑠𝑠
4𝑄𝑄 4 𝑥𝑥 1.9
Given 𝑉𝑉𝑚𝑚𝑚𝑚𝑚𝑚 = 𝑉𝑉𝐴𝐴𝐴𝐴 = 5 𝑚𝑚/𝑠𝑠 → 𝑄𝑄𝐴𝐴𝐴𝐴 = 𝑉𝑉𝐴𝐴𝐴𝐴 × 𝐴𝐴𝐴𝐴𝐴𝐴 → 𝐷𝐷𝐴𝐴𝐴𝐴 = � 𝐴𝐴𝐴𝐴 = � = 0.696 𝑚𝑚
𝜋𝜋 𝑉𝑉 𝜋𝜋 𝑥𝑥 5 𝐴𝐴𝐴𝐴
∆𝑷𝑷𝑨𝑨𝑨𝑨
2. Calculate and diameters:
𝑳𝑳
∆𝑃𝑃𝐴𝐴𝐴𝐴
From chart @ 𝑄𝑄𝐴𝐴𝐴𝐴 = 1.9 𝑚𝑚3 /𝑠𝑠 & 𝑉𝑉𝐴𝐴𝐴𝐴 = 5 𝑚𝑚/𝑠𝑠 → from chart: = 0.36 𝑃𝑃𝑃𝑃/𝑚𝑚 & 𝐷𝐷𝐴𝐴𝐴𝐴 = 0.70 𝑚𝑚
𝐿𝐿
∆𝑃𝑃𝐴𝐴𝐴𝐴
This method requires balancing = 0.36 𝑃𝑃𝑃𝑃/𝑚𝑚 for all other ducts:
𝐿𝐿
∆𝑃𝑃𝐵𝐵𝐵𝐵
Duct BC: @ 𝑄𝑄 = 1.3 𝑚𝑚3 /𝑠𝑠 & = 0.36 𝑃𝑃𝑃𝑃/𝑚𝑚 → 𝐷𝐷𝐵𝐵𝐵𝐵 = 0.61 𝑚𝑚 & 𝑉𝑉𝐵𝐵𝐵𝐵 = 4.6 𝑚𝑚/𝑠𝑠
𝐿𝐿
∆𝑃𝑃𝐶𝐶𝐶𝐶
Duct CD: @ 𝑄𝑄 = 1.1 𝑚𝑚3 /𝑠𝑠 & = 0.36 𝑃𝑃𝑃𝑃/𝑚𝑚 → 𝐷𝐷𝐶𝐶𝐶𝐶 = 0.56 𝑚𝑚 & 𝑉𝑉𝐶𝐶𝐶𝐶 = 4.4 𝑚𝑚/𝑠𝑠
𝐿𝐿
∆𝑃𝑃𝐶𝐶𝐶𝐶
Duct CF: @ 𝑄𝑄 = 0.2 𝑚𝑚3 /𝑠𝑠 & = 0.36 𝑃𝑃𝑃𝑃/𝑚𝑚 → 𝐷𝐷𝐶𝐶𝐶𝐶 = 0.29 𝑚𝑚 & 𝑉𝑉𝐶𝐶𝐶𝐶 = 2.9 𝑚𝑚/𝑠𝑠
𝐿𝐿
∆𝑃𝑃𝐵𝐵𝐵𝐵
Duct BE: @ 𝑄𝑄 = 0.6 𝑚𝑚3 /𝑠𝑠 & = 0.36 𝑃𝑃𝑃𝑃/𝑚𝑚 → 𝐷𝐷𝐵𝐵𝐵𝐵 = 0.45 𝑚𝑚 & 𝑉𝑉𝐵𝐵𝐵𝐵 = 3.8 𝑚𝑚/𝑠𝑠
𝐿𝐿
∆𝑃𝑃𝐴𝐴𝐴𝐴
Note: This method forces the main pressure drop � = 0.36 𝑃𝑃𝑃𝑃/𝑚𝑚� equals for each duct run which
𝐿𝐿
causes an unbalanced system. Thus, it is very important and vital to balance the ductwork. This is done
by considering all losses in the system as well as using dampers in branches to balance 𝑐𝑐𝑐𝑐𝑐𝑐. This is
carried out by first calculating the pressure drops for each duct in the system.
𝐿𝐿𝑒𝑒 𝐿𝐿
∆𝑃𝑃𝐶𝐶𝐶𝐶 ≠ ∆𝑃𝑃𝐶𝐶𝐶𝐶
� = 20 → 𝐿𝐿𝑒𝑒,𝑏𝑏𝑏𝑏𝑏𝑏𝑏𝑏𝑏𝑏ℎ = � 𝑒𝑒� � 𝐷𝐷𝐶𝐶𝐶𝐶 = 20 x 0.29 = 5.8 m
𝐷𝐷 𝑏𝑏𝑏𝑏𝑏𝑏𝑏𝑏𝑏𝑏ℎ 𝐷𝐷 𝑏𝑏𝑏𝑏𝑏𝑏𝑏𝑏𝑏𝑏ℎ
∆𝑃𝑃
So 𝐿𝐿𝑒𝑒𝑒𝑒𝑒𝑒 = 4 + 5.8 = 9.8 m → ∆𝑃𝑃𝐶𝐶𝐶𝐶 = � � 𝐿𝐿𝑒𝑒𝑒𝑒𝑒𝑒 = 0.36 × 9.8 = 3.53 𝑃𝑃𝑃𝑃
𝐿𝐿𝑒𝑒
Changing the length or diameter of the duct CD since ∆𝑃𝑃𝐶𝐶𝐶𝐶 < ∆𝑃𝑃𝐶𝐶𝐶𝐶 or
Introducing a damper to duct CD.
The easiest way is to introduce a damper → (∆𝑃𝑃𝐶𝐶𝐶𝐶 )𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷 = ∆𝑃𝑃𝐶𝐶𝐶𝐶 − ∆𝑃𝑃𝐶𝐶𝐶𝐶 = 3.53 − 3.456 = 0.078 𝑃𝑃𝑃𝑃
11
Ducts B-C and B-E: similarly, (∆𝑃𝑃𝐵𝐵𝐵𝐵 )𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷𝐷 = ∆𝑃𝑃𝐵𝐵𝐵𝐵 − ∆𝑃𝑃𝐵𝐵𝐵𝐵 = 9.54 − 7.56 = 1.98 𝑃𝑃𝑃𝑃
Therefore, the system requires 2 dampers, one in duct CD and another in duct BE. Further, duct CF is the
index run (the highest losses before the addition of dampers). Thus, the FTP may be found as:
∆𝑃𝑃
∆𝑃𝑃𝐴𝐴 = ∆𝑃𝑃𝐴𝐴𝐴𝐴 + ∆𝑃𝑃𝐵𝐵𝐵𝐵 where ∆𝑃𝑃𝐴𝐴𝐴𝐴 = � � . 𝐿𝐿𝑒𝑒 = 0.36 × 5 = 1.8 𝑃𝑃𝑃𝑃
𝐿𝐿𝑒𝑒
AHU 5m 6m C 4m D
A
+ 1.10 m3/s
FAN B
4m
Damper CD
0.20 m3/s F
13
PRACTICAL RECOMMENDATIONS & CONSIDERATIONS
The supply duct system
The two most common supply duct are the “extended plenum” and the “radial” systems. The other options
are spider and perimeter loop systems.
Trunk
a) Extended Plenum Systems
It consists of a large main supply trunk of equal
size connected directly to the AHU. Smaller
branch ducts are connected to the trunk. The
arrangement provides airflows that are easily
balanced and can be easily designed to be located
inside the conditioned space of the building.
The principal design limitation of the extended
(Single Extended Plenum System)
plenum is the maximum length of the main supply
trunk (of single size), which is usually limited 24 ft. maximum 24 ft. maximum
End cap
End cap
Supply
much airflow near the ends and insufficient Plenum
4 ft
Reduces to approximately 50%, the plenum minimum
1200 cfm
size is reduced to regain the velocity in the 900 fpm
15
e) Radial System
In a radial system, there is no trunk or branches; rather individual supply outlets are essentially connected
directly to the AHU, usually using a small supply plenum. The short, direct duct runs maximize airflow. The
radial system commonly is applied in attics, crawl spaces, and in slab on grade installations (with the ducts
embedded in the slab). It can be used with up-flow, down-flow, or horizontal AHU and furnaces.
Traditionally, this system is associated with an AHU
that is centrally located where ducts are arranged
in a radial pattern. However, symmetry is not
mandatory, and designs using parallel run-outs can
be designed so that duct runs remain in the
conditioned space (e.g., installed above a dropped
ceiling).
The radial system is most economical and easiest
to install, but is not practical if the AHU cannot be Radial duct system
centrally located.
Supply
Concrete Plenum
Slab
Perimeter outlets
16
Rules of thumb based on ACCA (Air Conditioning Contractors of America) for Residential Ducts.
• Use one size trunk up to 24' (7.30 m) of trunk length
• More than 24', reduce trunk duct every 15' (4.5 m) to 20' (6.0 m).
• Use tapered reducer for trunk reduction on capped trunk.
• Use offset takeoff rather than straight takeoff. See figure
• Damper each run as close to the trunk as possible.
• No branch should be installed closer than 12" to the end of a trunk.
• No takeoffs 4' after a reduction, or 1.5 times the greater dimension of the duct.
• Never take-off a reduction or increase the mains any closer than the diameter of the branch duct.
• Types of duct in attic: include extended plenum, the reducing trunk, and the radial arrangements.
• Flexible ducts: wide variety can be used with attic installations. However, great care must be taken
when installing a flexible duct. Improper installation that allows sagging, sharp bends, and crimping
of flexible duct will increase the friction loss of the system and increase the total static pressure
that the indoor fan must overcome. This can result in service problems and possible equipment
failure. It is always necessary to follow the recommendations of the manufacturer when installing a
system utilizing flexible duct products.
b) Basement installations
Also suitable to all duct system. If the basement is unconditioned, then ducts must have a vapor barrier
installed to prevent condensation on the exterior of the ductwork. It is recommended that a duct liner
be installed for sound attenuation. All joints and side seams must be sealed to prevent duct leakage.
17
Location of AHU
In general, it can be installed in the attic, in the garage area, or in a closet inside the premise. AHU should
be located where the shortest duct runs possible are attained. The shorter the duct runs are, the lower the
resistance to airflow and the lower the heat gains and heat losses will be. The disadvantage to locating
AHU in the attic space is serviceability. Moreover, when AHU is installed in an attic, an auxiliary drain pan is
required, along with a condensate line and/or emergency float switch to shut down the system in case of a
condensate overflow. Locating the return grilles in the conditioned space is recommended with attic
installations. This allows the homeowner to change the filters without having to enter the attic.
• Distributed Return
This means that each room has a return duct back to the AHU. The method avoids too much positive
pressurization, minimizes pressure imbalances, improves privacy, and is quiet. However, design and
installation costs are generally higher than for a central return system, and higher friction losses can
increase blower requirements.
• Central Return
In a central return duct system, return grilles are located in central locations on the plenum, usually close
to AHU. To ensure proper airflow from all rooms, especially when doors are closed, transfer grilles or
jumper ducts must be installed in each room.
Central return duct systems has the advantages of less ductwork and lower energy loss, since larger
plenum provides more direct path for airflow.
The size of the return grille is based on the following equation and divide the result by 0.65 to account for
𝑐𝑐𝑐𝑐𝑐𝑐
about 65% free area, which is normal for stamped return grilles: 𝐴𝐴 = where A in (ft2) & V in (ft/min)
𝑉𝑉
PRESSURE BALANCING
The return openings will need to be 2 to 3 times the size of the supply duct depending on system design
velocities. This can take the form of transfer grille and jump ducts.
a. Transfer Grilles: They allow air to move from one space to another to alleviate
Transfer Grille
pressure differences. For example, a transfer grille installed above a bedroom door
enables air to move between the bedroom and the hallway, regardless of whether
the door is open or closed. A transfer grille and/or jump ducts are often required to
equalize pressure and prevent over pressurization of spaces.
“Rule of Thumb”: consider 1 in2 of wall opening per cfm delivered to the room.
18
b. Jump ducts: they allow air from the uncomfortable
room to flow out and into another room containing
a return (help balancing airflow between rooms in
cases there is one shared return grille serving the whole
floor). They are short ducts and have less than 6” diameter.
DAMPERS: Dampers are used to control airflow and balance duct pressure:
a) Volume Control Dampers
They regulate the airflow (cfm). Two main types are in use:
• Parallel blades where the blades rotate in one direction. They are best suited for
full-open/close requirements or for fine control between 80% to 100% full flow.
• Opposed blade dampers where the adjacent blades rotate in opposite directions.
They are best for systems where air volume is changed over a wide range. AMCA
(Air Movement and Control Association) recommends using an opposed-blade
damper when volume control is needed.
These dampers should be installed close to the main supply as far away as possible from the outlets.
b) Balancing dampers
Balancing dampers regulate air pressure in rooms connected to the duct work. Air
pressure imbalances can cause annoyances for occupants and may cause larger
problems for the entire system.
Balancing dampers are adjusted by technicians, who will measure the air pressure in a
room as they adjust the angle of the damper’s blades. Once the correct air pressure is
found, the balancing damper’s blades are locked to maintain the necessary air pressure.
c) Terminal dampers:
These dampers are simply registers and diffusers and should not be considered in branch balancing as they
are meant to be used for fine adjustment only and would normally be in an almost fully open position to
prevent unnecessary noise.
d) Fire and Smoke Dampers
A fire damper is installed in ducts and air transfer openings to interrupt the
passage of a flame in case of a fire. They are equipped with a fusible link
{rated for 74 °C to 141°C} that holds the blades open until the link melts then
the blades close and stop the flame from moving into an adjoining
compartment.
Location:
• Fire dampers shall be installed in or near the wall or floor. Should the ductwork fall away, the
damper needs to stay in the wall or floor to maintain the integrity of the wall or floor. One should
19
actually think of the fire damper as part of the wall system itself. They must be installed no more
than 24 inches from the smoke barrier.
• Smoke dampers that are used to isolate AHU are not limited to this distance requirement. NFPA
90A states that smoke dampers are used to isolate AHU over 15,000 cfm.
20
system also requires enough return ducts to bring expended air back to the HVAC unit to be
conditioned again. Each room that receives heating or cooling should have at least one return duct. As
a rule of thumb, use 2 cfm for each in2 of return air opening. For example, 20” x 20” grille equals 400
in2 gross area of grille, which means 800 cfm of recommended airflow.
5. Be careful where you install ducts: Ducts placed in conditioned spaces are more efficient than those
placed in unconditioned spaces. If located within conditioned space, conductive and radiative losses,
leakage losses, and equipment cabinet losses are reduced or regained into the building space. If it is not
feasible to locate ductwork within conditioned spaces, the ducts should be properly sealed and
insulated. The trunk ducts are usually located above corridors in the cavity above the ceiling to
minimize noise transmission to the conditioned zones and allow easy access without disturbing the
building occupants.
6. Seal and insulate: Make sure all ductwork sections fit together tightly. Connections can be
mechanically sealed with sheet metal screws or other fasteners to improve connection strength. Seal
connections with mastic or metal tape. Cover the ductwork with insulation, such as rigid fiber board or
standard blanket-type insulation.
21
Balancing the System:
Balancing a system involves the following steps:
• Inspect the system by locating all ducts, openings, and dampers.
• Open all dampers in the ducts and at the grilles.
• Check the velocities at each outlet.
• Measure the "free" grille area.
• Determine the floor areas of each room then get total area.
𝐴𝐴𝑟𝑟𝑟𝑟𝑟𝑟𝑟𝑟
• Get the cfm for each room: 𝑐𝑐𝑐𝑐𝑐𝑐𝑟𝑟𝑟𝑟𝑟𝑟𝑟𝑟 = � � 𝑐𝑐𝑐𝑐𝑐𝑐𝑡𝑡𝑡𝑡𝑡𝑡𝑡𝑡𝑡𝑡
𝐴𝐴𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓 𝑎𝑎𝑎𝑎𝑎𝑎𝑎𝑎
Spacing
For sheet metal ductwork, the space between the hangers should not exceed the distances listed below:
22
Typical Duct Fabrication and Supporting
24
Typical Upper Hanger Attachment
25
DUCT CLEANING
There is also the question of when duct cleaning should be done, and how the job could be validated.
Ducts must be cleaned when:
• There is substantial evidence of visible mold growth inside the hard surface of ducts or on other
components of the heating and cooling system.
• If the insulation gets wet or moldy, it cannot be effectively cleaned and should be removed and
replaced.
• Ducts are infested with vermin, e.g. (rodents or insects).
• Ducts are blocked with excessive amounts of dust or debris, and maybe released into the home
from the supply registers.
Duct Cleaning Methods
Methods of duct cleaning vary, although standards have been established by industry associations
concerned with air duct cleaning. Typically, a service provider will use specialized tools to dislodge dirt and
other debris in ducts, and then vacuum them out with a high-powered vacuum cleaner. Common duct
cleaning methods include: (1) Contact vacuuming, (2) Air sweeping and (3) Power brushing.
Contact Vacuum Method:
Contact vacuuming involves cleaning the interior duct surfaces by way of existing openings and outlets or,
when necessary, through openings cut into the ducts. The vacuum unit should only use HEPA (High
Efficiency Particle Air) collection equipment, which release extremely fine particles into the atmosphere,
instead of gathering them.
Starting at the return side of the system, the vacuum cleaner head is inserted into the section of the duct
to be cleaned at the opening furthest
upstream, and then the vacuum cleaner is
turned on. Vacuuming proceeds
downstream slowly enough to allow the
vacuum to pick up all dirt and dust
particles.
Contact vacuuming usually requires larger
access windows than other methods, in
order to allow the cleaning equipment to
reach into the last corner of the duct. The distance between access hatches depends on the hovering
equipment and the target distance from the opening. The head of the vacuum cleaner is introduced into
the duct using the nearest opening at the beginning of the duct network. Hovering then starts, following
the direction of air flow, and slowly enough to capture and gather up all the dirt.
26
Air Sweep Method:
In the air sweep or air washing method, a vacuum collection unit is connected to the downstream end of
the duct section. The vacuum unit should use HEPA filtering, if it is exhausting into an occupied space. The
isolated section of duct being cleaned should be subjected to a minimum of 1" negative air pressure to
draw loosened materials into the vacuum collection system. Take care not to collapse the duct.
Inspection of each duct section and related components is performed to determine if the duct is clean.
When the section of duct is clean, the brush is removed from the duct and inserted through the next
opening, where the process continues.
27
28
29
30
ROUND DUCT FITTINGS & TRANSITIONS
31
RECTANGULAR DUCT FITTINGS & TRANSITION
32