0% found this document useful (0 votes)
33 views1 page

Prosurge Catalog DM S2 DM S4 SPD For Measuring and Control System

The document details the Prosurge DM S2 and DM S4 data network arresters designed for surge protection in information systems, suitable for various voltage levels and installation environments. Both models feature compact designs, compliance with safety standards, and multiple protection stages to limit transients. Key specifications include nominal voltages, discharge currents, and voltage protection levels for effective safeguarding of data networks.

Uploaded by

axlrose130695
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
33 views1 page

Prosurge Catalog DM S2 DM S4 SPD For Measuring and Control System

The document details the Prosurge DM S2 and DM S4 data network arresters designed for surge protection in information systems, suitable for various voltage levels and installation environments. Both models feature compact designs, compliance with safety standards, and multiple protection stages to limit transients. Key specifications include nominal voltages, discharge currents, and voltage protection levels for effective safeguarding of data networks.

Uploaded by

axlrose130695
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Maximum Safety in Surge Protection

Surge Protection for Information System

Prosurge DM S2 data network arrester is applied in protection for 2 single wires of balanced interfaces with measuring and controlling system, providing
coarse and fine protection, suitable for use in category location B, C (ANSI/IEEE C62.41) or directly at the upstream near the protected devices.
Technical Features
•• Data network protector in according with UL497b, IEC61643-21:2012; •• Compact size of 6.2mm to save much installation space;
•• 35mm Din-rail mounting design; •• Limit the transients with gas discharge tubes and transzorb diodes;
•• Three-stage protection circuit; •• One-pair line protection

Model DM-12/S2 DM-24/S2 DM-48/S2 DM-110/S2


Nominal Voltage Un 12V 24V 48V 110V
Rated Voltage (max. continuous dc/ac) Uc 14V/9.5V 33V/23V 55V/38.5V 170V/120V
Norminal Current IL 0.5A
Lightning Impulse Current (10/350μs) per line Iimp 1kA
Nominal Discharge Current (8/20μs) per line In 5kA
Nominal Discharge Current (8/20μs) Total In 10kA
Voltage Protection Level at In line-line ≤25V ≤50V ≤100V ≤260V
Voltage Protection Level at In line-PG ≤750V ≤750V ≤750V ≤750V
Up
Voltage Protection Level at 1kV/μs line-line ≤19V ≤45V ≤70V ≤230V
Voltage Protection Level at 1kV/μs line-PG ≤650V ≤650V ≤650V ≤650V
Bandwith line-line fG 2.5MHz 6MHz 10MHz 16MHz

6.2mm Width •• Dimension drawing •• Basic circuit diagram

Prosurge DM S4 Data network arrester provides protection for four single lines in the high-frequency bus systems or video transmissions, suitable for
use in category location B, C (ANSI/IEEE C62.41) or directly at the upstream near the protected devices.

Technical Features
•• Data network protector in according with UL497b, IEC61643-21:2012; •• Compact size of 7mm to save much installation space;
•• 35mm Din-rail mounting design; •• Limit the transients with gas discharge tubes and transzorb diodes;
•• Two-stage protection circuit; •• Two-pair line protection

Model DM-05/S4 DM-12/S4 DM-24/S4 DM-32/S4 DM-48/S4 DM-110/S4


Nominal Voltage Un 5V 12V 24V 32V 48V 110V
Rated Voltage (max. continuous dc/ac) Uc 6V/4.2V 15V/10.6V 33V/23.3V 36V/29V 54V/38V 170V/120V
Norminal Current IL 0.5A
Lightning Impulse Current (10/350μs) per line Iimp 1kA
Nominal Discharge Current (8/20μs) per line In 5kA
Nominal Discharge Current (8/20μs) Total In 20kA
Voltage Protection Level at In line-line ≤26V ≤40V ≤55V ≤75V ≤100V ≤400V
Voltage Protection Level at In line-PG ≤26V ≤40V ≤55V ≤75V ≤100V ≤400V
Up
Voltage Protection Level at 1kV/μs line-line ≤11V ≤25V ≤48V ≤65V ≤75V ≤350V
Voltage Protection Level at 1kV/μs line-PG ≤11V ≤25V ≤48V ≤65V ≤75V ≤350V
Bandwith line-line fG 100MHz

7mm Width •• Dimension drawing •• Basic circuit diagram

www.Prosurge.com 45