+0300083en (1) - 075942
+0300083en (1) - 075942
User manual
NO POWER
& SIGNAL
CABLES
TOGETHER
READ CAREFULLY IN THE TEXT!
H i g h E f f i c i e n c y S o l u t i o n s
ENG
WARNING DISPOSAL
CAREL developed its products thanks to the several years of experience in the INFORMATION FOR THE USERS REGARDING THE CORRECT HANDLING OF
HVAC field, continuous investment in technological innovation of the product, WASTE ELECTRIC AND ELECTRONIC EQUIPMENT (WEEE)
rigorous quality procedures and processes with in-circuit and function tests on
100% of its production, as well as the most innovative production technologies With reference to European Parliament and Council Directive 2002/96/EC issued
available on the market. CAREL and its branch offices/affiliates do not guarantee, on 27 January 2003 and the related national implementation legislation, please
in any case, that all the aspects of the product and the software included in the note that:
product will respond to the demands of the final application, even if the product is • WEEE cannot be disposed of as municipal waste, said waste must be collected
built according to state-of-the-art techniques. separately;
The client (builder, developer or installer of the final equipment) assumes every • the public or private waste collection systems defined by local legislation must
responsibility and risk relating to the configuration of the product in order to reach be used. Moreover, the equipment can be returned to the distributor at the end
the expected results in relation to the specific final installation and/or equipment. of its working life when buying new equipment;
CAREL, in this case, through specific agreements, can intervene as consultant for • this equipment may contain dangerous substances: improper use or incorrect
the positive result of the final start-up machine/application, but in no case can it be disposal of such may have negative effects on human health and on the
held responsible for the positive working of the final equipment/apparatus. environment;
• the symbol (crossed-out wheeley bin) shown on the product or on the
The CAREL product is a state-of-the-art product, whose operation is specified in the packaging and on the instruction sheet indicates that the equipment has been
technical documentation supplied with the product or can be downloaded, even introduced onto the market after 13 August 2005 and that it must be disposed
prior to purchase, from the website www.carel.com. of separately;
Each CAREL product, in relation to its advanced technological level, needs a phase • in the event of illegal disposal of electrical and electronic waste, the penalties are
of definition / configuration / programming / commissioning so that it can function specified by local waste disposal legislation.
at its best for the specific application. The lack of such phase of study, as indicated
in the manual, can cause the final product to malfunction of which CAREL cannot Materials warranty: 2 years (from the date of production, excluding consumables).
be held responsible.
Only qualified personnel can install or carry out technical assistance interventions Type-approval: the quality and safety of CAREL S.P.A. products are guaranteed by
on the product. the design system and ISO 9001 certified production.
The final client must use the product only in the manner described in the
documentation related to the product itself.
Without excluding proper compliance with further warnings present in the manual,
it is stressed that in any case it is necessary, for each CAREL product:
• Not allow the electronic circuits getting wet. Rain, humidity and all types of HACCP: CAUTION
liquids or condensate contain corrosive mineral substances that can damage
the electrical circuits. In any case, the product should be used and stored in
environments that respect the temperature and humidity limits specified in the
manual;
• Not to install the device in a particularly hot environments. Temperatures that
are too high can shorten the duration of the electronic devices, damaging them
and distorting or melting the parts in plastic. In any case, the product should be
The Food Safety programs based on HACCP procedures and on certain national
used and stored in environments that respect the temperature and humidity
standards, require that the devices used for food preservation are periodically
limits specified in the manual;
checked to make sure that the measuring errors are within the allowed limits of
• Not to try to open the device in any way different than that indicated in the the application of use.
manual;
• Not to drop, hit or shake the device, because the internal circuits and Carel recommends compliance with the indications of European standard
mechanisms could suffer irreparable damage.
“Temperature recorders and thermometers for transport, storage and distribution
• Not to use corrosive chemical products, aggressive solvents or detergents to of chilled, frozen, deep-frozen/ quick-frozen food and ice cream – PERIODIC
clean the device;
VERIFICATION “, EN 13486 -2001 (or subsequent updates)or similar standards and
• Not to use the product in application environments different than those prescriptions applicable in the country of use.
specified in the technical manual.
The manual contains further indications regarding technical feature, proper
All the above reported suggestions are also valid for the control, serial boards, installation and configuration of the product.
programming keys or however for any other accessory in the CAREL product
portfolio.
CAREL adopts a continuous development policy. Therefore, CAREL reserves the
right to carry out modifications and improvements on any product described in
this document without prior notice.
The technical data in the manual can undergo modifications without forewarning.
NO POWER
The liability of CAREL in relation to its products is specified in the CAREL general & SIGNAL
CABLES
contract conditions, available on the website www.carel.com and/or by specific
TOGETHER
agreements with customers; specifically, to the extent where allowed by applicable
legislation, in no case will CAREL, its employees or subsidiaries be liable for any READ CAREFULLY IN THE TEXT!
lost earnings or sales, losses of data and information, costs of replacement
goods or services, damage to things or people, downtime or any direct, indirect, WARNING: separate the probe cables and the digital input cables as
incidental, actual, punitive, exemplary, special or consequential damage of any
much as possible from the inductive load and power cables to prevent
kind whatsoever, whether contractual, extra-contractual or due to negligence, or
possible electro-magnetic interference. Never introduce power cables
any other liabilities deriving from the installation, use or impossibility to use the
product, even if CAREL or its subsidiaries are warned of the possibility of such and signal cables (including those of electric control board) into the same
damage. cable troughs.
UltraCella has a port for the insertion of a USB memory key to:
• load the languages for the graphic terminal during the first UltraCella
commissioning;
• parameters upload/download;
• other operations reserved for the service centre (e.g. software update);
• download log of temperature recorded.
When mounting the optional modules are matched to the right of the
main control system and connected to it with watertight coupling, to Fig. 1.a
ensure the IP degree of protection of the assembly.
Main characteristics:
• 6 relay outputs: compressor, defrost, fan, light, AUX1, AUX2;
• assembly on guide DIN or wall;
• LED board with bright display with 3 digits, with decimal point and 1.1 Codes
icons that indicate the operating status; Codes Description
• integration of the keys in the front panel (LED board) to ensure a high WB000S**F0 UltraCella, led display with single row
degree of protection (IP65) and safety during operation and cleaning; WB000D**F0 UltraCella, led display with double row
• availability of 10 sets of parameters (recipes) preloaded by CAREL Tab. 1.a
but modifiable, corresponding to the same number of parameters
configurations, to adapt the control to the specific conservation needs
required by the cold room;
• navigation on intuitive user interface with contextual backlight
keyboard;
• defrost can be driven using the keyboard, digital input and supervisor;
• various types of defrost managements, on one or two evaporators:
natural (with stop compressor), resistance, hot gas;
• control of compressors with up to 2 Hp or up to 3 Hp with the
accessory power module;
• temperature control with virtual adjustment probe;
• digital inputs that can be configurated for alarm activation, enabling or
activating defrost, door switch, auxiliary output, on / off, etc;
• control of 1 compressor with double step or of two compressors, even
with rotation;
• keyboard safety: operation of the single keys can be disabled to avoid
tampering;
• light management by door switch or dedicated key;
• alarm buzzer; Fig. 1.b Fig. 1.c
• HACCP function: temperature monitoring and adjustment in case of
alarm due to high temperature during operation or after black out;
• RS485 network connection for remote monitoring and supervision
sytems.
Codes Description
WM00ENS000 Ultra EVD Module without EVD display
WM00ENSI00 Ultra EVD Module with EVD I/E display
WM00ENNI00 Ultra EVD Module “blind” - commissioning through UltraCella
Tab. 1.b
Fig. 1.g
Fig. 1.j
30 30
47,5
47,5
87,5
87,5
290
290
N N
107,5
107,5
47,5
47,5
32 32 62 62 62
200 200 100 100 380 380
Mounting
A: with DIN rail B: without DIN rail
260
2
1
Ø 4,5
156
1.a: Fix the DIN rail and insert the controller 1.b: Make 4 holes (Ø 4,5 mm) according to the drilling
template and insert the dowels (mm)
1
1
2 1 2
2 2
1 1
2
1
1
2
1 2
1
1
2.a: Remove the frames, loosen the screws (1) and open the panel 2.b: Remove the frames
A A
1
2
1
2
1
B N
1
2
1 2
B A A
3.a: Mark on the wall the positions of the lower holes, 3.b: Fasten the screws (1) and fix the panel. Loosen the screws (2) and open the panel.
remove the panel and perform the drills (Ø 4.5 mm); insert
the plugs. Replace the panel on the DIN guide and fix it
fastening the lower screws.
1
2
connection
N
to option
modules
2.2 Structure
Models with single digit display cod. WB000S*
3 4 3
Key
1 Keyboard
2 Display
3 Wall mounting holes
4 Locking screws
5 Connector for UltraCella Service (*)
6 Green LED (*)
7 Red LED (*)
3 8 7 6 5 4 3 8 USB Port (*)
(*) Visible after removing the bottom frame
Fig. 2.c
Key
1 Keyboard
2 Display
3 Wall mounting holes
4 Locking screws
5 Connector for UltraCella Service (*)
6 Green LED (*)
7 Red LED (*)
8 USB port (*)
3 8 7 6 5 4 3
(*) Visible after removing the bottom frame
Fig. 2.d
GND
GND
250 V
UL 873 8 A res. 2FLA 5
12 LRA R1
4
3
2
1
230 V
20 A max
Fig. 2.e
87,5
290
260
drilling template
107,5
107,5
Ø32 Ø32
Ø 4,5 1 2
47,5 47,5
DIN RAIL
43
UltraCella Expansion
260
Module
214
Ø 4,5 mm
156 24 103
Fig. 2.g
Mounting
1 3
A B
2 1
2
2
1
1
2
1: Use a hole saw to drill the panel in correspondence with the predrilled 2: Remove the faceplates. Unscrew the screws (3) and open the
holes (steps A, B). If present, fasten the DIN rail for the module. UltraCella control
1 1
1 A A
B N
2
1 1
1 B A A
3: Raise the cover or remove the faceplates and unscrew the screws to 4: Put the module close to UltraCella control and insert the coupling
remove the panel and open the module. clamps supplied as standard.
B B A A
PRI 230 V PRI 230 V
B B N
COMA
NOA
1 3 2 4
G0
VBAT
G
N
COMA
NOA
1 3 2 4
G0
VBAT
G
SEC 24 V SEC 24 V
C C
VREF
GND
DI1
DI2
S1
GND
S4
S2
S3
Tx/Rx
VREF
GND
DI1
DI2
S1
GND
S4
S2
S3
Tx/Rx
B A A B A A
CAREL
ExV
Rx/Tx+
Rx/Tx-
GND
GND
GND
bianco/white
VL
verde/green
48 47 46 45 44 43 30 B3 CAREL NTC, PT1000
31 29 B2 CAREL NTC, PT1000
marrone/brown
32 28 B1 CAREL NTC, PT1000 giallo/yellow
33 27 Y1 analog output (0 to 10 Vdc, PWM)
34 26 B4 CAREL NTC, analog input 0 to 10 Vdc
49 50 51 52 53 54 35 25 B5
36
GND
Rx/Tx-
Rx/Tx+
GND
Rx/Tx-
Rx/Tx+
38 22 + Vdc +V
39 21 DI1 DI1 (**) 24 Vac
FieldBus BMS 40 20 DI2
41 19 DI3
42 Door switch 2 AT
25 VA
COMA
NOA
1 3 2 4
G0
VBAT
G
18
24 Vac
17
UltraCella Control
16
R6 CMP
R5 - R6 15
EN60730-1 12 (10) A
250 V 14
UL 873 12 A res. 2HP R5 DEF
12FLA 72 LRA 13
12
FAN
11
R3 - R4 R4
10 A res. 10
EN60730-1 5 (3) A LIGHT
250 V 9
UL 873 10 A res. 5FLA R3
18 LRA 8
R2
7
VREF
GND
R1 - R2
DI1
DI2
GND Tx/Rx
S1
S2
S3
S4
2
1
230 V
20 A max NTC
B N
C
2 3
B N
C
6 5
2 3
6 5
B A A
B A A
Fig. 2.l
Fig. 2.m
Power
Module
Rx/Tx+
Rx/Tx-
GND
GND
GND
VL
48 47 46 45 44 43 CMP
30 B3 CAREL NTC, PT1000
31 29 B2 CAREL NTC, PT1000
32 28 B1 CAREL NTC, PT1000
33 230 V~
27 Y1 analog output (0 to 10 Vdc, PWM)
34 26 B4 L N
49 50 51 52 53 54 CAREL NTC, analog input 0 to 10 Vdc
35 25 B5
GND
Rx/Tx-
Rx/Tx+
GND
Rx/Tx-
Rx/Tx+
11
FAN 5 2 6 5
R3 - R4 R4
10 A res. 10
EN60730-1 5 (3) A LIGHT
250 V 9
UL 873 10 A res. 5FLA R3
18 LRA 8
R2
7
R1 - R2 2 3
EN60730-1 8 (4) A N.O. 6
250 V
UL 873 8 A res. 2FLA 5 6 5
12 LRA R1
to connector 4
board BROWN
3
2
1
230 V
20 A max (*) Note: highlighted wires and 3hp relay supplied with the module code
WM00P0003N
Fig. 2.n
Rx/Tx+
Rx/Tx-
to LED display board
GND CAP
GND
GND
VL
48 47 46 45 44 43 30 B3 CAREL NTC, PT1000 Non rimuovere il cappuccio di
B
31 29 B2 CAREL NTC, PT1000 protezione!
ULTRACAP
32 28 B1 CAREL NTC, PT1000 Do not remove the protection cap!
Module
33
49 50 51 52 53 54
34
27
26
Y1
B4
analog output (0 to 10 Vdc, PWM)
CAREL NTC, analog input 0 to 10 Vdc
C D
35 25 B5
36
GND
Rx/Tx-
Rx/Tx+
GND
Rx/Tx-
Rx/Tx+
18
24 Vac
17 S2 S1
16
R6 CMP
R5 - R6 15
EN60730-1 12 (10) A
250 V 14
UL 873 12 A res. 2HP R5 DEF
GASType
Super Heat
12
FAN
11
R3 - R4 R4
10 A res. 10
EN60730-1 5 (3) A LIGHT
250 V 9
UL 873 10 A res. 5FLA R3
18 LRA 8
R2
7
R1 - R2
EN60730-1 8 (4) A N.O. 6
250 V
to connector board
shield
230 Vac
shield
Fig. 2.o
160
300
Fig. 2.p
•
•
•
•
290 to connector board
DEF
FAN
CMP
LIGHT
160
0 to 5Vdc
analog output (0 to 10 Vdc, PWM)
CAREL NTC, PT1000
CAREL NTC, PT1000
CAREL NTC, PT1000
2.9 Ultra 3ph module
B5
input
analog
Fig. 2.s
CAREL NTC, analog input 0 to 10 Vdc
(4 to 20 mA)
300
Fig. 2.r
DEF
FAN
Fig. 2.q
CMP
LIGHT
0 to 5Vdc
19 19
452FULL
analog output (0 to 10 Vdc, PWM)
1
condenser fan 1 MV3:1 101 XA1:103
M
Unscrew 6 fixing screws of frontal cover
18 18
CAREL NTC, PT1000
CAREL NTC, PT1000
CAREL NTC, PT1000
P
19 19
B5
20 20
analog
(4 to 20 mA)
1
condenser fan 2 MV4:1 105 XA1:104
M
18 18
condenser fan 2 MV4:2 106 XA1:108/XA1:102
21 21
crankcase heater RR2 107 KM3:62
18 18
crankcase heater RR2 108 XA1:106
38 38
aux 1 AUX1:1 109 KR2:11
37 37
aux 1 AUX1:2 110 KR2:14
25 25
L
kriwan AP2:L 111 FU2:2/XA1:113 27 27
AUX 1 AUX1:1 109
N
kriwan AP2:N 112 KR1:A2/FU1:2 26 26
25 25 AUX 1 AUX1:2 110
kriwan AP2:11 113 XA1:128/XA1:111
28 28 18 18
kriwan AP2:14 114 XA1:115 termostato di sicurezza TS1 117
P
28 28 20 20
pressure switch SP2 115 XA1:114
29 29 termostato di sicurezza TS1 118
pressure switch SP2 116 KR1:A1 19 19
27 27 Clicson evaporatore SP3 119
security thermostat TS1 117 ??:J10/NO1 380
31 31 22 22
security thermostat TS1 118 KM2:A1 Clicson evaporatore SP3 120
30 30 16 16
evaporator clicson SP3 119 ??:J10/NO2
33 33 UltraCella AP3:L 128
evaporator clicson SP3 120 KM1:A1 15 15
29 UltraCella AP3:N 129
121 ??:J11/C3/4/5
32 28 28
Ultra 3PH
123 29 29
P
35 35 defrost ST1 141
pump down TK1 124 30 30
186
130
34 34 defrost aux ST2 142
pump down TK1 125 KM3:A1
32 32 29 29
liquid valve YV1 126 XA1:122 defrost aux ST2 143
24 24 31 31
127
17
liquid valve YV1 KM3:A2/XA1:129 146
25 25 ventilatore evaporatore 0-10 Vdc Y TS2:Y
ultracella ULTRACELLA:L 128 ??:J12/NC6/XA1:113 29 29
24 24 ventilatore evaporatore 0-10 Vdc GND TS2:GND 147
ultracella ULTRACELLA:N 129 XA1:127/KR2:A2
39 39 25 25
AP1
Ultra 3PH
42 33 33
temp condensatore ST3 144 ??:J2/U3 controllo + AP1:J6/+ 161
I/O module
40 40
temp condensatore ST3 145 ??:J2/GND/XA1:143 34 34
45 45 controllo GND AP1:J6/GND 162
fan evaporatore 0-10vdc Y 7AP1:Y 146 ??:J2/U6 17
40 40 PE1
fan evaporatore 0-10vdc GND 7AP1:GND 147 KR1:11
46 46
controller - AP1:J6/- 160 AP:- PE2
47 47
controller + AP1:J6/+ 161 AP:+
AWG 22
48 48 PE3
controller GND AP1:J6/GND 162 AP:GND
TC1
AP1
26
PE109 TC1:PE
KR2
Important:
KR3
KR3
XA1
XA1
KM2
KM3
current absorption on the loads
XP1
KM2
KM1
XP1
cables (probes, digital inputs) and serial cable
KM1
QF2
QF1
QF2
90
80
70
63
QF1
QM1
• use cable with section suitable to current rating they have to carry
• separate the power cable (power supply, actuators) from the signal
Warnings:
• incorrect connection of the power supply may seriously damage the
control system;
• use cable ends that are suitable for the terminals. Loosen every screw
and fit the cable end, next tighten the screws and gently pull the cables Fig. 2.t
to check their tightness. If using an automatic screwdriver, adjust the UltraCella can be connected to both PlantVisor and PlantWatch via BMS
torque to a value less than 0.5 N · m; port (RS485).
• separate as much as possible (by at least 3 cm) the probe signal and Starting from 1.5 release software, both CAREL and Modbus protocols are
digital input cables from inductive loads and power cables, to avoid available from BMS port, selectable by H7 parameter.
any electromagnetic disturbance. Never lay power cables and probe - H7 = 0 CAREL protocol
cables in the same cable conduits (including those for the electrical - H7 = 1 Modbus protocol
panels). Do not install the probe cables in the immediate vicinity of
power devices (contactors, circuit breakers or other). Reduce the Starting from software release 1.7, the baud rate, stop bits and parity of
length of the sensor cables as much as possible, and avoid spirals the BMS port can be set using parameters H10, H11 and H12; the data bits
around power devices; setting on the other hand remains fixed at 8.
• only use IP67 guaranteed probes as end defrost probes; place the
probes with the vertical bulb upwards, so as to facilitate drainage of
any condensate. Remember that the thermistor temperature probes
(NTC) have no polarity, so the order of connection of terminals is not
important.
1. display the active loads and the main variables: temperature, humidity;
2. perform the control programming, facilitated by contextual help.
1 2 1 2
2
1
1 2 1 2
Note: the figure refers to the screens on models with single row
Fig. 2.u display, P/Ns WB000S*. In models with two rows, P/Ns WB000D*,
as well as the message indicated, during navigation the display shows the
scrolling message "recipes in USB device” on the second row.
2.13 Upload/downloadparameters(USBmemory
key)
Note: the download and upload operations, as well as the 10 lists
The USB memory key must be placed in the connector accessible after of parameters, also copy all the other parameters (one value only
removing the lower frame. Using the USB memory key you can: for all 10 lists).
1. download the parameters set (r01...r10): control saves inside the key the
10 parameters set;
2. upload the parameters set (r01...r10): control loads from the key the
10 parameters set);
2
1
USB key
Fig. 2.v
19 UltraCella +0300083EN - rel. 1.7 - 07.01.2016
ENG
3. USER INTERFACE
The front panel contains the display and keyboard, made up from 10
or 11 keys (depending on the model), which, pressed individually or
together, allow to perform all of the controller programming operations.
The accessory UltraCella Service terminal, accessory terminal, allows the
commissioning of the control system via a guided procedure (Wizard)
and also programming the parameters with a contextual help that
explains the various functions.
3.1 Display
On the LED display is shown the temperature range from -50 °C (-58 °F)
to +150 °C (302 °F). The resolution of the tenth for temperatures in the
range -19,9…99,9. In case of alarm the value of the probe is displayed in
alternance with the codes of the active alarms. During programming, it
displays the codes that identify the parameters and their value.
Note: you can select the standard display by properly configuring
parameter /t1 (/t1 and /t2 for double digit models).
Front panel for single row display models Front panel for double row display models
UltraCella Service Terminal (accessories)
cod. WB000S* cod. WB000D*
MENU
Multifunction menu
MENU
Multifunction menu
H M
HELP E E
HACCP L
P
Multifunction menu N
U
H M
HELP E E
PRG
HACCP L
P
Multifunction menuSET N
U
ESC
HACCP
PRG SET
ESC
HACCP
Normal operation
Icon Function Note
ON OFF Flashing
Technical Alarms, for example alarm due to EEprom Serious problem detected. Please contact
support or probe fault technical service
HACCP HACCP function enabled - HACCP alarm saved (HA and/or HF)
Door Door open Door Close Door open and door alarm active
Blinks when the activation of the
Compressor On Off Waiting for activation
compressor is delayed by safety times.
Blinks when the activation of the
Fan On Off Waiting for activation
compressor is delayed by safety times.
On if a scheduled defrost is
Clock
requested
Tab. 3.a
Door Door open Door Close Door open and door alarm active
Blinks when the activation of the
Compressor On Off Waiting for activation
compressor is delayed by safety times.
Blinks when the activation of the
Fan On Off Waiting for activation
compressor is delayed by safety times.
On if a scheduled defrost is
Clock
requested
Celsius Temperature visualization in
- .
degrees Celsius degrees
Farenheit Temperature visualization in
-
degrees Farenheit degrees
humidity
Humidity visualization -
percentage
Tab. 3.b
3.2 Keyboard
Key Normal operation Blink
Pressing the individual key Combined pressure with other keys
• Pressed for 2 s, turns the control OFF
• Pressed for 2 s, turns the control ON
On/Off
• ESC function, return to higher level Prg + Set: if pressed at the same time for 2
• Pressed for 2 s, enters the programming menu s, allow access to the multifunction menu
• In case of alarm: mutes the audible alarm (buzzer) and Available only in case of alarm
deactivates the alarm relay
ALARM • Pressed for 2 s, reset the manual reset alarms
• Turns the light on/off
• Turns auxiliary output 1 on/off (*) Flashing for 5 seconds: attempt to activate
auxiliary output 1 from button, yet output
has different configuration
• Turns auxiliary output 2 on/off (*) Flashing for 5 seconds: attempt to activate
auxiliary output 1 from button, yet output
has different configuration
• Activates/deactivates manual defrost Awaiting activation
DEF
• Set point setting Prg + Set: if pressed at the same time for 2 Indicates that the set point is not that
• Value setting s, allow access to the multifunction menu the value set for parameter St but rather
defined by one of the following algorithms:
• Set point variation from digital input
(St+r4)
• Set point variation by time band (St+ r4)
• Set point ramps (variable set point)
• Value increase/ decrease
/
UP/DOWN
Tab. 3.c
(*) To activate outputs AUX1 / AUX2 by button, set H1/H5=2. If parameters
are not set, if AUX1/AUX2 key are pressed, they blink for 5 seconds
Note: in the LED display model the keys are illuminated according
to the menu where the user is operating, in order to facilitate
navigation. Note: in the parameters or set point modification procedures, the
new value is saved every time the Set key is pressed.
1 2 1 2
3.3.3 Modificationoftheparameters(formodelswithdouble
digit display cod. WB000D*)
Procedure:
1. to modify the parameters, first switch the controller OFF (press ON/OFF
button);
1 2 1 2
2. press Prg for 2 sec: the second row of the display will show “PASS”
(password required);
3. press UP/DOWN to enter the password: 22;
Note: the figure refers to the screens on models with single row 4. press Set; the second row of the display will scroll the name of the first
display, P/Ns WB000S*. In models with two rows, P/Ns WB000D*, category of parameters: Probes (see the previous table and the
as well as the message indicated, during navigation the display shows the parameter table);
scrolling message “Setpoint” on the second row 5. press Set: the second row of the display will scroll the code and
description of the first parameter in the category: /21 – Probe1
meas. stab.; the first row of the display will show the current value of
the parameter;
6. press Set: the value on the first row of the display flashes, to indicate that
3.3.2 Modificationoftheparameters(formodelswithsingle
the value can be modified;
digit display cod. WB000S*) 7. press UP/DOWN until reaching the desired value;
Procedure: 8. press Set to confirm the new value; the value will stop flashing;
1. to modify the parameters, first switch the controller OFF (press ON/OFF 9. press UP/DOWN to scroll the other parameters;
button); 10. repeat steps 6) to 9) to modify other parameters;
2. press Prg for 2 s: on the display appears the message “PAS” - password 11. press Prg to return to the top level of parameter categories, or UP/
request; DOWN to move the next category: CtL (Control). Then repeat steps
3. press UP/DOWN and insert the password: 22. If you press Set, the code of from 5) to 9) to access the category and modify other parameters;
the first parameters category will appear: Probes (see the following 12. press Prg once or more than once to exit the parameter setting
table and parameters table); procedure and return to the standard display.
4. press Set: the first parameter of the category will appear: /21;
5. press UP/DOWN until reaching the parameter to be modified;
6. press Set key to display the parameter value;
7. press UP/DOWN to reach the desired value;
8. press Set to confirm the new value and return to parameter code display;
9. repeat the operations from 5) to 8) to change other parameters;
10. press Prg to return to higher level of the parameters categories and UP/
DOWN to pass to the next category: CtL. Repeat steps from 4) to 8) to
access the category and change other parameters;
11. press one or more times Prg to exit the parameters modification
procedure and return to standard display visualization.
1 2 1 2
1 2 1 2
Note: the figure refers to the screens on models with single row
display, P/Ns WB000S*. In models with two rows, P/Ns WB000D*, as well
as the message indicated, during navigation the display shows with a
scrolling message, parametercode and description: “tce - enable data
modification”.
1 2 1 2
Note: if no key is pressed, after about 120 s the control
automatically returns to standard display.
Note: the figure refers to the screens on models with single row
display, P/Ns WB000S*. In models with two rows, P/Ns WB000D*, as well
3.3.4 Example 1: current date/time setting as the message indicated, during navigation the display shows with a
scrolling message, parameter code and description: “dd1 - defrost1-day”
Procedure:
1. access the parameters modification menu as described in the relative
paragraph;
2. enter category “rtc”;
3. select parameter “tcE” and set it to 1 to enable the date exchange;
4. press UP 2 times and then set the parameters regarding the year (Y),
month (M), day of the month (d), hour (h), minutes (n) (see table
below);
5. press UP, select tct parameter and set it from 0 to 1 or from 1 to 0 to
perform the data/ time change;
6. select again parameter tcE and set it to 0;
7. press one or more times Prg to save the date/ time and return to
standard display.
3. Press Set to confirm.The control system loads the chosen parameters set;
4. Press once or more times Prg to return to standard display..
Note: the figure refers to the screens on models with single row
display, P/Ns WB000S*. In models with two rows, P/Ns WB000D*, as well
as the message indicated, during navigation the display shows the
scrolling message “bni - recipe index now active” on the second row.
Param Configurations
Std Red meat Poultry Fish Vegetables Fruit Summer and Frozen Restaurant - Bakery
CAREL tropical fruit fresh food
Heater Heater Heater defrost Heater defrost Timed defrost No defrost, Heater defrost Heater defrost Heater
defrost defrost with probe, with probe, by stopping evap. fans with probe, with probe, defrost
with probe, with probe, evap. fans evap. fans compressor, on with evap. fans evap. fans with probe,
evap. fans evap. fans controlled by on with evap. fans on compressor on with on with evap. fans
controlled by controlled by temperature compressor with compressor on, humidity compressor on compressor on controlled by
temperature temperature and off during on and on on and on control and off during and on during temperature
and off and off defrost during defrost, during defrost, defrost defrost and off
during during humidity humidity control during
defrost defrost control defrost
r01 r02 r03 r04 r05 r06 r07 r08 r09 r10
/4 0 0 0 0 0 0 0 0 0 0
/t2 6 4 4 4 4 4 11 4 4 4
/A2 1 1 1 1 1 0 0 1 1 1
/A3 0 0 0 0 0 0 0 0 0 0
/A4 0 0 0 0 0 0 0 0 0 0
/A5 0 0 0 0 1 1 1 0 0 0
St 0 -0,5 0 1 4 4 10 -22 3 -20
rd 2 2 2 2 2 2 2 2 2 2
StH 90 90 90 90 95 95 85 90 90 90
rdH 5 5 5 5 5 5 5 5 5 5
r1 -50 -5 -5 -5 0 0 5 -25 0 -25
r2 60 10 10 10 10 10 15 -15 10 -10
r3 0 0 0 0 0 0 1 0 0 0
c11 4 4 4 4 4 4 4 4 4 4
d0 0 0 0 0 0 2 0 0 0 0
dI 8 12 12 12 24 24 8 15 13 15
dt1 4 20 15 10 8 4 4 15 10 15
dP1 30 60 60 60 45 30 30 60 90 60
AL 0 4 4 4 4 5 5 10 4 10
AH 0 5 5 10 5 5 5 6 5 6
Ad 120 60 60 120 60 60 60 60 60 60
A5 0 0 0 0 0 0 0 0 0 0
A9 0 0 0 0 0 0 0 0 0 0
F0 0 1 1 1 0 0 0 0 0 1
F1 5 -8 0 0 5 5 5 5 5 -22
F2 30 30 30 30 15 15 10 30 30 30
F3 1 1 1 1 0 0 0 1 0 1
F4 1 1 1 1 1 1 1 1 1 1
H1 1 0 0 0 0 0 0 0 0 0
H5 1 2 2 2 15 15 15 3 2 3
HO1 0 0 0 0 0 0 0 0 0 0
c12 5 5 5 5 5 5 5 5 5 5
d8d 30 30 30 30 30 30 30 30 30 30
tLi 120 120 120 120 120 120 120 120 120 120
A4 0 0 0 0 0 0 0 0 0 0
Tab. 3.e
For all other parameters not included in this table, the default values will be used for all configurations, as shown in chap.7 Parameter table.
3.4.3 Defrost
In order to activate the defrost by temperature, the defrost probe must
detect a temperature lower than the temperature relative to defrost end 3.4.4 AUX1/AUX2/Light
(par. dt1). The defrost by time is activated setting dI parameter to a value In order to activate/deactivate the digital outputs AUX1/AUX2 (auxiliary
>0. mode outputs) from keyboard set the parameters H1/H5=2. The light
output is fixed and cannot be configured.
Procedure:
1. press DEF. There can be 3 cases: ACTIVATION
2. if the defrost probe detects a temperature greater than the value of the Press keys AUX1/AUX2/Light: message “On” will appear and the control
defrost end temperature, the control displays the message “no” and activates the relative output.
the defrost is not activated;
3. if there are protections in progress, the control waits before entering
the defrost. The DEF button blinks and when conditions permit, the
control enters the defrost;
4. control comes into defrost, it shows the message “On”. The DEF key is lit 1 2 1 2 1 2
1 2 1 2 1 2
3.4.5 On/Off
In order to turn off the control from keyboard:
• press On/Off for 2 s.
The display will alternate Off to the standard display.
The key On/Off lights up and any active output relay will be deactivated.
1 2 1 2 1 2
Note: The Figures refer to the screens on models with single row
display, P/Ns WB000S*. In models with two rows, P/Ns WB000D*,
the message “On” and “Off ” appear on the second row of the display.
Procedure:
1. press Prg and Set for 2 s; the first menu will appear: HcP;
2. press UP/DOWN to view other entries;
3. press Set to enter: follow the steps described in the following sections for
the relative explanations;
4. Press one or more times Prg to return to standard display.
1 2 1 2
Note: the figure refers to the screens on models with single row
display, P/Ns WB000S*. In models with two rows, P/Ns WB000D*,
as well as the message indicated, during navigation the display shows the
1 2 1 2
scrolling message “HACCP Alarms” on the second row.
Note: the figure refers to the screens on models with single row
display, P/Ns WB000S*. In models with two rows, P/Ns WB000D*,
as well as the message indicated, during navigation the display shows the 3.5.2 Continuous cycle
scrolling message “Menu” on the second row.
For explanation of continuous cycle, see chapter 6.
In order to activate the continuous cycle
• the control must be on;
3.5.1 HACCP alarms display • the value of the parameter cc must be >0.
For explanations regarding HACCP alarms, consult chapter “Alarms”.
Par. Description Def Min Max U.o.M.
In the multifunction menu you can see the date and time of the last 3 cc Continuous cycle duration 0 0 15 hour
alarms HA and HF. After entering the multifunction menu (see previous
par.), select with UP / DOWN the message “HcP”. After entering the multifunction menu (see previous par.), select with UP
/ DOWN the message “cc”.
Procedure:
1. press Set, and then UP / DOWN to display the parameters in the following
table: you can see the number of alarms, the relative date and you ACTIVATION
can also cancel the alarms; Procedure:
2. press Set to display the alarm date and time; 1. press Set; the message “OFF” will appear (continuous cycle disabled);
3. press Prg until you return to standard display. 2. press UP/DOWN: the message “ON” appears;
3. after about 1 s the control returns to standard display and the
compressor icon appears, to show the activation of the function.
1 2 1 2 1 2 1 2
Note: by pressing UP you will cancel both the maximum and the
minimum recorded temperature.
Note: the Figures refer to the screens on models with single row
display, P/Ns WB000S*. In models with two rows, P/Ns WB000D*:
1 2 1 2 • MAX --> Max temp recorder (scrolling)
• 36,9 --> Max
Note: the figure refers to the screens on models with single row • 13.Y --> year
display, P/Ns WB000S*. In models with two rows, P/Ns WB000D*, • 11.M --> month
as well as the message indicated, during navigation the display shows the • 22.d --> day
scrolling message “Continuous cycle” on the second row. • 9.H --> hour
• 34.m --> minute
DEACTIVATION
Follow the same activation steps and set “OFF”.
3.5.4 Input/output status display
Note: the activation of the continuous cycle function does not After entering the multifunction menu (see previous par.), select with UP
appear on display in standard mode. / DOWN the message “I/O”.
Procedure:
1. Press Set: the message “b1” appears regarding the probe B1;
3.5.3 Maximumandminimumtemperaturemonitoring 2. Press Set once again: the value read on probe B1 will appear alternating
The control allows you to continuously record the minimum and with the message b1;
maximum temperature measured by the control probe. The monitoring 3. Press Prg to return to upper level;
is always active. The values can be reset, as described below. 4. Press UP/DOWN and repeat steps 1)…3) to display the inputs/outputs
indicated in table;
After entering the multifunction menu (see previous par.), select with UP 5. Press one or more times Prg to return to standard display
/ DOWN the message “rEc”.
Text Description TextDescription
Procedure: b1 Analogue input 1 do5 Digital output 5
1. press Set; the message “MAX” will appear (maximum registered b2 Analogue input 2 do6 Digital output 6
temperature); in order to see the maximum temperature, registration b3 Analogue input 3 Y1 Analog output 1
date and time pass to point 3 or: b4 Analogue input 4 ESu EVD EVO suction temp.
2. press UP/DOWN: the message “MIn” appears (minimum temperature b5 Analogue input 5 ESA EVD EVO evap. temp.
di1 Digital input 1 ISu EVD ICE suction temperature
registered);
di2 Digital input 2 ISa EVD ICE evaporation temperature
3. press Set: the maximum/minimum recorded temperature will appear di3 Digital input 3 U1 Defrost probe Sd1 (3PH model)
along with the date/time of record (y=year, m = month, d = day, h = do1 Digital output 1 U2 Auxiliary defrost probe Sd2 (3PH
hour, m = minutes. Press UP to cancel (both temperatures), appears model)
RES and the control exits the menu, or press Prg for more than once do2 Digital output 2 U3 Condenser probe Sc (3PH model)
and exit the display. do3 Digital output 3 dU4 Motor protector (3PH model)
do4 Digital output 4 dU5 High/low pressure switch or Kriwan
Example: maximum registered temperature 36.9°C on 22/11/2013 at 9.34. alarm (3PH model)
Tab. 3.f
Note: the opened digital inputs/outputs are displayed along with
the message “oP” (=open), those closed with “cLo” (=closed).
Example 1: probe B1 measures the temperature of -1.0 °C..
1 2
1 2
1 2 1 2
1 2 1 2
1 2 1 2
Note: the figure refers to the screens on models with single row
1 2 1 2
display, P/Ns WB000S*. In models with two rows, P/Ns WB000D*,
as well as the message indicated, during navigation the display shows the
scrolling message “Probe1 status” on the second row “.
27 UltraCella +0300083EN - rel. 1.7 - 07.01.2016
ENG
Example 2: digital input 1 is closed.
1 2 1 2 1 2
1 2
Note: the figure refers to the screens on models with single row
display, P/Ns WB000S*. In models with two rows, P/Ns WB000D*,
as well as the message indicated, during navigation the display shows the
Note: the figures refer to the screens on models with single row
scrolling message “Digital input 1 status” on the second row.
display, P/Ns WB000S*. In models with two rows, P/Ns WB000D*,
as well as the message indicated, during navigation the display shows the
scrolling message “recipes in USB device” on the second row
3.5.5 USB memory key Note: the download and upload operations, as well as the 10 lists
Parameters upload/download of parameters, also copy all the other parameters (one value only
for all 10 lists).
Preliminary operations:
1. remove the lower frame and insert the USB memory key;
2. set the control to OFF.
Download saved alarms
Starting from software release 1.5, the last 64 alarms activated and saved
on UltraCella can be downloaded to a USB flash drive, in order from the
most recent to the oldest, in csv format. When the 64th alarm is saved, the
1
2 next one will overwrite the oldest.
Alarms that have been saved and are no longer active can only be
displayed on the UltraCella Service terminal, but can be downloaded
both from the terminal and the LED interface.
1. remove the bottom frame and plug in the USB flash drive. The red
USB key
and green LEDs on the side of the key will come on individually in
sequence to indicate that the unit recognises the USB flash drive;
Fig. 3.d 2. press Prg and Set for 2 sec; the first menu is displayed: “HcP”;
3. press UP 4 times until reaching the “USB” menu item;
After entering the multifunction menu (see previous par.), select with UP
4. press Set; the first submenu is shown: “rcP”;
/ DOWN the message “USb”.
5. press UP to access the “ALG” submenu;.
Procedure:
Press Set: the following commands will appear by scrolling UP/DOWN:
• rcP: press Set to confirm;
• EXt: press Set to exit;
• dnL: press Set, the control saves inside the key the 10 parameters set:
r01…r10;
1 2
• uPd: press Set, the control loads from the key the 10 parameters set:
r01…r10;
Note 6. press SET to confirm the download of the saved alarms. The message
“ALG” will flash during the download procedure; at the end, “ALG” will
• the parameters are saved in a text file type. txt, which can be viewed stop flashing and the green LED next to the USB port will come on,
on the computer; indicating the end of the procedure; if for some reason the procedure
• for information regarding the switching of the LEDs, see chapter 2.10.
is not successful, the alarm icon will be shown on the display;
7. unplug the key; to exit the “ALG” menu, press PRG twice.
Example: alarms saved starting 2 April 2014 at 10:30:00. The alarm log was
downloaded to the USB flash drive at 16:22:45 on the same day.
Start -> alarm activated
Stop -> alarm reset
1 2 1 2
TIME ID NAME EVENT VAR1 VAR2
2014-04-02 T10:30:00+00:00 11 ALARM_Ed1.Active Start
2014-04-02 T16:22:45+00:00 11 ALARM_Ed1.Active Stop
USB key
1 2 1 2 1 2 Fig. 3.f
Fig. 3.e To activate the data logging function, the probe/probes to be recorded
Procedure: must be configured (up to max 2) through the parameters tr1 and tr2.
1. press Set: the message “vEr” appears regarding the software revision; The sample time (for both the variables) is selectable between 2 and 60
2. press Set once again: the software revision will appear (e.g. 1.7); minuts (default 5).
3. press one or more times Prg to return to standard display .
Par. Description Def Min Max U.o.M.
Note: the figure refers to the screens on models with single row First temperature to be 0 0 8 -
display, P/Ns WB000S*. In models with two rows, P/Ns WB000D*, tr1 recorded selection
as well as the message indicated, during navigation the display shows the 0 = no log
scrolling message “Application version” on the second row 1 = Sv
2 = Sm (sonda letta da B1)
3 = Sr
4 = Sd1
3.5.7 Data logging function 5 = Sd2
UltraCella introduces the data logging function to cold room control, 6 = Sc
offering the possibility to record the temperature or the humidity read 7 = SA
by two probes. 8 = Su (humidity probe)
tr2 Second temperature to be 0 0 8 -
How to download the file with variables recorded by UltraCella: recorded selection
1. remove the bottom frame and insert the USB flash drive. The red and 0 = no log
green LEDs next to the flash drive will come on once in sequence to 1 = Sv
indicate the that unit has recognised the USB flash drive; 2 = Sm (sonda letta da B1)
2. press Prg and Set for 2 s; the first menu will be displayed: “HcP” 3 = Sr
3. press UP or DOWN until reaching the “LoG” menu item; 4 = Sd1
4. press SET to confirm the download of the recorded variables (log file) to 5 = Sd2
the USB flash drive. The message “LoG” will flash during downloading; 6 = Sc
at the end, “LoG” will stop flashing to indicate that the download has 7 = SA
been completed; if the procedure fails for some reason, the alarm icon 8 = Su (humidity probe)
trc Sample time temperature 5 2 60 min
will be shown on the display; recording
5. remove the flash drive; to exit the “LoG” menu, press PRG and/or SET.
• Channels recorded: two probes selected through tr1 and tr2
parameters
• Start logging: as soon as parameter tr1/tr2 is set to a value >0. The
instant the setting is confirmed is recorded in the log under event
name “Start”
• Sample time: trc (minutes) for both the variables
• Data logging duration: depends on the sampling time trc and the
1 2 maximum number of samples Nrec that UltraCella can record (209000),
based on the following formula:
Note: the figure refers to the screens on models with single row Data logging duration = Nrec * trc
display, P/Ns WB000S*. In models with two rows, P/Ns WB000D*,
as well as the message indicated, during navigation the display shows the Sampling time (trc) Data logging duration
2 min 290 days
scrolling message “recorder” on the second row.
5 min 726 days (around 2 years)
10 min 1451 days (around 4 years)
Note: if the procedure fails for some reason, when exiting the 30 min 4353 days (around 8 years)
60 min 8708 days (around 24 years)
menu, as well as the alarm icon the error message “LoG” will • Data extraction: any USB flash drive available on the market can be
also be shown on the display. used
The message error will be cleared after the next correct download or • Extracted log file names: Log_UltraCella_1.csv for the first variable
when restarting the controller. selected through the parameter tr1, Log_UltraCella_2.csv for the
When the probes to be recorded are suitably configured through the second variable selected through the parameter tr2
parameters tr1 and tr2 and the sample time through the parameter trc, • Other events: as well as the “Start” event, the log also records “Stop”
the unit starts recording the variables every trc minutes (sample time) for events (tr1=0 or tr2=0) and “Boot” (starting or restarting the controller)
a maximum period of 2 years each. After the second year, the controller • Log data format: the data is organised in columns: date (in standard
overwrites the oldest data saved. ISO 8601 format) , type of event, value of the variable specify as Src1
The variables log is available as a csv file via USB flash drive, which can be (first variable) and Src2 (second variable)
analysed in Excel or other widely-available programs.
The update.ap1 file needed to perform the update from the UltraCella
LED interface must only be supplied by CAREL personnel.
1. Create an “upgrade” folder in the main directory on the USB flash drive.
Copy the update.ap1 file to the new folder;
2. remove the bottom frame and plug in the USB flash drive. The red
and green LEDs on the side of the key will come on individually in
sequence to indicate that the unit recognises the USB flash drive;
3. press Prg and Set for 2 sec; the first menu is displayed: “HcP”;
4. press UP or DOWN until reaching the “SOF” menu item; Selecting the language
5. press SET to confirm the software update. The message “SOF” will flash
during the update; at the end, “SOF” will stop flashing, indicating 1. On the UltraCella Service terminal, access the multifunction menu by
the end of the procedure; if for some reason the procedure is not pressing the UP button;
2. The HACCP icon is displayed. Press UP or DOWN until reaching the“i”icon
successful, the alarm icon will be shown on the display; (information);
6. unplug the key; to exit the “SOF” menu, press PRG and/or SET 3. Press SET to access the language setting;
4. Select the desired language (in software release 1.6, the languages
available are Italian, English, German, French and Spanish) by
pressing UP or DOWN. Press SET to confirm. The change is effective
immediately;
5. Press ESC twice to exit the language selection menu and return to the
main screen
1 2
HACCP
Types of interfaces:
• board with LED display: parameters configuration is performed using
the display and the keyboard based on the procedure described in
chap.3 “parameters change”. Alternatively, you can connect the remote
graphic terminal “UltraCella Sevice Terminal” and enter the wizard
menu for first commissioning (wizard);
• USB memory key: put the control on OFF and load the programming
parameters from USB memory key (uPd command, UPLOAD, see
Chapter 3); Fig. 4.a
• supervisor: in order to facilitate the launch of a large number of controls
UltraCella using only the supervisor you can limit the operation of the
first commissioning to the serial address setting. The configuration is
postponed to a later time using the supervisor.
After the configuration you can enable the control of the cold room by
pressing the ON/OFF key.
1 2 1 2
4.2 Parameterstobesetforthecommissioning
Par Description Categ. Def Min Max U.o.M.
St Set point CtL 0 r1 r2 °C/°F
rd Differential CtL 2.0 0.1 20 °C/°F
/P Type B1 to B3 Pro 0 0 2 - 1 2 1 2
0=enabled
6. Press repeatedly UP to reach 7. Press Set to set the value of the
1=disabled
the parameter /P. parameter (see settings in the
tLi Light on with door open doL 120 0 240 min
A4 Light management doL 0 0 1 - parameter table).
0 = door switch + light key
1 = light key
c1 Minimum time between CmP 6 0 30 min
compressor starts
c2 Minimum compressor off time CmP 3 0 15 min
c3 Minimum compressor on time CmP 3 0 15 min
Tab. 4.a
1 2 1 2
1 2 1 2
12. Press UP to move to category CtL and follow the previous steps to set St
and the following parameters.
Fig. 4.b
11. Press UP to move to category CtL (the second row scrolls the name of
the second category of parameters: Control) and follow the previous steps
to set St and the subsequent parameters, as shown in the previous table
and in the parameter table.
1. First switch the controller OFF (press ON/OFF).
2. Press Prg for 2 sec: the second row of the display will show “PASS”
(password required).
+
ESC
H M
E E
L
P
Multifunction menu N
U
PRG SET
ESC
HACCP
H M
E E
L Parameters Categ. 1/16 N
Fig. 4.c P U
1-Probes
If the UltraCella controller has never been configured, as soon as the PRG SET
2-Control
terminal is connected, the wizard is shown automatically. The Wizard 3-Compressor
menu can also be accessed to repeat the guided commissioning ESC
Fig. 4.h
3. Press DOWN until reaching the “Wizard” menu
H M
2 E E
1
L Parameters Categ. 16/16 N
P U
Fig. 4.d
Fig. 4.i
Remove the bottom faceplate and connect the UltraCella Service
Terminal to the controller. 4. Confirm by selecting Set.
H M
E E
L
P Wizard N
U
Do you want to use the
4.5.1 First start - up PRG Wizard to configure
SET
When starting for the first time, once the Service Tool is connected, the the cold room ?
wizard is shown automatically. Select the desired language and then ESC
YES
answer the questions to set the other parameters.
H
E
M
E
Fig. 4.j
L Wizard N
P U
5. Press Up and SET to enter the guided commissioning procedure.
PRG Language: English SET
Up/Down: Choose language
Prg/Set: 1st question 4.6 Main function commissioning
ESC
Fig. 4.k
Key
Fig. 4.f St Set point
Sv Virtual probe
1.Switch the controller OFF (press DOWN and select the On/Off icon; rd Differential
press Set twice and then UP to switch the controller OFF; press Esc twice CMP Compressor
to exit) Note: see par. "6.3 Set point" for the options related to the
regulation of the control set point
Below the parameters with the selection: 4.6.4 Probes reading correction
The values read by the probes can be corrected by adding/removing an
Par. Description Def Min Max U.o.M. offset from the measure with the parameters /c1, ..., /c5.
/P Type B1 to B3 0 0 2 -
0 = NTC Standard Range -50T90°C Par. Description Def Min Max U.o.M.
1 = NTC Enhanced Range 0T150°C /c1 Offset B1 0 -20.0 20.0 °C/°F
2 = PT1000 /c2 Offset B2 0 -20.0 20.0 °C/°F
/c3 Offset B3 0 -20.0 20.0 °C/°F
/P4 Type B4 0 0 2 - /c4 Offset B4 0 -20.0 20.0 °C/°F/%rH
0 = NTC Standard Range -50T90°C /c5 Offset B5 0 -20.0 20.0 °C/°F/%rH/bar/psi
1 = NTC Enhanced Range 0T150°C
2 = 0 to 10 V The offset may need to comply with HACCP requirements. In this case,
/P5 Type B5 0 0 1 -
the offset should be calculated using a calibrated instrument. Setting
0 = 4 to 20 mA
these parameters affects the measurement and the value shown on the
1 = 0 to 5 Vrat
display, and consequently may not be allowed. If in doubt, contact the
food safety manager or site manager.
Selection Contacts
OPEN CLOSE ON
Timer
OFF
0 = Not active - -
1 = Immediate external alarm active not active ON UNIT 1
2 = Do not select - - Defrost
3 = Enable defrost not enabled enabled
4 = Start defrost not active active OFF
5 = Do not select - -
ON UNIT 2
6= Remote On/Off OFF ON
7 = Do not select - - Defrost
8 = Low pressure switch low pressure status normal status
9 = Do not select - - OFF
10 = Do not select - - UNIT 3
ON
11 = Do not select - -
12 = AUX activation deactivated activated Defrost
13 = Do not select - -
OFF
14 = Continuous cycle activation contact opening contact closing
(deactivation) (activation) t
15 = Alarm from generic function active / not active active / not active dP(1) dP(2) dP(3)
Tab. 4.c d5(2)
d5(3)
Below are indicated the parameters used to explain the selections for A5
and A9. Fig. 4.m
Key
1 = Immediate external alarm dP Maximum defrost duration
UNIT 1…3 Unit 1…3
Application: external alarm that requires immediate activation (for d5 Defrost delay form digital input
example, high pressure alarm or compressor thermal overload). The t Time
activation of the alarm:
1. • shows the message on the display (IA);
• activates the buzzer, if enabled; 5 = Do not select
• activates the alarm relay, if selected;
2. involves the following actions on the actuators: 6=On/Off remote
• compressor: operates depending on the values assigned to
parameter A6 (stop compressor on external alarm). The digital input can also be programmed as a remote ON/OFF switch.
• fans: continue to operate according to the fan parameters (F). When the control is set to OFF:
• the temperature is displayed alternately with the message “OFF”, the
Note: internal timer relative to the parameter dI is updated. If dI expires when
the unit is OFF, a defrost is performed when the unit is switched on
• when stopping the compressor, the minimum ON time (c3) is ignored. again;
• if more than 1 input is configured on immediate alarm, the alarm is • the auxiliary relays remain active set as an auxiliary output and light,
generated when one of the inputs is opened. the other auxiliary outputs are off;
• the buzzer and the alarm relay are off;
2 = Do not select • the control does not perform the control functions, defrosts, continuous
cycle, temperature alarm signalling and all the other functions;
3 = Enable defrost • the compressor protection times are respected.
Application: Any defrost request arriving when the contact is open will At control restart, all functions are reactivated, except:
remain pending until the contact closes. • defrost at start-up;
• compressor and fan delay at start-up.
A5/ A9 = 3
Contacts Defrost
Note: The ON/OFF from external digital input has priority over the
Open Not enabled keypad and the supervisor.
Closed Enabled (defrost start is still determined by the control)
Close with active when the digital input is opened, the defrost is
defrost immediately stopped and the unit restarts normal 7 = Do not select
operation (without performing the dripping or post-
dripping phases). The LED starts flashing to indicate 8 = Low pressure switch
that the defrost request is pending, waiting for the next
enabling signal (closing of the contact), when the defrost By setting A5/A9=8 you can manage the low pressure switch. The low
will be performed completely. pressure alarm “LP” is signalled when the low pressure switch is triggered:
Tab. 4.d • during normal regulation, with active compressor and pump down
function is disabled (c7=0)
35 UltraCella +0300083EN - rel. 1.7 - 07.01.2016
ENG
• with pump-down function enabled (c7 >0), if the pump down valve is 4.6.8 Door opening
opened and the compressor is active. If the door is left open, the signalling control is made via the door
The low pressure alarm signal is delayed by the time set for parameter A7. switch (if A3=1, digital input DI1, already configured as the door switch,
The low pressure alarm ‘LP’ stops the compressor. is disabled). When the door is open, the evaporator fans are turned off
if configured at fixed speed (F0=0,1), otherwise operate at minimum
speed defined by parameter F7 (if F7<50) if set as variable speed fans
(F0= 2); the compressor continues to operate for the time c12, then turns
off. Once passed the period of time d8d from door opening, compressor
and evaporator fans are running again and the error “dor” is displayed.
Par. Description Def Min Max U.o.M.
1 2 1 2
c12 Compressor safety time, door switch 5 0 5 min
0 = disabled door management
d8d Compressor restart time for door switch 30 c12 240 min
9, 10, 11 = Do not select Special cases refer figure 4.n and 4.o:
• to disable door alarm, set d8d =0. If d8d = 0, c12 is also considered =0;
12 = Auxiliary output • to keep only phase 2 (figure), in which the compressor is on, and to
eliminate phase 3 in which the compressor/ evaporator fan is off, set
Setting H1/H5 = 2 the corresponding output AUX1/ AUX2 is activated d8d=c12;
by the key AUX1/ AUX2 or from DI if set. Besides, it is possible to use • to keep only phase 3 (figure), c12=0;
alternatively one digital input DI2 or DI3 (set A5 or A9=12) to drive output • during phase 3 the compressor may be on if:
AUX2 or AUX3. In this case the key and the digital input have the same 1. pump down is activated;
priority as regards the switch on. 2. hot gas defrost is activated.
13 = Do not select
Note: If the door switch digital input DI1 is disabled (A3=1):
14 = Continuous cycle activation • Parameters C12 and d8d have no meaning, as the controller
Activation: passage of the contact from opened to closed; cannot know whether the door is open or closed
Deactivation: passage of the contact from closed to opened. • The door open icon will always be off
ON
Step1
4.8 Other configuration parameters
The configuration parameters must be set during the commissioning of
OFF the controller and concern:
ON
• date/time set;
• measurement stability of the analogue probes;
Step2 • display of the decimal point on control;
• serial address for monitoring network connection;
OFF
• ithe type of protocol on the BMS serial port for connection to the
Power_ON
t supervisor network
c0 c11 • temperature (°C / °F) and pressure (bar/psi) measurement unit
• disabling of keyboard, keys and buzzer;
Fig. 4.p
• display view during defrost.
Note: c2 parameter used to ensure the balance of the pressure
after the compressor stop and to avoid blocking at the next Date/ time set
reboot of those compressors that do not have sufficient starting torque. See example 2 in chap.3.
4.7.1 Door switch + light key Par. Description Def Min Max U.o.M.
/t1 Display variable 1 1 0 13 -
If A4=1 the light is on/off only using the light key. The open/closed status 0 None 7 B1
of the door is ignored. If A4=0, when the cold room door is opened, the 1 Virtual probe 8 B2
light is always on. When the door is closed, the light can be turned on or 2 Outlet probe 9 B3
off using the light key. Once turned on, the light will automatically turn 3 Intake probe 10 B4
off after the time set in parameter tLi. 4 Defrost probe 1 11 B5
5 Defrost probe 2 12 Sc
6 Set point 13 Variable speed
LIGHT CONTROL FROM DOOR SWITCH AND LIGHT KEY condenser
fans set point
ON
A4=0 /t2 Display variable 2 6 0 23 -
0 None 12 rd
Light_K 1 Virtual probe 13 superheat (EVD
EVO)
OFF 2 Outlet probe 14 valve opening
% (EVD EVO)
OP
3 Intake probe 15 valve opening
Door_sw step (EVD EVO)
4 Defrost probe 1 16 Sc
CL 5 Defrost probe 2 17 Sd1 (3PH mod.)
6 Set point 18 Sd2 (3PH mod.)
ON 7 B1 19 Sc (3PH mod.)
8 B2 20 Variable speed
Li condenser fans
set point
OFF
9 B3 21 Superheat
(EVDice)
t 10 B4 22 Valve opening
tLi tLi
% (EVDice)
11 B5 23 Step valve
Fig. 4.q opening
(EVDice)
37 UltraCella +0300083EN - rel. 1.7 - 07.01.2016
ENG
Serial address (parameter H0) 4.9 Ultra EVD EVO module commissioning
H0 assigns an address to check for serial connection to a supervision
WM00ENNI00: Connect UltraCella to the EVD module via serial, as shown
system and / or remote assistance.
in the wiring diagram in Figure 2.k, and refer to the following parameter
Par. Description Def Min Max U.o.M. table for configuration of the EVD EVO driver. The module will become
H0 Serial Address 193 0 247 - active when enabled by UltraCella, setting P1=1.
Starting from software release 1.5, both CAREL and Modbus protocols Par. Description Def Min Max U.o.M.
are available on the BMS serial port, selected by parameter H7. P1 Enable communication with EVD EVO 0 0 1 -
module
Note: H0 maximum value is 207 for CAREL protocol and 247 for 1 = EVD EVO module enabled
Modbus protocol.
WM00ENSI00 & WM00ENS000:
Par. Description Def Min Max U.o.M. 1. Using the EVD EVO display to configure the driver
H7 BMS serial protocol 0 0 1 -
Connect an auxiliary output on UltraCella (AUX1 or AUX2) electrically to
0= CAREL protocol
digital input DI1 on the EVD EVO and set the parameters as follows:
1= Modbus protocol
Starting from software release 1.7, the baud rate, stop bits and parity of • H1=7 (for AUX1) or H5=7 (for AUX2) -> delayed second compressor
the BMS port can be set using parameters H10, H11 and H12; the data bits • C11=0 -> second compressor activation delay = 0
setting on the other hand remains fixed at 8.
Par. Description Def Min Max U.o.M.
Par. Descrizione Def Min Max UoM H1 AUX1 output configuration 1 0 17 -
H10 BMS baud rate bit/s 4 0 9 - 7 = Delayed compressor
0 1200 5 38400 H5 AUX2 output configuration 1 0 17 -
1 2400 6 57600 7 = Delayed compressor
2 4800 7 76800 C11 Second compressor start delay 4 0 250 sec
3 9600 8 115200 0 = instant start with main compressor
4 19200 9 375000 output
H11 BMS stop bits 2 1 2 - In this way, the auxiliary output will be configured as a voltage-free contact
1 1 stop bit to control the compressor, suitable to be connected to digital input DI1
2 2 stop bits on the EVD EVO driver. No configuration is required on UltraCella.
H12 BMS parity 0 0 2 -
2. Configuring the EVD EVO driver from UltraCella
1 odd
Connect UltraCella to the EVD EVO module via serial, as shown in the
2 even
wiring diagram in Figure 2.k, and refer to the following parameter table
for configuration of the EVD EVO driver. The module will become active
Note: to make the changes active, switch the unit off and on
when enabled by UltraCella, setting P1=1.
again.
If connected via serial, the driver parameters can only be displayed (not
modified) on the EVD EVO local display. Once the driver has been enabled
Temperature unit of measure and decimal point display (parameter P1=1), its parameter settings will be sent by UltraCella, in
The control allows: accordance with the parameter table below (only modifiable from
• choosing the temperature measuring unit between Celsius (°C) and UltraCella); any parameters previously configured on the EVD EVO display
Fahrenheit (° F) degrees; will be overwritten.
• to enable/disable the display of the decimal point and buzzer.
Par. Description Def Min Max U.o.M.
Par. Description Def Min Max U.o.M. P1 Enable communication with EVD EVO 1 0 1 -
/5t Temperature unit of measure 0 0 1 - module
0/1 = °C / °F 1 = EVD EVO module enabled
/SP Pressure unit of measure 0 0 1 -
0/1 = bar / psi
/6 Display decimal point 0 0 1 - EVD EVO parameter table
0/1 = yes/no The following parameters corresponding to the EVD EVO driver can be
H4 Buzzer 0 0 1 - configured from UltraCella
0/1 = enabled/disabled Category: EVO
Par. Description Def Min Max U.o.M.
Disable keypad P1 Enable communication with EVD EVO 0 0 1 -
You can inhibit some functions relating to the use of the keypad, for module 0/1=disabled/enabled
example, the modification of the parameters and the set point if the unit P1t S1 probe type 0 0 3 -
is accessible to the public 0 RAZ. 0-5V 2 4 to 20mA REMOTE
Par. Description Def Min Max U.o.M. 1 4 to 20mA 3 4 to 20mA EXTERNAL
H6 Terminal keys block configuration 0 0 255 - P1M Max value of S1 probe 12,8 -20 200 bar/psi
0 = all keys enabled. P1n Min value of S1 probe -1 -20 200 Bar/psi
255 = all keys disabled
Configuration table
FUNCTION par. H6
Set-point modification 1
Defrost 2
- 4
AUX1output 8
PRG+SET (menu) 16
AUX2 output 32
On/Off management 64
Light management 128
Tab. 4.e
Example: to disable the activation functions of the outputs AUX1 and
AUX2, set H6 = 8+32 = 40.
Parameter name Description Def Min Max U.o.M. Type Parameter Present on Present
on EVD ICE name on UltraCella in wizard
UltraCella Service pGD (UltraCella
(LED display) Service pGD)
- Enable EVD ICE 0 0 1 - Advanced IPE
/1 = not enabled/ enabled
Operating mode 1=Multiplexed cabinet/cold room 1 1 6 - Initial IrE
2=Air-conditioner/chiller with plate heat (modes 2, configuration
exchanger 3, 4, 5 and 6
3=Air-conditioner/chiller with tube can only be
bundle heat exchanger selected on
4=Air-conditioner/chiller with finned UltraCella
coil heat exchanger service
5=Reserved
pGD)
6=Reserved
Superheat Superheat set point 11 C1 99 K Initial IP3
configuration
Type of gas 1=R22 2=R134a 3=R404A 3 1 23 - Initial PH
4=R407C 5=R410A 6=R507A configuration
7=R290 8=R600 9=R600a
10=R717 11=R744 12=R728
13=R1270 14=R417A 15=R422D
16=R413A 17=R422A 18=R423A
19=R407A 20=R427A 21=R245FA
22=R407F 23=R32
S1 Type of probe S1 3 1 11 - Advanced IS1
1=-1 to 4.2 barg
2=0.4 to 9.3 barg
3=-1 to 9.3 barg
4=0 to 17.3 barg
5=0.85 to 34.2 barg
6=0 to 34.5 barg
7=0 to 45 barg
8=-1 to 12.8 barg
9=0 to 20.7 barg
10=1.86 to 43.0 barg
11 = Reserved
CP PID: proportional gain 15 0 800 - Advanced ICP -
ti PID: integral time 150 0 999 sec Advanced Iti -
C1 LowSH protection: threshold 5 -9 IP3 °C/°F Advanced IC1 -
C2 LowSH protection: integral time 15 0 800 sec Advanced IC2 -
C3 LOP protection: threshold -50 -121 C5 °C/°F Advanced IC3 -
C4 LOP protection: integral time 0 0 800 sec Advanced IC4 -
C5 MOP protection: threshold 50 C3 392 °C/°F Advanced IC5 -
C6 MOP protection: integral time 20 0 800 sec Advanced IC6 -
C7 MOP protection: disable threshold 30 -121 200 °C/°F Advanced IC7 -
C8 Low suction temperature alarm threshold -121 -392 200 °C/°F Advanced IC8 -
IA Enable operating mode modification 0 0 1 - Advanced IIA -
0/1 = enabled/not enabled
U1 Enable manual valve positioning 0 0 1 - Advanced IU1 -
0/1 = enabled/not enabled
U2 Manual valve position 0 0 999 step Advanced IU2 -
U3 Valve control steps: 1/2 = 480/960 step 1 1 2 - Advanced IU3
U4 Valve opening at start (evaporator/valve 50 0 100 % Advanced IU4 -
capacity ratio)
n1 Serial address 99 1 99 - Advanced In1
- Enable EVD ICE regulation 0 0 1 - Advanced ICG
0/1 = not enabled/ enabled
Note: as EVD ICE has a two digit display, when its parameters are
displayed on UltraCella, the letter “I” has been added to every
parameter code: e.g. S1 -> IS1
Note: all EVD ICE parameters are visible both on the LED user
interface and on the UltraCella Service terminal (pGD).
c1
c3 c2
ON
Step1
OFF
ON
Step2
OFF
Power_ON
t
c0 c11
Fig. 5.a
Key
Step1 Step 1 compressor
Step2 Step 2 compressor
t Time
CMP
ON
6.2 Virtual probe
The control output of the controller is the compressor output. The control
probe is the ambient probe B1 (default setting), while the probes B2, B3, OFF
B4, B5 may be associated with the functions of defrost probe 1/2, outlet
probe, intake probe, condenser probe. If the cold room is very large you rd Sv
should also use a second probe to control the temperature of the room. St
The controller will activate the compressor based on the requirements
of the virtual probe (Sv), obtained from weighed average of the 2 probes Fig. 6.b
(B1, B2). Key
St Set point
Par. Description Def Min Max U.o.M.
rd Differential
/4 Virtual probe composition 0 0 100 - Sv Virtual probe
0 = probe B1 CMP Compressor
100 = probe B2
If you have activated the second compressor output (H1, H5 = 13, 14) on
The /4 parameter is used to determine the virtual probe (Sv) as a weighted AUX output, the activation of the compressor is at St + rd/2 and that of
average of the control sensor probe B1 and B2, according to the formula: the auxiliary compressor AUX in St + rd, according to the figure below.
[(B1*(100-/4)+B2*/4] AUX
Sv= ON
100
OFF
CMP
ON
OFF
rd/2 rd
rd/2 Sv
St
Fig. 6.c
UltraCella
Key
St Set point
rd Differential
Sv Virtual probe
CMP Compressor
AUX Auxiliary output
Fig. 6.a
The control set point, in normally operating conditions, is indicated by
Key parameter St.
B1 Outlet probe This value may however change based on other algorithms:
B2 Intake probe • Set point variation from digital input (St+r4)
• Set point variation by time band (St+r4)
• Set point variation by ramp (variable set point)
with the following priority:
Par. Description Def Min Max U.o.M. Note: when set point variation is enabled, the SET button flashes
A5 Configuration of digital input 2 (DI2) 0 0 15 - to indicate that the control set point is not the value set for
7 = set point variation parameter St.
A9 Configuration of digital input 3 (DI3) 0 0 15 -
7 = set point variation Note: if the second row of the display shows the set point (/t2 =
6, on models where featured), the value displayed will be the
When the digital input is active (closed), the control set point will be the effective control set point (therefore, either St or St + r4, depending on
sum of the values of parameters St and r4; when the digital input is not whether or not the time band is active).
active (open), the control set point will be the value set for parameter St
(normal operation).
6.3.3 Set point ramps
• DI2 / DI3 not active (open) -> control set point = St
• DI2 / DI3 active (close) -> control set point = St + r4
Very large cold rooms used to preserve food at below-zero temperatures
Par. Description Def Min Max U.o.M. (freezers) may, for logistics or constructional reasons, require concrete
r4 Offset set point 3,0 -20,0 20,0 °C/°F floors. Initially, the cold room, and thus its floor, which are initially at
ambient temperature, if cooled to the set point in the shortest possible
time (pull down), cracks may form in the floor, causing significant damage.
Note: when set point variation is enabled, the SET button flashes For this reason, in these types of cold rooms ramps of variable duration
to indicate that the control set point is no longer the value set for and intensity are used to bring the cold room to the set point over a time
parameter St. that is suitable for the concrete floor.
On UltraCella, ramps can be configured that are divided into three phases.
Note: if the second row of the display shows the set point (/t2 = The slope of the ramp depends on the final temperature set point and
6, on models where featured), the value displayed will be the the duration of each phase.
effective control set point (therefore, either St or St + r4, depending on Phase 1: typically this is an initial cooling ramp, from ambient temperature
the status of the digital input) to a final temperature around 0°C, lasting several days (default 6 days).
Phase 2: typically this is a phase in which the temperature reached in
phase 1 is maintained, lasting several days (default 2 days)
Phase 3: this is the second and final cooling ramp to the final temperature
6.3.2 Set point variation by time band set point for storing the frozen food and, being the most critical phase,
With UltraCella, the control set point can also be changed based on time typically lasts longer (default 10 days).
bands, using the RTC fitted on the device. The function is similar to the
one described in the previous paragraph, however this is more useful Par. Description Def Min Max U.o.M.
when needing to change the set point repeatedly at fixed times. PS1 Ramps: final set point, phase 1 0 -50,0 200,0 °C/°F
When the time band is active, the control set point will be the sum of the PS2 Ramps: final set point, phase 2 0 -50,0 200,0 °C/°F
values of parameters St and r4. PS3 Ramps: final set point, phase 3 -30,0 -50,0 200,0 °C/°F
PH1 Ramps: duration of phase 1 6 0 10 days
PH2 Ramps: duration of phase 2 2 0 10 days
• Time band not active -> control set point = St PH3 Ramps: duration of phase 3 10 0 10 days
• Time band active -> control set point = St + r4
Example: ramp starting from an ambient temperature of 30°C, the first
Par. Description Def Min Max U.o.M.
phase reaches 0°C in 6 days (phase 1), maintained at 0°C for 2 days (phase
r4 Offset set point 3,0 -20,0 20,0 °C/°F
2) and final cooling ramp to the set point of -30°C over 10 days (phase 3).
To activate set point variation by time band, a time band needs to be
REFRIGERATION CURVE FOR COLD ROOMS
enabled by setting the following parameters:
30 °C
0 = disable 10 °C
48 hours
1, 2, …7 = Sunday, Monday, … Saturday at 0°C
8 = Monday to Friday 0 °C
11 = every day
hSn Start set point variation by time band: 0 0 23 hours -20 °C
hours
-30 °C
MSn Start set point variation by time band: 0 0 59 min h h h h h h h h h h 0h 0h 0h 0h 0h 0h 0h 0h 0h
00 00 00 00 00 00 00 00 00 00 d0 d0 d0 d0 d0 d0 d0 d0 d0
minutes 0d 1d 2d 3d 4d 5d 6d 7d 8d 9d 10 11 12 13 14 15 16 17 18
time after starts of ramps
hSF End set point variation by time band: 0 0 23 hours
hours
MSF End set point variation by time band: 0 0 59 min Note: when the ramps are active, and throughout their duration,
minutes the control set point is no longer the value indicated by parameter
H9 Enable set point variation by time band 0 0 1 - St, but is automatically recalculated, depending on the values set for
0/1=disabled/enabled parameters PSi and PHi, every 12 hours.
Example: to have a control set point of 4°C from Monday to Saturday, Note: in the event of a blackout when a ramp is in progress, when
power returns, the ramp resumes from where it was interrupted if
45 UltraCella +0300083EN - rel. 1.7 - 07.01.2016
ENG
the temperature in the cold room during the blackout has not increased The pump down has the aim to completely empty the evaporator of the
by a value greater than parameter Pdt from the set point reached just refrigerant at each stop of the compressor. After this phase, you can safely
before the blackout turn off the compressor, so that the liquid is not present the next time the
• if (set point before blackout – current cold room temperature) ≤ compressor is started. When the set point is reached, the control closes
Pdt -> brief blackout -> resume ramp from the phase where it was the pump down valve to stop the flow of refrigerant to the evaporator,
interrupted, with a new starting set point equal to the temperature and, after a certain time, the compressor. In the application diagram
reached by the cold room, and the phase lasts the remaining duration there are the pump down valve and the low pressure switch. When the
(as if the blackout had not occurred); control requires turning on the compressor, if the safety periods c1 and
• if (set point before blackout – current cold room temperature) > Pdt c2 have passed, the pump down valve is opened and after the time set in
-> extended black-out, the temperature has increased too much -> parameter c8 the compressor is activated.
restart the ramp from the beginning (phase 1, PS1, PH1).
This aims to avoid damage to the floor due to an excessively fast pull Par. Description Def Min Max U.o.M.
down. c7 Maximum pump down time (PD) 0 0 900 s
0 = Pump down disabled.
Par. Description Def Min Max U.o.M. c8 Compressor start delay after opening of 5 0 60 s
Pdt Ramps: maximum set point variation 20,0 10,0 30,0 °C/°F pump down valve PD
after blackout H1 Configuration of output AUX1 1 0 17 -
…5 = pump down valve
H5 Configuration of output AUX2 1 0 17 -
…5 = pump down valve
Note: At the end of the third phase, the control set point returns
to the value set for parameter St -> to avoid abrupt variations, it is
recommended to set PS3 = St. C
CMP
Enable ramps
L
The ramps need to be enabled by setting parameter Pon=1
c7 c7 c7 c7
t
Fig. 6.e Fig. 6.f Fig. 6.g
Key Note: low pressure = pressure off/open.
CMP, FAN Compressor, fan
PDV pump down valve Key
Pressure switch Pressure switch CMP, FAN Compressor, fan t Time
Sv Virtual probe VPD Pump down valve AtS Autostart in pump down
c7 Pump down maximum time St Set point Pressure switch Pressure switch
Pd Pump down alarm Sv Control probe
t Time
St Set point
Note: Notes:
• if during the pump down there is a new demand for cooling, the pump • at compressor autostart, the safety times c1 and c2, not c3 are
down procedure terminates, and the pump down valve is opened (the respected;
compressor is already on from the previous pump down phase); • the message “AtS” is reset automatically on the next correct pump
• in case of “Pd” alarm the auto-start function is disabled. down cycle.
on parameter d0:
0. electric heater defrost by temperature (placed near the evaporator); dP1
t
1. hot gas defrost by temperature.
2. electric heater defrost by time; Fig. 6.h
3. hot gas defrost by time. Key
Note: Ed1 and Ed2 indicate that the defrost ended due to time- t Time
out. dt1 End of defrost temperature
dP1 Maximum defrost duration
Sd Defrost Probe
Note: Ed1 and Ed2 alarms can be disabled by A8 parameter. d0 Type of defrost
DEF Defrost
Par. Description Def Min Max U.o.M.
A8 Ed1, Ed2 enable 0 0 1 -
0/1= disabled/enabled
1. electric heater defrost (d0 = 0, 2): operating cycle.
The operating cycle refers to default values of the parameters F2 and F3.
The end of the defrost cycle can be by temperature, and in this case it is
necessary to install the defrost probe Sd (to select between B2 and B3) or
by time. In the first case the defrost ends if the probe Sd measures a value C
greater than the value of dt1 or dP1 time has elapsed, in the second case
if the defrosting phase exceeds the maximum time dP1. At the end of CMP
the defrost the controller can enter in dripping status (present if dd> 0),
in which the compressor and the fans are turned off, and subsequently in L
the state of post-dripping (if present Fd> 0), in which the control resumes
with fans off. You can choose the display on the user terminal during
defrost, using parameter d6. F
Par. Description Def Min Max U.o.M.
d0 Type of defrost 0 0 3 -
S
0 Heater by temperature
1 Hot gas by temperature PDV
2 Heater by time
3 Hot gas by time
T V2 M B3
dt1 End defrost temperature, main 4 -50 200 °C/°F E
evaporator
dt2 End defrost temperature, auxiliary 4 -50 200 °C/°F
evaporator
dP1 Maximum defrost duration 30 1 250 min Fig. 6.i
dP2 Maximum defrost duration, auxiliary 30 1 250 min
evaporator POST
d6 Terminal display during defrost 1 0 2 - REFRIG PUMP DEF DRIP DRIP REFRIG
0 = Temperature alternated with dEF DOWN (REF) (dd) (Fd)
1 = Last temperature shown before ON
c8
defrost CMP
2 = dEF OFF
ON
PDV
OFF
ON
FAN
OFF
F0=0 F3=1
ON
RES
OFF
t
Fig. 6.j
Key
UltraCella +0300083EN - rrel. 1.7 - 07.01.2016 48
ENG
Key
CMP Compressor
Refrig Refrigeration CMP Compressor
PDV Pump down valve Refrig Refrigeration
Pump down Pump down phase FAN Evaporator fan
FAN Evaporator fan Def Defrost
Def Defrost V_def Hot gas valve
RES Resistance (defrost heater) Drip Drip
Drip Drip E Evaporator
E Evaporator Post drip Post drip
Post drip Post drip C Condenser
C Condenser B3 Defrost probe
V2 Thermostatic expansion valve V2 Thermostatic expansion valve
F Dehydrator filter L Liquid receiver
t Time F Dehydrator filter
B3 Defrost probe S Liquid indicator
L Liquid receiver t Time
S Liquid indicator
The defrost is activated, upon priority:
Note: • from keyboard, using the defrost key;
• in pump-down the fan activation is determined by F0; • from clock, setting the event and the starting mode, with maximum 8
• in defrost the fan activation is determined by F3. defrosts a day (parameters dd1...dd8);
• setting the cyclic range “dI”;
• from digital input;
• from supervisor.
2. hot gas defrost (d0 = 1, 3): operating cycle.
The operating cycle refers to default values of the parameters F2 and F3. The defrost is disabled:
• defrost by temperature: when the defrost probe detects a temperature
greater than the defrost end temperature dt1;
C V_def • defrost by time: in the absence of the defrost probe, the defrost ends
after the maximum time set by parameter dP1.
CMP
M
L
6.8.1 Maximum period of time between consecutive
defrosts
F
Par. Description Def Min Max U.o.M.
dI Maximum interval between 8 0 250 hour
S consecutive defrosts
0 = defrost not performed
OFF
F0=0 F3=1
Fig. 6.m
ON Key
V_def dI Maximum interval of time between consecutive defrosts
dd1…dd3 Scheduled defrosts
OFF
DEF Defrost
t Time
t
Note:
Fig. 6.l
• if the interval dI expires when the controller is OFF, when it is started
again a defrost is performed;
• to ensure regular defrosts, the interval between defrosts must be
greater than the maximum defrost duration, plus the dripping time
and post-dripping time;
• if setting dl=0 the defrost is performed only if activated from keyboard
or by setting the scheduled defrosts (ddi).
49 UltraCella +0300083EN - rel. 1.7 - 07.01.2016
ENG
6.8.2 Other defrost parameters
Par. Description Def Min Max U.o.M.
d3 Defrost activation delay 0 0 250 min
ON
d4 Defrost at start-up
0/1=No/Yes
0 0 1 -
CMP
d5 Defrost delay at start-up 0 0 250 min
d8 High temperature alarm delay after 1 0 250 hour OFF
defrost (and door open)
dpr Defrost priority over continuos cycle 0 0 1 - ON F0=0
0/1=No/Yes
Evap. fan
• d3 determines the time that must elapse, when the defrost is activated,
between the stopping of the compressor (electric heater defrost) or PWM mod.
the starting of the compressor (hot gas defrost), and the activation of
the defrost relays on the main and auxiliary evaporators. In the hot gas Sd
defrost, the delay d3 is useful for ensuring a sufficient amount of hot Sv-F1
gas before activation of the hot gas valve; (Sv-F1)-Frd
• d4 determines whether to activate or not the defrost at the controller
start-up. The defrost at start-up request has priority over the activation ON
of the compressor and the continuous cycle. Force a defrost at
controller start-up may be useful in special situations. F0=1
Evap. fan
Example: frequent power drops inside the plant. In case of lack of voltage
the tool resets the inner clock that calculates the period of time between PWM mod.
two defrosts, starting from zero. If, in an extreme case, the frequency of
Fig. 6.n
the power failure were greater than the defrost frequency (e.g. a power t
Key
failure every 8 hours, against a defrost every 10 hours) the controller
would never perform a defrost. In a situation of this type, it is preferable CMP Compressor
to activate defrost on start-up, above all if the defrost is controlled by PWM mod. PWM modulation
F1 Fan activation threshold
temperature (probe on the evaporator), therefore avoiding unnecessary
Frd Fan activation differential
defrosts or at least reducing the running times. In the case of systems Evap.fan Evaporator fan
with a large number of units, if selecting defrosts at start-up, after a power t Time
failure all the units will start defrosting, thus causing a voltage overload. Sv Virtual probe
This can cause power overload. To overcome this, the parameter d5 can Sd Defrost probe
be used. It adds a delay before the defrost, and this delay must obviously
be different for each unit. The fan can be stopped:
• d5 represents the time that elapses between the start of the controller • when the compressor is off (parameter F2);
and the start of the defrost at start-up; • during defrost (parameter F3).
• dd is used to force the stop of the compressor and the evaporator fan
after a defrost cycle in order to facilitate the evaporator dripping;
• d8 indicates the time of exclusion of the high temperature alarm 6.9.2 Variable speed fans
signalling from the end of a defrost; The installation of variable speed fans may be useful to optimise energy
• if dpr = 0, the defrost and the cycle have the same priority; if dpr = 1, consumption. In this case, the fans are powered by the mains, while the
if the continuous cycle is in progress and a defrost request intervenes, control signal is provided by UltraCella by analogue output Y1 0…10 Vdc.
the continuous cycle ends and the defrost starts.
The maximum and minimum fan speed can be set using F6 and F7
parameters (in percentage respect range 0…10V). If using the fan speed
controller, F5 represents the temperature below which the fans are
activated, with a fix hysteresis of 1°C.
6.9 Evaporator Fans Par. Description Def Min Max U.o.M.
F5 Evaporator fans cut-off temperature 15 -50 200 °C/°F
(hysteresis 1°C)
6.9.1 Fixed speed fans F6 Maximum fans speed 100 F7 100 %
The status of the fans depends on the compressor status. F7 Minimum fans speed 0 0 F6 %
When the compressor is:
• on: the fan can also be on (F0=0) or activated based on the evaporator
temperature, virtual probe Sv, based on the formula: To enable the algorithm, it’s necessary to select variable speed fans mode
(F0=2) and set analogue output 0…10 Vdc (HO1=2).
if Sd ≤ (Sv - F1) -Frd --> FAN = ON
if Sd ≥ (Sv - F1) --> FAN = OFF Par.Description Def Min Max U.o.M.
F0 Evaporator fans management 0 0 2 -
• off: the fan is controlled by a PWM that has duty cycle with a fixed …
period of 60 minutes. 2 = variable speed fans
HO1 Output Y1 0…10 V configuration 0 0 3 -
duty_cycle = F2 …
60 2 = variable speed fans regulated on Sd
F5
F1
6.9.3 Evaporator fans during defrost
F1-Frd
t There is the possibility to force the start of the evaporator fans during
control (parameter F2) and during defrost (parameter F3). During
F6 the dripping periods (parameter dd > 0) and post-dripping periods
FAN (parameter Fd > 0) the evaporator fans are always off. This is useful to
F7 allow the evaporator to return to normal temperature after defrosting,
0% t thus avoiding forcing hot air on evaporator. dd is used to force the stop
of the compressor and the evaporator fan after a defrost cycle in order to
Fig. 6.o facilitate evaporator dripping.
Par. Description Def Min Max U.o.M.
Evaporator Fan (analog output) F0= 2 F2 Fan activation time with CMP off 30 0 60 min
F3 Evaporator fans during defrost 1 0 1 -
0/1=on/off
Key Fd Post dripping time (fans off ) 1 0 30 min
F4 Humidity output during defrost 1 0 1 -
Sd Evaporator probe 0/1 = ON/OFF
F0 Evaporator fans management dd Dripping time after defrost (fans off ) 2 0 30 min
F1 Fan start temperature
Frd Fan activation differential
Note:
• if two evaporator probes are configured (Sd1 and Sd2), speed fans is
calculated in relation to probe which is measuring higher temperature 6.10 Condenser fans
(to limit hot air flow): With UltraCella, the condenser fans can be managed by one of the
if Sd1>Sd2 –› regulation on Sd1; auxiliary relays AUX1/AUX2 (in ON/OFF mode), or by analogue output
if Sd1<Sd2 –› regulation on Sd2. Y1 (0 to 10 V).
In case of defrost probe failure, speed fans is fixed to maximum value
defined by parameter F6. 6.10.1 Fixed speed fans
• If F0=2 and HO1=2, speed fan is calculated in according to Figure 6.o. The condenser fans are activated based on parameters FC4 and A0, after
Anyway, if speed fan is higher than 0, “FAN” relay DO3 is ON anyhow configuring the digital output AUX.
(closed):
if speed fan (Y1) > 0V –› “FAN” relay ON (DO3 closed) Par. Description Def Min Max U.o.M.
if speed fan (Y1) = 0V –› “FAN” relay OFF (DO3 open) FC4 Condenser fan deactivation 40 -50 200 °C/°F
temperature
A0 Alarm and fan differential 2.0 0.1 20 °C/°F
• If F0=0,1 (fixed speed fans by “FAN” relay DO3), analogue output is set
to 0 (Y1=0V)
• Inside modulation interval (F1-Frd < Sd < F1), speed fan is modulated Par. Description Def Min Max U.o.M.
in proportional way (e.g. Sd=F1-Frd/2 –› Y1 correspond to (F6+F7)/2 H1 AUX1 output configuration 0 0 17 -
percentage) …
6= condenser fans
H5 AUX2 output configuration 0 0 17 -
Because of mechanical inertia of motor, some EC fans cannot start with …
a low speed set by parameter F7. To overcome this, fans can be started 6 = condenser fans
with maximum speed set by parameter F7 for a “peak time” defined by
parameter F8, irrespectively of Sd temperature.
On the other hand, if fans operates for too long time at a reduced speed, Sc
ice can form on the blades. To avoid this, at interval of F10 minutes, fans FC4+A0
are forced to maximum speed for “peak time” defined by F8
FC4
t
Fig. 6.p
speed fans defined by Sd
Key
F6 Sc Condenser probe
FAN Condenser fans
FC4 Turn off temperature
F7 t Time
A0 Differential
FCn
min capacity = 0%
6.10.3 Floating condensing temperature set point
FCL
min output The control set point for variable speed condenser fans (parameter FCS)
value= 0V
may be either fixed or variable (floating condensing temperature). The
Sc
differential differential (condenser type of set point is selected using parameter FCt.
temperature)
FCd FCd
FCS Par. Description Def Min Max U.o.M.
(setpoint) FCt Variable speed condenser fans: fixed or 0 0 1 -
variable set point
Fig. 6.q 0/1=fixed FCS/floating
In this example, the minimum modulation capacity FCn is 0, therefore the
range of modulation of the 0 to 10 V output is: FCS-FCd < Sc < FCS+FCd. The purpose of the floating condensing temperature function is to
. lower the condensing temperature based on the outside temperature,
so as to preserve correct compressor operation. The floating condensing
temperature set point algorithm requires an outside temperature probe
UltraCella +0300083EN - rrel. 1.7 - 07.01.2016 52
ENG
(SA), usually located near to the condenser, so as calculate the reference 6.12 Bowl resistance
control value, as shown in the following figure:
The resistor is used to heat the collection tank after the defrosting phase,
to prevent the ice from blocking the passage of water.
floating set point The resistance is activated for 3 minutes before the programmed defrost
FSH (max) or simultaneously with a manual defrost. The resistance is always off after
the defrost phase.
Par. Description Def Min Max U.o.M.
FSO H1 Configuration of output AUX1 1 0 17 -
(offset) …
3 = bowl resistance activation
FSL (min) H5 Configuration of output AUX2 1 0 17 -
SA …
3 =bowl resistance activation
t
external temperature
Fig. 6.t 6.13 Defrosting with 2 evaporators
To activate the floating condensing temperature function, as well as You can configure up to 2 defrost probes and up to 2 evaporator outputs.
setting FCt=1, B3 (parameter /A3) or B4 (parameter /A4) needs to be The control recognizes the configuration based on the following table
configured as an outside temperature probe (SA). (probe 1 is the control probe and cannot be configured)
Par. Description Def Min Max U.o.M.
DEFROST PROBES AND EVAPORATORS OUTPUT CONFIGURATION
/A3 Probe 3 configuration 0 0 5 -
… Case Defrost Evaporator Notes
4 = out. temp. probe (SA) probes outputs
/A4 Probe 4 configuration 0 0 4 - 1 B2 Evap. 1 B2 acts on the evap. 1
… 2 B2 Evap. 1 and 2 B2 acts on the evap. 1
1 = out. temp. probe (SA) 3 B2 and B3 Evap. 1 B2 and B3 act on evap. 1 (start
and end of defrost based on the
Note: if the outside temperature probe SA is not configured, or if minimum value probe)
the probe has an error (E2 for B3, E3 for B4), the floating condensing 4 B2 and B3 Evap. 1 and 2 B2 acts on the evap. 1 and B3 act
on evap. 2
temperature algorithm will be disabled, and the control set point will be
Tab. 6.b
fixed (FCS).
The algorithm allows for the floating condensing temperature set point
to vary between a minimum (parameter FSL) and a maximum (parameter
FSH) and, based on the outside temperature (SA), an offset is added
(parameter FSO). For details on these parameters, see the datasheet for
CASE 4: 2 PROBES AND 2 EVAPORATORS
the condenser used
.
C
Par. Description Def Min Max U.o.M.
FSL Floating condensing temp. set point: 5,0 -100,0 FSH °C/°F
min value
FSH Floating condensing temp. set point: 25,0 FSL 200,0 °C/°F L CMP
max value
FSO Floating condensing temp. set point: 5,0 -50,0 50,0 °C/°F
offset F
B2
6.11 Duty setting T V1
In the event the alarm “rE” (virtual control probe fault), the parameter c4 is E1
used to ensure the operation of the compressor until the fault is resolved.
The compressor cannot be activated according to the temperature (due
to the faulty probe), it is activated cyclically with a time of operation (ON)
equal to the value assigned to c4 and a switch-off time (OFF) fixed at 15 B3
minutes . T V2
E2
ON
CMP Fig. 6.v
OFF Key
E1/2 Evaporator 1/2
t
c4 15 C Condenser
V1/2 Thermostatic expansion valve 1/2
Fig. 6.u L Liquid Receiver
B2/B3 defrost probe 2, 3
Par. Description Def Min Max U.o.M. CMP Compressor
c4 Compressor running time in duty 0 0 100 min F Filter drier
setting S Liquid indicator
Par. Description Def Min Max U.o.M. To activate an auxiliary output by time band, a time band needs to be
H1 AUX1 output configuration 1 0 17 - enabled by setting the following parameters:
…
16 = output in reverse mode for Par. Description Def Min Max U.o.M.
control with dead band don AUX activation by time band: day 0 0 11 days
H5 AUX2 output configuration 1 0 17 - 0 = disable
… 1, 2, …7 = Sunday, Monday, …
16 = output in reverse mode for Saturday
control with dead band 8 = Monday to Friday
9 = Monday to Saturday
10 = Saturday & Sunday
The figure shown below refers to heating/cooling control with dead 11 = every day
band for a compressor (direct) with one capacity step. hon AUX activation by time band: hours 0 0 23 hours
Mon AUX activation by time band: minutes 0 0 59 min
hoF AUX deactivation by time band: hours 0 0 23 hours
MoF AUX deactivation by time band: minutes 0 0 59 min
H8 Enable AUX activation by time band 0 0 1 -
0/1=disabled/enabled
Fig. 6.ad
GND
GND
VL
humiSonic
48 47 46 45 44 43 30 B3
31 CAREL NTC, PT1000
29 B2 CAREL NTC, PT1000
28 B1 CAREL NTC, PT1000
27 Y1 analog output (0 to 10 Vdc)
49 50 51 52 53 54 26 B4 CAREL NTC, analog input 0 to 10 Vdc
25 B5
GND
Rx/Tx-
Rx/Tx+
GND
Rx/Tx-
Rx/Tx+
18
24 Vac
17
UltraCella Control
16
R6
R5 - R6 15
EN60730-1 12 (10) A
250 V 14
UL 873 12 A res. 2HP R5 DEF
12FLA 72 LRA 13
12
FAN (4)
11
R3 - R4 R4
10 A res. 10 (1) RS485
EN60730-1 5 (3) A LIGHT Supervisione
250 V 9 Supervision
UL 873 10 A res. 5FLA R3
18 LRA GND Tx Rx ON/OFF
8
R2
7
R1 - R2
EN60730-1 8 (4) A N.O. 6
250 V
UL 873 8 A res. 2FLA 5
12 LRA R1
4
3
2
1
230 V
20 A max
Fig. 6.af
Humidity probe with 4 to 20 mA output -> connect the probe to input 6. If the temperature inside the cold room is less than 2°C (virtual control
B5 and set temperature Sv) -> humidifier activation (AUX1/AUX2 relay) is
• /P5=0 always disabled (with a fixed hysteresis of 1°C).
• /A5=1 7. Humidity control can be disabled during the defrost (parameter F4):
• F4=0 -> humidity control enabled based on humidity set point
StH;
• F4=1 -> humidity control not enabled: during defrost, the
6.17.2 Display humidity reading on UltraCella external humidifier will not be activated.
On models with single row display, P/Ns WB000S*, the humidity can be 8. Humidifier activation (AUX1/AUX2 relay) is always disabled in the event
displayed instead of the cold room temperature, selecting: of an alarm that immediately stops the compressor. Examples:
• Humidity probe with 0 to 10 V output -> /t1=10 (B4) • CHT alarm;
• Humidity probe with 4 to 20 mA output -> /t1 = 11 (B5) • LP alarm (after 3 times);
• IA alarm (when A6=0).
Par. Description Def Min Max U.o.M.
/t1 Variable 1 on the display 1 0 13 - Par. Description Def Min Max U.o.M.
… F4 Humidifier relay during defrost 1 0 1 -
10 = B4 0 = relay enabled in defrost (based
11 = B5 on StH)
1 = relay not enabled in defrost
On models with double row display, P/Ns WB000D*, the humidity can
be displayed on the second row as the second process selecting:
• Humidity probe with 0 to 10 V output -> /t2=10 (B4)
• Humidity probe with 4 to 20 mA output -> /t2 = 11 (B5) 6.18 Generic functions
Par. Description Def Min Max U.o.M. With UltraCella, a number of generic functions can be configured, and
/t2 Variable 2 on the display (second row) 6 0 23 - associated with configurable inputs and outputs that have not already
… been configured for other uses.
10 = B4 The following functions are available:
11 = B5 • 2 ON/OFF control functions, using outputs AUX1/AUX2
• 1 modulating control function, using 0 to 10 V output Y1
• 2 alarms, using outputs AUX1/AUX2
The generic ON/OFF or 0 to 10 V modulating control functions can be
associated with an input that also has other functions (for example Sv,
6.17.3 AUX1/AUX2auxiliaryoutputconfigurationandbasic control probe, or Su, humidity probe), or to a free input that therefore
needs to be configured specifically.
humidity control logic .
To activate the humidifier connected to UltraCella, configure one of the
auxiliary outputs AUX1 or AUX2 for humidity control. Par. Description Def Min Max U.o.M.
Par. Description Def Min Max U.o.M. /A2 Probe 2 configuration 0 0 3 -
H1 AUX1 output configuration 1 0 17 - 3 = generic temperature probe 2
… /A3 Probe 3 configuration 0 0 5 -
15 = humidity output 5 = generic temperature probe 3
H5 AUX2 output configuration 1 0 17 - /A4 Probe 4 configuration 0 0 4 -
… 3 = generic temperature probe 4
15 = humidity output 4 = generic humidity probe 4
/A5 Probe 5 configuration 0 0 5 -
2 = generic temperature probe 5
3 = generic humidity probe 5
4 = generic pressure probe 5
rc1 rM1
SM1 Fig. 6.ai
To associate the generic alarm to a digital input, DI2 or DI3, set parameter
A5 or A9.
To use outputs AUX1/AUX2 for the generic alarms, set parameters H1/H5.
Example: AUX1 active for alarm from digital input DI3 with N.C. logic,
delay 15 minutes.
Set:
• AA2 = 0 -> Alarm 2 associated with digital input DI3
• r2A = 1 -> N.C. logic
• Ad5 = 15 -> delay 15 minutes
• A9 = 15 -> DI3 for alarm from generic function
• H1 = 11 -> AUX1 for generic alarm 2
Par. Description Def Min Max UOM Type CAREL SVP Modbus R/W page
SVP
Pro
/21 Probe measurement stability probe 1 4 0 9 - I 12 51 R/W 37
/22 Probe measurement stability probe 2 4 0 9 - I 13 52 R/W 37
/23 Probe measurement stability probe 3 4 0 9 - I 14 53 R/W 37
/24 Probe measurement stability probe 4 4 0 9 - I 15 54 R/W 37
/25 Probe measurement stability probe 5 4 0 9 - I 16 55 R/W 37
/4 Virtual probe composition 0 0 100 - I 17 56 R/W 44
0 = probe B1
100= probe B2
/5t Temperature unit of measure 0 0 1 - I 18 57 R/W 38
0/1 = °C / °F
/5P Pressure unit of measure 0 0 1 - I 19 58 R/W 38
0/1 = bar/psi
/6 Display decimal point 0 0 1 - D 19 8 R/W 38
0/1 = yes/no
/t1 Display variable 1 1 0 13 - I 67 106 R/W 38
0 None 7 B1 57
1 Virtual probe (Sv) 8 B2
2 Outlet probe (Sm) 9 B3
3 Intake probe (Sr) 10 B4
4 Defrost probe 1 (Sd1) 11 B5
5 Defrost probe 2 (Sd2) 12 Condenser probe (Sc)
6 Set point 13 Variable speed condenser fans
set point
/t2 Display variable 2 (*) 6 0 23 - I 68 107 R/W 38
0 None. 12 rd 57
1 Virtual probe (Sv) 13 Superheat (EVO)
2 Outlet probe (Sm) 14 Valve opening % (EVO)
3 Intake probe (Sr) 15 Valve opening step (EVO)
4 Defrost probe 1 (Sd1) 16 Condenser probe (Sc)
5 Defrost probe 2 (Sd2) 17 U1 probe (3ph model)
6 Set point 18 U2 probe (3ph model)
7 B1 19 U3 probe (3ph model)
8 B2 20 Variable speed condenser fans
set point (Y1)
9 B3 21 Superheat (EVDice))
10 B4 22 Valve opening % (EVDice)
11 B5 23 Step valve opening (EVDice)
(*) can be viewed only on UltraCella Sevice Terminal or on the controller
with double row display
/P Type B1 to B3 0 0 2 - I 20 59 R/W 34
0 NTC Standard range -50T90°C
1 NTC extended range 0T150°C
2 PT1000
/A2 B2 configuration 1 0 3 - I 21 60 R/W 34
0 Absent
1 Defrost probe 1 (Sd1)
2 Intake probe (Sr)
3 Generic function on probe 2
/A3 B3 configuration 0 0 5 - I 22 61 R/W 34
0 Absent
1 Defrost probe 2 (Sd2)
2 Condenser probe (Sc)
3 Defrost probe 1 (Sd1)
4 Ambient temperature probe (SA)
5 Generic function on probe 3
/P4 B4 type 0 0 2 - I 23 62 R/W 34
0 NTC Standard range -50T90°C 57
1 NTC Extended range 0T150°C
2 0 to 10 V
/A4 B4 configuration 0 0 4 - I 24 63 R/W 34
0 Absent 57
1 Ambient temperature probe (SA)
2 Humidity probe
3 Probe 4 generic temperature
4 Probe 4 generic humidity
/P5 B5 type 0 0 1 - I 25 64 R/W 34
0 4 to 20 mA 57
1 0 to 5 Vrat
/A5 B5 configuration 0 0 5 - I 26 65 R/W 34
0 Absent 57
1 Humidity probe
2 Probe 5 generic temperature
3 Probe 5 generic humidity
4 Probe 5 generic pressure
5 Scp (Condensing pressure probe)
CtL
St Set point 0 r1 r2 °C/°F A 12 5 R/W 44
rd Differential 2.0 0.1 20 °C/°F A 13 6 R/W 44
r1 Minimum set point -50.0 -50.0 r2 °C/°F A 14 7 R/W 44
r2 Maximum set point 60.0 r1 200 °C/°F A 15 8 R/W 44
r3 Operating mode 0 0 1 - D 11 0 R/W 44
0 direct with defrost
1 direct without defrost
rn Dead band 3,0 -20,0 20,0 °C/°F A 80 190 R/W 55
rr Differential for control with dead band 2,0 0,1 20 °C/°F A 81 191 R/W 55
r4 Offset set point 60.0 r1 200 °C/°F A 82 192 R/W 45
StH Humidity set point 90.0 0.0 100.0 %rH A 28 19 R/W 58
rdH Humidity differential 5.0 0.1 20.0 %rH A 29 20 R/W 58
PS1 Ramps: final set point, phase 1 0 -50.0 200.0 °C/°F A 77 187 R/W 45
PS2 Ramps: final set point, phase 2 0 -50.0 200.0 °C/°F A 78 188 R/W 45
PS3 Ramps: final set point, phase 3 -30.0 -50.0 -200.0 - A 79 189 R/W 45
PH1 Ramps: duration of phase 1 6 0 10 days A 102 212 R/W 45
PH2 Ramps: duration of phase 2 2 0 10 days A 103 213 R/W 45
PH3 Ramps: duration of phase 3 10 0 10 days A 104 214 R/W 45
Pdt Ramps: maximum set point variation after blackout 20.0 10.0 30.0 °C/°F A 106 216 R/W 46
Pon Enable set point ramps 0 0 1 - D 159 48 R/W 46
0/1 = ramps disabled/enabled
CMP
c0 Compressors/fan start delay at power on 0 0 15 min I 31 70 R/W 43
c1 Minimum time between compressor starts 6 0 30 min I 32 71 R/W 37
c2 Minimum compressor off time 3 0 15 min I 33 72 R/W 37
c3 Minimum compressor on time 3 0 15 min I 34 73 R/W 37
c4 Compressor running time in duty setting 0 0 100 min I 35 74 R/W 53
cc Continuous cycle duration 0 0 15 hours I 36 75 R/W 47
c6 Low temperature alarm delay after continuous cycle 2 0 250 hours I 37 76 R/W 47
c7 Maximum pump down (PD) time 0 0 900 s I 38 77 R/W 46
0 = Pump down disabled
c8 Compressor start delay after opening of pump down valve 5 0 60 s I 39 78 R/W 46
c9 Autostart in pump down 0 0 1 - D 13 2 R/W 47
0/1 = whenever pump down valve closes/ whenever pump down valve
closes & every request of low pressure switch without regulation request
c10 Pump down by time/pressure 0 0 1 - D 12 1 R/W 47
0/1 = pressure/ time
c11 Second compressor start delay 4 0 250 s I 40 79 R/W 43
FC4 Condenser fan deactivation temperature 40.0 -50.0 200.0 °C/°F A 16 9 R/W 52
FCH Variable speed condenser fans: max. output value 100 FCL 100 % A 131 241 R/W 52
FCL Variable speed condenser fans: min. output value 0 0 FCH % A 132 242 R/W 52
FCn Variable speed condenser fans: min. capacity % 0 0 FCH % A 133 243 R/W 52
FCS Variable speed condenser fans: set point 15.0 -100.0 200.0 °C/°F A 134 244 R/W 52
FCd Variable speed condenser fans: differential 2.0 0.1 10.0 °C/°F A 135 245 R/W 52
FCt Variable speed condenser fans: fixed or floating set point 0 0 1 - D 167 56 R/W 53
0/1= FCS fixed/floating
FSH Floating condensing temp. set point: max value 25.0 FSL 200.0 °C/°F A 136 246 R/W 53
FSL Floating condensing temp. set point: min value 5.0 -100.0 FSH °C/°F A 137 247 R/W 53
FSO Floating condensing temp. set point: offset 5.0 -50.0 50.0 °C/°F A 138 248 R/W 53
dEF
d0 Type of defrost 0 0 3 - I 41 80 R/W 36
0 Heater by temperature 48
1 Hot gas by temperature
2 Heater by time
3 Hot gas by time
dI Max interval between consecutive defrosts 8 0 250 hours I 42 81 R/W 49
0 = defrost not performed
dt1 End defrost temperature, main evaporator 4.0 -50.0 200.0 °C/°F A 17 10 R/W 36
48
dt2 End defrost temperature, auxiliary evaporator 4.0 -50.0 200.0 °C/°F A 18 11 R/W 48
dP1 Maximum defrost duration 30 1 250 min I 43 82 R/W 36
48
dP2 Maximum defrost duration, auxiliary evaporator 30 1 250 min I 44 83 R/W 45
dd Dripping time after defrost 2 0 30 min I 45 84 R/W 36
d3 Defrost activation delay 0 0 250 min I 46 85 R/W 50
ALM
A0 Alarm and fan differential 2.0 0.1 20.0 °C/°F A 19 12 R/W 52
73
A1 Alarm thresholds (AL, AH) relative to set point or absolute 0 0 1 - D 16 5 R/W 73
0/1=relative/absolute
AL Low temperature alarm threshold 0.0 -50.0 200.0 °C/°F A 20 13 R/W 73
If A1=0, AL=0: alarm disabled
If A1=1, AL=-50: alarm disabled
AH High temperature alarm threshold 0.0 -50.0 200.0 °C/°F A 21 14 R/W 73
If A1=0, AH=0: alarm disabled
If A1=1, AH=200: alarm disabled
Ad High/low temperature alarm delay 120 0 250 min I 50 89 R/W 73
A5 Digital input 2 (DI2) configuration 0 0 15 - I 51 90 R/W
0 Not active 8 Low pressure switch 35
1 Immediate external alarm 9 Do not select 45
2 Do not select 10 Do not select 47
3 Enable defrost 11 Do not select 58
4 Start defrost 12 AUX1 activation 60
5 Do not select 13 Do not select
6 Remote ON/OFF 14 Continuous cycle activation
7 Do not select 15 Alarm from generic funcion
A6 Stop compressor on external alarm 0 0 100 min I 53 92 R/W 73
A7 Low pressure (LP) alarm delay 1 0 250 min I 54 93 R/W 36
A8 Enable Ed1 and Ed2 alarms 0 0 1 - D 168 57 R/W 48
0/1= disabled/enabled alarms
A9 Digital input 3 (DI3) configuration 0 0 15 - I 52 91 R/W 35
0 Not active 8 Low pressure switch 45
1 Immediate external alarm 9 Do not select 47
2 Do not select 10 Do not select 58
3 Enable defrost 11 Do not select 60
4 Start defrost 12 AUX2 activation
5 Do not select 13 Do not select
6 Remote ON/OFF 14 Continuous cycle activation
7 Change set point 15 Alarm from generic funcion
A10 Low pressure alarm delay (LP), compressor running 3 0 60 min I 55 94 R/W
Ac High temperature condenser alarm threshold 70.0 -50.0 200.0 °C/°F A 22 15 R/W 74
Acd High temperature condenser alarm delay 0 0 250 min I 56 95 R/W 74
ULL Absolute low umidity alarm threshold 0 0 100.0 %rH A 84 194 R/W 73
0= alarm disabled
UHL Absolute high umidity alarm threshold 100.0 0 100.0 %rH A 83 193 R/W 73
100= alarm disabled
AdH Humidity alarms AUH, AUL delay 120 0 250 min A 117 227 R/W 73
Fan
F0 Evaporator fan management 0 0 2 - I 174 265 R/W 50
0 always on with compressor on 51
1 activation depends on Sd, Sv
2 variable speed fans
F1 Fan activation temperature 5.0 -50.0 200.0 °C/°F A 23 16 R/W 50
Frd Fan activation differential 2.0 0.1 20.0 °C/°F A 24 17 R/W 50
F2 Fan activation time with compressor off 30 0 60 min I 57 96 R/W 50
51
F3 Evaporator fan during defrost 1 0 1 - D 17 6 R/W 36
0/1= ON/OFF
Fd Post dripping time 1 0 30 min I 60 99 R/W 36
F4 Humidity output during defrost 1 0 1 - D 71 28 R/W 51
0/1 = ON/OFF 58
F5 Evaporator fans cut-off temperature (hysteresis 1°C) 15 -50 200 °C/°F A 25 18 R/W 51
F6 Maximum fan speed 100 F7 100 % I 58 97 R/W 51
F7 Minimum fan speed 0 0 F6 % I 59 98 R/W 51
F8 Fans peak time 0 0 240 s I 176 175 R/W 51
0 = disabled function
F10 Evaporator fans forcing time at maximum speed 0 0 240 min I 177 176 R/W 51
0 = disabled function
CnF
H0 Serial address 193 0 247 - I 69 108 R 38
In Type of unit 0 0 0 - - - - R
HcP
HCE Enable HACCP 0 0 1 - D 22 11 R/W 74
0/1 = No/Yes
Htd HACCP alarm delay 0 0 250 min I 71 110 R/W 74
rtC
tcE Enable data modification 0 0 1 - D 24 13 R/W 23
tcT Date/ time change 0 0 1 - D 25 14 R/W 23
Action on variation 01 o 10
y__ Date/ time: year 0 0 37 - I 98 111 R/W 23
UltraCella +0300083EN - rrel. 1.7 - 07.01.2016 64
ENG
Par. Description Def Min Max UOM Type CAREL SVP Modbus R/W page
SVP
M__ Date/ time: month 1 1 12 - I 99 112 R/W 23
d__ Date/ time : day of month 1 1 31 - I 100 113 R/W 23
h__ Date/ time: hour 0 0 23 - I 101 114 R/W 23
n__ Date/ time: minute 0 0 59 - I 102 115 R/W 23
tcL Hours/minutes visualization on the second row for models with two rows 0 0 1 - D 72 29 R/W 66
display 0/1=no/yes
ddi Defrost i (i=1…8): day 0 0 11 days I 103…110 116...123 R/W 48
hhi Defrost i (i=1…8): hour 0 0 23 hours I 111…118 124...131 R/W 48
nni Defrost i (i=1…8): minute 0 0 59 min I 119…126 132...139 R/W 48
don AUX activation by time band: day 0 0 11 days A 105 215 R/W 56
hon AUX activation by time band: hours 0 0 23 hours A 107 217 R/W 56
Mon AUX activation by time band: minutes 0 0 59 min A 109 219 R/W 56
hoF AUX deactivation by time band: hours 0 0 23 hours A 108 218 R/W 56
MoF AUX deactivation by time band: minutes 0 0 59 min A 110 220 R/W 56
H8 Enable AUX activation by time band 0 0 1 - D 160 49 R/W 56
0/1=disabled/enabled
dSn Set point variation by time band: day 0 0 11 days A 111 221 R/W 45
hSn Start set point variation by time band: hours 0 0 23 hours A 113 223 R/W 45
MSn Start set point variation by time band: minutes 0 0 59 min A 115 225 R/W 45
hSF End set point variation by time band: hours 0 0 23 hours A 114 224 R/W 45
MSF End set point variation by time band: minutes 0 0 59 min A 116 226 R/W 45
H9 Enable set point variation by time band 0 0 1 - D 161 50 R/W 45
0/1=disabled/enabled
doL
c12 Compressor safety time for door switch 5 0 5 min I 64 103 R/W 36
0 = disable door management
d8d Compressor restart time for door switch 30 c12 240 min I 65 104 R/W 36
A3 Disable door microswitch 1 0 1 - D 138 45 R/W 35
0 = door microswitch enabled
1 = door microswitch disabled
tLi Light on with door open 120 0 240 min I 66 105 R/W 37
A4 Light management 0 0 1 - D 18 7 R/W 37
0 = door switch + light key - 1 = light key
rcP (see chapter 3 the procedure for setting parameters to default values)
GEF
AS1 ON/OFF control 1: control variable configuration 3 0 14 - A 119 229 R/W 58
0 Sm 8 probe 2 generic temperature
1 Sd1 9 probe 3 generic temperature
2 Sr 10 probe 4 generic temperature
3 Sv 11 probe 5 generic temperature
4 Sd2 12 probe 4 generic humidity
5 Sc 13 probe 5 generic humidity
6 SA 14 probe 5 generic pressure
7 Su
r1S ON/OFF control 1: mode 0 0 1 - D 162 51 R/W 58
0/1=direct/reverse
SS1 ON/OFF control 1: set point 0.0 -50.0 200.0 °C/°F/ A 85 195 R/W 58
0.0 100.0 rH%/
-200.0 999 bar/psi
rS1 ON/OFF control 1: differential 2.0 0.1 20.0 °C/°F/ A 87 197 R/W 58
rH%/
bar/psi
AL1 ON/OFF control 1: absolute low alarm threshold 0.0 -50.0 200.0 °C/°F/ A 89 199 R/W 59
0.0 100.0 rH%/
-200.0 999 bar/psi
AH1 ON/OFF control 1: absolute high alarm threshold 0.0 -50.0 200.0 °C/°F/ A 91 201 R/W 59
0.0 100.0 rH%/
-200.0 999 bar/psi
Ad1 ON/OFF control 1: alarm delay 0 0 250 min A 121 231 R/W 59
AS2 ON/OFF control 2: control variable configuration 3 0 14 - A 120 230 R/W 58
0 Sm 8 probe 2 generic temperature
1 Sd1 9 probe 3 generic temperature
2 Sr 10 probe 4 generic temperature
3 Sv 11 probe 5 generic temperature
4 Sd2 12 probe 4 generic humidity
5 Sc 13 probe 5 generic humidity
6 SA 14 probe 5 generic pressure
7 Su
r2S ON/OFF control 2: mode 0 0 1 - D 163 52 R/W 58
0/1=direct/reverse
SS2 ON/OFF control 2: set point 0.0 -50.0 200.0 °C/°F/ A 86 196 R/W 58
0.0 100.0 rH%/
-200.0 999 bar/psi
rS2 ON/OFF control 2: differential 2.0 0.1 20.0 °C/°F/ A 88 198 R/W 58
rH%/
bar/psi
AL2 ON/OFF control 2: absolute low alarm threshold 0.0 -50.0 200.0 °C/°F/ A 90 200 R/W 59
0.0 100.0 rH%/
-200.0 999 bar/psi
EVO
P1 Enable communication with EVD EVO module 0 0 1 - D 70 27 R/W 39
0/1=no/yes
P1t S1 probe type 0 0 3 - I 139 150 R/W 39
0 RAZ. 0 to 5 V 2 4 to 20 mA remote
1 4 to 20 mA 3 4 to 20 mA external
P1M Max value of S1 probe 12.8 -20 200 °C/°F A 31 22 R/W 39
P1n Min value of S1 probe -1 -20 200 °C/°F A 30 21 R/W 39
PVt Valve type 1 1 22 - I 136 147 R/W 39
1 CAREL EXV 12 Sporlan seh 100
2 Alco ex4 13 Sporlan seh 175
3 Alco ex5 14 Danfoss ets 12.5 - 25b
4 Alco ex6 15 Danfoss ets 50b
5 Alco ex7 16 Danfoss ets 100b
6 Alco ex8 330hz CAREL recommended 17 Danfoss ets 250
7 Alco ex8 500hz Alco specification 18 Danfoss ets 400
8 Sporlan sei 0.5-11 19 2 CAREL EXV connected
together
9 Sporlan ser 1.5-20 20 Sporlan ser(i) g, j, k
10 Sporlan sei 30 21 Danfoss ccm 10-20-30
11 Sporlan sei 50 22 Danfoss ccm 40
ICE
IPE Enable EVDice communication 0 0 1 - D 183 59 R/W 39
0/1 = not enabled/ enabled
IrE 1= Multiplexed cabinet/cold room 1 1 6 - I 196 185 R/W 40
2= Air-conditioner/chiller with plate heat exchanger (2, 3, 4, 5
& 6 mode
3= Air-conditioner/chiller with tube bundle heat exchanger select.
4= Air-conditioner/chiller with finned coil heat exchanger only from
UltraCella
5= Reserved service
6= Reserved pGD)
IP3 Superheat set point 11 IC1 99 K A 150 255 R/W 40
PH 1 R22 6 R507A 11 R744 16 R413A 21 R245Fa 3 1 23 - I 135 146 R/W 40
2 R134a 7 R290 12 R728 17 R422A 22 R407F
3 R404A 8 R600 13 R1270 18 R423A 23 R32
4 R407C 9 R600a 14 R417A 19 R407A
5 R410A 10 R717 15 R422D 20 R427A
IS1 S1 probe type 3 1 11 - I 1 249 R/W 40
1 1 to 4.2 barg 7 0 to 45 barg
2 0.4 to 9.3 barg 8 1 to 12.8 barg
3 -1 to 9.3 barg 9 0 to 20.7 barg
4 0 to 17.3 barg 10 1.86 to 43.0 barg
5 0.85 to 34.2 barg 11 reserved
6 0 to 34.5 barg
ICP PID: proportional gain 15 0 800 - A 151 256 R/W 40
Iti PID: integral time 150 0 999 sec I 171 252 R/W 40
IC1 LowSH protection: threshold 5 -9 IP3 °C/°F A 152 257 R/W 40
IC2 LowSH protection: integral time 15 0 800 sec A 153 258 R/W 40
IC3 LOP protection: threshold -50 -121 IC5 °C/°F A 154 259 R/W 40
IC4 LOP protection: integral time 0 0 800 sec A 155 260 R/W 40
IC5 MOP protection: threshold 50 IC3 392 °C/°F A 156 261 R/W 40
IC6 MOP protection: integral time 20 0 800 sec A 157 262 R/W 40
IC7 MOP protection: disable threshold 30 -121 392 °C/°F A 158 263 R/W 40
IC8 Low suction temperature alarm threshold -50 -121 392 °C/°F A 159 264 R/W 40
IIA Enable operating mode modification 0 0 1 - I 2 250 R/W 40
0/1 = enabled/not enabled
IU1 Enable manual valve positioning 0 0 1 - D 182 58 R/W 40
0/1 = enabled/not enabled
IU2 Manual valve position 0 0 999 step I 128 141 R/W 40
IU3 Valve control steps: 1/2 = 480/960 step 1 1 2 - I 195 184 R/W 40
IU4 Valve opening at start (evaporator/valve capacity ratio) 50 0 100 % I 173 254 R/W 40
In1 Serial address 99 1 99 - I 133 144 R/W 40
ICG Enable EVDice regulation 0 0 1 - I 184 60 R/W 39
0/1 = not enabled/ enabled 40
On Switch ON
OFF Switch OFF
AUX Auxiliary output switch on request
rEc Temperature registration
no Operation not executed
uPd Parameters upload
dnL Parameters download 1 2 1 2 1 2
Button flashing
Icon flashing
Alarm code
description
Alarm relay
on display
on display
on display
1 2 1 2
Buzzer
Alarm
Reset
Note: the figures refer to the screens on models with single row
display, P/Ns WB000S*. In models with two rows, P/Ns WB000D*,
the display shows the alarm messages on the second row SHA Low superheat protection - ON ON Automatic
LOA LOP protection - ON ON Automatic
Example: HA alarm triggered Thursday at 13:17, with detected 8.6 EVDice alarms
temperature of 36.8 °C.
If an EVDice driver is connected via Fieldbus, UltraCella will be able to
signal the following alarms, which depend solely on the status of the
driver.
Button flashing
Icon flashing
Alarm code
description
Alarm relay
on display
on display
on display
Buzzer
Alarm
Reset
1 2 1 2
Icon flashing on
Button flashing
Alarm code on
Alarm cause
Alarm relay
on display
display
display
Buzzer
Reset
EPE 3PH Module off -line - ON ON Automatic
Sd1 probe fault (3PH
EP0 - ON ON Automatic
module)
Sd2 probe fault (3PH
EP1 - ON ON Automatic
module)
Sc probe fault (3PH
EP2 - ON ON Automatic
module)
3PH module
EPn - ON ON Automatic
configuration fault
Motor protector alarm
EPM - ON ON Manual
(3PH module)
High/low pressure
EPU or Kriwan alarm (3PH - ON ON Manual
module)
Tab. 8.d
ALARM TABLE
Continuous cycle
display flashing
Condenser fans
Cod. display
Alarm cause
Compressor
Icon on the
Display key
Alarm relay
Evaporator
PD valve
flashing
Defrost
Buzzer
Reset
Fans
rE Virtual control probe fault ON ON automatic duty setting(c4) duty setting(c4) - - - OFF
E0 Probe B1 fault ON ON automatic duty setting(c4) duty setting(c4) - - - OFF
E1 Probe B2 fault ON ON automatic - - - - - OFF
E2 Probe B3 fault ON ON automatic - - - - - -
E3 Probe B4 fault ON ON automatic - - - - - -
E4 Probe B5 fault ON ON automatic
LO Low temperature alarm - ON ON automatic - - - - - -
HI High temperature alarm - ON ON automatic - - - - - -
IA Immediate alarm from external contact - ON ON automatic duty setting (A6) duty setting(A6) OFF - - OFF
Pd Maximum pump down time alarm - ON ON automatic - - - - - -
LP Low pressure alarm - ON ON automatic OFF OFF OFF - - -
AtS Autostart in pump down - ON ON autom./man - - - - - -
CHt High condenser temperature alarm - ON ON manual OFF OFF - - OFF -
dor Door open too long alarm - ON ON automatic - - - - - -
Etc Real time clock is broken ON ON automatic - - - - - -
EE EEprom error, unit parameters ON ON automatic - - - - - -
EF Eeprom error, operating parameters ON ON automatic - - - - - -
Ed1, ON ON automatic
Defrost ended by timeout -
Ed2
HA HACCP alarm, HA type - ON ON manual - - - - - -
HF ON ON manual - - - - - -
HACCP alarm, HF type - +
ALARM
OFF
A0 A0 Sv
AL AH
Fig. 8.a
73 UltraCella +0300083EN - rel. 1.7 - 07.01.2016
ENG
8.9 HACCP Alarm parameters and
monitoring activation AH
t
ON
ALARM
OFF
t
8.10 High condenser temperature alarm
Ad Htc
You can monitor the temperature of the condenser to signal the high
Fig. 8.b temperature, probably due to situations of clogging. The signalling
Key follows the figure below.
Sv Virtual probe Par Description Def Min Max UM
St Set point Ac High condenser temperature alarm 70 -50,0 200 °C/°F
t Time threshold
AH High temperature alarm threshold Acd High condenser temperature alarm 0 0 250 min
ALARM HACCP alarm, HA type delay
Ad Delay time for low temperature and high temperature alarms
Htd HACCP alarm delay (0=monitoring disabled)
Ac+10
Sc
Ac
HF alarms
The HACCP alarm type HF is generated as a result of a power failure for a
long time (> 1 minute), when after mains voltage restore the temperature
t
read by the adjustment probe exceeds the high temperature threshold ON
AH . CHT
OFF
t
Acd
Fig. 8.d
Key
t Time
Acd High condenser temperature alarm delay
Sc Condenser probe
Ac High condenser temperature alarm threshold
CHT High condenser temperature alarm
Ultra 3PH Evaporator module 6kW Ultra 3PH Evaporator module 9kW
Code WT00E60N00 WT00E90N00
General
Main switch / general protection 4 poles magnetothermic 16A 6kA D 4 poles magnetothermic 25A 6KA D
Loads power supply 400V~(±10%), 50/60Hz, 3PH+N+T 400V~(±10%), 50/60Hz, 3PH+N+T
Insulating transformer PRI 230 Vac PRI 230 Vac
SEC1 230 Vac 40VA SEC1 230 Vac 40VA
SEC2 24 Vac 35VA SEC2 24 Vac 35VA
Protection SEC by fuses Protection SEC by fuses
Status and alarm indication By UltraCella By UltraCella
Input
Main defrost probe NTC 10kΩ NTC 10kΩ
Auxiliary evap. defrost probe NTC 10kΩ NTC 10kΩ
Clicson evaporator Present Present
Thermostat evaporator Present Present
Output
Condensing unit enabling / Solenoid valve 8A (AC1) / 2A (AC23) 1PH 8A (AC1) / 2A (AC23) 1PH
Defrost heaters 6kW, 9A (AC1) 3PH 9kW, 13A (AC1) 3PH
Evaporator fans 0,55kW, 1,5A* (AC23) 3PH 2kW, 5,7A* (AC23) 3PH
0…10Vdc 0…10Vdc
AUX1 output 16A (AC1) 1PH 16A (AC1) 1PH
Tab. 9.e
* Rating with cosφ=0,5;
With different power factor, to calculate the rating consider the formula: I = P / (400 * √3 * cosφ) where P is the power in W
Ultra 3PH Full module 4HP Ultra 3PH Full module 7.5HP
Code WT00F4B0N0 WT00F7C0N0
General
Main switch / general protection 4 poles magnetothermic 16A 6kA D 4 poles magnetothermic 25A 6KA D
Loads power supply 400V~ (±10%), 50/60Hz, 3PH+N+T 400V~ (±10%), 50/60Hz, 3PH+N+T
Insulating transformer PRI 230 Vac PRI 230 Vac
SEC1 230 Vac 40VA SEC1 230 Vac 40VA
SEC2 24 Vac 35VA SEC2 24 Vac 35VA
Protection SEC by fuses Protection SEC by fuses
Status and alarm indication By UltraCella By UltraCella
Regulation range of compressor current rating 10…16A (AC3) 3PH 16…20A (AC3) 3PH
Input
Main defrost probe NTC 10kΩ NTC 10kΩ
Auxiliary evap. defrost probe NTC 10kΩ NTC 10kΩ
Condensing probe NTC 10kΩ NTC 10kΩ
Partial condenser Present Present
Pump down Present Present
High/Low pressure Present Present
Kriwan compressor Present Present
Clicson evaporator Present Present
Thermostat evaporator Present Present
Output
Compressor 10...16A (AC3) 3PH 16...20A (AC3) 3PH
Oil compressor heater (Carter) 100W, 0,5A (AC1) 1PH 100W, 0,5A (AC1) 1PH
Condensing fans 0,8kW, 4A (AC15) 1PH 0,8kW, 4A (AC15) 1PH
Defrost heaters 6kW, 9A (AC1) 3PH 9kW, 13A (AC1) 3PH
Evaporator fans 0,55kW, 1,5A* (AC23) 3PH 2kW, 5,7A* (AC23) 3PH
0…10Vdc 0…10Vdc
AUX1 output 16A (AC1) 1PH 16A (AC1) 1PH
Solenoid valve Present Present
Tab. 9.g
* Rating with cosφ=0,5;
With different power factor, to calculate the rating consider the formula: I = P / (400 * √3 * cosφ) where P is the power in W
1 2 1
4/A1
L2
I d
3 4
L3
I d
5 6
10. ELECTRICAL WIRING 3PH MODULES
4
N 4/B1
I d
7 8
QF1
PER UNA CORRETTA INSTALLAZIONE
ELETTRICA SI RACCOMANDA
XP1
DI INSTALLARE A MONTE
DEL SEZIONATORE PRESENTE
PE
Fig. 10.a
OF THIS PANEL
78
10.1 Electrical wiring 3PH EVAPORATOR Module
5
KM1 KM2
5/D4 5/D3
6
2
2
4
4
BROWN
BROWN
WHITE
WHITE
CYAN
CYAN
GRAY
GRAY
6
2
8
4
MACHINE LIMIT
W
U
V
10.1.1 Power circuit
MV1 M RR1
EVAPORATOR FANS DEFROST HEATERS
ENG
ENG
10.1.2 Power circuit
3/A8
3/B8
MACHINE LIMIT
1
WHITE
CYAN
QF2
2 1
N2 N1
WHITE
CYAN
TC1
16
PE
14
13
5/E1
5/D1
XA1
PE1
7/C1
7/C1
Fig. 10.b
80
12
14
12
14
KR3 KR2
5/D5 5/D7
ORANGE 11
ORANGE 11
ORANGE
ORANGE
A1
A1
A1
A1
XA1 XA1 XA1 XA1
KM2 KM1 KR3 KR2
110
149
109
148
A2
A2
A2
A2
16
2
RED
4/D8
15 RED AUX2 AUX1
4/E8
CONSENT MAX 16A AC1
UNIT
119
117
118
129
120
128
MACHINE LIMIT
10.1.3 Auxiliary circuit
TS1 SP3
P
N
L
AP3
SECURITY THERMOSTAT EVAPORATOR CLICSON ULTRACELLA
ENG
ENG
81
RED
RED
RED
RED
Fig. 10.d
XA1 XA1 XA1 XA1 XA1 XA1
141
146
140
142
143
147
10.1.4 Auxiliary circuit
MACHINE LIMIT
ST1 ST2
GND
TS2
DEFROST DEFROST AUX FANS EVAPORATORE 0-10VDC
Ultra 3PH I/O module
AP1
J1 J6 J9
J1/G J1/G0 J1/VBAT J6/- J6/+ J6/GND J9/+5VREF J9/GND J11/+VDC
RED
RED
4/D8
82
13
4/D8 BELDEN
161
160
162
MACHINE LIMIT
10.1.5 Auxiliary circuit
+
-
GND
AP
485 ULTRACELLA
ENG
ENG
10.1.6 Connectionforoperationwithpowertosolenoidvalve
If the solenoid valve requires power, the 230 Vac power supply available at
terminals 128-129 can be used, as shown in the following wiring diagram:
128
129
148
149
N
L
liquid valve
XA1
ENG
5 5
Evaporator fans MV1:U 1 KM1:2
6 6
Terminals
M
Evaporator fans MV1:V 2 KM1:4
7 7
Evaporator fans MV1:W 3 KM1:6
4
8
7
6
5
3
2
1
4 QF1:8/QF2:N1
PE
PE3
PE2
PE1
162
161
160
149
148
147
146
143
142
141
140
129
128
120
119
118
117
110
109
8 8
Defrost heaters RR1 5 KM2:2
9 9
Defrost heaters RR1 6 KM2:4
10 10
Defrost heaters RR1 7 KM2:6
4 4
RS485 -
RS485 +
Defrost heaters RR1 8 QF1:8
10.1.7 Terminal units
AUX1 relay
RS485 GND
PE
Defrost heaters
Evaporator fans
Ground terminal
Ground terminals
Number and description
-
-
-
-
-
-
-
-
-
-
Safe thermostat TS1 117 ??:J10/NO1
20 20
Safe thermostat TS1 118 KM2:A1
84
Notes
19 19
Evaporator fans clicson SP3 119 ??:J10/NO2
22 22
UltraCella
UltraCella
Evaporator fans clicson SP3 120 KM1:A1
16 16
UltraCella AP3:L 128 FU2:2/??:J12/NC6
15 15
UltraCella AP3:N 129 KR1:A2/KR2:A2
28 28
defrost ST1 140 ??:J2/U1
To supply UltraCella
29 29
defrost ST1 141 XA1:143
30 30
defrost aux ST2 142 ??:J2/U2
29 29
defrost aux ST2 143 XA1:141/??:J2/GND
31 31
Evaporator fans 0...10Vdc Y TS2:Y 146 ??:J2/U6
29 29
Evaporator fans 0...10Vdc GND TS2:GND 147 ??:J2/GND
Normally closed. If active (open), evaporator fans are off and it’s not notified in
Normally closed. If active (open), evaporator fans are off and it’s not notified in
terminal block
Tab. 10.a
ENG
1 2 1
4/A1
L2 GRIGIO
I d
3 4
L3 BROWN
I d
5 6
N CYAN 4
4/B1
I d
7 8
QF1
PER UNA CORRETTA INSTALLAZIONE
ELETTRICA SI RACCOMANDA
XP1
DI INSTALLARE A MONTE
1
5
DEL SEZIONATORE PRESENTE
PE
QM1
SUL QUADRO, UNA PROTEZIONE
MAGNETOTERMICA DIFFERENZIALE
I > I > I >
FOR THE RIGHT INSTALLATION
6
2
4
IS RECOMMENDED A DIFFERENTIAL
85
BREAKER SWITCH MOUNTED
BROWN
WHITE
UPSTREAM THE GENERAL ISOLATOR
GRAY
OF THIS PANEL
5
KM3 KM1 KM2
5/D5 5/D4 5/D3
10.2 Electrical wiring 3PH FULL Module
6
2
2
4
4
BROWN
BROWN
BROWN
WHITE
WHITE
WHITE
CYAN
CYAN
GRAY
GRAY
GRAY
Fig. 10.g
XP1 XP1 XP1
1
11
9
6
2
8
10
4
MACHINE LIMIT
10.2.1 Power circuit
W
U
V
W
U
V
MV1 M RR1
MV2 M
COMPRESSOR EVAPORATOR FANS DEFROST HEATERS
1 WHITE
3/A8
4 CYAN
3/B8
N1
1
QF2
230
0(I)
TC1
40VA 35VA
CYAN
WHITE
PE
2
N2
FU1
FU2
FU3
FU4
XA1
PE1
PE2
PE3
230(O1)
24(O2)
0(O1)
0(O2)
86
13
61
KM3 KM3
RED
RED
RED
RED
5/D5 5/D5
23
14
62
7/C1
22
7/C1
25
5/D1
24
5/E1
XA1 XA1 XA1 XA1 XA1
101
106
102
103
105
107
108
104
MACHINE LIMIT
(Carter)
CONDENSER FANS 1 CONDENSER FANS 2
PARTIALIZATION PRESSURE SWITCH CONDENSER FAN
800W MAX
ENG
ENG
87
12
14
KR2
5/D7
11
ORANGE
ORANGE
A1
A1
A1
A1
A1
XA1 XA1
KR1 KM2 KM1 KM3 KR2
110
109
A2
A2
A2
A2
A2
25 RED
2
4/D8
24 RED AUX1
4/E8
MAX 16A AC1
Fig. 10.i
XA1 XA1 XA1 XA1 XA1 XA1 XA1 XA1 XA1 XA1 XA1 XA1 XA1 XA1
10.2.3 Auxiliary circuit
111
121
116
119
112
113
115
117
118
114
126
129
120
122
123
125
127
128
124
MACHINE LIMIT
YV1
N
11
12
14
L
SP2 TS1 SP3
P P
N
L
AP2 VEDI PG.9
AP3
TK1
LIQUID VALVE ULTRACELLA
KRIWAN PRESSURE SWITCH SECURITY THERMOSTAT EVAPORATOR CLICSON PUMP DOWN
Ultra 3PH I/O module
J2
J2/U1 J2/U2 J2/U3 J2/GND J2/U4 J2/U5 J2/U6 J2/GND J2/U7 J2/U8 J2/U9 J2/U10 J2/GND
RED
RED
13
12
14
QM1 KR1
3/B4 5/D2
11
14
88
RED
RED
RED
RED
RED
RED
RED
146
140
142
143
145
147
144
MACHINE LIMIT
10.2.4 Auxiliary circuit
GND
TS2
DEFROST PROBE DEFROST AUX PROBE CONDENSER PROBE EVAPORATOR FANS 0...10VDC
ENG
ENG
RED
23
4/D8
22
4/D8 BELDEN
89
Fig. 10.k
XA1
161
160
162
MACHINE LIMIT
10.2.5 Auxiliary circuit
+
-
GND
AP
RS485 FIELDBUS TO ULTRACELLA
ENG
10.2.6 Connection for Pump Down or thermostat Connections for pump down controlled by pressure, with
working simultaneous activation of the compressor and solenoid valve
Connections for pump down controlled by pressure, with If the pump down procedure needs to be performed, controlled by
pressure via a pressure switch connected to the Ultra 3PH Full three-
compressor shutdown due to low pressure
phase module rather than UltraCella, with simultaneous actvation and
If the pump down procedure needs to be performed, controlled by
deactivation of the compressor and solenoid valve, the connections are
pressure via a pressure switch connected to the Ultra 3PH Full three-
as shown in the following diagram.
phase module rather than UltraCella,
Connection and thepump
for operation compressor
down shuts down Connection for operation with thermostat
due to low pressure, the connections are as shown in the following
diagram.
Connection for operation pump down Connection for operation with thermostat
121
126
126
123
125
127
122
123
125
127
124
124
121
126
126
123
125
127
122
123
125
127
124
124
P P
P P
bridge
pressure switch
low pressure switch
liquid valve
bridge
pressure switch
low pressure switch
liquid valve
bridge
liquid valve
bridge
liquid valve
pressure
pressure
pump
pump
low
low
Fig. 9.c
Note: as the pressure switch is connected to the Ultra 3PH Full Nota: Do not enable pump down on UltraCella (set c7=0, H1≠5,
three-phase module, do not enable pump down on UltraCella (set c7=0, H5≠5).
H1≠5, H5≠5).
122
128
109
125
129
110
124
122
126
123
125
127
124
N
L
bridge
bridge
liquid valve
liquid valve
Fig. 9.g
Fig. 9.f
XP1
XA1
M
evaporator fans MV1:V 2 KM1:4
Term.
ENG
evaporator fans MV1:W 3 KM1:6
4 QF1:8/QF2:N1
9
8
7
6
5
3
2
defrost heaters RR1 5 KM2:2
11
10
PE2
103
102
101
109
108
107
106
105
104
116
115
114
113
112
111
110
120
119
118
117
127
126
125
124
142
141
140
129
128
147
146
143
162
161
160
defrost heaters RR1 6 KM2:4
defrost heaters RR1 7 KM2:6
defrost heaters RR1 8 QF1:8
compressor MV2:U 9 KM3:2
Kriwan
M
10
RS485 -
compressor MV2:V KM3:4
RS485 +
UX1 relay
compressor MV2:W 11 KM3:6
RS485 GND
Compressor
Pump Down
PE2
Solenoid valve
10.2.7 Terminal units
Defrost heaters
Evaporator fans
Ground terminal
Condensing fans 2
XP1
1
condenser fans 1 MV3:1 101 XA1:103
M
18 18
condenser fans 1 MV3:2 102 QF2:N2/XA1:106
P
19 19
1
condenser fans 2 MV4:1 105 XA1:104
M
18 18
condenser fans 2 MV4:2 106 XA1:108/XA1:102
21 21
crankcase heater RR2 107 KM3:62
18 18
crankcase heater RR2 108 XA1:106
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
38 38
aux 1 AUX1:1 109 KR2:11
37 37
aux 1 AUX1:2 110 KR2:14
Note
25 25
L
92
kriwan AP2:11 113 XA1:128/XA1:111
28 28
kriwan AP2:14 114 XA1:115
P
28 28
pressure switch SP2 115 XA1:114
29 29
pressure switch SP2 116 KR1:A1
27 27
To supply UltraCella
security thermostat TS1 117 ??:J10/NO1
31 31
security thermostat TS1 118 KM2:A1
30 30
evaporator clicson SP3 119 ??:J10/NO2
33 33
evaporator clicson SP3 120 KM1:A1
29
121 ??:J11/C3/4/5
32
122 XA1:126/??:J11/NO3
35
123
P
35 35
pump down TK1 124
34 34
pump down TK1 125 KM3:A1
32 32
Normally closed. If active (open), evaporator fans are off and it’s not notified in UltraCella
Normally closed. If active (open), evaporator fans are off and it’s not notified in UltraCella
terminal block
Tab. 10.b
ENG
11. SOFTWARE RELEASE
11.1 Software release table
Manual Availability Functions UltraCella Notes
release date Software
release
1.1 28/02/2014 Basic cold room management: compressor, defrost, evaporator fans, light, 1.1 UltraCella single digit display
2xAUX relays
Single digit display management
Commissioning UltraCella through both built-in LED display and pGD1
UltraCella Service
Commissioning through wizard on pGD1
Upload/Download parameters via USB key
Defrost schedule by RTC
HACCP alarms
Maximum and minimum temperature recording
Diagnosis: I/O status visualization
Second step compressor with automatic rotation
Evaporator fans in PWM mode (on/off ) with compressor off
Auxiliary evaporator management
Smart light management by door switch
Bowl heater activation
Condenser fan activation by temperature
Pump down management
Humidity probe reading
Pre-charged configurations (recipes)
Software update through pGD1
1.3 30/06/2014 Double digit display management 1.2 UltraCella double digit display (software
release 1.2) availability in production:
Data logging function (one temperature)
11/04/2014
Humidity ON/OFF output
Serial connection UltraCella - EVD EVO (only "start command")
Service menu on pGD1 (diagnosis)
Navigation improvements on both LED and pGD1 1.3 UltraCella software 1.3 availability in
production: 30/06/2014
Added alarm indication on USB functions (in case of bad working)
Commissioning EVD EVO via UltraCella
Defrost by dI (fixed interval time) enable with RTC defrost set too
Limit and default parameter setting change (H0, /t2, dd, Fd)
0…10V output for variable speed evaporator fans
"Bugfixing: 1.4 UltraCella software 1.4 availability in
Input B5 Humidity reading production: 03/11/2014
High/low temp. alarm delay
EVD communication in manual OFF status"
1.5 30/01/2015 3PH expansion module management (one to one) 1.5 UltraCella software 1.5 availability in
production: 22/12/2014
Data logging: 2 selectable temperatures, variable sampling time
Log of stored alarms
BMS serial line: Modbus / Carel protocols selectable
Software update by built-in LED display
Addition of pGD texts in German and French
New default /A2=1 (defrost probe configured in B2)
New default settings for EVD module (push from UltraCella)
Door switch disabling (new question in wizard and new parameter A3)
Agenzia / Agency: