MPR 53 53S User Manual
MPR 53 53S User Manual
MPR-53/53S MPR-53/53S
TECHNICAL DATA General
MPR-53/53S is developed for measuring all the electrical parameters on the Calculation Methods for Active / Reactive Power Values
Operating Voltage (Un) : Please look behind the device. network. Measured parameters are shown in 5 separate displays.This allows If the led on the most left side blinks it represents that active powers / reactive
to monitor more than 50 parameters at the same time. MPR-53S has also powers direction is negative.
Operating frequency (f) : 45-65 Hz There are two methods for calculating total active and total reactive powers:
MODBUS serial interface feature.
Auxiliary supply Power Consumption : < 4 VA 1) Active / Reactive power can be calculated by summing import and export
values and displaying as a single value.
Measuring Input Power Consumption: < 1VA 2) Active / Reactive power can be calculated according to direction as
VIn : 10-300 V AC 45-65 Hz. (L-N) import / export.
Note :
: 10-500 V AC 45-65 Hz. (L-L) 1) The dot at the most right digit of the fourth display (During SW is
IIn : 0.05 - 5.5 A~ displayed) represents that displayed value is export active power value.
Vice versa, displayed value is import active power value.
2-120 A~ (for CT-25) 2) The dot at the most right digit of the fourth display (During SVAr is
Measuring Range : 10V...200 kV AC displayed) represents that displayed value is capacitive reactive power
value. Vice versa, displayed value is inductive reactive power value.
: 0...215 M (W,VAr,VA) 3) The displayed parameter will not change if power is off after 30 seconds
: 99999999999.9 kWh, kVArh UP button of stand-by (ie. A).
Class : 1% ± 1 digit [(10%-110%) xFull Scale] Measured Parameters:
Voltage Transformer Ratio (Vtr) : 0,1 ... 4000,0 DOWN button VLN (Phase Voltage ) Cosj THD (Total Harmonic Distortion)
Current Transformer Ratio (Ctr) : 1 ... 2000 Max. LED VLL (Phase to Phase Voltage) AI ( kWh) (Import Active Energy I) Hz. (Frequency)
SET A (Phase Current, Neutral Current) AE (kWh) (Export Active Energy) SW (Total Active Power)
Max. Ctr x Vtr : 40.000
W (Active Power) rI (kVArh) (Import Reactive Energy) SVAr (Total Reactive Power)
Demand Time : 1-60 min. (programmable) Minimum LED VAr (Reactive Power) rE(kVArh) (Export Reactive Energy) SVA (Total Apparent Power)
Serial Interface (for MPR-53S) : MODBUS RTU (RS 485) Demand LED VA (Apparent Power)
Optically Isolated, programmable FUNCTIONS OF BUTTONS
Baud Rate (for MPR-53S) : 2400-38400 bps In the monitoring mode, it is used to switch between
Phase SW, SVA and SVAr and Back ESC (VLN, VLL, A, W, VAr, VA, Cosj, kWh, kVarh, THD) parameters.
Address (for MPR-53S) : 1-247 Displays Hz Display Cosj Display button button At the programming mode, it provides to increase value of desired
Parity (for MPR-53S) : No, Odd, Even, 8 Data bits, 2 Stop Bits Phase Displays parameter and pass to the next menu.
Pulse Output : NPN Transistor In the monitoring mode, it is used to pass between
Switch Period : Min. 100 msec pulse perriod (VLN, VLL, A, W, VAr, VA, Cosj, kWh, kVarh, THD) parameters.
UP At the programming mode, it provides to decrease value of desired
80 msec pulse width parameter and pass to the prevides menu.
Operation Current : Max. 50 mA DOWN (SET) In the monitoring mode, it is used to switch between min.,
Operation Voltage : 5.....24 V DC, max. 30 VDC max., demand and instant values. When it is pressed for 3 seconds,
Max. LED programming mode it is entered.
Input : 12...48 V AC / DC SET In the programming mode, it is used for saving parameters and
Ambient Temperature : -5°C; +50°C Minimum LED moving to the sub menu.
Demand LED (Back) In the monitoring mode, it is used to switch between SW, SVA
Display : Red LED Display SW, SVA and Hz SVAr ve Cosj Back ESC and Hz parameters. It used to switch to the previous digit in submenu.
Dimensions : PR-19, PK-26 Display Display
(ESC) In the monitoring mode, it provides to switch between SVAr
Equipment Protection Class : Double Insulation-Class II ( ) Using of MPR-53/53S: and Cosj values. In the programming mode, it is used to enter to
Box Protection Class : IP 40 (front panel) Parameters are shown in L1, L2, L3 displays (VLN; VLL; A; IN; W; VAr; VA; Cosj; the upper menu or it is used to quit from the programming mode
kWh, kVarh, THD) by using up-down buttons. Total Active (SW), Total Apparent without saving values.
Box Material : Non-flammable Power (SVA) and Frequency (Hz) are selected by back button. If user password is activated and set button is pressed for 3
Installation : Panel Mounted (PR-19) Total Reactive Power (SVAr) and Cosj are selected by Esc button. seconds, a pin code is required in order to enter to the menu.
Rail Mounted (PK-26) Digital Inputs
MPR-53/53S has 2 digital inputs which are used to monitor the status of Current Transformer Ratio Setup
Wire Thickness (for terminal block) : 2.5 mm2 electrical contacts. Digital input has 2 functions :
In this menu, current transformer ratio is set between 1 - 2000.
Weight : 0.45 kg (PR-19, PK-26) - Enabling remote control of the data received through the digital input terminal
(battery, thermostat, circuit breaker, pumps status) Note: If the current transformer is not used between the system
Installation Category : Class III - Controlling energy counters and determining which energy counter will be and MPR-53/53S, current transformer ratio is entered as 1.
active. Example: If a current transformer which has a ratio of 250/5A is
Factory Settings Energy Pulse Outputs used between the system and MPR-53/53S; Current transformer
Trafo : Eng Cnt : MPR-53/53S has 2 Energy Pulse Outputs. These outputs give the pulses only ratio is entered as 50 (250/5).
for E-1 (Energy Counter).
Ctr (Current Transformer Ratio) : 0001 E-1 (Energy Counter 1) : on Pul1 and Pul2: In o-1 (Pulse1), o-2 (Pulse2) menus which are in the pulse Press SET button for 3 seconds (trA Fo menu is displayed)
trn (Turn number for CT-25 device): 01 E-2 (Energy Counter 2) : on menu, device give pulse according to selected energy parameters as [Active
energy (ACt, A-I, A-E), Reactive energy (rEA, r-L, r-C)]. Press SET button; trA Fo Ctr menu is displayed (In CT-25 adapted
Utr (Voltage Transformer Ratio) : 0001.0 Please refer to the pulse menu for the coefficients of energies. devices, trA Fo trn is displayed instead.)
CAL (Calculation Method) : 1 PULSE : (Not: trA Fo Utr menu can be displayed by scrolling the UP/DOWN
Monitoring of Min.,Max. and Max. Demand Values: buttons.)
rAt (Ratio) : 1k Min. and max. values are defined for VLN, VLL, A, W, VAr, VA, SW, SVAr, SVA;
Pin : 0000 (Not Activated) o-1 (Output 1) : A-I demand values are defined for A, W, VAr, VA, SW, SVA, SVAr.
o-2 (Output 2) : r-L If measured instant value is smaller than min. value which was stored before,
RS-485 : it is stored as new min. value. If measured instant value is greater than max. Press SET button. Blinking the first digit of displayed value appears.
value which was stored before, it is stored as new max. value. (trA Fo Utr menu can be programmed similarly.)
Adr (Address) : 1 dEtý (Delay Time) : 15 Demand value is the average value of the measured values in demand time
Bau (Baud Rate) : 9600 (15 minute). Enter the blinking digit value by scrolling UP/DOWN buttons.
Switch to the other digits by using SET button, use BACK button
PAr (Parity) : no If one of defined parameters is displayed (ie. A) when deman button is
to go to previous digit. After you entered the last digit press SET
pressed min., max or max. demand values are displayed. When an undefined
parameter is displayed (ie. Cosj) if demand button is pressed, instant value button, trA Fo Ctr / trA Fo trn / trA Fo Utr is displayed. on
PRECAUTIONS FOR INSTALLATION AND SAFE USE is continued to display.
can be selected by scrolling UP/DOWN buttons. (Data is entered
but is not activated yet. For activating the new data please follow
The current terminal connections must be implemented with using CT-25. Monitoring THD Values the below steps).
Failure to follow those instructions will result in death or serious injury. When VLN and THD leds light on, voltage THD is monitored and also if A
- Disconnect all power before working on equipment.. and THD leds light on, current THD is monitored. Press ESC button one by one until SAU E SEt yES is displayed.
- When the device is connected to the network, do not remove the front panel. Monitoring Neutral Current
- Do not try to clean the device with solvent or the like.Only clean with dry cloth.
- Verify correct terminal connections when wiring. Neutral current can be monitored by scrolling after 3-phases current values Press SET button. When SAU E SEt yES is displayed, if you
- Electrical equipment should be serviced only by your component seller. has displayed. press ESC button or choose no option instead of yES option
- No responsibility is assured by manufacturer or any of its subsidiaries for any consequences arising out of the use of this material. H-L-M LEDs by using UP-DOWN buttons, new data will be cancelled and
- Only for rack panel mounting. H-L-M LEDs are dedicated to displaying the min., max. and max. demand previous value will be activated.
values according to selected parameters.
8 A3918/Rev.3 H: Maximum Value, L: Minimum Value, M: Max. Demand Value 1
NETWORK ANALYSER NETWORK ANALYSER
MPR-53/53S MPR-53/53S
Programming the Turn Number: Demand Time Setup:
This menu is available for CT-25 adapted devices. User enter In this menu,demand time is set between 1-60 minutes.
PK 26 Box Connection Diagram
the turn number, which is the number of how many tour the current
cable has rounded into the CT-25. Numbers can be selected
between 1-20. Greater the number of turn means greater the Max: 30 VDC Max: 30 VDC
sensivity.
+ +
Press SET button for 3 sec. (trA Fo menu is displayed) _ _
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
2.00 1.00 0.66 0.50 0.40 0.33 0.28 0.24 0.22 0.20 0.18 0.16 0.15 0.14 0.13 0.12 0.11 0.11 0.10 0.10 (12-48V DC) (12-48V DC)
- + - + - + - +
120 60.0 40.0 30.0 24.0 20.0 17.1 15.0 13.3 12.0 10.9 10.0 9.23 8.57 8.00 7.50 7.05 6.66 6.31 6.00 By using UP-DOWN buttons find
dE tý menu.
Gnd A B TR Gnd A B TR
PUL1L
PUL1H
PUL2L
PUL2H
IN1L
IN1H
IN2L
IN2H
PUL1L
PUL1H
PUL2L
PUL2H
IN1L
IN1H
IN2L
IN2H
Voltage Transformer Ratio Setup RS-485 RS-485
In this menu, voltage transformer ratio is set between Press SET button (First digit blinks.)
0000,1 - 4000,0. Auxiliary Current Measuring Input Auxiliary Current Measuring Input
Supply Voltage Measuring Input Supply Voltage Measuring Input
Note: If the voltage transformer is not used between the system Enter the blinking digit value by scrolling UP/DOWN buttons. Un Un
IL1 IL2 IL3 IL1 IL2 IL3
and MPR-53/53S, voltage transformer ratio is entered as 1. Switch to the other digits by using SET button, use BACK button ~ L1 L2 L3 N ~ L1 L2 L3 N
Example: If a voltage transformer which has a ratio of 34.5KV/100V to go to previous digit. After you entered the last digit press SET
is used between the system and MPR-53/53S; Voltage transformer button, dE tý is displayed. (Data is entered but is not activated N
yet. For activating the new data please follow the below steps). 1A 1A
k l
ratio is entered as 345. (34500/100) L1
K L
k l k l
L2 L1
Reactive Energy Calculation Method Setting Press ESC button one by one until (SAU E SEt yES) is displayed. K L K L
k l L2 k l
L3
Three different methods exist for reactive energy calculation in K L K L
N L3
MPR-53/53S. Brief informations about these methods are explained Press SET button. When SAU E SEt yES is displayed, if you
in below table. press ESC button or choose no option instead of yES option
Related values which must be entered in the menu are also by using UP-DOWN buttons, new data will be cancelled and 3 Phase neutral 3 Phase without neutral current input with
previous value will be activated. Aron wiring configuration
indicated in the table in order to select reactive power calculation
method for mechanical and digital energymeters.
Monitoring and Erasing of minimum, maximum and
energy values:
In this menu, values of min.,max. or energy counters are erased.
It saves the instantaneously measured min. and max. values of
Mechanical Energymeter Digital Energymeter Reactive Energy Description MPR-53/53S into its memory. Please kindly look at to the section
(Vectoral summation of 3-phase) (Each phase seperately) (Q) of FUNCTIONS OF BUTTONS for min. and max. values.
90° rotation of Note : Measured electrical parameters which are saved to the
It is the most preferred reactive power calculation
0 1 voltage vector and methode. memory are not affected from the electric interruptions. Max: 30 VDC Max: 30 VDC
multiply with current In the rESEt menu; when you quit from all menus, if you confirm
+
the changes,min. and max. values of all parameters or energy +
_ _
¥ Total value of the multiplication of Vn and In values up counter values are erased at the same time.
2 3 SVn.In.sin(jn)
n=1
to 19 th harmonics. This calculation methode is mostly
preferred for network analysers.
(12-48V DC)
- + - +
(12-48V DC)
- + - +
For erasing the values of min. and max. or energy counter,
In the measurement mode : Gnd A B TR
PUL1L
PUL1H
PUL2L
PUL2H
IN1L
IN1H
IN2L
IN2H
Gnd A B TR
PUL1L
PUL1H
PUL2L
PUL2H
IN1L
IN1H
IN2L
IN2H
Power Triangle Methode : According to this methode; RS-485
RS-485
4 5 S2-P2 Q = S2-P2 Press SET button for 3 seconds (trA Fo menu is displayed)
(Q : Reactive power, S : Active power, P : Apparent power)
Auxiliary Current Measuring Input Auxiliary Current Measuring Input
Supply Voltage Measuring Input Supply Voltage Measuring Input
By using UP-DOWN buttons, Un IL1 IL2 IL3 Un IL1 IL2 IL3
Press SET button for 3 seconds (trA Fo menu is displayed) find rES Et menu. ~ L1 L2 L3 N ~ L1 L2 L3 N
N N
1A 1A
k l
Press SET button. L1
Press SET button (trA Fo Ctr menu is displayed) (rESEt HL menu is displayed)
K L
k l k l
L2 L1
K L K L
L3 k l L2
K L k l
By using UP-DOWN buttons, select L3
By using UP-DOWN buttons, find 3 Phase without neutral K L
which parameter you want to reset. 3 Phase without neutral current input with
CAL CUL Atý on menu. Aron wiring configuration
Press SET button, one of the
parameter rES Et dE / rES Et HL /
Press SET button. (Most right digit of 5th display blinks) rES Et E-1 / rES Et E-2 is displayed. *Available only for MPR-53S
2
7
NETWORK ANALYSER NETWORK ANALYSER
MPR-53/53S MPR-53/53S
Pulse Menu User password Setup:
In this menu, three parameters can be selected : In this menu user password is defined and activated.
PR 19 Box Connection Diagram PUL SE rAt ýo, PUL SE o-1, PUL SE o-2 You must define and activate a 4 digit user password for
PUL SE rAt : Pulse menu which is defined for how many pulses preventing device settings from the illegal usage.
deticated for energy consumption. PUL SE rAt value can be There are 2 sub menus under the Pýn menu.
assigned as below:
Changing of User Password:
L1 K L L1 K L
1, 10, 100 (wh/VArh/VA); 1, 10, 100 (kwh/kVArh/kVA); 1 Mwh/MVArh/MVA.
This menu is used to change the user password .
K L PUL SE o-1 / PUL SE o-2: 1 Pulse is taken for respected energy Note: Factory default value for user password is
L2 k l L2 k l K L
consumption which assigned in PUL SE rAt. o-1 / o-2 can be assigned
K L 0000
k l as below :
L3 L3 k l
k l ACt (Export/Import), A-I (Active Import), A-E (Active Export), rEA (Inductive
N / Capacitive), r-L (Reactive Inductive), r-C (Reactive Capacitive). To change the user password,
6 In the monitoring mode :
1 2 3 4 5 Press SET button for 3 seconds (trA Fo menu is displayed)
IL1 IL2 IL3
1 2 3 4 5 6 Press SET button for 3 seconds (trA Fo menu is displayed)
Current Measuring Input IL1 IL2 IL3
Max: 30 VDC By using UP-DOWN buttons, find PULSE menu.
( 12-48V DC ) Current Measuring Input
Pul C InC In1 In2 RS485 Bu using UP-DOWN buttons, find Pýn menu.
_ Max: 30 VDC
+ 13 14 15 16 17 18 19 20 21 22 ( 12-48V DC )
GND B A TR Pul C InC In1 In2 RS485
Pul 1 Pul 2
_
+ 13 14 15 16 17 18 19 20 21 22 Press SET button (PUL SE rAt ýo menu is displayed)
GND B A TR Press SET button (Pýn ACt IUA tE menu is displayed)
Voltage Measuring Input Auxiliary Pul 1 Pul 2
L1 L2 N
Supply By using UP-DOWN buttons, select PUL SE rAt ýo,
L3
Voltage Measuring Input Auxiliary
Supply PUL SE o-1 or PUL SE o-2. By using the UP-DOWN buttons,
7 8 9 10 11 12 L1 L2 L3 N find Pýn CHA ngE menu.
1A
7 8 9 10 11 12
L1 Press SET button (1k / A-I / r-L blink)
1A
N L1 By using UP-DOWN-SET buttons, enter the old password
3 Phase neutral 3 Phase without neutral current input with N By using UP-DOWN buttons, select required parameter.
Aron wiring configuration
By using UP-DOWN-SET buttons, enter the new password
Press SET button. (Data is entered but is not activated yet.
For activating the new data please follow the below steps)
Press ESC button one by one until SAU E SEt yES is By using UP-DOWN-SET buttons, re-enter the new password.
displayed.
Press SET button. When SAU E SEt yES is displayed, if you Press SET button, Pýn CHA ngE is displayed. (Data is entered
press ESC button or choose no option instead of yES option but is not activated yet. For activating the new data please
by using UP-DOWN buttons, new data will be cancelled and follow the below steps).
previous value will be activated.
Press ESC button one by one until (SAU E SEt yES) is
Energy Counter (Eng Cnt) Menu displayed.
L1 K L L1 K L
MPR-53/53S has 2 energy counters : Press SET button. When SAU E SEt yES is displayed, if you
K L
L2 k l L2 k l Energy counter 1 (E-1), Energy counter 2 (E-2). press ESC button or choose no option instead of yES option
k l K L K L
E-1 / E-2 have 4 parameters : by using UP-DOWN buttons, new data will be cancelled and
L3 L3 on : Activate E-1 / E-2 counters for energy counting without depending previous value will be activated.
k l k l on any parameter. Activating the user password:
ý-1 : Activate E-1 / E-2 counters, when digital input 1 is on (=1).
6 This menu is used for activating the user password.
1 2 3 4 5 ý-2 : Activate E-1 / E-2 counters, when digital input 2 is on (=1).
IL1 IL3
After the user password is activated, while the instant values
IL2
6 E-2: E-1 does not count when E-2 is activated. (Only for E-1) are observed,user password is required in order to enter to
1 2 3 4 5
Current Measuring Input IL1 IL3 E-1: E-2 does not count when E-1 is activated. (Only for E-2) the menu. If the wrong user password is entered, user can
IL2
Max: 30 VDC not enter to the menu.
( 12-48V DC ) Current Measuring Input
Pul C InC In1 In2 RS485 Note: Counting status is undefned if E-2 is selected on E-1 and if E-1 is selected on Note: Factory default value of user password is 0000
_
13 14 15 16 17 18 19 20 21 22 Max: 30 VDC
+ ( 12-48V DC ) E-2. When the status is defined as above, both energy counters count while digital
GND B A TR Pul C InC In1 In2 RS485
Pul 1 Pul 2
_
+ 13 14 15 16 17 18 19 20 21 22 input is not on (=1), but if either one or both digital inputs are on (=1) then counters
GND B A TR will not count.
Voltage Measuring Input Auxiliary Pul 1 Pul 2
Supply Press SET button for 3 seconds (trA Fo menu is displayed) For activating the user password, In the monitoring mode :
L1 L2 L3 N Auxiliary
Voltage Measuring Input
7 8 9 10 11 12
L1 L2 N
Supply
L3 Press SET button for 3 seconds (trA Fo menu is displayed)
1A
Press ESC button one by one until SAU E SEt yES is Press SET button. When SAU E SEt yES is displayed, if you
displayed. press ESC button or choose no option instead of yES option
by using UP-DOWN buttons, new data will be cancelled and
Press SET button. When SAU E SEt yES is displayed, if you previous value will be activated.
press ESC button or choose no option instead of yES option
by using UP-DOWN buttons, new data will be cancelled and
previous value will be activated. 3
6
NETWORK ANALYSER NETWORK ANALYSER
MPR-53/53S MPR-53/53S
Serial Communication (Available only for MPR-53S) Preset Single Register (06) function is used for writting the setting values,
MPR-53S has MODBUS RTU communication protocol which is optical erasing the energy counter or resetting the min., max., demand values. MPR-53S COMPUTER CONNECTION
isolated. All measured parameters can be transfer to the computer. Current transformers ratio can be set 0-2000, voltage transformer ratio can
Transformer ratios and communication parameters can be set, saved be set 1-40000. Min., Max. and Demand values can be only clear. If sent
parameters for demand and energy values can be reset. value is outside of this range device responds with an error message. 31 DEVICES CAN BE CONNECTED AT THE SAME LINE
Parameter Settings (Available only for MPR-53S) i.e. Setting CT as 100;
01 06 80 02 00 64 XX XX
MAX. 1200 mt.
Address : 001-247
01 Device address RS485/RS232
Baud Rate : 2400, 4800, 9600, 19200, 34800 bps
06 Function
CONVERTER
Parity : no, odd and EUEn
80 MSB address
Press SET button for 3 seconds (trA Fo menu is displayed) 02 LSB address
B
00 Data MSB
64 Data LSB A PC
XX CRC MSB
By using UP-DOWN buttons, XX CRC LSB
GND
find rS-485 menu.
Preset Multiple Register(10H) is used to set more then one register at same
time.
...
Press SET button (Adr ESS menu is displayed) i.e. Setting CT as 100, Ut as 20.0;
01 10 80 00 00 02 04 00 C8 00 64 XX XX TR B A GND TR B A GND TR B A GND
01 Device Address
10 Function
By using UP-DOWN buttons, select Adr ESS / bAU d / 80 MSB address
PArýty
00 LSB address
00 Register number MSB
02 Register number LSB MPR-53S-31 MPR-53S-2 MPR-53S-1
Press SET button. (001 / 9600 / no displayed) 04 Byte count
00 Data MSB
C8 Data LSB
By using UP-DOWN buttons, select required parameter 00 Data MSB MAX. 247 DEVICES CAN BE CONNECTED AT SAME LINE BY USING REPEATER.
(001...247 / 2400...38400 / no, EUEn, odd). 64 Data LSB
XX CRC MSB
XX CRC LSB MAX. 1200 mt. MAX. 1200 mt. RS485/RS232
Press SET button, Adr ESS / bAU d / PArýty displayed. (Data is
entered but is not activated yet. For activating the new data please
CONVERTER
Digital Inputs (Available only for MPR-53S)
follow the below steps) Digital input are sent in 16 bit hexadecimal format as below: B
Press ESC button one by one until SAU E SEt yES is
input 1 A PC
displayed. 55H 15 1 0
U U U U U U U U U U U U U U DIN2 DIN1 GND
Press SET button. When SAU E SEt yES is displayed, if you MSB LSB input 2
(Most Significant Byte) (Least Significant Byte)
press ESC button or choose no option instead of yES option
U: undefined
... ...
by using UP-DOWN buttons, new data will be cancelled and
previous value will be activated. TR B A GND
If 12-48 V AC / DC is applied to ln1 (Input 1), 0 (zero) bit of DIN register
MODBUS RTU PROTOCOL (Available only for MPR-53S) is set as 1. Otherwise, 0 (zero) bit is set as 0.
Standart MODBUS RTU message is shown below. If 12-48 V AC / DC is applied to ln2 (Input 2), 1st bit of DIN register is
set as 1. Otherwise, 1st bit is set as 0.
ADDRESS FUNCTION DATA The Parameters are sent in 32bit Hexadecimal format. For Example, 230.0V
T CRCH CRCL T voltage will be sent as 000008FCH. Cosj values shall be divided to 1000. MPR-53S-247 REPEATER MPR-53S-31 MPR-53S-2 MPR-53S-1
8 BIT 8 BIT NX8BIT
0.980 Cosj will be sent as 000003D4H. Energy values are sent in 64 bytes.
1234567890123456789 Wh = AB 54 A9 8C EB 1F 0A 02 Wh
The T times corresponds to a time in which data must not be exchanged
on the communication bus to allow the connected devices to recognize the Specifications for data cable ;
end of one message and the beginning of another. This time must be at - 24 AWG or thicker
least 3.5 characters at the selected baud rate. Adress range (1-247 ) is - Less than 100 ohm/ km Dimensions
address of the connected device. The data field contains data sent to the - Nominal characteristic impedance at 100 kHz of 100 ohms
slave by master or data sent to master by slave. - Less than 60 pF/m mutual capacitance (between two wires in a pair)
10.8 30.1 7.6 9.5
- Less than 120 pF/m mutual pair capacitance ( the capacitance between one
CRC is a error check method by using MODBUS RTU protocol and consists
wire and all others connected to earth).
79.3mm
of 2 bytes.
- Twisted Pair
60.6
70mm
Available Modbus Function:
ERROR CODES (Available only for MPR-53S)
03H READ HOLD REGISTERS Slave device (MPR-53S) sends error message when receive any missing query.
96mm
Error codes are given below.
01 Invalid Function: If any message except given above is used, then 01 error
06H PRESET SINGLE REGISTER messages will be sent.
45.0
90mm
90.0
8.5
If any request of reading of a register, excepted mentioned in register table, 106.0
device will send an error message. For example to read phase1 voltage by
sending a message to the device. 10.0 Type PR 19
01 03 00 00 00 02 XX XX 26.5 21.5
53.0
01 Device address Type PK 26
03 Function 58.0
00 MSB address
00 LSB address
00 Register number MSB
02 Register number LSB
XX CRC MSB
XX CRC LSB
4 5
NETWORK ANALYSER MODBUS REGISTER MAP
MPR-53/53S