Operation Instruction

АКУАТЕРМ ЕООД гр. София бул. ” Данаил Николаев “ 32


Operation Description
GSM.: 0888 60 19 19 Turn ON/Turn Press“ ”key one time to turn on,press it again to turn off and close fan coil units
http://aquatherm-bg.net OFF and motorized valve.
Touch Screen Thermostat User Manual Setting In turn on state,press “ ”to decrease temperature and press“ ”to increase
Application Temperature temperature,press every time,temperature change 0.5℃.
HY08AC fan coil units thermostat is used for control room temperature in central air conditioning fan coil
units system.By comparing room temperature with setting temperature to open and close fan coil units and Fan Speed In turn on state,press“ ” to choose fan speed (High ),(Med ),(Low
motorized valve in the end of air conditioning system,to achieve purpose of adjusting room Choice ),(Auto ).
temperature,comfort and saving energy. It uses microprogrammed control unit,large LCD display,LCD
In turn on state,long press“ ”for 3-5seconds to enter into setting screen, short
display mode:working mode (cooling,heating,ventilation), fan speed (high,med,low, auto),room
press “ ” choose “ ” icon,press “ ” confirm to time setting:minute
temperature,setting temperature,time,7 days 4 period program,,timing turn on/off etc.
“mm”flashing,press “ ”or“ ”to adjust value, press “ ” confirm to next
Time Setting
Technical Data setting;hour “hh”flashing, press“ ”or“ ”to adjust value;press “ ”confirm to
Power Supply 220V 50/60Hz Installation Flush Installation next setting; week “ ”flashing,press“ ”or“ ”to adjust value.At last
press“ ”or no any operation for 5seconds to exit setting.
Rated current 5A Sensor NTC
In turn on state,long press“ ”for 3-5 seconds to enter into setting screen, choose
Set Point Range 5~35℃ Accuracy ±0.5°C “ONOFF”press“ ”confirm to timing turn on setting,it displays “ON”and
“--;--”or “hh mm”flashing at the same time,press press “ ” to confirm and press
Ambient 0~50℃ Protection Class IP30 “ ”or“ ”to adjust the hour and press “ ” and “ ”or“ ” to adjust minute
Timing Turn of turn on,adjust to “--;--” and press “ ” to cancel timing turn on and enter into
Size 86*86*14 Housing PC+ABS plastic on/off Setting timing turn off setting,it displays“OFF ”and “--;--”or “hh mm”flashing at the same
time,press press “ ” to confirm and press “ ”or“ ”to adjust the hour and
Ambient temperature 0°C~50°C Storage temperature -10°C-60°C press “ ” and “ ”or“ ” to adjust minute of turn off.Cancel timing turn on/off
setting:just to adjust both timing turn on and turn off as“--”;(timing turn on/off for
Operation Key
one time or cycle running,please set it in advanced setting)
NO. symbols represent
In turn on state,long press“ ”for 3-5seconds to enter into setting screen,press
A Increase key: adjust temperature and value
“ ” to choose “ ” and press “ ”to confirm:switch working mode between
B Setting key Working Mode “ ”.Display“ ” means cooling mode,display“ ”means heating
Choice mode,display“ ”means ventilation mode(HY08AC-2P no heating
C Decrease key:adjust temperature and value mode);display “ ”means cooling,heating mode switch
automatically(HY08AC-4P-A).
D Fan speed key; + is confirm key
In turn on state,short press“ ”for one time to run program mode;press “ ”
E Turn ON/OFF again to run manual mode
Manual And
Displays & Buttons Program Mode HY08AC-4P-M(MODBUS and RS485 version don’t have program mode)The time
Choice and temperature of program mode refer to Program Mode Setting And
Working,when working auto program mode,the temperature can’t be adjusted.

In cooling(heating)mode,when room temperature higher(lower)setting temperature


Motorized Valve 1℃,open motorized valve;when room temperature reach setting temperature,close
Control motorized valve,fan coil continues to work(it can be set as fan close together with
valve in advanced setting).
Ventilation mode(fan coil unit is not under controlling) Advanced Setting A
Fan coil unit is under controlling,it is valve and fan coil unit close together.
In turn off state,long press “ ” for 5 seconds to enter into advanced setting A.Press“ ”or“ ”to
Key Lock function:if thermostat opens key lock function,no any operation after 10
Key Lock set,short press “ ”to next option and press“ ”or“ ”to set
minutes will lock keys automatically(screen display “ ” icon),press “ ” for 5
Function
seconds will unlock(“ ” disappears)
Symbol Item Parameter Default
Door Key Enter into energy saving mode by door card.When pull out door card, “ ”door
Energy Saving card icon flashing,if thermostat is in cooling mode,temperature set as 26℃ A1 Temperature Calibration -9-+9℃ -1℃
Mode automatically,fan run in low speed;if thermostat is in heating mode,temperature set 0:half lock;(It is available to turn on/off
as 18℃ automatically,fan run in low speed
(HY08AC-K) and adjust temperature)
A2 Children Lock 2
1:full lock
Sleep mode In turn on state, long press , is flashing, short press to run it,short press
2: disable child lock
to cancel
Remark: Sleep mode is not available when run ventilate mode or auto mode Setting the low limit 5-15℃ 5℃
A3
Sensor occurs fault,thermostat close fan coil and motorized valve and display temperature
Alarm “E1”or“E2”. Setting the high limit 16-50℃ 35℃
A4
E1:internal sensor alarm E2:external sensor alarm temperature
0: valve off,fan off 0
A5 Fan energy saving control
Program Mode Setting And Working 1: valve off,fan always on
HY08AC fan coil units thermostat can set different time different temperature;there is 5+2,6+1,7days
0=5+2 1=6+1 0
programs can be chosen.
Long press “ ”for 3-5 seconds to enter into setting screen,,short press " ”to choose “ ” and A6 Program mode type 2=7 (everyday all the same)
press “ ”to confirm and enter into program mode setting. 3=disable program mode
After enter into program mode setting,To begin with the first period(“ ” flashing) of Monday,press 2:2pipe 4
“ ” to confirm,starting time(default 6:00),it can press“ ”or“ ”to adjust by yourself,press every A7 Choose valve output
one time to increase or decrease 30 minutes and then press “ ”,press “ ”or“ ” to adjust 4:4pipe
temperature,press “ ” enter into the second period “ ” setting,the same as above to finish 4
periods setting,then enter into Tuesday setting,the same setting method as Monday,then finish 7 days
Timing switch operation 0: Only run once 0
setting,no any operation for 5 seconds will save and exit automatically. A8
mode 1: Cycle run
Default Setting

Period Period Setting Default Time Default Temperature Set temperature for 20-60°C 38°C
A9
1 06:00 20°C external sensor

Monday 2 8:00 15°C AA Backlight sleep time 5-30S 20S


To Sunday 3 17:30 22°C
Display Ao, press key until whole Ao
AB Reset
4 22:00 15°C show
Advanced Setting B Cautions on Installation and Use

Turn off thermostat ,long press 5S to enter advanced setting B, Short press to set 1. To prevent the thermostat display from a high fluctuation, special treatment has been made to the
program. Therefore, it is
next item, press“ ”or“ ”to set item data
normal that the thermostat cannot immediately display the sudden change of temperature.
B1 0: inner sensor
2. The thermostat installed on 1.5m above the ground.
1: inner sensor with key card
3. For the thermostat installed,please take care not to install it to the wall corner, door / window side or
behind the door or in such
2:Double sensor when choose 2, In the heating state,
Sensor type 1
normally only valve is opened , and the fan is turned on unheated area as exterior wall. Avoid hot / cold air duct, radiator, flue or thermal pipe.
when the external temperature is detected to be ≥X°C. 4. If you have any problem for the installed ,please contact our company hysen, we will make a
When the temperature is detected to be lower than demonstration for you
(X-2) °C, the fan is turned off. 5. Only the professional technicians are permitted to open the transmitting and receiving box of the
thermostat for installation. When install the power supply, make sure that the power cable is well
B2 Key Card Type 00: S1 Connect S2 Means Put-out Card Status; 00 insulated.

Disconnection Means Pull-in Card Status 6. The thermostat is unrepairable product. The user shall not open the internal circuit board.

7. HY08AC series thermostat design for the standard 75x75x 35mm wall mount box installed. Follow
01: S1 Connect S2 Means Pull-in Card Status; the instructions to open the rear cover base, mount it on the wall and wire it.

Disconnect Means Put-out Card Status 8. Before installing the thermostat, make sure that the system is disconnected. The maximum voltage of
the system shall meet the requirements specified in the Instruction Manual (Max. AC Voltage:
B3 After Door Card Pull Out Setting Range 22~32℃ 26℃ 250V).

To Cool Temperature

B4 After Door Card Pull Out Setting Range 10~21℃ 18℃


To Heat Temperature

Wiring Diagram