2020 gv50
2020 gv50
Thailand
Malaysia
Singapore
Factory
Sales & Technical
Support Offices
Distribution Networks
INDEX
Australia
Bangladesh
Brunei
China
India 02 PRECISION SPECIALIST
Indonesia
Japan 05 G-VOLUTION
Laos
Macau 11 INTELLIGENT
Myanmar CONTROLS & DISPLAYS
We at CITEC, are committed to deliver innovative products and
Pakistan
services that are revolutionizing advances the precision cooling
Philippines needs. From design and manufacturing to product and after 15 PRODUCT OVERVIEW
Sri Lanka sales support services, we constantly build upon our proven
innovation of precision, efficiency and creativity to deliver a full
United Arab Emirates 18 TECHNICAL
range of consultancy for customized business needs or an array
Vietnam of designs and models to a myriad of clienteles. SPECIFICATION
Established in Malaysia since 1996, CITEC International has constantly reinvented itself to evolve into one of the
leading manufacturers for precision air conditioning products.
As experts in the field of precision air conditioning, CITEC thrives on Research and Development (R&D) to
deliver innovative products that are of exceptional standards with best performance, reliability and efficiency.
We create real value and business differentiation by taking an integrated approach covering all aspects of our
customers’ businesses.
Today, CITEC has established a wide network of distributors to provide excellent product support and long-
term services to various industries across Asia Oceanic and Pacific regions.
CERTIFICATIONS
G-VOLUTION
CITEC products are engineered to achieve Thus, best performance products with the highest
optimum reliability, eff iciency and ease of eff iciency are guaranteed.
installation and maintenance driven by the needs
of our customers. Products are designed using Our products undergo extensive and stringent tests
sophisticated 3D CAD system and Computational following ASHRAE standards in our well-equipped
Fluid Dynamics (CFD) analysis to ensure optimum
air flow with maximum eff iciency.
testing laboratory facilities accredited with Class A
certif ication by the national authorities. GROUNDBREAKING TECHNOLOGY
EC
Chilled Water series comes with exclusively two different range; EC and
ECL to suit various requirements and applications.
6 G-VOLUTION G-VOLUTION 7
Unique dual coil series, the EH range is designed to provide the highest level of
EH redundancy. There are two types of dual coil system; dual chilled water system or a Panel
combination of direct expansion and chilled water system. The EH range complies
with various applications preventing downtime whilst safeguarding the operations of
your data center. Should a fault be detected in the primary system, the unit operating
condition will be closely monitored while performing the switch from primary to the Panel Insulation
secondary system with CITEC powerful Genius 5+ controller.
Insulation
DESIGN FEATURE
INNOVATIVE MODULAR DESIGN
COMPLIES WITH TECHNOLOGY FULL FRONT
The modular concept ACCESS
offers flexibility in Built-in components
combining two smaller can be easily accessible
size units due to limited from the front which
corridor space. It also significantly improves
allows a combination of the maintainability and
additional unit onto an serviceability of the unit.
+ =
existing installed unit to
meet higher cooling
requirements for future
facility expansion.
8 G-VOLUTION G-VOLUTION 9
ELECTRONIC
EXPANSION VALVE
The innovative Electronic Expansion Valve (EEV)
provides highly efficient control of refrigerant
flow based on real-time feedback. The EEV can
provide fast, stable and precise control even
under low-load condition. The presence of the
temperature and pressure probe allow real time
monitoring of suction temperature and pressure
as well as the superheat of the system.
DIRECT DRIVE
EC FAN SYSTEM
The Electronically Commutated (EC) fan motor combination
offers a number of advantages over traditional belt-driven
forward curved centrifugal blower, such as:
Higher efficiency compared to forward curved fans
Reduced losses due to the absence of pulley and belt
usage in the standard belt-driven fan
ADVANCE COOLING WITH 15-30% more energy savings
UNDERFLOOR EC FAN Variable speed control
An underfloor version of the EC fan is available for Maintenance-free, higher reliability
downflow models. Studies have shown that the Soft start feature, where the fan slowly ramps up to
placement of underfloor EC fans contribute to a the desired speed
10% to 15% improvement in performance and is
recommended for users who would like to utilize the
full capacity of the EC fan. These fans are pre-wired
and pre-packaged into the Precision Air Conditioning
unit prior to delivery for instant installation.
SOLUTION
FOR A
PRECISE &
EFFICIENT
MODBUS RTU protocol can also be connected to BMS directly providing system
monitoring and management. With an optional BMS card, CITEC controller will be able
to connect to other communication protocol as illustrated below:
POWER LIES
Gateway - pCOWEB pCONET
Protocol
WITHIN THE
MODBUS RTU
pCONET MODBUS TCP / IP
INTELLIGENT
BACNET MS / TP
BACNET / IP
CONTROLS &
BACNET ETHERNET
pCOWEB SNMP
Touch screen display provides informative and user-friendly
DISPLAYS
interface for easy navigation. The display can show graphical HTTP
information via animated icons and also capable of plotting FTP
trend graphs for temperature and humidity.
SMTP
At-a-glance reporting on
PRODUCT
performance metrics and
room environment
OVERVIEW
03 Fan Configuration
Crankcase heater*
Hot gas bypass
3-way valve
Screwed water connection
Electronic Pressure Independent Valve (EPIV)
Water In & Out temperature sensor
Centrifugal fan with belt
driven AC motor (Standard) *Standard for Inverter models.
EC fan (Optional)
Note:
This diagram drawing is for illustration purpose only.
Gross Total Capacity kW 9.83 14.72 18.17 20.23 25.70 31.90 35.07 41.64 44.60 49.66 61.86 69.18 82.06 89.38 99.52
Gross Sensible Capacity kW 9.83 12.72 18.17 20.23 23.11 28.17 29.59 41.64 43.21 45.37 61.86 66.48 72.06 86.06 90.42
S.H.R. 1.00 0.86 1.00 1.00 0.90 0.88 0.84 1.00 0.97 0.91 1.00 0.96 0.88 0.96 0.91
Nominal Air Flow m3/s 1.00 1.00 1.84 1.84 1.84 2.24 2.24 3.70 3.70 3.70 5.30 5.30 5.30 7.20 7.20
No. of Fan(s) 1 1 1 1 1 1 1 2 2 2 2 2 2 3 3
No. of Compressor(s) 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2
No. of Refrigerant Circuit(s) 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2
Sound Level dBA 52 52 61 61 61 62 62 64 64 64 66 66 66 67 67
Nominal Air Cooled Model HEC 194 234 234 234 314 374 434 574 574 574 2x374 2x374 2x574 2x574 2x574
Nominal Water Cooled Model WA20 WA30 WB40 WB40 WB60 WB60 WB80 WB80 WB80 WC60 2xWB60 2xWB60 2xWB80 2xWB80 2xWC60
Nominal Water Flow Rate l/s 0.56 0.87 1.04 1.16 1.49 1.85 2.06 2.36 2.53 2.89 3.52 3.93 4.75 5.06 5.80
Waterside Pressure Drop of kPa 36.8 42.8 14.1 17.5 15.9 24.5 21.7 28.3 32.6 57.1 22.1 27.6 28.8 32.7 57.3
Condenser
Length mm 648 648 800 800 800 885 885 1315 1315 1315 1815 1815 1815 2500 2500
Depth mm 654 654 891 891 891 891 891 891 891 891 891 891 891 891 891
Height mm 1940 1940 1985 1985 1985 1985 1985 1985 1985 1985 1985 1985 1985 1985 1985
Gross Weight - “A” Version kg 165 195 275 275 300 310 310 445 450 450 610 610 617 790 790
- “W” Version kg 173 204 286 287 314 324 326 461 466 466 638 638 645 822 822
Min. Service Allowance mm 600 600 725 725 725 725 725 725 725 725 725 725 725 800 800
Notes:
1. Cooling capacity is based on 24ºC, 45%RH, R407C refrigerant, 45ºC condensing temperature, 400V/3ph+N/50Hz power supply, 50Pa ESP.
TECHNICAL
2. Sound level is for downflow models measured at 1m in free field conditions.
3. Nominal air cooled condenser sizing is suggestion only based on 35ºC ambient & nominal operating condition. Other sizes may be selected to suit requirement as necessary.
4. Nominal water cooled condenser sizing is suggestion only based on water in/out 30/35ºC & nominal operating condition. Other sizes may be selected to suit requirement as
necessary.
5. Water cooled condenser to be installed externally, please consult factory if required to be installed internally.
6. For underfloor EC fan option, raise floor height must be >400mm. *Option not available for model 8 and 12.
7. **For model 30 & 35, only EC fan version is available.
Due to our policy of continuous development and improvement, the specifications and data herein are subjected to change without notice. We must therefore reserve the
SPECIFICATION
right to supply equipment that may differ from that described and illustrated herein. All information, including illustrations, contained in this brochure, is believed to be
accurate and reliable. Users, however, should independently evaluate the suitability of each product for their own application. CITEC makes no warranties as to accuracy or
completeness of the information, and disclaims any liability regarding its use.
UNIT MODEL (ESD/ESU xx A/W) 20 25 30 35 40 45 60 70 80 90 UNIT MODEL (ECD/ECU xxx) 8*** 12*** 25* 30** 50* 60 70 80 95 110 125 135 150
Gross Total Capacity kW 21.06 25.03 30.34 34.92 41.17 46.36 59.70 72.64 79.98 92.81 Downflow
Gross Sensible Capacity kW 21.06 22.82 27.49 29.52 41.17 43.95 59.70 65.74 68.97 87.52 Gross Total Capacity kW 9.67 12.39 24.07 30.27 51.01 64.31 74.71 83.63 100.27 113.93 123.42 131.51 155.54
S.H.R. 1.00 0.91 0.91 0.85 1.00 0.95 1.00 0.91 0.86 0.94 Gross Sensible Capacity kW 9.42 11.65 22.31 27.58 46.08 57.00 66.77 73.76 87.09 99.01 106.18 115.05 133.88
S.H.R. 0.98 0.94 0.93 0.91 0.90 0.89 0.89 0.88 0.87 0.87 0.86 0.88 0.86
GENERAL DATA 20 25 30 35 40 45 60 70 80 90
Upflow
Nominal Air Flow m3/s 1.84 1.84 2.24 2.24 3.70 3.70 5.30 5.30 5.30 7.20 Gross Total Capacity kW 9.67 12.39 24.07 30.27 51.01 61.16 71.20 79.58 95.93 108.20 117.73 127.41 151.06
No. of Fan(s) 1 1 1 1 2 2 2 2 2 3 Gross Sensible Capacity kW 9.42 11.65 22.31 27.58 46.08 54.22 63.76 70.39 83.55 94.22 101.33 111.52 130.11
No. of Compressor(s) 1 1 1 1 1 1 2 2 2 2 S.H.R. 0.98 0.94 0.93 0.91 0.90 0.89 0.90 0.88 0.87 0.87 0.86 0.88 0.86
No. of Refrigerant Circuit(s) 1 1 1 1 1 1 2 2 2 2
Sound Level dBA 62 62 63 63 64 64 66 66 66 67 GENERAL DATA 8*** 12*** 25* 30** 50* 60 70 80 95 110 125 135 150
Nominal Air Flow (Downflow) m3/s 1.00 1.00 1.84 2.24 3.70 4.40 5.20 5.20 6.00 7.00 7.00 7.60 8.60
CONDENSER 20 25 30 35 40 45 60 70 80 90 Nominal Air Flow (Upflow) m3/s 1.00 1.00 1.84 2.24 3.70 4.20 5.00 5.00 5.80 6.70 6.70 7.40 8.40
Nominal Air Cooled Model HEC 234 314 374 434 574 574 2x374 2x434 2x574 2x574 No. of Fan(s) 1 1 1 1 2 2 2 2 2 3 3 3 3
Nominal Water Cooled Model WB40 WB60 WB60 WB80 WB80 WB80 2xWB60 2xWB80 2xWB80 2xWB80 Sound Level dBA 52 52 61 62 64 67 67 67 68 68 68 68 68
Condenser Water Flow Rate l/s 1.22 1.50 1.81 2.12 2.40 2.70 3.49 4.31 4.72 5.41
Waterside Pressure Drop of Condenser kPa 19.6 16.0 23.3 23.0 29.5 37.3 21.7 23.7 28.5 37.3 CHILLED WATER COIL 8*** 12*** 25* 30** 50* 60 70 80 95 110 125 135 150
Downflow
ELECTRIC RE-HEATER 20 25 30 35 40 45 60 70 80 90
Nominal Water Flow l/s 0.46 0.59 1.15 1.45 2.44 3.07 3.57 4.00 4.79 5.44 5.90 6.28 7.43
Nominal Heater Capacity kW 6 6 6 6 12 12 12 12 12 12 Water Pressure Drop kPa 27.4 44.6 34.6 56.6 67.7 107.9 69.2 70.9 107.6 145.4 90.6 60.6 87.2
No. of Heater Step(s) 1 1 1 1 2 2 2 2 2 2
Upflow
Nominal Water Flow l/s 0.46 0.59 1.15 1.45 2.44 2.92 3.40 3.80 4.58 5.17 5.63 6.09 7.22
ELECTRODE HUMIDIFIER 20 25 30 35 40 45 60 70 80 90
Water Pressure Drop kPa 27.4 44.6 34.6 56.6 67.7 104.0 65.8 65.9 101.2 135.0 89.5 59.8 86.5
Nominal Humidifier Capacity kg/hr 5 5 5 5 5 5 5 5 5 8
ELECTRIC RE-HEATER 8*** 12*** 25* 30** 50* 60 70 80 95 110 125 135 150
UNIT DIMENSION & WEIGHT 20 25 30 35 40 45 60 70 80 90
Nominal Heater Capacity kW 6 6 6 6 12 12 12 12 12 12 12 12 12
Length mm 800 800 885 885 1315 1315 1815 1815 1815 2500 No. of Heater Step(s) 1 1 1 1 2 2 2 2 2 2 2 2 2
Depth mm 891 891 891 891 891 891 891 891 891 891
Height mm 1985 1985 1985 1985 1985 1985 1985 1985 1985 1985 ELECTRODE HUMIDIFIER 8*** 12*** 25* 30** 50* 60 70 80 95 110 125 135 150
Gross Weight - “A” Version kg 265 265 275 280 415 430 545 545 570 725
Nominal Humidifier Capacity kg/hr 5 5 5 5 5 5 5 5 8 8 8 8 8
- “W” Version kg 277 279 289 296 431 446 573 573 602 757
Min. Service Allowance mm 725 725 725 725 725 725 725 725 725 800 UNIT DIMENSION & WEIGHT 8*** 12*** 25* 30** 50* 60 70 80 95 110 125 135 150
Length mm 648 648 800 885 1315 1550 1800 1800 2065 2300 2300 2550 2815
Depth mm 654 654 891 891 891 891 891 891 891 891 891 891 891
Height mm 1940 1940 1985 1985 1985 1985 1985 1985 1985 1985 1985 1985 1985
Gross Weight kg 139 165 245 260 355 405 485 505 535 570 595 635 710
Min. Service Allowance mm 600 600 725 725 725 725 725 725 725 725 725 725 725
Notes: Notes:
1. Cooling capacity is based on 24°C, 45%RH, R410A refrigerant, 45°C condensing temperature, 400V/3ph+N/50Hz power supply, 50Pa ESP. 1. Cooling capacity is based on 24ºC, 45%RH, Chilled Water in/out based on 7/12ºC, 400V/3ph+N/50Hz power supply, 50Pa ESP.
2. Sound level is for downflow models measured at 1m in free field conditions. 2. Sound level is measured at 1m in free field conditions.
3. Nominal air cooled condenser sizing is suggestion only based on 35ºC ambient & nominal operating condition. Other sizes may be selected to suit requirement as necessary. 3. For underfloor EC fan option, raise floor height must be >400mm.
4. Nominal water cooled condenser sizing is suggestion only based on water in/out 30/35ºC & nominal operating condition. Other sizes may be selected to suit requirement as 4. For upflow version, only EC fan is available (*except model 25 & 50).
necessary. 5. ** For downflow version, only EC fan is available.
5. Water cooled condenser to be installed externally, please consult factory if required to be installed internally. 6. ***For model 8 & 12, only direct driven/EC fan is available.
6. For underfloor EC fan option, raise floor height must be >400mm.
7. Standard unit comes with fan speed controller, crankcase heater, oil separator & liquid solenoid valve.
Due to our policy of continuous development and improvement, the specifications and data herein are subjected to change without notice. We must therefore reserve the Due to our policy of continuous development and improvement, the specifications and data herein are subjected to change without notice. We must therefore reserve the
right to supply equipment that may differ from that described and illustrated herein. All information, including illustrations, contained in this brochure, is believed to be right to supply equipment that may differ from that described and illustrated herein. All information, including illustrations, contained in this brochure, is believed to be
accurate and reliable. Users, however, should independently evaluate the suitability of each product for their own application. CITEC makes no warranties as to accuracy or accurate and reliable. Users, however, should independently evaluate the suitability of each product for their own application. CITEC makes no warranties as to accuracy or
completeness of the information, and disclaims any liability regarding its use. completeness of the information, and disclaims any liability regarding its use.
UNIT MODEL (ECL xxx) 70 80 125 140 180 200 UNIT MODEL (EHU/EHD xx C) 60 70 85 95
Gross Total Capacity kW 69.20 76.74 127.79 141.71 180.09 200.13 Gross Total Capacity - Downflow/Upflow kW 60.16 / 58.23 72.79 / 69.34 90.08 / 86.28 96.94 / 91.42
Gross Sensible Capacity kW 61.05 66.61 112.58 122.97 159.52 174.46 Gross Sensible Capacity - Downflow/Upflow kW 53.68 / 51.99 65.49 / 62.51 79.77 / 76.55 88.47 / 83.44
S.H.R. 0.88 0.87 0.88 0.87 0.89 0.87 S.H.R - Downflow / Upflow 0.89 / 0.89 0.90 / 0.90 0.89 / 0.89 0.91 / 0.91
Nominal Water Flow l/s 3.31 3.67 6.11 6.77 8.60 9.56 CHILLED WATER COIL 60 70 85 95
Water Pressure Drop kPa 105.3 68.3 86.3 86.3 111.5 122.3 Nominal Water Flow Rate - Downflow / Upflow l/s 2.87 / 2.78 3.48 / 3.31 4.30 / 4.12 4.63 / 4.37
Waterside Pressure Drop - Downflow / Upflow kPa 92.1 / 91.6 63.8 / 60.6 104.3 / 100.3 75.4 / 70.0
ELECTRIC RE-HEATER 70 80 125 140 180 200
Length mm 1315 1315 2065 2065 2815 2815 UNIT DIMENSION & WEIGHT 60 70 85 95
Depth mm 991 991 991 991 991 991
Length mm 1550 1800 2065 2300
Height mm 1985 1985 1985 1985 1985 1985
Depth mm 991 991 991 991
Gross Weight kg 385 400 600 630 785 825
Height mm 1985 1985 1985 1985
Min. Service Allowance mm 725 725 725 725 725 725
Gross Weight kg 475 565 610 650
Min. Service Allowance mm 725 725 725 725
Notes: Notes:
1. Cooling capacity is based on 24ºC, 45%RH, Chilled Water in/out based on 7/12ºC, 400V/3ph+N/50Hz power supply, 50Pa ESP. 1. Cooling capacity is based on 24ºC, 45%RH, Chilled Water in/out based on 7/12ºC, 400V/3ph+N/50Hz power supply, 50Pa ESP.
2. Sound level is for downflow models measured at 1m in free field conditions. 2. Sound level is for downflow models measured at 1m in free field conditions.
3. For underfloor EC fan, raise floor height must be >500mm. 3. For underfloor EC fan option, raise floor height must be >400mm.
4. Only downflow version with EC fan is available. 4. Only EC fan is available.
Due to our policy of continuous development and improvement, the specifications and data herein are subjected to change without notice. We must therefore reserve the Due to our policy of continuous development and improvement, the specifications and data herein are subjected to change without notice. We must therefore reserve the
right to supply equipment that may differ from that described and illustrated herein. All information, including illustrations, contained in this brochure, is believed to be right to supply equipment that may differ from that described and illustrated herein. All information, including illustrations, contained in this brochure, is believed to be
accurate and reliable. Users, however, should independently evaluate the suitability of each product for their own application. CITEC makes no warranties as to accuracy or accurate and reliable. Users, however, should independently evaluate the suitability of each product for their own application. CITEC makes no warranties as to accuracy or
completeness of the information, and disclaims any liability regarding its use. completeness of the information, and disclaims any liability regarding its use.
Nominal Air Flow - Downflow/Upflow m3/s 4.2 / 4.1 5.2 / 5.0 6.2 / 6.0 7.5 / 7.0 Nominal Air Flow - Downflow/Upflow m3/s 4.2 / 4.1 5.2 / 5.0 6.2 / 6.0
No. of Fans 2 2 3 3 No. of Fans 2 2 3
No. of Compressors 2 2 2 2 No. of Compressors 2 2 2
No. of Refrigerant Circuits 2 2 2 2 No. of Refrigerant Circuits 2 2 2
Sound Level dBA 67 67 68 68 Sound Level dBA 67 67 68
CONDENSER 60 70 85 95 CONDENSER 60 70 85
Nominal Air Cooled Condenser HEC 2x374 2x434 2x574 2x574 Nominal Air Cooled Condenser HEC 2x374 2x434 2x574
Nominal Water Cooled Model 2xWB60 2xWB80 2xWB80 2xWC50 Nominal Water Cooled Model 2xWB60 2xWB80 2xWB80
Nominal Water Flow Rate - Downflow/Upflow l/s 3.72 / 3.69 4.34 / 4.29 4.84 / 4.80 5.69 / 5.61 Nominal Water Flow Rate - Downflow/Upflow l/s 3.62 / 3.60 4.45 / 4.41 5.20 / 5.16
Waterside Pressure Drop of Condenser - kPa 24.7 / 24.3 24.0 / 23.6 29.9 / 29.4 77.2 / 75.2 Waterside Pressure Drop of Condenser - kPa 23.4 / 23.1 25.3 / 24.8 34.5 / 34.0
Downflow/Upflow
Nominal Water Flow Rate - Downflow/Upflow l/s 2.95 / 2.86 3.56 / 3.39 4.38 / 4.19 4.88 / 4.56 Nominal Water Flow Rate - Downflow/Upflow l/s 2.95 / 2.86 3.56 / 3.39 4.38 / 4.19
Waterside Pressure Drop - Downflow/Upflow kPa 99.7 / 99.3 68.5 / 65.2 110.3 / 106.2 84.4 / 77.0 Waterside Pressure Drop - Downflow/Upflow kPa 99.7 / 99.3 68.5 / 65.2 110.3 / 106.2
Notes:
Notes: 1. Cooling capacity is based on 24ºC, 45%RH, R410A refrigerant, 45ºC condensing temperature for DX system, chilled water in/out based on 7/12ºC, 400V/3ph+N/50Hz power supply,
1. Cooling capacity is based on 24ºC, 45%RH, R407C refrigerant, 45ºC condensing temperature for DX system, chilled water in/out based on 7/12ºC, 400V/3ph+N/50Hz power 50Pa ESP.
supply, 50Pa ESP. 2. Sound level is for downflow models measured at 1m in free field conditions.
2. Sound level is for downflow models measured at 1m in free field conditions. 3. Nominal air cooled condenser sizing is suggestion only based on 35ºC ambient & nominal operating condition. Other sizes may be selected to suit requirement as necessary.
3. Nominal air cooled condenser sizing is suggestion only based on 35ºC ambient & nominal operating condition. Other sizes may be selected to suit requirement as necessary. 4. Nominal water cooled condenser sizing is suggestion only based on water in/out 30/35ºC & operating condition. Other sizes may be selected to suit requirement as necessary.
4. Nominal water cooled condenser sizing is suggestion only based on water in/out 30/35ºC & operating condition. Other sizes may be selected to suit requirement as necessary. 5. For underfloor EC fan option, raise floor height must be >400mm.
5. For underfloor EC fan option, raise floor height must be >400mm. 6. Only EC fan is available.
6. Only EC fan is available. 7. Standard unit comes with fan speed controller, crankcase heater, oil separator & liquid solenoid valve.
Due to our policy of continuous development and improvement, the specifications and data herein are subjected to change without notice. We must therefore reserve the right to supply Due to our policy of continuous development and improvement, the specifications and data herein are subjected to change without notice. We must therefore reserve the
equipment that may differ from that described and illustrated herein. All information, including illustrations, contained in this brochure, is believed to be accurate and reliable. Users, right to supply equipment that may differ from that described and illustrated herein. All information, including illustrations, contained in this brochure, is believed to be
however, should independently evaluate the suitability of each product for their own application. CITEC makes no warranties as to accuracy or completeness of the information, and accurate and reliable. Users, however, should independently evaluate the suitability of each product for their own application. CITEC makes no warranties as to accuracy or
disclaims any liability regarding its use. completeness of the information, and disclaims any liability regarding its use.
C O N D E N S E R
UNIT MODEL HEC 194 234 274 314 374 434 574 654 904
Heat Rejection kW 18.96 22.63 26.64 31.00 37.43 43.04 57.03 65.17 90.46
Air Flow m3/s 2.33 2.10 2.19 2.24 2.53 2.65 4.50 4.60 6.60
No. of Fan(s) 1 1 1 1 1 1 2 2 3
Sound Level dBA 56 56 57 59 60 61 62 62 64
DIMENSION & WEIGHT HEC 194 234 274 314 374 434 574 654 904
Length mm 822 822 862 987 1212 1362 1562 1768 2318
Depth mm 473 473 473 494 494 524 494 494 494
Height mm 825 825 926 926 1028 1155 1063 1063 1063
Header Size 7/8” 7/8” 1 1/8” 1 1/8” 1 1/8” 1 3/8” 1 3/8” 1 3/8” 1 3/8”
Gross Weight kg 56 60 63 75 90 110 125 150 205
L D
www.citecinternational.com
F: +65 - 6281 4412 F: +66 – 2019 0548
E: [email protected] E: [email protected]