ADFweb HD67507-A1
ADFweb HD67507-A1
User Manual
Revision 2.200
English
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 2 of 38
Industrial Electronic Devices
Page Dear customer, we thank you for your attention and we remind you that you
INDEX 2 need to check that the following document is:
UPDATED DOCUMENTATION 2 Updated
REVISION LIST 2
Related to the product you own
WARNING 2
TRADEMARKS 2 To obtain the most recently updated document, note the “document code” that
SECURITY ALERT 3 appears at the top right-hand corner of each page of this document.
EXAMPLES OF CONNECTION 4
CONNECTION SCHEME 6 With this “Document Code” go to web page www.adfweb.com/download/ and
CHARACTERISTICS 11 search for the corresponding code on the page. Click on the proper “Document
POWER SUPPLY 12 Code” and download the updates.
FUNCTION MODES 13
LEDS (for HD67507-A1 and HD67507-B2) 14
LEDS (for HD67507-WiFi-B2) 15 REVISION LIST:
ETHERNET 16
Revision Date Author Chapter Description
WI-FI 16
1.110 03/09/2012 Fl All Software changed (v1.800)
RS232 17
2.000 14/01/2014 Fl All New hardware version
RS485 18
2.100 14/07/2014 Ff All Added chapters
RS422 19
2.200 27/12/2017 Ff All New Hardware for Wi-Fi
USE OF COMPOSITOR SW67507 20
NEW PROJECT / OPEN PROJECT 21
SOFTWARE OPTIONS 22 WARNING:
SET COMMUNICATION 23
OPERATION MODE 27 ADFweb.com reserves the right to change information in this manual about our
TRANSLATE TABLE 28 product without warning.
UPDATE VIA SERIAL 30 ADFweb.com is not responsible for any error this manual may contain.
UPDATE VIA UDP 31
MECHANICAL DIMENSIONS 33 TRADEMARKS:
ORDERING INFORMATIONS 35
ACCESSORIES 36 All trademarks mentioned in this document belong to their respective owners.
DISCLAIMER 37
OTHER REGULATIONS AND STANDARDS 37
WARRANTIES AND TECHNICAL SUPPORT 38
RETURN POLICY 38
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 3 of 38
Industrial Electronic Devices
SECURITY ALERT:
GENERAL INFORMATION
To ensure safe operation, the device must be operated according to the instructions in the manual. When using the device are required for
each individual application, legal and safety regulation. The same applies also when using accessories.
INTENDED USE
Machines and systems must be designed so the faulty conditions do not lead to a dangerous situation for the operator (i.e. independent limit
switches, mechanical interlocks, etc.).
QUALIFIED PERSONNEL
The device can be used only by qualified personnel, strictly in accordance with the specifications.
Qualified personnel are persons who are familiar with the installation, assembly, commissioning and operation of this equipment and who
have appropriate qualifications for their job.
RESIDUAL RISKS
The device is state of the art and is safe. The instrument can represent a potential hazard if they are inappropriately installed and operated
by personnel untrained. These instructions refer to residual risks with the following symbol:
This symbol indicates that non-observance of the safety instructions is danger for people to serious injury or death and / or the
possibility of damage.
CE CONFORMITY
The declaration is made by us. You can send an email to [email protected] or give us a call if you need it.
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 4 of 38
Industrial Electronic Devices
EXAMPLES OF CONNECTION:
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 5 of 38
Industrial Electronic Devices
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 6 of 38
Industrial Electronic Devices
CONNECTION SCHEME:
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 9 of 38
Industrial Electronic Devices
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 10 of 38
Industrial Electronic Devices
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 11 of 38
Industrial Electronic Devices
CHARACTERISTICS:
This HD67507-A1/B2 is able to manage a maximum of ten simultaneous connections from Ethernet side.
CONFIGURATION:
You need Compositor SW67507 software on your PC in order to perform the following:
Define the parameters of Modbus TCP line;
Define the parameters of Modbus Serial line;
Update the device.
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 12 of 38
Industrial Electronic Devices
POWER SUPPLY:
The devices can be powered at 8…24V AC and 12…35V DC. For more details see the two tables below.
VAC VDC
Vmin Vmax Vmin Vmax
8V 24V 12V 35V
HD67507-A1 HD67507-B2
HD67507-A1-422 HD67507-WiFi-B2
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 13 of 38
Industrial Electronic Devices
FUNCTION MODES:
The device has got two function modes depending on the position of the ‘Dip2 of Dip-Switch A’:
The first, with ‘Dip2 of Dip-Switch A’ at “OFF” position, is used for the normal working of the device.
The second, with ‘Dip2 of Dip-Switch A’ at “ON” position, is used for uploading the Project and/or Firmware.
For the operations to follow for the updating, see ‘UPDATE DEVICE’ section.
According to the functioning mode, the LEDs will have specific functions, see ‘LEDS’ section.
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 14 of 38
Industrial Electronic Devices
The devices has got four (five for HD67507-B2) LEDs that are used to give information of the functioning status.
The various meanings of the LEDs are described in the table below.
1: Serial Communication Blinks when Modbus frame Blinks quickly: Boot state
(green) (RS232/RS485/RS422) are received Blinks very slowly (~0.5Hz): update in progress
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 15 of 38
Industrial Electronic Devices
The devices has got five LEDs that are used to give information of the functioning status.
The various meanings of the LEDs are described in the table below.
4: Modbus TCP comm. Blinks when Modbus TCP frames (Ethernet or Blinks quickly: Boot state
(yellow) Wi-Fi) are received Blinks very slowly (~0.5Hz): update in progress
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 16 of 38
Industrial Electronic Devices
ETHERNET:
The Ethernet connection must be made using Connector5 of HD67507 with at least a Category 5E cable. The maximum length of the cable
should not exceed 100m. The cable has to conform to the T568 norms relative to connections in cat.5 up to 100 Mbps. To connect the device
to a Hub/Switch the use of a straight cable is recommended. To connect the device to a PC/PLC/other the use of a cross cable is
recommended.
The HD67507-WiFi-B2 can be configured as Wi-Fi Access Point or Wi-Fi Client. It supports DHCP functions.
The type of Wi-Fi used is the 802.11b/g/n and it supports different type of security protocol: WEP, WPA, WPA2 and none.
The antenna is integrated in the hardware, so any external antenna is ned.
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 17 of 38
Industrial Electronic Devices
RS232:
The connection from RS232 socket to a serial port (example one from a personal computer) must be made with a Null Modem cable (a serial
cable where the pins 2 and 3 are crossed).
It is recommended that the RS232 cable not exceed 15 meters.
The HD67507-A1/B2 is provided with a D-sub connector type DE-9 Male (also called DB-9). The cable must use a DE-9 Female connector.
The serial port is used for programming the device and for Modbus communication.
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 18 of 38
Industrial Electronic Devices
RS485:
To terminate the RS485 line with a 120Ω resistor, it is necessary to put dip 1 ON, like in figure.
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 19 of 38
Industrial Electronic Devices
RS422:
For terminating the RS422 line with a 220Ω resistor it is necessary to put ON dip 1 for T line and/or put ON dip 2 for R line, like in figure.
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 20 of 38
Industrial Electronic Devices
To configure the Converter, use the available software that runs with Windows called SW67507. It is downloadable on the site
www.adfweb.com and its operation is described in this document. (This manual is referenced to the last version of the software present on
our web site). The software works with MSWindows (XP, Vista, Seven, 8, 10; 32/64bit).
When launching the SW67507, the window below appears (Fig. 2).
Note:
The minimum version of the configuration software must be the 2.000.
Note:
It is necessary to have installed .Net Framework 4.
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 21 of 38
Industrial Electronic Devices
The “New Configuration” button creates the folder which contains the entire device’s configuration.
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 22 of 38
Industrial Electronic Devices
SOFTWARE OPTIONS:
By pressing the “Settings” ( ) button there is the possibility to change the language of the software and check the updatings for the
compositor.
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 23 of 38
Industrial Electronic Devices
SET COMMUNICATION:
This section defines the fundamental communication parameters of two Buses, Modbus and Modbus TCP.
By pressing the “Set Communication” button from the main window for SW67507 (Fig. 2) the window
“Set Communication” appears (Fig. 3).
In the section “Select Device” is possible to select the type of converter used:
HD67507-A1/B2 (Modbus TCP on Ethernet);
HD67507-WiFi-A1 (Modbus TCP on Wi-Fi);
HD67507-WiFi-B2 (Modbus TCP on Ethernet and Wi-Fi)
The section “Operation Mode” defines the operation of the Converter in “Routing Mode” or “NAT Mode”
(see the description at page 27).
If selected “HD67507-A1 / B2” the means of the fields for “Modbus TCP Slave” are:
In the field “IP Address” the IP address of Modbus TCP side of the converter is defined;
In the field “Subnet Mask” the SubNet Mask of Modbus TCP side of the converter is defined;
In the fields “GATEWAY” the default gateway of the net is defined. This feature can be enabled or
disabled pressing the Check Box field. This feature is used for going out of the net;
In the field “Port” the port used for Modbus TCP communication is defined;
Checking “Enable UDP Port” field it is possible to do a Broadcast request. This request must be
made at Port 64223 ($FADF) with these six byte of data: $53, $45, $41, $52, $43, $48. Each device
in response sends a total of 10 Bytes. These bytes are four for the IP and the other for the MAC
address (Example of response: 0xC0, 0xA8, 0x01, 0x2A, 0x11, 0x22, 0x33, 0x44, 0x55, 0x58. So the
IP is: 192.168.1.42; and the MAC Address: 11-22-33-44-55-58 );
If the field “Enable Special Command” is checked, it is possible to send a no-Modbus request
through the Converter. i.e. a TCP frame with the first two characters 0x55 and 0xAA is sent in the
Modbus RTU line as is. If you don’t want to send the first two bytes (0x55, 0xAA) in the RTU line it is
possible to check the field “Cancel the first two bytes”;
If the field “No TCP frame on RTU Timeout” is checked, the Converter don’t sends back the reply
on TCP (error response) if the Slave RTU interrogated has not replied.
If the field “Fast StartUp (only 100Mb/s)” is checked, the Converter take less time to go online. This command can use only if the
Converter is used in a 100Mb/s network;
The means for the fields of “Modbus Master” are the same for all the Device Type:
In the field “Serial” the type of serial port is defined;
In the field “Baud rate” the data rate of Modbus RTU is defined;
In the field “Parity” the parity of Modbus RTU is defined;
In the field “Timeout” the maximum time that the converter attends for the answer from the Modbus slave interrogated is defined;
In the field “RS485 Stop bits” the number of Stop-Bit of Modbus RTU is defined;
In the field “Communication Idle Time (ms)” the delay between the Modbus response from a slave and the following request is
defined.
If selected “HD67507-WiFi-A1” the means of the fields for “Modbus TCP Slave (Wi-Fi)” are:
In the field “IP Address” the IP address of Modbus TCP side of the converter is defined;
In the field “Subnet Mask” the SubNet Mask of Modbus TCP side of the converter is defined;
In the fields “GATEWAY” the default gateway of the net is defined. This feature can be
enabled or disabled pressing the Check Box field. This feature is used for going out of the net;
In the field “Port” the port used for Modbus TCP communication is defined;
In the field “SSID” the name of the Wi-Fi network to connect is defined;
In the field “Password” the password used to connect to the Wi-Fi network is defined;
In the field “Type” the type of security protocol used by the Wi-Fi network is defined.
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 25 of 38
Industrial Electronic Devices
The means of the fields for “Modbus TCP Slave on Wi-Fi” for Access Point configuration are:
In the field “IP Address” the IP address of Modbus TCP side of the converter is defined;
In the field “Subnet Mask” the SubNet Mask of Modbus TCP side of the converter is defined;
In the fields “GATEWAY” the default gateway of the net is defined. This feature can be
enabled or disabled pressing the Check Box field. This feature is used for going out of the net;
In the field “Port” the port used for Modbus TCP communication is defined;
In the field “SSID” the name of the Wi-Fi network to create is defined;
In the field “Password” the password used for Wi-Fi connection is defined;
In the field “Type” the type of security protocol used by the Wi-Fi network is defined;
If the field “Enable DHCP” is checked, the converter acts as DHCP Server for the Clients
connected. If the option is enabled, in the fields “DHCP First IP Address” and “DHCP
SUBNET Mask” the IP Addresses range used for DHCP is defined. In the field “Lease Time
(seconds)” the required time for the renewing of the IP Address assigned to the Client is
defined;
In the field “Max Client” the maximum number of Wi-Fi Clients accepted is defined;
In the field “Channel” the channel for Wi-Fi communication is defined.
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 26 of 38
Industrial Electronic Devices
The means of the fields for “Modbus TCP Slave on Wi-Fi” for Client configuration are:
If the field “Obtain an IP Address automatically” is checked, the converter gets the IP
Address using DHCP. Otherwise, the IP Address is defined as static;
In the field “IP Address” the IP address of Modbus TCP side of the converter is defined;
In the field “Subnet Mask” the SubNet Mask of Modbus TCP side of the converter is defined;
In the fields “GATEWAY” the default gateway of the net is defined. This feature can be
enabled or disabled pressing the Check Box field. This feature is used for going out of the net;
In the field “Port” the port used for Modbus TCP communication is defined;
In the field “SSID” the name of the Wi-Fi network to connect is defined;
In the field “Password” the password used to connect to the Wi-Fi network is defined;
In the field “Name”, the host name for the Wi-Fi node is defined (only for DHCP).
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 27 of 38
Industrial Electronic Devices
OPERATION MODE:
ROUTING:
A few characteristics of the Modbus RTU package have been modified in the standard of the Modbus TCP protocol. Two bytes of the final CRC
were eliminated (no longer necessary for the information to reach its already corrected destination). The first byte of the slave identification
was changed, leaving the one that is called PDU. A frame denominated as MBAP header with dimensions of 7 bytes was added to the head of
the PDU.
It is composed by the following:
Word transaction identifier (recopied from the slave in the response phase);
Word protocol identifier (0=Modbus protocol);
Word length (number of successive bytes);
Byte unit identifier (used for the routing operation).
By using the last byte of the MBAP header, it is possible to carry out the routing from a requested Modbus TCP toward a serial line using the
address from the slave which is specified by the byte unit identifier.
Example:
A requested Modbus TCP made in the device as the address 192.168.0.200 for the holding register address $2000, which is MBAP unit
identifier has the value of 2. It will be followed by the request on the serial for the device with the address 2 at the word $2000.
After the request is made, the RTU will respond. The master TCP will be given the same response which will be reconstructed according to
the specifications of the Modbus TCP.
If the RTU slave responds with an exception, that exception code will be transmitted again to the TCP master. If the RTU slave does not
respond in the estimated time defined by the Timeout parameter, an exception response will be given: error code $0B.
NATTING:
When NAT operation mode is used, the requested data will be processed through a table of translations of the Modbus network addresses.
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 28 of 38
Industrial Electronic Devices
TRANSLATE TABLE:
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 29 of 38
Industrial Electronic Devices
Example 1:
Note:
If the RTU slave responds with an exception, that exception code will be transmitted to the TCP Master. If the RTU slave does not
respond within the estimated time defined by the Timeout parameter, an exception response will be given on TCP side: error code $0B.
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 30 of 38
Industrial Electronic Devices
By pressing the “Update Via USB” button it is possible to load the created Configuration into the
device, and also the Firmware if is necessary, using the RS232 port.
In order to load the parameters or update the firmware in the device, follow these instructions:
Turn OFF the Device;
Connect the RS232 cable from your PC to the Converter;
Put Dip2 of ‘Dip-Switch A’ in ON position;
Select the “COM port” and press the “Connect” button;
Turn ON the device;
Check the “Device state” Led. It must blink quickly (see “LEDS” section);
Press the “Next” button;
Select which operations you want to do.
Press the “Execute update firmware” button to start the upload;
When all the operations are “OK” turn OFF the device;
Put Dip2 of ‘Dip-Switch A’ in OFF position;
Disconnect the RS232 cable;
Turn ON the device.
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 31 of 38
Industrial Electronic Devices
By pressing the “Update Device” button, it is possible to load the created Configuration into
the device; and also the Firmware, if necessary.
If you don’t know the actual IP address of the device you have to use this procedure:
Turn OFF the Device;
Put Dip2 of ‘Dip-Switch A’ in ON position;
Turn ON the device
Connect the Ethernet cable;
Insert the IP “192.168.2.205”;
Press the “Ping” button, “Device Found! must appear”;
Press the “Next” button;
Select which operations you want to do;
Press the “Execute update firmware” button to start the upload;
When all the operations are “OK” turn OFF the Device;
Put Dip2 of ‘Dip-Switch A’ in OFF position;
Turn ON the device.
If you know the actual IP address of the device, you have to use this procedure:
Turn on the Device with the Ethernet cable inserted;
Insert the actual IP of the Converter;
Press the “Ping” button, must appear “Device Found!”;
Press the “Next” button;
Select which operations you want to do;
Press the “Execute update firmware” button to start the upload;
When all the operations are “OK” the device automatically goes at Normal Mode.
Note:
When you install a new version of the software, if it is the first time it is better you do the update of the Firmware in the HD67507
device.
Note:
When you receive the device, for the first time, you also have to update the Firmware in the HD67507 device.
Warning:
If Fig. 7 appears when you try to do the Update try these points before seeking
assistance:
Check if the serial COM port selected is the correct one;
Check if the serial cable is connected between the PC and the device;
Try to repeat the operations for the updating;
If you are using a USBRS232 converter try with a native COM port or change the
converter;
Try to repeat the operations for the updating;
Try with another PC;
Try to restart the PC;
Check the LAN settings;
Check the Wi-Fi settings;
If you are using the program inside a Virtual Machine, try to use in the main Operating
System;
If you are using Windows Seven, Vista, 8 or 10 make sure that you have the
administrator privileges; Figure 7: “Protection” window
In case you have to program more than one device, using the "UDP Update", you have to cancel the ARP table every time you
connect a new device on Ethernet. For do this you have to launch the "Command Prompt" and write the command "arp -d". Pay
attention that with Windows Vista, Seven, 8 you have to launch the "Command Prompt" with Administrator Rights;
Pay attention at Firewall lock.
In the case of HD67507 you have to use the software “SW67507”: www.adfweb.com\download\filefold\SW67507.zip.
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 33 of 38
Industrial Electronic Devices
MECHANICAL DIMENSIONS:
Figure 8a: Mechanical dimensions scheme for HD67507-A1 Figure 8b: Mechanical dimensions scheme for HD67507-A1-422
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 34 of 38
Industrial Electronic Devices
Figure 8c: Mechanical dimensions scheme for HD67507-B2 Figure 8d: Mechanical dimensions scheme for HD67507-WiFi-B2-xxx
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 35 of 38
Industrial Electronic Devices
ORDERING INFORMATIONS:
Serial port:
None: RS232 + RS485 (only for HD67507-A1 and HD67507-B2)
232: RS232 (only for HD67507-WiFi-B2-xxx)
485: RS485 (only for HD67507-WiFi-B2-xxx)
422: RS422 (only for HD67507-A1)
Connectors Type
1: Removable 5mm Screw Terminal
2: Fixed 5mm Screw Terminal
Enclosure Type
A: 1M, 35mm DIN Rail mounting
B: 4M, 35mm DIN Rail mounting
Device Family
HD67507: Modbus TCP Slave / Modbus Master - Converter
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 36 of 38
Industrial Electronic Devices
ACCESSORIES:
Order Code: AC34107 - Null Modem Cable Fem/Fem D-sub 9 Pin 1,5 m
Order Code: AC34114 - Null Modem Cable Fem/Fem D-sub 9 Pin 5 m
Order Code: AC34001 - Rail DIN - Power Supply 220/240V AC 50/60Hz – 12 V AC
Order Code: AC34002 - Rail DIN - Power Supply 110V AC 50/60Hz – 12 V AC
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 37 of 38
Industrial Electronic Devices
DISCLAIMER:
All technical content within this document can be modified without notice. The content of the document is a under continual renewal.
For losses due to fire, earthquake, third party access or other accidents, or intentional or accidental abuse, misuse, or use under abnormal
conditions repairs are charged to the user. ADFweb.com S.r.l. will not be liable for accidental loss of use or inability to use this product, such
as loss of business income. ADFweb.com S.r.l. shall not be liable for consequences of improper use.
WEEE INFORMATION
Disposal of old electrical and electronic equipment (as in the European Union and other European countries with separate
collection systems).
This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish. Instead, it
should be taken to an applicable collection point for the recycling of electrical and electronic equipment. If the product is disposed
correctly, you will help prevent potential negative environmental factors and impact of human health, which could otherwise be
caused by inappropriate disposal. The recycling of materials will help to conserve natural resources. For more information about
recycling this product, please contact your local city office, your household waste disposal service or the shop where you purchased
the product.
CE MARKING
The product conforms with the essential requirements of the applicable EC directives.
ADFweb.com S.r.l.
User Manual Modbus TCP Slave / Modbus Master
Document code: MN67507_ENG Revision 2.200 Page 38 of 38
Industrial Electronic Devices
For fast and easy technical support for your ADFweb.com SRL products, consult our internet support at www.adfweb.com.
Otherwise contact us at the address [email protected]
RETURN POLICY:
If while using your product you have any problem and you wish to exchange or repair it, please do the following:
Obtain a Product Return Number (PRN) from our internet support at www.adfweb.com. Together with the request, you need to
provide detailed information about the problem.
Send the product to the address provided with the PRN, having prepaid the shipping costs (shipment costs billed to us will not be
accepted).
If the product is within the warranty of twelve months, it will be repaired or exchanged and returned within three weeks. If the product is no
longer under warranty, you will receive a repair estimate.
ADFweb.com S.r.l.
Via Strada Nuova, 17
IT-31010 Mareno di Piave
TREVISO (Italy)
Phone +39.0438.30.91.31
Fax +39.0438.49.20.99
www.adfweb.com
ADFweb.com S.r.l.