Thorn Security T 1216-C
Thorn Security T 1216-C
com
EQUIPMENT: T1216W-C
PUBLICATION: MARINEW-P-I
ISSUE No. & DATE: 1 11/12
TYCO T1216W-C
Marine Fire Detection/Alarm Control Panel and Repeater
Installation and Commissioning Manual
m
.co
es
uid
-g
all
T1216W-C
MARINEW-P-I
1 11/12
List of Contents
1. LIST OF FIGURES ................................................... 3 7.8.1 C1630 OUTPUT INTERFACE
2. LIST OF TABLES .................................................... 3 CONFIGURATION ................................... 24
7.8.2 C1634 8 WAY VOLT FREE RELAY OUTPUT
3. INTRODUCTION ...................................................... 4
MODULE CONFIGURATION ...................... 24
4. INSTALLATION AND COMMISSIONING OVERVIEW ..... 4 7.9 COMMISSIONING PROCEDURE...................... 25
5. INSTALLATION ....................................................... 4 7.9.1 ALARM CIRCUITS .................................. 25
5.1 ELECTRICAL SAFETY...................................... 4 7.9.2 ZONES ................................................. 25
5.2 INSTALLATION INSTRUCTIONS ......................... 6 7.9.3 CLASS CHANGE INPUT .......................... 26
5.2.1 T1216W PANEL INSTALLATION 7.9.4 FIRE [ROUTING] OUTPUT....................... 26
INSTRUCTIONS ........................................ 6 7.9.5 FAULT [ROUTING] OUTPUT .................... 26
5.2.2 CONNECTION OF THE INCOMING AC 7.9.6 FIRE PROTECTION OUTPUT ................... 26
POWER SUPPLY ...................................... 8 7.9.7 ANCILLARY INPUTS................................ 26
5.2.3 T1200B-C BATTERY BOX INSTALLATION .. 8 7.9.8 ANCILLARY OUTPUTS ............................ 26
5.2.4 BATTERY INSTALLATION .......................... 8 7.9.9 REPEATERS [WHEN SUPPLIED] ............... 26
5.2.5 BATTERY CONNECTION ........................... 8 7.9.10 REPEATER MUSTER LINK [IF FITTED] ...... 27
5.2.5.1 CONNECTING THE BATTERY BOX TO THE 7.9.11 POWER SUPPLY UNIT. .......................... 27
PANEL PSU 9 7.9.12 T1216W-C – WMRCP INTERFACE. ...... 27
5.2.6 INSTALLATION AND CONNECTION OF THE 7.9.13 FINAL DRESSING OF THE CABLES .......... 27
C1631 REPEATER INTERFACE ................. 9 8. USER INDICATIONS.............................................. 29
5.2.7 INSTALLATION AND CONNECTION OF THE 9. USER CONTROLS ................................................ 30
C1665 MUSTER INTERFACE .................... 9 10. PCB LAYOUTS ................................................. 31
5.3 MODIFICATIONS TO THE W ATER MIST RELAY
CONTROL PANEL ......................................... 12 11. INSTALLATION DETAILS ..................................... 34
5.3.1 MODIFICATION 1 [SYSTEM ABNORMAL]: .. 12 12. WIRING DIAGRAMS ........................................... 35
5.3.2 MODIFICATION 2 [SYSTEM OPERATED]: .. 12 13. WIRING DIAGRAM NOTES .................................. 39
5.3.3 MODIFICATION 3: [FAULT INPUT FROM
T1216W-C] ......................................... 13
5.4 INTERCONNECTIONS WITH THE W ATER MIST
RELAY CONTROL PANEL .............................. 13
5.4.1 FINAL CONNECTIONS BETWEEN THE
T1216W AND WMRCP ........................ 13
5.5 REPLACING THE DISPLAY INSERTS ............... 14
5.5.1 TO CHANGE THE INSERTS ...................... 14
5.5.2 TO FIT THE OPTIONAL DOOR STAY ........ 16
6. COMMISSIONING .................................................. 17
6.1 INTRODUCTION ............................................ 17
6.2 COMMISSIONING CHECKLIST ........................ 17
6.3 AN OVERVIEW OF THE COMMISSIONING
PROCEDURE................................................ 17
6.4 PRE-COMMISSIONING W IRING CHECK .......... 17
6.5 POWERING UP ............................................. 18
6.6 CONFIGURATION .......................................... 19
6.6.1 BASIC DEFAULT CONFIGURATION........... 19
6.6.2 VESSEL-SPECIFIC CONFIGURATION ....... 19
7. OPERATING THE ENGINEER’S FUNCTIONS ............. 19
7.1 ENGINEER’S ZONE/OUTPUT CONFIGURATION
PROCESS: ................................................... 19
7.2 ZONE OR OUTPUT CONFIGURATION: ............. 19
7.3 TO RESTORE THE FACTORY DEFAULT
CONFIGURATION FOR ZONES & OUTPUTS: .... 20
7.4 ENGINEER’S ZONE/OUTPUT CONFIGURATION
TIME-OUT W ARNING: ................................... 20
7.5 INVALID CONFIGURATION CONDITIONS: ......... 20
7.6 LIST OF CONFIGURATION DIL SWITCHES AND
THEIR FUNCTIONS: ....................................... 21
7.7 LIST OF LINK CONFIGURATION FEATURES...... 23
7.8 DIL SWITCH SETTINGS ON THE REPEATER
INTERFACE BOARD: ..................................... 24
PAGE 2 of 39
All manuals and user guides at all-guides.com
EQUIPMENT: T1216W-C
PUBLICATION: MARINEW-P-I
ISSUE No. & DATE: 1 11/12
1. List of Figures 2. List of Tables
FIGURE 1 – BULK HEAD MOUNTING DETAILS .............. 7 TABLE 1 – CONTENT OF SPARES BAG......................... 6
FIGURE 2 – BATTERY CLAMP DETAILS ...................... 10 TABLE 2 – C1631 SETTINGS FOR REPEATER QUANTITY
FIGURE 3 – REPEATER CONNECTION DIAGRAM ......... 11 ............................................................. 24
FIGURE 4 – MUSTER INTERFACE W IRING DIAGRAM... 11 TABLE 3 – C1631 SETTING FOR REPEATER ADDRESSES
FIGURE 5– SYSTEM ABNORMAL MODIFICATION ........ 12 ............................................................. 24
FIGURE 6– SYSTEM OPERATED MODIFICATION......... 12 TABLE 4 – SETTING QUANTITY AND TYPE OF O/P
FIGURE 7– ADDITIONAL FAULT RELAY ...................... 13 MODULES ON THE C1630 ...................... 24
FIGURE 8 – DISPLAY INSERT REPLACEMENT............. 15 TABLE 5 – SETTING C1634 BOARD ADDRESS ........... 24
FIGURE 9– DOOR STAY ASSEMBLY .......................... 16 TABLE 6 – SETTING C1634 ZONE RANGE ................. 24
FIGURE 10 – C1627 MOTHERBOARD LAYOUT .......... 31 TABLE 7 – SETTING C1634 TO FIRE PROTECTION
FIGURE 11 – REAR RIGHT HAND SIDE OF DISPLAY PCB MODE ................................................... 25
............................................................ 32 TABLE 8 – ZONE AND ZONAL OUTPUT ALLOCATION ... 25
FIGURE 12 – C1634 RELAY OUTPUT MODULE ......... 32
FIGURE 13 – C1630 OUTPUT EXPANSION INTERFACE
............................................................ 33
FIGURE 14 – C1631 REPEATER INTERFACE BOARD . 33
FIGURE 15 – C1665 MUSTER INTERFACE BOARD ..... 33
FIGURE 16 – T1216W-C INSTALLATION DRAWING.... 34
FIGURE 17 – MAINS AC CHANGE-OVER UNIT
ELECTRICAL INSTALLATION DIAGRAM ..... 35
FIGURE 18 – T1216W-C INTERNAL LAYOUT DIAGRAM
............................................................ 36
FIGURE 19 – T1216W-C MOTHERBOARD, PSU &
REPEATER W IRING DIAGRAM................. 37
FIGURE 20 – W ATERMIST PANEL W IRING DIAGRAM .. 38
T1216W-C
MARINEW-P-I
1 11/12
3. Introduction 4. Commission the panel
Refer to section 6. Commissioning.
This manual contains all the information necessary
for the installation, commissioning and maintenance
of the T1216W panel.
5. Installation
NOTE: It is important to read this manual fully The control panel must be installed by suitably
before commencing installation. qualified technicians familiar with the installation of
fire detection and alarm systems. In addition, it is
The following supporting documentation is also recommended to refer to the following information:
available: The Current edition of the relevant wiring
T1216W-C Application Guide regulations for ships.
Related Documentation: Any specific vessel requirements.
T1200-C Sales Literature Any field device installation instructions.
T1200-C Panel Application Guide
Any data sheet provided for the installation of
T1200-C User Manual Intrinsically Safe devices.
T1200-C Log Book
Notes:
T1200-C Insert Template
The rating plate, containing essential electrical
Mains AC Changeover Unit Fixing information is located on the outside of the
Instructions. panel, on the left side.
Note: References are made throughout this The mains supply cable should be a minimum
document to “Fire Protection Output” and “Fire 2
of 1mm copper protected by a 5A fuse.
Output”. These refer to particular outputs from the
T1216W panel and are provided for specific An appropriate lockable double pole disconnect
purposes: device shall be provided as part of the vessel
installation. This device must have a minimum
Fire Protection Output: An output used to contact gap of 3mm.
activate ancillary fire protection equipment or
systems. For example, fire doors or plant
shutdown. 5.1 Electrical Safety
WARNING:
Fire Output: An output used to send a
common fire warning signal to a remote fire Prior to commencing installation of the
monitoring station. control panel, ensure that adequate
precautions are taken to prevent
References are also made to “Manual Fire Alarm”
damage to the sensitive electronic components on
and “Muster”. These relate to fire alarm sounder
the display board and the control board due to
operating modes which are activated manually from
electrostatic discharge. You should discharge any
the fire panel display. The panel is configurable to
static electricity you may have accumulated by
one or other of the two modes.
touching a convenient earthed object. You should
Detailed descriptions of both outputs are provided repeat the process at regular intervals during the
within the following text. installation process, especially if you are required to
4. Installation and Commissioning walk over carpets.
Overview If possible, wear an anti-static wrist strap connected
to a suitable earth point when working on the panel.
This section lists the steps that are taken in
installing and commissioning a T1216W system.
Reference should be made to the T1216W The panel must be located in an area which
Application manual for technical details and complies with the environmental specification
description of panel features. detailed in the T1200-C Application Manual and
should be at least 2 metres away from pager
1. Install all field wiring and equipment systems or any other radio transmitting
Refer to the Installation instructions in section equipment. The operating temperature range of
5.2. Refer to the field device installation the panel & repeater is -10ºC to +55ºC. Batteries
manuals. are housed in a separate enclosure and are
2. Install the panel rated as operational between -20ºC to +50ºC for
Refer to the installation instructions in section charging purposes. Maximum humidity is 95%
5.2. Do not connect the field equipment at this for panel, repeater & batteries.
stage.
3. Connect any repeaters (if applicable)
Refer to the installation instructions in section
5.2.
PAGE 4 of 39
All manuals and user guides at all-guides.com
EQUIPMENT: T1216W-C
PUBLICATION: MARINEW-P-I
ISSUE No. & DATE: 1 11/12
IMPORTANT NOTES ON BATTERIES: ELECTRICAL SAFETY:
DANGER: Batteries are electrically live The volt-free relay contacts provided within the
at all times, take great care never to panel must not be used to directly switch any
short circuit the battery terminals. voltage that exceeds 30V. (Please also refer to
WARNING: Batteries are often heavy; relay rating data).
take great care when lifting and A 9V battery is supplied fitted to the inside of the
transporting batteries. For weights door. This battery provides power to the buzzer in
above 24 kilos, lifting aids should be the event of total power failure or display ribbon
used. disconnection. The connecting lead of this battery is
DANGER: Do NOT attempt to remove disconnected from the display board during
the battery lid or tamper with the shipping.
internal workings of the battery. 1. DO NOT short circuit the battery terminals or
Electrolyte is a highly corrosive the connecting lead.
substance, and presents significant danger to 2. DO NOT remove this battery unless it
yourself and to anything else it touches. In case of measures 8V or less.
accidental skin or eye contact, flush the affected
3. DISCONNECT THE LEAD from the display
area with plenty of clean, fresh water and seek
board BEFORE replacing the battery to avoid
immediate medical attention.
accidental polarity reversal which may damage
Valve Regulated Lead Acid (VRLA) batteries are the display circuitry.
“low maintenance”, requiring no electrolyte top-
4. ALWAYS secure the battery in the battery
up or measurement of specific gravity.
holder with a Tie-wrap.
WARNING: Only clean the battery case with a cloth
5. DO NOT use rechargeable batteries as these
that has been soaked or dampened with distilled
will gradually discharge due to internal
water. Do not use organic solvents (such as petrol,
resistance.
paint thinner, benzene or mineral spirits) or other
materials that can substantially weaken the case.
Do not use a dry cloth as this will generate static Some of the panels covered by this manual
electricity, which in turn may lead to an explosion. require a 110 or 230V AC supply. Refer to the
WARNING: Avoid operating temperatures outside equipment rating plate and T1200-C Application
the range of -15C/5F to +50°C/122°F for Manual for detailed information.
float/standby applications. All installation work should be carried out in
The recommended normal operating temperature is accordance with the recommendations of the
20°C. current edition of the IEE regulations by
suitably qualified and trained personnel.
HIGH TEMPERATURE will reduce battery service
life. In extreme cases this can cause Thermal
Runaway, resulting in high oxygen/hydrogen gas This is an IEC Class 1 electrical
production and battery swelling. Batteries are appliance and therefore must have
irrecoverable from this condition and should be the chassis connected to an
replaced. electrical earth.
LOW TEMPERATURE will prolong battery life but
reduce output capacity.
DANGER: Do not incinerate batteries.
If placed in a fire, the batteries may
rupture, with the potential to release
hazardous gases and electrolyte.
VRLA batteries contain substances
harmful to the environment.
Exhausted batteries must be recycled.
Return them to the battery
manufacturer or take them to your
Council waste disposal site for
appropriate disposal.
T1216W-C
MARINEW-P-I
1 11/12
Table 1 – Content of Spares Bag
Quantity Description Type
1 Mains Fuse T5AH250V 20mm
1 Battery Fuse T8AH250V 20mm
16 End-of-Line resistors for zone circuits 10k 0.25W
4 End-of-Line resistors for alarm circuits 3k9 0.25W
3 End-of-Line resistors for monitored outputs 3k9 0.25W
Key Ref - 801
2 Access Control key
Part no 509.023.061
Red – 250mm
m
1 Positive battery lead
1 Negative battery lead Black – 300mm
1 Battery coupling lead Blue – 250mm
1 Tie wrap cable clip for securing mains lead
8 Neoprene washers for box fixing Part no 2400174
.co
1 Total power failure battery [PP3] Supplied fitted
1 Alternative Button test insert Panel - English
1 x THORN
TYCO & THORN Logo Labels Self-Adhesive Label
1 x TYCO
1 T1200C Documentation CDROM CDROM
es
5.2 Installation Instructions 6. Locate the earth strap connected to the door.
Pull the earth strap connector off the spade
1. Carefully remove the control panel from the
terminal on the door.
packing and lay the panel on a flat surface.
7. Use a suitable flat blade screwdriver to
2. Locate the spares bag (either inside the
unscrew the hinges whilst supporting the door.
packing box or inside the panel) and check
that the items shown in Table 1 above are 8. Place the door and hinge fixing screws
uid
the opposite side of the enclosure. The installation the spade terminal on the enclosure
instructions below apply to top or bottom cable backbox.
entry. (b) Remove the two cross-head screws at the
bottom left & right corners of the chassis
1. Ensure that the panel is on a flat surface with (towards the gland plate).
the door facing up.
all
PAGE 6 of 39
All manuals and user guides at all-guides.com
EQUIPMENT: T1216W-C
PUBLICATION: MARINEW-P-I
ISSUE No. & DATE: 1 11/12
electronic components on them. You must place NEOPRENE WASHER
these items in a location where they will not be ENCLOSURE
damaged. Use the packing box to place these NEOPRENE WASHER
items inside, ensuring that the door & chassis M5 STAINLESS STEEL WASHER
M5 STAINLESS STEEL BOLT
remain separated. Store them in a safe place
which is clean, dry and dust-free.
Note: Do not allow the door & chassis to
come into contact with the packing foam as
this may hold a static charge.
11. Locate the earth lead connecting the gland BULKHEAD
plate to the earth bar. Disconnect the earth M5 STAINLESS STEEL WASHER
M5 STAINLESS STEEL NUT
lead from the earth bar.
12. Remove the screws securing the gland plate to Figure 1 – Bulk Head Mounting Details
the enclosure. Remove the gland plate.
For Console mounting:
13. Use a centre punch and hammer to remove
the required knock-outs by placing the centre (a) Cut a suitable hole in the console to fit the
punch diagonally opposite the fixing point on enclosure. Dimensions are shown in
the knockout and striking the centre punch with section 11.
the hammer. DO NOT remove the knock-outs (b) Identify the four holes in the outer flange
from any unused cable entries. of the enclosure that are used to mount
14. Refit the gland plate ensuring that the seal is the enclosure in a console.
correctly seated. (c) Insert the enclosure into the console. Note
15. Re-connect the earth lead from the gland plate that the flange will not sit flush with the
to the earth bar. console at this stage because of the four
For Bulk Head mounting: bushes used for securing the door.
(d) Mark the centre positions of the four
(a) Identify the four indented holes in the
bushes. Remove the enclosure and drill
back of the enclosure that are used to
suitable sized holes to accommodate the
mount the enclosure.
bushes (13mm to 15mm diameter).
(b) Mark the location of one of the upper
(e) Insert the enclosure into the console and
fixing holes on the wall/bulkhead. Drill and check that the flange now sits flush with
fix with a suitably plated or stainless steel
the console. Drill suitable mounting holes
M5 nut, bolt and washers (fixings not
in the console & fix with M5 counter sunk
supplied). The fixing must be sealed using
screws.
two neoprene washers [supplied with the
panel fixing kit], one fitted between the 16. Bring all field wiring into the enclosure through
panel and the bulkhead and the other suitable cable glands, ensuring that the cable
fitted between the panel and the steel conductors are of sufficient length inside the
washer inside the panel. See Figure 1 – enclosure (at least 30cm). Waterproof glands
Bulk Head Mounting Details. Do not fully and seals should be used to maintain ingress
tighten at this stage. protection against water. Ensure that all
conductors are clearly labelled. Any unused
(c) Level the panel and fix the remaining cable entries which are open must have
fixing points as above. waterproof knockout seals fitted.
(d) Check that neoprene seals have been
17. Connect the earth drain wires of the field
fitted as shown in Figure 1 then fully
cabling to the earth bar(s) positioned at the
tighten all of the fixing nuts & bolts.
back of the back-box. Up to two drain wires
(e) Check that the enclosure is firmly seated may be connected to each terminal.
against the bulk head and is not deformed 18. Ensure that the electrical continuity of any
in any way.
cable shield is maintained through to the last
device on the circuit. The shield must only be
connected to enclosure earth in the panel by
using the earth bars provided.
19. Clear any dust and debris from inside the
enclosure.
20. Reinstallation of the chassis is the reverse of
removal. Ensure that all keyholes on the
T1216W-C
MARINEW-P-I
1 11/12
chassis are fully mounted onto the posts in the washers [supplied with the fixing kit], one
back-box. fitted between the panel and the bulkhead
21. Reconnect all earth wires and ensure none are and the other fitted between the panel and
trapped between the chassis and back-box. Do the steel washer inside the panel. See Figure
not connect the field wiring at this stage. 1 – Bulk Head Mounting Details. Do not fully
tighten at this stage.
22. Refit the door. The refitting procedure is the
reverse of removal. Ensure that the earth strap (c) Level the enclosure and fix the remaining
and ribbon cable are reconnected correctly. fixing points as above.
23. If a door stay is supplied then this should now (d) Check that neoprene seals have been fitted
be fitted following the instructions in section as shown in Figure 1 then fully tighten all of
5.5.2. the fixing nuts & bolts.
24. Connect the incoming protective earth (e) Check that the enclosure is firmly seated
conductor to the Earth terminal in the mains against the bulk head and is not deformed in
terminal block. This is the primary earth point any way.
and is labelled [Also labelled E]; see (f) Mount the fused terminal box (not supplied)
section 12. Wiring Diagrams. adjacent to the battery box and fit a suitable
waterproof coupling to allow cable entry from
25. NOTE: When shutting the door of the panel, the terminal box to the battery box.
DO NOT over tighten the thumb-screws.
Tighten until finger-tight and then turn another 5.2.4 Battery Installation
quarter-turn using a screwdriver. The T1200B-C battery box will only hold 2 x 17Ah
5.2.2 Connection of the incoming AC PowerSonic SLA batteries.
Power Supply 1. Remove the battery clamps from the battery
Note: For installations requiring the Mains AC box before fitting the batteries.
switch-over unit, a 24Vdc supply will need to be 2. Place the left-hand battery into the battery box.
connected from the panel to the AC mains switch- The battery should be located toward the left
over unit to drive the LED indications. See Figure side of the enclosure, the battery terminals
17 for wiring details. should be positioned towards the front.
1. With both poles of the incoming power supply 3. Place the right-hand battery into the battery
safely isolated at the feeder end, connect the box. The battery should be located toward the
Live [AC] conductor to the mains terminal right side of the enclosure, the battery
block [L terminal] as shown in section 12. terminals should be positioned towards the
Wiring Diagrams. front.
2. Connect the Neutral [AC] conductor to the 4. Fix the battery retaining clamps. [See Figure 2]
mains terminal block [N terminal] as shown in
section 12. Wiring Diagrams. 5.2.5 Battery Connection
3. Secure the incoming supply cable using the
1. Connect the black battery lead to the terminal
cable tie supplied. NOTE: The cable tie should
marked BAT-, connect the red battery lead to
be over the outer cable insulation.
the terminal marked BAT+.
5.2.3 T1200B-C Battery Box Installation 2. The Thermistor assembly is supplied loose in
The T1200B-C battery box can only be bulk head the fixing kit supplied with the T1216W-C
mounted. The incoming cable must have an in-line panel. Connect the Thermistor leads to the
fuse in the positive power supply (fuse type: T6.3A terminals marked THERM.
HRC). The fuse must be mounted external to the 3. Tie-wrap the Thermistor to one of the battery
battery box, in a suitable terminal box which is leads so that when the battery leads are
close-coupled to the battery box. See Figure 19 for connected, the Thermistor is located just
wiring details. above one of the batteries.
To mount the T1200B-C battery box: 4. The blue lead is used to connect the batteries
together. Do not connect this lead until you are
(a) Identify the three indented holes in the back ready to power up the panel.
of the enclosure that are used to mount the
enclosure.
(b) Mark the location of one of the upper fixing
holes on the wall/bulkhead. Drill and fix with
a suitably plated or stainless steel M5 nut,
bolt and washers (fixings not supplied). The
fixing must be sealed using two neoprene
PAGE 8 of 39
All manuals and user guides at all-guides.com
EQUIPMENT: T1216W-C
PUBLICATION: MARINEW-P-I
ISSUE No. & DATE: 1 11/12
5.2.5.1 Connecting the battery box to Notes:
the panel PSU One repeater will draw up to 75mA which means
1. Run a suitable 4-core shielded cable between that the total resistance of the cable should not
the panel and the battery box. exceed 24 Ohms (12 Ohms in each core). The
2. Label each core appropriately (BAT+, BAT-, T1216W-C Application Guide lists cable types with
THERM, THERM). their nominal DC resistance.
3. Connect the negative battery conductor to the If more than one repeater is required or the cable
“Batt -” [battery negative] terminal and connect resistance is too great, then data cable is
the positive battery conductor to the “Batt +” unsuitable for supplying power and a separate
[battery positive] terminal. Both terminals are suitable 2-core cable must be used.
situated on the panel chassis. Use only Plenum rated screened data cable with at
4. Connect the Thermistor leads to the two least three core-pairs to accommodate repeater
terminals marked “Therm” on the panel chassis. communication & Muster Interface options. 4 pairs
5. Warning: Do not connect the leads to the battery will be required if power is also being provided
at this stage. Connection of the batteries will (subject to the limitations described above).
power up the panel even if the mains supply is Connect the cable screen to earth at the fire alarm
off. panel and the repeaters.
5.2.6 Installation and connection of
5.2.7 Installation and connection of the
the C1631 Repeater Interface
C1665 Muster Interface
Warning: Observe anti-static precautions
Warning: Observe anti-static precautions
The C1631 interface board is not provided as
standard with the panel. It is included in the spares The C1665 interface board is not provided as
kit of the repeater panel, to be fitted in the main fire standard with the panel. It is an optional item that
alarm panel when required. can be ordered separately and used with repeaters
to provide Muster Alarm control from repeater
1. Ensure that the panel and repeaters are panels.
powered down and the main and standby 1. Ensure that the panel and repeaters are
supplies are disconnected. powered down and the main and standby
2. On the fire alarm panel remove the jumper link supplies are disconnected.
at J22 (adjacent to J9) and fit a C1631 2. On the C1627 motherboard in the fire alarm
repeater interface to connectors J13 and J9 on panel and each repeater, identify link J23 and
the right-hand side of the C1627 motherboard. connector J2 which are located on the left
The board should be held in place by the hand side of the motherboard.
12mm high plastic spacer provided. See 3. Remove link J23 and carefully plug the C1665
Figure 10. PCB into connectors J2 and J23.
3. The Repeater is supplied with the C1631 4. Connect the field cable as shown in Figure 4.
Interface Board fitted. 5. Connect 2 off 3K9 monitoring resistors to the
4. Connect the RS485 data cable as shown in C1665 in the last repeater as shown in Figure
Figure 3. 4. [The resistors are supplied in the Muster
Interface fixing kit].
5. Connect the Aux 24Vdc supply from the panel
to the repeater. You can use two cores in the 6. On the fire alarm panel display PCB fit link J2
data cable for this purpose only if the voltage to the lower position for Muster operation
drop between the panel and repeater is not Note:
more than 2Vdc. Use three cores of the RS485 screened data
cable.
BACKBOX
11/12
PAGE 10 of 39
T1216W-C
MARINEW-P-I
T+
BA
T-
BA
N/C
E RM
TH
TH
E RM
3 WAY PSU TERMINAL
BLOCK (2 OFF)
EARTH POST
RATING LABEL
Fir
e
Th Ala
orn rm
Se Sys
cu te
rity m
KM
EARTH POST 95
74
Ltd
Ap 4
00
prov 86
-C
al: PD
Stan -555
da 92
rds: 1
Pr
od 00
uc 86
t: /09
Pa
rt
Se No:
ria
Inpu l No
Fu t: :
se
:
Mad
e in
Isol Great
DOOR ate Br
Ope Su itian
pp
TH ning ly
IS Be
BE UN Covefore
EA IT M r
RT US
HE T
D
DOOR SEAL
BATTERY CLAMPS
All manuals and user guides at all-guides.com
EQUIPMENT: T1216W-C
PUBLICATION: MARINEW-P-I
ISSUE No. & DATE: 1 11/12
GND
m
A
B
A
.co
[Top right hand corner of C1626 motherboard]
T1200 repeater panel [max 5 off]
[Top right hand corner of C1627 motherboard]
T1216W fire detection/alarm panel
2 off 3k9
resistors
M in Sin GND M out S out GND M in Sin GND M out S out GND M in Sin GND M out S out GND
-g
C1665 Muster
C1665 Muster C1665 Muster
Interface in Fire
Interface in Repeater Interface in last
Panel
Panel 1 Repeater Panel
all
T1216W-C
MARINEW-P-I
1 11/12
5.3 Modifications to the Water Mist 5.3.2 Modification 2 [System Operated]:
Relay Control Panel Refer to Figure 6 for details.
Three modifications to the Water Mist Relay Control Replace the 6k8 monitoring resistor connected
Panel [WMRCP] are necessary to provide the between wires 315 and 316 with a 10k 0.25W.
correct interface. See Modifications 1, 2 and 3 in Use two spare field terminals to connect 680 Ohm 1
section 13. Watt resistor in series with R44/3.
These modifications should be carried out by Relay shown in
either the Engineer responsible for the WMRCP quiescent
or under their direct guidance and instruction. (non-alarm)
condition TB5/1
315
R50/2
Site Wiring to
T1216W-C
10k
TB5/4 U3 Resistor U4
314
Wire
Link
After Modification
PAGE 12 of 39
All manuals and user guides at all-guides.com
EQUIPMENT: T1216W-C
PUBLICATION: MARINEW-P-I
ISSUE No. & DATE: 1 11/12
5.3.3 Modification 3: [Fault Input from The Engineer responsible for the
T1216W-C] commissioning of the WMRCP system is
available and a procedure is in place which
The Fault Signal Interface Relay includes the allocation of the various tasks
Refer to Figure 7 for details. associated with carrying out the final
The common fault relay logic circuit within the connections between the panels and testing
WMRCP operates at 220Vac. It is recommended the T1216W-C--WMRCP system as a whole.
that an additional relay is installed within the Any other vessel-specific precautions and
WMRCP and contacts on this interface relay be requirements are in place.
used to switch the 220Vac signal. Details for the See Figure 19 and Figure 20 for details of the
connections are shown in Figure 19 and Figure 20. interconnections between the T1216W-C and
Generic specification for the interface relay: WMRCP.
Octal or 11-pin type. WARNING:
Coil operating voltage range: 21Vdc to 28.5Vdc. THE WMRCP CONTAINS HAZARDOUS
Contacts required: 1 x volt-free changeover VOLTAGES.
rated 1A at 250Vac minimum.
5.4.1 Final Connections between the
Terminal socket with relay retaining clip.
Temperature range -20 to +70 deg C. T1216W and WMRCP
Relay and socket approved to VDE or similar. This procedure assumes that all interconnecting
Fit the fault interface relay [RL FLT I/F] and connect cabling between the two panels has been correctly
the N/O contact [relay de-energised] into TB2 installed, tested and the cores checked through and
terminals 7 and 8. identified at each end.
Site wiring 1. At the T1216W-C, ensure the panel is safe to
from Interface relay work on as described above.
T1216W-C shown de-energised
2. Terminate the 15 cores for 14 zone fire signals
[T1216W-C fault]
24Vdc Panel
and common return into the appropriate
N/C terminals in the T1216W-C. The 8 signal wires
wiring
TB2/7 for zones 1 to 8 should be connected to the
50V 1Amp diode N/O
pole of relays 1 - 8 on the C1634 address 1.
[for suppression] P [This is the left hand one of an adjacent pair of
TB2/8 C1634 output boards]. Signals for zones 9 to
14 should be connected to the pole of relays 1
Switched
- 6 on the C1634 address 2. [This is the right
0Vdc
hand one of an adjacent pair of C1634 output
Circuit Diagram for Additional Fault
boards].
Interface Relay to be fitted in WMRCP
3. The common return wire should be connected
Figure 7– Additional Fault Relay into the normally open contact terminal on
relay 1A and a link should be installed to
5.4 Interconnections with the Water common up all of the normally open contacts
on both C1634 boards. See Figure 20 for
Mist Relay Control Panel
details.
The Water Mist Relay Controls Panel [WMRCP] is
4. Record the identification numbers of each core
supplied by Tyco Safety Product Korea.
and its use [e.g. “Zone 1 fire signal”].
This document assumes that the WMRCP is fully
5. At the WMRCP, ensure the panel is safe to
and correctly installed and tested prior to carrying
work on as described above.
out the final connections to the T1216W-C.
6. Identify the 15 cores of cable for each of the
Before attempting access to the WMRCP to
controls. Using the WMRCP documentation,
carry out any modifications and connections
connect each core into the appropriate
between the T1216W-C panel and the WMRCP,
terminal on the WMRCP.
ensure:
7. In the WMRCP, identify the terminals for
All the current technical documentation is
[Watermist] System Operated output signal [as
available for the WMRCP.
modified under section 5.3.2]. Connect 2 cores
That the WMRCP is safe to work on and the to the appropriate terminals. Record the core
Water Mist System and any other plant or identification reference and circuit use.
equipment connected to or controlled by the 8. In the WMRCP, identify the terminals for
WMRPC is isolated/locked off and safe. [Watermist] System Abnormal output signal [as
All necessary permits to work are in place. modified under section 5.3.1]. Connect 2 cores
© 2012 Thorn Security Ltd PAGE 13 of 39
Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE
All manuals and user guides at all-guides.com
T1216W-C
MARINEW-P-I
1 11/12
to the appropriate terminals. Record the core 5.5.1 To change the inserts
identification reference and circuit use.
1. Isolate the mains supply to the panel.
9. In the WMRCP, identify the additional fault
2. Disconnect the batteries at the battery box.
interface relay described in section 5.3.3. The
normally open relay contacts [relay de- 3. The panel buzzer will sound continuously due
energised] should be connected to terminals 7 to total loss of power. Open the panel door.
and 8 on TB2. Connect 2 cores of the field 4. Locate and disconnect the wire from the 9V
cable to the relay coil. Record the core battery holder at J4 on the back of the display
identification references, circuit purpose and board (bottom-centre). [The PP3 battery is
polarity. [The core connected to the cathode of fixed to the display frame below the display
the suppression diode will be the +ve core]. board]. The buzzer will silence.
10. At the T1216W-C, identify the cable cores 5. Disconnect the buzzer lead from the display
connected to the WMRCP for the [Watermist] board (either connected at the bottom (J5) or
System Operated and [Watermist] System top (J6).
Abnormal outputs. Connect System Operated 6. Use an M3 box spanner to loosen and remove
to Z15+ and Z15- on the C1627 motherboard. the nuts and plain washers holding the display
Connect System Abnormal to Z16+ and Z16-. frame. Store the nuts and washers safely for
Polarity is not important. re-fitting.
11. At the T1216W-C, identify the cores for the 7. If the optional door stay is fitted then this will
signal to the additional fault interface relay in need to be removed from the frame.
the WMRCP. Test the circuit to ensure the
8. Remove the frame and store it safely.
cable is fault free and the cores are marked
with the correct polarity. Connect the cores as 9. To separate the display from the seal, carefully
follows: apply moderate pressure to the front of the
display at the edge of the rectangular hole in
T1216W-C Terminal on the door. Work progressively from the starting
Cable Core
C1627 Motherboard point around the edge of the PCB back to the
positive Aux DC 24V starting point.
negative Fault Routing C/- 10. When the display PCB is free of the seal,
remove the PCB from the door studs. Carefully
12. Install a wire link between Aux DC 0V and work the PCB off the studs keeping the PCB
Fault Routing terminal P. parallel to the door to prevent it jamming.
13. Ensure that the 6-way link below the Fault 11. The insert tabs can clearly be seen projecting
Routing terminals is removed to allow the relay from the edge of the PCB. Pull the tabs
to operate as volt-free contacts. carefully to remove the inserts.
14. This completes the connections required. 12. To re-fit an insert, locate the gap between the
PCB and the overlay and slide a corner of the
5.5 Replacing the Display Inserts insert in. Straighten the angle of entry, hold the
insert near the point of entry rather than at the
The display overlay is adhered to the display PCB
end and feed the insert down until the leading
and is fitted with a series of text label inserts to
edge of the insert is fully home.
identify the various user controls and indications.
The inserts slip into pockets in the overlay and 13. Visually inspect the front of the display to
provide a flexible method of providing foreign ensure the inserts are correctly located.
language variants without affecting the overlay. The 14. Re-fit the PCB to the studs on the door,
panel is provided with one set of standard English making sure that the display is the correct way
text inserts fitted. These inserts are reversible with up.
the rear blank to allow small volume language 15. Work the PCB down the studs keeping the
variants to be typed. Since one of the panel’s board parallel to the door to prevent jamming.
configurable options allows manual activation of the
16. When the board is down on the studs, apply
fire alarms in either the Manual Fire Alarm or
light pressure around the outside edge of the
Muster mode, an additional English text insert is
board to ensure it is correctly seated on the
provided for the switch section – one side identifies
seal.
the top left hand switch and LED as “Manual Fire
Alarm” the other side identifies this switch as 17. Refit the frame with the battery located
“Muster”. towards the bottom of the door.
Additional double sided inserts may be supplied for 18. When the frame is fully down on the studs,
Chinese or Japanese applications. apply light pressure around the outside edge to
ensure it is correctly seated.
PAGE 14 of 39
All manuals and user guides at all-guides.com
EQUIPMENT: T1216W-C
PUBLICATION: MARINEW-P-I
ISSUE No. & DATE: 1 11/12
19. Refit the washers to all studs and then fit the 23. Refit the door stay if previously removed.
nuts loosely only. 24. Reconnect the 9V battery lead to J4 on the
20. Using the box spanner, carefully tighten each rear of the display PCB.
nut down until it is just in contact with the 25. Reconnect the buzzer lead to J5 or J6 as
frame. Do not fully tighten at this stage. appropriate. The buzzer will sound.
21. Tighten each nut by turning the nut a quarter of 26. Reconnect the standby batteries at the battery
a turn. Press the frame against the enclosure box and re-instate the mains power. After a
door using fingers only and check for any few seconds the panel will return to the
slack. quiescent state.
22. Repeat step 21 until the frame is firmly seated.
Note – Over tightening the nut may cause
the stud to break away from the door.
T1216W-C
MARINEW-P-I
1 11/12
6. Offer the door stay door mounting bracket up to
5.5.2 To Fit the Optional Door Stay the studs on the display frame as shown in
1. A door stay is available as an option for the Figure 9 and fit one M6 washer and Nyloc nut
T1216W-C panel. [supplied] to each stud. The nuts should be tight
2. A single door stay may be fitted to the door/back enough to prevent movement between slider
box assembly during the installation of the panel assembly and door.
enclosure described in section 5.2.1. Also refer 7. Adjust the door opening angle and the
to Figure 9– Door Stay Assembly. orientation of the door stay arm so that the
3. Materials required – 1 off T1200 Door Stay enclosure mounting bracket can be fitted to the
Assembly kit [508.023.025]. studs on the enclosure. Secure with the M5
nyloc nuts provided. Tighten the nuts sufficiently
4. Tools – ratchet socket set with 8mm and 10mm
m
[with an M5 socket] to prevent any movement
sockets. between the bracket and the box.
5. Locate the four fixing studs used to secure the 8. Check the operation of the door stay. The door
stay. Two M6 studs are located on the frame should open to approximately 110 -120 degrees
holding the display board. These are used to allowing the sliding nut to spring into the latched
secure the door mounting bracket. Two M5
.co
position latching the door open. To close the
studs are located on the inner return face of the door, push the door stay arm up to release the
back box at the bottom towards the door hinge. door stay sliding assembly nut.
These are used to secure the door stay
enclosure mounting bracket.
es
uid
-g
all
PAGE 16 of 39
All manuals and user guides at all-guides.com
EQUIPMENT: T1216W-C
PUBLICATION: MARINEW-P-I
ISSUE No. & DATE: 1 11/12
T1216W-C
MARINEW-P-I
1 11/12
circuits. At the panel end, measure the detector/MCP discrimination; all devices will
resistance across the positive & negative ends raise a detector fire indication.
of the cables for each of the circuits; ensuring Intrinsically Safe alarm devices [sounders] may be
the value does not exceed 20. Remember to connected via an MTL 5021 or MTL5521 galvanic
remove the wire links after the tests. isolator. There are no requirements for configuring
Correct polarity throughout all circuits must be the panel’s sounder outputs. Note: Galvanic
maintained. Check and rectify any faults. isolators prevent fault monitoring of the
4. All sounders, detector heads and call points sounder circuit. Any cable fault between the
should now be connected and the correct end- isolator and I.S. sounders will not be detected.
of-line devices fitted. Use the spare end-of-line The 3k9 end of line monitoring resistor should be
devices supplied and leave the EOL devices in connected across the barrier terminals 11 and 12
the panel terminals at this stage. Remember to [i.e. in parallel with the sounder circuit input to the
remove any links fitted to detector bases. Be safe area terminals on the IS barrier]. The
very careful to maintain correct polarity at each installation requirements supplied with the I.S.
device. barrier and the I.S. sounders must be fully
observed.
Warning:
Intrinsically safe zone arrangement: 6.5 Powering up
1. Ensure that the installation has been carried out Prior to powering up, the panel will have been
in full accordance with the installation installed in accordance with the installation
documentation provided with the I.S. devices instructions, all cabling will have been fully installed
and I.S. barrier. Failure to carry out the and tested, glanded into the panel enclosure but
installation correctly is likely to render the not connected to the panel terminals. The mains
system unsafe and risks causing an explosion. supply should be isolated externally to the panel.
2. End-of-line resistors with a value of 10K must The interface connections to the WMRCP should
be used. Additionally, these resistors must also be isolated prior to powering up the T1216W-C.
comply with the requirements laid down in the
installation data sheets provided with the I.S. 1. Connect the 9V battery lead to J4 on the rear of
barrier and the I.S. fire detection devices. the display PCB.
3. Any zones used for I.S. applications must be 2. Connect the buzzer lead to J6. The buzzer will
configured to Intrinsically Safe mode. [Except for sound.
mixed I.S./Non-I.S. zones as detailed below]. 3. Check the 24V battery connections are correct.
4. Recommended I.S. barrier - MTL5061/MTL5561 4. Check the Fault Routing Output configuration
[galvanic type]. link (3-way link at J6, J7, J8) has been removed.
5. Mixed I.S and Non-I.S. Zones: [Link located on the C1627 motherboard directly
below the Fault Signal relay].
Where the Safety System Documentation
allows, zones can contain I.S. and Non I.S. 5. Final battery connections:
devices. The requirements of the Safety Fit the connector on the end of the black lead
Documentation must be applied and the number onto the negative (black) terminal of the left-
of I.S. devices must be limited to 3 in total. hand battery. Fit the connector on the end of
The I.S. devices must be located at the end of the red lead onto the positive (red) terminal of
the zone with the I.S. barrier located in an the right-hand battery.
adjacent safe area. All of the non-I.S. devices Connect the blue battery lead between the
must be connected in the zone wiring between positive (red) terminal of the left-hand battery
the barrier and the panel. The I.S devices and the negative (black) terminal of the right-
should be connected between the I.S. barrier hand battery.
and the end of line. Warning: Connection of the batteries will
The zone must be configured to the non-I.S. power up the panel even if the mains
mode [This simply sets the operating detection supply is not energised.
thresholds and is not a safety issue]. 6. Ensure the mains supply is safely isolated
The non-I.S. section [safe side - between the external to the panel. Remove the mains supply
panel and the I.S. barrier] will support full open fuse from the panel mains terminal block. Once
and short circuit fault monitoring and the permit to energise the mains supply is in
detector/MCPs fire event discrimination. The I.S. place, energise the mains. At the mains terminal
section (hazardous side - between the IS barrier block in the panel, check the voltage and polarity
and the end of line resistor) will support open are correct. Isolate the mains supply again
circuit fault monitoring only - short circuit fault before replacing the panel fuse and finally re-
will raise a detector fire. It will not support energising.
PAGE 18 of 39
All manuals and user guides at all-guides.com
EQUIPMENT: T1216W-C
PUBLICATION: MARINEW-P-I
ISSUE No. & DATE: 1 11/12
7. If all the end of line devices are correctly 7. Operating the Engineer’s functions
terminated in the panel and the 24V battery is
OK, the panel should be silent, displaying only 7.1 Engineer’s Zone/Output
the Power Supply On indication. Configuration Process:
8. Turn the Access keyswitch to “1” and press the Various programmable configuration options
Test Display button. The panel should respond associated with the zonal inputs and outputs can be
by lighting all indications and sounding the enabled & disabled by operating the appropriate
buzzer. This will continue for 5 seconds after the DIL switch located within the panel enclosure.
button is released. These are:
o Configure one or more zones for use with I.S.
6.6 Configuration barriers/isolators.
o Configure zones as latching/non-latching fire
6.6.1 Basic Default Configuration indication.
The factory-set default mode is: o Configure outputs to be delayed.
All zones latching fire indication, standard NOTE: The delay feature does not comply
[non-intrinsically safe]. with the requirements of EN54-2.
Machinery space zones – none programmed. o Configure Machinery Space Zones.
Fire output signal, Fire Protection and Sounder 7.2 Zone or Output Configuration:
outputs not delayed.
1. Select a programmable configuration mode:
Sounders – General steady Alarm mode
o Enable the controls on the display, by turning
selected (not zonal, not pulsed).
the Access keyswitch on the panel display to
Crew Alarm Mode – not selected. the “1” position.
Fire [Routing] Output – link selected to o If the panel is in the fire alarm condition,
powered/monitored mode. silence the alarms and reset.
Fire Protection Output – link selected to o Open the panel door and locate the
powered/monitored mode. appropriate DIL switch on the motherboard
Fault Signal [routing] Output – link selected to [Config Non-latch Zones; Config I.S. Zones;
powered/monitored mode. [NB – THIS Config Delay O/Ps] and move the required
OUTPUT NEEDS TO BE CHANGED TO THE switch to the ON position.
VOLT-FREE MODE BY REMOVING THE 3- The CONFIG ENABLED LED on the
WAY LINK J6, J7, J8]. motherboard will illuminate. If the LED
Earth fault monitoring – enabled [link fitted]. pulses then an invalid configuration option
has been selected.
Manual fire alarm/Muster sounder operation –
link selected to Manual Fire Alarm. The Panel’s System Fault LED will flash
and the buzzer will operate.
LED brightness – highest setting.
The Select LED on the front of the display
Fire Protection outputs not to operate on non will pulse unless an invalid configuration
latched zones – not selected. option has been selected.
Inhibit silence alarms/reset for 3 minutes – not Any standing fire or fault alarm indications
selected. and associated outputs will be inhibited.
Silence alarms before reset – not enabled. If active, the indications for evacuation,
Buzzer – enabled. silence buzzer, delay on or disablement
indications will clear.
Latching faults – not selected.
The panel will indicate the current status of
6.6.2 Vessel-Specific Configuration the selected programmable configuration
mode on the yellow fault/disabled LEDs on
It is possible to tailor the functionality of the
the Zones, Sounders, Fire Routing and Fire
T1216W-C fire alarm panel in line with vessel-
Protection outputs.
specific requirements. Details of the vessel
configurable options and the configuration process A steady indication denotes that the
are provided in sections 6.6 and 7.1 respectively. zone/output is already configured to the
Charts are provided in the System Log Book for selected mode.
planning/recording the actual configuration. This No indication denotes that the zone/output
configuration is not lost when the panel is powered has not been configured to the selected
down. mode.
o Close the panel door to allow access to the
T1216W-C
MARINEW-P-I
1 11/12
buttons on the display. IMPORTANT NOTE: WHILE THE PANEL IS
2. Select a zone or output to be configured: IN THE ENGINEER’S ZONAL/OUTPUT
CONFIGURATION MODE, ALL ZONAL
o On the panel display, press the Select On/Off
INPUTS ARE IN PERMANENT RESET AND
switch to enable the Cursor Select Mode.
OUTPUTS ARE INHIBITED – THE PANEL
The Select LED will become steady and the WILL NOT RESPOND TO ANY FIRE ALARM.
panel buzzer will silence.
A pulsing indication [cursor] will appear 7.3 To Restore the Factory Default
either on the Zone 1 Fault/Disabled LED or Configuration for Zones &
the Sounder Fault/Disabled LED/Test
depending upon which configuration DIL
Outputs:
switch is selected. Open the panel door and locate the DIL
o Use the Select ↑ and Select↓ buttons to scroll switches SW1-4 to SW1-8 on the motherboard
the cursor indication through the selectable [Config Non-latch Zones; Config I.S. Zones;
options: Config M/S Zones; Config Delay Zones; Config
Delay O/Ps] and move each switch to the On
For zonal configuration, through all zones position.
sequentially in forward [Select↓] or reverse
[Select ↑] sequence starting at zone 1. o The Config Enabled LED on the motherboard
will flash.
For Output Delay configuration, through
Sounders, Fire Protection and Fire Routing o The Panel’s System Fault LED and Disabled
outputs in forward [Select↓] or reverse LED will flash and the buzzer will operate.
[Select ↑] sequence starting at Sounders. o Any standing fault or disablement indications
3. To change the configuration of a selected will clear.
zone or output: o It will not be possible to enter the Select
o With the cursor flashing on the selected zone Mode.
or output: Press the Disable button on the panel’s display
Operation of the ENABLE button will set the and wait 5 seconds.
configuration for the selected zone/output Return DIL switches 1-4 to 1-8 to the OFF
causing the associated fault/disabled LED position.
to illuminate steady (with flashing cursor). o The Config Enabled LED on the motherboard
Operation of the DISABLE button will clear will clear.
the configuration from the selected o The Panel’s System Fault LED will flash and
zone/output and restore normal operation. the buzzer will clear.
The fault/disabled LED will clear (with
o The factory default configuration [all zones as
flashing cursor).
latching fire, non-intrinsically safe, non-
Move the cursor to each required zone/output in machinery space] will be restored and the
turn and press ENABLE or DISABLE as Fire output, Fire Protection and Sounder
required. outputs will no longer be delayed.
4. To quit the programmable configuration
mode: 7.4 Engineer’s Zone/Output
o To return the panel to normal operating mode Configuration Time-out Warning:
applying the updated configuration: This feature is provided to prevent the panel being
Open the panel door and return the left in the Zone/Output Configuration condition.
selected Config DIL switch on the 1 minute after the last button press:
motherboard to the OFF position. o The panel buzzer will restart.
The CONFIG ENABLED LED on the o The Select LED will flash.
motherboard will clear, the panel buzzer will
o The System Fault LED will continue flashing.
silence and the flashing System Fault
indication and zone/output configuration Press the Select On/Off button to continue with
status indications on the display will clear the configuration process otherwise quit the
as will the cursor and the Select indications. configuration process as described in step 4 of
Any current alarms, disablements, will be 7.2 above.
re-indicated along with any active status
indications [Delay on etc.].
7.5 Invalid Configuration conditions:
o Close and lock the panel door. Invalid condition: If 2 or more configuration
switches on the motherboard are in the On
o Return the ACCESS keyswitch to the “0” position at the same time:
position to disable the controls on the display.
o The Config LED on the motherboard will
PAGE 20 of 39
All manuals and user guides at all-guides.com
EQUIPMENT: T1216W-C
PUBLICATION: MARINEW-P-I
ISSUE No. & DATE: 1 11/12
flash. SW 1/5 - Config I/S Zones:
o The System Fault and Select LEDs on the o OFF: Configuration mode disabled.
display will flash. o ON: Enables selected zones to be configured
o The fault relay will operate. to Intrinsically Safe alarm thresholds via the
o The panel buzzer will sound. Engineer’s Select feature. [For use with
MTL5061/MTL5561 I.S. galvanic barriers].
o The Cursor indication will clear.
o Configuration will be inhibited. SW 1/6 - Config M/S Zones:
o OFF: Configuration mode disabled.
To clear the invalid condition check the zone
and output config switches [1/4, 1/5, 1/6, 1/7, o ON: Enables zones to be configured as
1/8] on the motherboard and ensure that only Machinery Space zones via the Engineer’s
m
one is selected to ON. Select feature.
Invalid condition: Selecting any config mode SW 1/7 – Not Used
switch [1/4, 1/5, 1/6, 1/7, 1/8] to the On position SW 1/8 - Configure Delay O/Ps:
whilst the panel is in the fire condition. o OFF: Configuration mode disabled.
o The Config LED on the motherboard will
.co
o ON: Enables the selection of outputs, via the
flash. Engineer’s Select feature, to which the panel
o The System Fault and Select LEDs on the delay will apply.
display will flash. NOTE: This feature does not comply with the
o The panel buzzer will sound. requirements of EN54-2.
o The Cursor indication will clear. SW 1/9 – Not Used
o Configuration will be inhibited. SW 1/10 - Alarms on Evac Only:
es
To clear the invalid condition, select the config o OFF: Sounders operate on any fire condition
switch to OFF. Reset the fire alarm condition including manual fire alarm/muster.
before attempting the configuration process o ON: Selects sounders to operate only when
again.
the panel is in the manual fire alarm/muster
condition.
7.6 List of configuration DIL switches [Non-EN54 compliant function].
uid
[Not EN54 compliant function]. fault condition. (Not permitted under EN54-
S/W 1/2 - Delay Alarm Sil & Rst: 2).
o OFF: Silence and reset available at all times. SW 2/2 - Pulse Alarms:
o ON: Prevents alarms being silenced or reset Select type of sounder Operation.
for a period of 3 minutes after a fire alarm o OFF: Sounders will be continuous.
all
condition occurs.
o ON: Sounders will pulse.
[Not EN54 compliant function].
NOTE: The Muster Alarm signal will override
SW 1/3 – Delay ON Auto: any configuration settings.
o OFF: Configuration mode disabled. SW 2/3 - Restart Delay:
o ON: Enables Coincidence on paired zones Select type of Delay response in Crew Mode
for Water-Mist Panel use. only.
SW 1/4 - Config Non-Latch Zones: o OFF: If Sounders are silenced before the end
o OFF: Configuration mode disabled. of the 2-minute delay, a new fire condition
o ON: Enables selected zones to be configured will immediately operate all delayed outputs
to non-latching fire mode via the Engineer’s without delay.
Select feature. o ON: If Sounders are silenced before the end
[Not EN54 compliant function]. of the 2-minute delay, a new fire condition
will restart the delay timer.
SW 2/4 to 2/5 – Not Used
© 2012 Thorn Security Ltd PAGE 21 of 39
Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE
All manuals and user guides at all-guides.com
T1216W-C
MARINEW-P-I
1 11/12
SW 2/6 - Enable Zonal Alarms, SW 2/7- Pulse Sounder circuits 3 & 4 on the control
Non Alarm Zones: board and any output board sounder
MODE SW 2/6 SW 2/7 circuits are always delayed by 2-minutes.
General Alarms OFF OFF The fire Output & Fire Protection Outputs
Crew Mode OFF ON can be optionally configured to be delayed
Zonal Alarms ON OFF along with the sounders.
Zonal Alarms with Alert ON ON Operation of Silence Alarms will stop the
delay if operated within the 2-minute delay
o General Alarms – all sounders operate period, preventing all delayed outputs
(continuously or pulsed – DIL SW 2/2) until from operating.
silenced. Operation of Resound alarms will clear
o Zonal Alarms – Only the Alarm circuit(s) for the delay and operate all delayed outputs.
the zone(s) in fire will operate (continuously Operation of a manual call point or the
or pulsed – DIL SW 2/2) until silenced. Delay Override button will clear the delay
Note: Zonal alarms on the T1216W-C affects & operate all delayed outputs.
only the expansion module sounder circuits, the The delay can be configured to restart for
motherboard sounder circuits always operate as a new fire condition if the alarms are
General Alarms. silenced within the 2-minute delay period
o Zonal Alarms with Alert – The Alarm (see SW 2/3 details above).
circuit(s) for the zone(s) in fire will operate SW 2/8 - Silent Zone Test:
(continuously or pulsed – DIL SW 2/2) until
Select sounder response in One Man [Detector]
silenced. All other Alarm circuits will pulse.
Test Mode:
Note: Zonal alarms on the T1216W-C affects
o OFF: Sounders operate once on each test.
only the expansion module sounder circuits,
the motherboard sounder circuits always o ON: Sounders do not respond to a zone test.
operate as General Alarms. SW 2/9 - Buzzer Disable:
o Crew Mode – Sounder circuit 2 is pre- Enable/disable panel fire/fault buzzer.
assigned to Bridge area, Sounder circuit 1 is o OFF: Buzzer is enabled.
pre-assigned to machinery space zones,
Sounder circuits 3 & 4 are for all other areas: o ON: Buzzer is disabled. General Disablement
LED illuminated.
Sounder circuits cannot be manually
configured for delayed operation. This is not compliant to EN54-2 & is provided for
commissioning purposes only. The buzzer will
Sounder circuit 2 on the panel control continue to sound for a system fault or for total
board always operates immediately on power failure if the 9V battery is fitted.
any fire alarm condition.
SW 2/10 - Latched Faults:
Sounder circuit 1 will operate immediately
if there is a fire in a machinery space When enabled, all fault conditions latch until
zone, but will be delayed for 2 minutes for the Reset switch is operated.
a fire on any other zone. o OFF: Non-latched faults.
o ON: Latched faults.
PAGE 22 of 39
All manuals and user guides at all-guides.com
EQUIPMENT: T1216W-C
PUBLICATION: MARINEW-P-I
ISSUE No. & DATE: 1 11/12
7.7 List of Link Configuration features
Link Link
Feature Function Link Location
Ref Configuration
Fault monitored/powered O/P J10 Fitted C1627 motherboard, to the
Fire Output J11 right of the Fire [Routing]
Volt-Free C/O relay O/P J12 Removed Output relay
Fault monitored/powered O/P J6 Fitted C1627 motherboard, to the
Fault Output J7 right of the Fault [Routing]
Volt-Free C/O relay O/P J8 Removed Output relay
Fire Fault monitored/powered O/P J14 Fitted C1627 motherboard, to the
Protection J15 right of the fire protection
Output Volt-Free C/O relay O/P J16 Removed relay
Link in upper
Manual Fire Alarm mode selected
position
Manual Fire Link in lower On the back of the C1628
Muster Alarm mode selected J2
Alarm/Muster position display PCB
Manual Fire Alarm/Muster
Link removed
disabled
Earth Fault E/F monitoring enabled Link fitted Lower right hand corner of
J18
monitoring E/F monitoring disabled Link removed C1627 motherboard
T1216W-C
MARINEW-P-I
1 11/12
7.8 DIL switch settings on the Table 4 – Setting Quantity and Type of O/P
Repeater Interface Board: Modules on the C1630
PAGE 24 of 39
All manuals and user guides at all-guides.com
EQUIPMENT: T1216W-C
PUBLICATION: MARINEW-P-I
ISSUE No. & DATE: 1 11/12
Table 7 – Setting C1634 to Fire Protection Mode 7.9.1 Alarm Circuits
SW1 Standard T1216W 1. Remove the resistor from the first alarm circuit
Function terminal and connect the first alarm circuit
VDR configuration
wiring to the terminals, observing correct
Fire protection polarity. Check that any alarm fault indications
Off
output module clear after a few seconds.
Not compatible 2. Use the Alarm Test facility [see T1200-C User
On
with T1216W-C Manual] or press Manual fire alarm to operate
the sounders. Check that all sounders
connected to the alarm circuit operate.
7.9 Commissioning Procedure 3. Clear the Alarms Test condition or if “Manual
After completion of the pre-commissioning wiring fire alarm” was used, press silence alarms to
check, panel power-up and configuration steps, stop the sounders operating.
commission the circuits in line with the following 4. Repeat steps 1 to 3 for the second and any
guide. subsequent alarm circuits.
T1216W-C
MARINEW-P-I
1 11/12
buttons after each device test and check the 3. Initiate a fire condition on a zone to operate the
alarm clears (Manual Call Points must be output. Check that the fire signal operates the
manually reset before resetting the panel). interface relay adjacent to the fire protection
3. Detector removal operation: equipment.
o Remove the 1st detector along the zone cable 4. Open-circuit the field wiring and confirm that the
[counting from the panel] on zone 1 and fire alarm panel indicates a Fire Protection
observe the following: output fault.
The appropriate amber zone fault LED 5. Reconnect the cabling and confirm the faults
illuminates. clear.
The internal buzzer sounds. 6. Final testing and commissioning of the loop
through to the fire protection equipment,
m
The fault relay operates. including test [simulated] activation of the
Refit the detector and check that the control equipment, should be carried out at the
panel returns to its normal state. appropriate time in conjunction with the engineer
Continue to test each of the other detectors responsible for the fire protection system.
in turn, checking on each removal that:
.co
7.9.7 Ancillary inputs
The appropriate amber zone fault LED
illuminates. Remote Silence Alarms, Reset and Evacuate
[Manual fire alarm/Muster] inputs should each be
The internal buzzer sounds. tested by the activation of the remote equipment.
The fault relay operates. The response should be verified for each signal.
4. Any faults that are found must be traced and
rectified before proceeding.
7.9.8 Ancillary outputs
es
5. Repeat steps 1 to 4, one zone at a time, until all The correct operation of equipment connected to
the zones are commissioned. the Zone Outputs, Disablement Active, Evacuate
[Manual fire alarm/Muster] Active and Buzzer Active
7.9.3 Class Change Input outputs should be verified in turn by initiating a fire
This is not a marine function. condition on each of the appropriate zones;
disabling/enabling a zone; operating the Manual fire
7.9.4 Fire [Routing] Output alarm/Muster and Buzzer Silence buttons on the
uid
panel’s display.
1. Remove the resistor from the Fire Output circuit
terminals and connect the field wiring to the 7.9.9 Repeaters [when supplied]
terminals, observing correct polarity. Check that
any fault indications clear after a few seconds. 1. Power-up the Panel. At the Repeater(s), only
the “Power Supply On” LED should be
2. To operate the output, initiate a fire condition on illuminated on the Panel and Repeaters.
a zone. Check that the fire signal is received at
the receiving station. Silence and reset the fire 2. At Repeater 1, turn the Access control switch
to “1”, and press the “Manual fire alarm”
-g
clear. repeaters.
7.9.5 Fault [Routing] Output 4. Repeat steps 2 and 3 for each repeater.
See section 7.9.12 below. 5. Operate a Manual Call Point on zone 1 and
check for correct fire indication at each
7.9.6 Fire Protection Output repeater.
1. Ensure any fire protection equipment to be 6. Press the “Silence Alarms” button on a
controlled via the Fire Protection output is locked repeater and check that the alarms are
off/safe before attempting any connection, silenced and the Zone 1 fire LED is constantly
testing or commissioning. illuminated on all repeater panels.
2. Remove the resistor from the Fire Protection 7. Press the “Reset” button on a repeater and
output circuit terminal and connect the field check that the panel and repeaters return to
wiring to the terminals, observing correct the quiescent state.
polarity. Check that any fault indications clear 8. Repeat steps 5 to 7 for each zone and ensure
after a few seconds. “Silence Alarms” and “Reset” operate correctly
from each repeater.
PAGE 26 of 39
All manuals and user guides at all-guides.com
EQUIPMENT: T1216W-C
PUBLICATION: MARINEW-P-I
ISSUE No. & DATE: 1 11/12
9. Set the DIL switches on the C1631 Repeater 7.9.12 T1216W-C – WMRCP Interface.
Interface card in the fire alarm panel OFF (No
Repeaters). Check that all repeaters indicate a This work must be carried out in conjunction
“Comms. Fault”. with the Engineer responsible for the
commissioning of the Watermist System.
10. Set the C1631 Repeater Interface card DIL
switches in the fire alarm panel back to their Before commencing commissioning of the
previous settings and check that the repeaters interface, ensure the Watermist System is
return to normal. suitably disabled such that the functionality
associated with the interface can be fully tested
11. Set the first repeater address to 0. Check that
and proven without risk of damage to other
the panel indicates a “Repeater fault” and any
plant/equipment or risk of injury to personnel.
additional repeaters display a steady “Comms
fault” LED. Any necessary permit to work must be in place
and strictly observed.
12. Set the repeater address back to normal and
check that the panel and repeaters return to 1. Recheck the cable cores at the T1216W-C and
normal. WMRCP for correct polarity before final
connection of the interface wiring.
13. Repeat steps 11 and 12 for any other
connected repeaters. 2. Reconnect the interface wiring at T1216W-C
and WMRCP in turn.
7.9.10 Repeater Muster link [if fitted] 3. Power up the T1216W-C and check that the
1. On repeater 1, select the Access Controls following indications associated with the
switch to position 1 and press the Muster WMRCP correctly represent the WMRCP
button on the display. status:
2. Check the fire panel and the fire alarm Zone 15–[System Activated] - No alarm.
sounders respond correctly. Zone 16–[System Abnormal] - Fault [because
3. On repeater 1, press the Silence Alarms button the WMRCP is de-energised].
and check that the fire alarm panel responds 4. Ensure that the T1216W-C is in the quiescent
correctly and the fire alarm sounders cease state.
operating.
5. Power up the WMRCP and check that none of
4. Repeat steps 1, to 3 at each repeater panel the Watermist fire protection zones are
fitted with a muster interface board. actuated.
5. At the last repeater panel disconnect one of 6. At the T1216W-C, check that Zone 16 [System
the 3k9 resistors connected to the C1665 and Abnormal] Fault clears.
check the fire alarm panel reports “Repeater
7. At the T1216W-C, initiate any fault condition
Fault”.
and confirm the correct response at the
6. Reconnect the resistor & confirm the Repeater WMRCP. The WMRCP will also send this
Fault clears at the fire alarm panel. signal back to the T1216W-C and indicate a
7. Disconnect the other resistor and confirm the fault on Zone 16. Clear the fault condition on
Repeater Fault at the fire alarm panel. the T1216W-C and confirm both panels clear
8. Reconnect the resistor and confirm the fault down.
signal clears. 8. Single knock fire tests: Trigger a fire detector
in each detection circuit starting at zone circuit
7.9.11 Power Supply Unit. 1 through to 14. Reset the T1216W-C after
Ensure that the system is fully commissioned each circuit test. Check the correct fire
with all output circuits loaded as required by indication is given on the T1216W-C and that
the system design. the Watermist system is not activated.
Ensure that the battery has been on charge for 9. Double knock fire tests: Trigger a fire detector
at least 2 hours. on both detection circuits in each Watermist
Isolate the primary power supply feed to the fire protection zone starting at zone 1 through
panel. to 7. Check the correct Watermist fire
protection system is activated for each test and
Check the panel indicates power supply fault. that Zone 15 on the T1216W-C indicates an
Operate Test Alarms to load the panel. alarm in response to receiving the System
Confirm that the system continues to respond Activated signal from the WMRCP.
correctly during the test. 7.9.13 Final Dressing of the Cables
Quit the test and restore the primary supply.
Ensure that the field conductors are secure and tidy
Note: The battery requires a period in excess of inside the enclosure. Use Tie-wraps to secure any
24hrs to achieve a fully charged condition. long conductors or looms which might be prone to
© 2012 Thorn Security Ltd PAGE 27 of 39
Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE
All manuals and user guides at all-guides.com
T1216W-C
MARINEW-P-I
1 11/12
damage due to vibration of the panel enclosure.
Check that all cables are firmly held in the terminal
blocks & Earth bars. Check that the Earth Bars are
firmly fixed to the enclosure. Check that all Earth EOL SLEEVING
leads are correctly & firmly connected. Check that RESISTOR ON LEAD
End-Of-Line resistors in unused circuits are
positioned in a safe manner and are unlikely to
create short circuit faults due to movement. It is KEEP
advised that unused EOL resistors have insulating LEAD
sleeving placed on the leads for safety. SHORT
[Caution - do not over-tighten] Unused
Circuit
Terminals
PAGE 28 of 39
All manuals and user guides at all-guides.com
EQUIPMENT: T1216W-C
PUBLICATION: MARINEW-P-I
ISSUE No. & DATE: 1 11/12
8. User Indications
General Indicator Section
Indicator Indication Colour Operating Condition
Power Supply On Green Illuminates Steady for Mains or Standby power On.
Flashes on any new fire alarm condition, changing to a steady indication on
Fire Red
operation of Silence Alarms.
Fire Output Active Red Illuminates Steady when the Fire Output is active.
General Fault Yellow Flashes for any fault condition.
Power Supply Fault Yellow Flashes for mains or standby power supply/charge fault.
Illuminates Steady to indicate Microcontroller or Memory Failure.
System Fault Yellow
Flashes to indicate Engineer’s Configuration Mode active.
Earth Fault Yellow Flashes for any positive or negative power supply earth fault.
Fuse Failed Yellow Flashes for any auxiliary supply fuse failure.
Repeater Fault Yellow Flashes for any Repeater fault or repeater communication fault.
Sounder
Yellow Flashes for any sounder fault. Steady for sounders disabled.
Fault/Disabled
Sounder Test Yellow Illuminates Steady while sounder walk test is active.
Fire Protection Flashes for a fault on the Fire Protection Output. Steady when the Output is
Yellow
Fault/Disabled disabled.
Fire Output
Yellow Flashes for a fault on the Fire Output. Steady when Fire Output is disabled.
Fault/Disabled
Fault Output
Yellow Flashes for a fault on the Fault Output. Steady when Fault Output is disabled.
Fault/Disabled
POWER SUPPLY ON
MUSTER 1.
FIRE ALARM TEST DISPLAY
2.
FIRE OUTPUT ACTIVE
3.
SILENCE/
GENERAL FAULT RESOUND ENABLE 4.
ALARMS
POWER SUPPLY FAULT 5.
SYSTEM FAULT 6.
RESET DISABLE
7.
EARTH FAULT
8.
FUSE FAILED
SILENCE 9.
BUZZER TEST
REPEATER FAULT 10.
SOUNDER FAULT/DISABLED 11.
DELAY 12.
SOUNDER TEST OVERRIDE
13.
FIRE PROTECTION FAULT/DISABLED SELECT
14.
FIRE OUTPUT FAULT/DISABLED SELECT
ON/OFF 15.
FAULT OUTPUT FAULT/DISABLED 16.
T1216W-C
MARINEW-P-I
1 11/12
9. User Controls
POWER SUPPLY ON
MUSTER 1.
FIRE ALARM TEST DISPLAY
2.
FIRE OUTPUT ACTIVE
3.
SILENCE/
GENERAL FAULT RESOUND ENABLE 4.
ALARMS
POWER SUPPLY FAULT 5.
SYSTEM FAULT 6.
RESET DISABLE
7.
EARTH FAULT
8.
FUSE FAILED
SILENCE 9.
BUZZER TEST
REPEATER FAULT 10.
SOUNDER FAULT/DISABLED 11.
DELAY 12.
SOUNDER TEST OVERRIDE
13.
FIRE PROTECTION FAULT/DISABLED SELECT
14.
FIRE OUTPUT FAULT/DISABLED SELECT
ON/OFF 15.
FAULT OUTPUT FAULT/DISABLED 16.
PAGE 30 of 39
All manuals and user guides at all-guides.com
EQUIPMENT: T1216W-C
PUBLICATION: MARINEW-P-I
ISSUE No. & DATE: 1 11/12
Fire Output Aux Outputs:
Remote Inputs: [Marked Fire Disablement active
Silence Alarms Routing] Evacuate Active
Zone Evacuate Buzzer Active Repeater
Detection Reset Fire Terminals:
Zone Inputs Alarm Circuits Protection A, B, GND
Outputs1-4 [Marked with Output
Active Reset
Polarity] Relay
Output
Connector
for O/P
m
Aux DC
expansion
Supply
modules
24V & 0V
Fault Output
[Marked Fault
.co
J2 and J23 Configuration links for routing]
Connector for C1665 Fire & Fault Signal
Muster Interface [Routing] O/Ps and Fire
Protection O/P Connector
Secondary for C1632,
AC from Zone
Microcontroller Power Supply LED C1630 Output transformer Expansion
Programming indicators: expansion Interface Board
Battery –
Connector OUTPUT OK Connectors
Thermistor Battery/Charger Fault C1631 Repeater
Factory Use
Terminals Charger Fault Interface Connectors
es
Only Mains Fault
J1 J24 DC supply out to
Battery expansion boards
Display
Terminals
Connector
J19 DC supply in & PSU fault
FS1 from PS136
Battery Fuse PULSE ALARMS
DELAY RESTART
uid
Configuration J18
mode enabled LED Configuration Earth Fault
-g
Configuration
switches
SW1/1 to SW1/10
10. PCB Layouts
all
T1216W-C
MARINEW-P-I
1 11/12
Keyswitch
Connector
Buzzer 9V Battery
Connector Connector Keyswitch
Motherboard
Ribbon Cable
Connector
Comms Fault
LED
Processor fault
LED
Power Supply On
LED
Relay outputs 1 to 8
SW2 - Reset Microcontroller Programming N/O – Normally Open
processor Fault Connector – Factory Use Only POLE – Pole (common)
N/C – Normally Closed
PAGE 32 of 39
All manuals and user guides at all-guides.com
EQUIPMENT: T1216W-C
PUBLICATION: MARINEW-P-I
ISSUE No. & DATE: 1 11/12
Configuration switches to set
quantity and type of O/P
modules connected.
1
F/P 0
From top to bottom: F/P 1 Configuration Switch
2
F/P0 – Fire Protection S/C 0 to set quantity & type
3
F/P1 – Fire Protection
S/C 1
4 5
S/C0 – Sounder Controller of modules connected.
S/C1 – Sounder controller LED 0
6
LED0 – LED driver LED 1
7
LED1 – LED driver VDR
VDR – Voyage Data Recorder
Configuration Switch
Panel: Sets number of
1
R0
R1 repeaters.
2
R2 Repeater: Sets
3
repeater address.
PAGE 34 of 39
CONSOLE MOUNTING DETAILS
T1216W-C
8mm
30mm
50mm
40mm
11. Installation Details
300mm
300mm
240mm
200mm
300mm
220mm
282mm
288mm CUT-OUT
40mm
FRONT VIEW 164mm REAR VIEW REAR VIEW
4mm
30mm
50mm
REAR MOUNTING NOTE:-
25mm Knockout Gland Plate HOLES 5.5mm – 4 Places DIMENSIONS SHOWN WITH BOTTOM
351mm
ENTRY CABLE GLAND PLATE. IF TOP
ENTRY REQUIRED REVERSE DIMENSIONS.
TECHNICAL DATA
DIMENSIONS: 400mm WIDE x 300 HIGH x 180 DEEP
ENCLOSURE: ENCLOSED SPACES SUBJECT TO TEMPERATURE, HUMIDITY & VIBRATION.
WEIGHT: T1216W-C - 9.0Kg
CABLE ENTRY
GLAND PLATE: 36 x 20mm TOP OR BOTTOM MOUNTING
WIRE SIZE
MIN: 0.5 sqmm
MAX: 2.5 sqmm
All manuals and user guides at all-guides.com
EQUIPMENT: T1216W-C
PUBLICATION: MARINEW-P-I
ISSUE No. & DATE: 1 11/12
12. Wiring Diagrams
0V DC
0V DC
+24V DC
+24V DC A1715 Mains AC Change-Over Unit
Motherboard
TB4
T1216W-C Panel
OUTGOING
24Vdc to AC
SWITCH-OVER
INCOMING AC
UNIT
MAINS SUPPLY
Mains fuse
FROM AC
SWITCH-OVER
L L UNIT TO PANEL
N
EVAC
N
RST.
AUX D.C.
4
SIL
+ - 24V 0V
PAGE 36 of 39
T1216W-C
MARINEW-P-I
C1634 Relay O/P module C1634 Relay O/P module Optional C1631 C1630 O/P
all
[address 2] – zonal outputs 9-14 [address 1] – zonal outputs 1-8 Repeater expansion
to Watermist panel to Watermist panel Interface Interface Field Wiring
-g Terminals
C1627
J1
uid
Ribbon motherboard
C1628 Display Board Cables
J1 Ribbon J3 J3 J9 J4
J4 J2
Cable
es
J2 J2 J17
PP3 battery
Internal view of door Earth Wiring
.co
Earth
Wiring
Gland Plate
0V
Earth Stud Battery leads supplied
24V
cable with in panel fixing kit
L Shield
Batt +
Ship's supply in Batt +
[110/230VAc 50Hz] Mains fuse N Batt -
Direct or via AC Batt - + - + -
each 50mA, 30Vdc max. 10k end of line 3k9 end of line Remote I/Ps
Connect return to Aux 24V
PUBLICATION:
1 2 3 4 1+ 1 - 2 + 2 - 3 + 3 - 4 + 4 - 5+ 5 - 6 + 6 - 7 + 7 - 8 + 8 - 1 + 1 - 2 + 2 - 3 + 3 - 4 + 4 - 24V 0V Sil Evac RST Cl/C Dis Evac BAct A B GND N/C A B GND N/C
Zone O/Ps Zone Circuits Alarm Circuits Aux DC Inputs Outputs Repeater RST
Repeater RST
Fault Fire
Zone Circuits C1627wiring Repeater
Aux DC Routing Fire Routing Protection RST
terminals terminals in
9 + 9 - 10 + 10 - 11+ 11 - 12+ 12 - 13 + 13 - 14+ 14 - 15 + 15 - 16 + 16 - 24V 0V O/+ P C/- C/+ P O/- C/+ P O/- P N/O optional
Repeater panel
+ - 5 x repeaters max
Reset relay
Zones 9-16
1
Registered Company: Thorn Security Ltd. Registered Office: Dunhams Lane Letchworth Garden City Hertfordshire SG6 1BE
Remote protection
indicating equipment
equipment
11/12
Remote Relays
T1216W-C
PAGE 37 of 39
1
11/12
PAGE 38 of 39
T1216W-C
MARINEW-P-I
Wire Links
Z15+
Z16+
Z15-
Z16-
P1
P2
P3
P4
P5
P6
P7
P8
P1
P2
P3
P4
P5
P6
N/O1
RL FLT I/F
EQUIPMENT: T1216W-C
PUBLICATION: MARINEW-P-I
ISSUE No. & DATE: 1 11/12