Omron Omrns02984 1-1740561

The D4SL-N Guard Lock Safety-door Switch is a compact safety device featuring various wiring options and built-in switches for different applications, with a key holding force of 1,300 N. It allows for easy key insertion point adjustments and has reduced power consumption. The accompanying Slide Key prevents workers from being trapped in hazardous areas and is designed for lightweight doors, with a mechanical durability of 20,000 operations.

Uploaded by

Gerson Rodrigues
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
19 views29 pages

Omron Omrns02984 1-1740561

The D4SL-N Guard Lock Safety-door Switch is a compact safety device featuring various wiring options and built-in switches for different applications, with a key holding force of 1,300 N. It allows for easy key insertion point adjustments and has reduced power consumption. The accompanying Slide Key prevents workers from being trapped in hazardous areas and is designed for lightweight doors, with a mechanical durability of 20,000 operations.

Uploaded by

Gerson Rodrigues
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 29

Guard Lock Safety-door Switch/D4SL-N-mounting Slide Key

D4SL-N / D4SL-NSK10-LK@
World's smallest Class 6-contact Guard Lock
Safety-door Switch
<Guard Lock Safety-door Switch D4SL-N>
• Wiring time is reduced with two types of wiring Guard Lock Safety-door Switch
methods capable of one-touch attachment and
removal.
• A wide variety of built-in switches can be used for
various devices.
(4-, 5-, and 6-contact models are available)
• Key holding force of 1,300 N.
• It is possible to change the key insertion point
without detaching the head.
• Significantly reduced solenoid current contributes
to the reduction of power supply cost. Slide Key
Terminal
Block Type Connector Type
<Slide Key D4SL-NSK10-LK@>
• Lockout Key to prevent workers from becoming
trapped inside the hazardous area.
• The vertical D4SL Guard Lock Safety-door Switch
can be easily mounted on 40 × 40 mm aluminum
frames.
• The plastic material makes the Slide Key suitable
for lightweight doors.
Be sure to read the “Safety Precautions”
on page 22.

1
D4SL-N / D4SL-NSK10-LK@
Model Number Structure
Model Number Legend
Switch (Standard type)

D4SL-N @@@@-@
(1) (2) (3) (4)
@@
(5) (6) (7)

(1) Conduit Size (4) Door Lock and Release


Contact Model Conduit Size Contact Model Door Lock and Release
4-contact Model 2: G1/2 4-contact Model
A: Mechanical lock/24VDC solenoid release
5-contact Model Common 3: 1/2-14NPT *1 5-contact Model Common
G: 24VDC solenoid lock/mechanical release
6-contact Model 4: M20 6-contact Model

(2) Built-in Switch (5) Indicator


Contact Model Built-in Switch Contact Model Indicator
Door monitor and Lock monitor are connected in series 4-contact Model −: None
internally.
5-contact Model Common
A: 1NC/1NO + 1NC/1NO D: 24VDC (orange LED indicator)
6-contact Model
B: 1NC/1NO + 2NC
C: 2NC + 1NC/1NO
D: 2NC + 2NC (6) Release Key Type
4-contact Model
Door monitor and Lock monitor are NOT connected in Contact Model Release Key Type
series internally.
S: 1NC/1NO + 1NC/1NO 4-contact Model −: Standard release key (metal)
T: 1NC/1NO + 2NC −: Standard release key (metal)
U: 2NC + 1NC/1NO 5-contact Model Common
4: Special release key (resin)
V: 2NC + 2NC 6-contact Model
(Note:Release keys are provided.)
E: 2NC/1NO + 1NC/1NO
F: 2NC/1NO + 2NC (7) Connection Method
5-contact Model
G: 3NC + 1NC/1NO
H: 3NC + 2NC Contact Model Connection Method
N: 2NC/1NO + 2NC/1NO 4-contact Model
−: Terminal block
P: 2NC/1NO + 3NC 5-contact Model Common
6-contact Model N: Connector *2
Q: 3NC + 2NC/1NO 6-contact Model
R: 3NC + 3NC

(3) Head Material


Contact Model Head Material
4-contact Model F: Resin
5-contact Model Common F: Resin
6-contact Model D: Metal

*1. M20, includes M20-to-1/2-14NPT conversion adapter.


*2. Connector cables are not included with the connector type and are to be purchased separately.

Operation key

D4SL-N K@@
(1) (2)

(1) Operation Key Type (2) Key Type


1: Horizontal mounting −: No cushion rubber
2: Vertical mounting G: Cushion rubber
3: Adjustable mounting (horizontal) S: No cushion rubber, short type

2
D4SL-N / D4SL-NSK10-LK@
Ordering Information
List of Models
Contact configuration Conduit
Release Wiring Solenoid voltage/ Lock and
(door open/closed detection switch size Model
Key Type method Indicator release type
and lock monitor switch contacts) (See Note.)
6-contact Model G1/2 D4SL-N2@FA-DN
Insert the built-in switch (N, P, Q or R) 1/2-14NPT D4SL-N3@FA-DN
into the blank @. M20 D4SL-N4@FA-DN
24VDC
(Orange) G1/2 D4SL-N2@FA-DN
5-contact Model
Connector Insert the built-in switch (E, F, G or H) 1/2-14NPT D4SL-N3@FA-DN
into the blank @. M20 D4SL-N4@FA-DN

4-contact Model G1/2 D4SL-N2@FA-N


24VDC
Insert the built-in switch (A, B, C, D, S, 1/2-14NPT D4SL-N3@FA-N
(without indicator)
T, U or V) into the blank @. M20 D4SL-N4@FA-N
Mechanical lock
Solenoid release G1/2 D4SL-N2@FA-D
6-contact Model
Insert the built-in switch (N, P, Q or R) 1/2-14NPT D4SL-N3@FA-D
into the blank @. M20 D4SL-N4@FA-D
24VDC
(Orange) G1/2 D4SL-N2@FA-D
5-contact Model
Terminal
Insert the built-in switch (E, F, G or H) 1/2-14NPT D4SL-N3@FA-D
block
into the blank @. M20 D4SL-N4@FA-D
4-contact Model G1/2 D4SL-N2@FA
Standard 24VDC
(metal) Insert the built-in switch (A, B, C, D, S, 1/2-14NPT D4SL-N3@FA
(without indicator)
T, U or V) into the blank @. M20 D4SL-N4@FA

6-contact Model G1/2 D4SL-N2@FG-DN


Insert the built-in switch (N, P, Q or R) 1/2-14NPT D4SL-N3@FG-DN
into the blank @. M20 D4SL-N4@FG-DN
24VDC
(Orange) G1/2 D4SL-N2@FG-DN
5-contact Model
Connector Insert the built-in switch (E, F, G or H) 1/2-14NPT D4SL-N3@FG-DN
into the blank @. M20 D4SL-N4@FG-DN
4-contact Model G1/2 D4SL-N2@FG-N
24VDC
Insert the built-in switch (A, B, C, D, S, 1/2-14NPT D4SL-N3@FG-N
(without indicator)
Solenoid lock T, U or V) into the blank @. M20 D4SL-N4@FG-N
Mechanical
release 6-contact Model G1/2 D4SL-N2@FG-D
Insert the built-in switch (N, P, Q or R) 1/2-14NPT D4SL-N3@FG-D
into the blank @. M20 D4SL-N4@FG-D
24VDC
(Orange) G1/2 D4SL-N2@FG-D
5-contact Model
Terminal
Insert the built-in switch (E, F, G or H) 1/2-14NPT D4SL-N3@FG-D
block
into the blank @. M20 D4SL-N4@FG-D

4-contact Model G1/2 D4SL-N2@FG


24VDC
Insert the built-in switch (A, B, C, D, S, 1/2-14NPT D4SL-N3@FG
(without indicator)
T, U or V) into the blank @. M20 D4SL-N4@FG
Note: The recommended models for equipment and machinery being exported to Europe are those with an M20 conduit sizes, and for North
America, the recommended models are those with a 1/2-14NPT conduit sizes.

3
D4SL-N / D4SL-NSK10-LK@

Contact configuration
Release Wiring Solenoid voltage/ Lock and Conduit size
(door open/closed detection switch Model
Key Type method Indicator release type (See Note.)
and lock monitor switch contacts)

6-contact Model G1/2 D4SL-N2@FA-D4N


Insert the built-in switch (N, P, Q or R) 1/2-14NPT D4SL-N3@FA-D4N
into the blank @. M20 D4SL-N4@FA-D4N
Connector
5-contact Model G1/2 D4SL-N2@FA-D4N
Insert the built-in switch (E, F, G or H) 1/2-14NPT D4SL-N3@FA-D4N
into the blank @. M20 D4SL-N4@FA-D4N
Mechanical lock
Solenoid release G1/2 D4SL-N2@FA-D4
6-contact Model
Insert the built-in switch (N, P, Q or R) 1/2-14NPT D4SL-N3@FA-D4
into the blank @. M20 D4SL-N4@FA-D4
Terminal
block G1/2 D4SL-N2@FA-D4
Special 5-contact Model
(resin) Insert the built-in switch (E, F, G or H) 1/2-14NPT D4SL-N3@FA-D4
into the blank @. M20 D4SL-N4@FA-D4
24VDC
(Orange) G1/2 D4SL-N2@FG-D4N
6-contact Model
Insert the built-in switch (N, P, Q or R) 1/2-14NPT D4SL-N3@FG-D4N
into the blank @. M20 D4SL-N4@FG-D4N
Connector
5-contact Model G1/2 D4SL-N2@FG-D4N
Insert the built-in switch (E, F, G or H) 1/2-14NPT D4SL-N3@FG-D4N
Solenoid lock into the blank @. M20 D4SL-N4@FG-D4N
Mechanical
release 6-contact Model G1/2 D4SL-N2@FG-D4
Insert the built-in switch (N, P, Q or R) 1/2-14NPT D4SL-N3@FG-D4
into the blank @. M20 D4SL-N4@FG-D4
Terminal
block G1/2 D4SL-N2@FG-D4
5-contact Model
Insert the built-in switch (E, F, G or H) 1/2-14NPT D4SL-N3@FG-D4
into the blank @. M20 D4SL-N4@FG-D4
Note: The recommended models for equipment and machinery being exported to Europe are those with an M20 conduit sizes, and for North
America, the recommended models are those with a 1/2-14NPT conduit sizes.

4
D4SL-N / D4SL-NSK10-LK@

Operation Keys
Type Model

Horizontal mounting D4SL-NK1

Horizontal mounting
(Short) D4SL-NK1S

Horizontal mounting
D4SL-NK1G
(Cushion rubber)

Vertical mounting D4SL-NK2

Vertical mounting
D4SL-NK2G
(Cushion rubber)

Adjustable
D4SL-NK3
(Horizontal)

Connector Cables
Cable length Model
1m D4SL-CN1
3m D4SL-CN3
5m D4SL-CN5

5
D4SL-N / D4SL-NSK10-LK@

Slide Key
Applicable
Type Specifications Contents Model
Door Switch

Slide Key: 1 (not yet mounted)


D4SL-N mounting plate: 1
Door Switch special mounting screws: 3
Weight: Approx. 0.6 kg
D4SL-NK1 (operation key): 1
Mechanical durability:
D4SL-NK1 special mounting screws: 2 D4SL-NSK10-LK D4SL-N
20,000 operations min.
Lockout keys: 2
Lockout key strap: 1
Caution labels (stickers): 2 sheets
(English and Japanese)

Weight: Approx. 0.1 kg Inner Lever: 1 D4SL-SK10H * ---

Slide Key: 1 (not yet mounted)


Inner Lever: 1
D4SL-N mounting plate: 1
Weight: Approx. 0.7 kg Door Switch special mounting screws: 3
Mechanical durability: D4SL-NK1 (operation key): 1
D4SL-NSK10-LKH D4SL-N
20,000 operations min. D4SL-NK1 special mounting screws: 2
Lockout keys: 2
Lockout key strap: 1
Caution labels (stickers): 2 sheets
(English and Japanese)

Note: 1. The Door Switch is not included. Select the Door Switch depending on the necessary number of contacts and the conduit size.
The contents are provided as a total set, individual contents cannot be ordered separately.
2. Perform risk assessment for the equipment in question, configure relay units and other safety circuits, and use properly.
* The inner lever for D4GL-SK10/D4SL-NSK10 that can not be used for other products and applications.

Applicable Door Switches


D4SL-NSK10-LK

+ =

D4SL-NSK10-LK D4SL-N

D4SL-NSK10-LKH

+ =

D4SL-NSK10-LKH D4SL-N

6
D4SL-N / D4SL-NSK10-LK@
Features
The lockout key prevents workers from becoming trapped without using a padlock.
Note: Using LEDs of D4SL-N enables confirming whether the door is open or closed and locked or unlocked.

Close door
Locked (power not supplied to
solenoid) The slide handle is closed.

The handle-shaped fixture makes


it easy to use the Door Switch.

CAUTION
Lockout key Guard Lock Safety-door
Switch will not be unlocked
with Lockout Key.
Lockout Key may be damaged
by operating Lockout Key
when the door is closed.
Always carry lockout key
when entering the Hazardous
area.

Close door
No. 7467139-3A

Attach the supplied


Unlocked (power supplied to solenoid) caution labels for display.
The slide handle is closed.

Left door
Lockout Key Door Opening to the Left.

The slide handle can be pulled. Do not turn the key as in the figure above if the
slide handle is closed.

Open door Open door Open door


The slide handle is open. The slide handle is open. The slide handle is open.
The slide handle
does not move.

When the slide handle is open, the The slide handle is secured at the position If the lockout key is not mounted, the
lockout key can be pulled regardless of shown in the figure. slide handle will not move and the
whether power is being supplied to the A worker holding the lockout key will not be door will not close.
solenoid or not. trapped locked inside the hazardous area by
another person.

7
D4SL-N / D4SL-NSK10-LK@
Structure and Nomenclature
Structure
D4SL-N@@@@-D@N Connector Type D4SL-@@@@-D@ Terminal Block Type
Two operation key holes Two operation key holes

The switch has The switch has


a release key a release key
on the back of on the back of Can be mounted
Can be mounted the switch as well. from four directions.
the switch as well.
from four directions.

The switch has an The switch has an


indicator on the back indicator on the back
of the switch as well. of the switch as well.

Connector/Terminal

Terminal Arrengement
for D4SL-N@N@@-D@
9 E1 (+)

10 E2 (−)

2 41 12 11 1
42

1 2 3 4 5 6 10 <LED> 4 52 51 22 21 3
ORANGE
8 64 63 34 33 5
Notched side is No. 1 7 6
1 3 5 7 9
2 4 6 8 10
Note: Numbers inside the boxes are terminal
numbers printed on the product.

8
D4SL-N / D4SL-NSK10-LK@

Operating Cycle Examples for Standard Models


D4SL-N@@@A-@ (Mechanical Lock Models)
Door condition Turning the special
Condition 1 Condition 2 Condition 3
release key

Return to
condition 1
Door open. Door closed. Door closed. Door closed.
The door will lock The door is locked. The door can be No power is supplied
when the door closes. opened. to the solenoid.
Terminal No. and The door is unlocked
Contact No. Function manually.
9 E1- 10 E2 Solenoid ON
2 42- 1 11 (NC) Door open/closed detection
4 52- 3 21 (NC) and lock monitor contacts
3 21- 4 22 (NC) Door open/closed detection
5 31- 6 32 (NC) contact

5 33- 6 34 (NO) Door open/closed detection


contact
1 41- 2 42 (NC)
Lock monitor contact
7 61- 8 62 (NC)
7 63- 8 64 (NO) Lock monitor contact

D4SL-N@@@G-@ (Solenoid Lock Models)


Door condition Even when the door
is closed, it does not Door closed.
Door closed.
lock until power is The door can be
The door is locked.
Terminal No. and supplied to the opened.
Contact No. Function solenoid.
9 E1- 10 E2 Solenoid ON
2 42- 1 11 (NC) Door open/closed detection
4 52- 3 21 (NC) and lock monitor contacts
3 21- 4 22 (NC) Door open/closed detection
5 31- 6 32 (NC) contact

5 33- 6 34 (NO)
Door open/closed detection
contact
The shaded areas indicate
1 41- 2 42 (NC) the contact is closed and
Lock monitor contact
7 61- 8 62 (NC) power is supplied to the
7 63- 8 64 (NO) Lock monitor contact solenoid.

Door open/closed detection and lock monitor contacts: Can be used in safety circuits because of the direct opening mechanisms.
Door open/closed detection contact: Can be used to confirm whether the key is inserted and to monitor the open/closed status of a door.
Lock monitor contact: Can be used to confirm whether power is supplied to the solenoid and to monitor whether or not a door can be opened or closed.
Note: 1. The door open/closed detection and lock monitor contact configuration depends on the model.
2. If a current is detected in the solenoid lock model (built-in switches; N, P, Q, R), before the door is closed, the door will remain unlocked.
Be sure to supply power to the solenoid after the door is closed.

9
D4SL-N / D4SL-NSK10-LK@
Specifications
Standards and EC Directives
Conforms to the following EC Directives:
• Machinery Directive
• Low Voltage Directive
• EMC Directive
• EN1088
• EN60204-1
• GS-ET-19

Certified Standards
Certification body Standard File No.
TÜV SÜD EN60947-5-1(certified direct opening)
Consult your OMRON representative for details.
UL UL508, CSA C22.2 No.14
CQC (CCC) GB14048.5 pending
KOSHA *1 EN60947-5-1 Consult your OMRON representative for details.
*1. Only certain models have been certified.

Certified Standard Ratings


TÜV (EN60947-5-1)
Utilization category AC-15 DC-13
1.5 A *1
Rated operating current (Ie) 0.22 A
1 A *2
Rated operating current (Ue) 120 V 125 V
Note: Use a 4 A fuse that conforms to IEC60127 as a short-circuit protection device. This fuse is not included with the switch.
*1. 11-42, 21-52, 21-22
*2. Other terminals

UL/CSA (UL508, CSA C22.2 No.14)


C150
Current (A) Volt-amperes (VA)
Rated voltage Carry current
Make Break Make Break
120 VAC 2.5 A 15 1.5 1,800 180

R150
Current (A) Volt-amperes (VA)
Rated voltage Carry current
Make Break Make Break
125 VDC 1.0 A 0.22 0.22 28 28

Solenoid Coil Characteristics


Item 24 VDC
Rated operating voltage (100% ED) 24 VDC +10%
−15%
Power ON:
6-contact type Approx. 6.4 W at 0.26 A
Current consumption *
4-contact/5-contact type Approx. 4.8 W at 0.2 A
Constant: Approx. 2.6 W (average) at 0.2 A (max.)
Insulation Class E (to 120°C)
* A starting current is applied to the solenoid for Approx. 10 seconds.
After this, the internal circuit switches to a constant current.

Indicator
Item LED type
Rated voltage 24 VDC
Current consumption Approx.10 mA
Color (LED) Orange

10
D4SL-N / D4SL-NSK10-LK@

Characteristics
Degree of protection *1 IP67 (EN60947-5-1)
Mechanical 1,000,000 operations min.
Durability *2
Electrical 150,000 operations min. (1 A resistance at 125 VAC) *3
Operating speed 0.05 to 1 m/s
Operating frequency 5 operations minute max.
Direct opening force *4 60 N min. (EN60947-5-1)
Direct opening travel *4 15 mm min. (EN60947-5-1)
Holding force *5 1,300 N min.
Contact resistance 200 mΩ max.
Minimum applicable load *6 1 mA resistive load at 5 VDC (N-level reference value)
Rated insulation voltage (Ui) 150 V (EN60947-5-1)
Rated frequency 50/60 Hz
Protection against electric shock Class II (double insulation)
Pollution degree (operating environment) 3 (EN60947-5-1)
Between terminals of same polarity 1.5 kV
Impulse
Between terminals of different polarity 1.5 kV
withstand voltage
(EN60947-5-1) Between other terminals and
2.5 kV
non-current carrying metallic parts
Insulation resistance 100 Ω min. (at 500 VDC)
Vibration resistance Malfunction 10 to 55 Hz, 0.35 mm single amplitude
Malfunction 80 m/s2 min.
Shock resistance
Destruction 1,000 m/s2 min.
Conditional short-circuit current 100 A (EN60947-5-1)
2.5A (11-42, 21-52, 21-22)
Conventional free air thermal current (Ith)
1A (Others)
Ambient operating temperature −10 to 55°C (with no icing)
Ambient operations humidity 95% max.
Head: Resin
Approx. 290 g (Connector model)
Approx. 330 g (Terminal block model)
Weight
Head: Metal
Approx. 370 g (Connector model)
Approx. 410 g (Terminal block model)
Note: 1. The above values are initial values.
2. The Switch contacts can be used with either standard loads or microloads.
Once the contacts have been used to switch a load, however, they cannot be used to switch smaller loads.
The contact surfaces will become rough once they have been used and contact reliability for smaller loads may be reduced.
*1. The degree of protection is tested using the method specified by the standard (EN60947-5-1).
Confirm that sealing properties are sufficient for the operating conditions and environment beforehand.
Although the switch box is protected from dust, oil or water penetration, do not use the D4SL in places where cutting chips, oil, water or
chemicals may enter through the key hole on the head, otherwise Switch damage or malfunctioning may occur.
*2. The durability is for an ambient temperature of 5 to 35°C and an ambient humidity of 40% to 70%. For more details, consult your OMRON
representative.
*3. Do not pass the 1 A, 125 VAC load through more than 3 circuits.
*4. These figures are minimum requirements for safe operation.
*5. This figure is based on the GS-ET-19 evaluation method.
*6. This value will vary with the switching frequency, environment, and reliability level.
Confirm that correct operation is possible with the actual load beforehand.

11
D4SL-N / D4SL-NSK10-LK@
Connection
Internal Circuit Diagram
Without indicator With indicator
24VDC D 24VDC D
E1 (+) E1 (+)

R
Control Control
ZD D ZD D
circuit circuit
LED
E2 (−) E2 (−)

Circuit Connection Example


• Direct opening contacts used as safety-circuit input are indicated with the mark.
• Do not switch circuits for three or more standard loads at the same time.
Doing so may adversely affect insulation performance.
• DC solenoids have polarity. (E1: Positive, E2: Negative)
Confirm terminal polarity before wiring.

Connection Example for D4SL-N@AF@-@ Connection Example for D4SL-N@SF@-@


Terminals 12-41 are connected internally.
E1
9 (+)
E1 Door open/
9 (+) Door open/ closed detection
closed detection 10 E2 switch
E2 switch (−)
10
(−) 2 1
42 41 AND To safety circuit
2 41 12 1 To safety circuit
42 11 4 22 21 3
(Not use) 4 3 (Not use)
8 64 63 34 33 5 To control circuit
8 64 63 34 5 To control circuit
33
Lock monitor
7 6
Lock monitor switch
7 6
switch To control circuit
To control circuit

Connection Example for D4SL-N@EF@-D@ Connection Example for D4SL-N@NF@-D@


Terminals 12-41 are connected internally. Terminals 12-41 and 22-51 are connected internally.

E1 E1
9 (+) 9
Door open/ (+) Door open/
LED closed detection LED closed detection
10 E2 switch E2 switch
10
(−) (−)
2 41 12 1 To safety circuit 2 41 12 1 To safety circuit
42 11 42 11
4 22 3 To safety circuit 4 51 22 3 To safety circuit
21 52 21
8 64 63 34 5 To control circuit 8 64 63 34 5 To control circuit
33 33

Lock monitor Lock monitor


7 6 7 6
switch switch
To control circuit To control circuit

12
D4SL-N / D4SL-NSK10-LK@

Contact Form
Indicates conditions where the Key is inserted and the lock is applied.
Contact Contact Form
(door open/ Door open/
Model Lock Operating pattern Remarks
closed detection closed
and lock monitor) monitor
detection

Door open/closed Lock position Only NC contact 11-12 has a


Lock monitor detection
42-11 certified direct opening
1NC/1NO+ 42 41 12 11 34-33 On mechanism.
D4SL-N@A@@-@
1NC/1NO 64-63 The terminals 42-11, 34-33, and
Stroke 64-63 can be used as unlike
64 63 34 33 Operation Key Insertion Extraction poles.
completion position completion position

Lock position
Door open/closed Only NC contact 11-12 has a
Lock monitor detection 42-11 certified direct opening
42 41 12 11 34-33 On mechanism.
D4SL-N@B@@-@ 1NC/1NO+2NC 62-61 The terminals 42-11, 34-33, and
Stroke 62-61 can be used as unlike
Operation Key Insertion Extraction
62 61 34 33
completion position completion position
poles.

Lock position
Door open/closed Only NC contact 11-12 and 31-
Lock monitor detection
42-11 32 has a certified direct opening
42 41 12 11 32-31 On mechanism.
D4SL-N@C@@-@ 2NC+1NC/1NO 64-63 The terminals 42-11, 32-31, and
Stroke 64-63 can be used as unlike
Operation Key Insertion Extraction
64 63 32 31
completion position completion position
poles.

Lock position
Door open/closed Only NC contact 11-12 and 31-
Lock monitor detection
42-11 32 has a certified direct opening
42 41 12 11 32-31 On mechanism.
D4SL-N@D@@-@ 2NC+2NC 62-61 The terminals 42-11, 32-31, and
Stroke 62-61 can be used as unlike
Operation Key Insertion Extraction
62 61 32 31
completion position completion position
poles.

Lock position
Door open/closed Only NC contact 21-22 has a
Lock monitor detection 42-41
certified direct opening
22-21
1NC/1NO+ 42 41 On mechanism.
D4SL-N@S@@-@ 34-33
1NC/1NO 64-63
The terminals 42-41, 22-21, 34-
22 21 33, and 64-63 can be used as
Stroke
64 63 34 33 Operation Key Insertion Extraction unlike poles.
completion position completion position

Lock position
Door open/closed Only NC contact 21-22 has a
Lock monitor detection 42-41
certified direct opening
22-21
42 41 On mechanism.
D4SL-N@T@@-@ 1NC/1NO+2NC 34-33
62-61
The terminals 42-11, 22-21, 34-
22 21 33, and 62-61 can be used as
Stroke
62 61 34 33 Operation Key Insertion Extraction unlike poles.
completion position completion position

Lock position
Door open/closed Only NC contact 21-22 and 31-
Lock monitor detection 42-41
32 has a certified direct opening
22-21
42 41 On mechanism.
D4SL-N@U@@-@ 2NC+1NC/1NO 32-31
64-63
The terminals 42-11, 22-21, 32-
22 21 31, and 64-63 can be used as
Stroke
64 63 32 31 Operation Key Insertion Extraction unlike poles.
completion position completion position

Lock position
Door open/closed Only NC contact 21-22 and 31-
Lock monitor detection 42-41
32 has a certified direct opening
22-21
42 41 On mechanism.
D4SL-N@V@@-@ 2NC+2NC 32-31
62-61
The terminals 42-11, 22-21, 32-
22 21 31, and 62-61 can be used as
Stroke
62 61 32 31 Operation Key Insertion Extraction unlike poles.
completion position completion position

13
D4SL-N / D4SL-NSK10-LK@

Contact Contact Form


(door open/ Door open/
Model Lock Operating pattern Remarks
closed detection closed
and lock monitor) monitor
detection
Lock position
Door open/closed Only NC contact 11-12 and 21-
Lock monitor detection 42-11
22 has a certified direct opening
22-21
D4SL-N@E@@-@ 2NC/1NO+ 42 41 12 11
34-33
On mechanism.
1NC/1NO 64-63
The terminals 42-11, 22-21, 34-
22 21 33, and 64-63 can be used as
Stroke
64 63 34 33 Operation Key Insertion Extraction unlike poles.
completion position completion position

Lock position
Door open/closed Only NC contact 11-12 and 21-
Lock monitor detection 42-11
22 has a certified direct opening
22-21
42 41 12 11 On mechanism.
D4SL-N@F@@-@ 2NC/1NO+2NC 34-33
62-61
The terminals 42-11, 22-21, 34-
22 21 33, and 62-61 can be used as
Stroke
62 61 34 33 Operation Key Insertion Extraction unlike poles.
completion position completion position

Lock position
Door open/closed Only NC contact 11-12 ,21-22
Lock monitor detection 42-11
and 31-32 has a certified direct
22-21
42 41 12 11 On opening mechanism.
D4SL-N@G@@-@ 3NC+1NC/1NO 32-31
64-63
The terminals 42-11, 22-21, 32-
22 21 31, and 64-63 can be used as
Stroke
64 63 32 31 Operation Key Insertion Extraction unlike poles.
completion position completion position

Lock position
Door open/closed Only NC contact 11-12 ,21-22
Lock monitor detection 42-11
and 31-32 has a certified direct
22-21
42 41 12 11 On opening mechanism.
D4SL-N@H@@-@ 3NC+2NC 32-31
62-61
The terminals 42-11, 22-21, 32-
22 21 31, and 62-61 can be used as
Stroke
62 61 32 31 Operation Key Insertion Extraction unlike poles.
completion position completion position

Lock position
Door open/closed Only NC contact 11-12 and 21-
Lock monitor detection 42-11
22 has a certified direct opening
52-21
2NC/1NO+ 42 41 12 11 On mechanism.
D4SL-N@N@@-@ 34-33
2NC/1NO 64-63
The terminals 42-11, 52-21, 34-
52 51 22 21 33, and 64-63 can be used as
Stroke
64 63 34 33 Operation Key Insertion Extraction unlike poles.
completion position completion position

Lock position
Door open/closed Only NC contact 11-12 and 21-
Lock monitor detection 42-11
22 has a certified direct opening
52-21
42 41 12 11 On mechanism.
D4SL-N@P@@-@ 2NC/1NO+3NC 34-33
62-61
The terminals 42-11, 52-21, 34-
52 51 22 21 33, and 62-61 can be used as
Stroke
62 61 34 33 Operation Key Insertion Extraction unlike poles.
completion position completion position

Lock position
Door open/closed
Only NC contact 11-12 ,21-22
Lock monitor detection 42-11 and 31-32 has a certified direct
52-21 opening mechanism.
42 41 12 11 On
D4SL-N@Q@@-@ 3NC+2NC/1NO 32-31 The terminals 42-11, 52-21, 32-
52 51 22 21
64-63 31, and 64-63 can be used as
Stroke unlike poles.
64 63 32 31 Operation Key Insertion Extraction
completion position completion position

Lock position
Door open/closed Only NC contact 11-12 ,21-22
Lock monitor detection 42-11
and 31-32 has a certified direct
52-21
42 41 12 11 On opening mechanism.
D4SL-N@R@@-@ 3NC+3NC 32-31
62-61
The terminals 42-11, 52-21, 32-
52 51 22 21 31, and 62-61 can be used as
Stroke
62 61 32 31 Operation Key Insertion Extraction unlike poles.
completion position completion position

14
D4SL-N / D4SL-NSK10-LK@
Dimensions and Operating Characteristics (Unit:mm)

Switches
D4SL-N@@@@-@N (Connector Type)
29.2
Head cap 29.2

9
Pre-travel distance

B
Operation Key 39
A
37 Side mounting
Front-side mounting
26.3 26.3 22±0.2 Three, 4.3 dia.
Two, 4.3 dia. 39
Mounting hole 10 Mounting hole

Spacers
4.5 dia. 42.9
22±0.2 4 31.5 38.7±0.2 38.5
(depth: 1.6)

41.7±0.2 41.7±0.2 41.7±0.2 41.7±0.2


(62.75) (155) (62.75)
(73.5) (73.5)
112.1±0.8
4.5 dia. Label
(depth: 1.6) 4.5 dia.
(depth: 1.6) LED indicators
LED indicators 4.5 dia.
Release key (depth: 1.6)
Release key
(10.85) (10.85) (1) (8)

B-B A-A B
26 dia.
A
Conduit cap One, Conduit

Model
D4SL-N@@@@-@N
Operating characteristics
Key insertion force 15 N max.
Key extraction force 30 N max. Two, Cover mounting screw
Pre-travel distance 15 mm max.
Movement before being locked 3 mm min.

D4SL-N@@@@-@ (Terminal Block Type)


29.2
Head cap 29.2

9
Pre-travel distance

B
39
Operation Key
A 37
Front-side mounting 22±0.2 Side mounting
26.3 26.3 Two, 4.3 dia. Three, 4.3 dia.
39 10
Mounting hole Mounting hole

Spacers
4.5 dia. 42.9
22±0.2 4 31.5 38.7±0.2 38.5
(depth: 1.6)

41.7±0.2 41.7±0.2 41.7±0.2 41.7±0.2


(62.75) (62.75)
(73.5) (179.9) (73.5)

4.5 dia. 4.5 dia. 137±0.8 4.5 dia.


(depth: 1.6) (depth: 1.6)
(depth: 1.6)
LED indicators Release key LED indicators
Release key

(10.85) (10.85) (1) (8) B

B-B A-A A 26 dia.


Conduit cap One, Conduit

Model
D4SL-N@@@@-@
Operating characteristics
Key insertion force 15 N max.
Two, Cover mounting screw
Key extraction force 30 N max.
Pre-travel distance 15 mm max.
Movement before being locked 3 mm min.

Note: Unless otherwise specified, a tolerance of ±0.4 mm applies to all dimensions.

15
D4SL-N / D4SL-NSK10-LK@

Operation key

D4SL-NK1 D4SL-NK1S

28 29 19.5
21.5 29
7 13
7

35 15 22.7
35 15 22.7

7
4.3 7
Four, R2.15 4.3
Four, R2.15

2
2

D4SL-NK1G D4SL-NK2
28 29
21.5 15.6 14.5
29
8
7
35 20 12 22.7
35 22.7 15

Two, 4.3 dia. Two, 9 dia.


7
4.3
(5.2) Four, R2.15

2 2
Mounting rubber

D4SL-NK2G D4SL-NK3

17.2 14.5
29
8

35 22.7 12 20
17.7
29
4.5 dia. 15 Angle adjustment bolt
4
Two, 4.3 dia. Two, 9 dia.
8 dia.

9 dia.
22.7 30 40 56
2
20°
Mounting rubber

Note: Unless otherwise specified, a tolerance of ±0.4 mm applies to all dimensions.

Connector Cables
D4SL-CN@
(30) L ±40 (150) Model L size
10
9
8
(5)
7
6
D4SL-CN1 1m
5
4
3 D4SL-CN3 3m
2
1
Cable *
AWG22, 10 conductors
D4SL-CN5 5m
Connector pin No. Connector
* All 10 lead wires laid bare.

Connector No. Lead wire color Connector No. Lead wire color
1 Black 6 Green/White
2 Black/White 7 Yellow
3 Red 8 Yellow/White
4 Red/White 9 Brown
5 Green 10 Brown/White

16
D4SL-N / D4SL-NSK10-LK@

Slide Key
D4SL-NSK10-LK
Open door Close door

10
40×40

12.5

Lockout key

(26.8)
(314) (232.2) (81.8) (71.8)
(35) (30.2)
(147) (112) 19.1
(35) 107 8
15+10
−5 (Between Slide Key)
(20)
11.5
B B Shot bolt

(56.5) SLIDE
LOCK
SLIDE
LOCK
17
50 (64)
SLIDE SLIDE
FREE FREE
20 (90.4)
(76.2)
Guide
38.7 (32.5)
Four, M6
Slide base mounting holes
D4SL-NK1S Three, M4
22 Operation Key
(330)

Cross-sectional view A-A


4

17 Guard Lock Safety-door Switch


A A D4SL-N
Cross-sectional view B-B
(19.5)

11.5

Two, M6 11.6
12.5 mounting holes Switch base

D4SL-NSK10-LKH
Open door Close door

10
Aluminum frame
40×40

12.5

Lockout key

(323) (71.8)
(35) (26.8) (39.2)
(147) (121) (241.2) (81.8) 19.1
(35) 107
15+10
−5 (Between Slide Key)
(20) 8
40
11.5
B B Shot bolt
(115)
(56.5) SLIDE
LOCK
SLIDE
LOCK (78)
17
SLIDE
50 (64) SLIDE
FREE FREE
20 90.4
12 dia.
(76.2) 40 dia.
38.7 (32.5) Guide Inner Lever
Four, M6
Slide base mounting holes
D4SL-NK1S
22 Operation Key Three, M4
330 4

Cross-sectional view B-B


4

Cross-sectional view A-A


17 A A
(19.5)

11.5 Guard Lock Safety-door Switch


D4SL-N@@@@-@@ 11.6
Guard Lock Safety-door Switch Two, M6 Switch base
D4SL-N@@@@-@@N 12.5 mounting holes

17
D4SL-N / D4SL-NSK10-LK@

Operation key Mounting

D4SL-N+D4SL-NK1
With Front-inserted Operation Key With Top-inserted Operation Key

Horizontal
59 min. insertion radius
(37) >180
61.5 max. R=
Key insertion
position
(15)
Center tolerance of
key hole: ±0.8 Horizontal Vertical
insertion radius insertion radius Center tolerance of
R>=180 Center tolerance of
R>=200 key hole: ±0.8
Vertical (15) key hole: ±0.8 9
insertion radius
59 min. (37) >200
R=
61.5 max.
Key insertion 60.5 min. 60.5 min.
position 63 max. 63 max.
Key insertion Key insertion
(38.5) position (38.5)
31.5 position

Center tolerance of
key hole: ±0.8

D4SL-N+D4SL-NK1S
With Front-inserted Operation Key With Top-inserted Operation Key

Horizontal
50.5 min. insertion radius
(37) >180
53 max. R=
Key insertion
position
(15)
Center tolerance of
key hole: ±0.8 Horizontal Vertical
insertion radius insertion radius Center tolerance of
R>=180 Center tolerance of
R>=200 key hole: ±0.8
Vertical (15) key hole: ±0.8
insertion radius 9
50.5 min. (37) >200
R=
53 max.
Key insertion 52 min. 52 min.
position 54.5 max. 54.5 max.
(38.5) Key insertion (38.5) Key insertion
31.5 position
position

Center tolerance of
key hole: ±0.8

D4SL-N+D4SL-NK1G
With Front-inserted Operation Key With Top-inserted Operation Key

Horizontal
59 min. insertion radius
(37) >120
61.5 max. Pitch 12 mm R=
Pitch 20 mm R> =170
Key insertion
position

Horizontal
(Pitch 12 mm) Center tolerance of insertion radius
(Pitch 20 mm) key hole: ±0.8 >120 Center tolerance of Vertical Center tolerance of
Pitch 12 mm R=
key hole: ±0.8 insertion radius key hole: ±0.8
Pitch 20 mm R> =170
(Pitch 12 mm) R>=140
Vertical (Pitch 20 mm) 9
59 min. insertion radius (6.4)
(37) >140
61.5max. R=
Key insertion 60.5 min. 60.5 min.
position 63 max. 63 max.
Key insertion Key insertion
(38.5) (38.5)
(28.9) 31.5 position position

Center tolerance of
key hole: ±0.8

18
D4SL-N / D4SL-NSK10-LK@

D4SL-N+D4SL-K2
With Front-inserted Operation Key With Top-inserted Operation Key

Horizontal
53.1 min. insertion radius
(37)
55.6 max. R>=180

Key insertion
position

(15) Center tolerance of


key hole: ±0.8 Horizontal Vertical
insertion radius Center tolerance of
insertion radius
R=>180 Center tolerance of key hole: ±0.8
(15) key hole: ±0.8 R>=200
Vertical
(17)
53.1 min. insertion radius
(37) R> 9
55.6 max =200

Key insertion
54.6 min. 54.6 min.
position
57.1 max. 57.1 max.
Key insertion Key insertion
31.5 (39.5) (38.5) (38.5)
position position

Center tolerance of
key hole: ±0.8

D4SL-N+D4SL-NK2G
With Front-inserted Operation Key With Top-inserted Operation Key

Horizontal
insertion radius
54.7 min. (37) >120
Pitch 12 mm R=
57.2 max. >170
Pitch 20 mm R=
Key insertion
position

Horizontal
(Pitch 12 mm) Center tolerance of
insertion radius
(Pitch 20 mm) key hole: ±0.8 Center tolerance of Vertical Center tolerance of
Pitch 12 mm R> =120 key hole: ±0.8 insertion radius key hole: ±0.8
Pitch 20 mm R> =170 (Pitch 12 mm) R>=140
Vertical (Pitch 20 mm) (21.5)
54.7 min. insertion radius 9
57.2 max. (37) >140
R=
Key insertion
56.2 min. 56.2 min.
position
58.7 max. 58.7 max.
Key insertion Key insertion
31.5 (39.5) (38.5) (38.5)
position position

Center tolerance of
key hole: ±0.8

D4SL-N+D4SL-NK3
With Front-inserted Operation Key With Top-inserted Operation Key

Horizontal
55.2 min. insertion radius
55.7 max. (37) >50
R=
Key insertion
position

(40±0.15)

(40±0.15) Center tolerance of


Center tolerance of Horizontal
key hole: ±0.8 key hole: ±0.8 Vertical
insertion radius Center tolerance of
>50 insertion radius
R= key hole: ±0.8
R>=200
Vertical
55.2 min. insertion radius (9)
(37) >200
55.7 max. R=
Key insertion 56.7 min. 56.7 min.
position 59.2 max. 59.2 max.
(38.5) Key insertion (38.5) Key insertion
31.5 position position

Center tolerance of
key hole: ±0.8

19
D4SL-N / D4SL-NSK10-LK@
Application Example
G9SA-321-T@ (24VAC/VDC) +D4SL-N@R@A-@ (Mechanical Lock Type) / Manual Reset

Lock release signal


KM1
S1: Safety Limit Switch with direct opening mechanism
KM2 (D4B-N, D4N or D4F)
S2 S2: D4SL-N
S4 9 10
S3: Reset switch
S4: Lock release switch
42
KM1 and KM2: Magnetic Contactor
41 M: 3-phase motor
12

11

1 2 3 4 5 6 7 8 to PLC
to PLC
Guard

S1
Feedback loop
OPEN
KM1

S3 KM2
Stop signal

A1 A2 T11 T12 T31 T32 13 23 33 43 53 61

1 3
TH K3 4
a K1 K2 K3 1
SA 2
a K4 3
4
K1 OffDelay Control 2 K1 JP 5
b K4 5 6
K2 Timer Circuit
K2
b
6
PE T21 T23 T22 A B 14 24 34 44 54 62

KM1 KM2

Timing Chart
(Operation instruction)
Guard opens Motor controller

Limit switch S1
Guard Lock KM1
Safety-door Switch S2

Lock release signal KM2

S4
Guard can be opened
Stop signal
M
Reset switch S3

K1 and K2 (NC) Note: 1. The above circuit diagram is for Category 3.


2. Numbers inside the boxes are terminal numbers printed on the
K1 and K2 (NO)
product.
K3 and K4 (NC)

K3 and K4 (NO)

KM1 and KM2 (NC)

KM1 and KM2 (NO)

Operation instruction

Motor rotation
OFF-delay time

20
D4SL-N / D4SL-NSK10-LK@

G9SA-301 (24 VAC/VDC)+D4SL-N@Q@G-@ (Solenoid Lock Type) / Auto-reset

Lock signal
S2 S1: Safety Limit Switch with direct opening mechanism
9 10 (D4B-N, D4N or D4F)
S2: D4SL-N
42
KM1 and KM2: Magnetic Contactor
41 M: 3-phase motor
12

11

1 2 3 4 5 6 7 8 to PLC

to PLC
S1
12 Feedback loop

OPEN 11 KM1

KM2

Operation signal

A1 A2 T11 T12 T31 T32 13 23 33 41


3
1 4
TH
a K1 K2 K1
1
SA K2 2
3
4
K1 a Control 2 JP 5
b Circuit 5 6
b K2

6
PE T21 T23 T22 A B 14 24 34 42

KM1 KM2

(Operation instruction)
Motor controller

KM1
Timing Chart
Guard opens
KM2
Limit switch S1
Guard Lock
Safety-door Switch S2

Operation signal M

Lock signal
Note: 1. This circuit diagram is for Category 4.
K1 and K2 (NC) 2. The lock can be released at any time. Therefore, do not use a
model with a solenoid lock in applications where the operator
K1 and K2 (NO)
may be exposed to danger when the guard opens. Use a model
KM1 and KM2 (NC)
with a mechanical lock.
3. Numbers inside the boxes are terminal numbers printed on the
KM1 and KM2 (NO) product.

21
D4SL-N / D4SL-NSK10-LK@
Safety Precautions
Be sure to read the precautions for All Safety Door Switches in the website at:http://www.ia.omron.com/.

Indicates an imminently hazardous Precautions for Safe Use


situation which, if not avoided, is likely to
DANGER result in serious injury or may result in D4SL-N
death. Additionally there may be severe Operating Environment
property damage. Do not use the Switch submersed in oil or water or in locations
continuously subject to splashes of oil or water. Doing so may result
Indicates a potentially hazardous situation in oil or water entering the Switch. (The IP67 degree of protection of
CAUTION which, if not avoided, may result in minor the Switch specifies the amount of water penetration after the Switch
or moderate injury or in property damage. is submerged in water for a certain period of time.)

Precautions Supplementary comments on what to do Wiring


for Safe Use or avoid doing, to use the product safely. • Do not switch circuits for three or more standard loads (125 VAC,
1A). Doing so may adversely affect insulation performance.
Precautions Supplementary comments on what to do • Do not allow the load current to exceed the rated value.
or avoid doing, to prevent failure to For metal connector, use a connector with the screw length of 9
for Correct operate, malfunction or undesirable effect mm or less. Otherwise it may result in electric shock.
Use on product performance. • Do not use metallic conduits. In the event of damage to the conduit
opening, this may cause seal failure and may result in electric
shock.
DANGER • Do not use a metal connector for a 1/2-14NPT connector. In the
event of damage to the conversion adapter, this may cause seal
Injury may occasionally occur. Always check to make failure and may result in electric shock.
sure that the safety functions operate correctly before • Always attach the cover after completing wiring and before using
using the machine. The safety functions may not the Switch. Do not supply power when the cover is not attached.
Electric shock may occur if the Switch is used without the cover
operate correctly because of wiring mistakes, setting
attached.
mistakes, or Switch malfunction, causing some
• When using the terminal block type, make sure that foreign
machines to continue operating in situations where
material does not adhere to the terminal block board. Otherwise a
they should be stopped.
short circuit may occur between terminals and safety functions
may fail to work properly.

CAUTION Installation
• Make sure the Switch is mounted securely to prevent it from falling
D4SL-N
off. Otherwise injury may result.
Injury may occasionally occur. When the Switch • Do not use a Switch as a stopper. Head Stopper
function is damaged, some machines may continue Be sure to install a stopper as shown in the
operating in situations where they should be stopped. following illustration so that the Operation
Key does not touch the head.
Do not impose a force exceeding the key holding
Do not subject the Switch to a shock that
force.
exceeds the Switch's shock resistance of
Always provide a lock separate from the Switch, Operation Key
1,000 m/s2.
attach a warning seal to avoid excessive force applied
to the Switch, or provide an indicator lamp to show the Switch
locked/unlocked status of the door.

D4SL-NSK10-LK@
Do not use this product mounted so that it slides
vertically.
This may cause malfunction, resulting in personal
injury.

Do not insert the operation key with the door open.


Devices may start to operate, resulting in injury.

22
D4SL-N / D4SL-NSK10-LK@

D4SL-NSK10-LK@
• Do not drop the Product. Doing so may prevent the Product from Precautions for Correct Use
functioning to full capacity.
D4SL-N
• Mount the Product securely to prevent it from falling. Otherwise,
injury may occur.
Solenoid Lock Models
• Do not attempt to disassemble or modify the Switch. Doing so may • Be sure to supply power to the solenoid after the door is closed
cause the Switch to malfunction. (after the Operation Key is inserted).
• Make sure that the gap between the shot bolt and the guide is ±0.5 • The solenoid lock locks the door only when power is supplied to the
mm. solenoid. Therefore, the door will be unlocked if the power supply
Otherwise, excessive wear or damage may cause malfunction. to the solenoid stops. Therefore, do not use solenoid lock models
• To ensure safety, do not operate the Switch with anything other for machines that may be operating and dangerous even after the
than the Slide Key Unit. machine stops operating.
• Your hand may be injured by being pinched between the Operation
Key and Switch when closing the door with your hand on the
Release Key
• The release key is used to unlock the Switch in case of emergency
Product.
• Be careful to avoid pinching your hand when operating the Slide or if the power supply to the Switch stops.
• If the release key setting is changed from LOCK to UNLOCK, the
Handle.
lock will be released and the safety door can be opened
• Do not impose a force of exceeding 1 N•m when operating the
Lockout Key. (mechanical lock models only).
Å@

Otherwise, the Product may be damaged and may not operate Front
properly. D4SL-N@@@@-@ D4SL-N@@@@-@4
To prevent damage, attach the supplied labels for display near the
Product. LOCK LOCK
• Do not force the slide handle to move when the lockout key is not
inserted. Doing so may damage the product and make operation
impossible.
• Do not force the slide handle to move when the door is locked.
Doing so may damage the product and make operation impossible.
• Do not close the door with the shot bolt removed. Doing so may
damage the product and make operation impossible.
• Turn the Lockout Key to the "SLIDE LOCK" position and remove it
when opening the door to prevent a third party from operating the UNLOCK UNLOCK
Slide Handle.
• The durability of the Switch varies considerably depending on the
Back
switching conditions. Always confirm the usage conditions by using
D4SL-N@@@@-@ D4SL-N@@@@-@4
the Switch in an actual application, and use the Switch only for the
number of switching operations given in the performance
LOCK LOCK
specifications.
• The user must not maintain or repair equipment incorporating the
Switch. Contact the manufacturer of the equipment for any
maintenance or repairs required.
• Refer to the D4SL-N Guard Lock Safety-door Switch Instruction
Sheet about storage conditions, ambient conditions,
Switch details, and handling methods.
• Do not apply excessive force in the direction of the slide. This may
damage the product and cause it to malfunction.
• Do not force the switch or cable. This may SLIDE
LOCK

damage the product. The cable should be fixed at SLIDE


FREE

a point separate from the switch.


UNLOCK UNLOCK

• After setting the release key to UNLOCK to, for example, perform
maintenance, be sure to return it to LOCK setting before resuming
operation.
• The release key is set in the unlock position at the factory for the
D4SL-N@@@A and to the lock position for the D4SL-N@@@G.
• In the unlock position, even when the door of large machines or
stamping machines is closed during preliminary adjustment, the
door will remain unlocked and the machines will not be activated.
• Do not use the release key to start or stop machines.
• The auxiliary lock must be released only by authorized personnel.
• Do not impose a force exceeding 0.2 N•m on the release key
screws. The release key may be damaged and may not operate
properly.
• To prevent the release key from being used by unauthorized
personnel, set it to LOCK and seal it with sealing wax.

Mounting Covers
• Confirm that the seal rubber has no defects before use. If the seal
rubber is displaced or raised, or has foreign particles adhered to it,
the sealing capability of the seal rubber will be adversely affected.

23
D4SL-N / D4SL-NSK10-LK@

Hinged Door Securing the Door


• If the Switch is mounted too close to the hinge, the force imposed When the door is closed (with the
on the lock will be much larger than for locations far from the hinge Operation Key inserted), the Operation
and the lock may be damaged. Mount the Switch close to the Key may exceed the set zone because
handle. of, for example, the door's own weight,
Set zone
machine vibration, or the door cushion (0.5 to 3 mm)
rubber.
Mounting
Secure the door with a stopper (hook)
Appropriate Tightening Torque so that the Operation Key remains Operation key
Loose screws may result in malfunction. Tighten the screws to the within the set zone.
specified torques.
Spacer
Cover mounting
0.4 to 0.5 N•m Do not remove a spacer. Rotate the spacer in accordance with the
screw
Switch mounting direction. Use of the Switch without spacer will
Operation Key 2.4 to 2.8 N•m (D4SL-NK@ and -NK@S) reduce the lock strength.
mounting screw 0.75 to 1.15 N•m (D4SL-NK@G)
Switch mounting
0.75 to 1.15 N•m
screw
1.8 to 2.2 N•m (except 1/2-14NPT) Mounting side
Connector
1.4 to 1.8 N•m (1/2-14NPT)
Terminal screw
* Terminal block type 0.5 to 0.6 N•m (D4SL-N@@@@-@@)
only Spacer

Switch and Operation Key Mounting Wiring


• Mount the Switch and Operation Key securely to the applicable Circuit Connection Example
tightening torque with M4 screws. Always use washers. • Direct opening contacts used as safety-circuit inputs are indicated
• The switch can be fastened more firmly by a stud (4 mm dia., 1.5 with the mark.
mm max height) inserted from back side at the hole of the switch. • DC solenoids have polarity. (E1: +, E2: −) Confirm terminal polarity
Switch mounting Operation Key mounting before wiring.
• The current of the 24 VDC solenoid is different from when it is first
Front 22±0.1 D4SL-NK1/-NK2
Two, M4
Two, M4 turned ON as to when it is in operation. To take into account
possible voltage drops, it is important to apply a rated operation
voltage.
41.7±0.15
15±0.1 • To enable the 24 VDC solenoid, it is necessary to select the
appropriate power supply capacity.
4±0.1 dia. 1.5 max. D4SL-NK1G/-NK2G • The ON and OFF contact operation will not engage
Two, M4
Side simultaneously.
10±0.1
Be sure to confirm operation under actual operating conditions.
12±0.1 or 20±0.1
22±0.1
(D4SL-N@N@@-D@)
38.7±0.1 Three, M4

D4SL-NK3 Two, M4 E1
9 (+) Door open/
41.7±0.15 LED closed detection
10 E2 switch
40±0.1 (−)
2 41 12 11 1 To safety circuit
42
4±0.1 dia. 1.5 max.
4 52 51 22 21 3 To safety circuit
• Do not impose excessive force on the key top while the operation 8 63 34 33 5 To control circuit
64
key is inserted into the switch body or drop the switch with the
Lock monitor
operation key inserted to avoid the deformation of the key or the switch
7 6

breakage of the switch body. To control circuit

• Do not use the operation key other than dedicated OMRON's


(D4SL-N@SF@-@)
(D4SL-NK@). Otherwise switch may be damaged.
• Do not use the operation key D4SL-K@. A lock will not be closed E1
9
and a machine will not be activated. (+)
Door open/
• Be sure that the operation key can be inserted properly to key hole 10 E2
closed detection
switch
with a tolerance of ±0.8 mm. (−)
1
2
• Insert the operation key into the key hole according to the specified
42 41 AND To safety circuit
4 22 21 3
“operation key insertion radius in horizontal direction”.
• When mounting at the side of switch body, mount the switch with 3
8 64 63 34 33 5 To control circuit

points including the head. Lock monitor


switch
7 6
• Attach cap heads to any operation key holes that are not being To control circuit
used.

24
D4SL-N / D4SL-NSK10-LK@

Wiring Precautions for D4SL-N@@@@-@@ Processing the Conduit Opening


• Do not wire the Switch while power is being supplied. Doing so may • Connect a recommended connector to the opening of the conduit
result in electric shock. and tighten the connector to the proper torque. The case may be
• Do not let particles, such as small pieces of lead wire, enter the damaged if excessive tightening torque is applied.
switch body when wiring. • Use the cable with the connector-specified outside diameter.
• Do not directly wire the stranded wire to the terminal block. • For the 1/2-14NPT conduit, mount a provided conversion adapter
• When connecting to the terminals via insulating tube and bar to use the connector above.
terminals, arrange the bar terminals so that they do not rise up onto
the case or the cover. Recommended Connectors
• Applicable lead wire size: AWG22 to AWG18 (0.3 to 0.75 mm2). • Use a connector with a screw section not exceeding 9 mm.
• Use lead wires of an appropriate length. Not doing so may result in Otherwise the screws will protrude into the case interior.
excess length causing the cover to rise and not fit properly. The connectors given in the following table have connectors with
• Remove the terminal block board out of the unit to perform wiring. screw sections not exceeding 9 mm.
Be sure to insert the connector properly. Use the following connectors to ensure conformance to IP67.
• Do not pull on the lead wires with excessive force. Doing so may
Applicable cable
disconnect them. Size Manufacturer Model Remarks
diameter
1 3 5 7 9 ST-PF1/2
LAPP 6.0 to 12.0 mm
40±3 mm G1/2 5380-1002
9
1 3 5
7 Ace Service Co. LS-2G 6.0 to 11.0 mm Short type
ST-M20×1.5
M20 LAPP 7.0 to 13.0 mm
5311-1020
8 10 1/2- ST-NPT1/2
4 6 LAPP 6.0 to 12.0 mm
2 14NPT 5301-6030
30±3 mm
• Use LAPP connectors together with Seal Packing (JPK-16 for G1/
2 4 6 8 10
2, or GPM20 for M20), and tighten to the applicable torque. Seal
Recommended Crimp Terminals Packing is sold separately.
• LAPP is a German manufacturer.
Manufacturer Model Applicable wire lead • Ace Service Co. is a Japanese manufacturer.
AI0.34-8 TQ AWG22
PHOENIX
AI0.5-8 WH AWG20
CONTACT
AI0.75-8 GY AWG18
L1: 14 mm max. L1
L2: 8 mm max. L2

Wiring Precautions for D4SL-N@@@@-@@N


• Do not wire the Switch while power is being supplied. Doing so may
result in electric shock.
• Do not let particles, such as small pieces of lead wire, enter the
switch body when wiring.
• Applicable lead wire size: AWG24 to AWG22 (0.2 to 0.3 mm2).
Do not apply a current of 2 A or more when using AWG24.
• Use lead wires of an appropriate length. Not doing so may result in
excess length causing the cover to rise and not fit properly.

1 2 3 4 5 6 10

1 2 10

30±3 mm

• Do not pull on the lead wires with excessive force. Doing so may
disconnect them.
• Do not forcibly insert the wired socket at the cable side into the
connector or D4SL-N’s conduit opening. Doing so may cause
cable break.
Be sure to insert the cable into the connector or D4SL’s conduit
opening before performing wiring to the socket, or insert the cable
into the connector or conduit opening from the opposite side of the
socket.

Applicable socket for cable side


Manufacturer Name Model
Housing XHP-10
J.S.T. Mfg Co. Contact
(applicable wire lead: SXH-001T-P0.6
AWG24 to AWG22)

25
D4SL-N / D4SL-NSK10-LK@

D4SL-NSK10-LK@ Differences between Lockout Key and Trapped Key


• Use this product for a lightweight door (20 kg max). Otherwise the (Reference)
product may be damaged. Trapped key
• This product is for D4SL-N Guard Lock Safety-door Switch only. Lockout key (Refer to information on the
This product cannot be used with any other manufacturer's door D4JL-@@@A-@7-@@)
switches. The door cannot be closed The door cannot be closed
• Use the Slide Handle in the direction A or B in the following figure. Closing unless the lockout key is unless the trapped key is
the door inserted in the slide and inserted in the Switch and
turned. turned.
SLIDE
LOCK
FREE
SLIDE
SLIDE
FREE
The door can be opened by The door can never be opened
LOCK
SLIDE
Opening supplying power to the Switch without both supplying power
the door solenoid without operating the to the Switch solenoid and
lockout switch. operating the trapped key.
B A
• When mounting the operation key, line up the inside edges of the
• Loose screws may result in malfunction. Use washers and tighten long operation key holes with the outer edges of the slide handle
the screws to the specified torques. Mount the Slide Base at four as in the following figure to ensure easy position adjustment.
points with screws. Adding adhesive is recommended for
preventing the screws from loosening.
Also, when mounting the Product to a door for disable-prevention
purposes, purchase and use tamper-resistant screws.

Approriate Tightening Torque


Slide Key mounting screw (M6) 6.0 to 7.0 N•m • Use the supplied special screws to mount the operation key and
D4SL-N Guard Lock Safety-door Switch.
Operation key special mounting screw • To tighten the screws, use the tip of a flat-head screwdriver on the
2.4 to 2.8 N•m
(screws supplied)
screw heads as shown in the following figure.
Switch special mounting screw
0.75 to 1.15 N•m
(screws supplied)
Note: The special screws are
Inner Lever 9 to 10 N•m designed so that they cannot
be turned counter-clockwise
Technical Specifications using a flat-head
screwdriver.
Ambient operating temperature −10 to 55°C (with no icing)
• The special screws cannot be removed once they are tightened.
Ambient operating humidity 95% max.
Mechanical durability 20,000 operations min. Mounting of innner lever
• Do not store the Switch where corrosive gases (e.g., H2S, SO2, Mounting method
NH3, HNO3 or Cl2) or dust is present, or in locations subject to high 1) Detaching of mounting screw
temperature or humidity. Remove the handle mounting screw with TORX screwdriver (T30).
• Perform maintenance inspections periodically.
Handle
• When the lockout key is attached to your wrist, be careful that the
strap does not get stuck in equipment.

Nomenclature
Hexagonal nut (M6)
Slide Key Unit Handle mounting screw
Spring washer (TORX_T30/M6)
Guide (M6)
Shot Bolt Fig.1
Slide Base
2) Mounting of inner lever
Tighten A portion of the inner lever to a suitable torque with wrench
(width across flat: 10mm).

Lockout key Slide Handle Tightening Torque

Inner lever (M6) 9 to 10 N.m


Operation Key
A
Release Key Inner lever
Spring washer
(M6)
D4SL-N Guard Lock Safety-door Switch
Fig.1

• This product is for Omron, the D4SL-NSK10 and the D4GL-SK10


only. This product cannot be used with any other products.
• Do not operate the handle with the handle mounting screw
removed. Doing so may result in malfunction.
• Be careful not to lose the spring washer and hexagonal nut when
remove the handle mounting screw. (Fig.1)
• Loose inner lever may result in malfunction. Use washers and
tighten the inner lever to the specified torque. (Fig.2)

26
READ AND UNDERSTAND THIS CATALOG
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions
or comments.

Warranty and Limitations of Liability


WARRANTY
OMRON’s exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if
specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT,
MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT
THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR
INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR
COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY,
NEGLIGENCE, OR STRICT LIABILITY.
In no event shall responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON’S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND
NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.

Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the
customer’s application or use of the product.
At the customer’s request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply
to the products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end
product, machine, system, or other application or use.

The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all
possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this document.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.

NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT
THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT IS PROPERLY RATED
AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.

Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.

It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the product may be changed without any notice. When in doubt, special model numbers may be assigned to fix
or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may
represent the result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject
to the OMRON Warranty and Limitations of Liability.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user’s programming of a programmable product, or any consequence thereof.

Copyright and Copy Permission


COPYRIGHT AND COPY PERMISSION
This document shall not be copied for sales or promotions without permission.

This document is protected by copyright and is intended solely for use in conjunction with the product. Please notify us before copying or
reproducing this document in any manner, for any other purpose. If copying or transmitting this document to another, please copy or transmit it in
its entirety.
OMRON Corporation Industrial Automation Company Authorized Distributor:
Tokyo, JAPAN
Contact: www.ia.omron.com
Regional Headquarters
OMRON EUROPE B.V. OMRON SCIENTIFIC TECHNOLOGIES INC.
Wegalaan 67-69-2132 JD Hoofddorp 6550 Dumbarton Circle,
The Netherlands Fremont, CA 94555-3605 U.S.A.
Tel: (31)2356-81-300/Fax: (31)2356-81-388 Tel: (1) 510-608-3400/Fax: (1) 510-744-1442

OMRON ASIA PACIFIC PTE. LTD. OMRON (CHINA) CO., LTD. © OMRON Corporation 2012 All Rights Reserved.
No. 438A Alexandra Road # 05-05/08 (Lobby 2), Room 2211, Bank of China Tower, In the interest of product improvement,
Alexandra Technopark, 200 Yin Cheng Zhong Road, specifications are subject to change without notice.
Singapore 119967 PuDong New Area, Shanghai, 200120, China CSM_1_2_0512
Tel: (65) 6835-3011/Fax: (65) 6835-2711 Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200 Cat. No. C146-E1-01 0512 (0412)
Mouser Electronics

Authorized Distributor

Click to View Pricing, Inventory, Delivery & Lifecycle Information:

Omron:
D4SL-N3QFA-D D4SL-N2HFA-D D4SL-N3NFG-DN D4SL-N3NFA-DN D4SL-N4AFG D4SL-N4SFG D4SL-N2GFA-
D D4SL-N3VFA D4SL-N3NFG-D D4SL-N3VFG D4SL-N2AFG D4SL-N3NFG-D4 D4SL-N4GFA-D D4SL-N4HFG-D
D4SL-N2FFA-D D4SL-N2NFA-DN D4SL-N2RFA-D D4SL-N2VFG D4SL-N3AFG D4SL-N3HFG-DN D4SL-N3QFA-
DN D4SL-N3RFG-D D4SL-NK5 D4SL-N4FFA-D D4SL-N3NFA-D4N D4SL-N3NFG-D4N D4SL-N3PFA-D D4SL-
N3PFA-D4N D4SL-N3PFA-DN D4SL-N3PFG-D D4SL-N4PFG-D4 D4SL-N4QFA-D4 D4SL-N4QFG-D4 D4SL-
N4RFA-D4 D4SL-N4RFG-D4 D4SL-N4GFG-D4 D4SL-N4HFA-D4 D4SL-N4HFG-D4 D4SL-N4NFA-D4 D4SL-
N4NFG-D4 D4SL-N4PFA-D4 D4SL-N3RFG-D4 D4SL-N4EFA-D4 D4SL-N4EFG-D4 D4SL-N4FFA-D4 D4SL-
N4FFG-D4 D4SL-N4GFA-D4 D4SL-N3HFG-D4 D4SL-N3PFA-D4 D4SL-N3PFG-D4 D4SL-N3QFA-D4 D4SL-
N3QFG-D4 D4SL-N3RFA-D4 D4SL-N3EFG-D4 D4SL-N3FFA-D4 D4SL-N3FFG-D4 D4SL-N3GFA-D4 D4SL-
N3GFG-D4 D4SL-N3HFA-D4 D4SL-N2PFG-D4 D4SL-N2QFA-D4 D4SL-N2QFG-D4 D4SL-N2RFA-D4 D4SL-
N2RFG-D4 D4SL-N3EFA-D4 D4SL-N2GFG-D4 D4SL-N2HFA-D4 D4SL-N2HFG-D4 D4SL-N2NFA-D4 D4SL-
N2NFG-D4 D4SL-N2PFA-D4 D4SL-N3NFA-D4 D4SL-N2EFA-D4 D4SL-N2EFG-D4 D4SL-N2FFA-D4 D4SL-N2FFG-
D4 D4SL-N2GFA-D4 D4SL-N3GFG-DN D4SL-N3HFA-D D4SL-N3HFA-D4N D4SL-N3HFA-DN D4SL-N3HFG-D
D4SL-N3HFG-D4N D4SL-N3FFG-DN D4SL-N3GFA-D D4SL-N3GFA-D4N D4SL-N3GFA-DN D4SL-N3GFG-D
D4SL-N3GFG-D4N D4SL-N3EFG-DN D4SL-N3FFA-D D4SL-N3FFA-D4N D4SL-N3FFA-DN D4SL-N3FFG-D D4SL-
N3FFG-D4N D4SL-N3DFG-N D4SL-N3EFA-D D4SL-N3EFA-D4N D4SL-N3EFA-DN D4SL-N3EFG-D

You might also like