RIELLO RL 30-100-130 Burners
RIELLO RL 30-100-130 Burners
TECHNICAL DATA. . . . . . . . . . . .. . . .. . .. . . .. . .. . . page 3 Do not store flammable or hazardous materials in the vicinity
Burner models designations . . . . .. . . .. . .. . . .. . .. . . ..... 3 of fuel burning appliances.
Accessories . . . . . . . . . . . . . . . . .. . . .. . .. . . .. . .. . . ..... 3
Burner description . . . . . . . . . . . .. . . .. . .. . . .. . .. . . ..... 4 Improper installation, adjustment, alteration, service or main-
Packaging - Weight . . . . . . . . . . .. . . .. . .. . . .. . .. . . ..... 4 tenance can cause property damage, personal injury or
Max. dimensions . . . . . . . . . . . . .. . . .. . .. . . .. . .. . . ..... 4
death. Refer to this manual for instructional or additional in-
Standard equipment . . . . . . . . . . .. . . .. . .. . . .. . .. . . ..... 4
Firing rate . . . . . . . . . . . . . . . . . . .. . . .. . .. . . .. . .. . . ..... 5
formation. Consult a certified installer, service representative
Minimum furnace dimensions . . . .. . . .. . .. . . .. . .. . . ..... 5 or the gas supplier for further assistance.
N.B.
Figures mentioned in the text are identified as follows:
1)(A) = part 1 of figure A, same page as text;
1)(A)p.4 = part 1 of figure A, page number 4.
2
TECHNICAL DATA
MODEL RL 70 RL 100 RL 130
Output (1) High fire MBtu/hr (3) 1792 - 3136 2688 - 4480 3584 - 5824
Delivery (1) GPH 12.8 - 22.4 19.2 - 32 25.6 - 41.6
Low fire MBtu/hr (3) 966 - 1792 1344 - 2688 1834 - 3584
GPH 6.9 - 12.8 9.6 - 19.2 13.1 - 25.6
Fuel # 2 Fuel oil
Operation Low - high
Nozzles number 2
Standard applications Hot water, steam, thermal oil
Ambient temperature °F 32 - 104 (0 - 40 °C)
Combustion air temperature °F max 140 (60 °C)
Main power supply (+/- 10 %) V/Ph/Hz 208-230 / 460 / 575 / 3/60
Fan motor rpm 3400 3400 3400
W - HP 1100 - 1.5 1800 - 2.5 2200 - 3
V 208 - 230/460/575 208 - 230/460/575 208 - 230/460/575
A 4.8 / 2.8 / 2 6.7 / 3.9 / 2.8 8.8 / 5.1 / 3.7
Ignition trasformer V1 - V2 120 V - 2 x 5 kV
I1 - I2 3.7 A - 35 mA
Pump delivery (174 Psi) GPH 54
pressure range PSI 145 - 290
Electrical power consumption W max 1400 2200 2600
Electrical protection NEMA1
Noise levels (2) dBA 68.0 70.0 70.0
(1) Reference conditions: Ambient temperature 68° F (20° C) - Barometric pressure 394” WC - Altitude 329 ft.
(2) Sound pressure measured in manufacturers combustion laboratory, with burner operating on test boiler and at maximum rated output.
(3) Equivalent Btu values based on 1 USGPH = 140,000 Btu/hr.
ACCESSORIES (optional):
• Available auxiliary panels
Auxiliary panel code Flame safeguard type
3010330 Fireye
3010334 Landis
Important:
The installer is responsible for the supply and installation of any safety device(s) not indicated in this manual.
3
BURNER DESCRIPTION (A)
1 Ignition electrodes
2 Combustion head
3 Screw for combustion head adjustment
4 Screw for fixing fan to flange
5 Slide bars for opening the burner and inspecting
the combustion head
6 Safety solenoid valve
7 Pump
8 Air inlet to fan
9 Air damper
10 Hydraulic cylinder for regulation of the air damper
at low and high positions. When the burner is not
operating the air damper is fully closed in order to
reduce heat loss from the boiler.
11 Fan pressure test point
12 Boiler mounting flange
13 Flame stability disk
14 Electrical motor
15 Extensions for slide bars 5)
16 Ignition transformer
17 Motor contactor and thermal cut-out with reset button
18 Low and high fire valve assembly
19 Terminal strip
20 Two switches:
- one "burner off - on"
- one low - high operation"
21 Knockouts for wiring carried out by the installer
22 Flame safeguard with lock-out pilot light and lock-
out reset button
23 Flame inspection window
24 Pump pressure adjustment
25 Photocell (cad cell)
26 Air pressure switch
D2324
Two types of burner failure may occur:
• FLAME SAFEGUARD LOCK-OUT:
if the Flame relay 22)(A) pushbutton lights up, it in-
dicates that the burner is in lock-out.
To reset, press the pushbutton.
• MOTOR TRIP:
(A) release by pressing the pushbutton on thermal relay.
PACKAGING-WEIGHT (B)
Approximate measurements
inch A(1) B C lbs • The burner is shipped on a skid. Outer dimensions
of packaging are indicated in (B)
RL70 37 25/32 ” - 45 9/32 ” 23 5/8 ” 25 11/16 ” 132 • The weight of the burner complete with packaging is
RL100 37 25/32 ” - 45 9/32 ” 23 5/8 ” 25 11/16 ” 139 indicated in table (B).
RL130 37 25/32 ” - 45 9/32 ” 23 5/8 ” 25 11/16 ” 146
D36 MAX. DIMENSIONS (C)
(B) Approximate measurements
The maximum dimensions of the burners are given in
(C).
Inspection of the combustion head requires the burner
to be opened and the rear part withdrawn on the slide
bars.
The maximum dimension of the burner when open is
given in measurement I.
STANDARD EQUIPMENT
2 - Flexible hoses
1 - Head gasket
4 - Screws to secure the burner flange to the boiler:
D686
(C) 1/2 W x 13/8”
1 - Instruction booklet
1 - Spare parts list
RL A B C D E F (1) G H I (1) 1 - Adaptor G1/8” - 1 3/8 ” NPT
70 22 27/32 ” 11 21/32 ” 11 3/16 ” 21 27/32 ” 26 25/32 ” 9 27/32 ” - 15 5/32 ” 7 1/16 ” 16 15/16 ” 37 7/16 ” - 42 3/4 ”
100 23 19/32 ” 12 9/32 ” 11 5/16 ” 21 27/32 ” 26 25/32 ” 9 27/32 ” - 15 5/32 ” 7 1/16 ” 16 15/16 ” 37 7/16 ” - 42 3/4 ”
130 24 5/8 ” 13 5/16 ” 11 5/16 ” 21 27/32 ” 26 25/32 ” 9 27/32 ” - 15 5/32 ” 7 7/16 ” 16 15/16 ” 37 7/16 ” - 42 3/4 ”
(1) Blast tube: short - long (obtainable with the kit)
4
FIRING RATE (A)
The RL 70 - 100 - 130 Model burners can work in two
ways: Low and High fire.
LOW FIRE DELIVERY must be selected within area A
comb. chamber “ WC
(A) D2325
Diameter (inches)
Furnace dimensions
Length (ft)
(B) D2919
5
INSTALLATION
6
The two nozzles usually have equal deliveries, but the
low fire nozzle may have the following specifications if
required:
• a delivery less than 50% of the total delivery when-
ever the back-pressure peak must be reduced at the
moment of firing: the burner allows good combustion
values also with a ratio 40 - 100 % between low and
high fire;
• a delivery higher than 50% of the total delivery
D2281 whenever the combustion during low fire must be
improved.
Example with the RL 70 Model:
D691 Boiler output = 2130 MBTU/hr - efficiency 80 %
(A) (B) Output required by the burner =
2130 : 0.8 = 2662 MBTU/hr;
2662 : 2 = 1331 MBTU/hr per nozzle;
therefore, two equal, 60°, 174 PSI nozzles are re-
quired:
1° = 7.0 GPH - 2° = 7.0 GPH,
or the following two different nozzles:
1° = 6.0 GPH - 2° = 8.0 GPH,
D2360
or:
1° = 8.0 GPH - 2° = 6.0 GPH.
NOZZLE ASSEMBLY
At this stage of installation the burner is still disassem-
bled from the blast tube; it is now possible to install the
two nozzles, after having removed the plastic plugs
2)(A), fitting the wrench through the central hole in the
(C) flame stability disk.
Do not use any sealing products such as gaskets,
sealing compound, or tape. Be careful to avoid damag-
ing the nozzle sealing seat. The nozzles must be
screwed into place tightly but carefully.
The nozzle for low fire operation is the one lying be-
neath the firing electrodes Fig. (B).
Make sure that the electrodes are positioned as shown
in Figure (B).
Finally remount the burner 3)(C) to the slide bars 2)
and slide it up to the flange 5), keeping it slightly raised
to prevent the flame stability disk from pressing
against the blast tube.
Tighten the screws 1) on the slide bars 2) and screws
(D) 4) fixing the burner to the flange.
D694
SETTING THE COMBUSTION HEAD If it proves necessary to change a nozzle with the
burner already fitted to the boiler, proceed as outlined
below:
- Retract the burner on its slide bars as shown in
fig. (B)p.6.
- Remove the nuts 1)(D) and the disk 2).
- Use wrench 3)(D) to change the nozzles.
7
HYDRAULIC SYSTEM
FUEL SUPPLY
7 5
A Double-pipe circuit (A)
V
The burner is equipped with a self-priming pump which
is capable of feeding itself within the limits listed in the
P
table at the left.
1 The tank higer than the burner A
6 The distance "P" must not exceed 32 ft in order to
avoid subjecting the pump's seal to excessive strain;
+H
the distance "V" must not exceed 13 ft in order to per-
3 15/16 ”
2 mit pump self-priming even when the tank is almost
completely empty.
(B)
8
PUMP (A)
1 - Suction 1/4” NPT
RL 70 - 100 - 130: SUNTEC AJ4 2 - Return 1/4” NPT
3 - Pressure gauge attachment G 1/8
4 - Vacuum gauge attachment G 1/8
5 - Pressure adjustment screw
6 - Screw for by-pass
A - Min. delivery rate at 174 PSI pressure
B - Delivery pressure range
D2329 C- Max. suction pressure
D- Viscosity range
E - Light oil max. temperature
F - Max. suction and return pressure
G- Pressure calibration in the factory
H- Filter mesh width
PUMP PRIMING
- Before starting the burner, make sure that the
tank return line is not clogged. Obstructions in
the line could cause the seal located on the
PUMP AJ4 pump shaft to break. (The pump leaves the factory
with the by-pass closed).
- In order for self-priming to take place, one of the
A GPH 54
screws 3)(A) of the pump must be loosened in order
B PSI 145 - 290
to bleed off the air contained in the suction line.
C “Hg 13
- Start the burner by closing the control circuit and
D cSt 2,8 - 75
with switch 1)(C)p.10 in the "ON" position. The
E °F - °C 140 - 60
pump must rotate in the direction of the arrow
F PSI 29 marked on the cover.
G PSI 174 - The pump can be considered to be primed when the
H inch 0,006 light oil starts coming out of the screw 3). Stop the
burner: switch 1)(C)p.12 set to "OFF" and tighten
(A)
the screw 3).
The time required for this operation depends upon the
diameter and length of the suction tubing. If the pump
fails to prime at the first starting of the burner and the
burner locks out, wait approx. 15 seconds, reset the
burner, and then repeat the starting operation as often
as required. After 5 or 6 starting operations allow 2 or
3 minutes for the transformer to cool.
Do not illuminate the photocell or the burner will lock
out; the burner should lock out anyway about 10 sec-
onds after it starts.
Important:
The priming operation is possible because the pump is
already full of fuel when it leaves the factory. If the
pump has been drained, fill it with fuel through the
opening on the vacuum gauge prior to starting; other-
wise, the pump will seize. Whenever the length of the
suction piping exceeds 66-99 ft, the supply line must
be filled using a separate pump.
9
BURNER CALIBRATION
FIRING
Set switch 1)(C) to "ON".
During the first firing, during the switch over from low
to the high fire, there is a momentary lowering of the
fuel pressure caused by the filling of the high fire noz-
zle tubing. This lowering of the fuel pressure can
cause the burner to lock-out and can sometimes give
rise to pulsations.
Once the following adjustments have been made, the
firing of the burner must generate a noise similar to the
noise generated during operation.
OPERATION
D699 The optimum calibration of the burner requires an
analysis of the flue gases at the boiler outlet and ad-
(A) (B) justments at the following points:
Burner 1 2 Stage • Low and high fire nozzles
See the information listed on page 6.
D2330
(E)
10
FINAL CHECKS
• Obscure the photocell and switch on the control devic-
es: the burner should start and then lock-out about 5 s
after opening of the low fire nozzle operation valve.
• Illuminate the photocell and switch on the control cir-
cuit: the burner should go into lock-out .
• Obscure the photocell while the burner is in high fire
operation, the following must occur in sequence: flame
extinguished within 1 s, pre-purging for about 20 s,
sparking for about 5 s, burner goes into lock-out.
• Switch off control device TL followed by control device
D707 TS while the burner is operating: the burner should stop.
MAINTENANCE
Combustion
An analysis of the flue gases is required at the boiler
outlet. Significant differences with respect to the previ-
(A) ous measurements indicate the points where more care
should be exercised during maintenance.
Pump
The pump delivery pressure must be stable at 174 PSI.
The suction must be less than 6.5 PSI.
Unusual noise must not be evident during pump opera-
tion.
If the pressure is found to be unstable or if the pump
runs noisily, the flexible hose must be detached from the
line filter and the fuel must be sucked from a tank
located near the burner. This measure permits the
cause of the anomaly to be traced to either the suction
line or the pump.
If the problem lies in the suction line, check to make
sure that the filter is clean and that air is not entering
the piping.
Filters (A)
Check the following filter boxes:
• on line 1) at pump 2) • at nozzle 3), and clean or
replace as required.
If rust or other impurities are observed inside the pump,
use a separate pump to suck out any water and other
D709 impurities that may have deposited on the bottom of the
tank.
(B)
D2365
(C) Fan
Check to make sure that no dust has accumulated
inside the fan or on its blades, as this condition will
cause a reduction in the air flow rate and produce
incomplete combustion.
Combustion head
Check to make sure that all the parts of the combustion
head are in good condition, positioned correctly, free of
all impurities, and that no deformation has been caused
by operation at high temperatures.
Nozzles
Do not clean the nozzle orifices.
Replace the nozzles every 2-3 years or whenever nec-
essary. Combustion must be checked after the nozzles
have been changed.
Photocell (cad cell) (B)
Clean the glass cover from any dust that may have
accumulated. Photocell 1) can be removed by pulling it
outward forcefully.
Flame inspection window (C)
(D) D2361
Clean the glass.
Flexible hoses
Check to make sure that the flexible hoses are still in
good condition.
Boiler
Clean the boiler as indicated in its accompanying
instructions in order to maintain all the original combus-
tion characteristics intact, especially the flue gas tem-
perature and combustion chamber pressure. Lastly,
check the condition of the flue gas stack.
TO OPEN THE BURNER (D)
- Switch off the electrical power.
- Loosen screws 1) and withdraw the cover 2).
- Unscrew screws 3).
- Fit the two extensions 4) supplied with the burner onto
the slide bars 5) (model with long blast tube, obtaina-
ble rwith the kit).
- Pull part A backward keeping it slightly raised to avoid
damaging the disk 6) on blast tube 7).
FUEL PUMP AND/OR COUPLINGS REPLACEMENT (E)
X As per fig. (E), dimension X should set as follows:
RL70 - 11/2 ”
dimension RL100 - 1 7/16 ”
(E) RL130 - 1 7/16 ”
D2854
11
BURNER OPERATION
FIRING FAILURE
If the burner does not fire, it goes into lock-out within 5
s of the opening of the low fire solenoid valve.
The flame relay pilot light will light up.
(A) D2331
12
PROCEDURE TO REFER BURNER OPERATING CONDITION IN HIGH ALTITUDE PLANTS
- Find the corrected burner capacity for the plant’s altitude in chart 1 and the corrected pressure in chart 2.
- Check in the firing rate graph of the burner (page 5), if the working point defined by the values above is within the range limits.
If not, higher burner size is needed.
Note Example
Charts are based only on altitude variation Rated capacity = 3000 MBtu/hr - Rated air pressure = 1.5”w.c.
(reference temperature = 68°F , 20°C) Real altitude = 5000 ft - Real temperature = 108°F
Δ = 108°F - 68°F (reference temp.) = 40°F (equivalent 2000 ft variation)
To get the combined correction in case of different
Proceeding as descripted above and considering a “virtual altitude” of (5000 + 2000) ft:
air temperature, a compensation of 1000 ft each
- the corrected capacity is 3847 MBtu/hr;
20°F (305 m each 11°C) is applicable. Burner RL 100 is OK
- the corrected burner air pressure is 1.92.
13
FLAME SIGNAL MEASUREMENT (A)
Min value for a good signal: 8 μA.
LAL2... Sub-base If the value is lower, it can be due to:
• Worn photocell;
• Low current;
• Bad set up of the burner.
In order to measure the current, use a microammeter of
100 μA c.c., connected to the scanner, as in the dia-
gram.
Min. detector current required at AC 230 V 8 μA
Max. detector current required without
0.8 μA
flame
Max. detector current that can occur 35 μA
LAL 2.25
t1 18 t5 optional
t2 4 t6 optional
t3 2 t7 12
t4 12 t8 4
14
BURNER FAULTS
15
Factory Wiring Diagram
RL70 - 130 three phase with burner mounted Siemens LAL control
D2428
(A) D2872
16
Field Wiring Diagram
RL 70 - 130 three phase burner with burner mounted LAL flame safeguard
Motor Connection
D3686
RL 70 RL 100 RL 130
208-230 V 460 V 575 V 208-230 V 460 V 575 V 208-230 V 460 V 575 V
F A T 10 T6 T6 T 15 T 10 T6 T 15 T 10 T 10
S AWG 14 14 14 14 14 14 14 14 14
(A) D2252
17
Factory Wiring Diagram RL 70 - 100 - 130
With remote control panel
18
(A)
LAYOUT (A) page 18
Burners RL 70 - 100 - 130
The flame safeguard is in an auxiliary panel.
See the internal electrical systems of the auxiliary panel in order to have the complete wiring diagram.
Key to Layout (A)
B2 - Photocell
F1 - Motor thermal overload
K... - Relay
M1 - Fan motor
S10 - Air pressure switch
T1 - Ignition transformer
XMB - Burner terminal strip
XMQ - Auxiliary panel terminal strip
Y20 - Safety solenoid valve
Y21 - Low fire solenoid valve
Y24 - High fire solenoid valve
19
SPARE PARTS LIST
15 20
21
65
20
9
8
7
6
5
4
3
2
1
64
0
13
3
49
4
27 63
26 12
48
N. CODE DESCRIPTION DESCRIZIONE
BURNER SERIAL NUMBER
MATRICOLA BRUCIATORE
C9714200 (3475073) *
C9514200 (3475070)
C9514201 (3475075)
C9714201 (3475073) *
C9515200 (3475270)
C9715200 (3475273) *
C9515201 (3475275)
C9715201 (3475273) *
C9716200 (3475473) *
C9716201 (3475473) *
C9516200 (3475470)
C9516201 (3475475)
1 3003948 • • • • • • • • • • • • AIR DAMPER ASSEMBLY GRUPPO SERRANDA
2 3003949 • • • • • • • • • • • • GRID PROTEZIONE
3 C5360001 3012950 • • • • • • CONTROL BOX BASE ZOCCOLO
4 C5830009 3012933 • • • • • • CONTROL BOX LAL 2.25 APPARECCHIATURA LAL 2.25
5 3013127 • • • • • • BASE PLATE MENSOLA
5 3013205 • • • • • • BASE PLATE MENSOLA
6 3003951 • • • • • • • • • • • • AIR INTAKE BOCCA D'ASPIRAZIONE
7 3003952 • • • • • • • • • • • • SOUND DAMPING FONOASSORBENTE
8 3003763 • • • • • • • • • • • • INSPECTION WINDOW VISORE
9 3013056 • • • • DRIVE COUPLING GRUPPO GIUNZIONE
9 3003954 • • • • • • • • DRIVE COUPLING GRUPPO GIUNZIONE
10 3012939 • • • • FAN GIRANTE
10 3012403 • • • • FAN GIRANTE
10 3012940 • • • • FAN GIRANTE
11 3012938 • • • • • • • • • • • • TRANSFORMER TRASFORMATORE
12 3013524 • • • • • • • • • • • • CONNECTOR RACCORDO
13 3012948 • • • • • • • • • • • • AIR PRESSURE SWITCH PRESSOSTATO ARIA
14 3003957 • • • • • • • • • • • • SUPPORT SUPPORTO
15 3012622 • • • • • • • • • • • • DRIVE DISC DISCO ELASTICO
21
16 3012935 • • OVERLOAD+CONTACTOR 208-230/460V RELE' TERMICO+CONTATTORE 208-230/460V
16 3012936 • • OVERLOAD+CONTACTOR 208-230/460V RELE' TERMICO+CONTATTORE 208-230/460V
16 3012937 • • OVERLOAD+CONTACTOR 208-230/460V RELE' TERMICO+CONTATTORE 208-230/460V
16 3012991 • • OVERLOAD+CONTACTOR 575V RELE' TERMICO+CONTATTORE 575V
16 3013124 • • OVERLOAD+CONTACTOR 575V RELE' TERMICO+CONTATTORE 575V
16 3013125 • • OVERLOAD+CONTACTOR 575V RELE' TERMICO+CONTATTORE 575V
17 3003770 • • • • • • SWITCH INTERRUTTORE
18 3007627 • • • • • • • • • • • • MEMBRAN MEMBRANA
19 3012934 • • • • • • • • • • • • COVER COFANO
20 3003825 • • • • • • • • • • • • HYDRAULIC JACK MARTINETTO
21 3003824 • • • • • • • • • • • • GRADUATE SECTOR QUADRANTE
22 3012941 • • MOTOR 208-230/460V MOTORE 208-230/460V
22 3012942 • • MOTOR 208-230/460V MOTORE 208-230/460V
22 3012943 • • MOTOR 208-230/460V MOTORE 208-230/460V
22 3013059 • • MOTOR 575V MOTORE 575V
22 3013060 • • MOTOR 575V MOTORE 575V
22 3013061 • • MOTOR 575V MOTORE 575V
23 3003969 • • • • • • • • • • • • HALF-SHELL GUSCIO
24 3003481 • • • • • • • • • • • • SCREW VITE
25 3003970 • • • • • • • • • • • • BAR PERNO
26 3012006 • • • • • • • • • • • • TUBE TUBO
27 3006784 • • • • • • • • • • • • CONNECTOR RACCORDO
28 3003971 • • • • • • • • • • • • SUPPORT SUPPORTO
29 3003814 • • • • • • • • • • • • NOZZLE HOLDER PORTASPRUZZO
30 3012959 • • • • • • • • • • • • H.T. LEAD COLLEGAMENTO
C9714200 (3475073) *
C9514200 (3475070)
C9514201 (3475075)
C9714201 (3475073) *
C9515200 (3475270)
C9715200 (3475273) *
C9515201 (3475275)
C9715201 (3475273) *
C9716200 (3475473) *
C9716201 (3475473) *
C9516200 (3475470)
C9516201 (3475475)
31 3003796 • • • • • • • • • • • • ELECTROD ELETTRODO
32 3003495 • • • • • • • • • • • • U BOLT CAVALLOTTO
33 3003974 • • • • • • • • • • • • CONTROL DEVICE GRUPPO REGOLAZIONE
34 3003975 • • • • • • • • FRONT PIECE FRONTONE
34 3003976 • • • • FRONT PIECE FRONTONE
35 3003977 • • • • SQUARE SQUADRETTA
35 3003979 • • • • SQUARE SQUADRETTA
35 3003981 • • • • SQUARE SQUADRETTA
36 3003983 • • • • • • • • SHUTTER OTTURATORE
36 3003984 • • • • SHUTTER OTTURATORE
37 3003985 • • • • END CONE IMBUTO FIAMMA
37 3003987 • • • • END CONE IMBUTO FIAMMA
37 3003989 • • • • END CONE IMBUTO FIAMMA
39 3003893 • • • • • • • • • • • • CONNECTOR RACCORDO
40 3003992 • • • • DIFFUSER DISC ELICA
40 3003993 • • • • • • • • DIFFUSER DISC ELICA
41 3003815 • • • • • • • • • • • • SUPPORT SUPPORTO
42 3003994 • • • • • • • • • • • • TUBE TUBO
43 3003995 • • • • • • • • • • • • TUBE TUBO
22
44 3006767 • • • • • • • • • • • • COIL BOBINA
45 3003996 • • • • • • • • • • • • PLUG TAPPO
46 C5360027 3006216 • • • • • • P.E. CELL FOTORESISTENZA
47 3003997 • • • • • • • • • • • • VALVE ASSEMBLY GRUPPO VALVOLE
48 3013525 • • • • • • • • • • • • CONNECTOR RACCORDO
49 3006722 • • • • • • • • • • • • CONNECTOR RACCORDO
50 3013523 • • • • • • • • • • • • PUMP POMPA
51 3007979 • • • • • • • • • • • • SEAL GUARNIZIONE
52 3007077 • • • • • • • • • • • • SEAL GUARNIZIONE
53 3006719 • • • • • • • • • • • • CONNECTOR RACCORDO
54 3005733 • • • • • • • • • • • • NEEDLE VALVE VALVOLA
55 3003823 • • • • • • • • • • • • PISTON SEAL ANELLO
56 3003820 • • • • • • • • • • • • PISTON SEAL ANELLO
57 3012000 • • • • • • • • • • • • TUBE TUBO
58 3012001 • • • • • • • • • • • • TUBE TUBO
59 3012952 • • • • • • • • • • • • SOLENOID VALVE VALVOLA
60 3012953 • • • • • • • • • • • • SOCKET PRESA
61 3012003 • • • • • • • • • • • • BAR PERNO
62 3009087 • • • • • • • • • • • • CONNECTOR RACCORDO
63 3003936 • • • • • • • • • • • • FILTER+SEAL FILTRO+GUARNIZIONE
64 3013015 • • • • • • • • • • • • LEAD COLLEGAMENTO
65 3013016 • • • • • • • • • • • • COIL BOBINA
66 3013228 • • • • • • PLUG SPINA
GAS OPERATION
OIL OPERATION
Low Fire Flame Signal: Net Stack Temp - Low Fire: High Fire:
High Fire Flame Signal: Comb. Efficiency - Low Fire: High Fire:
CONTROL SETTINGS
Operating Setpoint: Low Oil Pressure:
High Limit Setpoint: High Oil Pressure:
Low Gas Pressure: Flame Safeguard Model Number:
High Gas Pressure: Modulating Signal Type:
NOTES
23
RIELLO S.p.A.
Via degli Alpini 1
I - 37045 Legnago (VR)
Tel.: +39.0442.630111 Fax: +39.0442.630375
http:// www.rielloburners.com
Subject to modifications