MPR 53 53S User Manual

The MPR-53/53S Network Analyser is designed to measure various electrical parameters on a network, displaying over 50 parameters simultaneously. It features a MODBUS serial interface, programmable demand time, and multiple calculation methods for active and reactive power. The device is suitable for panel or rail mounting and includes digital inputs for monitoring electrical contacts.

Uploaded by

kipzy_pro
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
205 views5 pages

MPR 53 53S User Manual

The MPR-53/53S Network Analyser is designed to measure various electrical parameters on a network, displaying over 50 parameters simultaneously. It features a MODBUS serial interface, programmable demand time, and multiple calculation methods for active and reactive power. The device is suitable for panel or rail mounting and includes digital inputs for monitoring electrical contacts.

Uploaded by

kipzy_pro
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

NETWORK ANALYSER NETWORK ANALYSER

MPR-53/53S MPR-53/53S
TECHNICAL DATA General
MPR-53/53S is developed for measuring all the electrical parameters on the Calculation Methods for Active / Reactive Power Values
Operating Voltage (Un) : Please look behind the device. network. Measured parameters are shown in 5 separate displays.This allows If the led on the most left side blinks it represents that active power’s / reactive
to monitor more than 50 parameters at the same time. MPR-53S has also power’s direction is negative.
Operating frequency (f) : 45-65 Hz There are two methods for calculating total active and total reactive powers:
MODBUS serial interface feature.
Auxiliary supply Power Consumption : < 4 VA 1) Active / Reactive power can be calculated by summing import and export
values and displaying as a single value.
Measuring Input Power Consumption: < 1VA 2) Active / Reactive power can be calculated according to direction as
VIn : 10-300 V AC 45-65 Hz. (L-N) import / export.
Note :
: 10-500 V AC 45-65 Hz. (L-L) 1) The dot at the most right digit of the fourth display (During SW is
IIn : 0.05 - 5.5 A~ displayed) represents that displayed value is export active power value.
Vice versa, displayed value is import active power value.
2-120 A~ (for CT-25) 2) The dot at the most right digit of the fourth display (During SVAr is
Measuring Range : 10V...200 kV AC displayed) represents that displayed value is capacitive reactive power
value. Vice versa, displayed value is inductive reactive power value.
: 0...215 M (W,VAr,VA) 3) The displayed parameter will not change if power is off after 30 seconds
: 99999999999.9 kWh, kVArh UP button of stand-by (ie. A).
Class : 1% ± 1 digit [(10%-110%) xFull Scale] Measured Parameters:
Voltage Transformer Ratio (Vtr) : 0,1 ... 4000,0 DOWN button VLN (Phase Voltage ) Cosj THD (Total Harmonic Distortion)
Current Transformer Ratio (Ctr) : 1 ... 2000 Max. LED VLL (Phase to Phase Voltage) AI ( kWh) (Import Active Energy I) Hz. (Frequency)
SET A (Phase Current, Neutral Current) AE (kWh) (Export Active Energy) SW (Total Active Power)
Max. Ctr x Vtr : 40.000
W (Active Power) rI (kVArh) (Import Reactive Energy) SVAr (Total Reactive Power)
Demand Time : 1-60 min. (programmable) Minimum LED VAr (Reactive Power) rE(kVArh) (Export Reactive Energy) SVA (Total Apparent Power)
Serial Interface (for MPR-53S) : MODBUS RTU (RS 485) Demand LED VA (Apparent Power)
Optically Isolated, programmable FUNCTIONS OF BUTTONS
Baud Rate (for MPR-53S) : 2400-38400 bps In the monitoring mode, it is used to switch between
Phase SW, SVA and SVAr and Back ESC (VLN, VLL, A, W, VAr, VA, Cosj, kWh, kVarh, THD) parameters.
Address (for MPR-53S) : 1-247 Displays Hz Display Cosj Display button button At the programming mode, it provides to increase value of desired
Parity (for MPR-53S) : No, Odd, Even, 8 Data bits, 2 Stop Bits Phase Displays parameter and pass to the next menu.
Pulse Output : NPN Transistor In the monitoring mode, it is used to pass between
Switch Period : Min. 100 msec pulse perriod (VLN, VLL, A, W, VAr, VA, Cosj, kWh, kVarh, THD) parameters.
UP At the programming mode, it provides to decrease value of desired
80 msec pulse width parameter and pass to the prevides menu.
Operation Current : Max. 50 mA DOWN (SET) In the monitoring mode, it is used to switch between min.,
Operation Voltage : 5.....24 V DC, max. 30 VDC max., demand and instant values. When it is pressed for 3 seconds,
Max. LED programming mode it is entered.
Input : 12...48 V AC / DC SET In the programming mode, it is used for saving parameters and
Ambient Temperature : -5°C; +50°C Minimum LED moving to the sub menu.
Demand LED (Back) In the monitoring mode, it is used to switch between SW, SVA
Display : Red LED Display SW, SVA and Hz SVAr ve Cosj Back ESC and Hz parameters. It used to switch to the previous digit in submenu.
Dimensions : PR-19, PK-26 Display Display
(ESC) In the monitoring mode, it provides to switch between SVAr
Equipment Protection Class : Double Insulation-Class II ( ) Using of MPR-53/53S: and Cosj values. In the programming mode, it is used to enter to
Box Protection Class : IP 40 (front panel) Parameters are shown in L1, L2, L3 displays (VLN; VLL; A; IN; W; VAr; VA; Cosj; the upper menu or it is used to quit from the programming mode
kWh, kVarh, THD) by using up-down buttons. Total Active (SW), Total Apparent without saving values.
Box Material : Non-flammable Power (SVA) and Frequency (Hz) are selected by back button. If user password is activated and set button is pressed for 3
Installation : Panel Mounted (PR-19) Total Reactive Power (SVAr) and Cosj are selected by Esc button. seconds, a pin code is required in order to enter to the menu.
Rail Mounted (PK-26) Digital Inputs
MPR-53/53S has 2 digital inputs which are used to monitor the status of Current Transformer Ratio Setup
Wire Thickness (for terminal block) : 2.5 mm2 electrical contacts. Digital input has 2 functions :
In this menu, current transformer ratio is set between 1 - 2000.
Weight : 0.45 kg (PR-19, PK-26) - Enabling remote control of the data received through the digital input terminal
(battery, thermostat, circuit breaker, pumps status) Note: If the current transformer is not used between the system
Installation Category : Class III - Controlling energy counters and determining which energy counter will be and MPR-53/53S, current transformer ratio is entered as ‘1’.
active. Example: If a current transformer which has a ratio of 250/5A is
Factory Settings Energy Pulse Outputs used between the system and MPR-53/53S; Current transformer
Trafo : Eng Cnt : MPR-53/53S has 2 Energy Pulse Outputs. These outputs give the pulses only ratio is entered as “50” (250/5).
for E-1 (Energy Counter).
Ctr (Current Transformer Ratio) : 0001 E-1 (Energy Counter 1) : on Pul1 and Pul2: In “o-1 (Pulse1)”, “o-2 (Pulse2)” menus which are in the pulse Press SET button for 3 seconds (trA Fo menu is displayed)
trn (Turn number for CT-25 device): 01 E-2 (Energy Counter 2) : on menu, device give pulse according to selected energy parameters as [Active
energy (ACt, A-I, A-E), Reactive energy (rEA, r-L, r-C)]. Press SET button; trA Fo Ctr menu is displayed (In CT-25 adapted
Utr (Voltage Transformer Ratio) : 0001.0 Please refer to the pulse menu for the coefficients of energies. devices, trA Fo trn is displayed instead.)
CAL (Calculation Method) : 1 PULSE : (Not: trA Fo Utr menu can be displayed by scrolling the UP/DOWN
Monitoring of Min.,Max. and Max. Demand Values: buttons.)
rAt (Ratio) : 1k Min. and max. values are defined for VLN, VLL, A, W, VAr, VA, SW, SVAr, SVA;
Pin : 0000 (Not Activated) o-1 (Output 1) : A-I demand values are defined for A, W, VAr, VA, SW, SVA, SVAr.
o-2 (Output 2) : r-L If measured instant value is smaller than min. value which was stored before,
RS-485 : it is stored as new min. value. If measured instant value is greater than max. Press SET button. Blinking the first digit of displayed value appears.
value which was stored before, it is stored as new max. value. (trA Fo Utr menu can be programmed similarly.)
Adr (Address) : 1 dEtý (Delay Time) : 15 Demand value is the average value of the measured values in demand time
Bau (Baud Rate) : 9600 (15 minute). Enter the blinking digit value by scrolling UP/DOWN buttons.
Switch to the other digits by using SET button, use BACK button
PAr (Parity) : no If one of defined parameters is displayed (ie. “A”) when deman button is
to go to previous digit. After you entered the last digit press SET
pressed min., max or max. demand values are displayed. When an undefined
parameter is displayed (ie. “Cosj”) if demand button is pressed, instant value button, “trA Fo Ctr / trA Fo trn / trA Fo Utr” is displayed. “on”
PRECAUTIONS FOR INSTALLATION AND SAFE USE is continued to display.
can be selected by scrolling UP/DOWN buttons. (Data is entered
but is not activated yet. For activating the new data please follow
The current terminal connections must be implemented with using CT-25. Monitoring THD Values the below steps).
Failure to follow those instructions will result in death or serious injury. When “VLN” and “THD” leds light on, voltage THD is monitored and also if “A”
- Disconnect all power before working on equipment.. and “THD” leds light on, current THD is monitored. Press ESC button one by one until “SAU E SEt yES” is displayed.
- When the device is connected to the network, do not remove the front panel. Monitoring Neutral Current
- Do not try to clean the device with solvent or the like.Only clean with dry cloth.
- Verify correct terminal connections when wiring. Neutral current can be monitored by scrolling after 3-phases current values Press SET button. When “SAU E SEt yES” is displayed, if you
- Electrical equipment should be serviced only by your component seller. has displayed. press ESC button or choose “no” option instead of “yES” option
- No responsibility is assured by manufacturer or any of its subsidiaries for any consequences arising out of the use of this material. H-L-M LEDs by using UP-DOWN buttons, new data will be cancelled and
- Only for rack panel mounting. H-L-M LEDs are dedicated to displaying the min., max. and max. demand previous value will be activated.
values according to selected parameters.
8 A3918/Rev.3 H: Maximum Value, L: Minimum Value, M: Max. Demand Value 1
NETWORK ANALYSER NETWORK ANALYSER
MPR-53/53S MPR-53/53S
Programming the Turn Number: Demand Time Setup:
This menu is available for CT-25 adapted devices. User enter In this menu,demand time is set between 1-60 minutes.
PK 26 Box Connection Diagram
the turn number, which is the number of how many tour the current
cable has rounded into the CT-25. Numbers can be selected
between 1-20. Greater the number of turn means greater the Max: 30 VDC Max: 30 VDC
sensivity.
+ +
Press SET button for 3 sec. (trA Fo menu is displayed) _ _
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
2.00 1.00 0.66 0.50 0.40 0.33 0.28 0.24 0.22 0.20 0.18 0.16 0.15 0.14 0.13 0.12 0.11 0.11 0.10 0.10 (12-48V DC) (12-48V DC)
- + - + - + - +
120 60.0 40.0 30.0 24.0 20.0 17.1 15.0 13.3 12.0 10.9 10.0 9.23 8.57 8.00 7.50 7.05 6.66 6.31 6.00 By using UP-DOWN buttons find
“dE tý” menu.
Gnd A B TR Gnd A B TR

PUL1L
PUL1H
PUL2L
PUL2H
IN1L
IN1H
IN2L
IN2H

PUL1L
PUL1H
PUL2L
PUL2H
IN1L
IN1H
IN2L
IN2H
Voltage Transformer Ratio Setup RS-485 RS-485
In this menu, voltage transformer ratio is set between Press SET button (First digit blinks.)
0000,1 - 4000,0. Auxiliary Current Measuring Input Auxiliary Current Measuring Input
Supply Voltage Measuring Input Supply Voltage Measuring Input
Note: If the voltage transformer is not used between the system Enter the blinking digit value by scrolling UP/DOWN buttons. Un Un
IL1 IL2 IL3 IL1 IL2 IL3
and MPR-53/53S, voltage transformer ratio is entered as ‘1’. Switch to the other digits by using SET button, use BACK button ~ L1 L2 L3 N ~ L1 L2 L3 N
Example: If a voltage transformer which has a ratio of 34.5KV/100V to go to previous digit. After you entered the last digit press SET
is used between the system and MPR-53/53S; Voltage transformer button, “dE tý” is displayed. (Data is entered but is not activated N
yet. For activating the new data please follow the below steps). 1A 1A
k l
ratio is entered as 345. (34500/100) L1
K L
k l k l
L2 L1
Reactive Energy Calculation Method Setting Press ESC button one by one until (SAU E SEt yES) is displayed. K L K L
k l L2 k l
L3
Three different methods exist for reactive energy calculation in K L K L
N L3
MPR-53/53S. Brief informations about these methods are explained Press SET button. When “SAU E SEt yES” is displayed, if you
in below table. press ESC button or choose “no” option instead of “yES” option
Related values which must be entered in the menu are also by using UP-DOWN buttons, new data will be cancelled and 3 Phase neutral 3 Phase without neutral current input with
previous value will be activated. Aron wiring configuration
indicated in the table in order to select reactive power calculation
method for mechanical and digital energymeters.
Monitoring and Erasing of minimum, maximum and
energy values:
In this menu, values of min.,max. or energy counters are erased.
It saves the instantaneously measured min. and max. values of
Mechanical Energymeter Digital Energymeter Reactive Energy Description MPR-53/53S into its memory. Please kindly look at to the section
(Vectoral summation of 3-phase) (Each phase seperately) (Q) of FUNCTIONS OF BUTTONS for min. and max. values.
90° rotation of Note : Measured electrical parameters which are saved to the
It is the most preferred reactive power calculation
0 1 voltage vector and methode. memory are not affected from the electric interruptions. Max: 30 VDC Max: 30 VDC
multiply with current In the “rESEt” menu; when you quit from all menus, if you confirm
+
the changes,min. and max. values of all parameters or energy +
_ _
¥ Total value of the multiplication of Vn and In values up counter values are erased at the same time.
2 3 SVn.In.sin(jn)
n=1
to 19 th harmonics. This calculation methode is mostly
preferred for network analysers.
(12-48V DC)
- + - +
(12-48V DC)
- + - +
For erasing the values of min. and max. or energy counter,
In the measurement mode : Gnd A B TR

PUL1L
PUL1H
PUL2L
PUL2H
IN1L
IN1H
IN2L
IN2H
Gnd A B TR

PUL1L
PUL1H
PUL2L
PUL2H
IN1L
IN1H
IN2L
IN2H
Power Triangle Methode : According to this methode; RS-485
RS-485
4 5 S2-P2 Q = S2-P2 Press SET button for 3 seconds (trA Fo menu is displayed)
(Q : Reactive power, S : Active power, P : Apparent power)
Auxiliary Current Measuring Input Auxiliary Current Measuring Input
Supply Voltage Measuring Input Supply Voltage Measuring Input
By using UP-DOWN buttons, Un IL1 IL2 IL3 Un IL1 IL2 IL3
Press SET button for 3 seconds (trA Fo menu is displayed) find “rES Et” menu. ~ L1 L2 L3 N ~ L1 L2 L3 N

N N
1A 1A
k l
Press SET button. L1
Press SET button (trA Fo Ctr menu is displayed) (“rESEt HL” menu is displayed)
K L
k l k l
L2 L1
K L K L
L3 k l L2
K L k l
By using UP-DOWN buttons, select L3
By using UP-DOWN buttons, find 3 Phase without neutral K L
which parameter you want to reset. 3 Phase without neutral current input with
“CAL CUL Atý on” menu. Aron wiring configuration
Press SET button, one of the
parameter “rES Et dE / rES Et HL /
Press SET button. (Most right digit of 5th display blinks) rES Et E-1 / rES Et E-2” is displayed. *Available only for MPR-53S

By using UP-DOWN buttons, if you want to delete the min., max.,


max. demand or energy; select “yES” otherwise select “no” option. Note: For CT-25 models:
By using UP-DOWN buttons, select energy calculation method.
k: When CT-25 is used, Red cable is connected to k terminal.
Press SET button. (“rES Et dE / rES Et HL / rES Et E-1 / rES Et E- l: When CT-25 is used, Black cable is connected to l terminal.
Press set button, “CAL CUL Atý on” is displayed. (Data is entered 2” is displayed. Data is entered but is not activated yet. For
but is not activated yet. For activating the new data please follow activating the new data please follow the below steps.)
the below steps.)
Press ESC button one by one until (SAU E SEt yES) is
displayed.
Press ESC button one by one until “SAU E SEt yES” is displayed.
Press SET button. When “SAU E SEt yES” is displayed, if you
Press SET button. When “SAU E SEt yES” is displayed, if you press ESC button or choose “no” option instead of “yES” option
press ESC button or choose “no” option instead of “yES” option by using UP-DOWN buttons, new data will be cancelled and
by using UP-DOWN buttons, new data will be cancelled and previous value will be activated.
previous value will be activated.

2
7
NETWORK ANALYSER NETWORK ANALYSER
MPR-53/53S MPR-53/53S
Pulse Menu User password Setup:
In this menu, three parameters can be selected : In this menu user password is defined and activated.
PR 19 Box Connection Diagram “PUL SE rAt ýo”, “PUL SE o-1”, “PUL SE o-2” You must define and activate a 4 digit user password for
PUL SE rAt : Pulse menu which is defined for how many pulses preventing device settings from the illegal usage.
deticated for energy consumption. PUL SE rAt value can be There are 2 sub menus under the “Pýn” menu.
assigned as below:
Changing of User Password:
L1 K L L1 K L
1, 10, 100 (wh/VArh/VA); 1, 10, 100 (kwh/kVArh/kVA); 1 Mwh/MVArh/MVA.
This menu is used to change the user password .
K L PUL SE o-1 / PUL SE o-2: 1 Pulse is taken for respected energy Note: Factory default value for user password is
L2 k l L2 k l K L
consumption which assigned in “PUL SE rAt”. o-1 / o-2 can be assigned
K L “0000”
k l as below :
L3 L3 k l

k l ACt (Export/Import), A-I (Active Import), A-E (Active Export), rEA (Inductive
N / Capacitive), r-L (Reactive Inductive), r-C (Reactive Capacitive). To change the user password,
6 In the monitoring mode :
1 2 3 4 5 Press SET button for 3 seconds (trA Fo menu is displayed)
IL1 IL2 IL3
1 2 3 4 5 6 Press SET button for 3 seconds (trA Fo menu is displayed)
Current Measuring Input IL1 IL2 IL3
Max: 30 VDC By using UP-DOWN buttons, find “PULSE” menu.
( 12-48V DC ) Current Measuring Input
Pul C InC In1 In2 RS485 Bu using UP-DOWN buttons, find “Pýn” menu.
_ Max: 30 VDC
+ 13 14 15 16 17 18 19 20 21 22 ( 12-48V DC )
GND B A TR Pul C InC In1 In2 RS485
Pul 1 Pul 2
_
+ 13 14 15 16 17 18 19 20 21 22 Press SET button (”PUL SE rAt ýo” menu is displayed)
GND B A TR Press SET button (“Pýn ACt IUA tE” menu is displayed)
Voltage Measuring Input Auxiliary Pul 1 Pul 2

L1 L2 N
Supply By using UP-DOWN buttons, select “PUL SE rAt ýo”,
L3
Voltage Measuring Input Auxiliary
Supply “PUL SE o-1” or “PUL SE o-2”. By using the UP-DOWN buttons,
7 8 9 10 11 12 L1 L2 L3 N find “Pýn CHA ngE” menu.
1A

7 8 9 10 11 12
L1 Press SET button (1k / A-I / r-L blink)

1A
N L1 By using UP-DOWN-SET buttons, enter the old password

3 Phase neutral 3 Phase without neutral current input with N By using UP-DOWN buttons, select required parameter.
Aron wiring configuration
By using UP-DOWN-SET buttons, enter the new password
Press SET button. (Data is entered but is not activated yet.
For activating the new data please follow the below steps)

Press ESC button one by one until “SAU E SEt yES” is By using UP-DOWN-SET buttons, re-enter the new password.
displayed.
Press SET button. When “SAU E SEt yES” is displayed, if you Press SET button, “Pýn CHA ngE” is displayed. (Data is entered
press ESC button or choose “no” option instead of “yES” option but is not activated yet. For activating the new data please
by using UP-DOWN buttons, new data will be cancelled and follow the below steps).
previous value will be activated.
Press ESC button one by one until (SAU E SEt yES) is
Energy Counter (Eng Cnt) Menu displayed.
L1 K L L1 K L
MPR-53/53S has 2 energy counters : Press SET button. When “SAU E SEt yES” is displayed, if you
K L
L2 k l L2 k l Energy counter 1 (E-1), Energy counter 2 (E-2). press ESC button or choose “no” option instead of “yES” option
k l K L K L
“E-1 / E-2” have 4 parameters : by using UP-DOWN buttons, new data will be cancelled and
L3 L3 on : Activate “E-1 / E-2” counters for energy counting without depending previous value will be activated.
k l k l on any parameter. Activating the user password:
ý-1 : Activate “E-1 / E-2” counters, when digital input 1 is on (=1).
6 This menu is used for activating the user password.
1 2 3 4 5 ý-2 : Activate “E-1 / E-2” counters, when digital input 2 is on (=1).
IL1 IL3
After the user password is activated, while the instant values
IL2
6 E-2: “E-1” does not count when “E-2” is activated. (Only for “E-1”) are observed,user password is required in order to enter to
1 2 3 4 5
Current Measuring Input IL1 IL3 E-1: “E-2” does not count when “E-1” is activated. (Only for “E-2”) the menu. If the wrong user password is entered, user can
IL2
Max: 30 VDC not enter to the menu.
( 12-48V DC ) Current Measuring Input
Pul C InC In1 In2 RS485 Note: Counting status is undefned if E-2 is selected on E-1 and if E-1 is selected on Note: Factory default value of user password is “0000”
_
13 14 15 16 17 18 19 20 21 22 Max: 30 VDC
+ ( 12-48V DC ) E-2. When the status is defined as above, both energy counters count while digital
GND B A TR Pul C InC In1 In2 RS485
Pul 1 Pul 2
_
+ 13 14 15 16 17 18 19 20 21 22 input is not on (=1), but if either one or both digital inputs are on (=1) then counters
GND B A TR will not count.
Voltage Measuring Input Auxiliary Pul 1 Pul 2
Supply Press SET button for 3 seconds (trA Fo menu is displayed) For activating the user password, In the monitoring mode :
L1 L2 L3 N Auxiliary
Voltage Measuring Input
7 8 9 10 11 12
L1 L2 N
Supply
L3 Press SET button for 3 seconds (”trA Fo” menu is displayed)
1A

7 8 9 10 11 12 By using UP-DOWN buttons, find “Eng Cnt” menu.


L1
1A

N L1 By using UP-DOWN buttons, find “Pýn” menu.


3 Phase without neutral N Press SET button (”Eng Cnt E-1” menu is displayed)
3 Phase without neutral current input with
Aron wiring configuration Press SET button (”Pýn ACt IUA tE”
menu is displayed.)
*Available only for MPR-53S By using UP-DOWN buttons, select
“Eng Cnt E-1” / “Eng Cnt E-2”.
Press SET button (First digit blinks)
Press SET button. (on blinks) Enter the values for blinking digits by using UP-DOWN buttons,
Note: For CT-25 models: switch to other digits by using SET button use BACK button
k: When CT-25 is used, Red cable is connected to k terminal. to switch to previous digit “Pýn ACt oF” is displayed. “on” can
l: When CT-25 is used, Black cable is connected to l terminal. By using UP-DOWN buttons, select required parameter. be selected by using UP / DOWN buttons. (Data is entered
but is not activated yet. For activating the new data please follow
below steps)
Press SET button. (Data is entered but is not activated yet.
For activating the new data please follow the below steps) Press ESC button one by one until (SAU E SEt yES) is displayed.

Press ESC button one by one until “SAU E SEt yES” is Press SET button. When “SAU E SEt yES” is displayed, if you
displayed. press ESC button or choose “no” option instead of “yES” option
by using UP-DOWN buttons, new data will be cancelled and
Press SET button. When “SAU E SEt yES” is displayed, if you previous value will be activated.
press ESC button or choose “no” option instead of “yES” option
by using UP-DOWN buttons, new data will be cancelled and
previous value will be activated. 3
6
NETWORK ANALYSER NETWORK ANALYSER
MPR-53/53S MPR-53/53S
Serial Communication (Available only for MPR-53S) Preset Single Register (06) function is used for writting the setting values,
MPR-53S has MODBUS RTU communication protocol which is optical erasing the energy counter or resetting the min., max., demand values. MPR-53S COMPUTER CONNECTION
isolated. All measured parameters can be transfer to the computer. Current transformers ratio can be set 0-2000, voltage transformer ratio can
Transformer ratios and communication parameters can be set, saved be set 1-40000. Min., Max. and Demand values can be only clear. If sent
parameters for demand and energy values can be reset. value is outside of this range device responds with an error message. 31 DEVICES CAN BE CONNECTED AT THE SAME LINE
Parameter Settings (Available only for MPR-53S) i.e. Setting CT as 100;
01 06 80 02 00 64 XX XX
MAX. 1200 mt.
Address : 001-247
01 Device address RS485/RS232
Baud Rate : 2400, 4800, 9600, 19200, 34800 bps
06 Function
CONVERTER
Parity : “no”, “odd” and “EUEn”
80 MSB address
Press SET button for 3 seconds (trA Fo menu is displayed) 02 LSB address
B
00 Data MSB
64 Data LSB A PC
XX CRC MSB
By using UP-DOWN buttons, XX CRC LSB
GND
find “rS-485” menu.
Preset Multiple Register(10H) is used to set more then one register at same
time.

...
Press SET button (”Adr ESS” menu is displayed) i.e. Setting CT as 100, Ut as 20.0;
01 10 80 00 00 02 04 00 C8 00 64 XX XX TR B A GND TR B A GND TR B A GND
01 Device Address
10 Function
By using UP-DOWN buttons, select “Adr ESS / bAU d / 80 MSB address
PArýty”
00 LSB address
00 Register number MSB
02 Register number LSB MPR-53S-31 MPR-53S-2 MPR-53S-1
Press SET button. (001 / 9600 / no displayed) 04 Byte count
00 Data MSB
C8 Data LSB
By using UP-DOWN buttons, select required parameter 00 Data MSB MAX. 247 DEVICES CAN BE CONNECTED AT SAME LINE BY USING REPEATER.
(001...247 / 2400...38400 / no, EUEn, odd). 64 Data LSB
XX CRC MSB
XX CRC LSB MAX. 1200 mt. MAX. 1200 mt. RS485/RS232
Press SET button, “Adr ESS / bAU d / PArýty” displayed. (Data is
entered but is not activated yet. For activating the new data please
CONVERTER
Digital Inputs (Available only for MPR-53S)
follow the below steps) Digital input are sent in 16 bit hexadecimal format as below: B
Press ESC button one by one until “SAU E SEt yES” is
input 1 A PC
displayed. 55H 15 1 0
U U U U U U U U U U U U U U DIN2 DIN1 GND
Press SET button. When “SAU E SEt yES” is displayed, if you MSB LSB input 2
(Most Significant Byte) (Least Significant Byte)
press ESC button or choose “no” option instead of “yES” option
U: undefined

... ...
by using UP-DOWN buttons, new data will be cancelled and
previous value will be activated. TR B A GND
If 12-48 V AC / DC is applied to ln1 (Input 1), 0 (zero) bit of DIN register
MODBUS RTU PROTOCOL (Available only for MPR-53S) is set as “1”. Otherwise, 0 (zero) bit is set as “0”.
Standart MODBUS RTU message is shown below. If 12-48 V AC / DC is applied to ln2 (Input 2), 1st bit of DIN register is
set as “1”. Otherwise, 1st bit is set as “0”.

ADDRESS FUNCTION DATA The Parameters are sent in 32bit Hexadecimal format. For Example, 230.0V
T CRCH CRCL T voltage will be sent as 000008FCH. Cosj values shall be divided to 1000. MPR-53S-247 REPEATER MPR-53S-31 MPR-53S-2 MPR-53S-1
8 BIT 8 BIT NX8BIT
0.980 Cosj will be sent as 000003D4H. Energy values are sent in 64 bytes.
1234567890123456789 Wh = AB 54 A9 8C EB 1F 0A 02 Wh
The T times corresponds to a time in which data must not be exchanged
on the communication bus to allow the connected devices to recognize the Specifications for data cable ;
end of one message and the beginning of another. This time must be at - 24 AWG or thicker
least 3.5 characters at the selected baud rate. Adress range (1-247 ) is - Less than 100 ohm/ km Dimensions
address of the connected device. The data field contains data sent to the - Nominal characteristic impedance at 100 kHz of 100 ohms
slave by master or data sent to master by slave. - Less than 60 pF/m mutual capacitance (between two wires in a pair)
10.8 30.1 7.6 9.5
- Less than 120 pF/m mutual pair capacitance ( the capacitance between one
CRC is a error check method by using MODBUS RTU protocol and consists
wire and all others connected to earth).
79.3mm
of 2 bytes.
- Twisted Pair
60.6
70mm
Available Modbus Function:
ERROR CODES (Available only for MPR-53S)
03H READ HOLD REGISTERS Slave device (MPR-53S) sends error message when receive any missing query.

96mm
Error codes are given below.
01 Invalid Function: If any message except given above is used, then 01 error
06H PRESET SINGLE REGISTER messages will be sent.

45.0

90mm
90.0

02 Invalid Register: Error 02 will be send when a reading of a register is


10H PRESET MULTIPLE REGISTERS requested, except the registers which mentioned in table.
03 Invalid data: If any different value is been set for dedicated Transformer
Read Hold (03) function is used for reading measured values and set value. values and nonzero for demand value, then error message 03 will be sent.
96mm
14.0

8.5
If any request of reading of a register, excepted mentioned in register table, 106.0
device will send an error message. For example to read phase1 voltage by
sending a message to the device. 10.0 Type PR 19
01 03 00 00 00 02 XX XX 26.5 21.5
53.0
01 Device address Type PK 26
03 Function 58.0
00 MSB address
00 LSB address
00 Register number MSB
02 Register number LSB
XX CRC MSB
XX CRC LSB
4 5
NETWORK ANALYSER MODBUS REGISTER MAP
MPR-53/53S

MODBUS REGISTER MAP MODBUS REGISTER MAP


ADDRESS ADDRESS REGISTER R/W RANGE UNIT MULTIPLIER FORMAT ADDRESS ADDRESS REGISTER R/W RANGE UNIT MULTIPLIER FORMAT
(HEX) (HEX)
0 0000 L1 PHASE VOLTAGE R (0-3000)xUT Volt 0.1 unsigned int 152 0098 L3 PHASE MIN. APPARENT POWER R/W (0 - 18000)xCTxVT VA 0.1 unsigned int
2 0002 L2 PHASE VOLTAGE R (0-3000)xUT Volt 0.1 unsigned int 154 009A TOTAL MIN. IMPORT ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
4 0004 L3 PHASE VOLTAGE R (0-3000)xUT Volt 0.1 unsigned int 156 009C TOTAL MIN. EXPORT ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
6 0006 L1 PHASE CURRENT R (0-6000)xCT Amper 0.001 unsigned int 158 009E TOTAL MIN. IMPORT REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int
8 0008 L2 PHASE CURRENT R (0-6000)xCT Amper 0.001 unsigned int 160 00A0 TOTAL MIN. EXPORT REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int
10 000A L3 PHASE CURRENT R (0-6000)xCT Amper 0.001 unsigned int 162 00A2 TOTAL MIN. APPARENT POWER R/W (0 - 18000)xCTxVT VA 0.1 unsigned int
12 000C NEUTRAL CURRENT R (0-6000)xCT Amper 0.001 unsigned int 164 00A4 L1 PHASE MAX. VOLTAGE R/W (0-3000)xUT Volt 0.1 unsigned int
14 000E L1-L2 PHASE-PHASE VOLTAGE R (0-5000)xUT Volt 0.1 unsigned int 166 00A6 L2 PHASE MAX. VOLTAGE R/W (0-3000)xUT Volt 0.1 unsigned int
16 0010 L2-L3 PHASE-PHASE VOLTAGE R (0-5000)xUT Volt 0.1 unsigned int 168 00A8 L3 PHASE MAX. VOLTAGE R/W (0-3000)xUT Volt 0.1 unsigned int
18 0012 L3-L1 PHASE-PHASE VOLTAGE R (0-5000)xUT Volt 0.1 unsigned int 170 00AA L1-L2 PHASE-PHASE MAX. VOLTAGE R/W (0-5000)xUT Volt 0.1 unsigned int
20 0014 L1 PHASE ACTIVE POWER R (-18000 - 18000)xCTxVT Watt 0.1 int 172 00AC L2-L3 PHASE-PHASE MAX. VOLTAGE R/W (0-5000)xUT Volt 0.1 unsigned int
22 0016 L2 PHASE ACTIVE POWER R (-18000 - 18000)xCTxVT Watt 0.1 int 174 00AE L3-L1 PHASE-PHASE MAX. VOLTAGE R/W (0-5000)xUT Volt 0.1 unsigned int
24 0018 L3 PHASE ACTIVE POWER R (-18000 - 18000)xCTxVT Watt 0.1 int 176 00B0 L1 PHASE MAX. CURRENT R/W (0-6000)xCT Amper 0.001 unsigned int
26 001A L1 PHASE REACTIVE POWER R (-18000 - 18000)xCTxVT Var 0.1 int 178 00B2 L2 PHASE MAX. CURRENT R/W (0-6000)xCT Amper 0.001 unsigned int
28 001C L2 PHASE REACTIVE POWER R (-18000 - 18000)xCTxVT Var 0.1 int 180 00B4 L3 PHASE MAX. CURRENT R/W (0-6000)xCT Amper 0.001 unsigned int
30 001E L3 PHASE REACTIVE POWER R (-18000 - 18000)xCTxVT Var 0.1 int 182 00B6 L1 PHASE MAX. ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
32 0020 L1 PHASE APPARENT POWER R (0 -18000)xCTxVT VA 0.1 unsigned int 184 00B8 L2 PHASE MAX. ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
34 0022 L2 PHASE APPARENT POWER R (0 -18000)xCTxVT VA 0.1 unsigned int 186 00BA L3 PHASE MAX. ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
36 0024 L3 PHASE APPARENT POWER R (0 -18000)xCTxVT VA 0.1 unsigned int 188 00BC L1 PHASE MAX. REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int
38 0026 L1 PHASE COSj R (-1000 -1000) - 0.001 int 190 00BE L2 PHASE MAX. REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int
40 0028 L2 PHASE COSj R (-1000 -1000) - 0.001 int 192 00C0 L3 PHASE MAX. REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int
42 002A L3 PHASE COSj R (-1000 -1000) - 0.001 int 194 00C2 L1 PHASE MAX. APPARENT POWER R/W (0 - 18000)xCTxVT VA 0.1 unsigned int
44 002C TOTAL IMPORT ACTIVE POWER R (0 -54000)xCTxVT Watt 0.1 int 196 00C4 L2 PHASE MAX. APPARENT POWER R/W (0 - 18000)xCTxVT VA 0.1 unsigned int
46 002E TOTAL EXPORT ACTIVE POWER R (0 -54000)xCTxVT Watt 0.1 int 198 00C6 L3 PHASE MAX. APPARENT POWER R/W (0 - 18000)xCTxVT VA 0.1 unsigned int
48 0030 TOTAL INDUCTIVE REACTIVE POWER R (0 -54000)xCTxVT Var 0.1 int 200 00C8 TOTAL MAX. IMPORT ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
50 0032 TOTAL CAPACITIVE REACTIVE POWER R (0 -54000)xCTxVT Var 0.1 int 202 00CA TOTAL MAX. EXPORT ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
52 0034 TOTAL APPARENT POWER R (0 -54000)xCTxVT VA 0.1 unsigned int 204 00CC TOTAL MAX. IMPORT REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int
54 0036 AVERAGE INDUCTIVE COSj R (-1000 -1000) - 0.001 int 206 00CE TOTAL MAX. EXPORT REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int
56 0038 AVERAGE CAPACITIVE COSj R (-1000 -1000) - 0.001 int 208 00D0 TOTAL MAX. APPARENT POWER R/W (0 - 18000)xCTxVT VA 0.1 unsigned int
58 003A FREQUENCY R (4000 -7000) Hz 0.01 unsigned int 210 00D2 L1 PHASE MAX. CURRENT DEMAND R/W (0-6000)xCT Amper 0.001 unsigned int
60 003C L1 PHASE VOLTAGE ANGLE R 0-360 Degre 1 unsigned int 212 00D4 L2 PHASE MAX. CURRENT DEMAND R/W (0-6000)xCT Amper 0.001 unsigned int
62 003E L2 PHASE VOLTAGE ANGLE R 0-360 Degre 1 unsigned int 214 00D6 L3 PHASE MAX. CURRENT DEMAND R/W (0-6000)xCT Amper 0.001 unsigned int
64 0040 L3 PHASE VOLTAGE ANGLE R 0-360 Degre 1 unsigned int 216 00D8 L1 PHASE IMPORT MAX. DEMAND ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
66 0042 L1 PHASE CURRENT ANGLE R 0-360 Degre 1 unsigned int 218 00DA L1 PHASE EXPORT MAX. DEMAND ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
68 0044 L2 PHASE CURRENT ANGLE R 0-360 Degre 1 unsigned int 220 00DC L2 PHASE IMPORT MAX. DEMAND ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
70 0046 L3 PHASE CURRENT ANGLE R 0-360 Degre 1 unsigned int 222 00DE L2 PHASE EXPORT MAX. DEMAND ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
72 0048 L1 PHASE VOLTAGE THD R 0-999 % 0.1 unsigned int 224 00E0 L3 PHASE IMPORT MAX. DEMAND ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
74 004A L2 PHASE VOLTAGE THD R 0-999 % 0.1 unsigned int 226 00E2 L3 PHASE EXPORT MAX. DEMAND ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
76 004C L3 PHASE VOLTAGE THD R 0-999 % 0.1 unsigned int 228 00E4 L1 PHASE IMPORT MAX. DEMAND REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int
78 004E L1 PHASE CURRENT THD R 0-999 % 0.1 unsigned int 230 00E6 L1 PHASE EXPORT MAX. DEMAND REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int
80 0050 L2 PHASE CURRENT THD R 0-999 % 0.1 unsigned int 232 00E8 L2 PHASE IMPORT MAX. DEMAND REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int
82 0052 L3 PHASE CURRENT THD R 0-999 % 0.1 unsigned int 234 00EA L2 PHASE EXPORT MAX. DEMAND REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int
84 0054 DIGITAL INPUT STATUS R - - - - 236 00EC L3 PHASE IMPORT MAX. DEMAND REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int
86 0056 R/W 0-FFFFFFFFFFFFFFFF Wh 1 long int 238 00EE L3 PHASE EXPORT MAX. DEMAND REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int
IMPORT ACTIVE ENERGY-1
88 0058 R/W 0-FFFFFFFFFFFFFFFF Wh 1 long int 240 00F0 L1 PHASE MAX. DEMAND APPARENT POWER R/W (0 - 18000)xCTxVT VA 0.1 unsigned int
90 005A R/W 0-FFFFFFFFFFFFFFFF Wh 1 long int 242 00F2 L2 PHASE MAX. DEMAND APPARENT POWER R/W (0 - 18000)xCTxVT VA 0.1 unsigned int
EXPORT ACTIVE ENERGY-1
92 005C R/W 0-FFFFFFFFFFFFFFFF Wh 1 long int 244 00F4 L3 PHASE MAX. DEMAND APPARENT POWER R/W (0 - 18000)xCTxVT VA 0.1 unsigned int
94 005E R/W 0-FFFFFFFFFFFFFFFF VArh 1 long int 246 00F6 TOTAL IMPORT MAX. DEMAND ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
INDUCTIVE REACTIVE ENERGY-1
96 0060 R/W 0-FFFFFFFFFFFFFFFF VArh 1 long int 248 00F8 TOTAL EXPORT MAX. DEMAND ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
98 0062 R/W 0-FFFFFFFFFFFFFFFF VArh 1 long int 250 00FA TOTAL IMPORT MAX. DEMAND REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int
CAPACITIVE REACTIVE ENERGY-1
100 0064 R/W 0-FFFFFFFFFFFFFFFF VArh 1 long int 252 00FC TOTAL EXPORT MAX. DEMAND REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int
102 0066 R/W 0-FFFFFFFFFFFFFFFF Wh 1 long int 254 00FE TOTAL MAX. DEMAND APPARENT POWER R/W (0 - 18000)xCTxVT VA 0.1 unsigned int
IMPORT ACTIVE ENERGY-2
104 0068 R/W 0-FFFFFFFFFFFFFFFF Wh 1 long int
106 006A
EXPORT ACTIVE ENERGY-2
R/W 0-FFFFFFFFFFFFFFFF Wh 1 long int
ADDRESS ADDRESS REGISTER R/W RANGE UNIT MULTIPLIER FORMAT
108 006C R/W 0-FFFFFFFFFFFFFFFF Wh 1 long int (HEX)
110 006E R/W 0-FFFFFFFFFFFFFFFF VArh 1 long int 32768 8000 VOLTAGE TRANSFORMER RATIO R/W 0-40000 - 0.1 short-int
INDUCTIVE REACTIVE ENERGY-2
112 0070 R/W 0-FFFFFFFFFFFFFFFF VArh 1 long int 32769 8001 CURRENT TRANSFORMER RATIO R/W 0-2000 - 1 short-int
114 0072 R/W 0-FFFFFFFFFFFFFFFF VArh 1 long int 32770 8002 CALCULATION METHOD R/W 0-5 - - short-int
CAPACITIVE REACTIVE ENERGY-2
116 0074 R/W 0-FFFFFFFFFFFFFFFF VArh 1 long int 32771 8003 DEMAND TIME R/W 1-60 minute 1 short-int
118 0076 L1 PHASE MIN. VOLTAGE R/W (0-3000)xUT Volt 0.1 unsigned int 32772 8004 PULSE RATIO R/W 0-6 - - short-int
120 0078 L2 PHASE MIN. VOLTAGE R/W (0-3000)xUT Volt 0.1 unsigned int 32773 8005 PULSE OUTPUT 1 PARAMETER SETTING R/W 0-5 - - short-int
122 007A L3 PHASE MIN. VOLTAGE R/W (0-3000)xUT Volt 0.1 unsigned int 32774 8006 PULSE OUTPUT 2 PARAMETER SETTING R/W 0-5 - - short-int
124 007C L1-L2 PHASE-PHASE MIN. VOLTAGE R/W (0-3000)xUT Volt 0.1 unsigned int 32775 8007 ENERGY COUNTER 1 SELECTION R/W 0-3 - - short-int
126 007E L2-L3 PHASE-PHASE MIN. VOLTAGE R/W (0-3000)xUT Volt 0.1 unsigned int 32776 8008 ENERGY COUNTER 2 SELECTION R/W 0-3 - - short-int
128 0080 L3-L1 PHASE-PHASE MIN. VOLTAGE R/W (0-3000)xUT Volt 0.1 unsigned int 32777 8009 COMMUNICATION ADDRESS R/W 0 - 247 - - short-int
130 0082 L1 PHASE MIN. CURRENT R/W (0-6000)xCT Amper 0.001 unsigned int 32778 800A BAUD RATE R/W 1-5 - - short-int
132 0084 L2 PHASE MIN. CURRENT R/W (0-6000)xCT Amper 0.001 unsigned int 32779 800B PARITY R/W 0-2 - - short-int
134 0086 L3 PHASE MIN. CURRENT R/W (0-6000)xCT Amper 0.001 unsigned int 32780 800C PASSWORD ENABLE R/W 0-1 - - short-int
136 0088 L1 PHASE MIN. ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int 32781 800D PASSWORD R/W 0-9999 - - short-int
138 008A L2 PHASE MIN. ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
140 008C L3 PHASE MIN. ACTIVE POWER R/W (-18000 - 18000)xCTxVT Watt 0.1 int
PULSE OUTPUT 1-2 PULSE RATIO 0-6 : ENERGY COUNTER 1 SELECTION 0-3 : BAUD RATE 1-5 :
142 008E L1 PHASE MIN. REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int PARAMETER SETTING 0-5 : 0: 1 Watt / Pulse 0 : On (EC -Energy counter- will count on all conditions) 1: 38400 bps
144 0090 L2 PHASE MIN. REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int 0: Active 1: 10 Watt / Pulse 1: EC will count when Digital Input1 is 1 (1=active) 2: 19200 bps
146 0092 L3 PHASE MIN. REACTIVE POWER R/W (-18000 - 18000)xCTxVT Var 0.1 int 1: Active Import 2: 100 Watt / Pulse 2: EC will count when Digital Input2 is 1 (1=active) 3: 9600 bps
148 0094 L1 PHASE MIN. APPARENT POWER R/W (0 - 18000)xCTxVT VA 0.1 unsigned int 2: Active Export 3: 1 kW / Pulse 3: Inverse Energy Counter 2 (It will count when EC2 is not counted) 4: 4800 bps
150 0096 L2 PHASE MIN. APPARENT POWER R/W (0 - 18000)xCTxVT VA 0.1 unsigned int 3: Reactive 4: 10 kW / Pulse ENERGY COUNTER 2 SELECTION 0-3 : 5: 2400 bps
4: Reactive Import 5: 100 kW / Pulse 0 : On (EC -Energy counter- will count on all conditions) PARITY 0-2 :
*Available only for MPR-53S 5: Reactive Export 6: 1 MW / Pulse 1: EC will count when Digital Input1 is 1 (1=active) 0: No
2: EC will count when Digital Input2 is 1 (1=active) 1: Odd
CALCULATION 0-5 : 3: Inverse Energy Counter 1 (It will count when EC1 is not counted) 2: Even
Refer to “Reactive Energy Calculation Method Setting” on page 2. PASSWORD ENABLE 0-1 :
0: Disable
A4309/Rev.1 1: Enable