5147362-YTG-R-0323
Technical Guide
XYE/XXE/XQE Series
3 - 10 ton
60 Hertz
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
5147362-YTG-R-0323
Table of contents
Table of contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Component location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Factory-installed options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Field-installed accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
AHRI cooling rating table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
AHRI 270 outdoor sound power levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Physical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Capacity performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Airflow performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Power exhaust blower curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Typical wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Weights and dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Economizer options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Guide specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Product highlights
• Assembled in Norman, OK • State of the art microprocessor controls with specific
• ASHRAE 90.1 compliant programming for product applications
• R-410A refrigerant • Evaporator and condenser coils utilize copper tube/
aluminum fin design for proven reliability and
• Cooling only configurations available
performance.
• Scroll compressors
• TXV (thermostatic expansion valve) standard on all
• Up to 15.0 SEER and 12.5 EER on the Energy Star models
compliant energy level
• Single-stage Cooling (3 - 6 ton models)
• Up to 14.0 SEER2 and 12.0 EER2
• Alternate motor and drives
Options and accessories
• Economizers with barometric relief • Through-the-base connections for power and control
• Louvered hail guards wiring.
• Non-fused disconnect • Field-installed electric heat kits. Installation Instruction for
the electric heat kits may be found in the electric heat kits.
• Power exhaust
• IntelliSpeed™ with Premium Efficiency indoor motors to
• Smoke detectors
meet ASHRAE 90.1 requirements (6 - 10 ton XX and 6-
• Manual and motorized dampers 8.5 ton XY models)
• Hinged cabinet doors
2 Johnson Controls Ducted Systems
5147362-YTG-R-0323
Component location
Heat Pump (3 to 10 ton)
B
E
D H
Click on the letters to see a description of the features.
E B
G
C
Johnson Controls Ducted Systems 3
5147362-YTG-R-0323
Features and benefits
Standard and high efficiency available - The high efficiency
meets the requirements for Energy Star that exceeds 15 SEER,
12 EER, 14.0 SEER2 and 12.0 EER2. These efficiencies meet
or exceed all legislated minimum levels providing lower
operating costs.
B Balanced outdoor fan design makes for a quieter unit -
The outdoor condenser fans are dynamically balanced for
better performance and reliability. The direct drive fan design
mounted to the fan grill allows for quick and easy service.
A All models utilize a scroll compressor that is Where other's components might fail at extreme temperatures
environmentally friendly by utilizing R-410A refrigerant. Use of
our units are tested and rated up to 125°F ambient cooling
the scroll compressor technology means a simple internal
operation.
design, fewer moving parts, equating to a quiet, reliable, easy to
service and efficient system. Internal compressor protection is
standard and compressors include protection to prevent liquid
damage.
Total system design - A single circuit, single compressor
design is used on the 3 - 5 ton units for cost effectiveness and
reliability without compromising quality.
System protection - Liquid line filter-driers, high and low
pressure safeties are standard on each refrigerant circuit.
Suction line sensors monitor temperature to prevent possible
liquid flood back to the compressors and also protect against
loss of charge and coil frosting.
C Filter rack - Each unit comes with 2 in. filters. Units will ship
with MERV 4 throwaway filters standard; however MERV 8 and
MERV 13 filters can be easily added through the tool-free filter
access panel to meet LEED requirements. Refer to physical
data tables for filter size details.
4 Johnson Controls Ducted Systems
5147362-YTG-R-0323
with heating the high temperature limit switches are monitored
on electric heating units. The control also monitors the voltage
supplied to the unit and will protect the unit if low voltage due to
a brown out, or other electrical issue occurs.
Low ambient - An integrated low-ambient control allows units
to operate in the cooling mode down to 40°F outdoor ambient
without additional components or intervention. Optionally, the
control board can be programmed to lockout the compressors
when the outdoor air temperature is low or when free cooling is
available.
Anti-Short cycle protection - To aid compressor life, an anti-
short cycle delay is incorporated into the standard control.
Compressor reliability is further ensured by programmable
minimum run times. For testing, the anti-short cycle delay can
be temporarily overridden with the push of a button.
Fan delays - Fan on and fan off delays are fully programmable.
Furthermore, the heating and cooling fan delay times are
D Units will come with the new state of the art Smart independent of one another. All units are programmed with
Equipment™ control system. The new unit control default values based upon their configuration of cooling and/or
incorporates the best of the already proven Smart Equipment™ heating capacity.
controls and creates a more robust, intelligent control. The goal
of this control is to utilize cutting edge technology making the Nuisance trip protection and three strikes - To prevent
equipment easier to install, operate, and service. All units are nuisance calls, the control board uses a three times, you're out
Factory commissioned, configured, and run tested. philosophy. The high, low-pressure switch, anti-freeze
protection, low voltage or heating high limit must trip three times
Versatile - The Smart Equipment™ control can be configured within two hours before the unit control board will lock out the
to use with a standard thermostat (easy to connect screw associated compressor. The same safety must trip three times
terminals), a zone sensor, or can be setup to communicate with before a hard lockout will occur.
multiple BAS communication protocols to integrate with building
automation systems.
Reduce field-installed complexity - Each unit comes
equipped with factory-installed supply air, return air, and
outdoor air temperature sensors providing key temperature
readings thus reduce field-installed complexity.
On-board USB Port - The new control comes with a long list of
features including data logging, current and previous system
faults and software update capabilities using the on board USB
port and common flash drive. Energy use monitoring
capabilities allow custom tailoring to allow a system to work
more efficiently at all times and occupancy levels. Self test and
start-up reports also available from the board through the USB
port.
Embedded LCD - The board has a easy to read, built-in LCD
and easy to use navigation joystick and buttons allowing the
user to quickly navigate the menus displaying unit status, E Robust design - Each unit is designed with an embossed
options, current function, supply, return and outdoor top to increase structural support and ensure rigidity. The unit
temperatures, fault codes and other information. has a powder paint exterior finish including a industry leading
750 hour salt spray rating. All units are painted with a long
Safety monitoring - The control monitors the outdoor, supply, lasting, powder paint that stands up over the life of the unit.
and return air temperatures and the high and low pressure
switch status on the independent refrigerant circuits. On units
Johnson Controls Ducted Systems 5
5147362-YTG-R-0323
access panels for easier access, service, and maintenance.
X13 Direct drive (Standard Static Option) and belt drive
(Medium Static and High Static Options) options available on 3-
10 ton products.
Warranty - All models include a 1-year limited warranty on the
complete unit. Compressors carry a 5-year warranty.
F Full Perimeter base rail that fits on many existing curbs - Factory-installed options
This product was designed with the replacement market in
mind, which is why it will fit on many existing curbs in the field. It (Nomenclature digit position)
also takes into account the new construction market by being
Airflow options (8)
versatile and sturdy. This unit is equipped with heavier gauge
and innovatively designed base rails to prevent damage from Alternate indoor blower motor - For applications with high
transporting and rigging. static restrictions, units are offered with optional indoor motors
providing higher external static capability and/or higher airflow,
depending upon the installer's needs.
• A = Standard Static (Direct Drive for 3-5 Ton, Belt Drive
6-10 Ton)
• B = Medium Static (Belt Drive for 3-10 Ton)
• C = High Static (Belt Drive for 3-10 Ton; 3 Phase
Models Only)
VFD/VAV options (9)
IntelliSpeed™ supply fan control option (ASHRAE 90.1
compliant, section 6.4.3.10) - Units configured with the
IntelliSpeed™ Supply Fan Option will contain a VFD for
variable volume supply fan operation. This option allows the
supply fan RPM to vary based on the number of compressors
or heating stages energized. The economizer's minimum
position is also configurable.
G Coils - All condenser coils utilize copper tube with aluminum • 1 = None (Comes with standard constant volume
fin design for proven reliability and performance. controls)
• 3 = VFD IntelliSpeed™
All evaporator coils utilize copper tube with aluminum fin design
for proven reliability and performance.
Coil options (10)
E-Coat coils – Coils are coated with an epoxy polymer
coating to protect against corrosion. A 3-year warranty is
added when this option is selected.
• A = Standard indoor and outdoor coils (fin/tube design
on indoor and outdoor coils with no E-Coat coating
added).
• B = Standard indoor coil and E-Coat coil outdoor coil
(fin/tube design on indoor and outdoor coils. E-Coat
coating added to outdoor coil)
• C = E-Coat indoor coil and standard outdoor Coil (fin/
tube design on indoor and outdoor coils. E-Coat coating
added to indoor coil)
• D = E-Coat indoor coil and outdoor coil (fin/tube design
on indoor and outdoor coils. E-Coat coating added to
indoor and outdoor coil)
H Rigid mounted blower assembly - Dynamically balanced
indoor fans ensure better performance and reliability. Large
6 Johnson Controls Ducted Systems
5147362-YTG-R-0323
Controls (11) Economizer/damper (13)
Smart Equipment™ - This is the standard microprocessor Down flow economizers (with barometric relief) - All units
control with capabilities to work with a sensor or thermostat offer a variety of optional factory-installed economizers that
only. Smart Equipment™ with BAS includes communication are shipped, installed and wired with AMCA 511 Licensed
board with BACnet open-protocol system. Class 1A low leak dampers designed to exceed ASHRAE 90.1
and the International Energy Conservation Code (IECC)
FDD (fault detection and diagnostics) - Refrigerant side certification requirements by achieving leakage rates of 3 cfm/
factory-installed control system option on the commercial sq ft at 1 in. of static pressure. Each economizer goes through
equipment that constantly monitors refrigerant circuit a rigorous 60,000 cycle test. Dry bulb, single enthalpy, and
pressures, refrigerant circuit temperatures, as well as the dual enthalpy (with field-installed kit) can be selected. All
environmental temperatures and humidity via multiple sensor economizer options are fully integrated into the Smart
inputs. Provides a building owner, technician or contractor Equipment™ controls. The economizer has spring return, fully
with the operational characteristics of the RTUs entire modulating damper actuators and is capable of introducing up
refrigerant circuit to ensure the unit is functioning at its to 100% outdoor air. As the outdoor air intake dampers open,
specified performance level. Provides alarms if the unit is not the return air dampers close. The changeover from
functioning optimally. Remotely accessible via the Mobile mechanical refrigeration to economizer operation is regulated
Access Portal (MAP) gateway as well as scrolled on the UCB by the outdoor air dry bulb temperature or the outdoor air
LCD screen. enthalpy input. The dual enthalpy kit provides a second input
used to monitor the return air (field-installed). The installer
Verasys - Verasys provides a simple user experience with
needs only to assemble the outdoor air hood, attach the
configurable self-recognizing controllers without the need for
enthalpy control the hood and mount the hood to the unit
any additional tools. Verasys creates enhanced integration of
(Hood and control are provided).
HVACR equipment, zoning, and controls. Contractors are
able to offer a complete bundled solution of equipment and Dry bulb economizer - Economizer operation is enabled by
controls to serve the light commercial market. the outdoor air temperature being less than the setpoint of the
economizer module.
• A=Smart Equipment™
• B=Smart Equipment™ + BACnet MSTP, Mdbs, N2 Enthalpy economizer - The added outdoor air enthalpy
COM Card sensor enables economizer operation if the outdoor enthalpy
• C= Fault Detection Diagnostics (FDD) Refrigerant Side is less than the setpoint of the economizer logic module.
• J=Verasys Single Zone • A=None
• K=Verasys Change Over Bypass • B=Dry Bulb Economizer
• M=Verasys Single Zone W/FDD • C=Enthalpy Economizer
• N=Verasys Change Over Bypass W/FDD
Convenience outlet (14)
Convenience outlet - (powered and non-powered) - This
Sensor options (12)
option locates a 120V single-phase GFCI outlet with cover, on
• 1=None (Units come standard with factory-installed the corner of the unit housing adjacent to the compressors.
supply air, return air, and outdoor air temperature The Non-powered option requires the installer to provide the
sensors) 120V single-phase power source and wiring. Factory-installed
• 2=RA1 Smoke Detector option only.
• 3=SA Smoke Detector
• 1=None
• 4=RA1 and SA Smoke Detector
• 2=Non-powered Convenience Outlet
1. Return Air Smoke Detector Sensor Must Be Relocated in the • 3=Powered Convenience Outlet
Field. (See Unit Installation Manual.)
Johnson Controls Ducted Systems 7
5147362-YTG-R-0323
return air (field-installed). The installer needs only to
Electrical options (15) assemble the outdoor air hood, attach the enthalpy control
Disconnect switch - For units with field-installed electric heat the hood and mount the hood to the unit (Hood and
kits, two factory-installed disconnect sizes are available (60A control are provided).
or 100A non-fused disconnect). Depending on the field- • Dry bulb economizer - Economizer operation is enabled
installed heater kit selected, the factory-installed disconnect by the outdoor air temperature being less than the
may not be sufficient. Always refer to the unit nameplate or setpoint of the economizer module.
unit electrical data for the proper disconnect size. If the heater
• Single enthalpy control, accessory for economizer -
application requires a disconnect above 100 Amps, the
All field-installed economizers will come standard as a dry
factory-installed disconnect should be removed and an
bulb economizer. This kit adds an outdoor air enthalpy
appropriately sized external disconnect should be installed.
sensor which enables economizer operation if the outdoor
• 1=None enthalpy is less than the setpoint of the economizer logic
module.
• 2=Non-fused Disconnect1
• Dual enthalpy control, accessory for economizer - All
1. Verify on the unit nameplate that the disconnect is properly field-installed economizers will come standard as a dry
sized for the application. Units with field-installed electric heat bulb economizer. This kit adds an outdoor air enthalpy
may exceed the factory-installed disconnect amperage rating.
sensor and return air enthalpy sensor which enables
economizer operation if the outdoor enthalpy is less than
Cabinet options (16) the setpoint of the economizer logic module.
Louvered hail guard - This kit includes a decorative louvered • Power exhaust - This accessory installs in the unit with a
panel which installs over the outside condenser coil and down flow economizer or in the ductwork for a horizontal
prevents damage to the coil fins from hail strikes. application.
Hinged cabinet doors - The factory-installed hinged panel • Louvered hail guard - This kit includes a decorative
option will save time, money and labor while allowing easy louvered panel which installs over the outside condenser
servicing of blower components, filters and controls. With this coil and prevents damage to the coil fins from hail strikes.
option there is no longer a need to remove panels to access • Roof curbs - The roof curbs have insulated decks and
these critical sections and running the risk of losing panels or are shipped disassembled The roof curbs are available in
roof damage from loose panels and materials. Extra care was 14 in. and 24 in. heights.
taken to design a durable hinged panel with leak tight seal. • Thermostat - The units are designed to operate with 24-
• 1=None volt electronic and electro-mechanical thermostats.
• 2=Louvered Panels • Smoke detectors - The smoke detectors stop operation
of the unit by interrupting power and providing a fault
• 3=Hinged Cabinet Doors message to the control board if smoke is detected within
• 4=Hinged Cabinet Doors And Louvered Panels the air compartment. Smoke detectors are available for
both the supply and/or return air configurations.
Field-installed accessories • Hinged filter access panel for use with horizontal flow
economizer - Allows hinged access to the filter section
• Down flow economizers/horizontal economizers (with when used with a horizontal economizer.
barometric relief) - All units offer a variety of field- • Low ambient head pressure control kit - The Electronic
installed economizers that are installed and wired with Low Ambient Controller is designed to regulate condenser
AMCA 511 Licensed Class 1A low leak dampers designed head pressure at low ambient temperatures by varying the
to exceed ASHRAE 90.1 and the International Energy amount of airflow through the condenser.
Conservation Code (IECC) certification requirements by • Manual outdoor air damper - Like the motorized outdoor
achieving leakage rates of 3 cfm/sq ft at 1 in. of static air damper, each manual outdoor air damper includes a
pressure. Each economizer goes through a rigorous slide-in damper assembly with an outdoor air hood and
60,000 cycle test. Dry bulb, single enthalpy, and dual filters. Customers have a choice of dampers with ranges
enthalpy (with field-installed kit) can be selected. All of 0% to 100% or 0% to 35% outdoor air entry.
economizer options are fully integrated into the Smart
• Through the base connection - Kits are available to
Equipment™ controls. The economizer has spring return,
provide a way to route wiring to the unit through the base
fully modulating damper actuators and is capable of
of the unit and through the base or through the curb.
introducing up to 100% outdoor air. As the outdoor air
These kits provide a seal tight way to bring power to the
intake dampers open, the return air dampers close. The
unit without additional roof penetrations.
changeover from mechanical refrigeration to economizer
operation is regulated by the outdoor air dry bulb • Electric Heat (field-installed option only) - Select
temperature or the outdoor air enthalpy input. The dual heater sizes for 3-10 ton units available. Necessary
enthalpy kit provides a second input used to monitor the hardware and connectors are included with the heaters.
8 Johnson Controls Ducted Systems
5147362-YTG-R-0323
Nomenclature
3-10 Ton Model Number Nomenclature
XY E 04 A 2 A 1 A A 1 A 1 1 1 A 2
Product Category Product Generation
2 = Second Generation
XX = Pkg HP Standard Efficiency 7KLUG*HQHUDWLRQ
XY = Pkg HP High Efficiency
XQ = Pkg HP 14 SEER Standard Efficiency
Special Options
Heat Type (3) A = None
E = No Heat, Electric Heat Field Installed
Cabinet Options
Nominal Cooling Capacity 1 = None
2 = Louvered Panels Installed
3 = Hinged Cabinet Doors
04 = 3 Ton 4 = Hinged Cabinet Doors & Louvered Panels
05 = 4 Ton
06 = 5 Ton
A7 = 6 Ton w/2 Stage Cooling (XX, XY Only) Electrical Options
08 = 7.5 Ton
09 = 8.5 Ton 1 = None
12 = 10 Ton 2 = Non-fused Disconnect1
1. Verify on the unit nameplate that the
Heat Size disconnect is properly sized for the
application. Units with field installed
A = No Heat (Cooling Only) electric heat may exceed the factory
installed disconnect amperage rating.
Voltage
Convenience Outlet
1 = 208/230-1-60 (3-5 Ton Only) 1 = None
2 = 208/230-3-60 2 = Non-powered
4 = 460-3-60 3 = Powered
5 = 575-3-60
Economizer / Damper
Airflow
A = None
A = Standard Static B = Dry Bulb Economizer
B = Medium Static C = Enthalpy Economizer
C = High Static
Sensor Options
Options 1 = None (Units come standard with
factory installed supply air, return
1 = None air, and outdoor air temperature
3 = VFD IntelliSpeed (XYA7-09, XXA7-12) sensors)
2 = RA1 Smoke Detector
Note: Not all options may be available. Contact 3 = SA Smoke Detector
local distributor. 4 = RA1 & SA Smoke Detector
1. Return Air Smoke Detector Sensor
Must Be Relocated in the Field.
(See Unit Installation Manual.)
Controls
A = Smart Equipment™
B = Smart Equipment™ + BACnet MSTP, Mdbs, N2 COM Card
C= Fault Detection and Diagnostics (FDD)
J = Verasys Single Zone
K = Verasys Change Over Bypass
M = Verasys Single Zone W/FDD
N = Verasys Change Over Bypass W/FDD
Coil Options
A = Standard Indoor & Outdoor Coils
B = Standard Indoor Coil & E-Coat Outdoor Coil
C = E-Coat Indoor Coil & Standard Outdoor Coil
D = E-Coat Indoor & Outdoor Coils
Johnson Controls Ducted Systems 9
5147362-YTG-R-0323
XYE04-09, XXEA7-12, XQE04-06 Accessories
Accessory
Description Where used Voltage
Kit Number
XYE04, XYE05, XYE06, XQE04, XQE05, XQE06, All
2EE04706724 Econ, DB, Vertical Flow, Small Footprint
XXEA7
2EE04706824 Econ, DB, Vertical Flow, Large Footprint XYEA7, XYE08, XYE09, XXE08, XXE09, XXE12 All
2EE04707024 Econ, DB, Horizontal Flow, Small Footprint, Short Cabinet XYE04, XQE04 All
2EE04707124 Econ, DB, Horizontal Flow, Small Footprint, Tall Cabinet XYE05, XYE06, XQE05, XQE06, XXEA7 All
2EE04707224 Econ, DB, Horizontal Flow, Large Footprint, Short Cabinet XYEA7 All
2EE04707324 Econ, DB, Horizontal Flow, Large Footprint, Tall Cabinet XYE08, XYE09, XXE08, XXE09, XXE12 All
XYE04, XYE05, XYE06, XQE04, XQE05, XQE06, All
1FA0415 Manual Outside Air Damper 0-35%
XXEA7
1FA0416 Manual Outside Air Damper 0-35% XYEA7, XYE08, XYE09, XXE08, XXE09, XXE12 All
XYE04, XYE05, XYE06, XQE04, XQE05, XQE06, All
1FA0417 Manual Outside Air Damper 0-100%
XXEA7
1FA0418 Manual Outside Air Damper 0-100% XYEA7, XYE08, XYE09, XXE08, XXE09, XXE12 All
XYE04, XYE05, XYE06, XQE04, XQE05, XQE06, All
2MD04704224 Motorized Outside Air Damper 0-100%
XXEA7
2MD04704324 Motorized Outside Air Damper 0-100% XYEA7, XYE08, XYE09, XXE08, XXE09, XXE12 All
2EC0401 Kit, Single Enthalpy Field-installed All All
2EC0402 Kit, Dual Enthalpy Field-installed All All
Hinged Filter Access Panel For Units With A Horizontal All
1HD0401 XYE04, XQE04
Economizer
Hinged Filter Access Panel For Units With A Horizontal All
1HD0402 XYE05, XYE06, XQE05, XQE06, XXEA7
Economizer
Hinged Filter Access Panel For Units With A Horizontal All
1HD0403 XYEA7
Economizer
Hinged Filter Access Panel For Units With A Horizontal All
1HD0404 XYE08, XYE09, XXE08, XXE09, XXE12
Economizer
1HG0419 Hail Guard Kit Small Footprint, Short Cabinet XYE04, XQE04 All
1HG0420 Hail Guard Kit Small Footprint, Tall Cabinet XYE05, XYE06, XQE05, XQE06, XXEA7 All
XYE04, XYE05, XYE06, XQE04, XQE05, XQE06, All
1RC0456 Curb Rigid 14 in. Small Footprint
XXEA7
1RC0457 Curb Rigid 14 in. Large Footprint XYEA7, XYE08, XYE09, XXE08, XXE09, XXE12 All
XYE04, XYE05, XYE06, XQE04, XQE05, XQE06, All
1RC0458 Curb Rigid 24 in. Small Footprint
XXEA7
1RC0459 Curb Rigid 24 in. Large Footprint XYEA7, XYE08, XYE09, XXE08, XXE09, XXE12 All
XYE04, XYE05, XYE06, XQE04, XQE05, XQE06, 208/230-1-60
2PE04704206 Power Exhaust Vert Flow Small Footprint 208V-230V 1-ph
XXEA7
XYE04, XYE05, XYE06, XQE04, XQE05, XQE06, 208/230-3-60
2PE04704225 Power Exhaust Vert Flow Small Footprint 208V-230V 3-ph
XXEA7
XYE04, XYE05, XYE06, XQE04, XQE05, XQE06, 460-3-60
2PE04704246 Power Exhaust Vert Flow Small Footprint 460V 3-ph
XXEA7
XYE04, XYE05, XYE06, XQE04, XQE05, XQE06, 575-3-60
2PE04704258 Power Exhaust Vert Flow Small Footprint 575V 3-ph
XXEA7
2PE04704325 Power Exhaust Vert Flow Large Footprint 208V-230V 3-ph XYEA7, XYE08, XYE09, XXE08, XXE09, XXE12 208/230-3-60
2PE04704346 Power Exhaust Vert Flow Large Footprint 460V 3-ph XYEA7, XYE08, XYE09, XXE08, XXE09, XXE12 460-3-60
2PE04704358 Power Exhaust Vert Flow Large Footprint 575V 3-ph XYEA7, XYE08, XYE09, XXE08, XXE09, XXE12 575-3-60
XYE04, XYE05, XYE06, XQE04, XQE05, XQE06, 208/230-1-60
2PE04704406 Power Exhaust Horiz Flow Small Footprint 208V-230V 1-ph
XXEA7
XYE04, XYE05, XYE06, XQE04, XQE05, XQE06, 208/230-3-60
2PE04704425 Power Exhaust Horiz Flow Small Footprint 208V-230V 3-ph
XXEA7
XYE04, XYE05, XYE06, XQE04, XQE05, XQE06, 460-3-60
2PE04704446 Power Exhaust Horiz Flow Small Footprint 460V 3-ph
XXEA7
XYE04, XYE05, XYE06, XQE04, XQE05, XQE06, 575-3-60
2PE04704458 Power Exhaust Horiz Flow Small Footprint 575V 3-ph
XXEA7
2PE04704525 Power Exhaust Horiz Flow Large Footprint 208V-230V 3-ph XYEA7 XYE08, XYE09, XXE08, XXE09, XXE12 208/230-3-60
2PE04704546 Power Exhaust Horiz Flow Large Footprint 460V 3-ph XYEA7, XYE08, XYE09, XXE08, XXE09, XXE12 460-3-60
10 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XYE04-09, XXEA7-12, XQE04-06 Accessories (Continued)
Accessory
Description Where used Voltage
Kit Number
2PE04704558 Power Exhaust Horiz Flow Large Footprint 575V 3-ph XYEA7, XYE08, XYE09, XXE08, XXE09, XXE12 575-3-60
XYE04, XYE05, XYE06, XQE04, XQE05, XQE06, 208/230-3-60
2EK04510625 6.5 kW Electric Heat
XXEA7
XYE04, XYE05, XYE06, XQE04, XQE05, XQE06, 480-3-60
2EK04510646 6.0 kW Electric Heat
XXEA7
2EK04511058 9.2 kW Electric Heat XYE04, XYE05, XQE04, XQE05 575-3-60
XYE04, XYE05, XYE06, XQE04, XQE05, XQE06, 208/230-(1 or 3)-
2EK04511125 10.5 kW Electric Heat
XXEA7 60
XYE04, XYE05, XYE06, XQE04, XQE05, XQE06, 208/230-3-60
2EK04511625 16 kW Electric Heat
XXEA7
XYE04, XYE05, XYE06, XQE04, XQE05, XQE06, 480-3-60
2EK04511146 11.5 kW Electric Heat
XXEA7
XYE04, XYE05, XYE06, XQE04, XQE05, XQE06, 575-3-60
2EK04511458 13.8 kW Electric Heat
XXEA7
XYE04, XYE05, XYE06, XQE04, XQE05, XQE06, 480-3-60
2EK04511446 14 kW Electric Heat
XXEA7
2EK04510725 6.0 kW Electric Heat XYEA7 208/230-3-60
2EK04510746 6.0 kW Electric Heat XYEA7 460-3-60
2EK04511725 16 kW Electric Heat XYEA7, XYE08, XYE09, XXE08, XXE09, XXE12 208/230-3-60
2EK04511746 16.5 kW Electric Heat XYEA7, XYE08, XYE09, XXE08, XXE09, XXE12 460-3-60
2EK04511758 17 kW Electric Heat XYEA7, XYE08, XYE09, XXE08, XXE09, XXE12 575-3-60
2EK04512358 23 kW Electric Heat XYE06, XQE06, XXEA7 575-3-60
2EK04512525 24.8 kW Electric Heat XYEA7, XYE08, XYE09, XXE08, XXE09, XXE12 208/230-3-60
2EK04512646 25.5 kW Electric Heat XYEA7 460-3-60
2EK04512658 25.7 kW Electric Heat XYEA7 575-3-60
2EK04512846 27.8 kW Electric Heat XYEA7, XYE08, XYE09, XXE08, XXE09, XXE12 460-3-60
2EK04513225 32 kW Electric Heat XYEA7, XYE08, XYE09, XXE08, XXE09, XXE12 208/230-3-60
2EK04513346 33 kW Electric Heat XYEA7, XYE08, XYE09, XXE08, XXE09, XXE12 460-3-60
2EK04513458 34 kW Electric Heat XYEA7, XYE08, XYE09, XXE08, XXE09, XXE12 575-3-60
2EK04514225 42.4 kW Electric Heat XYEA7, XYE08, XYE09, XXE08, XXE09, XXE12 208/230-3-60
XYEA7, XYEA7, XYE08, XYE09, XXE08, XXE09, 460-3-60
2EK04514246 41.7 kW Electric Heat
XXE12
XYE04, XYE05, XYE06, XYEA7, XYE08, XYE09, All
2SD04701224 Supply Air Stream Smoke Detector
XXE12, XQE04, XQE05, XQE06
XYE04, XYE05, XYE06, XQE04, XQE05, XQE06, All
2SD04701124 Return Air Stream Smoke Detector
XXEA7
2SD04701424 Return Air Stream Smoke Detector XYEA7, XYE08, XYE09, XXE08, XXE09, XXE12 All
Combination Supply and Return Air Stream Smoke XYE04, XYE05, XYE06, XQE04, XQE05, XQE06, All
2SD04701324
Detector XXEA7
Combination Supply and Return Air Stream Smoke All
2SD04701624 XYEA7, XYE08, XYE09, XXE08, XXE09, XXE12
Detector
Field-installed Refrigeration-side FDD accessory for use XY04, XY05, XY06, XY07, XYA7, XQ04, XQ05, All
2FDD61
with SE Controls XQ06, XXEA7
Field-installed Refrigeration-side FDD accessory for use All
2FDD62 XY08, XY09, XX08, XX09, XX12
with SE Controls
XYE04, XYE05, XYE06, XQE04, XQE05, XQE06, All
1TB0403 Small Footprint through The Base Electrical
XXEA7
1TB0404 Large Footprint through The Base Electrical and Gas XYEA7, XYE08, XYE09, XX08, XX09, XXE12 All
XYE04, XYE05, XYE06, XQE04, XQE05, XQE06, All
1BD0409 Burglar Bar Kit
XXEA7
1BD0410 Burglar Bar Kit XYEA7, XYE08, XYE09, XX08, XX09, XXE12 All
Johnson Controls Ducted Systems 11
5147362-YTG-R-0323
AHRI cooling rating table
Nominal 17f 47f high
Net cooling Total
Cooling cooling heating heating IEER
Unit capacity power SEER SEER2 HSPF HSPF2 EER EER2
stages capacity capacity capacity IntelliSpeed
(MBH) (kW)
(ton) (MBH) (MBH)
XYE04 1 3.0 36.4 18.4 34.0 2.9 15.0 14.2 8.0 7.1 12.5 12.0 —
XYE05 1 4.0 47.0 26.0 46.0 3.8 15.0 14.4 8.2 7.3 12.5 12.0 —
XYE06 1 5.0 58.5 30.0 55.0 4.7 15.0 14.0 8.2 6.9 12.5 11.7 —
XYEA7 2 6.0 70.0 38.0 67.0 5.6 — — — — 12.0 — 16.5
XYE08 2 7.5 88.0 47.0 84.0 7.3 — — — — 12.1 — 16.0
XYE09 2 8.5 98.0 54.5 96.5 8.2 — — — — 12.0 — 15.8
XXEA7 2 6.0 66.7 35.0 64.4 6.1 — — — — 11.0 — 14.8
XXE08 2 7.5 90.0 49.0 84.0 8.4 — — — — 11.5 — 15.1
XXE09 2 8.5 102.0 57.0 94.0 8.8 — — — — 11.8 — 14.4
XXE12 2 10.0 115.0 62.0 114.0 10.3 — — — — 11.0 — 14.6
XQE04 1 3.0 35.6 18.5 34.2 2.9 14 13.4 8.1 6.7 12.1 12.0 —
XQE05 1 4.0 48.0 26.4 46.7 3.9 14.5 13.4 8.0 6.7 12.25 12.0 —
XQE06 1 5.0 57.4 30.6 54.5 4.7 14.5 13.4 8.25 6.7 12.25 11.9 —
AHRI 270 outdoor sound power levels
Sound rating1 Octave bands (Hz)
Unit (ton)
(dB-A) 63 125 250 500 1000 2000 4000 8000
XYE04 (3) 79.00 81.5 84.5 76.5 75.0 74.0 69.5 65.5 61.0
XYE05 (4) 79.00 82.0 85.0 77.5 75.5 74.0 70.0 66.5 62.0
XYE06 (5) 80.00 83.0 85.0 77.0 75.5 75.0 70.0 66.0 62.0
XYEA7 (6) 83.00 85.0 86.0 81.0 80.0 78.0 73.0 70.0 65.0
XYE08 (7.5) 88.86 93.5 82.5 83.0 84.5 85.5 81.5 75.5 70.0
XYE09 (8.5) 86.25 92.0 82.5 83.5 83.5 81.5 76.5 71.5 66.0
XXEA7 (6) 77.48 85.0 83.5 78.0 74.0 72.5 67.5 64.5 60.5
XXE08 (7.5) 83.16 86.5 85.5 81.0 80.0 79.0 74.5 70.5 66.0
XXE09 (8.5) 87.59 87.5 85.0 82.5 81.5 80.0 80.5 74.0 67.5
XXE12 (10) 86.00 97.0 87.5 85.0 83.5 81.5 78.0 75.0 71.0
XQE04 (03) 78.41 79.5 80.5 79.0 75.5 73.5 68.5 64.5 61.5
XQE05 (04) 78.41 79.5 80.5 79 75.5 73.5 68.5 64.5 61.5
XQE06 (05) 77.78 83.5 83.5 76.0 74.0 73.0 68.5 66.5 60.0
1. Rated in accordance with AHRI 270 standard.
12 Johnson Controls Ducted Systems
5147362-YTG-R-0323
Physical data
XYE04 - 09
Models
Component
XYE04 XYE05 XYE06 XYEA7 XYE08 XYE09
Nominal tonnage 3 4 5 6 7.5 8.5
AHRI cooling performance
Gross Capacity @ AHRI A point (Btu) 37,300 48,600 60,000 72,000 90,500 101,000
AHRI net capacity (MBH) 36,400 47,000 58,500 70,000 88,000 98,000
EER 12.5 12.5 12.5 12.0 12.1 12.0
SEER 15.0 15.0 15.0 — — —
SEER2 14.2 14.4 14.0 — — —
IEER IntelliSpeed — — — 16.5 16.0 15.8
CFM 1,250 1,490 1,682 2,440 2,850 3,000
System power (kW) 2.9 3.8 4.7 5.6 7.3 8.2
Refrigerant type R410A R410A R410A R410A R410A R410A
Refrigerant charge (lb-oz)
System 1 12-0 14-0 16-0 21.00 14.38 14.50
System 2 — — — — 14.25 14.63
ARI heating performance
47ºF capacity rating (MBH) 34,000 46,000 55,000 67,000 84,000 96,500
System power (kW) / COP 3.0 / 3.3 3.8 / 3.6 4.4 / 3.6 5.5 / 3.4 7.0 / 3.5 8.3 / 3.4
17ºF capacity rating (MBH) 18,400 26,000 30,000 38,000 47,000 54,500
System power (kW) / COP 2.7 / 2.0 3.3 / 2.3 3.9 / 2.3 4.7 / 2.4 5.7 / 2.4 7.1 / 2.26
HSPF (Btu/Watts-hr) 8.0 8.2 8.2 — — —
HSPF2 (Btu/Watts-hr) 7.1 7.3 6.9 — — —
Dimensions (in.)
Length 74.1 74.1 74.1 87.2 87.2 87.2
Width 48.9 48.9 48.9 61.7 61.7 61.7
Height 32.5 40.6 40.6 40.6 55.3 55.3
Operating weight (lb) 535 614 653 895 1,060 1,061
Compressor
Type Scroll Scroll Scroll 2-stage scroll Scroll Scroll
Quantity 1 1 1 1 2 2
Unit Capacity Steps (%) - - - 67/100 50/100 50/100
Outdoor coil data
Face area (sq ft) 15.1 19.4 19.4 21.0 25.6 25.6
Rows 2 2 2 3 3 3
Fins per in. 17 17 17 13 17 17
Tube diameter 0.375 0.375 0.375 0.375 0.375 0.375
Circuitry Type Split-face Split-face Split-face Intertwined Intertwined Intertwined
Refrigerant control TXV TXV TXV TXV TXV TXV
Indoor coil data
Face area (sq ft) 5.5 7.3 7.3 8.9 11.1 11.1
Rows 3 3 4 4 4 4
Fins per in. 15 15 15 15 15 15
Tube diameter 0.375 0.375 0.375 0.375 0.375 0.375
Circuitry Type Intertwined Intertwined Intertwined Intertwined Intertwined Intertwined
Refrigerant control TXV TXV TXV TXV TXV TXV
Outdoor fan data
Quantity 1 1 1 2 1 1
Fan diameter (in.) 22 22 22 22 30 30
Type Prop Prop Prop Prop Prop Prop
Drive type Direct drive Direct drive Direct drive Direct drive Direct drive Direct drive
No. speeds 1 1 1 2 1 1
Johnson Controls Ducted Systems 13
5147362-YTG-R-0323
XYE04 - 09 (Continued)
Models
Component
XYE04 XYE05 XYE06 XYEA7 XYE08 XYE09
Nominal tonnage 3 4 5 6 7.5 8.5
Number of motors 1 1 1 2 1 1
Motor HP each 1/2 1/2 1/2 1/2 1 1/2 1 1/2
RPM 1100 1100 1100 850 / 1100 1140 1140
Total CFM 3600 4000 4300 5800 / 7600 9700 9700
Belt drive indoor fan data
Airflow option B C B C B C A B C A B C A B C
Quantity 1 1 1 1 1 1
Fan diameter (in.) 10 x 10 10 x 10 11 x 10 15 x 15 15 x 15 15 x 15
Type Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal
Motor sheave 1VL34 1VL44 1VL34 1VL44 1VL34 1VL44 1VL34 1VL441VP501VL34 1VL441VP501VL34 1VL441VP50
Blower sheave AK46 AK46 AK46 AK46 AK46 AK46 AK74 AK74 AK74 AK74 AK74 AK74 AK74 AK74 AK74
Belt A39 A40 A39 A40 A37 A39 A47 A48 A48 A47 A48 A50 A47 A48 A50
Motor Max HP, single-phase 1.5 — 1.5 — 1.5 — — — —
Motor Max BHP, three-phase 2.4 2.4 2.4 2.4 2.4 2.9 2.4 2.9 3.7 2.4 2.4 3.7 2.4 2.4 3.7
RPM 1725 1725 1750 1725 1725 1725 1725 1725 1725 1725 1725 1725
Frame size 56Y 56Y 56HZ 56Y 56Y 56HZ 56Y 56Y 65HZ 56Y 56Y 65HZ
Direct drive indoor fan data
Air flow option A A A — — —
Quantity 1 1 1 — — —
Fan size (in.) 10 x 10 10 x 10 11 x 10 — — —
Type Centrifugal Centrifugal Centrifugal — — —
Motor HP each 3/4 1 1 — — —
RPM 1050 1050 1050 — — —
Filters
Quantity - size 2 - (16 x 25 x 2)1 4 - (16 x 16 x 2)1 4 - (16 x 16 x 2)1 4 - (16 x 20 x 2)1 4 - (20 x 20 x 2)1 4 - (20 x 20 x 2)1
1. 2 in. Throwaway, Standard, MERV 4 (Minimum Efficiency Reporting Value)
14 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XXEA7 - 12
Models
Component
XXEA7 XXE08 XXE09 XXE12
Nominal Tonnage 6 7.5 8.5 10
AHRI cooling performance
Gross Capacity @ AHRI A point (Btu) 68,500 93,000 105,000 119,000
AHRI net capacity (MBH) 66,700 90,000 102,000 115,000
EER 11.0 11.5 11.8 11.0
IEER IntelliSpeed 14.8 15.1 14.4 14.6
Nominal CFM 2,000 3,300 3,400 3,600
System power (kW) 6.1 8.4 8.8 10.3
Refrigerant type R410A R410A R410A R410A
Refrigerant charge (lb-oz)
System 1 15.75 12.00 14.00 12.25
System 2 - 12.00 14.00 12.25
ARI heating performance
47ºF capacity rating (MBH) 64,400 84,000 94,000 114,000
System power (kW) / COP 5.3 / 3.5 7.0 / 3.5 8.1 / 3.4 9.7 / 3.4
17ºF capacity rating (MBH) 35,000 49,000 57,000 62,000
System power (kW) / COP 4.7 / 2.3 6.4 / 2.25 7.5 / 2.25 3.0 / 2.25
HSPF (Btu/Watts-hr) — — — —
Dimensions (in.)
Length 74.1 87.2 87.2 87.2
Width 48.9 61.7 61.7 61.7
Height 40.6 48.6 48.6 48.6
Operating weight (lb) 652 976 1,025 1060
Compressors
Type 2-stage scroll Scroll Scroll Scroll
Quantity 1 2 2 2
Unit capacity steps (%) 67/100 50/100 50/100 50/100
Condenser coil data
Face area (sq ft) 19.4 25.6 25.6 25.6
Rows 2 2 3 3
Fins per in. 15 17 13 17
Tube diameter 0.375 0.375 0.375 0.375
Circuitry type Intertwined Intertwined Intertwined Intertwined
Refrigerant control TXV TXV TXV TXV
Evaporator coil data
Face area (sq ft) 7.3 11.1 11.1 11.1
Rows 4 4 4 4
Fins per in. 15 15 15 15
Tube diameter 0.375 0.375 0.375 0.375
Circuitry type Intertwined Intertwined Intertwined Intertwined
Refrigerant control TXV TXV TXV TXV
Condenser fan data
Quantity of fans 1 2 2 1
Fan diameter (in.) 22 22 22 30
Type Prop Prop Prop Prop
Drive type Direct drive Direct drive Direct drive Direct drive
Johnson Controls Ducted Systems 15
5147362-YTG-R-0323
XXEA7 - 12 (Continued)
Models
Component
XXEA7 XXE08 XXE09 XXE12
Nominal Tonnage 6 7.5 8.5 10
Number of motors 1 2 2 1
Motor HP each 1/2 1/2 1/2 1 1/2
No. speeds 1 1 1 1
RPM 1085 1085 1085 1140
Total CFM 4600 7600 7600 7700
Evap fan data belt drive
Airflow Option A B C A B C A B C A B C
Quantity 1 1 1 1
Fan diameter (in.) 11 x 10 15 x 15 15 x 15 15 x 15
Type Centrifugal Centrifugal Centrifugal Centrifugal
Motor sheave 1VL34 1VL441VP501VL34 1VL441VP501VL34 1VL441VP501VL341VP50 1VP56
Blower sheave AK51 AK51 AK51 AK74 AK74 AK74 AK74 AK74 AK74 AK79 AK79 AKBK85
Belt A39 A40 A41 A47 A48 A50 A47 A48 A50 A50 A50 BX52
Motor Max BHP, three-phase 2.4 2.9 3.7 2.4 2.4 3.7 2.4 2.4 3.7 2.4 3.7 5.25
RPM 1725 1725 1725 1725 1725 1725 1725 1725 1725 1725 1725 1725
Frame size 56Y 56Y 56HZ 56Y 56Y 65HZ 56Y 56Y 65HZ 56Y 56HZ 145TY
Filters
Quantity - Size 4 - (16 x 16 x 2)1 4 - (20 x 20 x 2)1 4 - (20 x 20 x 2)1 4 - (20 x 20 x 2)1
1. 2 in. Throwaway, Standard, MERV 4 (Minimum Efficiency Reporting Value)
16 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XQE04 - 06
Models
Component
XQE04 XQE05 XQE06
Nominal Tonnage 3 4 5
AHRI cooling performance
Gross Capacity @ AHRI A point (Btu) 36,238 49,153 58,512
AHRI net capacity (MBH) 35,600 48,000 57,000
EER 12.1 12.25 12.25
SEER 14.0 14.5 14.5
SEER2 13.4 13.4 13.4
CFM 1,238 1,550 1,640
System power (kW) 2.85 3.85 4.69
Refrigerant type R410A R410A R410A
Refrigerant charge (lb-oz)
System 1 10-12 13-4 14-8
System 2 — — —
ARI heating performance
47ºF capacity rating (MBH) 34,200 46,700 53,000
System power (kW) / COP 2.9 / 3.25 3.8 / 3.50 4.5 / 3.50
17ºF capacity rating (MBH) 18,500 26,400 29,000
System power (kW) / COP 2.6 / 2.12 3.6 / 2.00 4.0 / 2.20
HSPF (Btu/Watts-hr) 8.1 8.0 8.30
HSPF2 (Btu/Watts-hr) 6.7 6.7 6.7
Dimensions (in.)
Length 74.1 74.1 74.1
Width 48.9 48.9 48.9
Height 32.5 40.6 40.6
Operating weight (lb) 529 554 627
Compressors
Type Scroll Scroll Scroll
Quantity 1 1 1
Outdoor coil data
Face area (sq ft) 15.1 19.4 19.4
Rows 2 2 2
Fins per in. 17 17 17
Tube diameter 0.375 0.375 0.375
Circuitry type Split-face Split-face Split-face
Refrigerant control TXV TXV TXV
Indoor coil data
Face area (sq ft) 5.5 7.3 7.3
Rows 4 3 4
Fins per in. 15 15 15
Tube diameter 0.375 0.375 0.375
Circuitry type Intertwined Intertwined Intertwined
Refrigerant control TXV TXV TXV
Outdoor fan data
Quantity 1 1 1
Fan diameter (in.) 22 22 22
Type Prop Prop Prop
Drive type Direct drive Direct drive Direct drive
No. speeds 1 1 1
Number of motors 1 1 1
Motor HP each 1/2 1/2 1/2
RPM 1100 1085 1100
Johnson Controls Ducted Systems 17
5147362-YTG-R-0323
XQE04 - 06 (Continued)
Models
Component
XQE04 XQE05 XQE06
Nominal Tonnage 3 4 5
Total CFM 3600 4000 4300
Belt drive indoor fan data
Quantity 1 1 1
Fan diameter (in.) 10 x 10 10 x 10 11 x 10
Type Centrifugal Centrifugal Centrifugal
Motor sheave 1VL34 1VL44 1VL34 1VL44 1VL34 1VL44
Blower sheave AK46 AK46 AK46 AK46 AK46 AK46
Belt A39 A40 A39 A40 A37 A39
Motor HP each, single-phase 1.5 — 1.5 — 1.5 —
Motor HP each, three-phase 2.4 2.4 2.4 2.4 2.4 2.9
RPM 1725 1725 1750
Frame size 56Y 56Y 56HZ
Direct drive indoor fan data
Quantity 1 1 1
Fan size (in.) 10 x 10 10 x 10 11 x 10
Type Centrifugal Centrifugal Centrifugal
Motor HP each 3/4 1 1
RPM 1050 1050 1050
Filters
Quantity - size 2 - (16 x 25 x 2)1 4 - (16 x 16 x 2)1 4 - (16 x 16 x 2)1
1. 2 in. Throwaway, Standard, MERV 4 (Minimum Efficiency Reporting Value)
18 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XYE04-09, XQE04-06, XXEA7-12 unit limitations
Unit limitations
Size
Model Unit voltage Applied voltage Outdoor DB temp
(ton)
Min Max Max (°F)
208/230-1-60 187 252 125
208/230-3-60 187 252 125
XYE/XQE 04 (3)
460-3-60 432 504 125
575-3-60 540 630 125
208/230-1-60 187 252 125
208/230-3-60 187 252 125
XYE/XQE 05 (4)
460-3-60 432 504 125
575-3-60 540 630 125
208/230-1-60 187 252 125
208/230-3-60 187 252 125
XYE/XQE 06 (5)
460-3-60 432 504 125
575-3-60 540 630 125
208/230-3-60 187 252 125
XYE/XXE A7 (6) 460-3-60 432 504 125
575-3-60 540 630 125
208/230-3-60 187 252 125
XYE/XXE 08 (7.5) 460-3-60 432 504 125
575-3-60 540 630 125
208/230-3-60 187 252 125
XYE/XXE 09 (8.5) 460-3-60 432 504 125
575-3-60 540 630 125
208/230-3-60 187 252 125
12
XXE 460-3-60 432 504 125
(10)
575-3-60 540 630 125
Johnson Controls Ducted Systems 19
5147362-YTG-R-0323
Capacity performance
XYE04-09, XXEA7-12, XQE04-06 cooling capacities
XYE04 (3.0 ton)
Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBH) Total Total Sensible Capacity (MBH)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBH) (kW)2 (MBH) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 47.1 2.1 22.8 19.2 15.5 - - - 44.3 2.4 21.6 17.9 14.2 - - -
72 43.0 2.1 27.9 23.7 19.6 15.4 - - 40.3 2.4 26.7 22.6 18.4 14.2 - -
750
67 38.9 2.1 32.9 28.3 23.6 19.5 15.3 - 36.3 2.4 31.9 27.3 22.6 18.5 14.3 -
62 37.2 2.1 35.9 31.7 27.6 22.9 19.4 15.4 35.2 2.4 33.9 30.4 26.9 22.3 18.4 14.2
77 47.8 2.1 25.9 21.0 16.2 - - - 44.9 2.4 24.8 19.8 14.8 - - -
72 44.1 2.1 30.7 25.8 20.9 16.1 - - 41.4 2.4 29.5 24.6 19.7 14.8 - -
900 67 40.4 2.1 35.5 30.6 25.7 20.9 16.0 - 38.0 2.4 34.3 29.5 24.7 19.8 14.9 -
62 39.1 2.1 38.0 34.2 30.5 25.2 20.9 16.1 37.0 2.4 36.0 32.8 29.7 24.5 19.8 14.9
57 38.0 2.1 38.0 36.6 35.3 30.5 25.7 21.0 36.3 2.4 36.3 35.6 34.6 29.7 24.7 19.8
77 48.5 2.1 28.9 22.8 16.8 - - - 45.5 2.4 28.0 21.7 15.4 - - -
72 45.3 2.1 33.5 27.9 22.3 16.7 - - 42.6 2.4 32.3 26.7 21.1 15.4 - -
1050 67 42.0 2.1 38.2 33.0 27.8 22.3 16.7 - 39.6 2.4 36.6 31.7 26.8 21.1 15.5 -
62 41.0 2.1 40.1 36.8 33.4 27.5 22.3 16.8 38.9 2.4 38.1 35.3 32.5 26.6 21.1 15.5
57 40.1 2.1 40.1 39.4 38.8 33.4 27.9 22.4 38.3 2.4 38.3 38.3 38.1 32.5 26.8 21.1
77 49.3 2.1 32.0 24.7 17.4 - - - 46.1 2.4 31.2 23.6 16.0 - - -
72 46.4 2.1 36.4 30.0 23.7 17.4 - - 43.7 2.4 35.1 28.7 22.4 16.0 - -
1200 67 43.6 2.1 40.8 35.4 30.0 23.7 17.4 - 41.3 2.4 38.9 33.9 28.8 22.5 16.1 -
62 42.8 2.1 42.3 39.3 36.3 29.7 23.7 17.5 40.8 2.4 40.1 37.7 35.3 28.7 22.5 16.1
57 42.3 2.1 42.3 42.3 42.3 36.3 30.1 23.9 40.3 2.4 40.3 40.3 40.3 35.3 28.9 22.5
72 47.6 2.1 39.2 32.1 25.1 18.0 - - 44.8 2.4 37.9 30.8 23.7 16.6 - -
67 45.1 2.1 43.4 37.7 32.1 25.1 18.1 - 43.0 2.4 41.3 36.1 30.9 23.8 16.7 -
1350
62 44.7 2.1 44.4 41.8 39.2 32.0 25.2 18.2 42.6 2.4 42.2 40.1 38.0 30.9 23.8 16.7
57 44.4 2.1 44.4 44.4 44.4 39.3 32.3 25.3 42.3 2.4 42.3 42.3 42.3 38.1 31.0 23.9
72 48.7 2.1 42.0 34.2 26.4 18.7 - - 45.9 2.4 40.7 32.9 25.0 17.2 - -
67 46.7 2.1 46.0 40.1 34.2 26.5 18.7 - 44.6 2.4 43.6 38.3 32.9 25.1 17.3 -
1500
62 46.6 2.1 46.5 44.3 42.1 34.3 26.6 18.9 44.5 2.4 44.3 42.5 40.8 33.0 25.2 17.4
57 46.5 2.1 46.5 46.5 46.5 42.2 34.5 26.8 44.3 2.4 44.3 44.3 44.3 40.9 33.1 25.2
95°F 105°F
77 41.6 2.7 20.3 16.5 12.8 - - - 38.4 3.0 20.0 16.1 12.3 - - -
72 37.6 2.6 25.6 21.4 17.2 13.1 - - 35.1 3.0 24.7 20.5 16.4 12.2 - -
750
67 33.7 2.6 30.9 26.3 21.7 17.4 13.2 - 31.8 3.0 29.4 24.9 20.5 16.3 12.1 -
62 33.2 2.6 32.0 29.1 26.2 21.8 17.4 13.1 31.4 3.0 30.2 27.4 24.6 20.4 16.2 12.0
77 42.0 2.7 23.7 18.5 13.4 - - - 38.8 3.0 23.0 17.8 12.5 - - -
72 38.7 2.6 28.3 23.4 18.5 13.6 - - 36.0 3.0 27.1 22.3 17.4 12.6 - -
900 67 35.5 2.6 33.0 28.3 23.7 18.7 13.7 - 33.3 3.0 31.2 26.8 22.4 17.5 12.6 -
62 35.0 2.6 34.0 31.4 28.9 23.8 18.7 13.6 33.0 3.0 32.0 29.7 27.4 22.4 17.4 12.4
57 34.5 2.6 34.5 34.5 34.0 28.9 23.7 18.5 32.6 3.0 32.6 32.5 32.4 27.3 22.3 17.2
77 42.4 2.7 27.1 20.5 13.9 - - - 39.2 3.0 26.1 19.4 12.7 - - -
72 39.8 2.6 31.1 25.4 19.8 14.2 - - 37.0 3.0 29.6 24.1 18.5 13.0 - -
1050 67 37.2 2.6 35.0 30.4 25.7 20.0 14.3 - 34.8 3.0 33.1 28.7 24.4 18.7 13.0 -
62 36.8 2.6 36.0 33.8 31.6 25.8 20.0 14.2 34.6 3.0 33.7 32.0 30.2 24.4 18.6 12.8
57 36.4 2.6 36.4 36.4 36.4 31.6 25.7 19.8 34.3 3.0 34.3 34.3 34.3 30.1 24.2 18.3
77 42.8 2.6 30.5 22.5 14.5 - - - 39.6 3.0 29.2 21.0 12.9 - - -
72 40.9 2.6 33.8 27.5 21.1 14.7 - - 38.0 3.0 32.0 25.8 19.6 13.4 - -
1200 67 39.0 2.6 37.1 32.4 27.7 21.2 14.8 - 36.4 3.0 34.9 30.6 26.3 19.9 13.5 -
62 38.7 2.6 38.0 36.1 34.2 27.7 21.2 14.7 36.1 3.0 35.4 34.2 33.0 26.4 19.8 13.2
57 38.4 2.6 38.4 38.4 38.4 34.3 27.7 21.1 35.9 3.0 35.9 35.9 35.9 33.0 26.2 19.4
72 42.0 2.6 36.6 29.5 22.4 15.3 - - 38.9 3.0 34.5 27.6 20.7 13.8 - -
67 40.8 2.6 39.2 34.4 29.7 22.5 15.3 - 37.9 3.0 36.7 32.5 28.3 21.1 14.0 -
1350
62 40.5 2.6 40.0 38.5 36.9 29.7 22.5 15.3 37.7 3.0 37.2 36.5 35.9 28.5 21.1 13.6
57 40.3 2.6 40.3 40.3 40.3 36.9 29.7 22.4 37.5 3.0 37.5 37.5 37.5 35.8 28.1 20.5
72 43.1 2.6 39.3 31.5 23.7 15.8 - - 39.9 3.0 36.9 29.3 21.8 14.2 - -
67 42.5 2.6 41.3 36.5 31.6 23.8 15.9 - 39.5 3.0 38.5 34.4 30.2 22.3 14.5 -
1500
62 42.4 2.6 42.0 40.8 39.6 31.7 23.8 15.9 39.3 3.0 38.9 38.8 38.7 30.5 22.3 14.1
57 42.2 2.6 42.2 42.2 42.2 39.6 31.7 23.7 39.2 3.0 39.2 39.2 39.2 38.6 30.1 21.6
20 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XYE04 (3.0 ton) (Continued)
Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBH) Total Total Sensible Capacity (MBH)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBH) (kW)2 (MBH) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 35.1 3.4 19.6 15.7 11.8 - - - 31.9 3.7 19.3 15.3 11.2 - - -
72 32.5 3.4 23.8 19.7 15.5 11.3 - - 29.9 3.7 23.0 18.8 14.6 10.4 - -
750
67 29.8 3.3 28.0 23.6 19.2 15.1 11.0 - 27.9 3.7 26.6 22.3 18.0 14.0 10.0 -
62 29.6 3.3 28.4 25.7 22.9 18.9 15.0 11.0 27.8 3.7 26.6 24.0 21.3 17.5 13.7 9.9
77 35.5 3.4 22.4 17.0 11.6 - - - 32.2 3.7 21.7 16.2 10.7 - - -
72 33.3 3.4 26.0 21.2 16.4 11.6 - - 30.6 3.7 24.8 20.0 15.3 10.5 - -
900 67 31.1 3.4 29.5 25.3 21.1 16.3 11.4 - 29.0 3.7 27.8 23.8 19.8 15.1 10.3 -
62 30.9 3.4 29.9 27.9 25.9 21.0 16.1 11.2 28.9 3.7 27.9 26.1 24.4 19.6 14.8 10.0
57 30.7 3.4 30.3 30.3 30.3 25.7 20.8 15.9 28.8 3.7 27.9 27.9 27.9 24.2 19.4 14.5
77 35.9 3.4 25.1 18.3 11.4 - - - 32.6 3.7 24.2 17.2 10.2 - - -
72 34.2 3.4 28.1 22.7 17.2 11.8 - - 31.3 3.7 26.6 21.3 16.0 10.6 - -
1050 67 32.4 3.4 31.1 27.1 23.1 17.4 11.8 - 30.0 3.7 29.1 25.4 21.7 16.2 10.6 -
62 32.3 3.4 31.4 30.1 28.9 23.1 17.3 11.5 30.0 3.7 29.1 28.3 27.5 21.7 15.9 10.1
57 32.1 3.4 31.7 31.7 31.7 28.7 22.7 16.8 29.9 3.7 29.1 29.1 29.1 27.3 21.3 15.2
77 36.3 3.4 27.9 19.6 11.3 - - - 33.0 3.7 26.6 18.1 9.6 - - -
72 35.0 3.4 30.2 24.2 18.1 12.1 - - 32.1 3.7 28.4 22.5 16.6 10.7 - -
1200 67 33.7 3.4 32.6 28.8 25.0 18.6 12.2 - 31.1 3.7 30.3 27.0 23.6 17.3 10.9 -
62 33.6 3.4 32.9 32.4 31.9 25.1 18.4 11.7 31.1 3.7 30.3 30.3 30.3 23.9 17.0 10.2
57 33.5 3.4 33.2 33.2 33.2 31.7 24.7 17.6 31.0 3.7 30.3 30.3 30.3 30.3 23.2 15.9
72 35.9 3.4 32.4 25.7 19.0 12.3 - - 32.8 3.8 30.3 23.8 17.3 10.8 - -
67 35.1 3.4 34.1 30.5 26.9 19.8 12.6 - 32.2 3.8 31.6 28.6 25.5 18.4 11.3 -
1350
62 34.9 3.4 34.4 34.4 34.4 27.2 19.6 12.0 32.2 3.8 31.6 31.6 31.6 26.0 18.2 10.4
57 34.8 3.4 34.6 34.6 34.6 34.6 26.6 18.5 32.1 3.7 31.6 31.6 31.6 31.6 25.1 16.6
72 36.7 3.4 34.5 27.2 19.9 12.6 - - 33.5 3.8 32.1 25.0 18.0 10.9 - -
67 36.4 3.4 35.6 32.2 28.8 20.9 13.0 - 33.3 3.8 32.8 30.1 27.4 19.5 11.6 -
1500
62 36.3 3.4 35.9 35.9 35.9 29.3 20.8 12.3 33.2 3.8 32.8 32.8 32.8 28.1 19.3 10.5
57 36.2 3.4 36.1 36.1 36.1 36.1 28.5 19.4 33.2 3.7 32.8 32.8 32.8 32.8 27.0 17.3
1. These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat (MBH = 3.415 x kW). Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Ducted Systems 21
5147362-YTG-R-0323
XYE05 (4.0 ton)
Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBH) Total Total Sensible Capacity (MBH)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBH) (kW)2 (MBH) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 64.4 2.8 32.4 27.2 22.0 - - - 60.0 3.1 30.3 25.2 20.1 - - -
72 58.1 2.8 38.1 32.5 27.0 21.4 - - 54.2 3.1 36.3 30.8 25.2 19.7 - -
1000
67 51.8 2.8 43.8 37.9 31.9 26.3 20.9 - 48.5 3.1 42.2 36.3 30.4 24.8 19.4 -
62 48.4 2.8 48.4 42.6 36.9 30.3 25.9 20.5 46.4 3.1 46.0 40.8 35.6 29.5 24.5 19.0
77 64.4 2.8 35.0 28.4 21.8 - - - 60.3 3.1 33.7 26.9 20.1 - - -
72 58.9 2.8 41.0 34.6 28.1 21.7 - - 55.3 3.1 39.5 33.0 26.6 20.1 - -
1200 67 53.5 2.8 47.1 40.8 34.5 27.9 21.5 - 50.2 3.1 45.2 39.1 33.0 26.4 20.0 -
62 50.6 2.8 50.6 45.7 40.9 33.5 27.8 21.2 48.5 3.1 48.2 43.8 39.5 32.5 26.3 19.7
57 47.6 2.8 50.6 47.6 47.3 40.7 34.0 27.4 46.7 3.1 58.2 46.7 45.9 39.3 32.6 26.0
77 64.3 2.8 37.6 29.5 21.5 - - - 60.6 3.2 37.1 28.6 20.1 - - -
72 59.8 2.8 44.0 36.6 29.3 22.0 - - 56.3 3.1 42.6 35.3 27.9 20.5 - -
1400 67 55.2 2.8 50.4 43.8 37.1 29.6 22.1 - 51.9 3.1 48.2 41.9 35.6 28.1 20.6 -
62 52.8 2.8 52.8 48.9 45.0 36.7 29.6 22.0 50.6 3.1 50.4 46.9 43.4 35.4 28.1 20.4
57 50.4 2.8 52.8 50.4 50.2 45.0 37.1 29.3 49.2 3.1 50.4 49.2 49.2 43.3 35.6 27.8
77 64.3 2.8 40.2 30.7 21.2 - - - 60.9 3.2 40.5 30.4 20.2 - - -
72 60.6 2.8 46.9 38.7 30.5 22.2 - - 57.3 3.2 45.8 37.5 29.2 20.9 - -
1600 67 56.9 2.8 53.6 46.7 39.8 31.2 22.8 - 53.7 3.1 51.1 44.7 38.2 29.7 21.2 -
62 55.0 2.8 55.0 52.0 49.0 39.8 31.5 22.7 52.7 3.1 52.5 49.9 47.3 38.4 29.9 21.2
57 53.1 2.8 55.0 53.1 53.1 49.3 40.2 31.2 51.7 3.1 52.5 51.7 51.7 47.4 38.5 29.6
72 61.4 2.8 49.8 40.7 31.6 22.5 - - 58.3 3.2 49.0 39.8 30.5 21.3 - -
67 58.6 2.8 56.9 49.6 42.4 32.9 23.4 - 55.4 3.1 54.1 47.5 40.9 31.3 21.9 -
1800
62 57.2 2.8 57.2 55.1 53.1 43.0 33.4 23.5 54.8 3.1 54.7 52.9 51.2 41.3 31.6 21.9
57 55.8 2.8 57.2 55.8 55.8 53.6 43.4 33.1 54.2 3.1 54.7 54.2 54.2 51.5 41.4 31.4
72 62.2 2.8 52.8 42.8 32.8 22.8 - - 59.3 3.2 52.2 42.0 31.9 21.7 - -
67 60.3 2.8 58.5 52.6 45.0 34.5 24.0 - 57.1 3.2 57.0 50.3 43.5 33.0 22.5 -
2000
62 59.4 2.8 58.5 58.3 57.2 46.2 35.2 24.3 56.9 3.2 57.0 56.0 55.1 44.2 33.4 22.6
57 58.5 2.8 58.5 58.5 58.5 57.9 46.5 35.0 56.7 3.2 57.0 56.7 56.7 55.5 44.4 33.2
95°F 105°F
77 55.5 3.4 28.3 23.2 18.1 - - - 51.2 4.0 27.3 22.1 16.9 - - -
72 50.4 3.5 34.5 29.0 23.5 18.0 - - 46.7 4.0 33.2 27.6 22.1 16.6 - -
1000
67 45.2 3.5 40.7 34.8 28.9 23.4 17.8 - 42.1 4.0 39.0 33.2 27.4 21.9 16.4 -
62 44.4 3.5 43.6 39.0 34.3 28.7 23.1 17.5 41.6 3.9 41.1 36.9 32.7 27.1 21.6 16.1
77 56.2 3.5 32.5 25.5 18.5 - - - 51.7 4.0 31.3 24.2 17.0 - - -
72 51.6 3.5 37.9 31.4 25.0 18.5 - - 47.7 4.0 36.3 29.9 23.5 17.0 - -
1200 67 47.0 3.5 43.3 37.4 31.5 25.0 18.4 - 43.7 4.0 41.3 35.6 29.9 23.4 16.9 -
62 46.4 3.5 45.8 41.9 38.0 31.4 24.8 18.2 43.4 3.9 43.0 39.7 36.4 29.8 23.2 16.7
57 45.8 3.5 45.8 45.8 44.6 37.9 31.2 24.5 43.1 3.9 43.1 43.1 42.8 36.2 29.5 22.9
77 56.8 3.5 36.7 27.8 18.8 - - - 52.3 4.0 35.4 26.2 17.1 - - -
72 52.8 3.5 41.3 33.9 26.5 19.0 - - 48.8 4.0 39.4 32.1 24.8 17.4 - -
1400 67 48.7 3.5 45.9 40.0 34.1 26.6 19.1 - 45.4 4.0 43.5 38.0 32.4 24.9 17.5 -
62 48.4 3.5 47.9 44.8 41.8 34.1 26.5 18.9 45.2 4.0 44.9 42.5 40.1 32.5 24.9 17.3
57 48.1 3.5 48.1 48.1 48.1 41.7 34.0 26.3 45.0 3.9 45.0 45.0 45.0 40.0 32.2 24.5
77 57.5 3.5 40.9 30.1 19.2 - - - 52.8 4.0 39.4 28.3 17.3 - - -
72 54.0 3.5 44.8 36.4 28.0 19.6 - - 49.9 4.0 42.6 34.3 26.1 17.8 - -
1600 67 50.4 3.5 48.6 42.7 36.7 28.2 19.7 - 47.0 4.0 45.8 40.3 34.9 26.5 18.0 -
62 50.4 3.5 50.1 47.8 45.5 36.9 28.2 19.6 47.0 4.0 46.8 45.2 43.7 35.1 26.5 17.8
57 50.4 3.5 50.4 50.4 50.4 45.5 36.8 28.0 46.9 4.0 46.9 46.9 46.9 43.8 34.9 26.1
72 55.1 3.5 48.2 38.8 29.5 20.1 - - 51.0 4.0 45.7 36.6 27.4 18.2 - -
67 52.7 3.5 52.7 45.3 39.3 29.8 20.3 - 48.8 4.0 48.0 42.7 37.4 28.0 18.6 -
1800
62 52.7 3.5 52.7 50.7 49.2 39.6 29.9 20.3 48.8 4.0 48.6 48.0 47.4 37.8 28.1 18.4
57 52.7 3.5 52.7 52.7 52.7 49.3 39.5 29.7 48.8 4.0 48.8 48.8 48.8 47.5 37.6 27.7
72 56.3 3.5 51.6 41.3 30.9 20.6 - - 52.0 4.0 48.9 38.8 28.7 18.6 - -
67 55.0 3.5 55.0 47.9 42.0 31.5 21.0 - 50.8 4.0 50.3 45.1 39.9 29.5 19.1 -
2000
62 55.0 3.5 55.0 53.7 53.0 42.3 31.6 21.0 50.8 4.0 50.5 50.5 50.5 40.4 29.7 19.0
57 55.0 3.5 55.0 55.0 55.0 53.1 42.3 31.5 50.8 4.0 50.8 50.8 50.8 50.8 40.3 29.3
22 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XYE05 (4.0 ton) (Continued)
Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBH) Total Total Sensible Capacity (MBH)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBH) (kW)2 (MBH) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 46.9 4.5 26.2 20.9 15.7 - - - 42.6 5.0 25.2 19.8 14.4 - - -
72 42.9 4.4 31.8 26.3 20.8 15.3 - - 39.2 4.9 30.5 25.0 19.4 13.9 - -
1000
67 38.9 4.4 37.4 31.7 25.9 20.4 14.9 - 36.1 4.9 35.8 30.1 24.4 19.0 13.5 -
62 38.9 4.4 38.6 34.8 31.1 25.6 20.1 14.6 36.1 4.9 36.1 32.8 29.4 24.0 18.6 13.2
77 47.3 4.5 30.1 22.8 15.5 - - - 42.8 5.0 28.9 21.5 14.1 - - -
72 43.9 4.5 34.7 28.3 21.9 15.5 - - 40.0 4.9 33.1 26.7 20.4 14.1 - -
1200 67 40.5 4.4 39.3 33.8 28.3 21.9 15.4 - 37.6 4.9 37.2 32.0 26.7 20.3 13.9 -
62 40.4 4.4 40.2 37.5 34.7 28.2 21.7 15.1 37.6 4.9 37.4 35.2 33.0 26.6 20.1 13.6
57 40.3 4.4 40.3 40.3 40.3 34.5 27.9 21.3 37.6 4.9 37.6 37.6 37.6 32.8 26.2 19.7
77 47.7 4.5 34.0 24.7 15.4 - - - 43.1 5.0 32.6 23.2 13.7 - - -
72 44.8 4.5 37.6 30.3 23.1 15.8 - - 40.9 4.9 35.7 28.5 21.4 14.2 - -
1400 67 42.0 4.4 41.1 35.9 30.7 23.3 15.9 - 38.8 4.9 38.7 33.8 29.0 21.7 14.3 -
62 42.0 4.4 41.8 40.1 38.3 30.8 23.2 15.6 38.8 4.9 38.8 37.7 36.6 29.1 21.5 14.0
57 41.9 4.4 41.9 41.9 41.9 38.2 30.5 22.8 38.8 4.9 38.8 38.8 38.8 36.5 28.8 21.0
77 48.0 4.5 37.9 26.6 15.3 - - - 43.3 5.0 36.4 24.9 13.4 - - -
72 45.8 4.5 40.4 32.3 24.2 16.1 - - 41.7 5.0 38.3 30.3 22.3 14.4 - -
1600 67 43.6 4.5 43.0 38.0 33.1 24.7 16.4 - 40.2 4.9 40.2 35.7 31.3 23.0 14.7 -
62 43.5 4.4 43.4 42.7 42.0 33.4 24.7 16.1 40.1 4.9 40.2 40.1 40.1 31.6 23.0 14.4
57 43.5 4.4 43.5 43.5 43.5 42.0 33.1 24.2 40.0 4.9 40.2 40.1 40.1 40.0 31.3 22.3
72 46.8 4.5 43.3 34.3 25.3 16.4 - - 42.6 5.0 40.8 32.1 23.3 14.5 - -
67 45.1 4.5 44.8 40.2 35.5 26.2 16.8 - 41.6 4.9 41.6 37.6 33.6 24.3 15.1 -
1800
62 45.1 4.4 45.0 45.0 45.0 36.0 26.3 16.6 41.4 4.9 41.6 41.4 41.4 34.2 24.5 14.8
57 45.0 4.4 45.0 45.0 45.0 45.0 35.7 25.7 41.2 4.9 41.6 41.4 41.4 41.2 33.8 23.7
72 47.7 4.5 46.2 36.3 26.5 16.7 - - 43.4 5.0 43.4 33.8 24.3 14.7 - -
67 46.7 4.5 46.6 42.3 37.9 27.6 17.3 - 43.1 5.0 43.4 39.5 35.9 25.7 15.5 -
2000
62 46.6 4.5 46.6 46.6 46.6 38.6 27.8 17.1 42.7 4.9 43.4 42.7 42.7 36.7 25.9 15.2
57 46.6 4.5 46.6 46.6 46.6 46.6 38.3 27.2 42.4 4.9 43.4 42.7 42.7 42.4 36.3 25.0
1. These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat (MBH = 3.415 x kW). Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Ducted Systems 23
5147362-YTG-R-0323
XYE06 (5.0 ton)
Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBH) Total Total Sensible Capacity (MBH)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBH) (kW)2 (MBH) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 78.6 3.5 37.8 32.2 26.6 - - - 74.1 4.0 36.2 29.9 23.6 - - -
72 71.8 3.4 46.7 40.1 33.5 26.8 - - 67.6 3.9 45.3 38.2 31.1 24.0 - -
1250
67 64.9 3.4 55.7 48.0 40.4 33.4 26.8 - 61.1 3.8 54.5 46.6 38.6 31.4 24.3 -
62 62.4 3.4 54.9 51.1 47.3 37.4 33.4 26.4 59.3 3.8 55.2 50.6 46.1 37.4 31.6 24.4
77 79.7 3.5 43.5 35.2 26.9 - - - 74.9 4.0 42.0 33.0 24.0 - - -
72 73.8 3.5 51.6 43.5 35.4 27.2 - - 69.2 3.9 49.8 41.4 33.0 24.5 - -
1500 67 67.9 3.4 59.7 51.8 43.8 35.4 27.3 - 63.6 3.8 57.6 49.8 42.0 33.4 24.9 -
62 65.8 3.4 59.7 56.0 52.3 41.6 35.6 27.2 62.0 3.8 58.5 54.7 51.0 41.2 33.7 25.1
57 63.7 3.4 59.7 59.7 59.7 52.3 43.8 35.3 60.5 3.8 59.3 59.3 59.3 51.3 42.5 33.8
77 80.7 3.5 49.3 38.2 27.2 - - - 75.7 4.0 47.8 36.0 24.3 - - -
72 75.8 3.5 56.5 46.9 37.2 27.6 - - 70.9 3.9 54.3 44.6 34.8 25.1 - -
1750 67 70.8 3.4 63.8 55.5 47.3 37.4 27.9 - 66.0 3.8 60.8 53.1 45.3 35.4 25.6 -
62 69.2 3.4 64.5 60.9 57.3 45.8 37.7 28.0 64.7 3.8 61.8 58.8 55.9 45.0 35.8 25.8
57 67.5 3.4 65.2 65.2 65.2 57.5 47.6 37.8 63.3 3.8 62.7 62.7 62.7 56.2 46.1 35.9
77 81.7 3.5 55.0 41.3 27.5 - - - 76.5 4.0 53.6 39.1 24.6 - - -
72 77.8 3.5 61.4 50.3 39.1 28.0 - - 72.5 3.9 58.8 47.7 36.6 25.6 - -
2000 67 73.8 3.4 67.9 59.3 50.7 39.5 28.4 - 68.5 3.9 64.0 56.3 48.7 37.4 26.2 -
62 72.5 3.4 69.3 65.8 62.3 50.0 39.9 28.8 67.3 3.9 65.1 62.9 60.8 48.8 37.9 26.5
57 71.3 3.4 70.7 70.7 70.7 62.7 51.5 40.3 66.1 3.8 66.1 66.1 66.1 61.2 49.6 38.0
72 79.7 3.5 66.3 53.7 41.0 28.4 - - 74.2 3.9 63.3 50.9 38.5 26.1 - -
67 76.7 3.5 71.9 63.0 54.1 41.5 28.9 - 71.0 3.9 67.1 59.6 52.1 39.4 26.8 -
2250
62 75.9 3.4 74.1 70.7 67.3 54.1 42.1 29.5 70.0 3.9 68.4 67.0 65.6 52.5 40.0 27.2
57 75.1 3.4 75.1 75.1 75.1 67.9 55.3 42.8 69.0 3.9 69.0 69.0 69.0 66.2 53.2 40.1
72 81.7 3.5 71.2 57.0 42.9 28.7 - - 75.8 3.9 67.7 54.0 40.3 26.6 - -
67 79.7 3.5 76.0 66.8 57.6 43.5 29.4 - 73.4 3.9 70.3 62.8 55.4 41.4 27.5 -
2500
62 79.3 3.5 78.9 75.6 72.3 58.3 44.3 30.3 72.6 3.9 71.7 71.1 70.5 56.3 42.1 27.9
57 78.9 3.5 78.9 78.9 78.9 73.1 59.2 45.3 71.8 3.9 71.8 71.8 71.8 71.2 56.7 42.2
95°F 105°F
77 69.5 4.5 34.5 27.6 20.7 - - - 63.2 5.1 34.2 27.1 20.0 - - -
72 63.4 4.4 43.9 36.4 28.8 21.2 - - 58.3 5.0 42.1 34.7 27.4 20.0 - -
1250
67 57.2 4.2 53.3 45.1 36.9 29.3 21.8 - 53.4 4.9 50.0 42.4 34.8 27.5 20.2 -
62 56.3 4.2 55.4 50.2 45.0 37.4 29.9 22.4 52.7 4.8 51.9 47.0 42.1 34.9 27.7 20.5
77 70.1 4.5 40.4 30.7 21.0 - - - 64.1 5.0 39.5 29.7 19.8 - - -
72 64.7 4.4 48.0 39.3 30.6 21.9 - - 59.8 5.0 45.9 37.4 28.9 20.4 - -
1500 67 59.2 4.2 55.6 47.9 40.2 31.3 22.5 - 55.5 4.9 52.3 45.1 38.0 29.4 20.8 -
62 58.2 4.2 57.2 53.5 49.7 40.8 31.9 23.0 54.8 4.8 53.9 50.5 47.1 38.4 29.7 20.9
57 57.2 4.2 57.2 57.2 57.2 50.3 41.3 32.2 54.0 4.8 54.0 54.0 54.0 47.4 38.5 29.7
77 70.7 4.4 46.3 33.8 21.3 - - - 65.0 5.0 44.9 32.3 19.7 - - -
72 66.0 4.4 52.1 42.2 32.4 22.5 - - 61.3 5.0 49.7 40.1 30.5 20.9 - -
1750 67 61.2 4.3 57.8 50.6 43.4 33.4 23.3 - 57.6 4.9 54.5 47.9 41.3 31.4 21.4 -
62 60.2 4.2 59.0 56.8 54.5 44.2 33.9 23.6 56.8 4.9 55.9 54.0 52.1 41.8 31.6 21.3
57 59.1 4.2 59.1 59.1 59.1 55.0 44.5 34.0 56.0 4.8 56.0 56.0 56.0 52.3 41.7 31.2
77 71.3 4.4 52.2 36.9 21.6 - - - 65.8 5.0 50.2 34.9 19.5 - - -
72 67.3 4.3 56.1 45.1 34.2 23.2 - - 62.7 5.0 53.5 42.8 32.0 21.3 - -
2000 67 63.2 4.3 60.0 53.4 46.7 35.4 24.0 - 59.7 4.9 56.8 50.7 44.5 33.3 22.0 -
62 62.1 4.3 60.9 60.0 59.2 47.6 35.9 24.2 58.9 4.9 57.8 57.5 57.1 45.3 33.5 21.7
57 61.0 4.3 61.0 61.0 61.0 59.8 47.7 35.7 58.1 4.9 58.1 58.1 58.1 57.3 45.0 32.7
72 68.6 4.3 60.2 48.1 35.9 23.8 - - 64.2 5.0 57.3 45.4 33.6 21.7 - -
67 65.2 4.3 62.3 56.1 50.0 37.4 24.8 - 61.7 4.9 59.0 53.4 47.8 35.2 22.7 -
2250
62 64.1 4.3 62.7 62.7 62.7 50.9 37.9 24.8 60.9 4.9 59.8 59.8 59.8 48.7 35.4 22.1
57 62.9 4.3 62.9 62.9 62.9 62.9 51.0 37.5 60.1 4.9 60.1 60.1 60.1 60.1 48.2 34.2
72 69.9 4.3 64.3 51.0 37.7 24.5 - - 65.7 4.9 61.1 48.1 35.1 22.2 - -
67 67.2 4.3 64.5 58.9 53.2 39.4 25.5 - 63.8 4.9 61.3 56.2 51.1 37.2 23.3 -
2500
62 66.0 4.3 64.5 64.5 64.5 54.3 39.9 25.4 63.0 4.9 61.8 61.8 61.8 52.2 37.4 22.6
57 64.8 4.3 64.5 64.5 64.5 64.5 54.2 39.2 62.1 4.9 62.1 62.1 62.1 62.1 51.5 35.7
24 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XYE06 (5.0 ton) (Continued)
Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBH) Total Total Sensible Capacity (MBH)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBH) (kW)2 (MBH) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 56.9 5.7 33.9 26.6 19.3 - - - 50.6 6.2 33.6 26.1 18.6 - - -
72 53.3 5.6 40.3 33.1 26.0 18.8 - - 48.2 6.2 38.5 31.5 24.6 17.6 - -
1250
67 49.7 5.5 46.7 39.7 32.6 25.6 18.6 - 45.9 6.1 43.4 37.0 30.5 23.7 17.0 -
62 49.2 5.4 48.5 43.9 39.3 32.4 25.6 18.7 45.7 6.1 45.0 40.7 36.4 29.9 23.4 16.9
77 58.0 5.6 38.7 28.7 18.7 - - - 52.0 6.2 37.8 27.6 17.5 - - -
72 54.9 5.6 43.8 35.5 27.3 19.0 - - 50.0 6.2 41.7 33.7 25.6 17.6 - -
1500 67 51.8 5.5 49.0 42.4 35.9 27.5 19.1 - 48.1 6.1 45.7 39.7 33.7 25.5 17.3 -
62 51.3 5.5 50.6 47.5 44.5 35.9 27.4 18.9 47.9 6.1 47.3 44.6 41.9 33.5 25.2 16.8
57 50.9 5.4 50.9 50.9 50.9 44.4 35.8 27.1 47.7 6.1 47.7 47.7 47.7 41.5 33.0 24.5
77 59.2 5.6 43.4 30.7 18.0 - - - 53.4 6.2 42.0 29.2 16.4 - - -
72 56.6 5.6 47.3 38.0 28.6 19.2 - - 51.8 6.2 45.0 35.8 26.7 17.6 - -
1750 67 54.0 5.5 51.2 45.2 39.1 29.3 19.6 - 50.3 6.1 47.9 42.5 37.0 27.3 17.7 -
62 53.5 5.5 52.7 51.2 49.7 39.5 29.3 19.1 50.2 6.1 49.5 48.4 47.3 37.1 27.0 16.8
57 53.0 5.5 53.0 53.0 53.0 49.6 39.0 28.4 50.0 6.1 50.0 50.0 50.0 46.9 36.2 25.6
77 60.3 5.6 48.2 32.8 17.4 - - - 54.8 6.2 46.2 30.7 15.3 - - -
72 58.2 5.6 50.8 40.4 29.9 19.4 - - 53.7 6.2 48.2 38.0 27.8 17.6 - -
2000 67 56.1 5.5 53.5 47.9 42.4 31.2 20.0 - 52.5 6.1 50.2 45.2 40.2 29.1 18.1 -
62 55.6 5.5 54.8 54.8 54.8 43.0 31.1 19.3 52.4 6.1 51.8 51.8 51.8 40.7 28.8 16.8
57 55.2 5.5 55.2 55.2 55.2 54.8 42.2 29.7 52.3 6.1 52.3 52.3 52.3 52.3 39.5 26.6
72 59.8 5.6 54.4 42.8 31.2 19.6 - - 55.5 6.2 51.4 40.1 28.8 17.6 - -
67 58.3 5.5 55.7 50.7 45.6 33.1 20.5 - 54.8 6.2 52.5 48.0 43.5 31.0 18.4 -
2250
62 57.8 5.5 57.0 57.0 57.0 46.5 33.0 19.5 54.7 6.1 54.1 54.1 54.1 44.4 30.6 16.8
57 57.3 5.5 57.3 57.3 57.3 57.3 45.5 31.0 54.5 6.1 54.5 54.5 54.5 54.5 42.7 27.7
72 61.5 5.6 57.9 45.2 32.5 19.8 - - 57.3 6.2 54.7 42.3 29.9 17.5 - -
67 60.4 5.6 58.0 53.4 48.9 35.0 21.0 - 57.0 6.2 54.7 50.7 46.7 32.8 18.8 -
2500
62 59.9 5.6 59.1 59.1 59.1 50.1 34.9 19.7 56.9 6.2 56.3 56.3 56.3 48.0 32.4 16.8
57 59.5 5.6 59.5 59.5 59.5 59.5 48.7 32.2 56.8 6.2 56.8 56.8 56.8 56.8 46.0 28.8
1. These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat (MBH = 3.415 x kW). Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Ducted Systems 25
5147362-YTG-R-0323
XYEA7 (6.0 ton)
Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBH) Total Total Sensible Capacity (MBH)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBH) (kW)2 (MBH) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 90.7 4.1 43.2 36.5 29.9 - - - 86.4 4.6 41.4 34.9 28.3 - - -
72 82.7 4.0 53.0 45.0 37.1 29.1 - - 78.3 4.5 51.3 43.4 35.5 27.6 - -
1500
67 74.7 4.0 62.7 53.5 44.3 35.6 28.3 - 70.3 4.4 61.2 51.9 42.7 34.4 26.8 -
62 72.7 3.9 64.3 57.8 51.5 40.4 35.3 27.3 71.1 4.4 61.6 55.7 49.8 40.3 33.9 25.9
77 91.7 4.1 49.0 39.0 29.0 - - - 87.5 4.6 48.0 37.8 27.7 - - -
72 84.7 4.0 57.1 47.8 38.623 29.4 - - 80.3 4.5 55.6 46.3 37.1 27.8 - -
1800 67 77.7 4.0 65.2 56.7 48.3 38.2 29.2 - 73.2 4.5 63.1 54.8 46.5 36.8 27.6 -
62 73.4 4.0 67.8 62.8 57.9 45.6 38.2 28.4 71.4 4.4 65.0 60.5 55.9 45.0 36.5 26.8
57 60.7 3.9 60.7 60.7 60.7 57.4 47.2 37.1 59.4 4.4 59.4 59.4 59.4 55.4 45.5 35.5
77 92.6 4.1 54.8 41.4 28.1 - - - 88.6 4.6 54.6 40.8 27.0 - - -
72 86.7 4.0 61.2 50.7 40.2 29.7 - - 82.4 4.5 59.9 49.3 38.7 28.1 - -
2100 67 80.7 4.0 67.6 59.9 52.2 40.8 30.1 - 76.2 4.5 65.1 57.7 50.3 39.1 28.3 -
62 74.1 4.0 71.3 67.8 64.3 50.9 41.1 29.5 71.7 4.5 68.5 65.3 62.0 49.6 39.1 27.7
57 61.2 4.0 61.2 61.2 61.2 59.5 52.1 39.9 59.7 4.5 59.7 59.7 59.7 59.5 50.0 38.2
77 93.6 4.1 60.5 43.9 27.2 - - - 89.6 4.6 61.3 43.8 26.4 - - -
72 88.6 4.1 65.3 53.5 41.7 29.9 - - 84.4 4.5 64.1 52.2 40.3 28.3 - -
2400 67 83.7 4.0 70.0 63.1 56.2 43.4 31.1 - 79.1 4.5 67.0 60.6 54.2 41.5 29.1 -
62 74.8 4.0 74.8 72.9 70.7 56.1 44.0 30.6 72.1 4.5 71.9 70.0 68.0 54.3 41.8 28.7
57 61.7 4.0 61.7 61.7 61.7 61.7 56.9 42.8 59.9 4.5 59.9 59.9 59.9 59.9 54.5 40.8
72 90.6 4.1 69.4 56.3 43.2 30.2 - - 86.4 4.6 68.4 55.1 41.8 28.6 - -
67 86.7 4.0 72.4 66.3 60.2 45.9 32.0 - 82.1 4.5 69.0 63.5 58.0 43.8 29.8 -
2700
62 75.5 4.0 75.5 75.5 75.5 61.4 46.9 31.8 72.4 4.5 72.4 72.4 72.4 59.0 44.4 29.6
57 62.1 4.0 62.1 62.1 62.1 62.1 61.7 45.6 60.1 4.5 60.1 60.1 60.1 60.1 59.0 43.4
72 92.6 4.1 73.5 59.1 44.79 30.5 - - 88.4 4.6 72.7 58.1 43.4 28.8 - -
67 89.7 4.0 74.8 69.5 64.1 48.5 32.9 - 85.0 4.5 71.0 66.4 61.8 46.2 30.6 -
3000
62 76.2 4.1 76.2 76.2 76.2 66.6 49.8 32.9 72.7 4.5 72.7 72.7 72.7 63.6 47.1 30.5
57 62.6 4.1 62.6 62.6 62.6 62.6 62.6 48.4 60.4 4.6 60.4 60.4 60.4 60.4 60.4 46.0
95°F 105°F
77 82.1 5.0 39.6 33.2 26.8 - - - 79.9 5.7 38.7 31.5 24.4 - - -
72 74.0 5.0 49.6 41.7 33.9 26.1 - - 69.6 5.6 47.7 39.7 31.7 23.7 - -
1500
67 65.9 4.9 59.6 50.3 41.0 33.2 25.3 - 59.3 5.6 56.8 47.9 39.0 31.0 23.1 -
62 69.5 4.9 58.9 53.5 48.1 40.3 32.4 24.5 65.7 5.6 56.0 51.1 46.2 38.4 30.5 22.7
77 83.3 5.1 47.0 36.7 26.4 - - - 78.7 5.7 45.6 34.8 24.0 - - -
72 76.0 5.0 54.1 44.8 35.535 26.3 - - 70.8 5.6 51.8 42.5 33.2 23.9 - -
1800 67 68.8 4.9 61.1 52.9 44.7 35.3 25.9 - 62.8 5.6 58.1 50.3 42.5 33.1 23.7 -
62 69.4 4.9 62.3 58.1 53.9 44.3 34.8 25.2 65.6 5.6 59.0 55.3 51.7 42.3 32.8 23.4
57 58.2 4.9 58.2 58.2 58.2 53.4 43.7 34.0 60.5 5.6 59.9 59.9 59.9 51.4 41.9 32.4
77 84.5 5.1 54.5 40.2 25.9 - - - 77.6 5.7 52.6 38.1 23.5 - - -
72 78.1 5.0 58.5 47.9 37.2 26.5 - - 71.9 5.7 56.0 45.4 34.7 24.1 - -
2100 67 71.7 5.0 62.6 55.5 48.4 37.5 26.5 - 66.3 5.6 59.3 52.7 46.0 35.1 24.3 -
62 69.4 5.0 65.7 62.7 59.7 48.4 37.2 25.9 65.5 5.6 62.0 59.6 57.2 46.1 35.1 24.1
57 58.1 5.0 58.1 58.1 58.1 58.1 47.9 36.4 58.7 5.6 58.7 58.7 58.7 56.8 45.2 33.6
77 85.7 5.1 62.0 43.8 25.5 - - - 76.4 5.7 59.5 41.3 23.1 - - -
72 80.1 5.0 63.0 50.9 38.8 26.7 - - 73.0 5.7 60.1 48.2 36.3 24.4 - -
2400 67 74.6 5.0 64.1 58.1 52.1 39.6 27.1 - 69.7 5.6 60.6 55.0 49.5 37.2 24.9 -
62 69.3 5.0 69.0 67.2 65.4 52.5 39.6 26.7 65.3 5.6 64.9 63.8 62.6 50.0 37.4 24.8
57 58.1 5.0 58.1 58.1 58.1 58.1 52.1 38.8 57.0 5.6 57.0 57.0 57.0 57.0 48.5 34.8
72 82.2 5.0 67.5 54.0 40.4 26.9 - - 74.2 5.7 64.2 51.0 37.8 24.6 - -
67 77.5 5.0 65.6 60.7 55.8 41.7 27.7 - 73.2 5.7 61.9 57.4 53.0 39.3 25.5 -
2700
62 69.3 5.0 69.3 69.3 69.3 56.6 42.0 27.4 65.2 5.7 65.2 65.2 65.2 53.9 39.7 25.4
57 58.1 5.0 58.1 58.1 58.1 58.1 56.3 41.1 55.2 5.7 55.2 55.2 55.2 55.2 51.8 36.0
72 84.2 5.1 72.0 57.1 42.087 27.1 - - 75.3 5.7 68.3 53.8 39.3 24.8 - -
67 80.4 5.0 67.1 63.3 59.5 43.9 28.3 - 76.6 5.7 63.1 59.8 56.5 41.3 26.2 -
3000
62 69.3 5.0 69.3 69.3 69.3 60.6 44.4 28.1 65.0 5.7 65.0 65.0 65.0 57.8 42.0 26.1
57 58.1 5.1 58.1 58.1 58.1 58.1 58.1 43.5 53.5 5.7 53.5 53.5 53.5 53.5 53.5 37.2
26 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XYEA7 (6.0 ton) (Continued)
Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBH) Total Total Sensible Capacity (MBH)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBH) (kW)2 (MBH) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 77.7 6.3 37.7 29.9 22.1 - - - 75.6 6.9 36.8 28.3 19.7 - - -
72 65.3 6.3 45.9 37.7 29.5 21.3 - - 60.9 6.9 44.1 35.7 27.3 18.9 - -
1500
67 52.8 6.2 52.8 45.5 36.9 28.9 20.9 - 46.3 6.9 46.3 43.1 34.8 26.7 18.6 -
62 62.0 6.2 53.1 48.7 44.3 36.5 28.7 20.8 58.3 6.9 50.2 46.3 42.4 34.6 26.8 19.0
77 74.2 6.3 44.2 32.9 21.6 - - - 69.7 7.0 42.8 31.0 19.2 - - -
72 65.5 6.3 49.6 40.3 30.9 21.5 - - 60.3 6.9 47.4 38.0 28.6 19.2 - -
1800 67 56.8 6.2 55.1 47.6 40.2 30.9 21.5 - 50.9 6.9 50.9 45.0 38.0 28.6 19.3 -
62 61.8 6.2 55.7 52.6 49.5 40.2 30.8 21.5 58.0 6.9 52.4 49.9 47.3 38.1 28.9 19.6
57 62.8 6.2 56.3 56.3 56.3 49.5 40.2 30.9 65.1 6.9 52.7 52.7 52.7 47.6 38.4 29.3
77 70.7 6.3 50.6 35.9 21.1 - - - 63.7 7.0 48.7 33.7 18.7 - - -
72 65.7 6.3 53.4 42.8 32.3 21.8 - - 59.6 7.0 50.8 40.3 29.9 19.4 - -
2100 67 60.8 6.3 56.1 49.8 43.5 32.8 22.1 - 55.4 6.9 52.9 47.0 41.1 30.5 20.0 -
62 61.5 6.3 58.3 56.5 54.7 43.9 33.0 22.2 57.6 6.9 54.6 53.4 52.2 41.6 30.9 20.3
57 59.3 6.3 59.3 59.3 59.3 54.2 42.5 30.9 59.9 6.9 56.3 56.3 56.3 51.6 39.9 28.1
77 67.1 6.4 57.1 38.9 20.7 - - - 57.8 7.0 54.6 36.4 18.2 - - -
72 66.0 6.3 57.1 45.4 33.7 22.1 - - 58.9 7.0 54.1 42.7 31.2 19.7 - -
2400 67 64.8 6.3 57.1 52.0 46.8 34.8 22.8 - 59.9 7.0 53.7 48.9 44.2 32.4 20.6 -
62 61.3 6.3 60.8 60.4 59.9 47.5 35.2 22.9 57.3 7.0 56.7 56.7 56.7 45.1 33.0 21.0
57 55.8 6.3 55.8 55.8 55.8 55.8 44.9 30.9 54.6 6.9 54.6 54.6 54.6 54.6 41.3 26.9
72 66.2 6.4 60.9 48.0 35.2 22.3 - - 58.2 7.0 57.5 45.0 32.5 20.0 - -
67 68.8 6.3 58.2 54.1 50.1 36.8 23.4 - 64.5 7.0 54.4 50.9 47.3 34.3 21.3 -
2700
62 61.1 6.3 61.1 61.1 61.1 51.2 37.4 23.5 56.9 7.0 56.9 56.9 56.9 48.5 35.1 21.6
57 52.3 6.3 52.3 52.3 52.3 52.3 47.3 30.9 49.4 7.0 49.4 49.4 49.4 49.4 42.8 25.8
72 66.4 6.4 64.6 50.6 36.6 22.6 - - 57.5 7.0 57.5 47.4 33.8 20.3 - -
67 72.8 6.4 59.2 56.3 53.4 38.7 24.1 - 69.0 7.0 55.2 52.8 50.4 36.2 22.0 -
3000
62 60.8 6.4 60.8 60.8 60.8 54.9 39.6 24.2 56.6 7.0 56.6 56.6 56.6 52.0 37.1 22.3
57 48.8 6.4 48.8 48.8 48.8 48.8 48.8 30.9 44.2 7.0 44.2 44.2 44.2 44.2 44.2 24.6
1. These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat (MBH = 3.415 x kW). Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Ducted Systems 27
5147362-YTG-R-0323
XYE08 (7.5 ton)
Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBH) Total Total Sensible Capacity (MBH)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBH) (kW)2 (MBH) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 113.5 5.2 46.7 38.6 32.4 - - - 109.9 5.9 46.2 38.7 31.2 - - -
72 104.3 5.1 58.6 52.4 46.2 40.0 - - 99.9 5.8 59.2 51.7 44.2 36.7 - -
1875
67 95.0 5.0 70.5 66.2 60.0 53.8 47.6 - 89.9 5.7 72.3 64.8 57.3 49.7 42.2 -
62 85.3 5.0 85.3 85.3 72.1 65.9 59.7 53.5 81.8 5.7 81.8 81.8 68.9 61.4 53.8 46.3
77 118.7 5.2 52.7 44.2 35.6 - - - 114.1 5.9 53.0 43.6 34.2 - - -
72 109.0 5.1 67.9 59.3 50.7 42.1 - - 103.7 5.8 67.3 57.9 48.5 39.1 - -
2250 67 99.3 5.0 83.0 74.4 65.8 57.2 48.6 - 93.3 5.7 81.6 72.2 62.8 53.4 44.0 -
62 89.1 5.0 89.1 89.1 79.1 70.5 61.9 53.3 84.9 5.7 84.9 84.9 75.5 66.1 56.8 47.4
57 86.1 5.0 86.1 86.1 79.8 71.2 62.6 54.0 83.3 5.7 83.3 83.3 75.9 66.5 57.1 47.8
77 123.9 5.2 58.8 49.7 38.7 - - - 118.2 5.9 59.8 48.5 37.2 - - -
72 113.7 5.1 77.1 66.1 55.2 44.2 - - 107.5 5.8 75.3 64.1 52.8 41.5 - -
2625 67 103.6 5.0 95.4 82.6 71.6 60.6 49.6 - 96.7 5.7 90.9 79.6 68.4 57.1 45.8 -
62 93.0 5.0 93.0 93.0 86.0 75.0 64.1 53.1 88.0 5.7 88.0 88.0 82.2 70.9 59.7 48.4
57 89.9 5.0 89.9 89.9 86.8 75.8 64.9 53.9 86.3 5.7 86.3 86.3 82.6 71.4 60.1 48.8
77 129.0 5.2 64.9 55.2 41.8 - - - 122.4 5.9 66.6 53.4 40.3 - - -
72 118.5 5.1 86.4 73.0 59.6 46.2 - - 111.3 5.8 83.4 70.2 57.1 43.9 - -
3000 67 107.9 5.0 107.9 90.8 77.4 64.0 50.6 - 100.1 5.7 100.1 87.1 73.9 60.7 47.6 -
62 96.9 5.0 96.9 96.9 93.0 79.6 66.2 52.9 91.1 5.7 91.1 91.1 88.9 75.7 62.6 49.4
57 93.6 5.0 93.6 93.6 93.6 80.5 67.1 53.7 89.3 5.7 89.3 89.3 89.3 76.2 63.0 49.9
72 120.7 5.1 88.9 76.0 63.1 50.2 - - 113.3 5.8 88.1 74.4 60.8 47.1 - -
67 109.9 5.0 109.9 95.2 81.9 69.0 56.1 - 102.0 5.7 102.0 92.4 78.7 65.0 51.4 -
3375
62 98.7 5.0 98.7 98.7 96.8 83.9 71.0 58.1 92.8 5.7 92.8 92.8 91.7 78.0 64.3 50.7
57 95.4 5.0 95.4 95.4 95.4 82.6 69.7 56.8 91.0 5.7 91.0 91.0 91.0 77.3 63.7 50.0
72 122.9 5.2 91.4 79.0 66.6 54.2 - - 115.4 5.8 92.8 78.6 64.5 50.3 - -
67 111.9 5.1 111.9 99.5 86.4 74.0 61.6 - 103.8 5.8 103.8 97.7 83.5 69.3 55.2 -
3750
62 100.5 5.1 100.5 100.5 100.5 88.1 75.7 63.3 94.4 5.7 94.4 94.4 94.4 80.3 66.1 52.0
57 97.1 5.1 97.1 97.1 97.1 84.7 72.3 59.9 92.7 5.7 92.7 92.7 92.7 78.5 64.3 50.2
95°F 105°F
77 106.3 6.5 45.7 38.8 30.0 - - - 94.5 7.3 39.8 35.0 26.8 - - -
72 95.6 6.4 59.9 51.1 42.3 33.4 - - 85.3 7.3 55.2 47.1 38.9 30.7 - -
1875
67 84.8 6.4 74.1 63.4 54.6 45.7 36.9 - 76.1 7.2 70.7 59.2 51.0 42.8 34.7 -
62 78.3 6.3 78.3 78.3 65.7 56.9 48.0 39.2 71.2 7.1 71.2 71.2 60.0 51.9 43.7 35.5
77 109.4 6.5 53.2 43.1 32.9 - - - 98.0 7.3 48.6 39.1 29.6 - - -
72 98.4 6.5 66.7 56.5 46.3 36.1 - - 88.4 7.3 61.9 52.4 42.9 33.5 - -
2250 67 87.3 6.4 80.2 70.0 59.8 49.6 39.4 - 78.9 7.2 75.3 65.8 56.3 46.8 37.3 -
62 80.6 6.3 80.6 80.6 72.0 61.8 51.6 41.4 73.8 7.2 73.8 73.8 66.3 56.8 47.3 37.8
57 80.4 6.3 80.4 80.4 72.1 61.9 51.7 41.5 72.8 7.2 72.8 72.8 65.5 56.0 46.5 37.0
77 112.6 6.5 60.8 47.3 35.8 - - - 101.4 7.4 57.4 43.2 32.4 - - -
72 101.2 6.5 73.5 62.0 50.4 38.9 - - 91.5 7.3 68.6 57.8 47.0 36.2 - -
2625 67 89.8 6.4 86.3 76.7 65.1 53.5 42.0 - 81.6 7.3 79.8 72.4 61.6 50.8 40.0 -
62 82.9 6.3 82.9 82.9 78.4 66.8 55.3 43.7 76.4 7.2 76.4 76.4 72.5 61.7 50.9 40.1
57 82.7 6.4 82.7 82.7 78.4 66.9 55.3 43.8 75.3 7.2 75.3 75.3 71.6 60.8 50.0 39.2
77 115.7 6.5 68.4 51.6 38.7 - - - 104.8 7.4 66.1 47.3 35.2 - - -
72 104.0 6.5 80.3 67.4 54.5 41.6 - - 94.6 7.3 75.3 63.1 51.0 38.9 - -
3000 67 92.3 6.4 92.3 83.3 70.4 57.4 44.5 - 84.4 7.3 84.4 79.0 66.9 54.8 42.6 -
62 85.2 6.3 85.2 85.2 84.7 71.8 58.9 46.0 79.0 7.2 79.0 79.0 78.7 66.6 54.5 42.3
57 85.0 6.4 85.0 85.0 84.8 71.9 59.0 46.0 77.9 7.2 77.9 77.9 77.7 65.6 53.5 41.4
72 106.0 6.5 87.3 72.9 58.5 44.0 - - 96.0 7.3 81.5 68.1 54.7 41.4 - -
67 94.1 6.4 94.1 89.5 75.5 61.0 46.6 - 85.7 7.3 85.7 83.0 71.7 58.4 45.0 -
3375
62 86.8 6.3 86.8 86.8 86.6 72.1 57.7 43.3 80.1 7.2 80.1 80.1 80.0 66.7 53.3 39.9
57 86.6 6.3 86.6 86.6 86.5 72.1 57.7 43.2 79.0 7.2 79.0 79.0 79.0 65.6 52.2 38.9
72 107.9 6.4 94.2 78.3 62.4 46.5 - - 97.5 7.3 87.6 73.0 58.4 43.8 - -
67 95.8 6.4 95.8 95.8 80.6 64.6 48.7 - 87.0 7.3 87.0 87.0 76.6 62.0 47.4 -
3750
62 88.4 6.3 88.4 88.4 88.4 72.5 56.6 40.7 81.3 7.2 81.3 81.3 81.3 66.7 52.1 37.5
57 88.2 6.3 88.2 88.2 88.2 72.3 56.4 40.5 80.2 7.2 80.2 80.2 80.2 65.6 51.0 36.4
28 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XYE08 (7.5 ton) (Continued)
Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBH) Total Total Sensible Capacity (MBH)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBH) (kW)2 (MBH) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 82.8 8.1 33.9 31.2 23.7 - - - 71.0 9.0 33.1 26.4 20.6 - - -
72 75.1 8.1 50.6 43.1 35.6 28.1 - - 64.9 8.9 45.9 39.1 32.2 25.4 - -
1875
67 67.4 8.1 67.2 54.9 47.4 39.9 32.4 - 58.7 8.9 58.7 50.7 43.9 37.0 30.2 -
62 64.1 8.0 64.1 64.1 54.4 46.9 39.4 31.9 57.0 8.8 57.0 57.0 48.7 41.9 35.1 28.2
77 86.5 8.2 43.9 35.1 26.3 - - - 75.0 9.0 42.6 31.2 23.1 - - -
72 78.5 8.1 57.1 48.3 39.6 30.8 - - 68.5 9.0 52.3 44.2 36.2 28.1 - -
2250 67 70.4 8.1 70.3 61.5 52.8 44.0 35.2 - 62.0 8.9 62.0 57.3 49.2 41.2 33.1 -
62 66.9 8.0 66.9 66.9 60.5 51.7 42.9 34.1 60.1 8.9 60.1 60.1 54.7 46.6 38.6 30.5
57 65.1 8.0 65.1 65.1 58.8 50.0 41.3 32.5 57.4 8.9 57.4 57.4 52.2 44.1 36.1 28.0
77 90.2 8.2 53.9 39.1 29.0 - - - 79.0 9.0 52.1 35.9 25.6 - - -
72 81.8 8.2 63.6 53.6 43.5 33.5 - - 72.1 9.0 58.7 49.4 40.1 30.8 - -
2625 67 73.5 8.1 73.4 68.1 58.1 48.0 38.0 - 65.3 9.0 65.3 63.9 54.6 45.3 36.0 -
62 69.8 8.1 69.8 69.8 66.6 56.5 46.5 36.4 63.2 8.9 63.2 63.2 60.7 51.4 42.1 32.8
57 67.9 8.0 67.9 67.9 64.8 54.7 44.6 34.6 60.5 8.9 60.5 60.5 57.9 48.6 39.3 30.0
77 93.9 8.2 63.9 43.0 31.7 - - - 83.0 9.1 61.7 40.6 28.2 - - -
72 85.2 8.2 70.2 58.9 47.5 36.2 - - 75.7 9.0 65.1 54.6 44.0 33.5 - -
3000 67 76.5 8.1 76.5 74.7 63.4 52.1 40.7 - 68.5 9.0 68.5 68.5 59.9 49.4 38.8 -
62 72.7 8.1 72.7 72.7 72.7 61.3 50.0 38.7 66.4 9.0 66.4 66.4 66.4 56.1 45.6 35.1
57 70.7 8.1 70.7 70.7 70.7 59.4 48.0 36.7 63.5 8.9 63.5 63.5 63.5 53.1 42.6 32.0
72 86.1 8.2 75.6 63.3 51.0 38.7 - - 76.2 9.1 69.8 58.5 47.3 36.0 - -
67 77.3 8.2 77.3 76.4 68.0 55.7 43.4 - 68.9 9.0 68.9 68.9 64.3 53.1 41.8 -
3375
62 73.5 8.1 73.5 73.5 73.5 61.2 48.8 36.5 66.8 9.0 66.8 66.8 66.8 55.7 44.4 33.1
57 71.4 8.1 71.4 71.4 71.4 59.1 46.8 34.5 63.9 9.0 63.9 63.9 63.9 52.7 41.4 30.2
72 87.0 8.2 81.1 67.8 54.5 41.2 - - 76.6 9.1 74.5 62.5 50.5 38.5 - -
67 78.1 8.2 78.1 78.1 72.7 59.4 46.1 - 69.3 9.0 69.3 69.3 68.7 56.7 44.8 -
3750
62 74.3 8.1 74.3 74.3 74.3 61.0 47.7 34.4 67.2 9.0 67.2 67.2 67.2 55.2 43.2 31.2
57 72.2 8.1 72.2 72.2 72.2 58.9 45.6 32.3 64.2 9.0 64.2 64.2 64.2 52.2 40.3 28.3
1. These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat (MBH = 3.415 x kW). Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Ducted Systems 29
5147362-YTG-R-0323
XYE09 (8.5 ton)
Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBH) Total Total Sensible Capacity (MBH)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBH) (kW)2 (MBH) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 131.1 5.8 57.6 48.1 39.3 - - - 122.6 6.6 54.6 45.8 37.0 - - -
72 119.4 5.7 70.5 61.7 52.9 44.1 - - 111.9 6.5 68.1 59.4 50.6 41.8 - -
2125
67 107.8 5.5 83.5 75.4 66.5 57.7 48.9 - 101.1 6.4 81.7 72.9 64.1 55.3 46.6 -
62 99.7 5.5 99.7 94.3 80.6 71.8 63.0 54.2 93.6 6.4 93.6 91.0 77.5 68.7 59.9 51.2
77 135.4 5.8 63.5 53.2 42.9 - - - 126.6 6.6 60.9 50.7 40.4 - - -
72 123.4 5.7 78.4 68.1 57.9 47.6 - - 115.5 6.5 75.7 65.5 55.2 45.0 - -
2550 67 111.4 5.6 93.3 83.1 72.8 62.5 52.2 - 104.4 6.4 90.5 80.3 70.0 59.8 49.6 -
62 103.0 5.5 103.0 99.4 88.2 77.9 67.6 57.4 96.7 6.4 96.7 94.9 84.6 74.4 64.2 53.9
57 101.3 5.5 101.3 101.3 90.9 80.7 70.4 60.1 96.4 6.3 96.4 96.4 86.4 76.1 65.9 55.7
77 139.7 5.9 69.4 58.3 46.6 - - - 130.6 6.7 67.2 55.5 43.8 - - -
72 127.3 5.7 86.3 74.5 62.8 51.1 - - 119.1 6.6 83.3 71.6 59.9 48.2 - -
2975 67 114.9 5.6 103.1 90.7 79.0 67.3 55.6 - 107.6 6.5 99.3 87.6 75.9 64.2 52.6 -
62 106.3 5.6 106.3 104.5 95.7 84.0 72.3 60.6 99.7 6.4 99.7 98.8 91.8 80.1 68.4 56.7
57 104.5 5.5 104.5 104.5 98.7 87.0 75.3 63.6 99.4 6.4 99.4 99.4 93.6 82.0 70.3 58.6
77 144.0 5.9 75.4 63.5 50.3 - - - 134.5 6.7 73.5 60.4 47.3 - - -
72 131.2 5.8 94.1 80.9 67.8 54.6 - - 122.7 6.6 90.8 77.7 64.5 51.4 - -
3400 67 118.5 5.6 112.9 98.4 85.2 72.1 58.9 - 110.9 6.5 108.1 95.0 81.8 68.7 55.6 -
62 109.6 5.6 109.6 109.6 103.3 90.1 76.9 63.8 102.7 6.4 102.7 102.7 98.9 85.8 72.7 59.5
57 107.8 5.6 107.8 107.8 106.5 93.3 80.2 67.0 102.5 6.4 102.5 102.5 100.9 87.8 74.7 61.5
72 133.7 5.8 101.0 86.6 72.3 57.9 - - 124.7 6.6 97.7 83.4 69.0 54.7 - -
67 120.7 5.7 117.9 105.2 90.9 76.5 62.2 - 112.7 6.5 111.3 101.9 87.5 73.2 58.9 -
3825
62 111.6 5.6 111.6 111.6 108.5 94.2 79.8 65.5 104.4 6.5 104.4 104.4 102.5 88.2 73.8 59.5
57 109.8 5.6 109.8 109.8 109.2 94.9 80.5 66.2 104.1 6.4 104.1 104.1 103.3 89.0 74.7 60.4
72 136.2 5.8 107.8 92.3 76.7 61.2 - - 126.6 6.6 104.5 89.0 73.5 58.1 - -
67 123.0 5.7 123.0 112.0 96.5 81.0 65.5 - 114.4 6.5 114.4 108.7 93.2 77.8 62.3 -
4250
62 113.7 5.7 113.7 113.7 113.7 98.2 82.7 67.2 106.0 6.5 106.0 106.0 106.0 90.5 75.0 59.6
57 111.9 5.6 111.9 111.9 111.9 96.4 80.8 65.3 105.7 6.4 105.7 105.7 105.7 90.2 74.8 59.3
95°F 105°F
77 114.2 7.4 51.6 43.5 34.8 - - - 102.8 8.4 44.4 38.9 30.2 - - -
72 104.3 7.3 65.7 57.0 48.2 39.5 - - 94.8 8.4 61.4 52.7 44.1 35.4 - -
2125
67 94.4 7.3 79.8 70.4 61.7 53.0 44.2 - 86.8 8.3 78.4 66.6 58.0 49.3 40.6 -
62 87.6 7.2 87.6 87.6 74.4 65.6 56.9 48.2 81.7 8.2 81.7 81.7 67.9 59.3 50.6 41.9
77 117.8 7.4 58.3 48.1 37.9 - - - 106.3 8.4 53.6 43.4 33.2 - - -
72 107.6 7.4 73.0 62.8 52.6 42.4 - - 98.0 8.4 68.9 58.7 48.5 38.3 - -
2550 67 97.4 7.3 87.7 77.5 67.3 57.1 46.9 - 89.8 8.3 84.2 74.0 63.8 53.6 43.5 -
62 90.4 7.2 90.4 90.4 81.1 70.9 60.7 50.5 84.5 8.2 84.5 84.5 74.8 64.6 54.4 44.2
57 91.5 7.2 91.5 91.5 81.8 71.6 61.4 51.2 85.0 8.2 85.0 85.0 75.1 64.9 54.8 44.6
77 121.5 7.4 65.0 52.7 41.1 - - - 109.9 8.4 62.8 47.9 36.2 - - -
72 110.9 7.4 80.3 68.6 57.0 45.3 - - 101.3 8.4 76.4 64.7 53.0 41.3 - -
2975 67 100.3 7.3 95.5 84.5 72.9 61.2 49.6 - 92.8 8.3 90.0 81.4 69.7 58.0 46.3 -
62 93.1 7.2 93.1 93.1 87.8 76.2 64.5 52.9 87.4 8.2 87.4 87.3 81.6 69.9 58.2 46.5
57 94.4 7.2 94.4 94.4 88.5 76.9 65.3 53.6 87.8 8.2 87.8 87.8 82.0 70.3 58.6 46.9
77 125.1 7.4 71.7 57.3 44.2 - - - 113.4 8.5 72.0 52.5 39.2 - - -
72 114.2 7.4 87.5 74.4 61.3 48.2 - - 104.6 8.4 83.9 70.6 57.4 44.2 - -
3400 67 103.3 7.3 103.3 91.5 78.4 65.3 52.2 - 95.8 8.4 95.8 88.8 75.6 62.3 49.1 -
62 95.9 7.3 95.9 95.9 94.6 81.5 68.4 55.3 90.2 8.2 90.2 90.2 88.5 75.2 62.0 48.8
57 97.2 7.2 97.2 97.2 95.3 82.2 69.1 56.0 90.7 8.2 90.7 90.7 88.9 75.6 62.4 49.2
72 115.6 7.4 94.4 80.1 65.8 51.6 - - 105.6 8.4 90.0 75.7 61.5 47.2 - -
67 104.6 7.4 104.6 98.5 84.2 69.9 55.7 - 96.6 8.4 96.6 93.0 80.9 66.6 52.4 -
3825
62 97.1 7.3 97.1 97.1 96.4 82.1 67.9 53.6 91.0 8.3 91.0 91.0 90.2 75.9 61.6 47.4
57 98.4 7.2 98.4 98.4 97.4 83.2 68.9 54.6 91.5 8.2 91.5 91.5 90.6 76.3 62.1 47.8
72 117.0 7.4 101.2 85.8 70.4 54.9 - - 106.5 8.4 96.1 80.8 65.5 50.2 - -
67 105.9 7.4 105.9 105.4 90.0 74.5 59.1 - 97.5 8.4 97.5 97.3 86.2 71.0 55.7 -
4250
62 98.2 7.3 98.2 98.2 98.2 82.8 67.4 51.9 91.8 8.3 91.8 91.8 91.8 76.6 61.3 46.0
57 99.5 7.3 99.5 99.5 99.5 84.1 68.7 53.2 92.3 8.3 92.3 92.3 92.3 77.1 61.8 46.5
30 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XYE09 (8.5 ton) (Continued)
Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBH) Total Total Sensible Capacity (MBH)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBH) (kW)2 (MBH) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 91.3 9.4 37.2 34.2 25.6 - - - 79.9 10.4 34.1 28.2 21.0 - - -
72 85.2 9.4 57.1 48.5 39.9 31.3 - - 75.7 10.4 52.8 44.3 35.8 27.2 - -
2125
67 79.2 9.3 77.1 62.9 54.3 45.7 37.1 - 71.6 10.3 71.6 59.1 50.5 42.0 33.5 -
62 75.8 9.2 75.8 75.7 61.5 52.9 44.3 35.7 70.0 10.2 70.0 69.8 55.1 46.5 38.0 29.5
77 94.8 9.4 48.9 38.7 28.5 - - - 83.3 10.5 46.9 33.9 23.7 - - -
72 88.5 9.4 64.8 54.6 44.4 34.3 - - 78.9 10.4 60.7 50.5 40.4 30.2 - -
2550 67 82.2 9.3 80.8 70.6 60.4 50.2 40.0 - 74.6 10.4 74.6 67.1 57.0 46.8 36.6 -
62 78.7 9.2 78.7 78.6 68.5 58.3 48.1 37.9 72.9 10.2 72.9 72.8 62.1 51.9 41.8 31.6
57 78.4 9.2 78.4 78.4 68.5 58.3 48.1 37.9 71.9 10.2 71.9 71.9 61.9 51.7 41.5 31.3
77 98.3 9.5 60.5 43.1 31.4 - - - 86.7 10.5 59.7 39.7 26.5 - - -
72 91.7 9.4 72.5 60.7 49.0 37.2 - - 82.1 10.4 68.6 56.8 44.9 33.1 - -
2975 67 85.2 9.4 84.5 78.3 66.5 54.8 43.0 - 77.6 10.4 77.6 75.2 63.4 51.5 39.7 -
62 81.6 9.2 81.6 81.6 75.4 63.6 51.9 40.1 75.8 10.2 75.8 75.8 69.2 57.4 45.5 33.7
57 81.3 9.2 81.3 81.3 75.5 63.7 51.9 40.1 74.8 10.2 74.8 74.8 68.9 57.1 45.2 33.4
77 101.8 9.5 72.2 47.6 34.3 - - - 90.1 10.5 72.4 45.4 29.3 - - -
72 95.0 9.4 80.2 66.8 53.5 40.1 - - 85.4 10.4 76.5 63.0 49.5 36.0 - -
3400 67 88.2 9.4 88.2 86.0 72.7 59.3 46.0 - 80.6 10.4 80.6 80.6 69.8 56.3 42.8 -
62 84.5 9.2 84.5 84.5 82.4 69.0 55.7 42.3 78.8 10.2 78.8 78.8 76.3 62.8 49.3 35.8
57 84.2 9.2 84.2 84.2 82.4 69.1 55.7 42.3 77.7 10.2 77.7 77.7 76.0 62.5 49.0 35.5
72 95.5 9.4 85.6 71.3 57.1 42.8 - - 85.5 10.4 81.2 66.9 52.7 38.5 - -
67 88.7 9.4 88.7 87.6 77.6 63.3 49.1 - 80.7 10.4 80.7 80.7 74.3 60.0 45.8 -
3825
62 85.0 9.2 85.0 85.0 83.9 69.7 55.4 41.2 78.9 10.2 78.9 78.9 77.7 63.4 49.2 35.0
57 84.7 9.2 84.7 84.7 83.8 69.5 55.3 41.0 77.8 10.3 77.8 77.8 76.9 62.7 48.5 34.2
72 96.0 9.4 90.9 75.8 60.7 45.6 - - 85.6 10.4 85.6 70.8 55.9 40.9 - -
67 89.2 9.4 89.2 89.2 82.5 67.4 52.2 - 80.9 10.4 80.9 80.9 78.8 63.8 48.8 -
4250
62 85.4 9.2 85.4 85.4 85.4 70.3 55.2 40.1 79.0 10.2 79.0 79.0 79.0 64.1 49.1 34.1
57 85.1 9.3 85.1 85.1 85.1 70.0 54.9 39.8 77.9 10.3 77.9 77.9 77.9 63.0 48.0 33.0
1. These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat (MBH = 3.415 x kW). Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Ducted Systems 31
5147362-YTG-R-0323
XXEA7 (6.0 ton)
Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBH) Total Total Sensible Capacity (MBH)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBH) (kW)2 (MBH) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 87.8 4.2 42.7 35.7 28.9 - - - 83.4 4.9 35.9 30.7 24.0 - - -
72 81.3 4.1 50.8 44.0 37.2 30.4 - - 76.8 4.8 46.9 40.3 33.6 27.0 - -
1500
67 74.7 4.0 59.0 52.4 45.6 38.8 32.0 - 70.2 4.7 58.0 49.9 43.2 36.6 29.9 -
62 67.1 3.9 67.1 65.8 54.1 47.3 40.5 33.7 64.3 4.6 64.3 62.5 50.9 44.3 37.6 31.0
77 90.5 4.3 47.9 40.1 32.3 - - - 85.8 4.9 42.5 34.7 27.0 - - -
72 83.8 4.2 57.2 49.4 41.7 33.9 - - 79.0 4.8 53.3 45.5 37.8 30.1 - -
1800 67 77.0 4.1 66.6 58.8 51.0 43.2 35.4 - 72.2 4.7 64.1 56.3 48.6 40.9 33.1 -
62 69.2 3.9 69.2 68.3 60.5 52.7 44.9 37.1 66.2 4.6 66.2 65.0 57.2 49.5 41.8 34.0
57 69.9 4.0 69.9 68.9 61.1 53.3 45.5 37.7 66.5 4.6 66.5 65.3 57.5 49.8 42.1 34.3
77 93.2 4.4 53.2 44.6 35.8 - - - 88.2 4.9 49.0 38.8 30.0 - - -
72 86.3 4.3 63.6 54.9 46.1 37.3 - - 81.2 4.8 59.6 50.8 42.0 33.1 - -
2100 67 79.4 4.2 74.1 65.1 56.4 47.6 38.8 - 74.2 4.8 70.2 62.8 54.0 45.1 36.3 -
62 71.3 4.0 71.3 70.8 66.9 58.2 49.4 40.6 68.0 4.6 68.0 67.4 63.5 54.7 45.9 37.1
57 72.0 4.0 72.0 71.5 67.6 58.8 50.0 41.3 68.4 4.7 68.4 67.7 63.9 55.0 46.2 37.4
77 96.0 4.4 58.4 49.0 39.3 - - - 90.6 5.0 55.6 42.8 32.9 - - -
72 88.8 4.3 70.0 60.3 50.5 40.8 - - 83.4 4.9 65.9 56.0 46.1 36.2 - -
2400 67 81.7 4.2 81.7 71.5 61.8 52.0 42.2 - 76.2 4.8 76.2 69.2 59.3 49.4 39.5 -
62 73.3 4.1 73.3 73.3 73.3 63.6 53.8 44.1 69.8 4.7 69.8 69.8 69.8 59.9 50.0 40.1
57 74.1 4.1 74.1 74.1 74.1 64.3 54.6 44.8 70.2 4.7 70.2 70.2 70.2 60.3 50.4 40.5
72 90.8 4.3 74.7 63.7 52.8 41.8 - - 84.5 4.9 70.5 59.4 48.3 37.2 - -
67 83.5 4.2 83.5 77.4 64.5 53.5 42.5 - 77.2 4.8 77.2 73.2 62.1 51.0 39.9 -
2700
62 75.0 4.1 75.0 75.0 75.0 64.1 53.1 42.1 70.8 4.7 70.8 70.8 70.8 59.7 48.6 37.5
57 75.8 4.1 75.8 75.8 75.8 64.8 53.8 42.8 71.1 4.7 71.1 71.1 71.1 60.0 48.9 37.8
72 92.9 4.4 79.4 67.2 55.0 42.8 - - 85.6 5.0 75.1 62.8 50.5 38.2 - -
67 85.4 4.3 85.4 83.3 67.2 55.0 42.8 - 78.2 4.9 78.2 77.2 64.9 52.6 40.3 -
3000
62 76.7 4.1 76.7 76.7 76.7 64.5 52.3 40.1 71.7 4.8 71.7 71.7 71.7 59.4 47.1 34.8
57 77.5 4.1 77.5 77.5 77.5 65.3 53.1 40.9 72.0 4.8 72.0 72.0 72.0 59.7 47.4 35.2
95°F 105°F
77 79.1 5.5 29.1 25.7 19.2 - - - 72.9 6.2 27.2 24.6 18.3 - - -
72 72.4 5.4 43.0 36.5 30.0 23.5 - - 66.8 6.1 41.8 35.3 28.8 22.3 - -
1500
67 65.7 5.3 57.0 47.4 40.9 34.4 27.9 - 60.7 6.0 56.4 45.9 39.2 32.7 26.2 -
62 61.6 5.2 61.6 59.3 47.8 41.3 34.8 28.3 57.7 6.0 57.7 56.6 45.3 38.8 32.3 25.8
77 81.1 5.5 37.0 29.3 21.6 - - - 74.7 6.2 36.1 28.3 20.6 - - -
72 74.2 5.4 49.3 41.6 33.9 26.3 - - 68.4 6.1 47.7 40.0 32.3 24.6 - -
1800 67 67.4 5.3 61.6 53.9 46.2 38.6 30.9 - 62.2 6.0 59.3 51.7 44.0 36.3 28.6 -
62 63.2 5.3 63.2 61.6 54.0 46.3 38.6 30.9 59.1 6.0 59.1 58.3 50.8 43.1 35.4 27.7
57 63.2 5.3 63.2 61.6 54.0 46.3 38.6 30.9 59.0 6.0 59.0 58.1 50.4 42.7 35.0 27.3
77 83.1 5.5 44.9 33.0 24.1 - - - 76.4 6.3 45.0 31.9 22.8 - - -
72 76.1 5.4 55.6 46.7 37.8 29.0 - - 70.0 6.2 53.6 44.7 35.8 26.9 - -
2100 67 69.1 5.4 66.2 60.4 51.5 42.7 33.8 - 63.6 6.1 62.2 57.4 48.7 39.8 30.9 -
62 64.8 5.3 64.8 64.0 60.2 51.3 42.4 33.6 60.5 6.0 60.5 60.1 56.3 47.4 38.5 29.6
57 64.7 5.3 64.7 64.0 60.1 51.3 42.4 33.5 60.3 6.0 60.3 59.9 55.9 47.0 38.1 29.2
77 85.2 5.6 52.8 36.6 26.6 - - - 78.2 6.3 53.8 35.6 25.0 - - -
72 78.0 5.5 61.8 51.8 41.7 31.7 - - 71.6 6.2 59.5 49.4 39.3 29.2 - -
2400 67 70.8 5.4 70.8 66.9 56.8 46.8 36.7 - 65.1 6.1 65.1 63.1 53.5 43.4 33.3 -
62 66.3 5.3 66.3 66.3 66.3 56.3 46.3 36.2 61.8 6.0 61.8 61.8 61.8 51.8 41.7 31.6
57 66.3 5.3 66.3 66.3 66.3 56.3 46.2 36.2 61.7 6.0 61.7 61.7 61.3 51.2 41.1 31.1
72 78.1 5.5 66.2 55.0 43.8 32.6 - - 71.7 6.2 63.7 52.8 41.5 30.2 - -
67 70.9 5.4 70.9 69.0 59.7 48.5 37.3 - 65.1 6.1 65.1 64.2 56.6 45.2 33.9 -
2700
62 66.5 5.4 66.5 66.5 66.5 55.3 44.0 32.8 61.9 6.1 61.9 61.9 61.9 50.5 39.2 27.9
57 66.5 5.4 66.5 66.5 66.5 55.2 44.0 32.8 61.7 6.1 61.7 61.7 61.6 50.2 38.9 27.5
72 78.3 5.6 70.7 58.3 45.9 33.6 - - 71.7 6.3 67.9 56.3 43.7 31.2 - -
67 71.0 5.5 71.0 71.0 62.6 50.2 37.8 - 65.2 6.2 65.2 65.2 59.6 47.0 34.4 -
3000
62 66.6 5.4 66.6 66.6 66.6 54.2 41.8 29.5 61.9 6.2 61.9 61.9 61.9 49.3 36.7 24.2
57 66.6 5.4 66.6 66.6 66.6 54.2 41.8 29.5 61.8 6.1 61.8 61.8 61.8 49.2 36.6 24.0
32 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XXEA7 (6.0 ton) (Continued)
Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBH) Total Total Sensible Capacity (MBH)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBH) (kW)2 (MBH) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 66.8 7.0 25.3 23.6 17.5 - - - 60.7 7.7 27.7 21.5 16.7 - - -
72 61.3 6.9 40.5 34.0 27.5 21.0 - - 55.8 7.6 39.2 32.7 26.2 19.7 - -
1500
67 55.8 6.7 55.8 44.4 37.5 30.9 24.4 - 50.8 7.5 50.8 42.9 35.7 29.2 22.7 -
62 53.8 6.7 53.8 53.8 42.8 36.3 29.8 23.3 49.9 7.4 49.9 49.9 40.3 33.8 27.3 20.7
77 68.3 7.0 35.1 27.2 19.5 - - - 61.9 7.7 37.1 26.2 18.4 - - -
72 62.6 6.9 46.0 38.3 30.6 22.9 - - 56.8 7.6 44.4 36.7 28.9 21.2 - -
1800 67 57.0 6.8 57.0 49.4 41.7 34.0 26.3 - 51.8 7.5 51.8 47.2 39.4 31.7 23.9 -
62 55.0 6.7 55.0 55.0 47.6 39.9 32.2 24.5 50.9 7.4 50.9 50.9 44.5 36.7 29.0 21.3
57 54.7 6.7 54.7 54.5 46.8 39.1 31.4 23.6 50.5 7.4 50.5 50.5 43.2 35.5 27.8 20.0
77 69.8 7.0 45.0 30.9 21.5 - - - 63.1 7.7 46.5 30.8 20.2 - - -
72 64.0 6.9 51.6 42.6 33.7 24.8 - - 57.9 7.6 49.6 40.6 31.7 22.7 - -
2100 67 58.2 6.8 58.2 54.4 45.9 37.0 28.1 - 52.7 7.5 52.7 51.4 43.2 34.2 25.2 -
62 56.2 6.7 56.2 56.2 52.5 43.6 34.6 25.7 51.9 7.4 51.9 51.9 48.7 39.7 30.7 21.8
57 55.9 6.7 55.9 55.8 51.6 42.6 33.7 24.8 51.5 7.3 51.5 51.5 47.3 38.3 29.4 20.4
77 71.2 7.0 54.8 34.6 23.5 - - - 64.2 7.7 55.8 35.5 21.9 - - -
72 65.3 6.9 57.1 47.0 36.8 26.7 - - 59.0 7.6 54.8 44.6 34.4 24.2 - -
2400 67 59.4 6.8 59.4 59.4 50.2 40.1 29.9 - 53.7 7.5 53.7 53.7 46.9 36.7 26.5 -
62 57.3 6.7 57.3 57.3 57.3 47.2 37.1 26.9 52.8 7.4 52.8 52.8 52.8 42.7 32.5 22.3
57 57.1 6.7 57.1 57.1 56.3 46.2 36.1 25.9 52.5 7.3 52.5 52.5 51.4 41.2 31.0 20.8
72 65.2 7.0 61.1 50.7 39.2 27.7 - - 58.8 7.7 58.6 48.5 36.9 25.3 - -
67 59.3 6.9 59.3 59.3 53.4 41.9 30.5 - 53.6 7.6 53.6 53.6 50.2 38.7 27.1 -
2700
62 57.3 6.8 57.3 57.3 57.3 45.8 34.4 22.9 52.7 7.5 52.7 52.7 52.7 41.1 29.5 17.9
57 57.0 6.8 57.0 57.0 56.7 45.2 33.7 22.3 52.3 7.5 52.3 52.3 51.8 40.2 28.6 17.0
72 65.2 7.1 65.2 54.3 41.5 28.8 - - 58.6 7.8 58.6 52.4 39.4 26.3 - -
67 59.3 6.9 59.3 59.3 56.6 43.8 31.0 - 53.4 7.7 53.4 53.4 53.4 40.6 27.6 -
3000
62 57.2 6.9 57.2 57.2 57.2 44.4 31.7 18.9 52.6 7.6 52.6 52.6 52.6 39.6 26.6 13.6
57 57.0 6.8 57.0 57.0 57.0 44.2 31.4 18.6 52.2 7.6 52.2 52.2 52.2 39.2 26.2 13.2
1. These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat (MBH = 3.415 x kW). Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Ducted Systems 33
5147362-YTG-R-0323
XXE08 (7.5 ton)
Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBH) Total Total Sensible Capacity (MBH)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBH) (kW)2 (MBH) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 120.0 5.6 56.2 46.4 37.6 - - - 113.6 6.3 51.7 42.9 34.1 - - -
72 110.4 5.5 67.3 58.5 49.6 40.8 - - 104.2 6.2 64.1 55.3 46.5 37.7 - -
1875
67 100.9 5.3 78.4 70.5 61.7 52.9 44.1 - 94.9 6.1 76.5 67.7 58.9 50.1 41.3 -
62 93.8 5.3 93.8 93.8 87.2 76.8 67.9 59.1 87.4 6.1 87.4 83.9 70.8 62.0 53.2 44.4
77 123.4 5.6 61.2 51.0 40.9 - - - 116.8 6.3 57.5 47.4 37.3 - - -
72 113.6 5.5 74.3 64.2 54.0 43.9 - - 107.2 6.3 71.1 60.9 50.8 40.7 - -
2250 67 103.8 5.4 87.5 77.3 67.2 57.0 46.8 - 97.5 6.2 84.6 74.5 64.4 54.2 44.1 -
62 96.5 5.3 96.5 96.5 93.2 83.1 72.9 62.7 89.8 6.1 89.8 87.5 77.4 67.2 57.1 47.0
57 97.0 5.3 97.0 93.6 83.4 73.3 63.1 53.0 91.2 6.1 91.2 88.6 78.4 68.3 58.2 48.1
77 126.9 5.6 66.3 55.7 44.2 - - - 120.0 6.4 63.4 51.9 40.4 - - -
72 116.8 5.5 81.4 69.9 58.4 46.9 - - 110.1 6.3 78.0 66.6 55.1 43.7 - -
2625 67 106.7 5.4 96.6 84.1 72.6 61.1 49.6 - 100.2 6.2 92.7 81.3 69.8 58.4 46.9 -
62 99.2 5.3 99.2 99.2 99.2 89.4 77.9 66.4 92.3 6.1 92.3 91.1 83.9 72.5 61.0 49.5
57 99.7 5.3 99.7 98.0 90.2 78.7 67.2 55.7 93.7 6.1 93.7 92.4 85.1 73.6 62.2 50.7
77 130.3 5.7 71.3 60.4 47.5 - - - 123.2 6.4 69.2 56.4 43.6 - - -
72 120.0 5.6 88.5 75.6 62.8 49.9 - - 113.0 6.3 85.0 72.2 59.4 46.6 - -
3000 67 109.6 5.4 105.7 90.9 78.0 65.2 52.3 - 102.8 6.2 100.9 88.1 75.3 62.5 49.7 -
62 101.9 5.4 101.9 101.9 101.9 95.7 82.8 70.0 94.7 6.2 94.7 94.7 90.5 77.7 64.9 52.1
57 102.4 5.4 102.4 102.4 97.0 84.1 71.3 58.4 96.1 6.1 96.1 96.1 91.7 78.9 66.1 53.3
72 122.7 5.6 95.9 81.7 67.5 53.3 - - 115.2 6.3 91.8 77.8 63.7 49.6 - -
67 112.1 5.4 110.1 98.1 83.9 69.7 55.6 - 104.9 6.2 103.9 94.7 80.7 66.6 52.5 -
3375
62 104.2 5.4 104.2 104.2 104.2 97.5 83.3 69.1 96.6 6.2 96.6 96.6 94.5 80.4 66.3 52.3
57 104.7 5.4 104.7 104.7 102.0 87.8 73.6 59.4 98.1 6.1 98.1 98.1 95.9 81.8 67.7 53.6
72 125.4 5.6 103.3 87.8 72.3 56.7 - - 117.5 6.3 98.7 83.3 68.0 52.6 - -
67 114.5 5.4 114.5 105.3 89.8 74.3 58.8 - 106.9 6.2 106.9 101.4 86.1 70.7 55.4 -
3750
62 106.5 5.4 106.5 106.5 106.5 99.3 83.8 68.3 98.5 6.2 98.5 98.5 98.5 83.2 67.8 52.5
57 107.0 5.4 107.0 107.0 107.0 91.5 76.0 60.5 100.0 6.1 100.0 100.0 100.0 84.6 69.3 53.9
95°F 105°F
77 107.3 7.1 47.2 39.4 30.7 - - - 99.5 8.1 42.3 36.9 28.2 - - -
72 98.0 7.0 60.9 52.1 43.4 34.6 - - 90.9 8.0 58.0 49.4 40.7 32.1 - -
1875
67 88.8 7.0 74.6 64.9 56.1 47.3 38.6 - 82.3 7.9 73.8 61.9 53.2 44.5 35.9 -
62 81.0 6.9 78.7 64.8 56.0 47.3 38.5 29.8 77.0 7.9 75.8 67.8 56.5 47.9 39.2 30.6
77 110.2 7.1 53.8 43.8 33.7 - - - 102.0 8.1 51.1 41.1 31.1 - - -
72 100.7 7.0 67.8 57.7 47.6 37.5 - - 93.1 8.0 64.8 54.9 44.9 34.9 - -
2250 67 91.2 7.0 81.7 71.6 61.6 51.5 41.4 - 84.3 7.9 78.6 68.6 58.6 48.6 38.7 -
62 83.1 6.9 81.6 71.6 61.5 51.4 41.3 31.2 78.8 7.9 78.1 72.3 62.3 52.3 42.3 32.4
57 85.4 6.9 85.4 83.5 73.4 63.3 53.3 43.2 80.2 7.9 80.2 78.2 68.2 58.2 48.2 38.2
77 113.1 7.1 60.5 48.1 36.7 - - - 104.4 8.1 59.9 45.3 34.0 - - -
72 103.3 7.0 74.7 63.3 51.8 40.4 - - 95.3 8.0 71.7 60.3 49.0 37.7 - -
2625 67 93.6 7.0 88.9 78.4 67.0 55.6 44.2 - 86.3 7.9 83.5 75.4 64.1 52.7 41.4 -
62 85.3 6.9 84.6 78.3 66.9 55.5 44.1 32.7 80.7 7.9 80.3 76.9 68.1 56.8 45.5 34.1
57 87.6 6.9 87.6 86.7 79.9 68.5 57.1 45.7 82.1 7.9 82.1 81.1 74.5 63.2 51.8 40.5
77 116.0 7.1 67.1 52.4 39.7 - - - 106.8 8.1 68.7 49.5 36.8 - - -
72 106.0 7.1 81.6 68.8 56.1 43.3 - - 97.6 8.0 78.5 65.8 53.2 40.5 - -
3000 67 96.0 7.0 96.0 85.2 72.5 59.8 47.0 - 88.3 7.9 88.3 82.2 69.5 56.8 44.2 -
62 87.5 7.0 87.5 85.1 72.4 59.7 46.9 34.2 82.6 7.9 82.6 81.4 73.9 61.2 48.6 35.9
57 89.9 6.9 89.9 89.9 86.4 73.7 61.0 48.2 84.0 7.9 84.0 84.0 80.8 68.1 55.5 42.8
72 107.8 7.1 87.8 73.8 59.9 45.9 - - 99.3 8.0 84.4 70.6 56.7 42.9 - -
67 97.7 7.0 97.7 91.4 77.4 63.5 49.5 - 89.9 8.0 89.9 86.3 74.1 60.3 46.4 -
3375
62 89.0 7.0 89.0 87.8 77.3 63.3 49.4 35.4 84.0 7.9 84.0 83.4 77.6 63.8 49.9 36.1
57 91.4 6.9 91.4 91.4 89.7 75.7 61.8 47.8 85.5 7.9 85.5 85.5 83.9 70.0 56.1 42.3
72 109.6 7.1 94.0 78.9 63.7 48.5 - - 101.0 8.1 90.4 75.3 60.3 45.2 - -
67 99.3 7.0 99.3 97.5 82.3 67.1 52.0 - 91.4 8.0 91.4 90.5 78.8 63.7 48.7 -
3750
62 90.5 7.0 90.5 90.5 82.2 67.0 51.9 36.7 85.5 7.9 85.5 85.5 81.3 66.3 51.2 36.2
57 92.9 6.9 92.9 92.9 92.9 77.8 62.6 47.4 86.9 7.9 86.9 86.9 86.9 71.9 56.8 41.8
34 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XXE08 (7.5 ton) (Continued)
Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBH) Total Total Sensible Capacity (MBH)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBH) (kW)2 (MBH) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 91.8 9.2 37.3 34.3 25.7 - - - 84.0 10.2 35.3 30.2 23.3 - - -
72 83.8 9.1 55.1 46.6 38.0 29.5 - - 76.6 10.1 52.3 43.8 35.3 26.9 - -
1875
67 75.7 8.9 72.9 58.9 50.3 41.7 33.2 - 69.2 9.9 69.2 55.9 47.4 39.0 30.5 -
62 73.0 8.9 73.0 70.8 57.0 48.5 39.9 31.4 69.0 9.9 69.0 69.0 57.6 49.1 40.6 32.2
77 93.7 9.2 48.3 38.4 28.5 - - - 85.5 10.2 47.5 35.7 25.9 - - -
72 85.5 9.0 61.9 52.0 42.1 32.2 - - 78.0 10.0 59.0 49.2 39.3 29.5 - -
2250 67 77.4 8.9 75.5 65.6 55.7 45.8 35.9 - 70.4 9.9 70.4 62.6 52.8 43.0 33.2 -
62 74.5 8.9 74.5 73.1 63.2 53.3 43.4 33.5 70.2 9.9 70.2 70.2 64.0 54.2 44.4 34.6
57 75.0 8.9 75.0 72.8 62.9 53.0 43.1 33.2 69.8 9.9 69.8 67.5 57.7 47.9 38.1 28.3
77 95.7 9.1 59.3 42.5 31.3 - - - 87.0 10.2 59.7 41.3 28.6 - - -
72 87.3 9.0 68.7 57.4 46.2 34.9 - - 79.3 10.0 65.7 54.5 43.4 32.2 - -
2625 67 79.0 8.9 78.0 72.3 61.1 49.9 38.6 - 71.7 9.9 71.7 69.3 58.1 47.0 35.8 -
62 76.1 8.9 76.1 75.4 69.3 58.0 46.8 35.6 71.5 9.8 71.5 71.5 70.5 59.3 48.1 37.0
57 76.5 8.9 76.5 75.5 69.0 57.8 46.5 35.3 71.0 9.9 71.0 69.9 63.6 52.4 41.3 30.1
77 97.6 9.1 70.3 46.6 34.0 - - - 88.5 10.1 71.9 46.9 31.2 - - -
72 89.1 9.0 75.4 62.9 50.3 37.7 - - 80.7 10.0 72.4 59.9 47.4 34.8 - -
3000 67 80.6 8.9 80.6 79.1 66.5 53.9 41.3 - 72.9 9.8 72.9 72.9 63.5 51.0 38.5 -
62 77.7 8.9 77.7 77.7 75.4 62.8 50.2 37.6 72.7 9.8 72.7 72.7 72.7 64.4 51.9 39.4
57 78.1 8.9 78.1 78.1 75.1 62.5 50.0 37.4 72.2 9.8 72.2 72.2 69.5 57.0 44.4 31.9
72 90.7 9.0 81.1 67.3 53.6 39.8 - - 82.2 10.0 77.7 64.1 50.4 36.8 - -
67 82.0 8.9 82.0 81.3 70.9 57.1 43.4 - 74.2 9.9 74.2 74.2 67.6 53.9 40.3 -
3375
62 79.1 8.9 79.1 79.1 77.9 64.2 50.4 36.7 74.1 9.8 74.1 74.1 74.1 64.6 50.9 37.3
57 79.5 8.9 79.5 79.5 78.0 64.3 50.5 36.8 73.6 9.9 73.6 73.6 72.2 58.5 44.9 31.2
72 92.3 9.1 86.7 71.8 56.9 42.0 - - 83.7 10.1 83.0 68.2 53.5 38.7 - -
67 83.5 8.9 83.5 83.5 75.2 60.3 45.4 - 75.6 9.9 75.6 75.6 71.7 56.9 42.1 -
3750
62 80.4 8.9 80.4 80.4 80.4 65.5 50.6 35.7 75.4 9.9 75.4 75.4 75.4 64.8 50.0 35.2
57 80.9 8.9 80.9 80.9 80.9 66.0 51.1 36.2 74.9 9.9 74.9 74.9 74.9 60.1 45.3 30.5
1. These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat (MBH = 3.415 x kW). Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Ducted Systems 35
5147362-YTG-R-0323
XXE09 (8.5 ton)
Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBH) Total Total Sensible Capacity (MBH)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBH) (kW)2 (MBH) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 133.7 5.9 60.4 49.9 40.4 - - - 122.4 6.7 56.1 46.5 36.9 - - -
72 122.6 5.8 72.9 63.5 54.0 44.6 - - 113.0 6.6 70.1 60.5 50.9 41.3 - -
2125
67 111.5 5.7 85.4 77.1 67.6 58.1 48.7 - 103.6 6.6 84.1 74.5 64.9 55.3 45.8 -
62 102.4 5.7 102.4 91.5 79.4 69.9 60.5 51.0 94.6 6.5 94.6 89.1 75.8 66.2 56.7 47.1
77 137.0 5.9 65.7 54.9 44.0 - - - 126.1 6.8 62.3 51.3 40.3 - - -
72 125.7 5.8 80.5 69.7 58.8 48.0 - - 116.4 6.7 77.6 66.6 55.6 44.6 - -
2550 67 114.3 5.8 95.3 84.5 73.6 62.8 51.9 - 106.7 6.6 92.9 81.9 70.9 59.9 48.8 -
62 105.0 5.7 105.0 97.7 86.5 75.6 64.8 53.9 97.4 6.6 97.4 93.8 82.8 71.8 60.7 49.7
57 103.4 5.7 103.4 101.5 90.6 79.7 68.9 58.0 98.1 6.5 98.1 97.0 86.0 75.0 63.9 52.9
77 140.4 6.0 71.1 59.9 47.6 - - - 129.7 6.8 68.5 56.1 43.7 - - -
72 128.8 5.9 88.1 75.9 63.6 51.4 - - 119.8 6.7 85.1 72.7 60.2 47.8 - -
2975 67 117.1 5.8 105.2 91.9 79.6 67.4 55.1 - 109.8 6.6 101.7 89.3 76.8 64.4 51.9 -
62 107.6 5.8 107.6 103.9 93.5 81.3 69.0 56.8 100.2 6.6 100.2 98.4 89.7 77.3 64.8 52.4
57 105.9 5.7 105.9 104.9 98.0 85.8 73.5 61.2 101.0 6.6 101.0 100.4 93.2 80.7 68.3 55.8
77 143.8 6.0 76.4 64.9 51.2 - - - 133.4 6.8 74.8 60.9 47.0 - - -
72 131.8 5.9 95.8 82.1 68.4 54.8 - - 123.1 6.8 92.6 78.8 64.9 51.0 - -
3400 67 119.9 5.9 115.1 99.3 85.7 72.0 58.3 - 112.9 6.7 110.5 96.6 82.8 68.9 55.0 -
62 110.1 5.8 110.1 110.1 100.6 87.0 73.3 59.6 103.0 6.6 103.0 103.0 96.6 82.8 68.9 55.0
57 108.4 5.8 108.4 108.4 105.4 91.8 78.1 64.5 103.8 6.6 103.8 103.8 100.4 86.5 72.6 58.8
72 132.2 5.9 100.7 86.2 71.7 57.2 - - 125.1 6.8 98.3 83.5 68.6 53.7 - -
67 120.2 5.9 117.8 104.2 89.7 75.2 60.7 - 114.7 6.7 113.5 102.3 87.5 72.6 57.7 -
3825
62 110.4 5.8 110.4 110.4 105.7 91.2 76.7 62.1 104.7 6.6 104.7 104.7 101.5 86.6 71.7 56.8
57 108.6 5.8 108.6 108.6 107.1 92.6 78.1 63.6 105.5 6.6 105.5 105.5 103.8 88.9 74.0 59.1
72 132.6 6.0 105.7 90.3 75.0 59.6 - - 127.1 6.8 104.0 88.2 72.3 56.4 - -
67 120.5 5.9 120.5 109.1 93.7 78.4 63.0 - 116.5 6.7 116.5 108.0 92.2 76.3 60.4 -
4250
62 110.7 5.8 110.7 110.7 110.7 95.4 80.0 64.6 106.3 6.6 106.3 106.3 106.3 90.4 74.6 58.7
57 108.9 5.8 108.9 108.9 108.9 93.5 78.1 62.8 107.1 6.6 107.1 107.1 107.1 91.2 75.4 59.5
95°F 105°F
77 111.2 7.6 51.7 43.1 33.4 - - - 101.6 8.5 46.7 40.0 30.3 - - -
72 103.5 7.5 67.2 57.5 47.8 38.1 - - 94.6 8.5 63.8 54.1 44.4 34.7 - -
2125
67 95.8 7.4 82.7 71.9 62.2 52.5 42.8 - 87.5 8.4 81.0 68.2 58.5 48.7 39.0 -
62 86.8 7.4 86.8 86.8 72.2 62.5 52.8 43.2 79.1 8.3 79.1 79.1 66.6 56.9 47.1 37.4
77 115.1 7.6 58.9 47.7 36.5 - - - 105.7 8.6 56.1 44.7 33.4 - - -
72 107.1 7.5 74.6 63.5 52.3 41.2 - - 98.4 8.5 71.4 60.2 48.9 37.7 - -
2550 67 99.1 7.5 90.4 79.3 68.1 56.9 45.8 - 91.1 8.4 86.7 75.7 64.4 53.2 41.9 -
62 89.8 7.4 89.8 89.8 79.0 67.9 56.7 45.6 82.3 8.4 82.3 82.3 73.4 62.2 50.9 39.7
57 92.9 7.4 92.9 92.5 81.3 70.2 59.0 47.8 84.8 8.4 84.8 84.6 74.8 63.6 52.3 41.1
77 119.1 7.6 66.0 52.3 39.7 - - - 109.8 8.6 65.6 49.3 36.5 - - -
72 110.8 7.5 82.1 69.5 56.8 44.2 - - 102.2 8.5 79.0 66.3 53.5 40.7 - -
2975 67 102.5 7.5 98.2 86.6 74.0 61.3 48.7 - 94.6 8.5 92.5 83.2 70.4 57.7 44.9 -
62 92.9 7.4 92.9 92.9 85.9 73.2 60.6 48.0 85.5 8.4 85.5 85.5 80.2 67.5 54.7 41.9
57 96.1 7.4 96.1 95.9 88.3 75.7 63.1 50.4 88.1 8.4 88.1 88.0 81.8 69.0 56.2 43.4
77 123.0 7.6 73.2 56.9 42.8 - - - 113.9 8.6 75.1 53.9 39.6 - - -
72 114.4 7.6 89.5 75.4 61.3 47.2 - - 106.1 8.6 86.6 72.3 58.0 43.7 - -
3400 67 105.9 7.5 105.9 93.9 79.8 65.7 51.6 - 98.2 8.5 98.2 90.7 76.4 62.1 47.8 -
62 95.9 7.5 95.9 95.9 92.7 78.6 64.5 50.4 88.7 8.4 88.7 88.7 87.1 72.7 58.4 44.1
57 99.2 7.4 99.2 99.2 95.3 81.2 67.1 53.0 91.4 8.4 91.4 91.4 88.7 74.4 60.1 45.8
72 118.0 7.6 96.0 80.7 65.5 50.2 - - 106.8 8.6 92.1 76.8 61.4 46.1 - -
67 109.2 7.5 109.2 100.5 85.2 69.9 54.7 - 98.9 8.5 98.9 93.8 80.9 65.6 50.3 -
3825
62 98.9 7.5 98.9 98.9 97.3 82.0 66.8 51.5 89.3 8.4 89.3 89.3 88.5 73.2 57.8 42.5
57 102.3 7.5 102.3 102.3 100.4 85.1 69.9 54.6 92.0 8.4 92.0 92.0 90.7 75.4 60.0 44.7
72 121.6 7.6 102.4 86.0 69.6 53.2 - - 107.5 8.6 97.5 81.2 64.8 48.5 - -
67 112.5 7.5 112.5 107.0 90.6 74.2 57.7 - 99.5 8.5 99.5 96.8 85.4 69.1 52.7 -
4250
62 101.9 7.5 101.9 101.9 101.9 85.5 69.1 52.7 89.9 8.5 89.9 89.9 89.9 73.6 57.2 40.9
57 105.4 7.5 105.4 105.4 105.4 89.0 72.6 56.2 92.7 8.4 92.7 92.7 92.7 76.3 60.0 43.6
36 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XXE09 (8.5 ton) (Continued)
Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBH) Total Total Sensible Capacity (MBH)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBH) (kW)2 (MBH) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 91.9 9.5 41.6 37.0 27.2 - - - 82.3 10.5 43.1 33.2 24.2 - - -
72 85.6 9.4 60.5 50.7 41.0 31.2 - - 76.7 10.4 57.1 47.3 37.5 27.7 - -
2125
67 79.3 9.3 79.3 64.4 54.7 44.9 35.1 - 71.1 10.3 71.1 60.7 50.9 41.1 31.3 -
62 71.4 9.3 71.4 71.4 61.0 51.2 41.4 31.7 63.7 10.2 63.7 63.7 55.3 45.5 35.7 25.9
77 96.3 9.5 53.4 41.6 30.3 - - - 86.8 10.5 55.1 38.6 27.2 - - -
72 89.6 9.5 68.2 56.9 45.5 34.2 - - 80.9 10.4 65.0 53.6 42.1 30.7 - -
2550 67 83.0 9.4 83.0 72.1 60.8 49.4 38.1 - 75.0 10.3 75.0 68.6 57.1 45.7 34.2 -
62 74.7 9.3 74.7 74.7 67.8 56.4 45.1 33.7 67.2 10.2 67.2 67.2 62.2 50.7 39.3 27.8
57 76.6 9.3 76.6 76.6 68.3 57.0 45.6 34.3 68.5 10.3 68.5 68.5 61.8 50.4 38.9 27.5
77 100.6 9.6 65.2 46.3 33.3 - - - 91.3 10.6 67.0 44.0 30.2 - - -
72 93.7 9.5 76.0 63.1 50.1 37.2 - - 85.1 10.5 72.9 59.9 46.8 33.7 - -
2975 67 86.8 9.4 86.8 79.8 66.9 54.0 41.0 - 78.9 10.4 78.9 76.5 63.4 50.3 37.2 -
62 78.1 9.3 78.1 78.1 74.6 61.7 48.7 35.8 70.7 10.3 70.7 70.7 69.0 55.9 42.8 29.7
57 80.1 9.3 80.1 80.1 75.2 62.3 49.3 36.4 72.1 10.3 72.1 72.1 68.6 55.6 42.5 29.4
77 104.9 9.6 77.0 50.9 36.4 - - - 95.8 10.6 78.9 49.5 33.2 - - -
72 97.7 9.5 83.7 69.2 54.7 40.2 - - 89.3 10.5 80.9 66.1 51.4 36.7 - -
3400 67 90.5 9.5 90.5 87.5 73.0 58.5 44.0 - 82.8 10.4 82.8 82.8 69.6 54.9 40.1 -
62 81.4 9.4 81.4 81.4 81.4 66.9 52.4 37.9 74.2 10.3 74.2 74.2 74.2 61.1 46.4 31.6
57 83.5 9.4 83.5 83.5 82.1 67.6 53.0 38.5 75.7 10.4 75.7 75.7 75.5 60.7 46.0 31.3
72 95.6 9.6 88.2 72.8 57.4 42.0 - - 84.4 10.5 84.4 68.9 53.4 37.9 - -
67 88.5 9.5 88.5 87.1 76.6 61.2 45.8 - 78.2 10.5 78.2 78.2 72.4 56.9 41.4 -
3825
62 79.7 9.4 79.7 79.7 79.7 64.3 48.9 33.5 70.1 10.4 70.1 70.1 70.1 55.4 39.9 24.4
57 81.7 9.4 81.7 81.7 81.0 65.6 50.2 34.8 71.4 10.4 71.4 71.4 71.3 55.8 40.3 24.9
72 93.5 9.6 92.7 76.4 60.1 43.8 - - 79.4 10.6 79.4 71.6 55.4 39.2 - -
67 86.6 9.5 86.6 86.6 80.3 64.0 47.7 - 73.6 10.5 73.6 73.6 73.6 58.9 42.6 -
4250
62 77.9 9.4 77.9 77.9 77.9 61.6 45.3 29.0 65.9 10.4 65.9 65.9 65.9 49.7 33.5 17.2
57 79.9 9.4 79.9 79.9 79.9 63.6 47.3 31.0 67.1 10.4 67.1 67.1 67.1 50.9 34.7 18.4
1. These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat (MBH = 3.415 x kW). Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Ducted Systems 37
5147362-YTG-R-0323
XXE12 (10 ton)
Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBH) Total Total Sensible Capacity (MBH)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBH) (kW)2 (MBH) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 153.4 7.2 82.3 68.6 54.9 - - - 145.4 8.3 77.5 64.4 51.2 - - -
72 140.1 7.1 94.7 81.2 67.6 54.0 - - 131.6 8.1 91.0 77.5 63.9 50.4 - -
2500
67 126.8 6.9 107.2 93.7 80.2 65.7 53.5 - 117.8 8.0 104.5 90.6 76.6 62.7 49.9 -
62 117.7 6.8 117.7 105.4 92.9 76.2 66.5 53.3 108.9 7.9 108.9 101.6 89.3 74.4 62.9 49.8
77 156.1 7.2 90.5 72.8 55.0 - - - 147.2 8.3 85.9 68.5 51.1 - - -
72 143.7 7.1 103.0 87.0 71.0 54.9 - - 134.9 8.1 98.9 82.9 67.0 51.1 - -
3000 67 131.3 7.0 115.5 101.2 86.9 69.9 54.7 - 122.6 8.0 110.6 97.4 82.9 66.5 50.9 -
62 123.8 6.9 116.2 113.5 102.8 83.9 70.5 54.3 115.3 7.9 111.0 109.1 98.8 81.4 66.7 50.6
57 116.3 6.8 116.3 116.3 116.3 102.5 86.2 70.0 111.2 7.8 111.2 111.2 111.2 98.6 82.5 66.3
77 158.8 7.2 98.8 76.9 55.1 - - - 148.9 8.2 94.4 72.7 51.0 - - -
72 147.3 7.1 111.3 92.8 74.3 55.8 - - 138.2 8.1 106.7 88.4 70.1 51.8 - -
3500 67 135.8 7.0 123.8 108.7 93.6 74.1 55.9 - 127.4 8.0 115.1 104.2 89.2 70.3 52.0 -
62 129.8 7.0 123.8 121.6 112.8 91.5 74.4 55.3 121.6 8.0 115.7 115.7 108.3 88.4 70.5 51.5
57 123.9 7.0 123.9 123.9 123.9 112.5 93.0 73.5 115.8 7.9 115.8 115.8 115.8 108.2 88.9 69.7
77 161.5 7.2 107.0 81.1 55.2 - - - 150.6 8.2 102.8 76.9 50.9 - - -
72 150.9 7.2 119.6 98.6 77.7 56.8 - - 141.4 8.1 114.6 93.9 73.2 52.6 - -
4000 67 140.3 7.1 130.5 116.2 100.2 78.2 57.1 - 132.2 8.1 123.0 111.0 95.6 74.1 53.1 -
62 135.9 7.1 131.0 129.6 122.8 99.2 78.4 56.3 128.0 8.0 123.2 123.2 117.9 95.4 74.2 52.4
57 131.4 7.1 131.4 131.4 131.4 122.5 99.7 77.0 123.7 8.0 123.7 123.7 123.7 117.8 95.4 73.0
72 154.5 7.2 127.9 104.5 81.1 57.7 - - 144.7 8.1 122.5 99.4 76.4 53.3 - -
67 144.9 7.1 140.5 123.7 106.9 82.4 58.4 - 137.0 8.1 131.0 117.8 101.9 77.9 54.1 -
4500
62 141.9 7.1 141.9 137.7 132.7 106.9 82.4 57.3 134.3 8.1 131.5 131.5 127.4 102.3 78.0 53.3
57 139.0 7.1 142.4 142.4 142.4 132.5 106.5 80.5 131.6 8.1 131.6 131.6 131.6 127.4 101.9 76.3
72 158.1 7.2 136.1 110.3 84.5 58.6 - - 147.9 8.1 130.3 104.9 79.5 54.0 - -
67 149.4 7.2 146.0 131.2 113.6 86.6 59.6 - 141.8 8.1 139.0 124.6 108.2 81.7 55.2 -
5000
62 148.0 7.2 146.1 145.7 142.7 114.5 86.4 58.3 140.7 8.0 139.3 138.9 136.9 109.3 81.7 54.2
57 146.6 7.2 146.6 146.6 146.6 142.5 113.2 83.9 139.5 8.0 139.5 139.5 139.5 137.0 108.3 79.7
95°F 105°F
77 137.5 9.4 72.7 60.1 47.5 - - - 126.8 10.6 70.3 57.2 44.1 - - -
72 123.2 9.2 87.2 73.7 60.2 46.7 - - 114.6 10.4 84.3 70.7 57.1 43.5 - -
2500
67 108.9 9.0 101.0 87.4 73.0 59.7 46.3 - 102.4 10.2 96.2 84.2 70.1 56.5 42.8 -
62 101.3 8.9 101.3 97.8 85.7 72.6 59.4 46.2 97.5 10.2 97.5 93.2 83.1 69.4 55.6 41.8
77 138.2 9.3 81.4 64.3 47.2 - - - 127.7 10.6 78.7 61.0 43.2 - - -
72 126.1 9.2 94.7 78.9 63.1 47.3 - - 117.2 10.4 91.1 75.3 59.5 43.7 - -
3000 67 114.0 9.0 100.6 93.5 79.0 63.1 47.2 - 106.7 10.3 98.0 89.5 75.7 59.6 43.5 -
62 106.7 8.9 100.7 100.7 94.8 78.9 62.9 47.0 102.9 10.2 98.6 98.6 91.9 75.5 59.2 42.8
57 100.9 8.8 100.9 100.9 100.9 94.7 78.7 62.7 99.1 10.2 99.1 99.1 99.1 91.5 74.8 58.1
77 139.0 9.3 90.0 68.5 47.0 - - - 128.7 10.5 87.1 64.7 42.4 - - -
72 129.0 9.2 102.2 84.0 65.9 47.8 - - 119.9 10.4 97.9 79.8 61.8 43.8 - -
3500 67 119.1 9.0 110.0 99.6 84.9 66.5 48.1 - 111.1 10.3 104.8 94.9 81.2 62.7 44.2 -
62 113.4 9.0 110.2 110.2 103.9 85.2 66.5 47.8 108.3 10.2 105.0 105.0 100.7 81.7 62.7 43.7
57 110.6 8.9 110.6 110.6 110.6 103.9 84.9 65.9 105.5 10.2 105.5 105.5 105.5 100.6 81.2 61.7
77 139.7 9.2 98.6 72.7 46.7 - - - 129.7 10.5 95.4 68.5 41.5 - - -
72 131.9 9.1 109.6 89.2 68.8 48.4 - - 122.6 10.4 104.7 84.4 64.2 43.9 - -
4000 67 124.1 9.1 114.6 105.7 90.9 69.9 49.0 - 115.5 10.3 110.9 100.3 86.8 65.9 45.0 -
62 120.0 9.0 114.9 114.9 113.0 91.5 70.0 48.5 113.7 10.3 111.5 111.5 109.4 87.8 66.3 44.7
57 115.9 8.9 115.9 115.9 115.9 113.1 91.1 69.1 111.9 10.2 111.9 111.9 111.9 109.8 87.5 65.3
72 134.8 9.1 117.1 94.3 71.6 48.9 - - 125.2 10.4 111.5 89.0 66.5 44.1 - -
67 129.2 9.1 123.0 111.9 96.8 73.3 49.9 - 119.8 10.4 117.7 105.7 92.4 69.0 45.7 -
4500
62 126.7 9.0 124.0 124.0 122.0 97.8 73.6 49.3 119.1 10.3 118.0 118.0 118.0 94.0 69.8 45.6
57 124.2 9.0 124.2 124.2 124.2 122.2 97.2 72.2 118.4 10.3 118.4 118.4 118.4 118.4 93.9 68.9
72 137.8 9.1 124.5 99.5 74.5 49.4 - - 127.9 10.4 118.3 93.6 68.9 44.2 - -
67 134.3 9.1 131.3 118.0 102.8 76.8 50.7 - 124.8 10.4 123.9 111.1 97.9 72.2 46.4 -
5000
62 133.3 9.1 132.0 132.0 131.1 104.1 77.1 50.1 124.5 10.4 124.0 124.0 124.0 100.2 73.4 46.6
57 132.4 9.1 132.4 132.4 132.4 131.4 103.4 75.4 124.2 10.3 124.2 124.2 124.2 124.2 100.3 72.5
38 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XXE12 (10 ton) (Continued)
Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBH) Total Total Sensible Capacity (MBH)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBH) (kW)2 (MBH) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 116.1 11.9 67.9 54.3 40.7 - - - 105.4 13.1 65.6 51.4 37.3 - - -
72 105.9 11.6 81.3 67.6 54.0 40.3 - - 97.3 12.9 78.3 64.6 50.8 37.1 - -
2500
67 95.8 11.4 94.6 80.9 67.3 53.2 39.2 - 92.2 12.6 88.6 77.7 64.4 50.0 35.7 -
62 94.9 11.5 94.9 88.7 80.5 66.2 51.8 37.4 89.3 12.8 89.3 84.1 77.9 63.0 48.0 33.0
77 117.3 11.8 76.1 57.7 39.3 - - - 106.8 13.1 73.4 54.3 35.3 - - -
72 108.4 11.7 87.4 71.6 55.8 40.1 - - 99.5 12.9 83.8 68.0 52.2 36.4 - -
3000 67 99.5 11.5 97.6 85.6 72.4 56.1 39.8 - 97.4 12.7 91.7 81.6 69.1 52.6 36.1 -
62 99.0 11.5 98.2 94.7 89.0 72.2 55.4 38.6 95.2 12.8 92.1 89.7 86.1 68.8 51.6 34.3
57 98.6 11.5 98.6 98.6 98.6 88.2 70.9 53.6 92.2 12.9 92.2 92.2 92.2 85.0 67.0 49.0
77 118.4 11.8 84.2 61.0 37.8 - - - 108.2 13.0 81.3 57.3 33.3 - - -
72 110.8 11.7 93.6 75.6 57.7 39.8 - - 101.7 12.9 89.3 71.4 53.6 35.8 - -
3500 67 103.3 11.6 102.9 90.3 77.6 59.0 40.4 - 101.1 12.8 94.0 85.6 73.9 55.2 36.5 -
62 103.2 11.5 103.0 100.7 97.4 78.2 58.9 39.7 98.1 12.8 94.8 94.8 94.2 74.7 55.2 35.6
57 103.1 11.5 103.1 103.1 103.1 97.4 77.5 57.6 95.2 12.8 95.2 95.2 95.2 94.1 73.8 53.4
77 119.6 11.7 92.3 64.3 36.4 - - - 109.6 13.0 89.1 60.2 31.3 - - -
72 113.2 11.7 99.7 79.6 59.6 39.5 - - 103.9 13.0 94.7 74.8 55.0 35.1 - -
4000 67 107.9 11.6 105.9 94.9 82.7 61.8 41.0 - 102.2 12.9 98.8 89.5 78.7 57.8 37.0 -
62 107.4 11.6 106.0 106.0 105.9 84.2 62.5 40.8 101.0 12.9 99.5 99.5 99.5 80.5 58.7 36.9
57 106.5 11.5 106.5 106.5 106.5 106.5 84.0 61.5 100.1 12.8 100.0 100.0 100.0 100.0 80.5 57.8
72 115.6 11.7 105.8 83.6 61.4 39.2 - - 106.8 13.0 100.2 78.3 56.3 34.4 - -
67 112.6 11.7 108.9 99.6 87.9 64.7 41.5 - 106.0 13.0 100.6 93.5 83.4 60.4 37.4 -
4500
62 111.5 11.6 110.0 110.0 110.0 90.2 66.1 41.9 104.0 12.9 101.0 101.0 101.0 86.4 62.3 38.3
57 110.2 11.5 110.2 110.2 110.2 110.2 90.6 65.5 101.9 12.8 101.7 101.7 101.7 101.7 87.3 62.2
72 118.1 11.7 112.0 87.6 63.3 38.9 - - 109.7 13.0 103.6 81.7 57.7 33.7 - -
67 117.0 11.8 112.6 104.3 93.0 67.6 42.1 - 108.2 13.1 104.0 97.4 88.2 63.0 37.8 -
5000
62 115.7 11.7 112.9 112.9 112.9 96.2 69.6 43.1 106.9 12.9 104.5 104.5 104.5 92.3 65.9 39.6
57 113.2 11.5 113.2 113.2 113.2 113.2 97.2 69.5 104.8 12.7 104.8 104.8 104.8 104.8 94.0 66.5
1. These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat (MBH = 3.415 x kW). Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Ducted Systems 39
5147362-YTG-R-0323
XQE04 (3 ton)
Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBH) Total Total Sensible Capacity (MBH)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBH) (kW)2 (MBH) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 49.1 2.0 23.0 18.6 15.0 - - - 45.0 2.4 20.4 16.9 13.3 - - -
72 44.8 2.0 27.2 23.6 20.0 16.4 - - 41.3 2.4 25.4 21.9 18.3 14.7 - -
750
67 40.5 2.0 31.5 28.6 25.0 21.4 17.8 - 37.6 2.4 30.4 26.9 23.3 19.7 16.2 -
62 36.9 2.0 36.9 35.4 29.9 26.3 22.7 19.1 34.2 2.4 34.2 33.5 28.0 24.4 20.8 17.3
77 50.0 2.1 24.5 20.3 16.2 - - - 46.0 2.4 22.8 18.6 14.4 - - -
72 45.7 2.1 29.8 25.7 21.5 17.3 - - 42.2 2.4 28.2 24.0 19.9 15.7 - -
900 67 41.3 2.1 35.2 31.0 26.9 22.7 18.5 - 38.4 2.4 33.6 29.4 25.3 21.1 17.0 -
62 37.6 2.1 37.6 36.7 32.2 28.0 23.9 19.7 35.0 2.4 35.0 34.5 30.3 26.2 22.0 17.9
57 37.1 2.0 37.1 37.1 33.2 29.1 24.9 20.7 34.8 2.3 34.8 34.8 30.9 26.8 22.6 18.5
77 51.0 2.1 26.0 22.0 17.3 - - - 47.0 2.4 25.1 20.3 15.6 - - -
72 46.5 2.1 32.5 27.8 23.0 18.3 - - 43.1 2.4 30.9 26.2 21.4 16.7 - -
1050 67 42.1 2.1 38.9 33.5 28.7 24.0 19.3 - 39.3 2.4 36.8 32.0 27.3 22.5 17.8 -
62 38.4 2.1 38.4 37.9 34.4 29.7 25.0 20.3 35.7 2.4 35.7 35.5 32.7 28.0 23.2 18.5
57 37.8 2.1 37.8 37.8 35.6 30.9 26.1 21.4 35.6 2.3 35.6 35.6 33.4 28.6 23.9 19.1
77 51.9 2.1 27.6 23.8 18.5 - - - 48.0 2.4 27.4 22.1 16.7 - - -
72 47.4 2.1 35.1 29.8 24.5 19.3 - - 44.0 2.4 33.7 28.4 23.0 17.6 - -
1200 67 42.9 2.1 42.7 35.9 30.6 25.3 20.0 - 40.1 2.4 40.0 34.6 29.3 23.9 18.5 -
62 39.1 2.1 39.1 39.1 36.7 31.4 26.1 20.8 36.5 2.4 36.5 36.5 35.1 29.8 24.4 19.0
57 38.5 2.1 38.5 38.5 37.9 32.6 27.3 22.1 36.3 2.3 36.3 36.3 35.8 30.5 25.1 19.7
72 47.6 2.1 37.4 31.5 25.6 19.7 - - 44.1 2.4 35.8 29.8 23.9 17.9 - -
67 43.1 2.1 43.0 37.8 32.0 26.1 20.2 - 40.2 2.4 40.1 36.3 30.4 24.4 18.5 -
1350
62 39.2 2.1 39.2 39.2 38.1 32.2 26.3 20.4 36.6 2.4 36.6 36.6 35.9 29.9 24.0 18.0
57 38.7 2.1 38.7 38.7 38.4 32.5 26.6 20.7 36.4 2.4 36.4 36.4 36.2 30.2 24.2 18.3
72 47.8 2.1 39.6 33.1 26.7 20.2 - - 44.3 2.4 37.8 31.3 24.7 18.2 - -
67 43.2 2.1 43.2 39.8 33.3 26.8 20.3 - 40.3 2.4 40.3 38.0 31.5 24.9 18.4 -
1500
62 39.4 2.1 39.4 39.4 39.4 32.9 26.5 20.0 36.7 2.4 36.7 36.7 36.7 30.1 23.6 17.0
57 38.8 2.1 38.8 38.8 38.8 32.4 25.9 19.4 36.5 2.4 36.5 36.5 36.5 30.0 23.4 16.9
95°F 105°F
77 41.0 2.8 17.9 15.1 11.6 - - - 38.3 3.1 15.7 13.9 10.4 - - -
72 37.8 2.7 23.6 20.1 16.6 13.1 - - 35.1 3.1 22.3 18.8 15.3 11.8 - -
750
67 34.7 2.7 29.4 25.1 21.6 18.1 14.6 - 32.0 3.0 29.0 23.7 20.2 16.7 13.2 -
62 31.6 2.7 31.6 31.6 26.0 22.5 19.0 15.5 29.6 3.1 29.6 29.6 23.9 20.3 16.8 13.3
77 42.0 2.7 21.0 16.9 12.7 - - - 39.1 3.1 19.8 15.6 11.4 - - -
72 38.8 2.7 26.5 22.4 18.2 14.1 - - 35.9 3.1 25.2 21.0 16.9 12.7 - -
900 67 35.6 2.7 32.0 27.9 23.7 19.6 15.4 - 32.7 3.0 30.6 26.5 22.3 18.1 13.9 -
62 32.4 2.7 32.4 32.4 28.5 24.4 20.2 16.1 30.2 3.0 30.2 30.2 26.3 22.1 18.0 13.8
57 32.6 2.7 32.6 32.6 28.7 24.5 20.4 16.2 30.4 3.0 30.4 30.4 26.3 22.2 18.0 13.8
77 43.0 2.7 24.2 18.6 13.8 - - - 39.9 3.1 23.9 17.3 12.5 - - -
72 39.7 2.7 29.4 24.6 19.8 15.0 - - 36.6 3.0 28.1 23.3 18.4 13.6 - -
1050 67 36.4 2.6 34.7 30.6 25.8 21.0 16.2 - 33.3 3.0 32.3 29.2 24.4 19.5 14.7 -
62 33.1 2.7 33.1 33.1 31.0 26.2 21.4 16.6 30.8 3.0 30.8 30.8 28.8 23.9 19.1 14.3
57 33.4 2.6 33.4 33.4 31.2 26.4 21.6 16.8 31.0 3.0 31.0 31.0 28.8 24.0 19.1 14.3
77 44.1 2.7 27.3 20.4 15.0 - - - 40.7 3.0 27.9 19.0 13.5 - - -
72 40.7 2.7 32.3 26.9 21.4 16.0 - - 37.3 3.0 31.0 25.5 20.0 14.5 - -
1200 67 37.3 2.6 37.3 33.3 27.9 22.5 17.0 - 34.0 3.0 34.0 31.9 26.4 20.9 15.5 -
62 33.9 2.6 33.9 33.9 33.5 28.1 22.7 17.2 31.5 3.0 31.5 31.5 31.2 25.7 20.2 14.7
57 34.2 2.6 34.2 34.2 33.7 28.3 22.8 17.4 31.6 3.0 31.6 31.6 31.2 25.7 20.3 14.8
72 40.7 2.7 34.2 28.1 22.1 16.1 - - 37.5 3.0 32.9 26.8 20.7 14.6 - -
67 37.3 2.6 37.3 34.8 28.8 22.7 16.7 - 34.2 3.0 34.2 32.9 27.4 21.3 15.2 -
1350
62 33.9 2.7 33.9 33.9 33.7 27.7 21.7 15.7 31.6 3.0 31.6 31.6 31.5 25.4 19.3 13.2
57 34.2 2.6 34.2 34.2 33.9 27.9 21.9 15.9 31.7 3.0 31.7 31.7 31.6 25.5 19.4 13.3
72 40.7 2.7 36.0 29.4 22.8 16.1 - - 37.7 3.1 34.9 28.2 21.4 14.7 - -
67 37.3 2.7 37.3 36.2 29.6 23.0 16.4 - 34.3 3.0 34.3 33.8 28.4 21.7 15.0 -
1500
62 34.0 2.7 34.0 34.0 34.0 27.3 20.7 14.1 31.7 3.0 31.7 31.7 31.7 25.0 18.3 11.6
57 34.2 2.7 34.2 34.2 34.2 27.5 20.9 14.3 31.9 3.0 31.9 31.9 31.9 25.2 18.5 11.8
40 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XQE04 (3 ton) (Continued)
Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBH) Total Total Sensible Capacity (MBH)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBH) (kW)2 (MBH) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 35.6 3.4 13.5 12.6 9.1 - - - 32.9 3.8 12.9 10.6 7.9 - - -
72 32.4 3.4 21.0 17.5 14.0 10.4 - - 29.7 3.8 19.7 16.2 12.6 9.1 - -
750
67 29.3 3.4 28.5 22.3 18.8 15.3 11.7 - 26.6 3.8 26.6 20.9 17.4 13.8 10.3 -
62 27.6 3.4 27.6 27.6 21.7 18.2 14.7 11.1 25.7 3.8 25.7 25.7 19.6 16.1 12.5 9.0
77 36.1 3.4 18.5 14.3 10.1 - - - 33.2 3.8 18.3 13.0 8.8 - - -
72 33.0 3.4 23.9 19.7 15.5 11.3 - - 30.0 3.8 22.6 18.3 14.1 9.9 - -
900 67 29.8 3.4 29.3 25.1 20.9 16.7 12.5 - 26.8 3.8 26.8 23.7 19.4 15.2 11.0 -
62 28.1 3.4 28.1 28.1 24.1 19.9 15.7 11.5 25.9 3.8 25.9 25.9 21.9 17.7 13.5 9.2
57 28.2 3.4 28.2 28.2 24.0 19.8 15.6 11.4 26.0 3.7 26.0 26.0 21.7 17.5 13.3 9.0
77 36.7 3.4 23.5 16.0 11.1 - - - 33.6 3.7 23.7 15.5 9.7 - - -
72 33.5 3.4 26.8 21.9 17.0 12.1 - - 30.4 3.7 25.4 20.5 15.6 10.7 - -
1050 67 30.2 3.4 30.0 27.8 22.9 18.0 13.2 - 27.1 3.7 27.1 26.4 21.5 16.5 11.6 -
62 28.5 3.4 28.5 28.5 26.5 21.6 16.7 11.9 26.2 3.7 26.2 26.2 24.2 19.3 14.4 9.5
57 28.6 3.4 28.6 28.6 26.4 21.5 16.6 11.8 26.2 3.7 26.2 26.2 24.0 19.1 14.2 9.3
77 37.3 3.4 28.6 17.7 12.1 - - - 33.9 3.7 29.2 18.0 10.7 - - -
72 34.0 3.4 29.6 24.1 18.5 13.0 - - 30.7 3.7 28.3 22.7 17.1 11.5 - -
1200 67 30.7 3.3 30.7 30.5 25.0 19.4 13.9 - 27.4 3.7 27.4 27.4 23.5 17.9 12.3 -
62 29.0 3.3 29.0 29.0 28.9 23.3 17.8 12.2 26.5 3.7 26.5 26.5 26.5 20.9 15.3 9.7
57 29.1 3.3 29.1 29.1 28.8 23.2 17.7 12.1 26.5 3.7 26.5 26.5 26.3 20.7 15.1 9.5
72 34.3 3.4 31.7 25.5 19.3 13.2 - - 31.2 3.7 30.4 24.2 17.9 11.7 - -
67 31.0 3.4 31.0 30.9 26.0 19.9 13.7 - 27.9 3.7 27.9 27.9 24.7 18.4 12.2 -
1350
62 29.3 3.4 29.3 29.3 29.2 23.0 16.9 10.7 26.9 3.7 26.9 26.9 26.9 20.7 14.4 8.2
57 29.3 3.3 29.3 29.3 29.2 23.0 16.8 10.7 26.9 3.7 26.9 26.9 26.8 20.6 14.3 8.1
72 34.7 3.4 33.7 26.9 20.1 13.3 - - 31.6 3.7 31.6 25.7 18.8 11.9 - -
67 31.3 3.4 31.3 31.3 27.1 20.3 13.5 - 28.3 3.7 28.3 28.3 25.8 19.0 12.1 -
1500
62 29.5 3.4 29.5 29.5 29.5 22.7 15.9 9.2 27.3 3.7 27.3 27.3 27.3 20.4 13.6 6.7
57 29.6 3.4 29.6 29.6 29.6 22.8 16.0 9.2 27.3 3.7 27.3 27.3 27.3 20.5 13.6 6.7
1. These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat (MBH = 3.415 x kW). Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Ducted Systems 41
5147362-YTG-R-0323
XQE05 (4 ton)
Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBH) Total Total Sensible Capacity (MBH)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBH) (kW)2 (MBH) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 63.6 2.8 30.9 26.6 22.3 - - - 60.1 3.1 29.2 24.9 20.7 - - -
72 58.2 2.8 37.5 32.2 27.0 21.8 - - 54.9 3.1 36.1 30.9 25.6 20.4 - -
1000
67 52.8 2.7 44.1 37.9 31.7 26.4 21.1 - 49.7 3.1 43.1 36.8 30.5 25.2 19.9 -
62 48.9 2.7 44.1 40.2 36.4 30.7 25.6 20.2 46.6 3.1 44.1 39.8 35.5 29.9 24.6 19.2
77 64.6 2.8 34.6 28.4 22.3 - - - 60.8 3.1 33.2 27.0 20.8 - - -
72 59.9 2.8 41.1 34.8 28.5 22.1 - - 56.4 3.1 39.7 33.4 27.1 20.7 - -
1200 67 55.2 2.7 47.6 41.1 34.6 28.2 21.8 - 52.0 3.1 46.3 39.8 33.3 26.9 20.5 -
62 52.0 2.7 47.6 44.2 40.8 34.0 27.8 21.2 49.6 3.1 47.1 43.3 39.6 32.9 26.6 20.1
57 48.9 2.7 47.6 47.3 46.9 40.3 33.7 27.1 47.1 3.1 47.1 46.8 45.8 39.2 32.7 26.1
77 65.6 2.8 38.3 30.3 22.3 - - - 61.6 3.1 37.2 29.1 21.0 - - -
72 61.6 2.8 44.7 37.3 29.9 22.5 - - 58.0 3.1 43.3 35.9 28.5 21.1 - -
1400 67 57.5 2.8 51.1 44.3 37.5 30.0 22.5 - 54.4 3.1 49.4 42.7 36.1 28.6 21.1 -
62 55.2 2.8 51.1 48.1 45.1 37.3 29.9 22.3 52.6 3.1 50.0 46.8 43.7 36.0 28.5 21.0
57 52.8 2.7 51.1 51.1 51.1 45.0 37.3 29.6 50.7 3.1 50.6 50.6 50.6 43.6 35.9 28.3
77 66.6 2.8 42.0 32.1 22.3 - - - 62.4 3.2 41.2 31.2 21.1 - - -
72 63.2 2.8 48.3 39.8 31.4 22.9 - - 59.6 3.1 46.9 38.4 30.0 21.5 - -
1600 67 59.8 2.8 54.7 47.5 40.4 31.9 23.2 - 56.8 3.1 52.6 45.7 38.9 30.3 21.8 -
62 58.3 2.8 54.7 52.1 49.5 40.6 32.0 23.3 55.6 3.1 53.0 50.4 47.8 39.1 30.5 21.9
57 56.7 2.7 54.7 54.7 54.7 49.7 40.9 32.0 54.3 3.1 53.4 53.4 53.4 47.9 39.2 30.5
72 64.9 2.8 51.9 42.4 32.8 23.3 - - 61.2 3.2 50.5 41.0 31.4 21.9 - -
67 62.2 2.8 58.2 50.8 43.4 33.7 23.9 - 59.2 3.1 55.7 48.7 41.6 32.0 22.4 -
1800
62 61.4 2.8 58.2 56.0 53.9 44.0 34.2 24.3 58.6 3.1 55.9 53.9 51.9 42.1 32.4 22.7
57 60.6 2.8 58.2 58.2 58.2 54.4 44.4 34.4 58.0 3.1 56.1 56.1 56.1 52.3 42.5 32.7
72 66.5 2.8 55.6 44.9 34.3 23.6 - - 62.7 3.2 54.1 43.5 32.9 22.3 - -
67 64.5 2.8 61.7 54.0 46.3 35.5 24.7 - 61.6 3.1 58.8 51.6 44.4 33.7 23.1 -
2000
62 64.5 2.8 61.7 60.0 58.2 47.3 36.3 25.4 61.6 3.1 58.8 57.4 56.0 45.2 34.4 23.6
57 64.5 2.8 61.8 61.8 61.8 59.1 48.0 36.9 61.6 3.1 58.8 58.8 58.8 56.6 45.7 34.9
95°F 105°F
77 56.5 3.4 27.5 23.3 19.1 - - - 50.9 4.0 26.5 22.1 17.7 - - -
72 51.5 3.4 34.8 29.5 24.2 18.9 - - 47.5 4.0 33.4 28.0 22.7 17.4 - -
1000
67 46.5 3.4 42.1 35.8 29.4 24.0 18.7 - 44.2 3.9 40.3 34.0 27.7 22.4 17.1 -
62 44.2 3.4 44.2 39.3 34.5 29.1 23.6 18.2 42.7 3.9 41.8 37.3 32.8 27.4 22.1 16.7
77 57.1 3.5 31.8 25.6 19.4 - - - 51.8 4.0 30.7 24.2 17.7 - - -
72 53.0 3.4 38.4 32.0 25.7 19.3 - - 49.0 4.0 36.7 30.3 24.0 17.7 - -
1200 67 48.9 3.4 44.9 38.5 32.0 25.6 19.2 - 46.3 3.9 42.7 36.5 30.3 23.9 17.6 -
62 47.1 3.4 45.2 42.4 38.3 31.9 25.4 18.9 45.1 3.9 43.8 40.2 36.6 30.2 23.8 17.4
57 45.2 3.4 45.2 45.2 44.7 38.1 31.6 25.1 43.9 3.9 43.9 43.9 42.9 36.4 30.0 23.5
77 57.6 3.5 36.1 27.9 19.6 - - - 52.6 4.0 34.9 26.3 17.8 - - -
72 54.5 3.5 41.9 34.5 27.1 19.7 - - 50.5 4.0 40.0 32.6 25.3 18.0 - -
1400 67 51.4 3.4 47.7 41.2 34.7 27.2 19.8 - 48.5 4.0 45.0 39.0 32.9 25.5 18.1 -
62 50.0 3.4 48.6 45.5 42.2 34.7 27.2 19.7 47.5 3.9 45.9 43.2 40.4 33.0 25.5 18.0
57 48.6 3.4 48.6 48.6 48.6 42.1 34.6 27.0 46.6 3.9 46.6 46.6 46.6 40.5 32.9 25.3
77 58.1 3.5 40.5 30.2 19.9 - - - 53.5 4.0 39.1 28.5 17.8 - - -
72 56.0 3.5 45.5 37.0 28.6 20.1 - - 52.0 4.0 43.3 34.9 26.6 18.3 - -
1600 67 53.8 3.5 50.5 43.9 37.3 28.8 20.3 - 50.6 4.0 47.4 41.4 35.5 27.0 18.6 -
62 52.9 3.5 51.2 48.6 46.0 37.5 28.9 20.4 50.0 4.0 48.0 46.1 44.3 35.7 27.2 18.6
57 52.0 3.5 52.0 52.0 52.0 46.1 37.5 29.0 49.3 4.0 48.5 48.5 48.5 44.5 35.8 27.1
72 57.4 3.5 49.0 39.5 30.0 20.5 - - 53.5 4.0 46.6 37.3 27.9 18.6 - -
67 56.2 3.5 53.2 46.6 39.9 30.4 20.9 - 52.7 4.0 49.8 43.9 38.0 28.6 19.1 -
1800
62 55.8 3.5 53.6 51.7 49.8 40.3 30.7 21.1 52.4 4.0 50.1 49.1 48.1 38.5 28.9 19.3
57 55.3 3.5 54.0 54.0 54.0 50.1 40.5 30.9 52.0 4.0 50.3 50.3 50.3 48.5 38.7 28.9
72 58.9 3.5 52.6 42.0 31.488 20.9 - - 55.0 4.0 49.9 39.6 29.2 18.9 - -
67 58.7 3.5 56.0 49.3 42.6 32.0 21.4 - 54.9 4.0 52.0 46.4 40.6 30.1 19.6 -
2000
62 58.7 3.5 56.0 54.8 53.7 43.1 32.5 21.8 54.8 4.0 52.0 52.0 52.0 41.3 30.6 19.9
57 58.7 3.5 56.0 56.0 56.0 54.1 43.5 32.8 54.8 4.0 52.0 52.0 52.0 52.0 41.6 30.7
42 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XQE05 (4 ton) (Continued)
Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBH) Total Total Sensible Capacity (MBH)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBH) (kW)2 (MBH) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 45.3 4.5 25.4 20.9 16.3 - - - 39.6 5.1 24.4 19.6 14.9 - - -
72 43.6 4.5 31.9 26.6 21.2 15.8 - - 39.6 5.0 30.5 25.1 19.7 14.3 - -
1000
67 41.9 4.5 38.4 32.3 26.1 20.8 15.5 - 39.6 5.0 36.5 30.5 24.5 19.2 13.9 -
62 41.2 4.4 39.4 35.2 31.0 25.8 20.5 15.3 39.6 5.0 37.0 33.2 29.3 24.1 18.9 13.8
77 46.4 4.5 29.5 22.8 16.1 - - - 41.1 5.1 28.4 21.4 14.4 - - -
72 45.1 4.5 35.0 28.7 22.4 16.0 - - 41.1 5.0 33.3 27.0 20.7 14.4 - -
1200 67 43.7 4.5 40.4 34.5 28.6 22.3 15.9 - 41.1 5.0 38.1 32.5 26.9 20.6 14.3 -
62 43.1 4.4 41.2 38.0 34.9 28.5 22.2 15.8 41.1 5.0 38.5 35.8 33.1 26.8 20.5 14.2
57 42.5 4.4 42.0 41.6 41.1 34.8 28.4 22.0 41.1 4.9 38.9 38.9 38.9 33.1 26.7 20.4
77 47.6 4.5 33.6 24.8 15.9 - - - 42.6 5.0 32.4 23.2 14.0 - - -
72 46.6 4.5 38.0 30.8 23.5 16.2 - - 42.6 5.0 36.1 28.9 21.7 14.5 - -
1400 67 45.6 4.5 42.4 36.8 31.1 23.8 16.4 - 42.6 5.0 39.8 34.6 29.3 22.0 14.7 -
62 45.1 4.5 43.0 40.8 38.7 31.3 23.8 16.3 42.6 5.0 40.0 38.5 37.0 29.6 22.1 14.7
57 44.6 4.4 43.5 43.5 43.5 38.8 31.2 23.6 42.6 5.0 40.2 40.2 40.2 37.1 29.5 22.0
77 48.8 4.5 37.7 26.7 15.7 - - - 44.1 5.0 36.4 25.0 13.6 - - -
72 48.1 4.5 41.1 32.9 24.7 16.5 - - 44.1 5.0 38.9 30.8 22.7 14.6 - -
1600 67 47.4 4.5 44.4 39.0 33.6 25.2 16.8 - 44.1 5.0 41.4 36.6 31.8 23.4 15.1 -
62 47.0 4.5 44.7 43.7 42.6 34.0 25.4 16.9 44.1 5.0 41.5 41.2 40.9 32.3 23.7 15.1
57 46.7 4.5 45.1 45.1 45.1 42.8 34.0 25.3 44.1 5.0 41.6 41.6 41.6 41.1 32.3 23.5
72 49.6 4.5 44.1 35.0 25.8 16.7 - - 45.7 5.0 41.7 32.7 23.7 14.7 - -
67 49.2 4.5 46.4 41.3 36.1 26.7 17.3 - 45.7 5.0 43.0 38.6 34.2 24.9 15.5 -
1800
62 49.0 4.5 46.5 46.5 46.4 36.8 27.1 17.4 45.6 5.0 43.0 43.0 43.0 35.0 25.3 15.6
57 48.8 4.5 46.6 46.6 46.6 46.6 36.9 27.0 45.5 5.0 43.0 43.0 43.0 43.0 35.1 25.0
72 51.1 4.5 47.2 37.1 27.0 16.9 - - 47.3 5.0 44.5 34.6 24.7 14.8 - -
67 51.1 4.5 48.3 43.5 38.6 28.2 17.8 - 47.3 5.0 44.6 40.6 36.6 26.3 15.9 -
2000
62 51.0 4.5 48.3 48.3 48.3 39.5 28.7 18.0 47.1 5.0 44.7 44.7 44.7 37.7 26.9 16.0
57 50.9 4.5 48.3 48.3 48.3 48.3 39.7 28.6 47.0 5.0 44.7 44.7 44.7 44.7 37.8 26.5
1. These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat (MBH = 3.415 x kW). Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Ducted Systems 43
5147362-YTG-R-0323
XQE06 (5 ton)
Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBH) Total Total Sensible Capacity (MBH)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBH) (kW)2 (MBH) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 78.3 3.6 38.6 34.0 29.5 - - - 73.5 3.9 36.7 31.6 26.5 - - -
72 70.9 3.5 46.7 40.5 34.3 28.1 - - 66.9 3.9 44.9 38.5 32.0 25.5 - -
1250
67 63.6 3.4 54.8 46.9 39.0 33.5 27.2 - 60.2 3.8 53.2 45.3 37.5 31.4 25.0 -
62 59.0 3.4 54.3 49.0 43.8 36.5 32.6 27.1 58.0 3.8 54.8 48.9 43.0 36.1 30.9 24.9
77 79.4 3.5 43.4 36.3 29.3 - - - 74.3 3.9 41.7 34.1 26.5 - - -
72 73.0 3.5 51.2 43.6 36.0 28.4 - - 68.7 3.9 49.4 41.6 33.7 25.9 - -
1500 67 66.6 3.4 59.0 50.9 42.7 35.6 27.7 - 63.0 3.8 57.1 49.1 41.0 33.4 25.5 -
62 62.8 3.4 59.0 54.2 49.5 40.7 34.7 27.2 61.1 3.8 58.6 53.5 48.3 39.9 32.9 25.2
57 59.0 3.3 59.0 57.6 56.2 48.9 41.6 34.3 59.3 3.9 59.3 57.9 55.6 47.9 40.3 32.6
77 80.6 3.5 48.1 38.6 29.0 - - - 75.1 3.9 46.8 36.6 26.4 - - -
72 75.1 3.5 55.7 46.7 37.7 28.8 - - 70.5 3.9 53.9 44.7 35.5 26.3 - -
1750 67 69.5 3.4 63.2 54.8 46.5 37.6 28.2 - 65.8 3.9 61.1 52.8 44.6 35.4 25.9 -
62 66.6 3.4 63.7 59.5 55.2 44.9 36.7 27.4 64.3 3.9 62.4 58.0 53.7 43.7 34.8 25.4
57 63.7 3.4 63.6 63.0 62.3 54.5 45.1 35.7 62.8 3.9 62.8 62.7 61.9 53.2 43.7 34.2
77 81.8 3.5 52.9 40.8 28.8 - - - 75.9 3.9 51.8 39.1 26.4 - - -
72 77.1 3.5 60.2 49.8 39.5 29.1 - - 72.3 3.9 58.4 47.8 37.2 26.6 - -
2000 67 72.5 3.5 67.4 58.8 50.2 39.6 28.7 - 68.7 3.9 65.1 56.6 48.1 37.3 26.4 -
62 70.4 3.4 68.5 64.7 60.9 49.1 38.7 27.6 67.5 3.9 66.2 62.6 59.0 47.5 36.8 25.6
57 68.3 3.4 68.3 68.3 68.3 60.2 48.7 37.2 66.4 3.9 66.4 66.4 66.4 58.5 47.1 35.7
72 79.2 3.5 64.7 52.9 41.2 29.5 - - 74.1 3.9 62.9 51.0 39.0 27.0 - -
67 75.5 3.5 71.7 62.8 53.9 41.7 29.2 - 71.5 3.9 69.0 60.3 51.7 39.3 26.9 -
2250
62 74.2 3.5 73.2 69.9 66.6 53.3 40.7 27.8 70.7 3.9 70.1 67.2 64.3 51.4 38.7 25.9
57 72.9 3.5 72.9 72.9 72.9 65.8 52.2 38.7 69.9 3.9 69.9 69.9 69.9 63.8 50.5 37.3
72 81.3 3.5 69.2 56.1 43.0 29.8 - - 75.9 3.9 67.5 54.1 40.8 27.4 - -
67 78.5 3.5 75.9 66.7 57.6 43.7 29.7 - 74.3 3.9 73.0 64.1 55.2 41.3 27.4 -
2500
62 78.0 3.5 78.0 75.2 72.3 57.5 42.8 28.0 73.9 3.9 73.9 71.8 69.7 55.2 40.7 26.1
57 77.5 3.5 77.5 77.5 77.5 71.4 55.8 40.2 73.4 3.9 73.4 73.4 73.4 69.1 53.9 38.8
95°F 105°F
77 68.8 4.3 34.8 29.2 23.5 - - - 63.2 4.9 34.2 28.0 21.9 - - -
72 62.8 4.3 43.2 36.4 29.7 23.0 - - 58.3 4.9 41.6 34.8 28.0 21.2 - -
1250
67 56.8 4.2 51.6 43.7 35.9 29.3 22.7 - 53.3 4.8 49.0 41.5 34.1 27.4 20.8 -
62 56.9 4.3 55.4 48.8 42.1 35.7 29.2 22.8 53.3 4.9 52.2 46.2 40.1 33.7 27.2 20.7
77 69.3 4.3 40.1 31.9 23.7 - - - 63.7 4.9 38.9 30.2 21.5 - - -
72 64.4 4.3 47.7 39.6 31.5 23.4 - - 59.7 4.9 45.6 37.5 29.4 21.4 - -
1500 67 59.5 4.2 55.3 47.3 39.3 31.2 23.2 - 55.7 4.9 52.2 44.8 37.3 29.2 21.2 -
62 59.5 4.3 58.3 52.7 47.1 39.1 31.1 23.1 55.7 4.9 54.8 50.0 45.2 37.1 29.0 20.9
57 59.5 4.4 59.5 58.1 54.9 47.0 39.0 31.0 55.7 5.0 55.7 55.2 53.1 45.0 36.9 28.8
77 69.7 4.3 45.4 34.6 23.8 - - - 64.2 4.9 43.7 32.4 21.2 - - -
72 65.9 4.3 52.2 42.7 33.2 23.8 - - 61.1 4.9 49.6 40.2 30.9 21.5 - -
1750 67 62.1 4.3 59.0 50.8 42.7 33.1 23.6 - 58.0 4.9 55.5 48.0 40.6 31.0 21.5 -
62 62.0 4.3 61.1 56.6 52.1 42.5 32.9 23.4 58.0 4.9 57.4 53.8 50.3 40.6 30.9 21.1
57 62.0 4.4 62.0 62.0 61.5 51.9 42.3 32.6 57.9 5.0 57.9 57.9 57.9 50.1 40.2 30.3
77 70.1 4.3 50.8 37.4 24.0 - - - 64.7 4.9 48.5 34.7 20.8 - - -
72 67.4 4.3 56.7 45.9 35.0 24.2 - - 62.6 4.9 53.6 43.0 32.3 21.7 - -
2000 67 64.8 4.3 62.7 54.4 46.1 35.1 24.1 - 60.4 4.9 58.7 51.3 43.8 32.9 21.9 -
62 64.6 4.3 64.0 60.5 57.1 46.0 34.8 23.7 60.3 4.9 59.9 57.6 55.3 44.0 32.7 21.4
57 64.4 4.4 64.4 64.4 64.4 56.8 45.5 34.3 60.2 5.0 60.2 60.2 60.2 55.2 43.5 31.8
72 69.0 4.3 61.2 49.0 36.8 24.6 - - 64.0 4.9 57.6 45.7 33.8 21.9 - -
67 67.4 4.3 66.4 57.9 49.4 37.0 24.5 - 62.8 4.9 62.0 54.5 47.1 34.7 22.2 -
2250
62 67.2 4.3 66.9 64.5 62.1 49.4 36.7 24.0 62.6 5.0 62.5 61.5 60.4 47.5 34.5 21.6
57 66.9 4.4 66.9 66.9 66.9 61.8 48.8 35.9 62.4 5.0 62.4 62.4 62.4 60.3 46.8 33.4
72 70.5 4.4 65.7 52.1 38.6 25.0 - - 65.5 5.0 61.6 48.4 35.2 22.0 - -
67 70.1 4.4 70.1 61.5 52.8 38.9 25.0 - 65.2 5.0 65.2 57.8 50.4 36.5 22.6 -
2500
62 69.7 4.4 69.7 68.4 67.1 52.8 38.5 24.3 64.9 5.0 64.9 64.9 64.9 50.9 36.4 21.8
57 69.4 4.3 69.4 69.4 69.4 66.7 52.1 37.5 64.7 5.0 64.7 64.7 64.7 64.7 50.1 34.9
44 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XQE06 (5 ton) (Continued)
Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBH) Total Total Sensible Capacity (MBH)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBH) (kW)2 (MBH) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 57.6 5.5 33.5 26.9 20.3 - - - 52.0 6.1 32.8 25.8 18.7 - - -
72 53.7 5.5 39.9 33.1 26.3 19.4 - - 49.1 6.1 38.3 31.4 24.5 17.6 - -
1250
67 49.7 5.5 46.4 39.3 32.2 25.5 18.8 - 46.2 6.1 43.8 37.1 30.3 23.6 16.9 -
62 49.8 5.5 49.1 43.6 38.2 31.6 25.1 18.6 46.2 6.1 45.9 41.1 36.2 29.6 23.1 16.5
77 58.2 5.5 37.7 28.6 19.4 - - - 52.7 6.1 36.5 26.9 17.3 - - -
72 55.0 5.5 43.5 35.4 27.4 19.4 - - 50.3 6.1 41.3 33.3 25.3 17.3 - -
1500 67 51.8 5.5 49.2 42.3 35.3 27.2 19.1 - 48.0 6.1 46.2 39.8 33.4 25.2 17.1 -
62 51.8 5.5 51.3 47.3 43.3 35.1 26.9 18.8 48.0 6.1 47.9 44.6 41.4 33.1 24.9 16.6
57 51.8 5.6 51.8 51.8 51.3 43.0 34.8 26.5 48.0 6.2 48.0 48.0 48.0 41.0 32.6 24.2
77 58.8 5.5 42.0 30.3 18.6 - - - 53.3 6.1 40.2 28.1 15.9 - - -
72 56.4 5.5 47.0 37.7 28.5 19.3 - - 51.6 6.1 44.4 35.3 26.2 17.1 - -
1750 67 54.0 5.5 52.0 45.2 38.5 28.9 19.4 - 49.9 6.1 48.5 42.4 36.4 26.8 17.3 -
62 53.9 5.5 53.6 51.0 48.5 38.6 28.8 18.9 49.9 6.1 49.8 48.2 46.6 36.6 26.7 16.7
57 53.9 5.6 53.9 53.9 53.9 48.3 38.1 27.9 49.9 6.2 49.9 49.9 49.9 46.4 36.0 25.6
77 59.4 5.5 46.2 31.9 17.7 - - - 54.0 6.1 43.9 29.2 14.5 - - -
72 57.7 5.5 50.5 40.1 29.7 19.2 - - 52.9 6.1 47.4 37.2 27.0 16.8 - -
2000 67 56.1 5.5 54.8 48.2 41.6 30.7 19.7 - 51.7 6.1 50.8 45.1 39.4 28.5 17.5 -
62 56.0 5.6 55.9 54.7 53.6 42.1 30.6 19.1 51.7 6.2 51.7 51.7 51.7 40.2 28.5 16.8
57 55.9 5.6 55.9 55.9 55.9 53.5 41.5 29.4 51.7 6.2 51.7 51.7 51.7 51.7 39.4 27.0
72 59.1 5.6 54.0 42.4 30.8 19.2 - - 54.1 6.2 50.4 39.1 27.8 16.5 - -
67 58.2 5.6 57.6 51.2 44.8 32.4 20.0 - 53.5 6.2 53.2 47.8 42.4 30.1 17.7 -
2250
62 58.1 5.6 58.1 58.1 58.1 45.6 32.4 19.2 53.5 6.2 53.5 53.5 53.5 43.7 30.2 16.8
57 58.0 5.6 58.0 58.0 58.0 58.0 44.8 30.8 53.5 6.2 53.5 53.5 53.5 53.5 42.8 28.3
72 60.4 5.6 57.5 44.7 31.9 19.1 - - 55.4 6.2 53.4 41.0 28.6 16.2 - -
67 60.3 5.6 60.3 54.1 47.9 34.1 20.3 - 55.4 6.2 55.4 50.5 45.5 31.7 17.9 -
2500
62 60.2 5.6 60.2 60.2 60.2 49.1 34.2 19.4 55.4 6.2 55.4 55.4 55.4 47.2 32.0 16.9
57 60.0 5.6 60.0 60.0 60.0 60.0 48.1 32.3 55.4 6.2 55.4 55.4 55.4 55.4 46.2 29.7
1. These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat (MBH = 3.415 x kW). Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Ducted Systems 45
5147362-YTG-R-0323
XYE04-09, XXEA7-12, XQE04-06 heating capacities
XYE04 heating capacities
Air over
Size Capacity Outdoor temperature (ºF @ 72% RH)
Model evaporator coil
(ton) and kW
CFM DB -10 0 10 20 30 40 50 60
MBH 2.5 8.1 13.7 19.3 24.8 30.4 36.0 41.6
55
kW 2.2 2.3 2.4 2.6 2.7 2.9 3.0 3.1
MBH 2.5 7.9 13.3 18.7 24.0 29.4 34.8 40.2
900 70
kW 2.7 2.8 3.0 3.1 3.3 3.4 3.5 3.7
MBH 2.5 7.8 13.0 18.3 23.5 28.7 34.0 39.2
80
kW 3.0 3.2 3.4 3.6 3.7 3.9 4.1 4.3
MBH 3.1 8.7 14.4 20.0 25.6 31.2 36.8 42.4
55
kW 2.3 2.4 2.4 2.5 2.6 2.6 2.7 2.8
04 MBH 3.0 8.4 13.8 19.3 24.7 30.1 35.5 40.9
XYE 1200 70
(3) kW 2.4 2.5 2.7 2.8 2.9 3.0 3.1 3.2
MBH 2.5 7.8 13.2 18.5 23.8 29.2 34.5 39.9
80
kW 2.8 2.9 3.0 3.1 3.3 3.4 3.5 3.6
MBH 4.2 9.7 15.3 20.9 26.4 32.0 37.6 43.1
55
kW 2.1 2.2 2.3 2.4 2.4 2.5 2.6 2.7
MBH 3.5 9.0 14.4 19.8 25.2 30.6 36.1 41.5
1500 70
kW 2.4 2.5 2.6 2.7 2.8 2.9 3.0 3.1
MBH 2.5 7.9 13.3 18.7 24.1 29.5 34.9 40.3
80
kW 2.8 2.9 3.0 3.1 3.2 3.3 3.4 3.5
XYE05 heating capacities
Air over
Size Capacity Outdoor Temperature (ºF @ 72% RH)
Model evaporator coil
(ton) and kW
CFM DB -10 0 10 20 30 40 50 60
MBH 5.1 12.6 20.0 27.5 35.0 42.4 49.9 57.4
55
kW 2.5 2.7 2.9 3.1 3.3 3.5 3.6 3.8
MBH 5.5 12.5 19.5 26.5 33.5 40.5 47.5 54.5
1200 70
kW 2.9 3.1 3.3 3.5 3.7 4.0 4.2 4.4
MBH 4.4 11.4 18.4 25.4 32.5 39.5 46.5 53.5
80
kW 3.2 3.4 3.7 3.9 4.1 4.3 4.6 4.8
MBH 4.0 12.0 20.0 28.0 36.0 44.0 52.0 60.0
55
kW 2.4 2.6 2.8 2.9 3.1 3.3 3.4 3.6
05 MBH 4.3 11.8 19.4 26.9 34.4 42.0 49.5 57.1
XYE 1600 70
(4) kW 2.9 3.0 3.2 3.4 3.6 3.8 3.9 4.1
MBH 4.0 11.3 18.5 25.8 33.1 40.4 47.7 55.0
80
kW 3.1 3.3 3.5 3.7 3.9 4.1 4.3 4.5
MBH 4.4 12.4 20.4 28.4 36.4 44.3 52.3 60.3
55
kW 3.0 3.1 3.2 3.3 3.4 3.5 3.6 3.7
MBH 4.9 12.4 19.9 27.4 34.9 42.4 49.9 57.4
2000 70
kW 3.4 3.5 3.6 3.8 3.9 4.0 4.1 4.2
MBH 4.5 11.8 19.0 26.3 33.5 40.8 48.0 55.3
80
kW 3.7 3.8 3.9 4.0 4.2 4.3 4.4 4.6
46 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XYE06 heating capacities
Size Air over evaporator coil Capacity Outdoor temperature (ºF @ 72% RH)
Model
(ton) and kW
CFM DB -10 0 10 20 30 40 50 60
MBH 6.5 15.6 24.7 33.7 42.8 51.9 61.0 70.1
55
kW 3.6 3.7 3.8 3.9 4.0 4.2 4.3 4.4
MBH 4.6 13.5 22.5 31.5 40.5 49.4 58.4 67.4
1500 70
kW 4.0 4.1 4.3 4.4 4.6 4.7 4.9 5.0
MBH 3.4 12.2 21.0 29.9 38.7 47.5 56.3 65.2
80
kW 4.3 4.5 4.6 4.8 5.0 5.1 5.3 5.5
MBH 5.3 14.5 23.8 33.0 42.3 51.6 60.8 70.1
55
kW 3.5 3.6 3.7 3.9 4.0 4.1 4.3 4.4
06 MBH 4.2 13.3 22.3 31.3 40.3 49.4 58.4 67.4
XYE 2000 70
(5) kW 3.8 4.0 4.2 4.4 4.5 4.7 4.9 5.1
MBH 2.9 11.8 20.8 29.7 38.6 47.6 56.5 65.5
80
kW 4.2 4.4 4.5 4.7 4.9 5.1 5.3 5.5
MBH 4.1 13.5 22.9 32.4 41.8 51.3 60.7 70.2
55
kW 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8
MBH 3.1 12.3 21.5 30.7 39.9 49.1 58.3 67.5
2500 70
kW 4.3 4.5 4.6 4.7 4.9 5.0 5.2 5.3
MBH 2.2 11.2 20.3 29.3 38.4 47.4 56.5 65.5
80
kW 4.7 4.8 5.0 5.1 5.3 5.4 5.6 5.7
Johnson Controls Ducted Systems 47
5147362-YTG-R-0323
XYEA7 heating capacities
Outdoor temperature (ºF) (72% RH)
Size Airflow Indoor Capacity
Model
(ton) CFM Temp and kW
-10 0 10 20 30 40 50 60
MBH 15.4 24.1 32.7 41.3 50.0 58.6 67.2 75.9
55
kW 3.34 3.58 3.81 4.05 4.28 4.52 4.75 4.99
MBH 12.7 21.3 30.0 38.6 47.2 55.9 64.5 73.1
1800 70
kW 4.02 4.25 4.49 4.72 4.96 5.19 5.43 5.66
MBH 9.8 18.4 27.0 35.7 44.3 52.9 61.6 70.2
80
kW 4.51 4.74 4.98 5.21 5.45 5.68 5.92 6.15
MBH 16.8 25.5 34.1 42.7 51.4 60.0 68.6 77.3
55
kW 2.97 3.21 3.44 3.68 3.91 4.15 4.38 4.62
MBH 14.1 22.7 31.3 40.0 48.6 57.2 65.9 74.5
A7
XYE 2400 70
(6) kW 3.65 3.88 4.12 4.35 4.59 4.82 5.06 5.29
MBH 11.1 19.8 28.4 37.0 45.7 54.3 62.9 71.6
80
kW 4.13 4.37 4.60 4.84 5.07 5.31 5.54 5.78
MBH 17.2 25.8 34.5 43.1 51.7 60.4 69.0 77.6
55
kW 2.72 2.96 3.19 3.43 3.66 3.90 4.13 4.37
MBH 14.4 23.1 31.7 40.3 49.0 57.6 66.2 74.9
3000 70
kW 3.40 3.63 3.87 4.10 4.34 4.57 4.81 5.04
MBH 11.5 20.2 28.8 37.4 46.0 54.7 63.3 71.9
80
kW 3.89 4.12 4.36 4.59 4.83 5.06 5.30 5.53
XYE08 heating capacities
Size Airflow Indoor Capacity Outdoor temperature (ºF) (72% RH)
Model
(ton) CFM Temp and kW -10 0 10 20 30 40 50 60
MBH 20.5 31.9 43.3 54.7 66.2 77.6 89.0 100.5
55
kW 4.26 4.56 4.87 5.18 5.49 5.79 6.10 6.41
MBH 16.9 28.4 39.8 51.2 62.7 74.1 85.5 97.0
2250 70
kW 4.98 5.29 5.59 5.90 6.21 6.51 6.82 7.13
MBH 15.7 27.2 38.6 50.0 61.5 72.9 84.3 95.8
80
kW 5.74 6.05 6.36 6.67 6.97 7.28 7.59 7.89
MBH 20.6 32.1 43.5 54.9 66.4 77.8 89.2 100.7
55
kW 3.82 4.12 4.43 4.74 5.05 5.35 5.66 5.97
08 MBH 17.1 28.6 40.0 51.4 62.9 74.3 85.7 97.2
XYE 3000 70
(7.5) kW 4.54 4.85 5.15 5.46 5.77 6.08 6.38 6.69
MBH 15.9 27.3 38.8 50.2 61.6 73.1 84.5 95.9
80
kW 5.30 5.61 5.92 6.22 6.53 6.84 7.15 7.45
MBH 21.9 33.3 44.8 56.2 67.6 79.0 90.5 101.9
55
kW 3.57 3.88 4.18 4.49 4.80 5.11 5.41 5.72
MBH 18.4 29.8 41.2 52.7 64.1 75.5 87.0 98.4
3750 70
kW 4.29 4.60 4.91 5.21 5.52 5.83 6.13 6.44
MBH 17.2 28.6 40.0 51.5 62.9 74.3 85.8 97.2
80
kW 5.06 5.36 5.67 5.98 6.29 6.59 6.90 7.21
48 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XYE09 heating capacities
Size Airflow Indoor Capacity Outdoor temperature (ºF) (72% RH)
Model
(tons) CFM Temp and kW -10 0 10 20 30 40 50 60
MBH 20.6 34.0 47.5 61.0 74.4 87.9 101.4 114.8
55
kW 4.30 4.70 5.10 5.50 5.90 6.30 6.70 7.10
MBH 15.1 28.6 42.0 55.5 69.0 82.4 95.9 109.4
2550 70
kW 5.32 5.72 6.12 6.52 6.92 7.32 7.72 8.12
MBH 12.1 25.6 39.1 52.5 66.0 79.5 92.9 106.4
80
kW 6.19 6.59 6.99 7.39 7.79 8.19 8.59 8.99
MBH 22.4 35.8 49.3 62.8 76.2 89.7 103.2 116.6
55
kW 3.63 4.03 4.43 4.82 5.22 5.62 6.02 6.42
09 MBH 17.0 30.4 43.9 57.4 70.8 84.3 97.8 111.2
XYE 3400 70
(8.5) kW 4.66 5.06 5.46 5.85 6.25 6.65 7.05 7.45
MBH 13.9 27.4 40.9 54.3 67.8 81.3 94.7 108.2
80
kW 5.52 5.92 6.32 6.71 7.11 7.51 7.91 8.31
MBH 22.7 36.2 49.7 63.1 76.6 90.1 103.5 117.0
55
kW 3.25 3.65 4.05 4.44 4.84 5.24 5.64 6.04
MBH 17.3 30.7 44.2 57.7 71.1 84.6 98.1 111.5
4250 70
kW 4.27 4.67 5.07 5.47 5.87 6.27 6.67 7.06
MBH 14.3 27.8 41.2 54.7 68.2 81.6 95.1 108.6
80
kW 5.14 5.54 5.94 6.34 6.74 7.13 7.53 7.93
XXEA7 heating capacities
Size Airflow Indoor Capacity Outdoor temperature (ºF) (72% RH)
Model
(ton) CFM Temp and kW -10 0 10 20 30 40 50 60
MBH 10.7 20.9 31.0 41.1 51.3 61.4 71.5 81.7
55
kW 3.28 3.50 3.72 3.94 4.16 4.38 4.60 4.83
MBH 7.3 17.5 27.6 37.7 47.9 58.0 68.2 78.3
1800 70
kW 3.87 4.09 4.32 4.54 4.76 4.98 5.20 5.42
MBH 4.7 14.9 25.0 35.1 45.3 55.4 65.6 75.7
80
kW 4.38 4.60 4.82 5.04 5.26 5.48 5.70 5.93
MBH 10.6 20.8 30.9 41.0 51.2 61.3 71.4 81.6
55
kW 2.75 2.97 3.20 3.42 3.64 3.86 4.08 4.30
A7 MBH 7.3 17.5 27.6 37.7 47.9 58.0 68.1 78.3
XXE 2400 70
(6) kW 3.38 3.60 3.82 4.04 4.27 4.49 4.71 4.93
MBH 4.7 14.8 24.9 35.1 45.2 55.4 65.5 75.6
80
kW 3.87 4.09 4.31 4.53 4.75 4.97 5.19 5.42
MBH 10.5 20.6 30.8 40.9 51.0 61.2 71.3 81.4
55
kW 2.60 2.82 3.04 3.26 3.48 3.70 3.92 4.15
MBH 7.1 17.2 27.4 37.5 47.6 57.8 67.9 78.0
3000 70
kW 3.19 3.41 3.64 3.86 4.08 4.30 4.52 4.74
MBH 4.5 14.6 24.8 34.9 45.0 55.2 65.3 75.4
80
kW 3.70 3.92 4.14 4.36 4.58 4.80 5.02 5.25
Johnson Controls Ducted Systems 49
5147362-YTG-R-0323
XXE08 Heating Capacities
Size Airflow Indoor Capacity Outdoor temperature (ºF) (72% RH)
Model
(ton) CFM Temp and kW -10 0 10 20 30 40 50 60
MBH 16.0 27.6 39.3 51.0 62.6 74.3 86.0 97.6
55
kW 4.65 4.85 5.05 5.25 5.45 5.66 5.86 6.06
MBH 11.3 23.0 34.6 46.3 58.0 69.6 81.3 92.9
2250 70
kW 5.60 5.80 6.00 6.20 6.41 6.61 6.81 7.01
MBH 7.2 18.9 30.5 42.2 53.8 65.5 77.2 88.8
80
kW 6.34 6.54 6.74 6.95 7.15 7.35 7.55 7.75
MBH 19.3 31.0 42.6 54.3 66.0 77.6 89.3 100.9
55
kW 4.08 4.28 4.48 4.68 4.89 5.09 5.29 5.49
08 MBH 14.6 26.3 38.0 49.6 61.3 73.0 84.6 96.3
XXE 3000 70
(7.5) kW 5.03 5.23 5.44 5.64 5.84 6.04 6.24 6.44
MBH 10.5 22.2 33.8 45.5 57.2 68.8 80.5 92.1
80
kW 5.77 5.97 6.17 6.37 6.58 6.78 6.98 7.18
MBH 19.7 31.4 43.0 54.7 66.3 78.0 89.7 101.3
55
kW 3.77 3.97 4.17 4.37 4.58 4.78 4.98 5.18
MBH 15.0 26.7 38.4 50.0 61.7 73.3 85.0 96.7
3750 70
kW 4.72 4.92 5.13 5.33 5.53 5.73 5.93 6.13
MBH 10.9 22.6 34.2 45.9 57.6 69.2 80.9 92.5
80
kW 5.46 5.66 5.87 6.07 6.27 6.47 6.67 6.87
XXE09 Heating Capacities
Size Airflow Indoor Capacity Outdoor temperature (ºF) (72% RH)
Model
(ton) CFM Temp and kW -10 0 10 20 30 40 50 60
MBH 17.0 29.9 42.8 55.7 68.7 81.6 94.5 107.4
55
kW 5.83 6.07 6.30 6.54 6.78 7.02 7.25 7.49
MBH 14.1 27.0 39.9 52.8 65.7 78.7 91.6 104.5
2550 70
kW 7.06 7.30 7.54 7.78 8.01 8.25 8.49 8.73
MBH 8.8 21.7 34.6 47.5 60.5 73.4 86.3 99.2
80
kW 7.88 8.12 8.35 8.59 8.83 9.07 9.30 9.54
MBH 22.2 35.2 48.1 61.0 73.9 86.8 99.7 112.7
55
kW 4.58 4.82 5.06 5.30 5.53 5.77 6.01 6.25
09 MBH 19.2 32.1 45.0 57.9 70.9 83.8 96.7 109.6
XXE 3400 70
(8.5) kW 5.79 6.02 6.26 6.50 6.74 6.97 7.21 7.45
MBH 13.9 26.9 39.8 52.7 65.6 78.5 91.5 104.4
80
kW 6.61 6.85 7.09 7.32 7.56 7.80 8.04 8.27
MBH 22.1 35.0 48.0 60.9 73.8 86.7 99.6 112.6
55
kW 4.08 4.31 4.55 4.79 5.03 5.26 5.50 5.74
MBH 19.2 32.1 45.0 58.0 70.9 83.8 96.7 109.6
4250 70
kW 5.31 5.55 5.79 6.02 6.26 6.50 6.74 6.97
MBH 13.9 26.8 39.8 52.7 65.6 78.5 91.4 104.4
80
kW 6.13 6.37 6.60 6.84 7.08 7.31 7.55 7.79
50 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XXE12 heating capacities
Size Airflow Indoor Capacity Outdoor temperature (ºF) (72% RH)
Model
(ton) CFM Temp and kW -10 0 10 20 30 40 50 60
MBH 12.1 26.5 46.1 65.6 85.2 104.8 124.3 143.9
55
kW 5.9 6.2 6.6 7.0 7.3 7.7 8.1 8.4
MBH 4.9 20.1 39.7 59.2 78.8 98.4 117.9 137.5
3000 70
kW 7.0 7.4 7.7 8.1 8.5 8.8 9.2 9.6
MBH 3.3 16.9 36.5 56.0 75.6 95.1 114.7 134.3
80
kW 7.9 8.3 8.7 9.0 9.4 9.7 10.1 10.5
MBH 12.1 26.6 46.2 66.3 85.3 105.4 124.6 144.0
55
kW 5.0 5.4 5.8 6.1 6.5 6.8 7.2 7.6
4000 MBH 5.0 20.2 39.9 59.6 79.0 98.6 118.1 137.6
12 (10) XXE 70
kW 6.3 6.6 7.0 7.4 7.7 8.1 8.4 8.8
MBH 4.0 17.0 36.6 56.2 75.7 95.2 114.9 134.6
80
kW 7.2 7.5 7.9 8.3 8.6 9.0 9.4 9.7
MBH 19.9 34.3 53.8 73.4 93.0 112.5 132.1 151.6
55
kW 4.6 5.0 5.4 5.7 6.1 6.5 6.8 7.2
5000 MBH 13.5 27.9 47.4 67.0 86.6 106.1 125.7 145.3
70
kW 5.8 6.2 6.5 6.9 7.2 7.6 8.0 8.3
MBH 10.2 24.7 44.2 63.8 83.3 102.9 122.5 142.0
80
kW 6.7 7.1 7.4 7.8 8.2 8.5 8.9 9.2
XQE04 heating capacities
Size Airflow Indoor Capacity Outdoor temperature (ºF) (72% RH)
Model
(ton) CFM Temp and kW -10 0 10 20 30 40 50 60
MBH 5.9 11.2 16.5 21.8 27.1 32.4 37.7 43.0
55
kW 1.93 2.05 2.18 2.30 2.43 2.56 2.68 2.81
MBH 4.0 9.3 14.6 19.9 25.2 30.5 35.8 41.1
900 70
kW 2.38 2.50 2.63 2.75 2.88 3.01 3.13 3.26
MBH 3.0 8.3 13.6 18.9 24.2 29.5 34.8 40.1
80
kW 2.78 2.91 3.04 3.16 3.29 3.41 3.54 3.67
MBH 5.8 11.1 16.4 21.7 27.0 32.3 37.6 42.9
55
kW 1.62 1.74 1.87 2.00 2.12 2.25 2.37 2.50
04 MBH 3.9 9.2 14.5 19.8 25.1 30.4 35.7 41.0
XQE 1200 70
(3) kW 2.06 2.19 2.31 2.44 2.57 2.69 2.82 2.94
MBH 2.8 8.1 13.4 18.7 24.0 29.3 34.6 39.9
80
kW 2.47 2.59 2.72 2.85 2.97 3.10 3.22 3.35
MBH 6.5 11.8 17.1 22.4 27.7 33.0 38.3 43.6
55
kW 1.49 1.62 1.74 1.87 2.00 2.12 2.25 2.37
MBH 4.6 9.9 15.2 20.5 25.8 31.2 36.5 41.8
1500 70
kW 1.94 2.07 2.19 2.32 2.45 2.57 2.70 2.82
MBH 3.6 8.9 14.2 19.5 24.8 30.1 35.4 40.7
80
kW 2.35 2.48 2.60 2.73 2.85 2.98 3.11 3.23
Johnson Controls Ducted Systems 51
5147362-YTG-R-0323
XQE05 heating capacities
Size Airflow Indoor Capacity Outdoor Temperature (F @ 72% RH)
Model
(ton) CFM Temp and kW -10 0 10 20 30 40 50 60
MBH 7.9 14.6 21.2 27.9 34.5 41.1 47.8 54.4
55
kW 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8
MBH 7.3 13.7 20.1 26.6 33.0 39.5 45.9 52.4
1200 70
kW 3.6 3.8 3.9 4.0 4.1 4.3 4.4 4.5
MBH 6.6 13.0 19.3 25.7 32.1 38.4 44.8 51.2
80
kW 4.1 4.2 4.4 4.5 4.7 4.8 5.0 5.1
MBH 8.3 15.1 21.9 28.7 35.5 42.3 49.1 55.9
55
kW 3.0 3.1 3.1 3.2 3.3 3.3 3.4 3.4
05 MBH 7.8 14.3 20.9 27.5 34.1 40.7 47.2 53.8
XQ 1600 70
(4) kW 3.4 3.5 3.6 3.7 3.8 3.9 4.0 4.1
MBH 7.0 13.5 20.0 26.5 33.0 39.5 46.0 52.6
80
kW 3.8 3.9 4.0 4.1 4.2 4.3 4.4 4.5
MBH 9.1 16.0 22.8 29.7 36.6 43.4 50.3 57.2
55
kW 3.3 3.4 3.4 3.4 3.5 3.5 3.6 3.6
MBH 8.2 15.0 21.7 28.5 35.3 42.0 48.8 55.5
2000 70
kW 3.8 3.9 3.9 4.0 4.0 4.1 4.1 4.1
MBH 7.0 13.7 20.5 27.3 34.1 40.9 47.6 54.4
80
kW 4.2 4.2 4.3 4.3 4.4 4.5 4.5 4.6
XQE06 Heating Capacities
Size Airflow Indoor Capacity Outdoor Temperature (F @ 72% RH)
Model
(ton) CFM Temp and kW -10 0 10 20 30 40 50 60
MBH 8.4 16.7 24.9 33.1 41.3 49.5 57.7 66.0
55
kW 3.6 3.7 3.8 4.0 4.1 4.3 4.4 4.5
MBH 6.4 14.4 22.4 30.5 38.5 46.5 54.5 62.5
1500 70
kW 4.0 4.1 4.3 4.5 4.7 4.8 5.0 5.2
MBH -- 13.2 21.1 29.0 36.9 44.8 52.7 60.6
80
kW 4.4 4.6 4.8 4.9 5.1 5.3 5.5 5.7
MBH 7.8 16.3 24.8 33.2 41.7 50.1 58.6 67.1
55
kW 3.8 3.9 4.0 4.1 4.2 4.3 4.4 4.5
06 MBH 4.7 13.2 21.7 30.2 38.7 47.2 55.7 64.2
XQ 2000 70
(5) kW 4.2 4.3 4.4 4.6 4.7 4.8 4.9 5.0
MBH -- 9.5 18.2 27.0 35.7 44.5 53.2 61.9
80
kW 4.5 4.7 4.8 4.9 5.1 5.2 5.3 5.5
MBH 7.8 16.5 25.3 34.0 42.7 51.4 60.1 68.8
55
kW 4.0 4.1 4.1 4.2 4.2 4.3 4.4 4.4
MBH 4.2 13.0 21.9 30.7 39.6 48.4 57.2 66.1
2500 70
kW 4.4 4.5 4.6 4.6 4.7 4.8 4.9 5.0
MBH 3.7 12.2 20.7 29.2 37.8 46.3 54.8 63.3
80
kW 4.8 4.9 5.0 5.1 5.2 5.2 5.3 5.4
52 Johnson Controls Ducted Systems
5147362-YTG-R-0323
Drive selection
1. Determine side or bottom supply duct Application.
2. Determine desired airflow.
3. Calculate or measure the amount of external static pressure.
4. Add or deduct any additional static resistance from “Additional Static Resistance Table”.
5. Using the operating point determined from steps 1, 2 and 3, locate this point on the appropriate supply air blower performance
table. (Linear interpolation may be necessary.)
6. Noting the RPM and BHP from step 4, locate the appropriate motor and, or drive on the RPM selection table.
7. Review the BHP compared to the motor options available. Select the appropriate motor and, or drive.
8. Review the RPM range for the motor options available. Select the appropriate drive if multiple drives are available for the
chosen motor.
9. Determine turns open to obtain the desired operation point.
Example
1. 1600 CFM
2. 1.4 iwg
3. Using the airflow performance table below, the following data point was located: 1417 RPM and 1.28 BHP.
4. Using the RPM selection table below, Model XYE and Size 05 (4-Tons) is found.
5. The High Static Option is selected to achieve the required 1417 RPM.
6. Using the High Static Option, 2 turns open will achieve 1417 RPM.
Airflow performance
Example supply air blower performance
XYE05 (4.0 ton) bottom duct
Available External Static
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1200 801 0.25 903 0.38 999 0.51 1089 0.63 1173 0.76 1252 0.88 1327 1.00 1396 1.11 1461 1.22 1521 1.33
1300 822 0.31 924 0.44 1020 0.57 1110 0.69 1194 0.82 1273 0.94 1348 1.06 1417 1.17 1482 1.28 1542 1.39
1400 844 0.38 946 0.51 1042 0.64 1132 0.76 1216 0.89 1295 1.01 1370 1.13 1439 1.24 1504 1.35 1564 1.46
1500 867 0.46 969 0.59 1065 0.71 1155 0.84 1239 0.96 1319 1.08 1393 1.20 1462 1.32 1527 1.43 1587 1.53
1600 891 0.54 993 0.67 1089 0.79 1179 0.92 1264 1.04 1343 1.16 1417 1.28 1486 1.40 1551 1.51 1612 1.61
1700 917 0.63 1019 0.75 1115 0.88 1205 1.01 1289 1.13 1368 1.25 1442 1.37 1512 1.48 1577 1.60 1637 1.70
1800 943 0.72 1045 0.85 1141 0.97 1231 1.10 1316 1.22 1395 1.34 1469 1.46 1538 1.58 1603 1.69 -- --
1900 971 0.81 1073 0.94 1169 1.07 1259 1.19 1344 1.32 1423 1.44 1497 1.56 1566 1.67 1631 1.78 -- --
2000 1000 0.92 1102 1.04 1198 1.17 1288 1.29 1372 1.42 1452 1.54 1526 1.66 1595 1.77 -- -- -- --
kW = 0.929 x BHP
Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 2.4-hp
Bold Field-supplied AK41 x 3/4 in. fixed blower pulley with motor rated at 2.4-hp
-- Exceeds recommended blower speed
Example RPM selection
Size Airflow Max Blower Motor 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turns Fully
Model Phase
(ton) Option BHP Sheave Sheave Open Open Open Open Open Open Closed
Std. Direct Drive
05
XYE Med. 3 2.4 AK46 1VL34 N/A 792 875 958 1042 1125 1208
(4)
H. Static 3 2.4 AK46 1VL44 N/A 1167 1250 1333 1417 1500 1593
Example Additional Static Resistance
Size 4 in. Electric Heat kW2
Model CFM Economizer1 2
(ton) Filter1 6/6.5 9.2/10.5/11 13.8/14/16 23 ---
1200 0.24 --- 0.01 0.01 0.02 0.03 ---
1300 0.28 --- 0.01 0.01 0.03 0.03 ---
1400 0.33 --- 0.02 0.02 0.03 0.04 ---
1500 0.44 --- 0.02 0.02 0.04 0.04 ---
05
XYE 1600 0.52 --- 0.02 0.02 0.04 0.05 ---
(4.0)
1700 0.59 --- 0.03 0.03 0.05 0.05 ---
1800 0.66 --- 0.03 0.03 0.05 0.06 ---
1900 0.74 --- 0.04 0.04 0.06 0.07 ---
2000 0.81 --- 0.04 0.04 0.07 0.08 ---
Johnson Controls Ducted Systems 53
5147362-YTG-R-0323
Altitude and temperature correction for CFM, static use the indoor blower tables for high altitude applications,
pressure and power. certain corrections are necessary.
The information below should be used to assist in application of A centrifugal fan is a "constant volume" device. This means
product when being applied at altitudes at or exceeding 1000 ft that, if the RPM remains constant, the CFM delivered is the
above sea level. same regardless of the density of the air. However, since the air
at high altitude is less dense, less static pressure will be
The air flow rates listed in the standard blower performance
generated and less power will be required than a similar
tables are based on standard air at sea level. As the altitude or
application at sea level. Air density correction factors are shown
temperature increases, the density of air decreases. In order to
below.
Altitude/temperature correction factors
Air Altitude (ft)
Temp. (°F) 0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000
40 1.060 1.022 0.986 0.950 0.916 0.882 0.849 0.818 0.788 0.758 0.729
50 1.039 1.002 0.966 0.931 0.898 0.864 0.832 0.802 0.772 0.743 0.715
60 1.019 0.982 0.948 0.913 0.880 0.848 0.816 0.787 0.757 0.729 0.701
70 1.000 0.964 0.930 0.896 0.864 0.832 0.801 0.772 0.743 0.715 0.688
80 0.982 0.947 0.913 0.880 0.848 0.817 0.787 0.758 0.730 0.702 0.676
90 0.964 0.929 0.897 0.864 0.833 0.802 0.772 0.744 0.716 0.689 0.663
100 0.946 0.912 0.880 0.848 0.817 0.787 0.758 0.730 0.703 0.676 0.651
1.100
1.050
1.000
Sea Level
0.950
Correction Factor
1000 ft
0.900 2000 ft
3000 ft
0.850
4000 ft
0.800 5000 ft
6000 ft
0.750 7000 ft
8000 ft
0.700
9000 ft
10000 ft
0.650
0.600
40 50 60 70 80 90 100
Air Temperature (ºF)
The examples below will assist in determining the airflow Example 2: A system, located at 5,000 ft of elevation, is to
performance of the product at altitude. deliver 3,000 CFM at a static pressure of 1.4". Use the unit
blower tables to select the blower speed and the BHP
Example 1: What are the corrected CFM, static pressure, and
requirement.
BHP at an elevation of 5,000 ft if the airflow performance data is
3,000 CFM, 1.4 IWC and 2.0 BHP? Solution: As in the example above, no temperature
information is given so 70°F is assumed.
Solution: At an elevation of 5,000 ft the indoor blower will still
deliver 3,000 CFM if the rpm is unchanged. However, the Altitude The 1.4 in. static pressure given is at an elevation of 5,000 ft.
correction must be used to determine the static pressure and The first step is to convert this static pressure to equivalent sea
BHP. Since no temperature data is given, we will assume an Air level conditions.
Temperature of 70°F. The Altitude/Temperature Factors show
Sea level static pressure = 1.4 in. / .832 = 1.68"
the correction factor to be 0.832.
Enter the Supply Air Blower Performance Table at 3,000 CFM
Corrected static pressure = 1.4 x 0.832 = 1.16 IWC and static pressure of 1.68". The rpm listed will be the same
Corrected BHP = 2.0 x 0.832 = 1.66 rpm needed at 5,000 ft.
54 Johnson Controls Ducted Systems
5147362-YTG-R-0323
Suppose that the corresponding BHP listed in the table is 2.0. BHP at 5,000 ft = 2.0 x .832 = 1.66
This value must be corrected for elevation.
Indoor blower specifications
Motor Motor sheave Blower sheave
Size Airflow
Model Datum Dia. Datum Dia. Belt
(ton) option Phase Bhp RPM Eff. SF Frame Bore (in.) Model Bore (in.) Model
(in.) (in.)
Std. Direct drive
04 Med. 1 1.5 1725 0.79 1.15 56HZ 1.9 - 2.9 5/8 1VL34 4.2 3/4 AK46 A39
XYE
(3) Med. 3 2.4 1725 0.80 1.15 56Y 1.9 - 2.9 5/8 1VL34 4.2 3/4 AK46 A39
H. Static 3 2.4 1725 0.80 1.15 56Y 2.8 - 3.8 5/8 1VL44 4.2 3/4 AK46 A40
Std. Direct drive
05 Med. 1 1.5 1725 0.79 1.15 56HZ 1.9 - 2.9 5/8 1VL34 4.2 3/4 AK46 A39
XYE
(4) Med. 3 2.4 1725 0.80 1.15 56Y 1.9 - 2.9 5/8 1VL34 4.2 3/4 AK46 A39
H. Static 3 2.4 1725 0.80 1.15 56Y 2.8 - 3.8 5/8 1VL44 4.2 3/4 AK46 A40
Std. Direct drive
06 Med. 1 1.5 1750 0.83 1.15 56H 1.9 - 2.9 5/8 1VL34 4.2 3/4 AK46 A37
XYE
(5) Med. 3 2.4 1750 0.87 1.15 56HZ 1.9 - 2.9 5/8 1VL34 4.2 3/4 AK46 A37
H. Static 3 2.9 1750 0.87 1.15 56Z 2.8 - 3.8 7/8 1VL44 4.2 3/4 AK46 A39
Std. 3 2.4 1725 0.80 1.15 56Y 1.9 - 2.9 5/8 1VL34 7.0 1 AK74 A47
A7
XYE Med. 3 2.9 1725 0.81 1.15 56Y 2.8 - 3.8 7/8 1VL44 7.0 1 AK74 A48
(6)
H. Static 3 3.7 1725 0.84 1.15 56HZ 3.4 - 4.4 7/8 1VP50 7.0 1 AK74 A48
Std. 3 2.4 1725 0.80 1.15 56Y 1.9 - 2.9 5/8 1VL34 7.0 1 AK74 A47
08
XYE Med. 3 2.4 1725 0.80 1.15 56Y 2.8 - 3.8 5/8 1VL44 7.0 1 AK74 A48
(7.5)
H. Static 3 3.7 1725 0.84 1.15 56HZ 3.4 - 4.4 7/8 1VP50 7.0 1 AK74 A50
Std. 3 2.4 1725 0.80 1.15 56Y 1.9 - 2.9 5/8 1VL34 7.0 1 AK74 A47
09
XYE Med. 3 2.4 1725 0.80 1.15 56Y 2.8 - 3.8 5/8 1VL44 7.0 1 AK74 A48
(8.5)
H. Static 3 3.7 1725 0.84 1.15 56HZ 3.4 - 4.4 7/8 1VP50 7.0 1 AK74 A50
Std. 3 2.4 1725 0.80 1.15 56Y 1.9 - 2.9 5/8 1VL34 4.7 3/4 AK51 A39
A7
XXE Med. 3 2.9 1725 0.81 1.15 56Y 2.8 - 3.8 7/8 1VL44 4.7 3/4 AK51 A40
(6)
H. Static 3 3.7 1725 0.84 1.15 56HZ 3.4 - 4.4 7/8 1VP50 4.7 3/4 AK51 A41
Std. 3 2.4 1725 0.80 1.15 56Y 1.9 - 2.9 5/8 1VL34 7.0 1 AK74 A47
08
XXE Med. 3 2.4 1725 0.80 1.15 56Y 2.8 - 3.8 5/8 1VL44 7.0 1 AK74 A48
(7.5)
H. Static 3 3.7 1725 0.84 1.15 56HZ 3.4 - 4.4 7/8 1VP50 7.0 1 AK74 A50
Std. 3 2.4 1725 0.80 1.15 56Y 1.9 - 2.9 5/8 1VL34 7.0 1 AK74 A47
09
XXE Med. 3 2.4 1725 0.80 1.15 56Y 2.8 - 3.8 5/8 1VL44 7.0 1 AK74 A48
(8.5)
H. Static 3 3.7 1725 0.84 1.15 56HZ 3.4 - 4.4 7/8 1VP50 7.0 1 AK74 A50
Std. 3 2.4 1725 0.80 1.15 56Y 2.8 - 3.8 5/8 1VL44 7.5 1 AK79 A50
12
XXE Med. 3 3.7 1725 0.84 1.15 56HZ 3.4 - 4.4 7/8 1VP50 7.5 1 AK79 A50
(10)
H. Static 3 5.25 1725 0.84 1.15 145TY 4.3 - 5.3 7/8 1VP56 7.9 1 BK85 BX52
Std. Direct drive
04 Med. 1 1.5 1725 0.79 1.15 56HZ 1.9 - 2.9 5/8 1VL34 4.2 3/4 AK46 A39
XQE
(3) Med. 3 2.4 1725 0.80 1.15 56Y 1.9 - 2.9 5/8 1VL34 4.2 3/4 AK46 A39
H. Static 3 2.4 1725 0.80 1.15 56Y 2.8 - 3.8 5/8 1VL44 4.2 3/4 AK46 A40
Std. Direct drive
05 Med. 1 1.5 1725 0.79 1.15 56HZ 1.9 - 2.9 5/8 1VL34 4.2 3/4 AK46 A39
XQE
(4) Med. 3 2.4 1725 0.80 1.15 56Y 1.9 - 2.9 5/8 1VL34 4.2 3/4 AK46 A39
H. Static 3 2.4 1725 0.80 1.15 56Y 2.8 - 3.8 5/8 1VL44 4.2 3/4 AK46 A40
Std. Direct drive
06 Med. 1 1.5 1750 0.83 1.15 56H 1.9 - 2.9 5/8 1VL34 4.2 3/4 AK46 A37
XQE
(5) Med. 3 2.4 1750 0.87 1.15 56HZ 1.9 - 2.9 5/8 1VL34 4.2 3/4 AK46 A37
H. Static 3 2.9 1750 0.87 1.15 56Z 2.8 - 3.8 7/8 1VL44 4.2 3/4 AK46 A39
Johnson Controls Ducted Systems 55
5147362-YTG-R-0323
RPM Selection
Size Airflow Max Blower Motor 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turns Fully
Model Phase
(ton) option BHP Sheave Sheave Open Open Open Open Open Open Closed
Std. Direct Drive
04 Med 1 1.5 AK46 1VL34 N/A 792 875 958 1042 1125 1208
XYE
(3) Med 3 2.4 AK46 1VL34 N/A 792 875 958 1042 1125 1208
H. Static 3 2.4 AK46 1VL44 N/A 1167 1250 1333 1417 1500 1593
Std. Direct Drive
05 Med 1 1.5 AK46 1VL34 N/A 792 875 958 1042 1125 1208
XYE
(4) Med 3 2.4 AK46 1VL34 N/A 792 875 958 1042 1125 1208
H. Static 3 2.4 AK46 1VL44 N/A 1167 1250 1333 1417 1500 1593
Std. Direct Drive
06 Med 1 1.5 AK46 1VL34 N/A 792 875 958 1042 1125 1208
XYE
(5) Med 3 2.4 AK46 1VL34 N/A 792 875 958 1042 1125 1208
H. Static 3 2.9 AK46 1VL44 N/A 1167 1250 1333 1417 1500 1593
Std. 3 2.4 AK74 1VL34 N/A 475 525 575 625 675 725
A7
XYE Med. 3 2.9 AK74 1VL44 N/A 700 750 800 850 900 950
(6)
H. Static 3 3.7 AK74 1VP50 N/A 850 900 950 1000 1050 1100
Std. 3 2.4 AK74 1VL34 N/A 475 525 575 625 675 725
08
XYE Med. 3 2.4 AK74 1VL44 N/A 700 750 800 850 900 950
(7.5)
H. Static 3 3.7 AK74 1VP50 N/A 850 900 950 1000 1050 1100
Std. 3 2.4 AK74 1VL34 N/A 475 525 575 625 675 725
09
XYE Med. 3 2.4 AK74 1VL44 N/A 700 750 800 850 900 950
(8.5)
H. Static 3 3.7 AK74 1VP50 N/A 850 900 950 1000 1050 1100
Std. 3 2.4 AK51 1VL34 N/A 707 782 856 931 1005 1080
A7
XXE Med. 3 2.9 AK51 1VL44 N/A 1043 1117 1191 1266 1340 1415
(6)
H. Static 3 3.7 AK51 1VP50 N/A 1266 1340 1415 1489 1564 1638
Std. 3 2.4 AK74 1VL34 N/A 475 525 575 625 675 725
08
XXE Med. 3 2.9 AK74 1VL44 N/A 700 750 800 850 900 950
(7.5)
H. Static 3 3.7 AK74 1VP50 N/A 850 900 950 1000 1050 1100
Std. 3 2.4 AK74 1VL34 N/A 475 525 575 625 675 725
9
XXE Med. 3 2.4 AK74 1VL44 N/A 700 750 800 850 900 950
(8.5)
H. Static 3 3.7 AK74 1VP50 N/A 850 900 950 1000 1050 1100
Std. 3 2.4 AK79 1VL44 N/A 653 700 747 793 840 887
12
XXE Med. 3 3.7 AK79 1VP50 N/A 793 840 887 933 980 1027
(10)
H. Static 3 5.25 BK85 1VP56 953 997 1041 1085 1130 1174 N/A
Std. Direct Drive
04 Med 1 1.5 AK46 1VL34 N/A 792 875 958 1042 1125 1208
XQE
(3) Med 3 2.4 AK46 1VL34 N/A 792 875 958 1042 1125 1208
H. Static 3 2.4 AK46 1VL44 N/A 1167 1250 1333 1417 1500 1593
Std. Direct Drive
05 Med 1 1.5 AK46 1VL34 N/A 792 875 958 1042 1125 1208
XQE
(4) Med 3 2.4 AK46 1VL34 N/A 792 875 958 1042 1125 1208
H. Static 3 2.4 AK46 1VL44 N/A 1167 1250 1333 1417 1500 1593
Std. Direct Drive
06 Med 1 1.5 AK46 1VL34 N/A 792 875 958 1042 1125 1208
XQE
(5) Med 3 2.4 AK46 1VL34 N/A 792 875 958 1042 1125 1208
H. Static 3 2.9 AK46 1VL44 N/A 1167 1250 1333 1417 1500 1593
56 Johnson Controls Ducted Systems
5147362-YTG-R-0323
Additional static resistance - XYE04-06
Size Electric heat kW2
Model CFM Economizer1 2 4 in. Filter1
(ton) 6/6.5 9.2/10.5/11 13.8/14/16 23 ---
900 0.15 --- 0.00 0.00 0.01 0.01 ---
1000 0.18 --- 0.00 0.00 0.02 0.02 ---
1100 0.21 --- 0.01 0.01 0.02 0.03 ---
04
XYE 1200 0.24 --- 0.01 0.01 0.02 0.03 ---
(3.0)
1300 0.28 --- 0.01 0.01 0.03 0.03 ---
1400 0.33 --- 0.02 0.02 0.03 0.04 ---
1500 0.44 --- 0.02 0.02 0.04 0.04 ---
1200 0.24 --- 0.01 0.01 0.02 0.03 ---
1300 0.28 --- 0.01 0.01 0.03 0.03 ---
1400 0.33 --- 0.02 0.02 0.03 0.04 ---
1500 0.44 --- 0.02 0.02 0.04 0.04 ---
05
XYE 1600 0.52 --- 0.02 0.02 0.04 0.05 ---
(4.0)
1700 0.59 --- 0.03 0.03 0.05 0.05 ---
1800 0.66 --- 0.03 0.03 0.05 0.06 ---
1900 0.74 --- 0.04 0.04 0.06 0.07 ---
2000 0.81 --- 0.04 0.04 0.07 0.08 ---
1800 0.66 --- 0.03 0.03 0.05 0.06 ---
2000 0.81 --- 0.04 0.04 0.07 0.08 ---
06
XYE 2200 0.95 --- 0.06 0.06 0.08 0.09 ---
(5.0)
2400 1.10 --- 0.07 0.07 0.10 0.11 ---
2500 1.17 --- 0.08 0.08 0.11 0.12 ---
1. Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.
2. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct
is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
Additional static resistance - XYEA7
Size Electric Heat kW2
Model CFM Economizer1 2 4 in. Filter1
(ton) 6/6.5 16/16.5/17 24.8/25.5/27.8
1800 0.11 --- 0.03 0.05 0.06
1900 0.11 --- 0.04 0.06 0.06
2000 0.11 --- 0.04 0.06 0.07
2100 0.12 --- 0.05 0.07 0.08
2200 0.12 --- 0.06 0.07 0.09
2300 0.12 --- 0.06 0.08 0.09
XYE A7 (6) 2400 0.13 --- 0.07 0.08 0.10
2500 0.13 --- 0.08 0.09 0.11
2600 0.13 --- 0.08 0.09 0.11
2700 0.15 --- 0.09 0.10 0.12
2800 0.15 --- 0.09 0.10 0.12
2900 0.16 --- 0.10 0.11 0.13
3000 0.17 --- 0.11 0.12 0.14
1. Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.
2. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct
is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
Johnson Controls Ducted Systems 57
5147362-YTG-R-0323
Additional static resistance - XYE08 - 09
Size Electric Heat kW2
Model CFM Economizer1 2 4 in. Filter1
(ton) 16/16.5/17 24.8/25.5/27.8 32/33/34 41.7/42.4
2200 0.11 --- 0.07 0.09 0.10 0.12
2600 0.13 --- 0.09 0.11 0.12 0.15
3000 0.17 --- 0.12 0.14 0.15 0.19
3400 0.20 --- 0.15 0.18 0.19 0.23
3800 0.25 --- 0.19 0.22 0.23 0.27
08 (7.5),
XYE 4000 0.28 --- 0.21 0.24 0.25 0.30
09 (8.5)
4400 0.33 --- 0.25 0.29 0.30 0.35
4800 0.38 --- 0.30 0.34 0.35 0.41
5200 0.43 --- 0.35 0.39 0.41 0.47
5600 0.46 --- 0.41 0.45 0.47 0.54
6000 0.50 --- 0.48 0.52 0.54 0.60
1. Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.
2. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct
is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
Additional static resistance - XXEA7
Size 4 in. Electric Heat kW2
Model CFM Economizer 1 2
(ton) Filter2 6/6.5 9.2/10.5/11 13.8/14/16 16/16.5/17 23 24.8/25.5/27.8 32/33/34 41.7/42.4
1800 0.13 --- 0.03 0.03 0.05 --- --- --- --- ---
2000 0.15 --- 0.04 0.04 0.06 --- --- --- --- ---
2200 0.18 --- 0.06 0.06 0.07 --- --- --- --- ---
A7
XXE 2400 0.21 --- 0.07 0.07 0.08 --- --- --- --- ---
(6.0)
2600 0.24 --- 0.08 0.08 0.09 --- --- --- --- ---
2800 0.29 --- 0.09 0.09 0.10 --- --- --- --- ---
3000 0.35 --- 0.11 0.11 0.12 --- --- --- --- ---
1. Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.
2. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct
is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
58 Johnson Controls Ducted Systems
5147362-YTG-R-0323
Additional static resistance - XXE08-12
Size Electric Heat kW2
Model CFM Economizer1 2 4 in. Filter1
(ton) 16/16.5/17 24.8/25.5/27.8 32/33/34 41.7/42.4
2200 0.11 --- 0.07 0.09 0.10 0.12
2600 0.13 --- 0.09 0.11 0.12 0.15
3000 0.17 --- 0.12 0.14 0.15 0.19
3400 0.20 --- 0.15 0.18 0.19 0.23
3800 0.25 --- 0.19 0.22 0.23 0.27
08 (7.5),
XXE 4000 0.28 --- 0.21 0.24 0.25 0.30
09 (8.5)
4400 0.33 --- 0.25 0.29 0.30 0.35
4800 0.38 --- 0.30 0.34 0.35 0.41
5200 0.43 --- 0.35 0.39 0.41 0.47
5600 0.46 --- 0.41 0.45 0.47 0.54
6000 0.50 --- 0.48 0.52 0.54 0.60
2200 0.11 --- 0.07 0.09 0.10 0.12
2600 0.13 --- 0.09 0.11 0.12 0.15
3000 0.17 --- 0.12 0.14 0.15 0.19
3400 0.20 --- 0.15 0.18 0.19 0.23
3800 0.25 --- 0.19 0.22 0.23 0.27
12
XXE 4000 0.28 --- 0.21 0.24 0.25 0.30
(10.0)
4400 0.33 --- 0.25 0.29 0.30 0.35
4800 0.38 --- 0.30 0.34 0.35 0.41
5200 0.43 --- 0.35 0.39 0.41 0.47
5600 0.46 --- 0.41 0.45 0.47 0.54
6000 0.50 --- 0.48 0.52 0.54 0.60
1. Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.
2. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct
is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
Additional static resistance - XQE04-06
Size Electric Heat kW2
Model CFM Economizer1 2 4 in. Filter1
(ton) 6/6.5 9.2/10.5/11 13.8/14/16 23 ---
900 0.15 --- 0.00 0.00 0.01 0.01 ---
1000 0.18 --- 0.00 0.00 0.02 0.02 ---
1100 0.21 --- 0.01 0.01 0.02 0.03 ---
04
XQE 1200 0.24 --- 0.01 0.01 0.02 0.03 ---
(3.0)
1300 0.28 --- 0.01 0.01 0.03 0.03 ---
1400 0.33 --- 0.02 0.02 0.03 0.04 ---
1500 0.44 --- 0.02 0.02 0.04 0.04 ---
1200 0.24 --- 0.01 0.01 0.02 0.03 ---
1300 0.28 --- 0.01 0.01 0.03 0.03 ---
1400 0.33 --- 0.02 0.02 0.03 0.04 ---
1500 0.44 --- 0.02 0.02 0.04 0.04 ---
05
XQE 1600 0.52 --- 0.02 0.02 0.04 0.05 ---
(4.0)
1700 0.59 --- 0.03 0.03 0.05 0.05 ---
1800 0.66 --- 0.03 0.03 0.05 0.06 ---
1900 0.74 --- 0.04 0.04 0.06 0.07 ---
2000 0.81 --- 0.04 0.04 0.07 0.08 ---
1800 0.66 --- 0.03 0.03 0.05 0.06 ---
2000 0.81 --- 0.04 0.04 0.07 0.08 ---
06
XQE 2200 0.95 --- 0.06 0.06 0.08 0.09 ---
(5.0)
2400 1.10 --- 0.07 0.07 0.10 0.11 ---
2500 1.17 --- 0.08 0.08 0.11 0.12 ---
1. Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.
2. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct
is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
Johnson Controls Ducted Systems 59
5147362-YTG-R-0323
Airflow performance
XYE04-09 side duct application (belt drive)
XYE04 (3.0 ton) side duct
Available External Static
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
900 810 0.27 922 0.38 1024 0.49 1118 0.59 1205 0.69 1285 0.80 1359 0.91 1429 1.03 1496 1.16
1000 703 0.19 826 0.31 938 0.43 1041 0.53 1135 0.64 1221 0.74 1301 0.85 1376 0.96 1446 1.08 1513 1.21
1100 721 0.25 843 0.37 956 0.48 1058 0.59 1152 0.69 1239 0.80 1319 0.90 1393 1.01 1463 1.13 1530 1.26
1200 738 0.31 861 0.43 973 0.54 1076 0.65 1170 0.75 1256 0.86 1336 0.96 1411 1.08 1481 1.19 1548 1.33
1300 756 0.38 879 0.50 991 0.61 1094 0.72 1188 0.82 1274 0.92 1354 1.03 1429 1.14 1499 1.26 1566 1.39
1400 774 0.45 897 0.57 1009 0.68 1112 0.79 1206 0.89 1292 1.00 1372 1.10 1447 1.21 1517 1.33 1584 1.47
1500 792 0.53 915 0.65 1027 0.76 1129 0.87 1223 0.97 1310 1.07 1390 1.18 1464 1.29 1535 1.41 1602 1.54
kW = 0.929 x BHP
Bold Field-supplied AK51 x 3/4 in.fixed blower pulley with motor rated at 2.4-hp
Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 2.4-hp
Bold Field-supplied AK41 x 3/4 in.fixed blower pulley with motor rated at 2.4-hp
XYE05 (4.0 ton) side duct
Available External Static
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1200 759 0.28 860 0.38 957 0.49 1050 0.62 1139 0.76 1224 0.89 1306 1.03 1383 1.15 1457 1.26 1527 1.36
1300 777 0.34 878 0.44 975 0.55 1068 0.68 1157 0.81 1242 0.95 1324 1.08 1401 1.21 1475 1.32 1545 1.42
1400 796 0.40 897 0.50 995 0.61 1088 0.74 1177 0.88 1262 1.01 1343 1.15 1420 1.27 1494 1.38 1564 1.48
1500 816 0.46 918 0.56 1015 0.68 1108 0.81 1197 0.94 1282 1.08 1363 1.21 1440 1.34 1514 1.45 1584 1.54
1600 837 0.53 938 0.63 1035 0.75 1129 0.88 1218 1.01 1303 1.15 1384 1.28 1461 1.41 1535 1.52 1605 1.61
1700 858 0.61 960 0.71 1057 0.83 1150 0.95 1239 1.09 1324 1.22 1405 1.36 1482 1.48 1556 1.60 1626 1.69
1800 880 0.69 981 0.79 1078 0.91 1171 1.04 1260 1.17 1345 1.31 1427 1.44 1504 1.57 1578 1.68 1648 1.77
1900 902 0.78 1003 0.88 1100 1.00 1193 1.12 1282 1.26 1367 1.40 1448 1.53 1526 1.65 1599 1.77 -- --
2000 924 0.88 1025 0.98 1122 1.09 1215 1.22 1304 1.35 1389 1.49 1470 1.62 1548 1.75 1621 1.86 -- --
kW = 0.929 x BHP
Bold Field-supplied AK51 x 3/4 in.fixed blower pulley with motor rated at 2.4-hp
Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 2.4-hp
Bold Field-supplied AK41 x 3/4 in.fixed blower pulley with motor rated at 2.4-hp
-- Exceeds recommended blower speed
XYE06 (5.0 ton) side duct
Available External Static
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1500 770 0.40 836 0.50 901 0.60 964 0.69 1025 0.79 1084 0.89 1142 0.98 1197 1.07 1250 1.15 1300 1.23
1600 779 0.45 845 0.54 910 0.64 973 0.74 1034 0.83 1093 0.93 1151 1.02 1206 1.11 1259 1.20 1309 1.27
1700 791 0.50 857 0.60 922 0.69 985 0.79 1046 0.89 1105 0.98 1162 1.07 1218 1.16 1271 1.25 1321 1.33
1800 805 0.56 872 0.66 936 0.75 999 0.85 1060 0.95 1120 1.04 1177 1.13 1232 1.22 1285 1.31 1335 1.39
1900 822 0.63 888 0.72 953 0.82 1016 0.92 1077 1.01 1136 1.11 1194 1.20 1249 1.29 1302 1.38 1352 1.46
2000 841 0.70 907 0.80 972 0.89 1035 0.99 1096 1.09 1155 1.18 1212 1.27 1268 1.36 1321 1.45 1371 1.53
2100 862 0.78 928 0.87 993 0.97 1056 1.07 1117 1.16 1176 1.26 1233 1.35 1289 1.44 1341 1.53 1392 1.61
2200 885 0.86 951 0.96 1016 1.05 1079 1.15 1140 1.25 1199 1.34 1256 1.43 1311 1.52 1364 1.61 1415 1.69
2300 910 0.95 976 1.04 1040 1.14 1103 1.23 1165 1.33 1224 1.43 1281 1.52 1336 1.61 1389 1.69 1440 1.77
2400 936 1.03 1002 1.13 1067 1.23 1130 1.32 1191 1.42 1250 1.52 1307 1.61 1362 1.70 1415 1.78 1466 1.86
2500 964 1.13 1030 1.22 1095 1.32 1158 1.41 1219 1.51 1278 1.61 1335 1.70 1390 1.79 1443 1.87 1494 1.95
kW = 0.857 x BHP
Bold Field-supplied AK51 x 3/4 in.fixed blower pulley with motor rated at 2.4-hp
Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 2.9-hp
60 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XYEA7 (6.0 ton) side duct
Available External Static
CFM 0.20 0.40 0.60 0.80 1.00 1.20 1.40 1.60 1.80 2.00
RPMs BHP RPMs BHP RPMs BHP RPMs BHP RPMs BHP RPMs BHP RPMs BHP RPMs BHP RPMs BHP RPMs BHP
1800 532 0.30 592 0.48 647 0.66 698 0.84 746 1.02 793 1.19 842 1.34 892 1.48 946 1.60 1006 1.69
1900 540 0.34 600 0.52 655 0.70 706 0.88 754 1.06 802 1.23 850 1.39 900 1.52 954 1.64 1014 1.73
2000 548 0.39 609 0.56 664 0.74 714 0.92 763 1.10 810 1.27 859 1.43 909 1.57 963 1.68 1023 1.77
2100 558 0.43 618 0.61 673 0.79 724 0.97 772 1.15 820 1.32 868 1.47 918 1.61 972 1.73 1032 1.82
2200 567 0.48 628 0.66 683 0.84 733 1.02 782 1.20 829 1.37 877 1.52 928 1.66 982 1.78 1042 1.86
2300 578 0.53 638 0.71 693 0.89 744 1.07 792 1.25 839 1.42 888 1.57 938 1.71 992 1.83 1052 1.91
2400 588 0.59 648 0.76 703 0.94 754 1.12 802 1.30 850 1.47 898 1.63 948 1.77 1003 1.88 1062 1.97
2500 599 0.64 659 0.82 714 1.00 765 1.18 813 1.36 861 1.53 909 1.69 959 1.82 1013 1.94 1073 2.03
2600 610 0.71 670 0.88 725 1.06 776 1.24 824 1.42 872 1.59 920 1.75 971 1.89 1025 2.00 1084 2.09
2700 622 0.77 682 0.95 737 1.13 788 1.31 836 1.49 883 1.66 932 1.81 982 1.95 1036 2.07 1096 2.16
2800 633 0.84 694 1.02 749 1.20 799 1.38 848 1.56 895 1.73 943 1.89 994 2.02 1048 2.14 - -
2900 646 0.92 706 1.09 761 1.27 812 1.46 860 1.63 907 1.80 956 1.96 1006 2.10 1060 2.21 - -
3000 658 1.00 718 1.17 773 1.35 824 1.54 872 1.71 920 1.88 968 2.04 1018 2.18 1073 2.29 - -
Standard Static Option with Motor rated at 2.4-Max Bhp
Medium Static Option with Motor rated at 2.4-Max Bhp
High Static Option with Motor rated at 3.7-Max Bhp
-- Exceeds recommended blower speed
XYE08 (7.5 ton) side duct
Available External Static
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2250 562 0.17 616 0.36 671 0.57 726 0.78 781 1.00 835 1.20 886 1.40 935 1.59 979 1.75 1019 1.89
2400 567 0.26 620 0.45 675 0.65 730 0.87 785 1.08 839 1.29 890 1.49 939 1.67 983 1.84 1023 1.97
2600 572 0.38 625 0.58 680 0.78 736 0.99 790 1.21 844 1.42 895 1.62 944 1.80 989 1.96 1029 2.10
2800 578 0.53 632 0.72 687 0.93 742 1.14 797 1.35 850 1.56 902 1.76 950 1.95 995 2.11 1035 2.24
3000 586 0.69 639 0.88 694 1.08 749 1.30 804 1.51 858 1.72 909 1.92 958 2.10 1002 2.27 1043 2.40
3200 595 0.86 648 1.05 703 1.25 758 1.46 813 1.68 867 1.89 918 2.09 967 2.27 1012 2.43 1052 2.57
3400 606 1.03 660 1.23 714 1.43 770 1.64 824 1.86 878 2.07 930 2.27 978 2.45 1023 2.61 1063 2.75
3600 619 1.22 673 1.41 728 1.62 783 1.83 838 2.04 891 2.25 943 2.45 991 2.63 1036 2.80 1076 2.93
3750 631 1.36 684 1.55 739 1.76 794 1.97 849 2.19 903 2.39 954 2.59 1003 2.78 1047 2.94 1087 3.08
Standard Static Option with Motor rated at 2.4-hp
Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 3.7-hp
kW = 0.929 x BHP for Standard and Medium Static options kW = 0.895 x BHP for High Static option
XYE09 (8.5 ton) side duct
Available External Static
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2550 571 0.35 624 0.54 679 0.75 734 0.96 789 1.17 843 1.38 894 1.58 943 1.77 987 1.93 1027 2.07
2600 572 0.38 625 0.58 680 0.78 736 0.99 790 1.21 844 1.42 895 1.62 944 1.80 989 1.96 1029 2.10
2800 578 0.53 632 0.72 687 0.93 742 1.14 797 1.35 850 1.56 902 1.76 950 1.95 995 2.11 1035 2.24
3000 586 0.69 639 0.88 694 1.08 749 1.30 804 1.51 858 1.72 909 1.92 958 2.10 1002 2.27 1043 2.40
3200 595 0.86 648 1.05 703 1.25 758 1.46 813 1.68 867 1.89 918 2.09 967 2.27 1012 2.43 1052 2.57
3400 606 1.03 660 1.23 714 1.43 770 1.64 824 1.86 878 2.07 930 2.27 978 2.45 1023 2.61 1063 2.75
3600 619 1.22 673 1.41 728 1.62 783 1.83 838 2.04 891 2.25 943 2.45 991 2.63 1036 2.80 1076 2.93
3800 635 1.41 688 1.60 743 1.81 798 2.02 853 2.23 907 2.44 958 2.64 1007 2.83 1051 2.99 1091 3.13
4000 652 1.61 706 1.80 761 2.01 816 2.22 871 2.43 924 2.64 976 2.84 1024 3.02 1069 3.19 -- --
4200 672 1.81 726 2.00 781 2.21 836 2.42 891 2.64 944 2.84 996 3.04 1044 3.23 1089 3.39 -- --
4250 678 1.86 731 2.06 786 2.26 841 2.47 896 2.69 950 2.90 1001 3.10 1050 3.28 1094 3.44 -- --
Standard Static Option with Motor rated at 2.4-hp
Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 3.7-hp
Bold Field-supplied AK79 x 1 fixed pulley with Motor rated at 3.7-hp
-- Exceeds recommended blower speed
kW = 0.929 x BHP for Standard and Medium Static options kW = 0.895 x BHP for High Static option
Johnson Controls Ducted Systems 61
5147362-YTG-R-0323
XXEA7, XXE08 - XXE09, XXE12 side duct application (belt drive)
XXEA7 (6.0 ton) side duct
Available External Static Pressure - IWG
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1800 845 0.46 901 0.58 959 0.71 1017 0.83 1076 0.96 1133 1.08 1188 1.21 1240 1.34 1288 1.47 1332 1.60
1900 860 0.53 917 0.66 974 0.78 1033 0.91 1091 1.03 1148 1.16 1203 1.28 1255 1.41 1303 1.54 1347 1.68
2000 878 0.62 934 0.74 992 0.86 1050 0.99 1108 1.11 1165 1.24 1220 1.36 1272 1.49 1321 1.62 1365 1.76
2100 897 0.70 954 0.83 1011 0.95 1070 1.08 1128 1.20 1185 1.33 1240 1.45 1292 1.58 1340 1.71 1384 1.84
2200 919 0.80 975 0.92 1033 1.05 1091 1.17 1149 1.29 1206 1.42 1261 1.55 1313 1.68 1362 1.81 1406 1.94
2300 942 0.90 998 1.02 1056 1.15 1114 1.27 1172 1.40 1229 1.52 1284 1.65 1336 1.78 1385 1.91 1429 2.04
2400 966 1.01 1022 1.14 1080 1.26 1138 1.38 1196 1.51 1253 1.63 1308 1.76 1361 1.89 1409 2.02 1453 2.15
2500 992 1.13 1048 1.25 1106 1.38 1164 1.50 1222 1.63 1279 1.75 1334 1.88 1386 2.01 1435 2.14 1479 2.27
2600 1018 1.26 1075 1.38 1132 1.51 1191 1.63 1249 1.76 1306 1.88 1361 2.01 1413 2.14 1461 2.27 1505 2.40
2700 1046 1.40 1102 1.52 1160 1.64 1218 1.77 1276 1.89 1333 2.02 1388 2.14 1441 2.27 1489 2.40 1533 2.54
2800 1075 1.54 1131 1.67 1188 1.79 1247 1.91 1305 2.04 1362 2.16 1417 2.29 1469 2.42 1518 2.55 1561 2.68
2900 1104 1.70 1160 1.82 1218 1.94 1276 2.07 1334 2.19 1391 2.32 1446 2.45 1498 2.57 1547 2.70 1591 2.84
3000 1134 1.86 1190 1.98 1248 2.11 1306 2.23 1364 2.36 1421 2.48 1476 2.61 1528 2.74 1577 2.87 1621 3.00
Standard Static Option with Motor rated at 2.4-hp
Medium Static Option with Motor rated at 2.9-hp
High Static Option with Motor rated at 3.7-hp
- Exceeds recommended blower speed
Note: See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = 0.929 x BHP
XXE08 (7.5 ton) side duct
Available External Static
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2250 562 0.17 616 0.36 671 0.57 726 0.78 781 1.00 835 1.20 886 1.40 935 1.59 979 1.75 1019 1.89
2400 567 0.26 620 0.45 675 0.65 730 0.87 785 1.08 839 1.29 890 1.49 939 1.67 983 1.84 1023 1.97
2600 572 0.38 625 0.58 680 0.78 736 0.99 790 1.21 844 1.42 895 1.62 944 1.80 989 1.96 1029 2.10
2800 578 0.53 632 0.72 687 0.93 742 1.14 797 1.35 850 1.56 902 1.76 950 1.95 995 2.11 1035 2.24
3000 586 0.69 639 0.88 694 1.08 749 1.30 804 1.51 858 1.72 909 1.92 958 2.10 1002 2.27 1043 2.40
3200 595 0.86 648 1.05 703 1.25 758 1.46 813 1.68 867 1.89 918 2.09 967 2.27 1012 2.43 1052 2.57
3400 606 1.03 660 1.23 714 1.43 770 1.64 824 1.86 878 2.07 930 2.27 978 2.45 1023 2.61 1063 2.75
3600 619 1.22 673 1.41 728 1.62 783 1.83 838 2.04 891 2.25 943 2.45 991 2.63 1036 2.80 1076 2.93
3750 631 1.36 684 1.55 739 1.76 794 1.97 849 2.19 903 2.39 954 2.59 1003 2.78 1047 2.94 1087 3.08
Standard Static Option with Motor rated at 2.4-hp
Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 3.7-hp
kW = 0.929 x BHP for Standard and Medium Static options kW = 0.895 x BHP for High Static option
62 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XXE09 (8.5 ton) side duct
Available External Static
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2550 571 0.35 624 0.54 679 0.75 734 0.96 789 1.17 843 1.38 894 1.58 943 1.77 987 1.93 1027 2.07
2600 572 0.38 625 0.58 680 0.78 736 0.99 790 1.21 844 1.42 895 1.62 944 1.80 989 1.96 1029 2.10
2800 578 0.53 632 0.72 687 0.93 742 1.14 797 1.35 850 1.56 902 1.76 950 1.95 995 2.11 1035 2.24
3000 586 0.69 639 0.88 694 1.08 749 1.30 804 1.51 858 1.72 909 1.92 958 2.10 1002 2.27 1043 2.40
3200 595 0.86 648 1.05 703 1.25 758 1.46 813 1.68 867 1.89 918 2.09 967 2.27 1012 2.43 1052 2.57
3400 606 1.03 660 1.23 714 1.43 770 1.64 824 1.86 878 2.07 930 2.27 978 2.45 1023 2.61 1063 2.75
3600 619 1.22 673 1.41 728 1.62 783 1.83 838 2.04 891 2.25 943 2.45 991 2.63 1036 2.80 1076 2.93
3800 635 1.41 688 1.60 743 1.81 798 2.02 853 2.23 907 2.44 958 2.64 1007 2.83 1051 2.99 1091 3.13
4000 652 1.61 706 1.80 761 2.01 816 2.22 871 2.43 924 2.64 976 2.84 1024 3.02 1069 3.19 -- --
4200 672 1.81 726 2.00 781 2.21 836 2.42 891 2.64 944 2.84 996 3.04 1044 3.23 1089 3.39 -- --
4250 678 1.86 731 2.06 786 2.26 841 2.47 896 2.69 950 2.90 1001 3.10 1050 3.28 1094 3.44 -- --
Standard Static Option with Motor rated at 2.4-hp
Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 3.7-hp
Bold Field-supplied AK79 x 1 fixed pulley with Motor rated at 3.7-hp
-- Exceeds recommended blower speed
kW = 0.929 x BHP for Standard and Medium Static options kW = 0.895 x BHP for High Static option
XXE12 (10 ton) side duct
Available External Static Pressure - IWG
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3000 665 0.63 707 0.90 750 1.15 795 1.39 842 1.62 888 1.85 935 2.07 980 2.30 1024 2.53
3200 673 0.79 714 1.06 758 1.31 803 1.56 849 1.79 896 2.01 942 2.24 988 2.47 1032 2.70
3400 682 0.97 723 1.24 767 1.50 812 1.74 858 1.97 905 2.20 951 2.42 997 2.65 1041 2.88
3600 654 0.88 692 1.17 733 1.44 777 1.69 822 1.93 868 2.17 915 2.39 961 2.62 1007 2.84 1051 3.08
3800 665 1.10 704 1.38 745 1.65 788 1.91 834 2.15 880 2.38 927 2.61 973 2.83 1018 3.06 1062 3.29
4000 678 1.32 717 1.61 758 1.88 801 2.13 847 2.37 893 2.61 940 2.83 986 3.06 1032 3.28 1076 3.52
4200 693 1.57 731 1.85 772 2.12 816 2.37 861 2.62 907 2.85 954 3.07 1000 3.30 1046 3.53 1090 3.76
4400 709 1.82 747 2.11 788 2.38 832 2.63 877 2.87 923 3.10 970 3.33 1016 3.55 1062 3.78 1106 4.01
4600 726 2.09 764 2.37 806 2.64 849 2.90 894 3.14 941 3.37 987 3.60 1034 3.82 1079 4.05 1123 4.28
4800 745 2.37 783 2.65 824 2.92 868 3.18 913 3.42 959 3.65 1006 3.88 1052 4.10 1098 4.33 1142 4.56
5000 765 2.66 803 2.95 844 3.22 888 3.47 933 3.71 979 3.94 1026 4.17 1072 4.39 1118 4.62 1162 4.85
Standard Static Option with Motor rated at 2.4-hp
Medium Static Option with Motor rated at 3.7-hp
Bold Field Supplied AK84 x 1 fixed pulley with Motor rated at 3.7-hp
High Static Option with Motor rated at 5.25-hp
Exceeds recommended blower speed
Johnson Controls Ducted Systems 63
5147362-YTG-R-0323
XQE04-06 side duct application (belt drive)
XQE04 (3.0 ton) side duct
Available External Static
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
900 810 0.27 922 0.38 1024 0.49 1118 0.59 1205 0.69 1285 0.80 1359 0.91 1429 1.03 1496 1.16
1000 703 0.19 826 0.31 938 0.43 1041 0.53 1135 0.64 1221 0.74 1301 0.85 1376 0.96 1446 1.08 1513 1.21
1100 721 0.25 843 0.37 956 0.48 1058 0.59 1152 0.69 1239 0.80 1319 0.90 1393 1.01 1463 1.13 1530 1.26
1200 738 0.31 861 0.43 973 0.54 1076 0.65 1170 0.75 1256 0.86 1336 0.96 1411 1.08 1481 1.19 1548 1.33
1300 756 0.38 879 0.50 991 0.61 1094 0.72 1188 0.82 1274 0.92 1354 1.03 1429 1.14 1499 1.26 1566 1.39
1400 774 0.45 897 0.57 1009 0.68 1112 0.79 1206 0.89 1292 1.00 1372 1.10 1447 1.21 1517 1.33 1584 1.47
1500 792 0.53 915 0.65 1027 0.76 1129 0.87 1223 0.97 1310 1.07 1390 1.18 1464 1.29 1535 1.41 1602 1.54
kW = 0.929 x BHP
Bold Field-supplied AK51 x 3/4 in.fixed blower pulley with motor rated at 2.4-hp
Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 2.4-hp
Bold Field-supplied AK41 x 3/4 in.fixed blower pulley with motor rated at 2.4-hp
XQE05 (4.0 ton) side duct
Available External Static
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1200 759 0.28 860 0.38 957 0.49 1050 0.62 1139 0.76 1224 0.89 1306 1.03 1383 1.15 1457 1.26 1527 1.36
1300 777 0.34 878 0.44 975 0.55 1068 0.68 1157 0.81 1242 0.95 1324 1.08 1401 1.21 1475 1.32 1545 1.42
1400 796 0.40 897 0.50 995 0.61 1088 0.74 1177 0.88 1262 1.01 1343 1.15 1420 1.27 1494 1.38 1564 1.48
1500 816 0.46 918 0.56 1015 0.68 1108 0.81 1197 0.94 1282 1.08 1363 1.21 1440 1.34 1514 1.45 1584 1.54
1600 837 0.53 938 0.63 1035 0.75 1129 0.88 1218 1.01 1303 1.15 1384 1.28 1461 1.41 1535 1.52 1605 1.61
1700 858 0.61 960 0.71 1057 0.83 1150 0.95 1239 1.09 1324 1.22 1405 1.36 1482 1.48 1556 1.60 1626 1.69
1800 880 0.69 981 0.79 1078 0.91 1171 1.04 1260 1.17 1345 1.31 1427 1.44 1504 1.57 1578 1.68 1648 1.77
1900 902 0.78 1003 0.88 1100 1.00 1193 1.12 1282 1.26 1367 1.40 1448 1.53 1526 1.65 1599 1.77 -- --
2000 924 0.88 1025 0.98 1122 1.09 1215 1.22 1304 1.35 1389 1.49 1470 1.62 1548 1.75 1621 1.86 -- --
kW = 0.929 x BHP
Bold Field-supplied AK51 x 3/4 in.fixed blower pulley with motor rated at 2.4-hp
Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 2.4-hp
Bold Field-supplied AK41 x 3/4 in.fixed blower pulley with motor rated at 2.4-hp
-- Exceeds recommended blower speed
XQE06 (5.0 ton) side duct
Available External Static
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1500 770 0.40 836 0.50 901 0.60 964 0.69 1025 0.79 1084 0.89 1142 0.98 1197 1.07 1250 1.15 1300 1.23
1600 779 0.45 845 0.54 910 0.64 973 0.74 1034 0.83 1093 0.93 1151 1.02 1206 1.11 1259 1.20 1309 1.27
1700 791 0.50 857 0.60 922 0.69 985 0.79 1046 0.89 1105 0.98 1162 1.07 1218 1.16 1271 1.25 1321 1.33
1800 805 0.56 872 0.66 936 0.75 999 0.85 1060 0.95 1120 1.04 1177 1.13 1232 1.22 1285 1.31 1335 1.39
1900 822 0.63 888 0.72 953 0.82 1016 0.92 1077 1.01 1136 1.11 1194 1.20 1249 1.29 1302 1.38 1352 1.46
2000 841 0.70 907 0.80 972 0.89 1035 0.99 1096 1.09 1155 1.18 1212 1.27 1268 1.36 1321 1.45 1371 1.53
2100 862 0.78 928 0.87 993 0.97 1056 1.07 1117 1.16 1176 1.26 1233 1.35 1289 1.44 1341 1.53 1392 1.61
2200 885 0.86 951 0.96 1016 1.05 1079 1.15 1140 1.25 1199 1.34 1256 1.43 1311 1.52 1364 1.61 1415 1.69
2300 910 0.95 976 1.04 1040 1.14 1103 1.23 1165 1.33 1224 1.43 1281 1.52 1336 1.61 1389 1.69 1440 1.77
2400 936 1.03 1002 1.13 1067 1.23 1130 1.32 1191 1.42 1250 1.52 1307 1.61 1362 1.70 1415 1.78 1466 1.86
2500 964 1.13 1030 1.22 1095 1.32 1158 1.41 1219 1.51 1278 1.61 1335 1.70 1390 1.79 1443 1.87 1494 1.95
kW = 0.857 x BHP
Bold Field-supplied AK51 x 3/4 in.fixed blower pulley with motor rated at 2.4-hp
Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 2.9-hp
64 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XYE04-09 bottom duct application (belt drive)
XYE04 (3.0 ton) bottom duct
Available External Static
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
900 743 0.14 852 0.26 955 0.37 1050 0.48 1140 0.57 1225 0.67 1306 0.77 1384 0.87 1460 0.98 1535 1.09
1000 757 0.20 867 0.33 969 0.44 1065 0.54 1155 0.64 1240 0.74 1321 0.84 1399 0.94 1475 1.04 1549 1.16
1100 774 0.27 884 0.40 986 0.51 1082 0.61 1172 0.71 1257 0.81 1338 0.91 1416 1.01 1492 1.11 1566 1.23
1200 793 0.35 903 0.47 1005 0.58 1101 0.69 1191 0.78 1276 0.88 1357 0.98 1435 1.08 1511 1.19 1585 1.30
1300 814 0.42 924 0.54 1026 0.65 1122 0.76 1212 0.86 1297 0.96 1378 1.05 1456 1.15 1532 1.26 1606 1.37
1400 837 0.49 947 0.61 1049 0.72 1145 0.83 1235 0.93 1320 1.03 1401 1.12 1479 1.23 1555 1.33 1629 1.45
1500 862 0.56 972 0.68 1074 0.79 1170 0.90 1260 1.00 1345 1.09 1426 1.19 1504 1.29 1580 1.40 -- --
kW = 0.929 x BHP
Bold Field-supplied AK51 x 3/4 in.fixed blower pulley with motor rated at 2.4-hp
Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 2.4-hp
Bold Field-supplied AK41 x 3/4 in.fixed blower pulley with motor rated at 2.4-hp
-- Exceeds recommended blower speed
XYE05 (4.0 ton) bottom duct
Available External Static
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1200 801 0.25 903 0.38 999 0.51 1089 0.63 1173 0.76 1252 0.88 1327 1.00 1396 1.11 1461 1.22 1521 1.33
1300 822 0.31 924 0.44 1020 0.57 1110 0.69 1194 0.82 1273 0.94 1348 1.06 1417 1.17 1482 1.28 1542 1.39
1400 844 0.38 946 0.51 1042 0.64 1132 0.76 1216 0.89 1295 1.01 1370 1.13 1439 1.24 1504 1.35 1564 1.46
1500 867 0.46 969 0.59 1065 0.71 1155 0.84 1239 0.96 1319 1.08 1393 1.20 1462 1.32 1527 1.43 1587 1.53
1600 891 0.54 993 0.67 1089 0.79 1179 0.92 1264 1.04 1343 1.16 1417 1.28 1486 1.40 1551 1.51 1612 1.61
1700 917 0.63 1019 0.75 1115 0.88 1205 1.01 1289 1.13 1368 1.25 1442 1.37 1512 1.48 1577 1.60 1637 1.70
1800 943 0.72 1045 0.85 1141 0.97 1231 1.10 1316 1.22 1395 1.34 1469 1.46 1538 1.58 1603 1.69 -- --
1900 971 0.81 1073 0.94 1169 1.07 1259 1.19 1344 1.32 1423 1.44 1497 1.56 1566 1.67 1631 1.78 -- --
2000 1000 0.92 1102 1.04 1198 1.17 1288 1.29 1372 1.42 1452 1.54 1526 1.66 1595 1.77 -- -- -- --
kW = 0.929 x BHP
Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 2.4-hp
Bold Field-supplied AK41 x 3/4 in.fixed blower pulley with motor rated at 2.4-hp
-- Exceeds recommended blower speed
XYE06 (5.0 ton) bottom duct
Available External Static
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1500 812 0.36 869 0.46 931 0.55 997 0.64 1063 0.74 1129 0.84 1193 0.94 1253 1.05 1307 1.16 1354 1.27
1600 829 0.43 886 0.52 948 0.61 1013 0.71 1080 0.80 1146 0.90 1210 1.01 1270 1.11 1324 1.22 1370 1.34
1700 846 0.50 904 0.59 966 0.68 1031 0.78 1097 0.87 1164 0.97 1227 1.07 1287 1.18 1341 1.29 1388 1.41
1800 865 0.57 922 0.66 985 0.75 1050 0.85 1116 0.95 1182 1.05 1246 1.15 1306 1.25 1360 1.36 1407 1.48
1900 885 0.65 943 0.74 1005 0.83 1070 0.93 1136 1.02 1203 1.12 1266 1.23 1326 1.33 1380 1.44 1427 1.56
2000 907 0.73 964 0.82 1026 0.92 1092 1.01 1158 1.11 1224 1.21 1288 1.31 1348 1.42 1402 1.53 1449 1.64
2100 930 0.82 987 0.91 1049 1.01 1115 1.10 1181 1.20 1247 1.30 1311 1.40 1371 1.51 1425 1.62 1472 1.73
2200 955 0.92 1012 1.01 1074 1.10 1139 1.20 1206 1.29 1272 1.39 1336 1.50 1396 1.60 1450 1.71 1496 1.83
2300 981 1.02 1038 1.11 1101 1.20 1166 1.30 1232 1.39 1298 1.49 1362 1.60 1422 1.70 1476 1.81 1523 1.93
2400 1009 1.12 1066 1.22 1128 1.31 1194 1.40 1260 1.50 1326 1.60 1390 1.70 1450 1.81 1504 1.92 1551 2.03
2500 1038 1.24 1096 1.33 1158 1.42 1223 1.52 1290 1.61 1356 1.71 1420 1.82 1480 1.92 1534 2.03 1580 2.15
kW = 0.857 x BHP
Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 2.9-hp
Johnson Controls Ducted Systems 65
5147362-YTG-R-0323
XYEA7 (6.0 ton) bottom duct
Available External Static
CFM 0.20 0.40 0.60 0.80 1.00 1.20 1.40 1.60 1.80 2.00
RPMs BHP RPMs BHP RPMs BHP RPMs BHP RPMs BHP RPMs BHP RPMs BHP RPMs BHP RPMs BHP RPMs BHP
1800 517 0.35 592 0.51 661 0.67 723 0.83 779 0.99 832 1.15 881 1.30 927 1.43 973 1.56 1017 1.66
1900 526 0.39 601 0.55 670 0.71 732 0.87 789 1.03 841 1.19 890 1.34 937 1.48 982 1.60 1026 1.71
2000 535 0.44 611 0.60 679 0.76 741 0.92 798 1.08 850 1.24 899 1.39 946 1.52 991 1.65 1036 1.76
2100 544 0.49 620 0.65 688 0.81 750 0.97 807 1.13 859 1.29 908 1.44 955 1.57 1000 1.70 1045 1.80
2200 554 0.54 629 0.70 698 0.86 760 1.02 816 1.18 869 1.34 918 1.49 964 1.63 1010 1.75 1054 1.86
2300 563 0.60 639 0.76 707 0.92 769 1.08 826 1.24 878 1.40 927 1.55 974 1.68 1019 1.81 1064 1.91
2400 573 0.66 649 0.82 717 0.98 779 1.14 836 1.30 888 1.46 937 1.61 984 1.74 1029 1.87 1074 1.98
2500 583 0.73 658 0.88 727 1.04 789 1.20 846 1.37 898 1.52 947 1.67 994 1.81 1039 1.93 1084 2.04
2600 593 0.79 669 0.95 737 1.11 799 1.27 856 1.43 908 1.59 957 1.74 1004 1.88 1049 2.00 1094 2.11
2700 603 0.87 679 1.02 747 1.18 809 1.35 866 1.51 919 1.66 968 1.81 1014 1.95 1059 2.07 - -
2800 614 0.94 690 1.10 758 1.26 820 1.42 877 1.58 929 1.74 978 1.89 1025 2.03 1070 2.15 - -
2900 625 1.02 701 1.18 769 1.34 831 1.50 888 1.66 940 1.82 989 1.97 1036 2.11 1081 2.23 - -
3000 636 1.11 712 1.27 780 1.43 842 1.59 899 1.75 951 1.91 1000 2.05 1047 2.19 1092 2.32 - -
Standard Static Option with Motor rated at 2.4-Max Bhp
Medium Static Option with Motor rated at 2.9-Max Bhp
High Static Option with Motor rated at 3.7-Max Bhp
-- Exceeds recommended blower speed
kW = 0.929 x BHP for Standard and Medium Static options kW = 0.895 x BHP for High Static option
XYE08 (7.5 ton) bottom duct
Available External Static
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2250 552 0.25 614 0.43 674 0.63 733 0.83 789 1.02 844 1.22 898 1.41 950 1.58 1000 1.75 1049 1.89
2400 559 0.34 621 0.52 682 0.72 740 0.91 797 1.11 852 1.31 905 1.49 957 1.67 1007 1.83 1056 1.98
2600 569 0.47 631 0.65 691 0.85 750 1.04 806 1.24 861 1.44 915 1.62 967 1.80 1017 1.96 1066 2.11
2800 579 0.61 641 0.79 701 0.99 760 1.19 817 1.38 872 1.58 925 1.77 977 1.94 1027 2.11 1076 2.25
3000 590 0.76 652 0.95 713 1.14 771 1.34 828 1.54 883 1.73 936 1.92 988 2.10 1038 2.26 1087 2.40
3200 602 0.92 665 1.11 725 1.30 783 1.50 840 1.70 895 1.89 948 2.08 1000 2.26 1050 2.42 1099 2.57
3400 616 1.09 678 1.28 738 1.47 797 1.67 854 1.87 909 2.06 962 2.25 1014 2.43 1064 2.59 -- --
3600 631 1.27 693 1.45 754 1.65 812 1.85 869 2.04 924 2.24 977 2.43 1029 2.60 1079 2.77 -- --
3750 644 1.40 706 1.59 766 1.78 824 1.98 881 2.18 936 2.37 990 2.56 1041 2.74 1092 2.90 -- --
Standard Static Option with Motor rated at 2.4-hp
Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 3.7-hp
-- Exceeds recommended blower speed
kW = 0.929 x BHP for Standard and Medium Static options kW = 0.895 x BHP for High Static option
XYE09 (8.5 ton) bottom duct
Available External Static
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2550 567 0.43 629 0.62 689 0.81 747 1.01 804 1.21 859 1.40 912 1.59 964 1.77 1014 1.93 1063 2.07
2600 569 0.47 631 0.65 691 0.85 750 1.04 806 1.24 861 1.44 915 1.62 967 1.80 1017 1.96 1066 2.11
2800 579 0.61 641 0.79 701 0.99 760 1.19 817 1.38 872 1.58 925 1.77 977 1.94 1027 2.11 1076 2.25
3000 590 0.76 652 0.95 713 1.14 771 1.34 828 1.54 883 1.73 936 1.92 988 2.10 1038 2.26 1087 2.40
3200 602 0.92 665 1.11 725 1.30 783 1.50 840 1.70 895 1.89 948 2.08 1000 2.26 1050 2.42 1099 2.57
3400 616 1.09 678 1.28 738 1.47 797 1.67 854 1.87 909 2.06 962 2.25 1014 2.43 1064 2.59 -- --
3600 631 1.27 693 1.45 754 1.65 812 1.85 869 2.04 924 2.24 977 2.43 1029 2.60 1079 2.77 -- --
3800 648 1.45 710 1.64 770 1.83 829 2.03 885 2.23 940 2.42 994 2.61 1046 2.78 1096 2.95 -- --
4000 666 1.64 729 1.82 789 2.01 847 2.21 904 2.41 959 2.61 1012 2.79 1064 2.97 -- -- -- --
4200 687 1.82 749 2.01 809 2.20 867 2.42 924 2.60 979 2.79 1032 2.98 1084 3.16 -- -- -- --
4250 692 1.87 754 2.06 814 2.25 873 2.45 929 2.65 984 2.84 1038 3.03 1090 3.21 -- -- -- --
Standard Static Option with Motor rated at 2.4-hp
Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 3.7-hp
-- Exceeds recommended blower speed
kW = 0.929 x BHP for Standard and Medium Static options kW = 0.895 x BHP for High Static option
66 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XXEA7-12 bottom duct application (belt drive)
XXEA7 (6.0 ton) bottom duct
Available External Static Pressure - IWG
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1800 843 0.55 911 0.66 975 0.79 1035 0.93 1092 1.07 1148 1.21 1203 1.36 1258 1.49 1316 1.62 1376 1.74
1900 870 0.62 939 0.74 1003 0.86 1063 1.00 1120 1.14 1175 1.29 1230 1.43 1286 1.56 1343 1.69 1404 1.81
2000 898 0.70 967 0.82 1031 0.95 1090 1.08 1147 1.22 1203 1.37 1258 1.51 1314 1.64 1371 1.77 1432 1.89
2100 926 0.79 995 0.91 1059 1.04 1119 1.17 1176 1.31 1231 1.46 1286 1.60 1342 1.73 1399 1.86 1460 1.98
2200 955 0.89 1023 1.01 1087 1.14 1147 1.27 1204 1.41 1260 1.56 1315 1.70 1370 1.83 1428 1.96 1488 2.08
2300 983 1.00 1052 1.12 1116 1.24 1176 1.38 1233 1.52 1288 1.67 1343 1.81 1399 1.94 1456 2.07 1517 2.19
2400 1012 1.12 1081 1.23 1145 1.36 1205 1.50 1262 1.64 1317 1.79 1372 1.93 1428 2.06 1485 2.19 1546 2.31
2500 1041 1.25 1110 1.36 1173 1.49 1233 1.63 1290 1.77 1346 1.91 1401 2.06 1457 2.19 1514 2.32 1574 2.44
2600 1070 1.38 1139 1.50 1202 1.63 1262 1.77 1319 1.91 1375 2.05 1430 2.19 1485 2.33 1543 2.46 1603 2.57
2700 1098 1.53 1167 1.65 1231 1.78 1291 1.91 1348 2.06 1404 2.20 1459 2.34 1514 2.48 1572 2.60 1632 2.72
2800 1127 1.69 1196 1.80 1260 1.93 1320 2.07 1377 2.21 1432 2.36 1487 2.50 1543 2.63 1600 2.76 - -
2900 1156 1.85 1225 1.97 1289 2.10 1348 2.24 1406 2.38 1461 2.52 1516 2.66 1572 2.80 1629 2.93 - -
3000 1184 2.03 1253 2.14 1317 2.27 1377 2.41 1434 2.55 1490 2.69 1545 2.84 1600 2.97 1658 3.10 - -
Standard Static Option with Motor rated at 2.4-hp
Medium Static Option with Motor rated at 2.9-hp
High Static Option with Motor rated at 3.7-hp
-- Exceeds recommended blower speed
Note: See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = 0.929 x BHP
XXE08 (7.5 ton) bottom duct
Available External Static
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2250 552 0.25 614 0.43 674 0.63 733 0.83 789 1.02 844 1.22 898 1.41 950 1.58 1000 1.75 1049 1.89
2400 559 0.34 621 0.52 682 0.72 740 0.91 797 1.11 852 1.31 905 1.49 957 1.67 1007 1.83 1056 1.98
2600 569 0.47 631 0.65 691 0.85 750 1.04 806 1.24 861 1.44 915 1.62 967 1.80 1017 1.96 1066 2.11
2800 579 0.61 641 0.79 701 0.99 760 1.19 817 1.38 872 1.58 925 1.77 977 1.94 1027 2.11 1076 2.25
3000 590 0.76 652 0.95 713 1.14 771 1.34 828 1.54 883 1.73 936 1.92 988 2.10 1038 2.26 1087 2.40
3200 602 0.92 665 1.11 725 1.30 783 1.50 840 1.70 895 1.89 948 2.08 1000 2.26 1050 2.42 1099 2.57
3400 616 1.09 678 1.28 738 1.47 797 1.67 854 1.87 909 2.06 962 2.25 1014 2.43 1064 2.59 -- --
3600 631 1.27 693 1.45 754 1.65 812 1.85 869 2.04 924 2.24 977 2.43 1029 2.60 1079 2.77 -- --
3750 644 1.40 706 1.59 766 1.78 824 1.98 881 2.18 936 2.37 990 2.56 1041 2.74 1092 2.90 -- --
Standard Static Option with Motor rated at 2.4-hp
Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 3.7-hp
-- Exceeds recommended blower speed
kW = 0.929 x BHP for Standard and Medium Static options kW = 0.895 x BHP for High Static option
Johnson Controls Ducted Systems 67
5147362-YTG-R-0323
XXE09 (8.5 ton) bottom duct
Available External Static
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2550 567 0.43 629 0.62 689 0.81 747 1.01 804 1.21 859 1.40 912 1.59 964 1.77 1014 1.93 1063 2.07
2600 569 0.47 631 0.65 691 0.85 750 1.04 806 1.24 861 1.44 915 1.62 967 1.80 1017 1.96 1066 2.11
2800 579 0.61 641 0.79 701 0.99 760 1.19 817 1.38 872 1.58 925 1.77 977 1.94 1027 2.11 1076 2.25
3000 590 0.76 652 0.95 713 1.14 771 1.34 828 1.54 883 1.73 936 1.92 988 2.10 1038 2.26 1087 2.40
3200 602 0.92 665 1.11 725 1.30 783 1.50 840 1.70 895 1.89 948 2.08 1000 2.26 1050 2.42 1099 2.57
3400 616 1.09 678 1.28 738 1.47 797 1.67 854 1.87 909 2.06 962 2.25 1014 2.43 1064 2.59 -- --
3600 631 1.27 693 1.45 754 1.65 812 1.85 869 2.04 924 2.24 977 2.43 1029 2.60 1079 2.77 -- --
3800 648 1.45 710 1.64 770 1.83 829 2.03 885 2.23 940 2.42 994 2.61 1046 2.78 1096 2.95 -- --
4000 666 1.64 729 1.82 789 2.01 847 2.21 904 2.41 959 2.61 1012 2.79 1064 2.97 -- -- -- --
4200 687 1.82 749 2.01 809 2.20 867 2.42 924 2.60 979 2.79 1032 2.98 1084 3.16 -- -- -- --
4250 692 1.87 754 2.06 814 2.25 873 2.45 929 2.65 984 2.84 1038 3.03 1090 3.21 -- -- -- --
Standard Static Option with Motor rated at 2.4-hp
Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 3.7-hp
-- Exceeds recommended blower speed
kW = 0.929 x BHP for Standard and Medium Static options kW = 0.895 x BHP for High Static option
XXE12 (10 ton) bottom duct
Available External Static Pressure - IWG
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3000 665 0.84 715 1.05 763 1.25 809 1.45 855 1.64 901 1.84 947 2.04 995 2.26 1045 2.48
3200 675 1.01 726 1.22 774 1.42 820 1.61 866 1.81 911 2.01 958 2.21 1005 2.42 1055 2.65
3400 687 1.19 737 1.40 785 1.60 832 1.80 878 1.99 923 2.19 970 2.40 1017 2.61 1067 2.83
3600 700 1.39 750 1.60 798 1.80 845 2.00 891 2.20 936 2.39 983 2.60 1030 2.81 1080 3.04
3800 662 1.39 715 1.61 765 1.82 813 2.02 859 2.22 905 2.41 951 2.61 997 2.81 1045 3.03 1094 3.25
4000 677 1.62 730 1.84 780 2.05 828 2.26 875 2.45 921 2.65 966 2.85 1013 3.05 1060 3.26 1110 3.49
4200 694 1.87 747 2.09 797 2.30 845 2.50 892 2.70 937 2.90 983 3.09 1029 3.30 1077 3.51 1127 3.74
4400 712 2.13 765 2.35 815 2.57 863 2.77 910 2.96 956 3.16 1001 3.36 1048 3.56 1095 3.77 1145 4.00
4600 732 2.41 785 2.63 835 2.84 883 3.04 929 3.24 975 3.44 1021 3.63 1067 3.84 1115 4.05 1165 4.28
4800 752 2.70 805 2.92 856 3.13 904 3.33 950 3.53 996 3.73 1041 3.92 1088 4.13 1135 4.34 - -
5000 774 3.00 827 3.22 878 3.43 925 3.64 972 3.83 1018 4.03 1063 4.23 1110 4.43 1157 4.64 - -
Standard Static Option with Motor rated at 2.4-hp
Medium Static Option with Motor rated at 3.7-hp
Bold Field Supplied AK84 x 1 fixed pulley with Motor rated at 3.7-hp
High Static Option with Motor rated at 5.25-hp
-- Exceeds recommended blower speed
68 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XQE04-09 bottom duct application (belt drive)
XQE04 (3.0 ton) bottom duct
Available External Static
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
900 743 0.14 852 0.26 955 0.37 1050 0.48 1140 0.57 1225 0.67 1306 0.77 1384 0.87 1460 0.98 1535 1.09
1000 757 0.20 867 0.33 969 0.44 1065 0.54 1155 0.64 1240 0.74 1321 0.84 1399 0.94 1475 1.04 1549 1.16
1100 774 0.27 884 0.40 986 0.51 1082 0.61 1172 0.71 1257 0.81 1338 0.91 1416 1.01 1492 1.11 1566 1.23
1200 793 0.35 903 0.47 1005 0.58 1101 0.69 1191 0.78 1276 0.88 1357 0.98 1435 1.08 1511 1.19 1585 1.30
1300 814 0.42 924 0.54 1026 0.65 1122 0.76 1212 0.86 1297 0.96 1378 1.05 1456 1.15 1532 1.26 1606 1.37
1400 837 0.49 947 0.61 1049 0.72 1145 0.83 1235 0.93 1320 1.03 1401 1.12 1479 1.23 1555 1.33 1629 1.45
1500 862 0.56 972 0.68 1074 0.79 1170 0.90 1260 1.00 1345 1.09 1426 1.19 1504 1.29 1580 1.40 -- --
kW = 0.929 x BHP
Bold Field-supplied AK51 x 3/4 in. fixed blower pulley with motor rated at 2.4-hp
Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 2.4-hp
Bold Field-supplied AK41 x 3/4 in. fixed blower pulley with motor rated at 2.4-hp
-- Exceeds recommended blower speed
XQE05 (4.0 ton) bottom duct
Available External Static
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1200 801 0.25 903 0.38 999 0.51 1089 0.63 1173 0.76 1252 0.88 1327 1.00 1396 1.11 1461 1.22 1521 1.33
1300 822 0.31 924 0.44 1020 0.57 1110 0.69 1194 0.82 1273 0.94 1348 1.06 1417 1.17 1482 1.28 1542 1.39
1400 844 0.38 946 0.51 1042 0.64 1132 0.76 1216 0.89 1295 1.01 1370 1.13 1439 1.24 1504 1.35 1564 1.46
1500 867 0.46 969 0.59 1065 0.71 1155 0.84 1239 0.96 1319 1.08 1393 1.20 1462 1.32 1527 1.43 1587 1.53
1600 891 0.54 993 0.67 1089 0.79 1179 0.92 1264 1.04 1343 1.16 1417 1.28 1486 1.40 1551 1.51 1612 1.61
1700 917 0.63 1019 0.75 1115 0.88 1205 1.01 1289 1.13 1368 1.25 1442 1.37 1512 1.48 1577 1.60 1637 1.70
1800 943 0.72 1045 0.85 1141 0.97 1231 1.10 1316 1.22 1395 1.34 1469 1.46 1538 1.58 1603 1.69 -- --
1900 971 0.81 1073 0.94 1169 1.07 1259 1.19 1344 1.32 1423 1.44 1497 1.56 1566 1.67 1631 1.78 -- --
2000 1000 0.92 1102 1.04 1198 1.17 1288 1.29 1372 1.42 1452 1.54 1526 1.66 1595 1.77 -- -- -- --
kW = 0.929 x BHP
Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 2.4-hp
Bold Field-supplied AK41 x 3/4 in. fixed blower pulley with motor rated at 2.4-hp
-- Exceeds recommended blower speed
XQE06 (5.0 ton) bottom duct
Available External Static
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1500 812 0.36 869 0.46 931 0.55 997 0.64 1063 0.74 1129 0.84 1193 0.94 1253 1.05 1307 1.16 1354 1.27
1600 829 0.43 886 0.52 948 0.61 1013 0.71 1080 0.80 1146 0.90 1210 1.01 1270 1.11 1324 1.22 1370 1.34
1700 846 0.50 904 0.59 966 0.68 1031 0.78 1097 0.87 1164 0.97 1227 1.07 1287 1.18 1341 1.29 1388 1.41
1800 865 0.57 922 0.66 985 0.75 1050 0.85 1116 0.95 1182 1.05 1246 1.15 1306 1.25 1360 1.36 1407 1.48
1900 885 0.65 943 0.74 1005 0.83 1070 0.93 1136 1.02 1203 1.12 1266 1.23 1326 1.33 1380 1.44 1427 1.56
2000 907 0.73 964 0.82 1026 0.92 1092 1.01 1158 1.11 1224 1.21 1288 1.31 1348 1.42 1402 1.53 1449 1.64
2100 930 0.82 987 0.91 1049 1.01 1115 1.10 1181 1.20 1247 1.30 1311 1.40 1371 1.51 1425 1.62 1472 1.73
2200 955 0.92 1012 1.01 1074 1.10 1139 1.20 1206 1.29 1272 1.39 1336 1.50 1396 1.60 1450 1.71 1496 1.83
2300 981 1.02 1038 1.11 1101 1.20 1166 1.30 1232 1.39 1298 1.49 1362 1.60 1422 1.70 1476 1.81 1523 1.93
2400 1009 1.12 1066 1.22 1128 1.31 1194 1.40 1260 1.50 1326 1.60 1390 1.70 1450 1.81 1504 1.92 1551 2.03
2500 1038 1.24 1096 1.33 1158 1.42 1223 1.52 1290 1.61 1356 1.71 1420 1.82 1480 1.92 1534 2.03 1580 2.15
kW = 0.857 x BHP
Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 2.9-hp
Johnson Controls Ducted Systems 69
5147362-YTG-R-0323
XYE04-06 side duct application (direct drive)
XYE04-06 side duct
Available External Static
Unit Motor
0.2 0.4 0.6 0.8 1.0
(ton) Speed
CFM WATTS RPM CFM WATTS RPM CFM WATTS RPM CFM WATTS RPM CFM WATTS RPM
1 (LOW) 987 120 651 813 145 774 698 162 864 541 180 959 383 201 1047
2 (MED/LOW) 1079 144 677 936 171 795 793 190 886 692 214 975 521 232 1063
XYE04
3 (MED) 1153 166 701 1037 195 812 875 221 913 786 239 986 654 263 1076
(3)
4 (MED/HI) 1191 178 712 1086 206 815 927 233 916 837 257 998 711 278 1083
5 (HI) 1326 229 757 1235 261 856 1124 291 951 973 319 1035 896 336 1099
1 (LOW) 1302 207 727 1188 240 841 1037 266 933 941 296 1022 882 318 1098
2 (MED/LOW) 1421 247 757 1323 282 861 1209 315 958 1064 346 1043 993 368 1116
XYE05
3 (MED) 1538 297 795 1453 332 888 1343 367 982 1216 396 1058 1093 427 1146
(4)
4 (MED/HI) 1571 315 809 1496 352 898 1385 389 996 1288 420 1072 1135 444 1147
5 (HI) 1779 432 878 1707 470 960 1615 511 1042 1516 544 1123 1165 468 1160
1 (LOW) 1588 298 695 1517 330 761 1409 358 835 1273 393 913 1167 418 973
2 (MED/LOW) 1624 321 713 1557 352 777 1464 383 845 1315 418 924 1224 446 983
XYE06
3 (MED) 1942 504 792 1881 536 852 1800 565 908 1714 605 969 1611 644 1038
(5)
4 (MED/HI) 2146 631 840 2064 692 908 2001 713 954 1932 757 1007 1843 794 1065
5 (HI) 2316 812 892 2240 861 954 2181 894 1000 2113 938 1045 2003 946 1093
XYE04-06 bottom duct application (direct drive)
XYE04-06 bottom duct
Available External Static
Unit Motor
0.2 0.4 0.6 0.8 1.0
(ton) Speed
CFM WATTS RPM CFM WATTS RPM CFM WATTS RPM CFM WATTS RPM CFM WATTS RPM
1 (LOW) 929 128 699 782 148 794 663 164 880 514 187 976 377 202 1053
2 (MED/LOW) 1036 157 732 870 177 827 803 198 905 649 217 996 508 236 1074
XYE04
3 (MED) 1106 181 760 956 204 849 878 225 928 755 245 1010 616 266 1092
(3)
4 (MED/HI) 1147 197 776 1042 218 860 916 243 944 820 262 1017 671 286 1103
5 (HI) 1272 252 830 1177 277 909 1037 304 986 975 323 1053 872 347 1125
1 (LOW) 1256 220 776 1170 242 851 1077 266 931 988 298 1025 872 321 1113
2 (MED/LOW) 1350 272 828 1279 292 893 1196 320 966 1105 347 1048 1003 372 1131
XYE05
3 (MED) 1449 323 866 1380 350 937 1303 370 996 1223 402 1071 1133 428 1149
(4)
4 (MED/HI) 1488 345 882 1418 374 954 1357 394 1006 1264 424 1083 1160 442 1155
5 (HI) 1677 471 966 1602 507 1034 1543 525 1083 1475 545 1131 1209 465 1162
1 (LOW) 1548 310 720 1441 336 792 1337 370 864 1213 397 928 1097 421 988
2 (MED/LOW) 1593 337 738 1488 363 805 1381 394 875 1271 425 937 1150 451 997
XYE06
3 (MED) 1880 532 827 1792 563 890 1719 588 944 1632 629 1006 1527 652 1061
(5)
4 (MED/HI) 2066 689 895 1999 712 942 1907 761 999 1830 773 1048 1734 809 1100
5 (HI) 2237 862 949 2163 882 996 2097 929 1036 1998 946 1085 1815 883 1115
70 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XQE04-06 side duct application (direct drive)
XQE04-06 side duct
Available External Static
Unit Motor
0.2 0.4 0.6 0.8 1.0
(ton) Speed
CFM WATTS RPM CFM WATTS RPM CFM WATTS RPM CFM WATTS RPM CFM WATTS RPM
1 (LOW) 987 120 651 813 145 774 698 162 864 541 180 959 383 201 1047
2 (MED/LOW) 1079 144 677 936 171 795 793 190 886 692 214 975 521 232 1063
XYE04
3 (MED) 1153 166 701 1037 195 812 875 221 913 786 239 986 654 263 1076
(3)
4 (MED/HI) 1191 178 712 1086 206 815 927 233 916 837 257 998 711 278 1083
5 (HI) 1326 229 757 1235 261 856 1124 291 951 973 319 1035 896 336 1099
1 (LOW) 1302 207 727 1188 240 841 1037 266 933 941 296 1022 882 318 1098
2 (MED/LOW) 1421 247 757 1323 282 861 1209 315 958 1064 346 1043 993 368 1116
XYE05
3 (MED) 1538 297 795 1453 332 888 1343 367 982 1216 396 1058 1093 427 1146
(4)
4 (MED/HI) 1571 315 809 1496 352 898 1385 389 996 1288 420 1072 1135 444 1147
5 (HI) 1779 432 878 1707 470 960 1615 511 1042 1516 544 1123 1165 468 1160
1 (LOW) 1588 298 695 1517 330 761 1409 358 835 1273 393 913 1167 418 973
2 (MED/LOW) 1624 321 713 1557 352 777 1464 383 845 1315 418 924 1224 446 983
XYE06
3 (MED) 1942 504 792 1881 536 852 1800 565 908 1714 605 969 1611 644 1038
(5)
4 (MED/HI) 2146 631 840 2064 692 908 2001 713 954 1932 757 1007 1843 794 1065
5 (HI) 2316 812 892 2240 861 954 2181 894 1000 2113 938 1045 2003 946 1093
XQE04-06 bottom duct application (direct drive)
XQE04-06 bottom duct
Available External Static
Unit Motor
0.2 0.4 0.6 0.8 1.0
(ton) Speed
CFM WATTS RPM CFM WATTS RPM CFM WATTS RPM CFM WATTS RPM CFM WATTS RPM
1 (LOW) 929 128 699 782 148 794 663 164 880 514 187 976 377 202 1053
2 (MED/LOW) 1036 157 732 870 177 827 803 198 905 649 217 996 508 236 1074
XQE04
3 (MED) 1106 181 760 956 204 849 878 225 928 755 245 1010 616 266 1092
(3)
4 (MED/HI) 1147 197 776 1042 218 860 916 243 944 820 262 1017 671 286 1103
5 (HI) 1272 252 830 1177 277 909 1037 304 986 975 323 1053 872 347 1125
1 (LOW) 1256 220 776 1170 242 851 1077 266 931 988 298 1025 872 321 1113
2 (MED/LOW) 1350 272 828 1279 292 893 1196 320 966 1105 347 1048 1003 372 1131
XQE05
3 (MED) 1449 323 866 1380 350 937 1303 370 996 1223 402 1071 1133 428 1149
(4)
4 (MED/HI) 1488 345 882 1418 374 954 1357 394 1006 1264 424 1083 1160 442 1155
5 (HI) 1677 471 966 1602 507 1034 1543 525 1083 1475 545 1131 1209 465 1162
1 (LOW) 1548 310 720 1441 336 792 1337 370 864 1213 397 928 1097 421 988
2 (MED/LOW) 1593 337 738 1488 363 805 1381 394 875 1271 425 937 1150 451 997
XQE06
3 (MED) 1880 532 827 1792 563 890 1719 588 944 1632 629 1006 1527 652 1061
(5)
4 (MED/HI) 2066 689 895 1999 712 942 1907 761 999 1830 773 1048 1734 809 1100
5 (HI) 2237 862 949 2163 882 996 2097 929 1036 1998 946 1085 1815 883 1115
Johnson Controls Ducted Systems 71
5147362-YTG-R-0323
Power exhaust blower curves
cfm cfm
0 500 1000 1500 2000 0 500 1000 1500 2000 2500
250 1.00 250 1.00
200 0.80 200 0.80
230V
150 0.60 150 0.60
In.
Pa In.
WG Pa
WG
100 0.40 100 0.40
Forbidden area
Forbidden area 230V
50 208V 0.20 50 0.20
0 0 0 0
0 500 1000 1500 2000 2500 3000 3500 4000 0 500 1000 1500 2000 2500 3000 3500 4000 4500
Air volume[CMH] Air volume[CMH]
208/280-1-60 power exhaust fan curve 208/280-3-60 power exhaust fan curve
cfm cfm
0 500 1000 1500 2000 2500 0 500 1000 1500 2000 2500
250 1.00 250 1.00
200 0.80 200 0.80
460V 575V
150 0.60 150 0.60
In. In.
Pa Pa
WG WG
100 0.40 100 0.40
Forbidden area
Forbidden area
50 0.20 50 0.20
0 0 0 0
0 500 1000 1500 2000 2500 3000 3500 4000 4500 0 500 1000 1500 2000 2500 3000 3500 4000 4500
Air volume[CMH] Air volume[CMH]
460-3-60 power exhaust fan curve 575-3-50 power exhaust fan curve
72 Johnson Controls Ducted Systems
5147362-YTG-R-0323
Electrical data
XYE04-09 standard indoor blower - without powered convenience outlet
Min Max Min
Min Max Min Fuse2/ Fuse2/
OD Electric Heat MCA1 Discon-
Nominal Compressor 1 Supply Pwr Pwr Fuse 2/
Fuse 2/ Discon- Breaker 3
Breaker 3
Size Compressor 2 Fan Field-installed KitMCA1 w/Pwr nect
Unit Blower Exh Conv Breaker3 Breaker3 nect Size Size
(ton) Motors 2EK045* (Amps) Exh Rating4/
Voltage Motor Motor Outlet Size Size Rating4 w/ w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
None - - - 27.9 30 40 28 90 29.4 30 40 29 94
208-1-60 15.4 83.9 24 2 6.6 1.5 10625 4.9 1 23.6 57.4 60 60 55 114 58.9 60 60 56 117
11125 7.9 1 38 75.4 80 80 71 128 76.9 80 80 73 132
None - - - 27.6 30 40 27 91 28.9 30 40 29 94
230-1-60 15.4 83.9 24 2.3 6 1.3 10625 6.5 1 27.1 61.5 70 70 58 118 62.8 70 70 60 121
11125 10.5 1 43.8 82.4 90 90 78 135 83.7 90 90 79 138
None - - - 21.6 25 30 22 79 22.7 25 30 23 82
10625 4.9 1 13.6 38.6 40 45 37 93 39.7 40 45 39 96
208-3-60 10.4 73 16 2 6.6 1.1
11125 7.9 1 21.9 49 50 50 47 101 50.1 60 60 48 104
11625 12 1 33.3 63.2 70 70 60 113 64.3 70 70 61 115
04
None - - - 21.3 25 30 22 80 22.3 25 30 23 82
(3)
10625 6.5 1 15.6 40.8 45 45 39 96 41.8 45 45 41 98
230-3-60 10.4 73 16 2.3 6 1
11125 10.5 1 25.3 52.9 60 60 51 105 53.9 60 60 52 108
11625 16 1 38.5 69.4 70 70 66 118 70.4 80 80 67 121
None - - - 11.8 15 15 12 43 12.3 15 15 12 44
10646 6 1 7.2 20.8 25 25 20 50 21.3 25 25 21 51
460-3-60 5.8 38 9 1.3 3.2 0.5
11146 11.5 1 13.8 29.1 30 30 28 57 29.6 30 30 28 58
11446 14 1 16.8 32.8 35 35 31 60 33.3 35 35 32 61
None - - - 8.2 15 15 8 40 8.6 15 15 9 41
575-3-60 3.8 36.5 6 1 6 0.4 11058 9.2 1 8.9 19.3 20 20 19 49 19.7 20 20 19 49
11458 13.8 1 13.3 24.8 25 25 24 53 25.2 30 30 24 54
None - - - 34.9 35 50 35 136 36.4 40 50 36 140
208-1-60 19.6 130 31 2 8.4 1.5 10625 4.9 1 23.6 64.4 70 70 62 160 65.9 70 70 63 163
11125 7.9 1 38 82.4 90 90 78 174 83.9 90 90 80 178
None - - - 34.4 35 50 34 137 35.7 40 50 35 140
230-1-60 19.6 130 31 2.3 7.6 1.3 10625 6.5 1 27.1 68.3 70 80 65 164 69.6 70 80 67 167
11125 10.5 1 43.8 89.2 90 90 84 181 90.5 100 100 86 184
None - - - 27.5 30 40 28 90 28.6 30 40 29 92
10625 4.9 1 13.6 44.5 45 50 43 103 45.6 50 50 45 106
208-3-60 13.7 83.1 21 2 8.4 1.1
11125 7.9 1 21.9 54.9 60 60 53 111 56 60 60 54 114
11625 12 1 33.3 69.1 70 70 66 123 70.2 80 80 67 125
05
None - - - 27 30 40 27 90 28 30 40 28 92
(4)
10625 6.5 1 15.6 46.5 50 50 45 106 47.5 50 50 46 108
230-3-60 13.7 83.1 21 2.3 7.6 1
11125 10.5 1 25.3 58.6 60 60 56 115 59.6 60 60 57 118
11625 16 1 38.5 75.1 80 80 71 129 76.1 80 80 73 131
None - - - 13.1 15 15 13 46 13.6 15 15 14 47
10646 6 1 7.2 22.1 25 25 22 53 22.6 25 25 22 54
460-3-60 6.2 41 10 1.3 4 0.5
11146 11.5 1 13.8 30.4 35 35 29 60 30.9 35 35 30 61
11446 14 1 16.8 34.1 35 35 33 63 34.6 35 35 33 64
None - - - 10 15 15 10 36 10.4 15 15 11 37
575-3-60 4.8 33 8 1 7.6 0.4 11058 9.2 1 8.9 21.1 25 25 20 45 21.5 25 25 21 46
11458 13.8 1 13.3 26.6 30 30 25 49 27 30 30 26 50
Johnson Controls Ducted Systems 73
5147362-YTG-R-0323
XYE04-09 standard indoor blower - without powered convenience outlet (Continued)
Min Max Min
Min Max Min Fuse2/ Fuse2/
OD Electric Heat MCA1 Discon-
Nominal Compressor 1 Supply Pwr Pwr 2
Fuse / Fuse /2 Discon- Breaker Breaker3
3
Size Compressor 2 Fan Field-installed KitMCA1
w/Pwr nect
Unit Blower Exh Conv Breaker3 Breaker3 nect Size Size
(ton) Motors 2EK045* (Amps) Exh Rating4/
Voltage Motor Motor Outlet Size Size Rating4 w/ w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
None - - - 40.9 45 60 40 151 42.4 45 60 42 154
208-1-60 24.4 144.2 38 2 8.4 1.5 10625 4.9 1 23.6 70.4 80 80 67 174 71.9 80 90 69 178
11125 7.9 1 38 88.4 90 100 84 189 89.9 90 100 85 192
None - - - 40.4 45 60 39 151 41.7 45 60 41 154
230-1-60 24.4 144.2 38 2.3 7.6 1.3 10625 6.5 1 27.1 74.3 80 90 71 178 75.6 80 90 72 181
11125 10.5 1 43.8 95.2 100 100 90 195 96.5 100 100 91 198
None - - - 30.4 35 45 30 116 31.5 35 45 32 119
10625 4.9 1 13.6 47.4 50 60 46 130 48.5 50 60 47 133
208-3-60 16 110 25 2 8.4 1.1
11125 7.9 1 21.9 57.8 60 60 56 138 58.9 60 60 57 141
11625 12 1 33.3 72 80 80 69 150 73.1 80 80 70 152
06
None - - - 29.9 30 45 30 117 30.9 35 45 31 119
(5)
10625 6.5 1 15.6 49.4 50 60 48 133 50.4 60 60 49 135
230-3-60 16 110 25 2.3 7.6 1
11125 10.5 1 25.3 61.5 70 70 59 142 62.5 70 70 60 145
11625 16 1 38.5 78 80 80 74 155 79 80 80 75 158
None - - - 15.1 20 20 15 57 15.6 20 20 16 58
10646 6 1 7.2 24.1 25 30 23 64 24.6 25 30 24 65
460-3-60 7.8 52 12 1.3 4 0.5
11146 11.5 1 13.8 32.4 35 35 31 71 32.9 35 35 32 72
11446 14 1 16.8 36.1 40 40 34 74 36.6 40 40 35 75
None - - - 11.1 15 15 11 42 11.5 15 15 12 43
575-3-60 5.7 38.9 9 1 7.6 0.4 11458 13.8 1 13.3 27.7 30 30 26 55 28.1 30 30 27 56
12358 23 1 22.1 38.7 40 40 37 64 39.1 40 40 37 65
With VFD
None - - - 33.4 35 50 33 196 35.6 40 50 36 201
10725 4.9 1 13.6 50.4 60 60 49 210 52.6 60 60 52 215
208-3-60 17.6 136 27 4.4 7 1.1
11725 12 1 33.3 75 80 80 72 229 77.2 80 80 74 234
12525 18.6 1 51.6 97.9 100 100 93 248 100.1 110 110 95 253
None - - - 33.6 35 50 34 198 35.6 40 50 36 202
10725 6.5 1 15.6 53.1 60 60 52 213 55.1 60 60 54 218
230-3-60 17.6 136 27 4.4 7.2 1
11725 16 1 38.5 81.7 90 90 78 236 83.7 90 90 80 241
A7
12525 24.8 1 59.7 108.2 110 110 102 258 110.2 125 125 105 262
(6)
None - - - 19.2 20 25 20 97 20.2 25 25 21 99
10746 6 1 7.2 28.2 30 30 28 104 29.2 30 30 29 106
460-3-60 8.5 66.1 13 2.5 3.6 0.5
11746 16.5 1 19.8 44 45 45 42 117 45 45 45 44 119
12646 25.5 1 30.7 57.6 60 60 55 128 58.6 60 60 56 130
None - - - 19.2 20 25 20 73 20 20 25 21 75
575-3-60 6.3 55.3 10 4.4 2.5 0.4 11758 17 1 16.4 39.7 40 40 39 89 40.5 45 45 40 91
12658 25.7 1 24.7 50.1 60 60 49 98 50.9 60 60 50 100
None - - - 43.7 45 50 46 248 45.9 50 50 49 258
11725 12 1 33.3 85.3 90 90 85 282 87.5 90 90 87 292
208-3-60 13.8 83.1 22 13.6 83.1 21 5.8 7 1.1 12525 18.6 1 51.6 108.2 110 110 106 300 110.4 125 125 108 310
13225 24 1 66.6 127 150 150 123 315 129.2 150 150 125 325
14225 31.8 2 88.3 119.1 125 125 114 307 121.9 125 125 117 317
None - - - 43.3 45 50 46 247 45.3 50 50 48 252
11725 16 1 38.5 91.4 100 100 90 286 93.4 100 100 92 295
230-3-60 13.8 83.1 22 13.6 83.1 21 5.2 7.2 1 12525 24.8 1 59.7 117.9 125 125 114 307 119.9 125 125 117 316
08 13225 32 1 77 139.6 150 150 134 324 141.6 150 150 137 333
(7.5) 14225 42.4 2 102 136.5 150 150 124 315 139 150 150 126 324
None - - - 20.4 25 25 22 124 21.4 25 25 23 126
11746 16.5 1 19.8 45.2 50 50 44 144 46.2 50 50 46 148
460-3-60 6.2 41 10 6.1 41 10 2.9 3.6 0.5 12846 27.8 1 33.4 62.2 70 70 60 157 63.2 70 70 61 162
13346 33 1 39.7 70 70 70 67 164 71 80 80 68 168
14246 41.7 2 50.2 67.3 70 70 60 157 68.5 70 70 61 162
None - - - 15 20 20 16 95 15.8 20 20 17 97
575-3-60 4.9 33 8 4.2 33 7 2.2 2.5 0.4 11758 17 1 16.4 35.5 40 40 35 111 36.3 40 40 36 115
13458 34 1 32.7 55.9 60 60 53 128 56.7 60 60 54 131
74 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XYE04-09 standard indoor blower - without powered convenience outlet (Continued)
Min Max Min
Min Max Min Fuse2/ Fuse2/
OD Electric Heat MCA1 Discon-
Nominal Compressor 1 Supply Pwr Pwr 2
Fuse / Fuse /2 Discon- Breaker Breaker3
3
Size Compressor 2 Fan Field-installed KitMCA1
w/Pwr nect
Unit Blower Exh Conv Breaker3 Breaker3 nect Size Size
(ton) Motors 2EK045* (Amps) Exh Rating4/
Voltage Motor Motor Outlet Size Size Rating4 w/ w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
None - - - 44.6 45 50 47 263 46.8 50 60 50 273
11725 12 1 33.3 86.2 90 90 85 297 88.4 90 90 88 307
208-3-60 14.5 98 23 13.7 83.1 21 5.8 7 1.1 12525 18.6 1 51.6 109.1 110 110 106 315 111.3 125 125 109 325
13225 24 1 66.6 127.9 150 150 124 330 130.1 150 150 126 340
14225 31.8 2 88.3 119.1 125 125 115 322 121.9 125 125 118 332
None - - - 44.2 45 50 47 262 46.2 50 60 49 267
11725 16 1 38.5 92.3 100 100 91 300 94.3 100 100 93 310
230-3-60 14.5 98 23 13.7 83.1 21 5.2 7.2 1 12525 24.8 1 59.7 118.8 125 125 115 322 120.8 125 125 118 331
09 13225 32 1 77 140.5 150 150 135 339 142.5 150 150 138 348
(8.5) 14225 42.4 2 102 136.5 150 150 125 330 139 150 150 127 339
None - - - 20.6 25 25 22 138 21.6 25 25 23 140
11746 16.5 1 19.8 45.4 50 50 45 158 46.4 50 50 46 162
460-3-60 6.3 55 10 6.2 41 10 2.9 3.6 0.5 12846 27.8 1 33.4 62.4 70 70 60 171 63.4 70 70 61 176
13346 33 1 39.7 70.2 80 80 68 178 71.2 80 80 69 182
14246 41.7 2 50.2 67.3 70 70 60 171 68.5 70 70 61 176
None - - - 17 20 20 18 103 17.8 20 20 19 105
575-3-60 6 41 9 4.8 33 8 2.2 2.5 0.4 11758 17 1 16.4 37.5 40 40 37 119 38.3 40 40 38 123
13458 34 1 32.7 57.9 60 60 55 136 58.7 60 60 56 139
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field-installed
electric heat kits may exceed the factory-installed disconnect amperage rating.
Johnson Controls Ducted Systems 75
5147362-YTG-R-0323
XYE04-09 standard indoor blower - with powered convenience outlet
Min Min
Min Max Fuse2/
Electric Heat Min Max Fuse2/ Discon-
OD 2/ 2/ Discon- MCA1 3 Breaker
3
Nominal Compressor 1 Compressor 2 Fan Supply Pwr Pwr Field-installed Kit Fuse Fuse Breaker nect
Size MCA1 nect w/Pwr Size
Unit Blower Exh Conv 2EK045* Breaker3 Breaker3 Size Rating4/
(ton) Motors (Amps) Rating4 Exh w/
Voltage Motor Motor Outlet Size Size w/ Pwr Exh
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh
(Amps)
(Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
None - - - 32.2 35 45 33 95 33.7 35 45 34 98
208-1-60 15.4 83.9 24 2 6.6 1.5 8.6 10625 4.9 1 23.6 61.7 70 70 60 118 63.2 70 70 61 122
11125 7.9 1 38 79.7 80 80 76 133 81.2 90 90 78 136
None - - - 31.9 35 45 32 95 33.2 35 45 34 98
230-1-60 15.4 83.9 24 2.3 6 1.3 8.6 10625 6.5 1 27.1 65.8 70 70 63 122 67.1 70 70 65 125
11125 10.5 1 43.8 86.7 90 90 83 139 88 90 90 84 142
None - - - 25.9 30 35 27 84 27 30 35 28 86
10625 4.9 1 13.6 42.9 45 45 42 97 44 45 50 44 100
208-3-60 10.4 73 16 2 6.6 1.1 8.6
11125 7.9 1 21.9 53.3 60 60 52 106 54.4 60 60 53 108
11625 12 1 33.3 67.5 70 70 65 117 68.6 70 70 66 120
04
None - - - 25.6 30 35 26 84 26.6 30 35 28 87
(3)
10625 6.5 1 15.6 45.1 50 50 44 100 46.1 50 50 46 102
230-3-60 10.4 73 16 2.3 6 1 8.6
11125 10.5 1 25.3 57.2 60 60 56 110 58.2 60 60 57 112
11625 16 1 38.5 73.7 80 80 71 123 74.7 80 80 72 125
None - - - 14 15 15 14 45 14.5 15 15 15 46
10646 6 1 7.2 23 25 25 23 52 23.5 25 25 23 53
460-3-60 5.8 38 9 1.3 3.2 0.5 8.6
11146 11.5 1 13.8 31.3 35 35 30 59 31.8 35 35 31 60
11446 14 1 16.8 35 35 35 34 62 35.5 40 40 34 63
None - - - 9.9 15 15 10 41 10.3 15 15 11 42
575-3-60 3.8 36.5 6 1 6 0.4 8.6 11058 9.2 1 8.9 21 25 25 20 50 21.4 25 25 21 51
11458 13.8 1 13.3 26.5 30 30 26 55 26.9 30 30 26 56
None - - - 39.2 40 50 39 141 40.7 45 60 41 144
208-1-60 19.6 130 31 2 8.4 1.5 8.6 10625 4.9 1 23.6 68.7 70 80 67 164 70.2 80 80 68 168
11125 7.9 1 38 86.7 90 90 83 179 88.2 90 90 85 182
None - - - 38.7 40 50 39 141 40 40 50 40 144
230-1-60 19.6 130 31 2.3 7.6 1.3 8.6 10625 6.5 1 27.1 72.6 80 80 70 168 73.9 80 80 72 171
11125 10.5 1 43.8 93.5 100 100 89 185 94.8 100 100 91 188
None - - - 31.8 35 45 33 94 32.9 35 45 34 96
10625 4.9 1 13.6 48.8 50 50 48 107 49.9 50 60 50 110
208-3-60 13.7 83.1 21 2 8.4 1.1 8.6
11125 7.9 1 21.9 59.2 60 60 58 116 60.3 70 70 59 118
11625 12 1 33.3 73.4 80 80 71 127 74.5 80 80 72 130
05
None - - - 31.3 35 45 32 94 32.3 35 45 33 97
(4)
10625 6.5 1 15.6 50.8 60 60 50 110 51.8 60 60 51 112
230-3-60 13.7 83.1 21 2.3 7.6 1 8.6
11125 10.5 1 25.3 62.9 70 70 61 120 63.9 70 70 62 122
11625 16 1 38.5 79.4 80 80 76 133 80.4 90 90 78 135
None - - - 15.3 20 20 16 48 15.8 20 20 16 49
10646 6 1 7.2 24.3 25 25 24 55 24.8 25 25 25 56
460-3-60 6.2 41 10 1.3 4 0.5 8.6
11146 11.5 1 13.8 32.6 35 35 32 62 33.1 35 35 32 63
11446 14 1 16.8 36.3 40 40 35 65 36.8 40 40 36 66
None - - - 11.8 15 15 12 38 12.2 15 15 13 39
575-3-60 4.8 33 8 1 7.6 0.4 8.6 11058 9.2 1 8.9 22.9 25 25 22 47 23.3 25 25 23 48
11458 13.8 1 13.3 28.4 30 30 27 51 28.8 30 30 28 52
76 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XYE04-09 standard indoor blower - with powered convenience outlet (Continued)
Min Min
Min Max Fuse2/
Electric Heat Min Max Fuse2/ Discon-
OD 2 2 Discon- MCA1 3 Breaker
3
Nominal Compressor 1 Compressor 2 Fan Supply Pwr Pwr Field-installed Kit Fuse / Fuse / Breaker nect
Size MCA1 nect w/Pwr Size
Unit Blower Exh Conv 2EK045* Breaker3 Breaker3 Size Rating4/
(ton) Motors (Amps) Rating4 Exh w/
Voltage Motor Motor Outlet Size Size w/ Pwr Exh
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh
(Amps)
(Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
None - - - 45.2 50 60 45 155 46.7 50 70 47 158
144.
208-1-60 24.4 38 2 8.4 1.5 8.6 10625 4.9 1 23.6 74.7 80 90 72 179 76.2 80 90 74 182
2
11125 7.9 1 38 92.7 100 100 89 193 94.2 100 100 90 196
None - - - 44.7 45 60 44 155 46 50 70 46 158
144.
230-1-60 24.4 38 2.3 7.6 1.3 8.6 10625 6.5 1 27.1 78.6 80 90 76 183 79.9 80 90 77 185
2
11125 10.5 1 43.8 99.5 100 110 95 199 100.8 110 110 96 202
None - - - 34.7 35 50 35 121 35.8 40 50 37 123
10625 4.9 1 13.6 51.7 60 60 51 134 52.8 60 60 52 137
208-3-60 16 110 25 2 8.4 1.1 8.6
11125 7.9 1 21.9 62.1 70 70 60 143 63.2 70 70 62 145
11625 12 1 33.3 76.3 80 80 74 154 77.4 80 80 75 157
06
None - - - 34.2 35 50 35 121 35.2 40 50 36 124
(5)
10625 6.5 1 15.6 53.7 60 60 53 137 54.7 60 60 54 139
230-3-60 16 110 25 2.3 7.6 1 8.6
11125 10.5 1 25.3 65.8 70 70 64 147 66.8 70 70 65 149
11625 16 1 38.5 82.3 90 90 79 160 83.3 90 90 80 162
None - - - 17.3 20 25 18 59 17.8 20 25 18 60
10646 6 1 7.2 26.3 30 30 26 66 26.8 30 30 26 67
460-3-60 7.8 52 12 1.3 4 0.5 8.6
11146 11.5 1 13.8 34.6 35 35 33 73 35.1 40 40 34 74
11446 14 1 16.8 38.3 40 40 37 76 38.8 40 40 37 77
None - - - 12.9 15 15 13 44 13.3 15 15 14 45
575-3-60 5.7 38.9 9 1 7.6 0.4 8.6 11458 13.8 1 13.3 29.5 30 30 29 57 29.9 30 30 29 58
12358 23 1 22.1 40.5 45 45 39 66 40.9 45 45 39 67
With VFD
None - - - 37.7 40 50 38 200 39.9 40 50 41 205
10725 4.9 1 13.6 54.7 60 60 54 214 56.9 60 70 56 219
208-3-60 17.6 136 27 4.4 7 1.1 8.6
11725 12 1 33.3 79.3 80 80 77 234 81.5 90 90 79 239
12525 18.6 1 51.6 102.2 110 110 98 252 104.4 110 110 100 257
None - - - 37.9 40 50 39 202 39.9 40 50 41 207
10725 6.5 1 15.6 57.4 60 70 56 218 59.4 60 70 59 222
230-3-60 17.6 136 27 4.4 7.2 1 8.6
11725 16 1 38.5 86 90 90 83 241 88 90 90 85 245
A7
12525 24.8 1 59.7 112.5 125 125 107 262 114.5 125 125 109 266
(6)
None - - - 21.4 25 25 22 99 22.4 25 25 23 101
10746 6 1 7.2 30.4 35 35 30 106 31.4 35 35 32 109
460-3-60 8.5 66.1 13 2.5 3.6 0.5 8.6
11746 16.5 1 19.8 46.2 50 50 45 119 47.2 50 50 46 121
12646 25.5 1 30.7 59.8 60 60 58 130 60.8 70 70 59 132
None - - - 20.9 25 25 22 75 21.7 25 25 23 77
575-3-60 6.3 55.3 10 4.4 2.5 0.4 8.6 11758 17 1 16.4 41.4 45 45 41 91 42.2 45 45 42 93
12658 25.7 1 24.7 51.8 60 60 51 99 52.6 60 60 52 101
None - - - 48 50 60 51 253 50.2 60 60 54 263
11725 12 1 33.3 89.6 90 90 89 286 91.8 100 100 92 296
208-3-60 13.8 83.1 22 13.6 83.1 21 5.8 7 1.1 8.6 12525 18.6 1 51.6 112.5 125 125 111 304 114.7 125 125 113 314
13225 24 1 66.6 131.3 150 150 128 319 133.5 150 150 130 329
14225 31.8 2 88.3 124.5 125 125 119 312 127.3 150 150 122 322
None - - - 47.6 50 60 51 251 49.6 50 60 53 256
11725 16 1 38.5 95.7 100 100 95 290 97.7 100 100 97 299
230-3-60 13.8 83.1 22 13.6 83.1 21 5.2 7.2 1 8.6 12525 24.8 1 59.7 122.2 125 125 119 311 124.2 125 125 122 320
08 13225 32 1 77 143.9 150 150 139 328 145.9 150 150 142 338
(7.5) 14225 42.4 2 102 141.9 150 150 129 319 144.4 150 150 131 329
None - - - 22.6 25 25 24 126 23.6 25 25 25 128
11746 16.5 1 19.8 47.4 50 50 47 146 48.4 50 50 48 150
460-3-60 6.2 41 10 6.1 41 10 2.9 3.6 0.5 8.6 12846 27.8 1 33.4 64.4 70 70 63 159 65.4 70 70 64 164
13346 33 1 39.7 72.2 80 80 70 166 73.2 80 80 71 170
14246 41.7 2 50.2 69.9 70 70 63 159 71.2 80 80 64 164
None - - - 16.7 20 20 18 97 17.5 20 20 19 99
575-3-60 4.9 33 8 4.2 33 7 2.2 2.5 0.4 8.6 11758 17 1 16.4 37.2 40 40 37 113 38 40 40 38 117
13458 34 1 32.7 57.6 60 60 55 129 58.4 60 60 56 133
Johnson Controls Ducted Systems 77
5147362-YTG-R-0323
XYE04-09 standard indoor blower - with powered convenience outlet (Continued)
Min Min
Min Max Fuse2/
Electric Heat Min Max Fuse2/ Discon-
OD 2 2 Discon- MCA1 3 Breaker3
Nominal Compressor 1 Compressor 2 Fan Supply Pwr Pwr Field-installed Kit Fuse / Fuse / Breaker nect
Size MCA1 nect w/Pwr Size
Unit Blower Exh Conv 2EK045* Breaker3 Breaker3 Size Rating4/
(ton) Motors (Amps) Rating4 Exh w/
Voltage Motor Motor Outlet Size Size w/ Pwr Exh
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh
(Amps)
(Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
None - - - 48.9 50 60 52 268 51.1 60 60 55 278
11725 12 1 33.3 90.5 100 100 90 301 92.7 100 100 93 311
208-3-60 14.5 98 23 13.7 83.1 21 5.8 7 1.1 8.6 12525 18.6 1 51.6 113.4 125 125 111 319 115.6 125 125 114 329
13225 24 1 66.6 132.2 150 150 129 334 134.4 150 150 131 344
14225 31.8 2 88.3 124.5 125 125 120 327 127.3 150 150 123 337
None - - - 48.5 50 60 52 266 50.5 60 60 54 271
11725 16 1 38.5 96.6 100 100 96 305 98.6 100 100 98 314
230-3-60 14.5 98 23 13.7 83.1 21 5.2 7.2 1 8.6 12525 24.8 1 59.7 123.1 125 125 120 326 125.1 150 150 123 335
09 13225 32 1 77 144.8 150 150 140 343 146.8 150 150 142 352
(8.5) 14225 42.4 2 102 141.9 150 150 130 334 144.4 150 150 132 344
None - - - 22.8 25 25 24 140 23.8 25 25 26 142
11746 16.5 1 19.8 47.6 50 50 47 160 48.6 50 50 48 164
460-3-60 6.3 55 10 6.2 41 10 2.9 3.6 0.5 8.6 12846 27.8 1 33.4 64.6 70 70 63 173 65.6 70 70 64 178
13346 33 1 39.7 72.4 80 80 70 180 73.4 80 80 71 184
14246 41.7 2 50.2 69.9 70 70 63 173 71.2 80 80 64 178
None - - - 18.7 20 20 20 105 19.5 20 20 21 107
575-3-60 6 41 9 4.8 33 8 2.2 2.5 0.4 8.6 11758 17 1 16.4 39.2 40 40 39 121 40 40 40 40 125
13458 34 1 32.7 59.6 60 60 57 137 60.4 70 70 58 141
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field-installed
electric heat kits may exceed the factory-installed disconnect amperage rating.
78 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XYE04-09 medium indoor blower - without powered convenience outlet
Min Max Min
Min Max Min MCA1 Fuse2/ Fuse2/
OD Electric Heat Discon-
Nominal Compressor 1 1
Fuse2/ Fuse2/ Discon- w/Pwr Breaker3 Breaker3
Size Compressor 2 Fan Supply Pwr Pwr Field-installed Kit MCA nect
Unit Blower Exh Conv (Amp Breaker3 Breaker3 nect Exh Size Size
(ton) Motors 2EK045* Rating4/
Voltage Motor Motor Outlet s) Size Size Rating4 (Amp w/ w/
(each) Pwr Exh
(Amps) (Amps) s) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
None - - - 28.9 30 40 29 121 30.4 35 45 30 125
208-1-60 15.4 83.9 24 2 7.6 1.5 10625 4.9 1 23.6 58.4 60 60 56 145 59.9 60 60 58 148
11125 7.9 1 38 76.4 80 80 72 159 77.9 80 80 74 163
None - - - 28.6 30 40 28 124 29.9 30 45 30 127
230-1-60 15.4 83.9 24 2.3 7 1.3 10625 6.5 1 27.1 62.5 70 70 60 151 63.8 70 70 61 154
11125 10.5 1 43.8 83.4 90 90 79 168 84.7 90 90 80 171
None - - - 20.2 25 30 20 100 21.3 25 30 22 102
10625 4.9 1 13.6 37.2 40 40 36 113 38.3 40 45 37 116
208-3-60 10.4 73 16 2 5.2 1.1
11125 7.9 1 21.9 47.6 50 50 45 122 48.7 50 50 47 124
11625 12 1 33.3 61.8 70 70 59 133 62.9 70 70 60 136
04
None - - - 20.5 25 30 21 103 21.5 25 30 22 105
(3)
10625 6.5 1 15.6 40 40 45 39 119 41 45 45 40 121
230-3-60 10.4 73 16 2.3 5.2 1
11125 10.5 1 25.3 52.1 60 60 50 128 53.1 60 60 51 131
11625 16 1 38.5 68.6 70 70 65 141 69.6 70 70 66 144
None - - - 11.2 15 15 11 53 11.7 15 15 12 55
10646 6 1 7.2 20.2 25 25 19 61 20.7 25 25 20 62
460-3-60 5.8 38 9 1.3 2.6 0.5
11146 11.5 1 13.8 28.5 30 30 27 67 29 30 30 28 68
11446 14 1 16.8 32.2 35 35 30 70 32.7 35 35 31 71
None - - - 7.8 15 15 8 49 8.2 15 15 8 50
575-3-60 3.8 36.5 6 1 2 0.4 11058 9.2 1 8.9 18.9 20 20 18 58 19.3 20 20 19 59
11458 13.8 1 13.3 24.4 25 25 23 62 24.8 25 25 24 63
None - - - 34.1 35 50 34 167 35.6 40 50 35 171
208-1-60 19.6 130 31 2 7.6 1.5 10625 4.9 1 23.6 63.6 70 70 61 191 65.1 70 70 62 194
11125 7.9 1 38 81.6 90 90 77 205 83.1 90 90 79 209
None - - - 33.8 35 50 33 170 35.1 40 50 35 173
230-1-60 19.6 130 31 2.3 7 1.3 10625 6.5 1 27.1 67.7 70 80 64 198 69 70 80 66 200
11125 10.5 1 43.8 88.6 90 90 84 214 89.9 90 90 85 217
None - - - 24.3 25 35 24 110 25.4 30 35 25 112
10625 4.9 1 13.6 41.3 45 50 40 124 42.4 45 50 41 126
208-3-60 13.7 83.1 21 2 5.2 1.1
11125 7.9 1 21.9 51.7 60 60 49 132 52.8 60 60 50 134
11625 12 1 33.3 65.9 70 70 62 143 67 70 70 64 146
05
None - - - 24.6 25 35 24 113 25.6 30 35 26 115
(4)
10625 6.5 1 15.6 44.1 45 50 42 129 45.1 50 50 43 131
230-3-60 13.7 83.1 21 2.3 5.2 1
11125 10.5 1 25.3 56.2 60 60 53 138 57.2 60 60 55 141
11625 16 1 38.5 72.7 80 80 69 152 73.7 80 80 70 154
None - - - 11.7 15 15 12 56 12.2 15 15 12 58
10646 6 1 7.2 20.7 25 25 20 64 21.2 25 25 20 65
460-3-60 6.2 41 10 1.3 2.6 0.5
11146 11.5 1 13.8 29 30 30 27 70 29.5 30 30 28 71
11446 14 1 16.8 32.7 35 35 31 73 33.2 35 35 32 74
None - - - 9 15 15 9 45 9.4 15 15 9 46
575-3-60 4.8 33 8 1 2 0.4 11058 9.2 1 8.9 20.1 25 25 19 54 20.5 25 25 20 55
11458 13.8 1 13.3 25.6 30 30 24 59 26 30 30 25 60
Johnson Controls Ducted Systems 79
5147362-YTG-R-0323
XYE04-09 medium indoor blower - without powered convenience outlet (Continued)
Min Max Min
Min Max Min MCA1 Fuse2/ Fuse2/
OD Electric Heat Discon-
Nominal Compressor 1 MCA 1 Fuse2/ Fuse2/ Discon- w/Pwr Breaker3 Breaker3
Size Compressor 2 Fan Supply Pwr Pwr Field-installed Kit nect
Unit Blower Exh Conv (Amp Breaker Breaker3
3 nect Exh Size Size
(ton) Motors 2EK045* Rating4/
Voltage Motor Motor Outlet s) Size Size Rating4 (Amp w/ w/
(each) Pwr Exh
(Amps) (Amps) s) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
None - - - 39.3 40 60 38 181 40.8 45 60 40 185
144.
208-1-60 24.4 38 2 6.8 1.5 10625 4.9 1 23.6 68.8 70 80 65 205 70.3 80 80 67 208
2
11125 7.9 1 38 86.8 90 100 82 219 88.3 90 100 84 223
None - - - 39 40 60 38 182 40.3 45 60 39 185
144.
230-1-60 24.4 38 2.3 6.2 1.3 10625 6.5 1 27.1 72.9 80 90 69 209 74.2 80 90 70 212
2
11125 10.5 1 43.8 93.8 100 100 88 226 95.1 100 100 90 229
None - - - 29 30 45 29 175 30.1 35 45 30 177
10625 4.9 1 13.6 46 50 50 44 188 47.1 50 50 46 191
208-3-60 16 110 25 2 7 1.1
11125 7.9 1 21.9 56.4 60 60 54 196 57.5 60 60 55 199
11625 12 1 33.3 70.6 80 80 67 208 71.7 80 80 68 210
06
None - - - 29.5 30 45 29 177 30.5 35 45 30 179
(5)
10625 6.5 1 15.6 49 50 60 47 192 50 50 60 48 195
230-3-60 16 110 25 2.3 7.2 1
11125 10.5 1 25.3 61.1 70 70 58 202 62.1 70 70 60 204
11625 16 1 38.5 77.6 80 80 74 215 78.6 80 80 75 218
None - - - 14.7 15 20 15 86 15.2 20 20 15 87
10646 6 1 7.2 23.7 25 25 23 93 24.2 25 25 23 94
460-3-60 7.8 52 12 1.3 3.6 0.5
11146 11.5 1 13.8 32 35 35 30 100 32.5 35 35 31 101
11446 14 1 16.8 35.7 40 40 34 103 36.2 40 40 35 104
None - - - 10.6 15 15 11 59 11 15 15 11 60
575-3-60 5.7 38.9 9 1 2.5 0.4 11458 13.8 1 13.3 27.2 30 30 26 72 27.6 30 30 26 73
12358 23 1 22.1 38.2 40 40 36 81 38.6 40 40 36 82
With VFD
None - - - 35.3 40 50 36 198 37.5 40 50 38 203
10725 4.9 1 13.6 52.3 60 60 51 211 54.5 60 60 54 216
208-3-60 17.6 136 27 4.4 8.9 1.1
11725 12 1 33.3 76.9 80 80 74 231 79.1 80 80 76 236
12525 18.6 1 51.6 99.8 100 100 95 249 102 110 110 97 254
None - - - 34.6 35 50 35 205 36.6 40 50 37 210
10725 6.5 1 15.6 54.1 60 60 53 221 56.1 60 60 55 225
230-3-60 17.6 136 27 4.4 8.2 1
11725 16 1 38.5 82.7 90 90 79 244 84.7 90 90 81 248
A7
12525 24.8 1 59.7 109.2 110 110 103 265 111.2 125 125 106 269
(6)
None - - - 19.7 20 25 20 101 20.7 25 25 21 103
10746 6 1 7.2 28.7 30 35 29 108 29.7 30 35 30 110
460-3-60 8.5 66.1 13 2.5 4.1 0.5
11746 16.5 1 19.8 44.5 45 45 43 120 45.5 50 50 44 123
12646 25.5 1 30.7 58.1 60 60 56 131 59.1 60 60 57 134
None - - - 19.9 20 25 21 81 20.7 25 25 22 83
575-3-60 6.3 55.3 10 4.4 3.2 0.4 11758 17 1 16.4 40.4 45 45 40 98 41.2 45 45 41 100
12658 25.7 1 24.7 50.8 60 60 49 106 51.6 60 60 50 108
None - - - 43.7 45 50 46 248 45.9 50 50 49 258
11725 12 1 33.3 85.3 90 90 85 282 87.5 90 90 87 292
208-3-60 13.8 83.1 22 13.6 83.1 21 5.8 7 1.1 12525 18.6 1 51.6 108.2 110 110 106 300 110.4 125 125 108 310
13225 24 1 66.6 127 150 150 123 315 129.2 150 150 125 325
14225 31.8 2 88.3 119.1 125 125 114 307 121.9 125 125 117 317
None - - - 43.3 45 50 46 247 45.3 50 50 48 252
11725 16 1 38.5 91.4 100 100 90 286 93.4 100 100 92 295
230-3-60 13.8 83.1 22 13.6 83.1 21 5.2 7.2 1 12525 24.8 1 59.7 117.9 125 125 114 307 119.9 125 125 117 316
08 13225 32 1 77 139.6 150 150 134 324 141.6 150 150 137 333
(7.5) 14225 42.4 2 102 136.5 150 150 124 315 139 150 150 126 324
None - - - 20.4 25 25 22 124 21.4 25 25 23 126
11746 16.5 1 19.8 45.2 50 50 44 144 46.2 50 50 46 148
460-3-60 6.2 41 10 6.1 41 10 2.9 3.6 0.5 12846 27.8 1 33.4 62.2 70 70 60 157 63.2 70 70 61 162
13346 33 1 39.7 70 70 70 67 164 71 80 80 68 168
14246 41.7 2 50.2 67.3 70 70 60 157 68.5 70 70 61 162
None - - - 15 20 20 16 95 15.8 20 20 17 97
575-3-60 4.9 33 8 4.2 33 7 2.2 2.5 0.4 11758 17 1 16.4 35.5 40 40 35 111 36.3 40 40 36 115
13458 34 1 32.7 55.9 60 60 53 128 56.7 60 60 54 131
80 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XYE04-09 medium indoor blower - without powered convenience outlet (Continued)
Min Max Min
Min Max Min MCA1 Fuse2/ Fuse2/
OD Electric Heat Discon-
Nominal Compressor 1 MCA 1 Fuse2/ Fuse2/ Discon- w/Pwr Breaker3 Breaker3
Size Compressor 2 Fan Supply Pwr Pwr Field-installed Kit nect
Unit Blower Exh Conv (Amp Breaker Breaker3
3 nect Exh Size Size
(ton) Motors 2EK045* Rating4/
Voltage Motor Motor Outlet s) Size Size Rating4 (Amp w/ w/
(each) Pwr Exh
(Amps) (Amps) s) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
None - - - 44.6 45 50 47 263 46.8 50 60 50 273
11725 12 1 33.3 86.2 90 90 85 297 88.4 90 90 88 307
208-3-60 14.5 98 23 13.7 83.1 21 5.8 7 1.1 12525 18.6 1 51.6 109.1 110 110 106 315 111.3 125 125 109 325
13225 24 1 66.6 127.9 150 150 124 330 130.1 150 150 126 340
14225 31.8 2 88.3 119.1 125 125 115 322 121.9 125 125 118 332
None - - - 44.2 45 50 47 262 46.2 50 60 49 267
11725 16 1 38.5 92.3 100 100 91 300 94.3 100 100 93 310
230-3-60 14.5 98 23 13.7 83.1 21 5.2 7.2 1 12525 24.8 1 59.7 118.8 125 125 115 322 120.8 125 125 118 331
09 13225 32 1 77 140.5 150 150 135 339 142.5 150 150 138 348
(8.5) 14225 42.4 2 102 136.5 150 150 125 330 139 150 150 127 339
None - - - 20.6 25 25 22 138 21.6 25 25 23 140
11746 16.5 1 19.8 45.4 50 50 45 158 46.4 50 50 46 162
460-3-60 6.3 55 10 6.2 41 10 2.9 3.6 0.5 12846 27.8 1 33.4 62.4 70 70 60 171 63.4 70 70 61 176
13346 33 1 39.7 70.2 80 80 68 178 71.2 80 80 69 182
14246 41.7 2 50.2 67.3 70 70 60 171 68.5 70 70 61 176
None - - - 17 20 20 18 103 17.8 20 20 19 105
575-3-60 6 41 9 4.8 33 8 2.2 2.5 0.4 11758 17 1 16.4 37.5 40 40 37 119 38.3 40 40 38 123
13458 34 1 32.7 57.9 60 60 55 136 58.7 60 60 56 139
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field-installed
electric heat kits may exceed the factory-installed disconnect amperage rating.
Johnson Controls Ducted Systems 81
5147362-YTG-R-0323
XYE04-09 medium indoor blower - with powered convenience outlet
Min Min
Min Max Fuse2/
Min Max Fuse2/
OD Electric Heat
Discon- MCA1 Breaker3 Discon-
Nominal Compressor 1 Compressor 2 Supply Pwr Pwr Field-installed Kit Fuse2/ Fuse2/ Breaker3 nect
Size Fan MCA1 nect w/Pwr Size
Unit Blower Exh Conv 2EK045* Breaker3 Breaker3 Size Rating4/
(ton) Motors (Amps) Rating4 Exh w/
Voltage Motor Motor Outlet Size Size w/
(each) (Amps) Pwr Exh Pwr Exh
(Amps) (Amps) Pwr Exh
(Amps)
(Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
None - - - 33.2 35 45 34 126 34.7 35 50 35 129
208-1-60 15.4 83.9 24 2 7.6 1.5 8.6 10625 4.9 1 23.6 62.7 70 70 61 149 64.2 70 70 63 153
11125 7.9 1 38 80.7 90 90 77 164 82.2 90 90 79 167
None - - - 32.9 35 45 33 129 34.2 35 45 35 132
230-1-60 15.4 83.9 24 2.3 7 1.3 8.6 10625 6.5 1 27.1 66.8 70 70 65 156 68.1 70 70 66 159
11125 10.5 1 43.8 87.7 90 90 84 172 89 90 90 85 175
None - - - 24.5 25 30 25 104 25.6 30 35 26 107
10625 4.9 1 13.6 41.5 45 45 41 118 42.6 45 45 42 120
208-3-60 10.4 73 16 2 5.2 1.1 8.6
11125 7.9 1 21.9 51.9 60 60 50 126 53 60 60 52 129
11625 12 1 33.3 66.1 70 70 63 137 67.2 70 70 65 140
04
None - - - 24.8 25 35 26 107 25.8 30 35 27 110
(3)
10625 6.5 1 15.6 44.3 45 50 43 123 45.3 50 50 45 125
230-3-60 10.4 73 16 2.3 5.2 1 8.6
11125 10.5 1 25.3 56.4 60 60 55 133 57.4 60 60 56 135
11625 16 1 38.5 72.9 80 80 70 146 73.9 80 80 71 148
None - - - 13.4 15 15 14 56 13.9 15 15 14 57
10646 6 1 7.2 22.4 25 25 22 63 22.9 25 25 23 64
460-3-60 5.8 38 9 1.3 2.6 0.5 8.6
11146 11.5 1 13.8 30.7 35 35 30 69 31.2 35 35 30 70
11446 14 1 16.8 34.4 35 35 33 72 34.9 35 35 34 73
None - - - 9.5 15 15 10 51 9.9 15 15 10 51
575-3-60 3.8 36.5 6 1 2 0.4 8.6 11058 9.2 1 8.9 20.6 25 25 20 59 21 25 25 20 60
11458 13.8 1 13.3 26.1 30 30 25 64 26.5 30 30 26 65
None - - - 38.4 40 50 39 172 39.9 40 50 40 175
208-1-60 19.6 130 31 2 7.6 1.5 8.6 10625 4.9 1 23.6 67.9 70 80 66 195 69.4 70 80 67 199
11125 7.9 1 38 85.9 90 90 82 210 87.4 90 90 84 213
None - - - 38.1 40 50 38 175 39.4 40 50 40 178
230-1-60 19.6 130 31 2.3 7 1.3 8.6 10625 6.5 1 27.1 72 80 80 69 202 73.3 80 80 71 205
11125 10.5 1 43.8 92.9 100 100 89 219 94.2 100 100 90 221
None - - - 28.6 30 40 29 114 29.7 30 40 30 117
10625 4.9 1 13.6 45.6 50 50 45 128 46.7 50 50 46 130
208-3-60 13.7 83.1 21 2 5.2 1.1 8.6
11125 7.9 1 21.9 56 60 60 54 136 57.1 60 60 55 139
11625 12 1 33.3 70.2 80 80 67 148 71.3 80 80 69 150
05
None - - - 28.9 30 40 29 117 29.9 30 40 30 120
(4)
10625 6.5 1 15.6 48.4 50 50 47 133 49.4 50 50 48 135
230-3-60 13.7 83.1 21 2.3 5.2 1 8.6
11125 10.5 1 25.3 60.5 70 70 58 143 61.5 70 70 60 145
11625 16 1 38.5 77 80 80 74 156 78 80 80 75 158
None - - - 13.9 15 20 14 59 14.4 15 20 15 60
10646 6 1 7.2 22.9 25 25 22 66 23.4 25 25 23 67
460-3-60 6.2 41 10 1.3 2.6 0.5 8.6
11146 11.5 1 13.8 31.2 35 35 30 72 31.7 35 35 31 73
11446 14 1 16.8 34.9 35 35 33 75 35.4 40 40 34 76
None - - - 10.7 15 15 11 47 11.1 15 15 11 48
575-3-60 4.8 33 8 1 2 0.4 8.6 11058 9.2 1 8.9 21.8 25 25 21 56 22.2 25 25 22 57
11458 13.8 1 13.3 27.3 30 30 26 60 27.7 30 30 27 61
82 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XYE04-09 medium indoor blower - with powered convenience outlet (Continued)
Min Min
Min Max Fuse2/
Min Max Fuse2/
OD Electric Heat
Discon- MCA1 Breaker3 Discon-
Nominal Compressor 1 Compressor 2 Supply Pwr Pwr Field-installed Kit Fuse2/ Fuse2/ Breaker3 nect
Size Fan MCA1 nect w/Pwr Size
Unit Blower Exh Conv 2EK045* Breaker Breaker3
3 Size Rating4/
(ton) Motors (Amps) Rating4 Exh w/
Voltage Motor Motor Outlet Size Size w/ Pwr Exh
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh
(Amps)
(Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
None - - - 43.6 45 60 43 185 45.1 50 60 45 189
144.
208-1-60 24.4 38 2 6.8 1.5 8.6 10625 4.9 1 23.6 73.1 80 90 70 209 74.6 80 90 72 212
2
11125 7.9 1 38 91.1 100 100 87 223 92.6 100 100 89 227
None - - - 43.3 45 60 43 186 44.6 45 60 44 189
144.
230-1-60 24.4 38 2.3 6.2 1.3 8.6 10625 6.5 1 27.1 77.2 80 90 74 214 78.5 80 90 75 216
2
11125 10.5 1 43.8 98.1 100 110 93 230 99.4 100 110 95 233
None - - - 33.3 35 45 34 179 34.4 35 50 35 181
10625 4.9 1 13.6 50.3 60 60 49 192 51.4 60 60 51 195
208-3-60 16 110 25 2 7 1.1 8.6
11125 7.9 1 21.9 60.7 70 70 59 201 61.8 70 70 60 203
11625 12 1 33.3 74.9 80 80 72 212 76 80 80 73 215
06
None - - - 33.8 35 45 34 181 34.8 35 50 35 183
(5)
10625 6.5 1 15.6 53.3 60 60 52 197 54.3 60 60 53 199
230-3-60 16 110 25 2.3 7.2 1 8.6
11125 10.5 1 25.3 65.4 70 70 63 206 66.4 70 70 65 209
11625 16 1 38.5 81.9 90 90 79 220 82.9 90 90 80 222
None - - - 16.9 20 20 17 88 17.4 20 20 18 89
10646 6 1 7.2 25.9 30 30 25 95 26.4 30 30 26 96
460-3-60 7.8 52 12 1.3 3.6 0.5 8.6
11146 11.5 1 13.8 34.2 35 35 33 102 34.7 35 35 34 103
11446 14 1 16.8 37.9 40 40 36 105 38.4 40 40 37 106
None - - - 12.3 15 15 13 61 12.7 15 15 13 62
575-3-60 5.7 38.9 9 1 2.5 0.4 8.6 11458 13.8 1 13.3 28.9 30 30 28 74 29.3 30 30 28 75
12358 23 1 22.1 39.9 40 40 38 83 40.3 45 45 38 84
With VFD
None - - - 39.6 40 50 40 202 41.8 45 50 43 207
10725 4.9 1 13.6 56.6 60 70 56 216 58.8 60 70 59 221
208-3-60 17.6 136 27 4.4 8.9 1.1 8.6
11725 12 1 33.3 81.2 90 90 79 235 83.4 90 90 81 240
12525 18.6 1 51.6 104.1 110 110 100 254 106.3 110 110 102 259
None - - - 38.9 40 50 40 209 40.9 45 50 42 214
10725 6.5 1 15.6 58.4 60 70 58 225 60.4 70 70 60 230
230-3-60 17.6 136 27 4.4 8.2 1 8.6
11725 16 1 38.5 87 90 90 84 248 89 90 90 86 252
12525 24.8 1 59.7 113.5 125 125 108 269 115.5 125 125 111 274
A7 None - - - 21.9 25 30 23 103 22.9 25 30 24 105
(6) 10746 6 1 7.2 30.9 35 35 31 110 31.9 35 35 32 112
460-3-60 8.5 66.1 13 2.5 4.1 0.5 8.6
11746 16.5 1 19.8 46.7 50 50 46 123 47.7 50 50 47 125
12646 25.5 1 30.7 60.3 70 70 58 133 61.3 70 70 59 136
None - - - 21.6 25 25 23 83 22.4 25 25 24 85
575-3-60 6.3 55.3 10 4.4 3.2 0.4 8.6 11758 17 1 16.4 42.1 45 45 42 100 42.9 45 45 43 101
12658 25.7 1 24.7 52.5 60 60 51 108 53.3 60 60 52 110
None - - - 39.6 40 50 40 202 41.8 45 50 43 207
208-3-60 17.6 136 27 4.4 8.9 1.1 8.6 10725 4.9 1 13.6 56.6 60 70 56 216 58.8 60 70 59 221
11725 12 1 33.3 81.2 90 90 79 235 83.4 90 90 81 240
None - - - 48 50 60 51 253 50.2 60 60 54 263
11725 12 1 33.3 89.6 90 90 89 286 91.8 100 100 92 296
208-3-60 13.8 83.1 22 13.6 83.1 21 5.8 7 1.1 8.6 12525 18.6 1 51.6 112.5 125 125 111 304 114.7 125 125 113 314
13225 24 1 66.6 131.3 150 150 128 319 133.5 150 150 130 329
14225 31.8 2 88.3 124.5 125 125 119 312 127.3 150 150 122 322
None - - - 47.6 50 60 51 251 49.6 50 60 53 256
11725 16 1 38.5 95.7 100 100 95 290 97.7 100 100 97 299
230-3-60 13.8 83.1 22 13.6 83.1 21 5.2 7.2 1 8.6 12525 24.8 1 59.7 122.2 125 125 119 311 124.2 125 125 122 320
08 13225 32 1 77 143.9 150 150 139 328 145.9 150 150 142 338
(7.5) 14225 42.4 2 102 141.9 150 150 129 319 144.4 150 150 131 329
None - - - 22.6 25 25 24 126 23.6 25 25 25 128
11746 16.5 1 19.8 47.4 50 50 47 146 48.4 50 50 48 150
460-3-60 6.2 41 10 6.1 41 10 2.9 3.6 0.5 8.6 12846 27.8 1 33.4 64.4 70 70 63 159 65.4 70 70 64 164
13346 33 1 39.7 72.2 80 80 70 166 73.2 80 80 71 170
14246 41.7 2 50.2 69.9 70 70 63 159 71.2 80 80 64 164
None - - - 16.7 20 20 18 97 17.5 20 20 19 99
575-3-60 4.9 33 8 4.2 33 7 2.2 2.5 0.4 8.6 11758 17 1 16.4 37.2 40 40 37 113 38 40 40 38 117
13458 34 1 32.7 57.6 60 60 55 129 58.4 60 60 56 133
Johnson Controls Ducted Systems 83
5147362-YTG-R-0323
XYE04-09 medium indoor blower - with powered convenience outlet (Continued)
Min Min
Min Max Fuse2/
Min Max Fuse2/
OD Electric Heat
Discon- MCA1 Breaker3 Discon-
Nominal Compressor 1 Compressor 2 Supply Pwr Pwr Field-installed Kit Fuse2/ Fuse2/ Breaker3 nect
Size Fan MCA1 nect w/Pwr Size
Unit Blower Exh Conv 2EK045* Breaker3 Breaker3 Size Rating4/
(ton) Motors (Amps) Rating4 Exh w/
Voltage Motor Motor Outlet Size Size w/ Pwr Exh
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh
(Amps)
(Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
None - - - 48.9 50 60 52 268 51.1 60 60 55 278
11725 12 1 33.3 90.5 100 100 90 301 92.7 100 100 93 311
208-3-60 14.5 98 23 13.7 83.1 21 5.8 7 1.1 8.6 12525 18.6 1 51.6 113.4 125 125 111 319 115.6 125 125 114 329
13225 24 1 66.6 132.2 150 150 129 334 134.4 150 150 131 344
14225 31.8 2 88.3 124.5 125 125 120 327 127.3 150 150 123 337
None - - - 48.5 50 60 52 266 50.5 60 60 54 271
11725 16 1 38.5 96.6 100 100 96 305 98.6 100 100 98 314
230-3-60 14.5 98 23 13.7 83.1 21 5.2 7.2 1 8.6 12525 24.8 1 59.7 123.1 125 125 120 326 125.1 150 150 123 335
09 13225 32 1 77 144.8 150 150 140 343 146.8 150 150 142 352
(8.5) 14225 42.4 2 102 141.9 150 150 130 334 144.4 150 150 132 344
None - - - 22.8 25 25 24 140 23.8 25 25 26 142
11746 16.5 1 19.8 47.6 50 50 47 160 48.6 50 50 48 164
460-3-60 6.3 55 10 6.2 41 10 2.9 3.6 0.5 8.6 12846 27.8 1 33.4 64.6 70 70 63 173 65.6 70 70 64 178
13346 33 1 39.7 72.4 80 80 70 180 73.4 80 80 71 184
14246 41.7 2 50.2 69.9 70 70 63 173 71.2 80 80 64 178
None - - - 18.7 20 20 20 105 19.5 20 20 21 107
575-3-60 6 41 9 4.8 33 8 2.2 2.5 0.4 8.6 11758 17 1 16.4 39.2 40 40 39 121 40 40 40 40 125
13458 34 1 32.7 59.6 60 60 57 137 60.4 70 70 58 141
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field-installed
electric heat kits may exceed the factory-installed disconnect amperage rating.
84 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XYE04-09 high indoor blower - without powered convenience outlet
Min Max Min
Min Max Min MCA1 Fuse2/ Fuse2/
OD Electric Heat Discon-
Nominal Compressor 1 Fuse2/ Fuse2/ Discon- w/Pwr Breaker3 Breaker3
Size Compressor 2 Fan Supply Pwr Pwr Field-installed Kit MCA1 nect
Unit Blower Exh Conv Breaker3 Breaker3 nect Exh Size Size
(ton) Motors 2EK045* (Amps) Rating4/
Voltage Motor Motor Outlet Size Size Rating4 (Amp w/ w/
(each) Pwr Exh
(Amps) (Amps) s) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
None - - - 20.2 25 30 20 100 21.3 25 30 22 102
10625 4.9 1 13.6 37.2 40 40 36 113 38.3 40 45 37 116
208-3-60 10.4 73 16 2 5.2 1.1
11125 7.9 1 21.9 47.6 50 50 45 122 48.7 50 50 47 124
11625 12 1 33.3 61.8 70 70 59 133 62.9 70 70 60 136
None - - - 20.5 25 30 21 103 21.5 25 30 22 105
10625 6.5 1 15.6 40 40 45 39 119 41 45 45 40 121
230-3-60 10.4 73 16 2.3 5.2 1
11125 10.5 1 25.3 52.1 60 60 50 128 53.1 60 60 51 131
04
11625 16 1 38.5 68.6 70 70 65 141 69.6 70 70 66 144
(3)
None - - - 11.2 15 15 11 53 11.7 15 15 12 55
10646 6 1 7.2 20.2 25 25 19 61 20.7 25 25 20 62
460-3-60 5.8 38 9 1.3 2.6 0.5
11146 11.5 1 13.8 28.5 30 30 27 67 29 30 30 28 68
11446 14 1 16.8 32.2 35 35 30 70 32.7 35 35 31 71
None - - - 7.8 15 15 8 49 8.2 15 15 8 50
575-3-60 3.8 36.5 6 1 2 0.4 11058 9.2 1 8.9 18.9 20 20 18 58 19.3 20 20 19 59
11458 13.8 1 13.3 24.4 25 25 23 62 24.8 25 25 24 63
None - - - 24.3 25 35 24 110 25.4 30 35 25 112
10625 4.9 1 13.6 41.3 45 50 40 124 42.4 45 50 41 126
208-3-60 13.7 83.1 21 2 5.2 1.1
11125 7.9 1 21.9 51.7 60 60 49 132 52.8 60 60 50 134
11625 12 1 33.3 65.9 70 70 62 143 67 70 70 64 146
None - - - 24.6 25 35 24 113 25.6 30 35 26 115
10625 6.5 1 15.6 44.1 45 50 42 129 45.1 50 50 43 131
230-3-60 13.7 83.1 21 2.3 5.2 1
11125 10.5 1 25.3 56.2 60 60 53 138 57.2 60 60 55 141
05
11625 16 1 38.5 72.7 80 80 69 152 73.7 80 80 70 154
(4)
None - - - 11.7 15 15 12 56 12.2 15 15 12 58
10646 6 1 7.2 20.7 25 25 20 64 21.2 25 25 20 65
460-3-60 6.2 41 10 1.3 2.6 0.5
11146 11.5 1 13.8 29 30 30 27 70 29.5 30 30 28 71
11446 14 1 16.8 32.7 35 35 31 73 33.2 35 35 32 74
None - - - 9 15 15 9 45 9.4 15 15 9 46
575-3-60 4.8 33 8 1 2 0.4 11058 9.2 1 8.9 20.1 25 25 19 54 20.5 25 25 20 55
11458 13.8 1 13.3 25.6 30 30 24 59 26 30 30 25 60
None - - - 30.9 35 45 31 191 32 35 45 32 194
10625 4.9 1 13.6 47.9 50 60 47 205 49 50 60 48 207
208-3-60 16 110 25 2 8.9 1.1
11125 7.9 1 21.9 58.3 60 60 56 213 59.4 60 60 57 216
11625 12 1 33.3 72.5 80 80 69 225 73.6 80 80 70 227
None - - - 30.5 35 45 30 194 31.5 35 45 32 196
10625 6.5 1 15.6 50 50 60 48 210 51 60 60 50 212
230-3-60 16 110 25 2.3 8.2 1
11125 10.5 1 25.3 62.1 70 70 60 219 63.1 70 70 61 222
06
11625 16 1 38.5 78.6 80 80 75 232 79.6 80 80 76 235
(5)
None - - - 15.2 20 20 15 89 15.7 20 20 16 91
10646 6 1 7.2 24.2 25 30 23 97 24.7 25 30 24 98
460-3-60 7.8 52 12 1.3 4.1 0.5
11146 11.5 1 13.8 32.5 35 35 31 103 33 35 35 32 104
11446 14 1 16.8 36.2 40 40 35 106 36.7 40 40 35 107
None - - - 11.3 15 15 11 67 11.7 15 15 12 68
575-3-60 5.7 38.9 9 1 3.2 0.4 11458 13.8 1 13.3 27.9 30 30 27 81 28.3 30 30 27 82
12358 23 1 22.1 38.9 40 40 37 89 39.3 40 40 37 90
Johnson Controls Ducted Systems 85
5147362-YTG-R-0323
XYE04-09 high indoor blower - without powered convenience outlet (Continued)
Min Max Min
Min Max Min MCA1 Fuse2/ Fuse2/
OD Electric Heat Discon-
Nominal Compressor 1 Fuse2/ Fuse2/ Discon- w/Pwr Breaker3 Breaker3
Size Compressor 2 Fan Supply Pwr Pwr Field-installed Kit MCA1 nect
Unit Blower Exh Conv Breaker Breaker3
3 nect Exh Size Size
(ton) Motors 2EK045* (Amps) Rating4/
Voltage Motor Motor Outlet Size Size Rating4 (Amp w/ w/
(each) Pwr Exh
(Amps) (Amps) s) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
With VFD
None - - - 36.3 40 50 37 209 38.5 40 50 39 214
10725 4.9 1 13.6 53.3 60 60 52 222 55.5 60 60 55 227
208-3-60 17.6 136 27 4.4 9.9 1.1
11725 12 1 33.3 77.9 80 80 75 242 80.1 90 90 78 247
12525 18.6 1 51.6 100.8 110 110 96 260 103 110 110 99 265
None - - - 35.8 40 50 36 217 37.8 40 50 38 221
10725 6.5 1 15.6 55.3 60 60 54 232 57.3 60 70 56 237
230-3-60 17.6 136 27 4.4 9.4 1
11725 16 1 38.5 83.9 90 90 80 255 85.9 90 90 83 260
A7
12525 24.8 1 59.7 110.4 125 125 105 276 112.4 125 125 107 281
(6)
None - - - 20.3 25 25 21 106 21.3 25 25 22 109
10746 6 1 7.2 29.3 30 35 29 114 30.3 35 35 30 116
460-3-60 8.5 66.1 13 2.5 4.7 0.5
11746 16.5 1 19.8 45.1 50 50 44 126 46.1 50 50 45 128
12646 25.5 1 30.7 58.7 60 60 56 137 59.7 60 60 57 139
None - - - 21 25 25 22 95 21.8 25 25 23 97
575-3-60 6.3 55.3 10 4.4 4.3 0.4 11758 17 1 16.4 41.5 45 45 41 112 42.3 45 45 42 114
12658 25.7 1 24.7 51.9 60 60 51 120 52.7 60 60 52 122
None - - - 46.6 50 60 50 261 48.8 50 60 52 271
11725 12 1 33.3 88.2 90 90 88 294 90.4 100 100 90 304
208-3-60 13.8 83.1 22 13.6 83.1 21 5.8 9.9 1.1 12525 18.6 1 51.6 111.1 125 125 109 312 113.3 125 125 111 322
13225 24 1 66.6 129.9 150 150 126 327 132.1 150 150 129 337
14225 31.8 2 88.3 122.8 125 125 118 320 125.5 150 150 120 330
None - - - 45.5 50 50 48 266 47.5 50 60 51 270
11725 16 1 38.5 93.6 100 100 93 304 95.6 100 100 95 314
230-3-60 13.8 83.1 22 13.6 83.1 21 5.2 9.4 1 12525 24.8 1 59.7 120.1 125 125 117 326 122.1 125 125 119 335
08 13225 32 1 77 141.8 150 150 137 343 143.8 150 150 139 352
(7.5) 14225 42.4 2 102 139.3 150 150 127 334 141.8 150 150 129 343
None - - - 21.5 25 25 23 133 22.5 25 25 24 136
11746 16.5 1 19.8 46.3 50 50 46 153 47.3 50 50 47 158
460-3-60 6.2 41 10 6.1 41 10 2.9 4.7 0.5 12846 27.8 1 33.4 63.3 70 70 61 167 64.3 70 70 62 171
13346 33 1 39.7 71.1 80 80 69 173 72.1 80 80 70 177
14246 41.7 2 50.2 68.6 70 70 61 167 69.9 70 70 62 171
None - - - 16.8 20 20 18 117 17.6 20 20 19 119
575-3-60 4.9 33 8 4.2 33 7 2.2 4.3 0.4 11758 17 1 16.4 37.3 40 40 37 134 38.1 40 40 38 137
13458 34 1 32.7 57.7 60 60 56 150 58.5 60 60 56 154
None - - - 47.5 50 60 50 276 49.7 50 60 53 286
11725 12 1 33.3 89.1 90 90 89 309 91.3 100 100 91 319
208-3-60 14.5 98 23 13.7 83.1 21 5.8 9.9 1.1 12525 18.6 1 51.6 112 125 125 110 327 114.2 125 125 112 337
13225 24 1 66.6 130.8 150 150 127 342 133 150 150 130 352
14225 31.8 2 88.3 122.8 125 125 118 335 125.5 150 150 121 345
None - - - 46.4 50 60 49 281 48.4 50 60 52 285
11725 16 1 38.5 94.5 100 100 93 319 96.5 100 100 96 328
230-3-60 14.5 98 23 13.7 83.1 21 5.2 9.4 1 12525 24.8 1 59.7 121 125 125 118 340 123 125 125 120 350
09 13225 32 1 77 142.7 150 150 138 358 144.7 150 150 140 367
(8.5) 14225 42.4 2 102 139.3 150 150 128 349 141.8 150 150 130 358
None - - - 21.7 25 25 23 147 22.7 25 25 24 150
11746 16.5 1 19.8 46.5 50 50 46 167 47.5 50 50 47 172
460-3-60 6.3 55 10 6.2 41 10 2.9 4.7 0.5 12846 27.8 1 33.4 63.5 70 70 62 181 64.5 70 70 63 185
13346 33 1 39.7 71.3 80 80 69 187 72.3 80 80 70 191
14246 41.7 2 50.2 68.6 70 70 62 181 69.9 70 70 63 185
None - - - 18.8 20 20 20 125 19.6 20 20 21 127
575-3-60 6 41 9 4.8 33 8 2.2 4.3 0.4 11758 17 1 16.4 39.3 40 40 39 142 40.1 45 45 40 145
13458 34 1 32.7 59.7 60 60 58 158 60.5 70 70 58 162
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field-installed
electric heat kits may exceed the factory-installed disconnect amperage rating.
86 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XYE04-09 high indoor blower - with powered convenience outlet
Min Max Min
Min Max Min MCA1 Fuse2/ Fuse2/
OD Electric Heat Discon-
Nominal Compressor 1 Fuse2/ Fuse2/ Discon- w/Pwr Breaker3 Breaker3
Size Compressor 2 Fan Supply Pwr Pwr Field-installed Kit MCA1 nect
Unit Blower Exh Conv Breaker Breaker3
3 nect Exh Size Size
(ton) Motors 2EK045* (Amps) Rating4/
Voltage Motor Motor Outlet Size Size Rating4 (Amp w/ w/
(each) Pwr Exh
(Amps) (Amps) s) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
None - - - 24.5 25 30 25 104 25.6 30 35 26 107
10625 4.9 1 13.6 41.5 45 45 41 118 42.6 45 45 42 120
208-3-60 10.4 73 16 2 5.2 1.1 8.6
11125 7.9 1 21.9 51.9 60 60 50 126 53 60 60 52 129
11625 12 1 33.3 66.1 70 70 63 137 67.2 70 70 65 140
None - - - 24.8 25 35 26 107 25.8 30 35 27 110
10625 6.5 1 15.6 44.3 45 50 43 123 45.3 50 50 45 125
230-3-60 10.4 73 16 2.3 5.2 1 8.6
11125 10.5 1 25.3 56.4 60 60 55 133 57.4 60 60 56 135
04
11625 16 1 38.5 72.9 80 80 70 146 73.9 80 80 71 148
(3)
None - - - 13.4 15 15 14 56 13.9 15 15 14 57
10646 6 1 7.2 22.4 25 25 22 63 22.9 25 25 23 64
460-3-60 5.8 38 9 1.3 2.6 0.5 8.6
11146 11.5 1 13.8 30.7 35 35 30 69 31.2 35 35 30 70
11446 14 1 16.8 34.4 35 35 33 72 34.9 35 35 34 73
None - - - 9.5 15 15 10 51 9.9 15 15 10 51
575-3-60 3.8 36.5 6 1 2 0.4 8.6 11058 9.2 1 8.9 20.6 25 25 20 59 21 25 25 20 60
11458 13.8 1 13.3 26.1 30 30 25 64 26.5 30 30 26 65
None - - - 28.6 30 40 29 114 29.7 30 40 30 117
10625 4.9 1 13.6 45.6 50 50 45 128 46.7 50 50 46 130
208-3-60 13.7 83.1 21 2 5.2 1.1 8.6
11125 7.9 1 21.9 56 60 60 54 136 57.1 60 60 55 139
11625 12 1 33.3 70.2 80 80 67 148 71.3 80 80 69 150
None - - - 28.9 30 40 29 117 29.9 30 40 30 120
10625 6.5 1 15.6 48.4 50 50 47 133 49.4 50 50 48 135
230-3-60 13.7 83.1 21 2.3 5.2 1 8.6
11125 10.5 1 25.3 60.5 70 70 58 143 61.5 70 70 60 145
05
11625 16 1 38.5 77 80 80 74 156 78 80 80 75 158
(4)
None - - - 13.9 15 20 14 59 14.4 15 20 15 60
10646 6 1 7.2 22.9 25 25 22 66 23.4 25 25 23 67
460-3-60 6.2 41 10 1.3 2.6 0.5 8.6
11146 11.5 1 13.8 31.2 35 35 30 72 31.7 35 35 31 73
11446 14 1 16.8 34.9 35 35 33 75 35.4 40 40 34 76
None - - - 10.7 15 15 11 47 11.1 15 15 11 48
575-3-60 4.8 33 8 1 2 0.4 8.6 11058 9.2 1 8.9 21.8 25 25 21 56 22.2 25 25 22 57
11458 13.8 1 13.3 27.3 30 30 26 60 27.7 30 30 27 61
None - - - 35.2 40 50 36 196 36.3 40 50 37 198
10625 4.9 1 13.6 52.2 60 60 52 209 53.3 60 60 53 212
208-3-60 16 110 25 2 8.9 1.1 8.6
11125 7.9 1 21.9 62.6 70 70 61 217 63.7 70 70 62 220
11625 12 1 33.3 76.8 80 80 74 229 77.9 80 80 75 231
None - - - 34.8 35 50 35 198 35.8 40 50 37 201
10625 6.5 1 15.6 54.3 60 60 53 214 55.3 60 60 55 216
230-3-60 16 110 25 2.3 8.2 1 8.6
11125 10.5 1 25.3 66.4 70 70 65 224 67.4 70 70 66 226
06
11625 16 1 38.5 82.9 90 90 80 237 83.9 90 90 81 239
(5)
None - - - 17.4 20 25 18 92 17.9 20 25 18 93
10646 6 1 7.2 26.4 30 30 26 99 26.9 30 30 27 100
460-3-60 7.8 52 12 1.3 4.1 0.5 8.6
11146 11.5 1 13.8 34.7 35 35 34 105 35.2 40 40 34 106
11446 14 1 16.8 38.4 40 40 37 108 38.9 40 40 38 109
None - - - 13 15 15 13 69 13.4 15 15 14 70
575-3-60 5.7 38.9 9 1 3.2 0.4 8.6 11458 13.8 1 13.3 29.6 30 30 29 82 30 30 30 29 83
12358 23 1 22.1 40.6 45 45 39 91 41 45 45 39 92
Johnson Controls Ducted Systems 87
5147362-YTG-R-0323
XYE04-09 high indoor blower - with powered convenience outlet (Continued)
Min Max Min
Min Max Min MCA1 Fuse2/ Fuse2/
OD Electric Heat Discon-
Nominal Compressor 1 Fuse2/ Fuse2/ Discon- w/Pwr Breaker3 Breaker3
Size Compressor 2 Fan Supply Pwr Pwr Field-installed Kit MCA1 nect
Unit Blower Exh Conv Breaker Breaker3
3 nect Exh Size Size
(ton) Motors 2EK045* (Amps) Rating4/
Voltage Motor Motor Outlet Size Size Rating4 (Amp w/ w/
(each) Pwr Exh
(Amps) (Amps) s) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
With VFD
None - - - 40.6 45 50 42 213 42.8 45 50 44 218
10725 4.9 1 13.6 57.6 60 70 57 226 59.8 60 70 60 231
208-3-60 17.6 136 27 4.4 9.9 1.1 8.6
11725 12 1 33.3 82.2 90 90 80 246 84.4 90 90 82 251
12525 18.6 1 51.6 105.1 110 110 101 264 107.3 110 110 104 269
None - - - 40.1 45 50 41 221 42.1 45 50 43 226
10725 6.5 1 15.6 59.6 60 70 59 237 61.6 70 70 61 241
230-3-60 17.6 136 27 4.4 9.4 1 8.6
11725 16 1 38.5 88.2 90 90 85 259 90.2 100 100 88 264
A7
12525 24.8 1 59.7 114.7 125 125 110 281 116.7 125 125 112 285
(6)
None - - - 22.5 25 30 23 109 23.5 25 30 25 111
10746 6 1 7.2 31.5 35 35 32 116 32.5 35 35 33 118
460-3-60 8.5 66.1 13 2.5 4.7 0.5 8.6
11746 16.5 1 19.8 47.3 50 50 46 128 48.3 50 50 47 131
12646 25.5 1 30.7 60.9 70 70 59 139 61.9 70 70 60 141
None - - - 22.7 25 25 24 97 23.5 25 25 25 99
575-3-60 6.3 55.3 10 4.4 4.3 0.4 8.6 11758 17 1 16.4 43.2 45 45 43 113 44 45 45 44 115
12658 25.7 1 24.7 53.6 60 60 53 122 54.4 60 60 54 124
None - - - 50.9 60 60 55 265 53.1 60 60 57 275
11725 12 1 33.3 92.5 100 100 93 298 94.7 100 100 95 308
208-3-60 13.8 83.1 22 13.6 83.1 21 5.8 9.9 1.1 8.6 12525 18.6 1 51.6 115.4 125 125 114 317 117.6 125 125 116 327
13225 24 1 66.6 134.2 150 150 131 332 136.4 150 150 134 342
14225 31.8 2 88.3 128.1 150 150 122 324 130.9 150 150 125 334
None - - - 49.8 50 60 53 270 51.8 60 60 56 275
11725 16 1 38.5 97.9 100 100 98 309 99.9 100 100 100 318
230-3-60 13.8 83.1 22 13.6 83.1 21 5.2 9.4 1 8.6 12525 24.8 1 59.7 124.4 125 125 122 330 126.4 150 150 124 339
08 13225 32 1 77 146.1 150 150 142 347 148.1 150 150 144 356
(7.5) 14225 42.4 2 102 144.6 150 150 132 338 147.1 150 150 134 347
None - - - 23.7 25 25 25 135 24.7 25 25 27 138
11746 16.5 1 19.8 48.5 50 50 48 155 49.5 50 50 49 160
460-3-60 6.2 41 10 6.1 41 10 2.9 4.7 0.5 8.6 12846 27.8 1 33.4 65.5 70 70 64 169 66.5 70 70 65 173
13346 33 1 39.7 73.3 80 80 71 175 74.3 80 80 72 180
14246 41.7 2 50.2 71.3 80 80 64 169 72.6 80 80 65 173
None - - - 18.5 20 20 20 119 19.3 20 20 21 121
575-3-60 4.9 33 8 4.2 33 7 2.2 4.3 0.4 8.6 11758 17 1 16.4 39 40 40 39 135 39.8 40 40 40 139
13458 34 1 32.7 59.4 60 60 58 152 60.2 70 70 58 155
None - - - 51.8 60 60 55 280 54 60 60 58 290
11725 12 1 33.3 93.4 100 100 94 313 95.6 100 100 96 323
208-3-60 14.5 98 23 13.7 83.1 21 5.8 9.9 1.1 8.6 12525 18.6 1 51.6 116.3 125 125 115 332 118.5 125 125 117 342
13225 24 1 66.6 135.1 150 150 132 347 137.3 150 150 135 357
14225 31.8 2 88.3 128.1 150 150 123 339 130.9 150 150 126 349
None - - - 50.7 60 60 54 285 52.7 60 60 56 290
11725 16 1 38.5 98.8 100 100 98 324 100.8 110 110 101 333
230-3-60 14.5 98 23 13.7 83.1 21 5.2 9.4 1 8.6 12525 24.8 1 59.7 125.3 150 150 123 345 127.3 150 150 125 354
09 13225 32 1 77 147 150 150 143 362 149 150 150 145 371
(8.5) 14225 42.4 2 102 144.6 150 150 132 353 147.1 150 150 135 362
None - - - 23.9 25 30 26 149 24.9 25 30 27 152
11746 16.5 1 19.8 48.7 50 50 48 169 49.7 50 50 50 174
460-3-60 6.3 55 10 6.2 41 10 2.9 4.7 0.5 8.6 12846 27.8 1 33.4 65.7 70 70 64 183 66.7 70 70 65 187
13346 33 1 39.7 73.5 80 80 71 189 74.5 80 80 72 194
14246 41.7 2 50.2 71.3 80 80 64 183 72.6 80 80 65 187
None - - - 20.5 25 25 22 127 21.3 25 25 23 129
575-3-60 6 41 9 4.8 33 8 2.2 4.3 0.4 8.6 11758 17 1 16.4 41 45 45 41 143 41.8 45 45 42 147
13458 34 1 32.7 61.4 70 70 59 160 62.2 70 70 60 163
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field-installed
electric heat kits may exceed the factory-installed disconnect amperage rating.
88 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XXEA7-12 standard indoor blower - without powered convenience outlet
Max
Min Min
Min Min Fuse2/
Max MCA1 Fuse2/
OD Electric Heat Fuse2/ 2 Discon- Breaker Discon-
Nominal Compressor 1 Compressor 2 Supply Pwr Pwr Field-installed Kit Fuse / w/Pwr Breaker3 nect
Size Fan MCA1 Breaker nect
3
Unit Blower Exh Conv 2EK045* 3 Breaker3 Exh Size Rating4/
(ton) Motors (Amps) 4
Rating (Amps Size
Voltage Motor Motor Outlet Size w/ Pwr Exh
(each) Size w/
(Amps) ) Pwr Exh
(Amps) Pwr Exh
(Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA (Amps) FLA LRA
With VFD
None - - - 31 35 45 31 201 32.1 35 45 32 203
10625 4.9 1 13.6 48 50 60 46 214 49.1 50 60 47 217
208-3-60 17.6 136 27 2 7 1.1
11125 7.9 1 21.9 58.4 60 70 56 222 59.5 60 70 57 225
11625 12 1 33.3 72.6 80 80 69 234 73.7 80 80 70 236
None - - - 31.5 35 45 31 203 32.5 35 50 32 205
10625 6.5 1 15.6 51 60 60 49 218 52 60 60 50 221
A7 230-3-60 17.6 136 27 2.3 7.2 1
11125 10.5 1 25.3 63.1 70 70 60 228 64.1 70 70 61 230
(6)
11625 16 1 38.5 79.6 80 80 75 241 80.6 90 90 77 244
None - - - 15.5 20 20 15 100 16 20 20 16 101
10646 6 1 7.2 24.5 25 30 24 107 25 25 30 24 108
460-3-60 8.5 66.1 13 1.3 3.6 0.5
11146 11.5 1 13.8 32.8 35 35 31 114 33.3 35 35 32 115
11446 14 1 16.8 36.5 40 40 35 117 37 40 40 35 118
575-3-60 6.3 55.3 10 1 2.5 0.4 None - - - 11.4 15 15 11 75 11.8 15 15 12 76
None - - - 42.1 45 50 44 235 44.3 45 50 47 240
11725 12 1 33.3 83.7 90 90 83 268 85.9 90 90 85 273
208-3-60 13.8 83.1 22 13.8 83.1 22 2 7 1.1 12525 18.6 1 51.6 106.6 110 110 104 287 108.8 110 110 106 292
13225 24 1 66.6 125.4 150 150 121 302 127.6 150 150 124 307
14225 31.8 2 88.3 119.1 125 125 112 294 121.9 125 125 115 299
None - - - 42.9 45 50 45 238 44.9 45 50 48 242
11725 16 1 38.5 91 100 100 90 276 93 100 100 92 281
230-3-60 13.8 83.1 22 13.8 83.1 22 2.3 7.2 1 12525 24.8 1 59.7 117.5 125 125 114 298 119.5 125 125 116 302
08 13225 32 1 77 139.2 150 150 134 315 141.2 150 150 136 319
(7.5) 14225 42.4 2 102 136.5 150 150 124 306 139 150 150 126 311
None - - - 20.2 25 25 21 119 21.2 25 25 23 121
11746 16.5 1 19.8 45 45 45 44 139 46 50 50 45 141
460-3-60 6.2 41 10 6.2 41 10 1.3 3.6 0.5 12846 27.8 1 33.4 62 70 70 60 152 63 70 70 61 154
13346 33 1 39.7 69.8 70 70 67 158 70.8 80 80 68 161
14246 41.7 2 50.2 67.3 70 70 60 152 68.5 70 70 61 154
None - - - 15.5 20 20 16 88 16.3 20 20 17 90
575-3-60 4.9 33 8 4.9 33 8 1 2.5 0.4 11758 17 1 16.4 36 40 40 35 105 36.8 40 40 36 107
13458 34 1 32.7 56.4 60 60 54 121 57.2 60 60 55 123
Johnson Controls Ducted Systems 89
5147362-YTG-R-0323
XXEA7-12 standard indoor blower - without powered convenience outlet
Max
Min Min
Min Min Fuse2/
Max MCA1 Fuse2/
OD Electric Heat Fuse2/
2 Discon- 3 Breaker Discon-
Nominal Compressor 1 Compressor 2 Supply Pwr Pwr Field-installed Kit Fuse / w/Pwr Breaker nect
Size Fan MCA1 Breaker nect
3
Unit Blower Exh Conv 2EK045* 3 Breaker3 Exh Size Rating4/
(ton) Motors (Amps) Rating4 Size
Voltage Motor Motor Outlet Size (Amps w/ Pwr Exh
(each) Size w/
(Amps) ) Pwr Exh
(Amps) Pwr Exh
(Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA (Amps) FLA LRA
None - - - 43.6 45 50 46 265 45.8 50 50 49 270
11725 12 1 33.3 85.2 90 90 84 298 87.4 90 90 87 303
208-3-60 14.5 98 23 14.5 98 23 2 7 1.1 12525 18.6 1 51.6 108.1 110 110 105 317 110.3 125 125 108 322
13225 24 1 66.6 126.9 150 150 123 332 129.1 150 150 125 337
14225 31.8 2 88.3 119.1 125 125 114 324 121.9 125 125 116 329
None - - - 44.4 45 50 47 268 46.4 50 60 49 272
11725 16 1 38.5 92.5 100 100 91 306 94.5 100 100 93 311
230-3-60 14.5 98 23 14.5 98 23 2.3 7.2 1 12525 24.8 1 59.7 119 125 125 116 327 121 125 125 118 332
09 13225 32 1 77 140.7 150 150 135 345 142.7 150 150 138 349
(8.5) 14225 42.4 2 102 136.5 150 150 125 336 139 150 150 128 340
None - - - 20.4 25 25 22 147 21.4 25 25 23 149
11746 16.5 1 19.8 45.2 50 50 44 167 46.2 50 50 46 169
460-3-60 6.3 55 10 6.3 55 10 1.3 3.6 0.5 12846 27.8 1 33.4 62.2 70 70 60 180 63.2 70 70 61 182
13346 33 1 39.7 70 70 70 67 186 71 80 80 68 189
14246 41.7 2 50.2 67.3 70 70 60 180 68.5 70 70 61 182
None - - - 18 20 20 19 104 18.8 20 20 20 106
575-3-60 6 41 9 6 41 9 1 2.5 0.4 11758 17 1 16.4 38.5 40 40 38 121 39.3 40 40 39 123
13458 34 1 32.7 58.9 60 60 57 137 59.7 60 60 58 139
None - - - 47.5 50 60 50 392 49.7 50 60 53 397
11725 12 1 33.3 89.1 90 90 88 425 91.3 100 100 91 430
208-3-60 15.4 155 24 15.4 155 24 5.8 7 1.1 12525 18.6 1 51.6 112 125 125 109 444 114.2 125 125 112 449
13225 24 1 66.6 130.8 150 150 127 459 133 150 150 129 464
14225 31.8 2 88.3 121.4 125 125 118 451 123.6 125 125 121 456
None - - - 47.1 50 60 50 391 49.1 50 60 52 395
11725 16 1 38.5 95.2 100 100 94 429 97.2 100 100 96 434
230-3-60 15.4 155 24 15.4 155 24 5.2 7.2 1 12525 24.8 1 59.7 121.7 125 125 118 451 123.7 125 125 121 455
12 13225 32 1 77 143.4 150 150 138 468 145.4 150 150 141 472
(10) 14225 42.4 2 102 136.5 150 150 128 459 139 150 150 130 464
None - - - 23.8 25 30 25 166 24.8 25 30 26 168
11746 16.5 1 19.8 48.6 50 50 48 186 49.6 50 50 49 188
460-3-60 7.7 62 12 7.7 62 12 2.9 3.6 0.5 12846 27.8 1 33.4 65.6 70 70 64 199 66.6 70 70 65 202
13346 33 1 39.7 73.4 80 80 71 206 74.4 80 80 72 208
14246 41.7 2 50.2 67.3 70 70 64 199 68.5 70 70 65 202
None - - - 18.2 20 20 19 125 19 20 20 20 126
575-3-60 6 48 9 6 48 9 2.2 2.5 0.4 11758 17 1 16.4 38.7 40 40 38 141 39.5 40 40 39 143
13458 34 1 32.7 59.1 60 60 57 157 59.9 60 60 58 159
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field-installed
electric heat kits may exceed the factory-installed disconnect amperage rating.
90 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XXEA7-12 standard indoor blower - with powered convenience outlet
Min Max Min
Min Max Min Fuse2/ Fuse2/ Discon-
OD Electric Heat MCA1
Nominal Supply Pwr Pwr 2
Fuse / 2
Fuse / Discon- Breaker3 Breaker3 nect
Size Compressor 1 Compressor 2 Fan Field-installed KitMCA1 w/Pwr
Unit Blower Exh Conv Breaker3 Breaker3 nect Size Size
(ton) Motors 2EK045* (Amps) 4 Exh Rating4/
Voltage Motor Motor Outlet Size Size Rating w/ w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
With VFD
None - - - 35.3 40 50 36 205 36.4 40 50 37 207
10625 4.9 1 13.6 52.3 60 60 51 218 53.4 60 60 52 221
208-3-60 17.6 136 27 2 7 1.1 8.6
11125 7.9 1 21.9 62.7 70 70 61 227 63.8 70 70 62 229
11625 12 1 33.3 76.9 80 80 74 238 78 80 80 75 241
None - - - 35.8 40 50 36 207 36.8 40 50 37 209
10625 6.5 1 15.6 55.3 60 60 54 223 56.3 60 70 55 225
A7 230-3-60 17.6 136 27 2.3 7.2 1 8.6
11125 10.5 1 25.3 67.4 70 70 65 232 68.4 70 70 66 235
(6)
11625 16 1 38.5 83.9 90 90 80 246 84.9 90 90 82 248
None - - - 17.7 20 25 18 102 18.2 20 25 19 103
10646 6 1 7.2 26.7 30 30 26 109 27.2 30 30 27 110
460-3-60 8.5 66.1 13 1.3 3.6 0.5 8.6
11146 11.5 1 13.8 35 35 40 34 116 35.5 40 40 34 117
11446 14 1 16.8 38.7 40 40 37 119 39.2 40 40 38 120
575-3-60 6.3 55.3 10 1 2.5 0.4 8.6 None - - - 13.1 15 15 13 77 13.5 15 15 14 78
None - - - 46.4 50 60 49 239 48.6 50 60 52 244
11725 12 1 33.3 88 90 90 88 273 90.2 100 100 90 278
208-3-60 13.8 83.1 22 13.8 83.1 22 2 7 1.1 8.6 12525 18.6 1 51.6 110.9 125 125 109 291 113.1 125 125 111 296
13225 24 1 66.6 129.7 150 150 126 306 131.9 150 150 128 311
14225 31.8 2 88.3 124.5 125 125 117 299 127.3 150 150 120 304
None - - - 47.2 50 60 50 242 49.2 50 60 53 247
11725 16 1 38.5 95.3 100 100 95 281 97.3 100 100 97 285
230-3-60 13.8 83.1 22 13.8 83.1 22 2.3 7.2 1 8.6 12525 24.8 1 59.7 121.8 125 125 119 302 123.8 125 125 121 306
08 13225 32 1 77 143.5 150 150 139 319 145.5 150 150 141 324
(7.5) 14225 42.4 2 102 141.9 150 150 129 310 144.4 150 150 131 315
None - - - 22.4 25 25 24 121 23.4 25 25 25 123
11746 16.5 1 19.8 47.2 50 50 47 141 48.2 50 50 48 143
460-3-60 6.2 41 10 6.2 41 10 1.3 3.6 0.5 8.6 12846 27.8 1 33.4 64.2 70 70 62 154 65.2 70 70 63 156
13346 33 1 39.7 72 80 80 70 161 73 80 80 71 163
14246 41.7 2 50.2 69.9 70 70 62 154 71.2 80 80 63 156
None - - - 17.2 20 20 18 90 18 20 20 19 92
575-3-60 4.9 33 8 4.9 33 8 1 2.5 0.4 8.6 11758 17 1 16.4 37.7 40 40 37 106 38.5 40 40 38 108
13458 34 1 32.7 58.1 60 60 56 123 58.9 60 60 57 125
None - - - 47.9 50 60 51 269 50.1 60 60 53 274
11725 12 1 33.3 89.5 90 90 89 303 91.7 100 100 92 308
208-3-60 14.5 98 23 14.5 98 23 2 7 1.1 8.6 12525 18.6 1 51.6 112.4 125 125 110 321 114.6 125 125 113 326
13225 24 1 66.6 131.2 150 150 128 336 133.4 150 150 130 341
14225 31.8 2 88.3 124.5 125 125 119 328 127.3 150 150 121 333
None - - - 48.7 50 60 52 272 50.7 60 60 54 277
11725 16 1 38.5 96.8 100 100 96 310 98.8 100 100 98 315
230-3-60 14.5 98 23 14.5 98 23 2.3 7.2 1 8.6 12525 24.8 1 59.7 123.3 125 125 121 332 125.3 150 150 123 336
09 13225 32 1 77 145 150 150 140 349 147 150 150 143 354
(8.5) 14225 42.4 2 102 141.9 150 150 130 340 144.4 150 150 132 345
None - - - 22.6 25 25 24 149 23.6 25 25 25 151
11746 16.5 1 19.8 47.4 50 50 47 169 48.4 50 50 48 171
460-3-60 6.3 55 10 6.3 55 10 1.3 3.6 0.5 8.6 12846 27.8 1 33.4 64.4 70 70 63 182 65.4 70 70 64 184
13346 33 1 39.7 72.2 80 80 70 189 73.2 80 80 71 191
14246 41.7 2 50.2 69.9 70 70 63 182 71.2 80 80 64 184
None - - - 19.7 20 25 21 106 20.5 25 25 22 108
575-3-60 6 41 9 6 41 9 1 2.5 0.4 8.6 11758 17 1 16.4 40.2 45 45 40 122 41 45 45 41 124
13458 34 1 32.7 60.6 70 70 59 139 61.4 70 70 59 141
Johnson Controls Ducted Systems 91
5147362-YTG-R-0323
XXEA7-12 standard indoor blower - with powered convenience outlet (Continued)
Min Max Min
Min Max Min Fuse2/ Fuse2/ Discon-
OD Electric Heat MCA1
Nominal Supply Pwr Pwr 2
Fuse / 2
Fuse / Discon- Breaker3 Breaker3 nect
Size Compressor 1 Compressor 2 Fan Field-installed KitMCA1 w/Pwr
Unit Blower Exh Conv Breaker3 Breaker3 nect Size Size
(ton) Motors 2EK045* (Amps) 4 Exh Rating4/
Voltage Motor Motor Outlet Size Size Rating w/ w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
None - - - 51.8 60 60 55 396 54 60 60 58 401
11725 12 1 33.3 93.4 100 100 93 430 95.6 100 100 96 435
208-3-60 15.4 155 24 15.4 155 24 5.8 7 1.1 8.6 12525 18.6 1 51.6 116.3 125 125 114 448 118.5 125 125 117 453
13225 24 1 66.6 135.1 150 150 132 463 137.3 150 150 134 468
14225 31.8 2 88.3 125.7 150 150 123 456 127.9 150 150 126 461
None - - - 51.4 60 60 55 395 53.4 60 60 57 400
11725 16 1 38.5 99.5 100 100 99 434 101.5 110 110 101 438
230-3-60 15.4 155 24 15.4 155 24 5.2 7.2 1 8.6 12525 24.8 1 59.7 126 150 150 123 455 128 150 150 126 459
12 13225 32 1 77 147.7 150 150 143 472 149.7 150 150 145 477
(10) 14225 42.4 2 102 141.9 150 150 133 463 144.4 150 150 135 468
None - - - 26 30 30 28 168 27 30 30 29 170
11746 16.5 1 19.8 50.8 60 60 50 188 51.8 60 60 52 190
460-3-60 7.7 62 12 7.7 62 12 2.9 3.6 0.5 8.6 12846 27.8 1 33.4 67.8 70 70 66 201 68.8 70 70 67 204
13346 33 1 39.7 75.6 80 80 73 208 76.6 80 80 75 210
14246 41.7 2 50.2 69.9 70 70 66 201 71.2 80 80 67 204
None - - - 19.9 20 25 21 126 20.7 25 25 22 128
575-3-60 6 47.8 9 6 47.8 9 2.2 2.5 0.4 8.6 11758 17 1 16.4 40.4 45 45 40 143 41.2 45 45 41 145
13458 34 1 32.7 60.8 70 70 59 159 61.6 70 70 60 161
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field-installed
electric heat kits may exceed the factory-installed disconnect amperage rating.
92 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XXEA7-12 Medium Indoor Blower - Without Powered Convenience Outlet
Min Max Min
Min Max Min Fuse2/ Fuse2/ Discon-
OD Electric Heat MCA1
Nominal Supply Pwr Pwr 2
Fuse / 2
Fuse / Discon- Breaker3 Breaker3 nect
Size Compressor 1 Compressor 2 Fan Field-installed KitMCA1 w/Pwr
Unit Blower Exh Conv Breaker3 Breaker3 nect Size Size
(ton) Motors 2EK045* (Amps) 4 Exh Rating4/
Voltage Motor Motor Outlet Size Size Rating w/ w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
With VFD
None - - - 32.9 35 50 33 217 34 35 50 34 220
10625 4.9 1 13.6 49.9 50 60 48 231 51 60 60 50 233
208-3-60 17.6 136 27 2 8.9 1.1
11125 7.9 1 21.9 60.3 70 70 58 239 61.4 70 70 59 242
11625 12 1 33.3 74.5 80 80 71 251 75.6 80 80 72 253
None - - - 32.5 35 50 32 220 33.5 35 50 33 222
10625 6.5 1 15.6 52 60 60 50 236 53 60 60 51 238
A7 230-3-60 17.6 136 27 2.3 8.2 1
11125 10.5 1 25.3 64.1 70 70 61 245 65.1 70 70 63 248
(6)
11625 16 1 38.5 80.6 90 90 77 258 81.6 90 90 78 261
None - - - 16 20 20 16 104 16.5 20 20 17 105
10646 6 1 7.2 25 25 30 24 111 25.5 30 30 25 112
460-3-60 8.5 66.1 13 1.3 4.1 0.5
11146 11.5 1 13.8 33.3 35 35 32 117 33.8 35 35 32 118
11446 14 1 16.8 37 40 40 35 120 37.5 40 40 36 121
575-3-60 6.3 55.3 10 1 3.2 0.4 None - - - 12.1 15 15 12 84 12.5 15 15 13 85
None - - - 42.1 45 50 44 235 44.3 45 50 47 240
11725 12 1 33.3 83.7 90 90 83 268 85.9 90 90 85 273
208-3-60 13.8 83.1 22 13.8 83.1 22 2 7 1.1 12525 18.6 1 51.6 106.6 110 110 104 287 108.8 110 110 106 292
13225 24 1 66.6 125.4 150 150 121 302 127.6 150 150 124 307
14225 31.8 2 88.3 119.1 125 125 112 294 121.9 125 125 115 299
None - - - 42.9 45 50 45 238 44.9 45 50 48 242
11725 16 1 38.5 91 100 100 90 276 93 100 100 92 281
230-3-60 13.8 83.1 22 13.8 83.1 22 2.3 7.2 1 12525 24.8 1 59.7 117.5 125 125 114 298 119.5 125 125 116 302
08 13225 32 1 77 139.2 150 150 134 315 141.2 150 150 136 319
(7.5) 14225 42.4 2 102 136.5 150 150 124 306 139 150 150 126 311
None - - - 20.2 25 25 21 119 21.2 25 25 23 121
11746 16.5 1 19.8 45 45 45 44 139 46 50 50 45 141
460-3-60 6.2 41 10 6.2 41 10 1.3 3.6 0.5 12846 27.8 1 33.4 62 70 70 60 152 63 70 70 61 154
13346 33 1 39.7 69.8 70 70 67 158 70.8 80 80 68 161
14246 41.7 2 50.2 67.3 70 70 60 152 68.5 70 70 61 154
None - - - 15.5 20 20 16 88 16.3 20 20 17 90
575-3-60 4.9 33 8 4.9 33 8 1 2.5 0.4 11758 17 1 16.4 36 40 40 35 105 36.8 40 40 36 107
13458 34 1 32.7 56.4 60 60 54 121 57.2 60 60 55 123
None - - - 43.6 45 50 46 265 45.8 50 50 49 270
11725 12 1 33.3 85.2 90 90 84 298 87.4 90 90 87 303
208-3-60 14.5 98 23 14.5 98 23 2 7 1.1 12525 18.6 1 51.6 108.1 110 110 105 317 110.3 125 125 108 322
13225 24 1 66.6 126.9 150 150 123 332 129.1 150 150 125 337
14225 31.8 2 88.3 119.1 125 125 114 324 121.9 125 125 116 329
None - - - 44.4 45 50 47 268 46.4 50 60 49 272
11725 16 1 38.5 92.5 100 100 91 306 94.5 100 100 93 311
230-3-60 14.5 98 23 14.5 98 23 2.3 7.2 1 12525 24.8 1 59.7 119 125 125 116 327 121 125 125 118 332
09 13225 32 1 77 140.7 150 150 135 345 142.7 150 150 138 349
(8.5) 14225 42.4 2 102 136.5 150 150 125 336 139 150 150 128 340
None - - - 20.4 25 25 22 147 21.4 25 25 23 149
11746 16.5 1 19.8 45.2 50 50 44 167 46.2 50 50 46 169
460-3-60 6.3 55 10 6.3 55 10 1.3 3.6 0.5 12846 27.8 1 33.4 62.2 70 70 60 180 63.2 70 70 61 182
13346 33 1 39.7 70 70 70 67 186 71 80 80 68 189
14246 41.7 2 50.2 67.3 70 70 60 180 68.5 70 70 61 182
None - - - 18 20 20 19 104 18.8 20 20 20 106
575-3-60 6 41 9 6 41 9 1 2.5 0.4 11758 17 1 16.4 38.5 40 40 38 121 39.3 40 40 39 123
13458 34 1 32.7 58.9 60 60 57 137 59.7 60 60 58 139
Johnson Controls Ducted Systems 93
5147362-YTG-R-0323
XXEA7-12 Medium Indoor Blower - Without Powered Convenience Outlet (Continued)
Min Max Min
Min Max Min Fuse2/ Fuse2/ Discon-
OD Electric Heat MCA1
Nominal Supply Pwr Pwr 2
Fuse / 2
Fuse / Discon- Breaker3 Breaker3 nect
Size Compressor 1 Compressor 2 Fan Field-installed KitMCA1 w/Pwr
Unit Blower Exh Conv Breaker3 Breaker3 nect Size Size
(ton) Motors 2EK045* (Amps) 4 Exh Rating4/
Voltage Motor Motor Outlet Size Size Rating w/ w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
None - - - 50.4 60 60 53 405 52.6 60 60 56 410
11725 12 1 33.3 92 100 100 92 438 94.2 100 100 94 443
208-3-60 15.4 155 24 15.4 155 24 5.8 9.9 1.1 12525 18.6 1 51.6 114.9 125 125 113 456 117.1 125 125 115 461
13225 24 1 66.6 133.7 150 150 130 471 135.9 150 150 133 476
14225 31.8 2 88.3 124.3 125 125 121 464 126.5 150 150 124 469
None - - - 49.3 50 60 52 410 51.3 60 60 55 414
11725 16 1 38.5 97.4 100 100 96 448 99.4 100 100 99 453
230-3-60 15.4 155 24 15.4 155 24 5.2 9.4 1 12525 24.8 1 59.7 123.9 125 125 121 469 125.9 150 150 123 474
12 13225 32 1 77 145.6 150 150 141 487 147.6 150 150 143 491
(10) 14225 42.4 2 102 139.3 150 150 131 478 141.8 150 150 133 482
None - - - 24.9 25 30 26 175 25.9 30 30 28 178
11746 16.5 1 19.8 49.7 50 50 49 195 50.7 60 60 50 197
460-3-60 7.7 62 12 7.7 62 12 2.9 4.7 0.5 12846 27.8 1 33.4 66.7 70 70 65 209 67.7 70 70 66 211
13346 33 1 39.7 74.5 80 80 72 215 75.5 80 80 73 217
14246 41.7 2 50.2 68.6 70 70 65 209 69.9 70 70 66 211
None - - - 20 25 25 21 147 20.8 25 25 22 149
575-3-60 6 47.8 9 6 47.8 9 2.2 4.3 0.4 11758 17 1 16.4 40.5 45 45 40 163 41.3 45 45 41 165
13458 34 1 32.7 60.9 70 70 59 180 61.7 70 70 60 181
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field-installed
electric heat kits may exceed the factory-installed disconnect amperage rating.
94 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XXEA7-12 Medium Indoor Blower - With Powered Convenience Outlet
Min Max Min
Min Max Min Fuse2/ Fuse2/ Discon-
OD Electric Heat MCA1
Nominal Supply Pwr Pwr 2
Fuse / 2
Fuse / Discon- Breaker3 Breaker3 nect
Size Compressor 1 Compressor 2 Fan Field-installed KitMCA1 w/Pwr
Unit Blower Exh Conv Breaker3 Breaker3 nect Size Size
(Tons) Motors 2EK045* (Amps) 4 Exh Rating4/
Voltage Motor Motor Outlet Size Size Rating w/ w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
With VFD
None - - - 37.2 40 50 38 222 38.3 40 50 39 224
10625 4.9 1 13.6 54.2 60 60 53 235 55.3 60 60 55 238
208-3-60 17.6 136 27 2 8.9 1.1 8.6
11125 7.9 1 21.9 64.6 70 70 63 243 65.7 70 70 64 246
11625 12 1 33.3 78.8 80 80 76 255 79.9 80 80 77 257
None - - - 36.8 40 50 37 224 37.8 40 50 38 227
10625 6.5 1 15.6 56.3 60 70 55 240 57.3 60 70 56 242
A7 230-3-60 17.6 136 27 2.3 8.2 1 8.6
11125 10.5 1 25.3 68.4 70 70 66 250 69.4 70 80 68 252
(6)
11625 16 1 38.5 84.9 90 90 82 263 85.9 90 90 83 265
None - - - 18.2 20 25 19 106 18.7 20 25 19 107
10646 6 1 7.2 27.2 30 30 27 113 27.7 30 30 27 114
460-3-60 8.5 66.1 13 1.3 4.1 0.5 8.6
11146 11.5 1 13.8 35.5 40 40 34 119 36 40 40 35 121
11446 14 1 16.8 39.2 40 40 38 122 39.7 40 40 38 124
575-3-60 6.3 55.3 10 1 3.2 0.4 8.6 None - - - 13.8 15 20 14 85 14.2 15 20 14 86
None - - - 46.4 50 60 49 239 48.6 50 60 52 244
11725 12 1 33.3 88 90 90 88 273 90.2 100 100 90 278
208-3-60 13.8 83.1 22 13.8 83.1 22 2 7 1.1 8.6 12525 18.6 1 51.6 110.9 125 125 109 291 113.1 125 125 111 296
13225 24 1 66.6 129.7 150 150 126 306 131.9 150 150 128 311
14225 31.8 2 88.3 124.5 125 125 117 299 127.3 150 150 120 304
None - - - 47.2 50 60 50 242 49.2 50 60 53 247
11725 16 1 38.5 95.3 100 100 95 281 97.3 100 100 97 285
230-3-60 13.8 83.1 22 13.8 83.1 22 2.3 7.2 1 8.6 12525 24.8 1 59.7 121.8 125 125 119 302 123.8 125 125 121 306
08 13225 32 1 77 143.5 150 150 139 319 145.5 150 150 141 324
(7.5) 14225 42.4 2 102 141.9 150 150 129 310 144.4 150 150 131 315
None - - - 22.4 25 25 24 121 23.4 25 25 25 123
11746 16.5 1 19.8 47.2 50 50 47 141 48.2 50 50 48 143
460-3-60 6.2 41 10 6.2 41 10 1.3 3.6 0.5 8.6 12846 27.8 1 33.4 64.2 70 70 62 154 65.2 70 70 63 156
13346 33 1 39.7 72 80 80 70 161 73 80 80 71 163
14246 41.7 2 50.2 69.9 70 70 62 154 71.2 80 80 63 156
None - - - 17.2 20 20 18 90 18 20 20 19 92
575-3-60 4.9 33 8 4.9 33 8 1 2.5 0.4 8.6 11758 17 1 16.4 37.7 40 40 37 106 38.5 40 40 38 108
13458 34 1 32.7 58.1 60 60 56 123 58.9 60 60 57 125
None - - - 47.9 50 60 51 269 50.1 60 60 53 274
11725 12 1 33.3 89.5 90 90 89 303 91.7 100 100 92 308
208-3-60 14.5 98 23 14.5 98 23 2 7 1.1 8.6 12525 18.6 1 51.6 112.4 125 125 110 321 114.6 125 125 113 326
13225 24 1 66.6 131.2 150 150 128 336 133.4 150 150 130 341
14225 31.8 2 88.3 124.5 125 125 119 328 127.3 150 150 121 333
None - - - 48.7 50 60 52 272 50.7 60 60 54 277
11725 16 1 38.5 96.8 100 100 96 310 98.8 100 100 98 315
230-3-60 14.5 98 23 14.5 98 23 2.3 7.2 1 8.6 12525 24.8 1 59.7 123.3 125 125 121 332 125.3 150 150 123 336
09 13225 32 1 77 145 150 150 140 349 147 150 150 143 354
(8.5) 14225 42.4 2 102 141.9 150 150 130 340 144.4 150 150 132 345
None - - - 22.6 25 25 24 149 23.6 25 25 25 151
11746 16.5 1 19.8 47.4 50 50 47 169 48.4 50 50 48 171
460-3-60 6.3 55 10 6.3 55 10 1.3 3.6 0.5 8.6 12846 27.8 1 33.4 64.4 70 70 63 182 65.4 70 70 64 184
13346 33 1 39.7 72.2 80 80 70 189 73.2 80 80 71 191
14246 41.7 2 50.2 69.9 70 70 63 182 71.2 80 80 64 184
None - - - 19.7 20 25 21 106 20.5 25 25 22 108
575-3-60 6 41 9 6 41 9 1 2.5 0.4 8.6 11758 17 1 16.4 40.2 45 45 40 122 41 45 45 41 124
13458 34 1 32.7 60.6 70 70 59 139 61.4 70 70 59 141
Johnson Controls Ducted Systems 95
5147362-YTG-R-0323
XXEA7-12 Medium Indoor Blower - With Powered Convenience Outlet (Continued)
Min Max Min
Min Max Min Fuse2/ Fuse2/ Discon-
OD Electric Heat MCA1
Nominal Supply Pwr Pwr 2
Fuse / 2
Fuse / Discon- Breaker3 Breaker3 nect
Size Compressor 1 Compressor 2 Fan Field-installed KitMCA1 w/Pwr
Unit Blower Exh Conv Breaker3 Breaker3 nect Size Size
(Tons) Motors 2EK045* (Amps) 4 Exh Rating4/
Voltage Motor Motor Outlet Size Size Rating w/ w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
None - - - 54.7 60 70 58 409 56.9 60 70 61 414
11725 12 1 33.3 96.3 100 100 97 442 98.5 100 100 99 447
208-3-60 15.4 155 24 15.4 155 24 5.8 9.9 1.1 8.6 12525 18.6 1 51.6 119.2 125 125 118 460 121.4 125 125 120 465
13225 24 1 66.6 138 150 150 135 475 140.2 150 150 138 480
14225 31.8 2 88.3 128.6 150 150 126 468 130.9 150 150 129 473
None - - - 53.6 60 60 57 414 55.6 60 70 59 419
11725 16 1 38.5 101.7 110 110 101 452 103.7 110 110 104 457
230-3-60 15.4 155 24 15.4 155 24 5.2 9.4 1 8.6 12525 24.8 1 59.7 128.2 150 150 126 474 130.2 150 150 128 478
12 13225 32 1 77 149.9 150 150 146 491 151.9 175 175 148 496
(10) 14225 42.4 2 102 144.6 150 150 135 482 147.1 150 150 138 487
None - - - 27.1 30 30 29 177 28.1 30 30 30 180
11746 16.5 1 19.8 51.9 60 60 52 197 52.9 60 60 53 199
460-3-60 7.7 62 12 7.7 62 12 2.9 4.7 0.5 8.6 12846 27.8 1 33.4 68.9 70 70 67 211 69.9 70 70 69 213
13346 33 1 39.7 76.7 80 80 75 217 77.7 80 80 76 219
14246 41.7 2 50.2 71.3 80 80 67 211 72.6 80 80 69 213
None - - - 21.7 25 25 23 149 22.5 25 25 24 150
575-3-60 6 47.8 9 6 47.8 9 2.2 4.3 0.4 8.6 11758 17 1 16.4 42.2 45 45 42 165 43 45 45 43 167
13458 34 1 32.7 62.6 70 70 61 181 63.4 70 70 62 183
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field-installed
electric heat kits may exceed the factory-installed disconnect amperage rating.
96 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XXEA7-12 high indoor blower - without powered convenience outlet
Min Max Min
Min Max Min Fuse2/ Fuse2/ Discon-
OD Electric Heat MCA1
Nominal Supply Pwr Pwr 2
Fuse / 2
Fuse / Discon- Breaker3 Breaker3 nect
Size Compressor 1 Compressor 2 Fan Field-installed KitMCA1 w/Pwr
Unit Blower Exh Conv Breaker3 Breaker3 nect Size Size
(ton) Motors 2EK045* (Amps) 4 Exh Rating4/
Voltage Motor Motor Outlet Size Size Rating w/ w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
With VFD
None - - - 33.9 35 50 34 213 35 35 50 35 215
10625 4.9 1 13.6 50.9 60 60 50 227 52 60 60 51 229
208-3-60 17.6 136 27 2 9.9 1.1
11125 7.9 1 21.9 61.3 70 70 59 235 62.4 70 70 60 237
11625 12 1 33.3 75.5 80 80 72 246 76.6 80 80 73 249
None - - - 33.7 35 50 34 222 34.7 35 50 35 224
10625 6.5 1 15.6 53.2 60 60 52 237 54.2 60 60 53 239
A7 230-3-60 17.6 136 27 2.3 9.4 1
11125 10.5 1 25.3 65.3 70 70 63 247 66.3 70 70 64 249
(6)
11625 16 1 38.5 81.8 90 90 78 260 82.8 90 90 79 262
None - - - 16.6 20 25 17 109 17.1 20 25 17 110
10646 6 1 7.2 25.6 30 30 25 117 26.1 30 30 26 118
460-3-60 8.5 66.1 13 1.3 4.7 0.5
11146 11.5 1 13.8 33.9 35 35 33 123 34.4 35 35 33 124
11446 14 1 16.8 37.6 40 40 36 126 38.1 40 40 37 127
575-3-60 6.3 55.3 10 1 4.3 0.4 None - - - 13.2 15 15 13 98 13.6 15 15 14 99
None - - - 45 45 50 48 248 47.2 50 50 50 253
11725 12 1 33.3 86.6 90 90 86 281 88.8 90 90 89 286
208-3-60 13.8 83.1 22 13.8 83.1 22 2 9.9 1.1 12525 18.6 1 51.6 109.5 110 110 107 299 111.7 125 125 110 304
13225 24 1 66.6 128.3 150 150 124 314 130.5 150 150 127 319
14225 31.8 2 88.3 122.8 125 125 116 307 125.5 150 150 118 312
None - - - 45.1 50 50 48 257 47.1 50 60 50 261
11725 16 1 38.5 93.2 100 100 92 295 95.2 100 100 94 300
230-3-60 13.8 83.1 22 13.8 83.1 22 2.3 9.4 1 12525 24.8 1 59.7 119.7 125 125 116 316 121.7 125 125 119 321
08 13225 32 1 77 141.4 150 150 136 334 143.4 150 150 139 338
(7.5) 14225 42.4 2 102 139.3 150 150 126 325 141.8 150 150 128 329
None - - - 21.3 25 25 23 128 22.3 25 25 24 130
11746 16.5 1 19.8 46.1 50 50 45 148 47.1 50 50 47 150
460-3-60 6.2 41 10 6.2 41 10 1.3 4.7 0.5 12846 27.8 1 33.4 63.1 70 70 61 162 64.1 70 70 62 164
13346 33 1 39.7 70.9 80 80 68 168 71.9 80 80 69 170
14246 41.7 2 50.2 68.6 70 70 61 162 69.9 70 70 62 164
None - - - 17.3 20 20 19 111 18.1 20 20 19 112
575-3-60 4.9 33 8 4.9 33 8 1 4.3 0.4 11758 17 1 16.4 37.8 40 40 37 127 38.6 40 40 38 129
13458 34 1 32.7 58.2 60 60 56 143 59 60 60 57 145
None - - - 46.5 50 60 49 277 48.7 50 60 52 282
11725 12 1 33.3 88.1 90 90 88 311 90.3 100 100 90 316
208-3-60 14.5 98 23 14.5 98 23 2 9.9 1.1 12525 18.6 1 51.6 111 125 125 109 329 113.2 125 125 111 334
13225 24 1 66.6 129.8 150 150 126 344 132 150 150 128 349
14225 31.8 2 88.3 122.8 125 125 117 336 125.5 150 150 120 341
None - - - 46.6 50 60 49 286 48.6 50 60 52 291
11725 16 1 38.5 94.7 100 100 94 325 96.7 100 100 96 330
230-3-60 14.5 98 23 14.5 98 23 2.3 9.4 1 12525 24.8 1 59.7 121.2 125 125 118 346 123.2 125 125 120 351
09 13225 32 1 77 142.9 150 150 138 363 144.9 150 150 140 368
(8.5) 14225 42.4 2 102 139.3 150 150 128 355 141.8 150 150 130 359
None - - - 21.5 25 25 23 156 22.5 25 25 24 158
11746 16.5 1 19.8 46.3 50 50 46 176 47.3 50 50 47 178
460-3-60 6.3 55 10 6.3 55 10 1.3 4.7 0.5 12846 27.8 1 33.4 63.3 70 70 61 190 64.3 70 70 62 192
13346 33 1 39.7 71.1 80 80 69 196 72.1 80 80 70 198
14246 41.7 2 50.2 68.6 70 70 61 190 69.9 70 70 62 192
None - - - 19.8 20 25 21 127 20.6 25 25 22 128
575-3-60 6 41 9 6 41 9 1 4.3 0.4 11758 17 1 16.4 40.3 45 45 40 143 41.1 45 45 41 145
13458 34 1 32.7 60.7 70 70 59 159 61.5 70 70 60 161
Johnson Controls Ducted Systems 97
5147362-YTG-R-0323
XXEA7-12 high indoor blower - without powered convenience outlet (Continued)
Min Max Min
Min Max Min Fuse2/ Fuse2/ Discon-
OD Electric Heat MCA1
Nominal Supply Pwr Pwr 2
Fuse / 2
Fuse / Discon- Breaker3 Breaker3 nect
Size Compressor 1 Compressor 2 Fan Field-installed KitMCA1 w/Pwr
Unit Blower Exh Conv Breaker3 Breaker3 nect Size Size
(ton) Motors 2EK045* (Amps) 4 Exh Rating4/
Voltage Motor Motor Outlet Size Size Rating w/ w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
None - - - 54 60 60 58 435 56.2 60 70 60 440
11725 12 1 33.3 95.6 100 100 96 468 97.8 100 100 98 473
208-3-60 15.4 155 24 15.4 155 24 5.8 13.5 1.1 12525 18.6 1 51.6 118.5 125 125 117 486 120.7 125 125 119 491
13225 24 1 66.6 137.3 150 150 134 501 139.5 150 150 137 506
14225 31.8 2 88.3 127.9 150 150 126 494 130.1 150 150 128 499
None - - - 53.3 60 60 57 431 55.3 60 70 59 436
11725 16 1 38.5 101.4 110 110 101 470 103.4 110 110 103 474
230-3-60 15.4 155 24 15.4 155 24 5.2 13.4 1 12525 24.8 1 59.7 127.9 150 150 125 491 129.9 150 150 128 495
12 13225 32 1 77 149.6 150 150 145 508 151.6 175 175 148 513
(10) 14225 42.4 2 102 144.3 150 150 135 499 146.8 150 150 137 504
None - - - 26.9 30 30 29 186 27.9 30 30 30 188
11746 16.5 1 19.8 51.7 60 60 52 206 52.7 60 60 53 208
460-3-60 7.7 62 12 7.7 62 12 2.9 6.7 0.5 12846 27.8 1 33.4 68.7 70 70 67 219 69.7 70 70 68 222
13346 33 1 39.7 76.5 80 80 74 226 77.5 80 80 76 228
14246 41.7 2 50.2 71.1 80 80 67 219 72.4 80 80 68 222
None - - - 21.1 25 25 23 147 21.9 25 25 23 149
575-3-60 6 47.8 9 6 47.8 9 2.2 5.4 0.4 11758 17 1 16.4 41.6 45 45 41 163 42.4 45 45 42 165
13458 34 1 32.7 62 70 70 60 180 62.8 70 70 61 181
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field-installed
electric heat kits may exceed the factory-installed disconnect amperage rating.
98 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XXEA7-12 high indoor blower - with powered convenience outlet
Min Max Min
Min Max Min Fuse2/ Fuse2/ Discon-
OD Electric Heat MCA1
Nominal Supply Pwr Pwr 2
Fuse / 2
Fuse / Discon- Breaker3 Breaker3 nect
Size Compressor 1 Compressor 2 Fan Field-installed KitMCA1 w/Pwr
Unit Blower Exh Conv Breaker3 Breaker3 nect Size Size
(ton) Motors 2EK045* (Amps) 4 Exh Rating4/
Voltage Motor Motor Outlet Size Size Rating w/ w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
With VFD
None - - - 38.2 40 50 39 217 39.3 40 50 40 220
10625 4.9 1 13.6 55.2 60 60 55 231 56.3 60 70 56 233
208-3-60 17.6 136 27 2 9.9 1.1 8.6
11125 7.9 1 21.9 65.6 70 70 64 239 66.7 70 70 65 242
11625 12 1 33.3 79.8 80 80 77 251 80.9 90 90 78 253
None - - - 38 40 50 39 226 39 40 50 40 228
10625 6.5 1 15.6 57.5 60 70 57 241 58.5 60 70 58 244
A7 230-3-60 17.6 136 27 2.3 9.4 1 8.6
11125 10.5 1 25.3 69.6 70 80 68 251 70.6 80 80 69 253
(6)
11625 16 1 38.5 86.1 90 90 83 264 87.1 90 90 84 267
None - - - 18.8 20 25 19 111 19.3 20 25 20 113
10646 6 1 7.2 27.8 30 30 27 119 28.3 30 30 28 120
460-3-60 8.5 66.1 13 1.3 4.7 0.5 8.6
11146 11.5 1 13.8 36.1 40 40 35 125 36.6 40 40 36 126
11446 14 1 16.8 39.8 40 40 39 128 40.3 45 45 39 129
575-3-60 6.3 55.3 10 1 4.3 0.4 8.6 None - - - 14.9 15 20 15 99 15.3 20 20 16 100
None - - - 49.3 50 60 53 252 51.5 60 60 55 257
11725 12 1 33.3 90.9 100 100 91 285 93.1 100 100 93 290
208-3-60 13.8 83.1 22 13.8 83.1 22 2 9.9 1.1 8.6 12525 18.6 1 51.6 113.8 125 125 112 303 116 125 125 115 308
13225 24 1 66.6 132.6 150 150 129 318 134.8 150 150 132 323
14225 31.8 2 88.3 128.1 150 150 121 311 130.9 150 150 123 316
None - - - 49.4 50 60 53 261 51.4 60 60 55 266
11725 16 1 38.5 97.5 100 100 97 299 99.5 100 100 99 304
230-3-60 13.8 83.1 22 13.8 83.1 22 2.3 9.4 1 8.6 12525 24.8 1 59.7 124 125 125 121 321 126 150 150 124 325
08 13225 32 1 77 145.7 150 150 141 338 147.7 150 150 144 343
(7.5) 14225 42.4 2 102 144.6 150 150 131 329 147.1 150 150 133 334
None - - - 23.5 25 25 25 130 24.5 25 25 26 132
11746 16.5 1 19.8 48.3 50 50 48 150 49.3 50 50 49 152
460-3-60 6.2 41 10 6.2 41 10 1.3 4.7 0.5 8.6 12846 27.8 1 33.4 65.3 70 70 64 164 66.3 70 70 65 166
13346 33 1 39.7 73.1 80 80 71 170 74.1 80 80 72 172
14246 41.7 2 50.2 71.3 80 80 64 164 72.6 80 80 65 166
None - - - 19 20 20 20 112 19.8 20 20 21 114
575-3-60 4.9 33 8 4.9 33 8 1 4.3 0.4 8.6 11758 17 1 16.4 39.5 40 40 39 129 40.3 45 45 40 131
13458 34 1 32.7 59.9 60 60 58 145 60.7 70 70 59 147
None - - - 50.8 60 60 54 282 53 60 60 57 287
11725 12 1 33.3 92.4 100 100 93 315 94.6 100 100 95 320
208-3-60 14.5 98 23 14.5 98 23 2 9.9 1.1 8.6 12525 18.6 1 51.6 115.3 125 125 114 333 117.5 125 125 116 338
13225 24 1 66.6 134.1 150 150 131 348 136.3 150 150 133 353
14225 31.8 2 88.3 128.1 150 150 122 341 130.9 150 150 125 346
None - - - 50.9 60 60 54 291 52.9 60 60 57 295
11725 16 1 38.5 99 100 100 99 329 101 110 110 101 334
230-3-60 14.5 98 23 14.5 98 23 2.3 9.4 1 8.6 12525 24.8 1 59.7 125.5 150 150 123 350 127.5 150 150 125 355
09 13225 32 1 77 147.2 150 150 143 368 149.2 150 150 145 372
(8.5) 14225 42.4 2 102 144.6 150 150 133 359 147.1 150 150 135 363
None - - - 23.7 25 25 25 158 24.7 25 25 27 160
11746 16.5 1 19.8 48.5 50 50 48 178 49.5 50 50 49 180
460-3-60 6.3 55 10 6.3 55 10 1.3 4.7 0.5 8.6 12846 27.8 1 33.4 65.5 70 70 64 192 66.5 70 70 65 194
13346 33 1 39.7 73.3 80 80 71 198 74.3 80 80 72 200
14246 41.7 2 50.2 71.3 80 80 64 192 72.6 80 80 65 194
None - - - 21.5 25 25 23 128 22.3 25 25 24 130
575-3-60 6 41 9 6 41 9 1 4.3 0.4 8.6 11758 17 1 16.4 42 45 45 42 145 42.8 45 45 43 147
13458 34 1 32.7 62.4 70 70 61 161 63.2 70 70 62 163
Johnson Controls Ducted Systems 99
5147362-YTG-R-0323
XXEA7-12 high indoor blower - with powered convenience outlet (Continued)
Min Max Min
Min Max Min Fuse2/ Fuse2/ Discon-
OD Electric Heat MCA1
Nominal Supply Pwr Pwr 2
Fuse / 2
Fuse / Discon- Breaker3 Breaker3 nect
Size Compressor 1 Compressor 2 Fan Field-installed KitMCA1 w/Pwr
Unit Blower Exh Conv Breaker3 Breaker3 nect Size Size
(ton) Motors 2EK045* (Amps) 4 Exh Rating4/
Voltage Motor Motor Outlet Size Size Rating w/ w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
None - - - 58.3 60 70 63 439 60.5 70 70 65 444
11725 12 1 33.3 99.9 100 100 101 472 102.1 110 110 103 477
208-3-60 15.4 155 24 15.4 155 24 5.8 13.5 1.1 8.6 12525 18.6 1 51.6 122.8 125 125 122 491 125 150 150 124 496
13225 24 1 66.6 141.6 150 150 139 506 143.8 150 150 142 511
14225 31.8 2 88.3 132.6 150 150 131 498 135.4 150 150 133 503
None - - - 57.6 60 70 62 435 59.6 60 70 64 440
11725 16 1 38.5 105.7 110 110 106 474 107.7 110 110 108 478
230-3-60 15.4 155 24 15.4 155 24 5.2 13.4 1 8.6 12525 24.8 1 59.7 132.2 150 150 130 495 134.2 150 150 133 500
12 13225 32 1 77 153.9 175 175 150 512 155.9 175 175 153 517
(10) 14225 42.4 2 102 149.6 150 150 140 503 152.1 175 175 142 508
None - - - 29.1 30 35 31 188 30.1 35 35 32 190
11746 16.5 1 19.8 53.9 60 60 54 208 54.9 60 60 55 210
460-3-60 7.7 62 12 7.7 62 12 2.9 6.7 0.5 8.6 12846 27.8 1 33.4 70.9 80 80 70 222 71.9 80 80 71 224
13346 33 1 39.7 78.7 80 80 77 228 79.7 80 80 78 230
14246 41.7 2 50.2 73.8 80 80 70 222 75.1 80 80 71 224
None - - - 22.8 25 25 24 149 23.6 25 25 25 150
575-3-60 6 47.8 9 6 47.8 9 2.2 5.4 0.4 8.6 11758 17 1 16.4 43.3 45 45 43 165 44.1 45 45 44 167
13458 34 1 32.7 63.7 70 70 62 181 64.5 70 70 63 183
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field-installed
electric heat kits may exceed the factory-installed disconnect amperage rating.
100 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XQE04-06 standard indoor blower - without powered convenience outlet
Min
Max Fuse2/ Min
Electric Heat Min Max Min Fuse2/
OD 2 2 MCA1 Breaker3 Discon-nect
Nominal Compressor 1 Compressor 2 Supply Pwr Pwr Field-installed Kit 1 Fuse / Fuse / Disconnect Breaker3
Size Fan MCA 3 3 w/Pwr Size Rating4/
Unit Blower Exh Conv 2EK045* Breaker Breaker Rating4 Size
(ton) Motors (Amps) Exh w/ Pwr Exh
Voltage Motor Motor Outlet Size Size w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh
(Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA (Amps) FLA LRA
None - - - 27.9 30 40 28 90 29.4 30 40 29 94
208-1-60 15.4 83.9 24 2 6.6 1.5 10625 4.9 1 23.6 57.4 60 60 55 114 58.9 60 60 56 117
11125 7.9 1 38 75.4 80 80 71 128 76.9 80 80 73 132
None - - - 27.6 30 40 27 91 28.9 30 40 29 94
230-1-60 15.4 83.9 24 2.3 6 1.3 10625 6.5 1 27.1 61.5 70 70 58 118 62.8 70 70 60 121
11125 10.5 1 43.8 82.4 90 90 78 135 83.7 90 90 79 138
None - - - 21.6 25 30 22 79 22.7 25 30 23 82
10625 4.9 1 13.6 38.6 40 45 37 93 39.7 40 45 39 96
208-3-60 10.4 73 16 2 6.6 1.1
11125 7.9 1 21.9 49 50 50 47 101 50.1 60 60 48 104
11625 12 1 33.3 63.2 70 70 60 113 64.3 70 70 61 115
04
None - - - 21.3 25 30 22 80 22.3 25 30 23 82
(3)
10625 6.5 1 15.6 40.8 45 45 39 96 41.8 45 45 41 98
230-3-60 10.4 73 16 2.3 6 1
11125 10.5 1 25.3 52.9 60 60 51 105 53.9 60 60 52 108
11625 16 1 38.5 69.4 70 70 66 118 70.4 80 80 67 121
None - - - 11.8 15 15 12 43 12.3 15 15 12 44
10646 6 1 7.2 20.8 25 25 20 50 21.3 25 25 21 51
460-3-60 5.8 38 9 1.3 3.2 0.5
11146 11.5 1 13.8 29.1 30 30 28 57 29.6 30 30 28 58
11446 14 1 16.8 32.8 35 35 31 60 33.3 35 35 32 61
None - - - 8.2 15 15 8 40 8.6 15 15 9 41
575-3-60 3.8 36.5 6 1 6 0.4 11058 9.2 1 8.9 19.3 20 20 19 49 19.7 20 20 19 49
11458 13.8 1 13.3 24.8 25 25 24 53 25.2 30 30 24 54
None - - - 34.9 35 50 35 136 36.4 40 50 36 140
208-1-60 19.6 130 31 2 8.4 1.5 10625 4.9 1 23.6 64.4 70 70 62 160 65.9 70 70 63 163
11125 7.9 1 38 82.4 90 90 78 174 83.9 90 90 80 178
None - - - 34.4 35 50 34 137 35.7 40 50 35 140
230-1-60 19.6 130 31 2.3 7.6 1.3 10625 6.5 1 27.1 68.3 70 80 65 164 69.6 70 80 67 167
11125 10.5 1 43.8 89.2 90 90 84 181 90.5 100 100 86 184
None - - - 27.5 30 40 28 90 28.6 30 40 29 92
10625 4.9 1 13.6 44.5 45 50 43 103 45.6 50 50 45 106
208-3-60 13.7 83.1 21 2 8.4 1.1
11125 7.9 1 21.9 54.9 60 60 53 111 56 60 60 54 114
11625 12 1 33.3 69.1 70 70 66 123 70.2 80 80 67 125
05
None - - - 27 30 40 27 90 28 30 40 28 92
(4)
10625 6.5 1 15.6 46.5 50 50 45 106 47.5 50 50 46 108
230-3-60 13.7 83.1 21 2.3 7.6 1
11125 10.5 1 25.3 58.6 60 60 56 115 59.6 60 60 57 118
11625 16 1 38.5 75.1 80 80 71 129 76.1 80 80 73 131
None - - - 13.1 15 15 13 46 13.6 15 15 14 47
10646 6 1 7.2 22.1 25 25 22 53 22.6 25 25 22 54
460-3-60 6.2 41 10 1.3 4 0.5
11146 11.5 1 13.8 30.4 35 35 29 60 30.9 35 35 30 61
11446 14 1 16.8 34.1 35 35 33 63 34.6 35 35 33 64
None - - - 10 15 15 10 36 10.4 15 15 11 37
575-3-60 4.8 33 8 1 7.6 0.4 11058 9.2 1 8.9 21.1 25 25 20 45 21.5 25 25 21 46
11458 13.8 1 13.3 26.6 30 30 25 49 27 30 30 26 50
Johnson Controls Ducted Systems 101
5147362-YTG-R-0323
XQE04-06 standard indoor blower - without powered convenience outlet (Continued)
Min
Max Fuse2/ Min
Electric Heat Min Max Min Fuse2/
OD 2 2 MCA1 Breaker3 Discon-nect
Nominal Compressor 1 Compressor 2 Supply Pwr Pwr Field-installed Kit 1 Fuse / Fuse / Disconnect Breaker3
Size Fan MCA 3 3 w/Pwr Size Rating4
/
Unit Blower Exh Conv 2EK045* Breaker Breaker Rating4 Size
(ton) Motors (Amps) Exh w/ Pwr Exh
Voltage Motor Motor Outlet Size Size w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh
(Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA (Amps) FLA LRA
None - - - 40.9 45 60 40 151 42.4 45 60 42 154
144.
208-1-60 24.4 38 2 8.4 1.5 10625 4.9 1 23.6 70.4 80 80 67 174 71.9 80 90 69 178
2
11125 7.9 1 38 88.4 90 100 84 189 89.9 90 100 85 192
None - - - 40.4 45 60 39 151 41.7 45 60 41 154
144.
230-1-60 24.4 38 2.3 7.6 1.3 10625 6.5 1 27.1 74.3 80 90 71 178 75.6 80 90 72 181
2
11125 10.5 1 43.8 95.2 100 100 90 195 96.5 100 100 91 198
None - - - 30.4 35 45 30 116 31.5 35 45 32 119
10625 4.9 1 13.6 47.4 50 60 46 130 48.5 50 60 47 133
208-3-60 16 110 25 2 8.4 1.1
11125 7.9 1 21.9 57.8 60 60 56 138 58.9 60 60 57 141
11625 12 1 33.3 72 80 80 69 150 73.1 80 80 70 152
06
None - - - 29.9 30 45 30 117 30.9 35 45 31 119
(5)
10625 6.5 1 15.6 49.4 50 60 48 133 50.4 60 60 49 135
230-3-60 16 110 25 2.3 7.6 1
11125 10.5 1 25.3 61.5 70 70 59 142 62.5 70 70 60 145
11625 16 1 38.5 78 80 80 74 155 79 80 80 75 158
None - - - 15.1 20 20 15 57 15.6 20 20 16 58
10646 6 1 7.2 24.1 25 30 23 64 24.6 25 30 24 65
460-3-60 7.8 52 12 1.3 4 0.5
11146 11.5 1 13.8 32.4 35 35 31 71 32.9 35 35 32 72
11446 14 1 16.8 36.1 40 40 34 74 36.6 40 40 35 75
None - - - 11.1 15 15 11 42 11.5 15 15 12 43
575-3-60 5.7 38.9 9 1 7.6 0.4 11458 13.8 1 13.3 27.7 30 30 26 55 28.1 30 30 27 56
12358 23 1 22.1 38.7 40 40 37 64 39.1 40 40 37 65
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field-installed
electric heat kits may exceed the factory-installed disconnect amperage rating.
102 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XQE04-06 standard indoor blower - with powered convenience outlet
Min
Max Fuse2/ Min
Electric Heat Min Max Min Fuse2/
OD 2 2 MCA1 Breaker3 Discon-nect
Nominal Compressor 1 Compressor 2 Supply Pwr Pwr Field-installed Kit 1 Fuse / Fuse / Disconnect Breaker3
Size Fan MCA 3 3 w/Pwr Size Rating4/
Unit Blower Exh Conv 2EK045* Breaker Breaker Rating4 Size
(ton) Motors (Amps) Exh w/ Pwr Exh
Voltage Motor Motor Outlet Size Size w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh
(Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA (Amps) FLA LRA
None - - - 32.2 35 45 33 95 33.7 35 45 34 98
208-1-60 15.4 83.9 24 2 6.6 1.5 8.6 10625 4.9 1 23.6 61.7 70 70 60 118 63.2 70 70 61 122
11125 7.9 1 38 79.7 80 80 76 133 81.2 90 90 78 136
None - - - 31.9 35 45 32 95 33.2 35 45 34 98
230-1-60 15.4 83.9 24 2.3 6 1.3 8.6 10625 6.5 1 27.1 65.8 70 70 63 122 67.1 70 70 65 125
11125 10.5 1 43.8 86.7 90 90 83 139 88 90 90 84 142
None - - - 25.9 30 35 27 84 27 30 35 28 86
10625 4.9 1 13.6 42.9 45 45 42 97 44 45 50 44 100
208-3-60 10.4 73 16 2 6.6 1.1 8.6
11125 7.9 1 21.9 53.3 60 60 52 106 54.4 60 60 53 108
11625 12 1 33.3 67.5 70 70 65 117 68.6 70 70 66 120
04
None - - - 25.6 30 35 26 84 26.6 30 35 28 87
(3)
10625 6.5 1 15.6 45.1 50 50 44 100 46.1 50 50 46 102
230-3-60 10.4 73 16 2.3 6 1 8.6
11125 10.5 1 25.3 57.2 60 60 56 110 58.2 60 60 57 112
11625 16 1 38.5 73.7 80 80 71 123 74.7 80 80 72 125
None - - - 14 15 15 14 45 14.5 15 15 15 46
10646 6 1 7.2 23 25 25 23 52 23.5 25 25 23 53
460-3-60 5.8 38 9 1.3 3.2 0.5 8.6
11146 11.5 1 13.8 31.3 35 35 30 59 31.8 35 35 31 60
11446 14 1 16.8 35 35 35 34 62 35.5 40 40 34 63
None - - - 9.9 15 15 10 41 10.3 15 15 11 42
575-3-60 3.8 36.5 6 1 6 0.4 8.6 11058 9.2 1 8.9 21 25 25 20 50 21.4 25 25 21 51
11458 13.8 1 13.3 26.5 30 30 26 55 26.9 30 30 26 56
None - - - 39.2 40 50 39 141 40.7 45 60 41 144
208-1-60 19.6 130 31 2 8.4 1.5 8.6 10625 4.9 1 23.6 68.7 70 80 67 164 70.2 80 80 68 168
11125 7.9 1 38 86.7 90 90 83 179 88.2 90 90 85 182
None - - - 38.7 40 50 39 141 40 40 50 40 144
230-1-60 19.6 130 31 2.3 7.6 1.3 8.6 10625 6.5 1 27.1 72.6 80 80 70 168 73.9 80 80 72 171
11125 10.5 1 43.8 93.5 100 100 89 185 94.8 100 100 91 188
None - - - 31.8 35 45 33 94 32.9 35 45 34 96
10625 4.9 1 13.6 48.8 50 50 48 107 49.9 50 60 50 110
208-3-60 13.7 83.1 21 2 8.4 1.1 8.6
11125 7.9 1 21.9 59.2 60 60 58 116 60.3 70 70 59 118
11625 12 1 33.3 73.4 80 80 71 127 74.5 80 80 72 130
05
None - - - 31.3 35 45 32 94 32.3 35 45 33 97
(4)
10625 6.5 1 15.6 50.8 60 60 50 110 51.8 60 60 51 112
230-3-60 13.7 83.1 21 2.3 7.6 1 8.6
11125 10.5 1 25.3 62.9 70 70 61 120 63.9 70 70 62 122
11625 16 1 38.5 79.4 80 80 76 133 80.4 90 90 78 135
None - - - 15.3 20 20 16 48 15.8 20 20 16 49
10646 6 1 7.2 24.3 25 25 24 55 24.8 25 25 25 56
460-3-60 6.2 41 10 1.3 4 0.5 8.6
11146 11.5 1 13.8 32.6 35 35 32 62 33.1 35 35 32 63
11446 14 1 16.8 36.3 40 40 35 65 36.8 40 40 36 66
None - - - 11.8 15 15 12 38 12.2 15 15 13 39
575-3-60 4.8 33 8 1 7.6 0.4 8.6 11058 9.2 1 8.9 22.9 25 25 22 47 23.3 25 25 23 48
11458 13.8 1 13.3 28.4 30 30 27 51 28.8 30 30 28 52
Johnson Controls Ducted Systems 103
5147362-YTG-R-0323
XQE04-06 standard indoor blower - with powered convenience outlet (Continued)
Min
Max Fuse2/ Min
Electric Heat Min Max Min Fuse2/
OD 2 2 MCA1 Breaker3 Discon-nect
Nominal Compressor 1 Compressor 2 Supply Pwr Pwr Field-installed Kit 1 Fuse / Fuse / Disconnect Breaker3
Size Fan MCA 3 3 w/Pwr Size Rating4
/
Unit Blower Exh Conv 2EK045* Breaker Breaker Rating4 Size
(ton) Motors (Amps) Exh w/ Pwr Exh
Voltage Motor Motor Outlet Size Size w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh
(Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA (Amps) FLA LRA
None - - - 45.2 50 60 45 155 46.7 50 70 47 158
144.
208-1-60 24.4 38 2 8.4 1.5 8.6 10625 4.9 1 23.6 74.7 80 90 72 179 76.2 80 90 74 182
2
11125 7.9 1 38 92.7 100 100 89 193 94.2 100 100 90 196
None - - - 44.7 45 60 44 155 46 50 70 46 158
144.
230-1-60 24.4 38 2.3 7.6 1.3 8.6 10625 6.5 1 27.1 78.6 80 90 76 183 79.9 80 90 77 185
2
11125 10.5 1 43.8 99.5 100 110 95 199 100.8 110 110 96 202
None - - - 34.7 35 50 35 121 35.8 40 50 37 123
10625 4.9 1 13.6 51.7 60 60 51 134 52.8 60 60 52 137
208-3-60 16 110 25 2 8.4 1.1 8.6
11125 7.9 1 21.9 62.1 70 70 60 143 63.2 70 70 62 145
11625 12 1 33.3 76.3 80 80 74 154 77.4 80 80 75 157
06
None - - - 34.2 35 50 35 121 35.2 40 50 36 124
(5)
10625 6.5 1 15.6 53.7 60 60 53 137 54.7 60 60 54 139
230-3-60 16 110 25 2.3 7.6 1 8.6
11125 10.5 1 25.3 65.8 70 70 64 147 66.8 70 70 65 149
11625 16 1 38.5 82.3 90 90 79 160 83.3 90 90 80 162
None - - - 17.3 20 25 18 59 17.8 20 25 18 60
10646 6 1 7.2 26.3 30 30 26 66 26.8 30 30 26 67
460-3-60 7.8 52 12 1.3 4 0.5 8.6
11146 11.5 1 13.8 34.6 35 35 33 73 35.1 40 40 34 74
11446 14 1 16.8 38.3 40 40 37 76 38.8 40 40 37 77
None - - - 12.9 15 15 13 44 13.3 15 15 14 45
575-3-60 5.7 38.9 9 1 7.6 0.4 8.6 11458 13.8 1 13.3 29.5 30 30 29 57 29.9 30 30 29 58
12358 23 1 22.1 40.5 45 45 39 66 40.9 45 45 39 67
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field-installed
electric heat kits may exceed the factory-installed disconnect amperage rating.
104 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XQE04-06 medium indoor blower - without powered convenience outlet
Min
Max Fuse2/ Min
Electric Heat Min Max Min Fuse2/
OD 2 2 MCA 1 Breaker3 Discon-nect
Nominal Compressor 1 Compressor 2 Supply Pwr Pwr Field-installed Kit 1 Fuse / Fuse / Disconnect Breaker3
Size Fan MCA 3 3 w/Pwr Size Rating4/
Unit Blower Exh Conv 2EK045* Breaker Breaker Rating4 Size
(ton) Motors (Amps) Exh w/ Pwr Exh
Voltage Motor Motor Outlet Size Size w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh
(Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA (Amps) FLA LRA
None - - - 28.9 30 40 29 121 30.4 35 45 30 125
208-1-60 15.4 83.9 24 2 7.6 1.5 10625 4.9 1 23.6 58.4 60 60 56 145 59.9 60 60 58 148
11125 7.9 1 38 76.4 80 80 72 159 77.9 80 80 74 163
None - - - 28.6 30 40 28 124 29.9 30 45 30 127
230-1-60 15.4 83.9 24 2.3 7 1.3 10625 6.5 1 27.1 62.5 70 70 60 151 63.8 70 70 61 154
11125 10.5 1 43.8 83.4 90 90 79 168 84.7 90 90 80 171
None - - - 20.2 25 30 20 100 21.3 25 30 22 102
10625 4.9 1 13.6 37.2 40 40 36 113 38.3 40 45 37 116
208-3-60 10.4 73 16 2 5.2 1.1
11125 7.9 1 21.9 47.6 50 50 45 122 48.7 50 50 47 124
11625 12 1 33.3 61.8 70 70 59 133 62.9 70 70 60 136
04
None - - - 20.5 25 30 21 103 21.5 25 30 22 105
(3)
10625 6.5 1 15.6 40 40 45 39 119 41 45 45 40 121
230-3-60 10.4 73 16 2.3 5.2 1
11125 10.5 1 25.3 52.1 60 60 50 128 53.1 60 60 51 131
11625 16 1 38.5 68.6 70 70 65 141 69.6 70 70 66 144
None - - - 11.2 15 15 11 53 11.7 15 15 12 55
10646 6 1 7.2 20.2 25 25 19 61 20.7 25 25 20 62
460-3-60 5.8 38 9 1.3 2.6 0.5
11146 11.5 1 13.8 28.5 30 30 27 67 29 30 30 28 68
11446 14 1 16.8 32.2 35 35 30 70 32.7 35 35 31 71
None - - - 7.8 15 15 8 49 8.2 15 15 8 50
575-3-60 3.8 36.5 6 1 2 0.4 11058 9.2 1 8.9 18.9 20 20 18 58 19.3 20 20 19 59
11458 13.8 1 13.3 24.4 25 25 23 62 24.8 25 25 24 63
None - - - 34.1 35 50 34 167 35.6 40 50 35 171
208-1-60 19.6 130 31 2 7.6 1.5 10625 4.9 1 23.6 63.6 70 70 61 191 65.1 70 70 62 194
11125 7.9 1 38 81.6 90 90 77 205 83.1 90 90 79 209
None - - - 33.8 35 50 33 170 35.1 40 50 35 173
230-1-60 19.6 130 31 2.3 7 1.3 10625 6.5 1 27.1 67.7 70 80 64 198 69 70 80 66 200
11125 10.5 1 43.8 88.6 90 90 84 214 89.9 90 90 85 217
None - - - 24.3 25 35 24 110 25.4 30 35 25 112
10625 4.9 1 13.6 41.3 45 50 40 124 42.4 45 50 41 126
208-3-60 13.7 83.1 21 2 5.2 1.1
11125 7.9 1 21.9 51.7 60 60 49 132 52.8 60 60 50 134
11625 12 1 33.3 65.9 70 70 62 143 67 70 70 64 146
05
None - - - 24.6 25 35 24 113 25.6 30 35 26 115
(4)
10625 6.5 1 15.6 44.1 45 50 42 129 45.1 50 50 43 131
230-3-60 13.7 83.1 21 2.3 5.2 1
11125 10.5 1 25.3 56.2 60 60 53 138 57.2 60 60 55 141
11625 16 1 38.5 72.7 80 80 69 152 73.7 80 80 70 154
None - - - 11.7 15 15 12 56 12.2 15 15 12 58
10646 6 1 7.2 20.7 25 25 20 64 21.2 25 25 20 65
460-3-60 6.2 41 10 1.3 2.6 0.5
11146 11.5 1 13.8 29 30 30 27 70 29.5 30 30 28 71
11446 14 1 16.8 32.7 35 35 31 73 33.2 35 35 32 74
None - - - 9 15 15 9 45 9.4 15 15 9 46
575-3-60 4.8 33 8 1 2 0.4 11058 9.2 1 8.9 20.1 25 25 19 54 20.5 25 25 20 55
11458 13.8 1 13.3 25.6 30 30 24 59 26 30 30 25 60
Johnson Controls Ducted Systems 105
5147362-YTG-R-0323
XQE04-06 medium indoor blower - without powered convenience outlet (Continued)
Min
Max Fuse2/ Min
Electric Heat Min Max Min Fuse2/
OD 2 2 MCA 1 Breaker3 Discon-nect
Nominal Compressor 1 Compressor 2 Supply Pwr Pwr Field-installed Kit 1 Fuse / Fuse / Disconnect Breaker3
Size Fan MCA 3 3 w/Pwr Size Rating4
/
Unit Blower Exh Conv 2EK045* Breaker Breaker Rating4 Size
(ton) Motors (Amps) Exh w/ Pwr Exh
Voltage Motor Motor Outlet Size Size w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh
(Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA (Amps) FLA LRA
None - - - 39.3 40 60 38 181 40.8 45 60 40 185
144.
208-1-60 24.4 38 2 6.8 1.5 10625 4.9 1 23.6 68.8 70 80 65 205 70.3 80 80 67 208
2
11125 7.9 1 38 86.8 90 100 82 219 88.3 90 100 84 223
None - - - 39 40 60 38 182 40.3 45 60 39 185
144.
230-1-60 24.4 38 2.3 6.2 1.3 10625 6.5 1 27.1 72.9 80 90 69 209 74.2 80 90 70 212
2
11125 10.5 1 43.8 93.8 100 100 88 226 95.1 100 100 90 229
None - - - 29 30 45 29 175 30.1 35 45 30 177
10625 4.9 1 13.6 46 50 50 44 188 47.1 50 50 46 191
208-3-60 16 110 25 2 7 1.1
11125 7.9 1 21.9 56.4 60 60 54 196 57.5 60 60 55 199
11625 12 1 33.3 70.6 80 80 67 208 71.7 80 80 68 210
06
None - - - 29.5 30 45 29 177 30.5 35 45 30 179
(5)
10625 6.5 1 15.6 49 50 60 47 192 50 50 60 48 195
230-3-60 16 110 25 2.3 7.2 1
11125 10.5 1 25.3 61.1 70 70 58 202 62.1 70 70 60 204
11625 16 1 38.5 77.6 80 80 74 215 78.6 80 80 75 218
None - - - 14.7 15 20 15 86 15.2 20 20 15 87
10646 6 1 7.2 23.7 25 25 23 93 24.2 25 25 23 94
460-3-60 7.8 52 12 1.3 3.6 0.5
11146 11.5 1 13.8 32 35 35 30 100 32.5 35 35 31 101
11446 14 1 16.8 35.7 40 40 34 103 36.2 40 40 35 104
None - - - 10.6 15 15 11 59 11 15 15 11 60
575-3-60 5.7 38.9 9 1 2.5 0.4 11458 13.8 1 13.3 27.2 30 30 26 72 27.6 30 30 26 73
12358 23 1 22.1 38.2 40 40 36 81 38.6 40 40 36 82
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field-installed
electric heat kits may exceed the factory-installed disconnect amperage rating.
106 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XQE04-06 medium indoor blower - with powered convenience outlet
Min
Max Fuse2/ Min
Electric Heat Min Max Min Fuse2/
OD 2 2 MCA 1 Breaker3 Discon-nect
Nominal Compressor 1 Compressor 2 Supply Pwr Pwr Field-installed Kit 1 Fuse / Fuse / Disconnect Breaker3
Size Fan MCA 3 3 w/Pwr Size Rating4/
Unit Blower Exh Conv 2EK045* Breaker Breaker Rating4 Size
(ton) Motors (Amps) Exh w/ Pwr Exh
Voltage Motor Motor Outlet Size Size w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh
(Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA (Amps) FLA LRA
None - - - 33.2 35 45 34 126 34.7 35 50 35 129
208-1-60 15.4 83.9 24 2 7.6 1.5 8.6 10625 4.9 1 23.6 62.7 70 70 61 149 64.2 70 70 63 153
11125 7.9 1 38 80.7 90 90 77 164 82.2 90 90 79 167
None - - - 32.9 35 45 33 129 34.2 35 45 35 132
230-1-60 15.4 83.9 24 2.3 7 1.3 8.6 10625 6.5 1 27.1 66.8 70 70 65 156 68.1 70 70 66 159
11125 10.5 1 43.8 87.7 90 90 84 172 89 90 90 85 175
None - - - 24.5 25 30 25 104 25.6 30 35 26 107
10625 4.9 1 13.6 41.5 45 45 41 118 42.6 45 45 42 120
208-3-60 10.4 73 16 2 5.2 1.1 8.6
11125 7.9 1 21.9 51.9 60 60 50 126 53 60 60 52 129
11625 12 1 33.3 66.1 70 70 63 137 67.2 70 70 65 140
04
None - - - 24.8 25 35 26 107 25.8 30 35 27 110
(3)
10625 6.5 1 15.6 44.3 45 50 43 123 45.3 50 50 45 125
230-3-60 10.4 73 16 2.3 5.2 1 8.6
11125 10.5 1 25.3 56.4 60 60 55 133 57.4 60 60 56 135
11625 16 1 38.5 72.9 80 80 70 146 73.9 80 80 71 148
None - - - 13.4 15 15 14 56 13.9 15 15 14 57
10646 6 1 7.2 22.4 25 25 22 63 22.9 25 25 23 64
460-3-60 5.8 38 9 1.3 2.6 0.5 8.6
11146 11.5 1 13.8 30.7 35 35 30 69 31.2 35 35 30 70
11446 14 1 16.8 34.4 35 35 33 72 34.9 35 35 34 73
None - - - 9.5 15 15 10 51 9.9 15 15 10 51
575-3-60 3.8 36.5 6 1 2 0.4 8.6 11058 9.2 1 8.9 20.6 25 25 20 59 21 25 25 20 60
11458 13.8 1 13.3 26.1 30 30 25 64 26.5 30 30 26 65
None - - - 38.4 40 50 39 172 39.9 40 50 40 175
208-1-60 19.6 130 31 2 7.6 1.5 8.6 10625 4.9 1 23.6 67.9 70 80 66 195 69.4 70 80 67 199
11125 7.9 1 38 85.9 90 90 82 210 87.4 90 90 84 213
None - - - 38.1 40 50 38 175 39.4 40 50 40 178
230-1-60 19.6 130 31 2.3 7 1.3 8.6 10625 6.5 1 27.1 72 80 80 69 202 73.3 80 80 71 205
11125 10.5 1 43.8 92.9 100 100 89 219 94.2 100 100 90 221
None - - - 28.6 30 40 29 114 29.7 30 40 30 117
10625 4.9 1 13.6 45.6 50 50 45 128 46.7 50 50 46 130
208-3-60 13.7 83.1 21 2 5.2 1.1 8.6
11125 7.9 1 21.9 56 60 60 54 136 57.1 60 60 55 139
11625 12 1 33.3 70.2 80 80 67 148 71.3 80 80 69 150
05
None - - - 28.9 30 40 29 117 29.9 30 40 30 120
(4)
10625 6.5 1 15.6 48.4 50 50 47 133 49.4 50 50 48 135
230-3-60 13.7 83.1 21 2.3 5.2 1 8.6
11125 10.5 1 25.3 60.5 70 70 58 143 61.5 70 70 60 145
11625 16 1 38.5 77 80 80 74 156 78 80 80 75 158
None - - - 13.9 15 20 14 59 14.4 15 20 15 60
10646 6 1 7.2 22.9 25 25 22 66 23.4 25 25 23 67
460-3-60 6.2 41 10 1.3 2.6 0.5 8.6
11146 11.5 1 13.8 31.2 35 35 30 72 31.7 35 35 31 73
11446 14 1 16.8 34.9 35 35 33 75 35.4 40 40 34 76
None - - - 10.7 15 15 11 47 11.1 15 15 11 48
575-3-60 4.8 33 8 1 2 0.4 8.6 11058 9.2 1 8.9 21.8 25 25 21 56 22.2 25 25 22 57
11458 13.8 1 13.3 27.3 30 30 26 60 27.7 30 30 27 61
Johnson Controls Ducted Systems 107
5147362-YTG-R-0323
XQE04-06 medium indoor blower - with powered convenience outlet (Continued)
Min
Max Fuse2/ Min
Electric Heat Min Max Min Fuse2/
OD 2 2 MCA 1 Breaker3 Discon-nect
Nominal Compressor 1 Compressor 2 Supply Pwr Pwr Field-installed Kit 1 Fuse / Fuse / Disconnect Breaker3
Size Fan MCA 3 3 w/Pwr Size Rating4
/
Unit Blower Exh Conv 2EK045* Breaker Breaker Rating4 Size
(ton) Motors (Amps) Exh w/ Pwr Exh
Voltage Motor Motor Outlet Size Size w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh
(Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA (Amps) FLA LRA
None - - - 43.6 45 60 43 185 45.1 50 60 45 189
144.
208-1-60 24.4 38 2 6.8 1.5 8.6 10625 4.9 1 23.6 73.1 80 90 70 209 74.6 80 90 72 212
2
11125 7.9 1 38 91.1 100 100 87 223 92.6 100 100 89 227
None - - - 43.3 45 60 43 186 44.6 45 60 44 189
144.
230-1-60 24.4 38 2.3 6.2 1.3 8.6 10625 6.5 1 27.1 77.2 80 90 74 214 78.5 80 90 75 216
2
11125 10.5 1 43.8 98.1 100 110 93 230 99.4 100 110 95 233
None - - - 33.3 35 45 34 179 34.4 35 50 35 181
10625 4.9 1 13.6 50.3 60 60 49 192 51.4 60 60 51 195
208-3-60 16 110 25 2 7 1.1 8.6
11125 7.9 1 21.9 60.7 70 70 59 201 61.8 70 70 60 203
11625 12 1 33.3 74.9 80 80 72 212 76 80 80 73 215
06
None - - - 33.8 35 45 34 181 34.8 35 50 35 183
(5)
10625 6.5 1 15.6 53.3 60 60 52 197 54.3 60 60 53 199
230-3-60 16 110 25 2.3 7.2 1 8.6
11125 10.5 1 25.3 65.4 70 70 63 206 66.4 70 70 65 209
11625 16 1 38.5 81.9 90 90 79 220 82.9 90 90 80 222
None - - - 16.9 20 20 17 88 17.4 20 20 18 89
10646 6 1 7.2 25.9 30 30 25 95 26.4 30 30 26 96
460-3-60 7.8 52 12 1.3 3.6 0.5 8.6
11146 11.5 1 13.8 34.2 35 35 33 102 34.7 35 35 34 103
11446 14 1 16.8 37.9 40 40 36 105 38.4 40 40 37 106
None - - - 12.3 15 15 13 61 12.7 15 15 13 62
575-3-60 5.7 38.9 9 1 2.5 0.4 8.6 11458 13.8 1 13.3 28.9 30 30 28 74 29.3 30 30 28 75
12358 23 1 22.1 39.9 40 40 38 83 40.3 45 45 38 84
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field-installed
electric heat kits may exceed the factory-installed disconnect amperage rating.
108 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XQE04-06 high indoor blower - without powered convenience outlet
Min
Max Fuse2/ Min
Electric Heat Min Max Min Fuse2/
OD 2/ 2/ MCA1 Breaker3 Discon-nect
Nominal Compressor 1 Compressor 2 Supply Pwr Pwr Field-installed Kit 1 Fuse Fuse Disconnect Breaker3
Size Fan MCA 3 3 w/Pwr Size Rating4/
Unit Blower Exh Conv 2EK045* Breaker Breaker Rating4 Size
(ton) Motors (Amps) Exh w/ Pwr Exh
Voltage Motor Motor Outlet Size Size w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh
(Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA (Amps) FLA LRA
None - - - 20.2 25 30 20 100 21.3 25 30 22 102
10625 4.9 1 13.6 37.2 40 40 36 113 38.3 40 45 37 116
208-3-60 10.4 73 16 2 5.2 1.1
11125 7.9 1 21.9 47.6 50 50 45 122 48.7 50 50 47 124
11625 12 1 33.3 61.8 70 70 59 133 62.9 70 70 60 136
None - - - 20.5 25 30 21 103 21.5 25 30 22 105
10625 6.5 1 15.6 40 40 45 39 119 41 45 45 40 121
230-3-60 10.4 73 16 2.3 5.2 1
11125 10.5 1 25.3 52.1 60 60 50 128 53.1 60 60 51 131
04
11625 16 1 38.5 68.6 70 70 65 141 69.6 70 70 66 144
(3)
None - - - 11.2 15 15 11 53 11.7 15 15 12 55
10646 6 1 7.2 20.2 25 25 19 61 20.7 25 25 20 62
460-3-60 5.8 38 9 1.3 2.6 0.5
11146 11.5 1 13.8 28.5 30 30 27 67 29 30 30 28 68
11446 14 1 16.8 32.2 35 35 30 70 32.7 35 35 31 71
None - - - 7.8 15 15 8 49 8.2 15 15 8 50
575-3-60 3.8 36.5 6 1 2 0.4 11058 9.2 1 8.9 18.9 20 20 18 58 19.3 20 20 19 59
11458 13.8 1 13.3 24.4 25 25 23 62 24.8 25 25 24 63
None - - - 24.3 25 35 24 110 25.4 30 35 25 112
10625 4.9 1 13.6 41.3 45 50 40 124 42.4 45 50 41 126
208-3-60 13.7 83.1 21 2 5.2 1.1
11125 7.9 1 21.9 51.7 60 60 49 132 52.8 60 60 50 134
11625 12 1 33.3 65.9 70 70 62 143 67 70 70 64 146
None - - - 24.6 25 35 24 113 25.6 30 35 26 115
10625 6.5 1 15.6 44.1 45 50 42 129 45.1 50 50 43 131
230-3-60 13.7 83.1 21 2.3 5.2 1
11125 10.5 1 25.3 56.2 60 60 53 138 57.2 60 60 55 141
05
11625 16 1 38.5 72.7 80 80 69 152 73.7 80 80 70 154
(4)
None - - - 11.7 15 15 12 56 12.2 15 15 12 58
10646 6 1 7.2 20.7 25 25 20 64 21.2 25 25 20 65
460-3-60 6.2 41 10 1.3 2.6 0.5
11146 11.5 1 13.8 29 30 30 27 70 29.5 30 30 28 71
11446 14 1 16.8 32.7 35 35 31 73 33.2 35 35 32 74
None - - - 9 15 15 9 45 9.4 15 15 9 46
575-3-60 4.8 33 8 1 2 0.4 11058 9.2 1 8.9 20.1 25 25 19 54 20.5 25 25 20 55
11458 13.8 1 13.3 25.6 30 30 24 59 26 30 30 25 60
None - - - 30.9 35 45 31 191 32 35 45 32 194
10625 4.9 1 13.6 47.9 50 60 47 205 49 50 60 48 207
208-3-60 16 110 25 2 8.9 1.1
11125 7.9 1 21.9 58.3 60 60 56 213 59.4 60 60 57 216
11625 12 1 33.3 72.5 80 80 69 225 73.6 80 80 70 227
None - - - 30.5 35 45 30 194 31.5 35 45 32 196
10625 6.5 1 15.6 50 50 60 48 210 51 60 60 50 212
230-3-60 16 110 25 2.3 8.2 1
11125 10.5 1 25.3 62.1 70 70 60 219 63.1 70 70 61 222
06
11625 16 1 38.5 78.6 80 80 75 232 79.6 80 80 76 235
(5)
None - - - 15.2 20 20 15 89 15.7 20 20 16 91
10646 6 1 7.2 24.2 25 30 23 97 24.7 25 30 24 98
460-3-60 7.8 52 12 1.3 4.1 0.5
11146 11.5 1 13.8 32.5 35 35 31 103 33 35 35 32 104
11446 14 1 16.8 36.2 40 40 35 106 36.7 40 40 35 107
None - - - 11.3 15 15 11 67 11.7 15 15 12 68
575-3-60 5.7 38.9 9 1 3.2 0.4 11458 13.8 1 13.3 27.9 30 30 27 81 28.3 30 30 27 82
12358 23 1 22.1 38.9 40 40 37 89 39.3 40 40 37 90
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field-installed
electric heat kits may exceed the factory-installed disconnect amperage rating.
Johnson Controls Ducted Systems 109
5147362-YTG-R-0323
XQE04-06 high indoor blower - with powered convenience outlet
Min
Max Fuse2/ Min
Electric Heat Min Max Min Fuse2/
OD 2/ 2/ MCA1 Breaker3 Discon-nect
Nominal Compressor 1 Compressor 2 Supply Pwr Pwr Field-installed Kit 1 Fuse Fuse Disconnect Breaker3
Size Fan MCA 3 3 w/Pwr Size Rating4/
Unit Blower Exh Conv 2EK045* Breaker Breaker Rating4 Size
(ton) Motors (Amps) Exh w/ Pwr Exh
Voltage Motor Motor Outlet Size Size w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh
(Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA (Amps) FLA LRA
None - - - 24.5 25 30 25 104 25.6 30 35 26 107
10625 4.9 1 13.6 41.5 45 45 41 118 42.6 45 45 42 120
208-3-60 10.4 73 16 2 5.2 1.1 8.6
11125 7.9 1 21.9 51.9 60 60 50 126 53 60 60 52 129
11625 12 1 33.3 66.1 70 70 63 137 67.2 70 70 65 140
None - - - 24.8 25 35 26 107 25.8 30 35 27 110
10625 6.5 1 15.6 44.3 45 50 43 123 45.3 50 50 45 125
230-3-60 10.4 73 16 2.3 5.2 1 8.6
11125 10.5 1 25.3 56.4 60 60 55 133 57.4 60 60 56 135
04
11625 16 1 38.5 72.9 80 80 70 146 73.9 80 80 71 148
(3)
None - - - 13.4 15 15 14 56 13.9 15 15 14 57
10646 6 1 7.2 22.4 25 25 22 63 22.9 25 25 23 64
460-3-60 5.8 38 9 1.3 2.6 0.5 8.6
11146 11.5 1 13.8 30.7 35 35 30 69 31.2 35 35 30 70
11446 14 1 16.8 34.4 35 35 33 72 34.9 35 35 34 73
None - - - 9.5 15 15 10 51 9.9 15 15 10 51
575-3-60 3.8 36.5 6 1 2 0.4 8.6 11058 9.2 1 8.9 20.6 25 25 20 59 21 25 25 20 60
11458 13.8 1 13.3 26.1 30 30 25 64 26.5 30 30 26 65
None - - - 28.6 30 40 29 114 29.7 30 40 30 117
10625 4.9 1 13.6 45.6 50 50 45 128 46.7 50 50 46 130
208-3-60 13.7 83.1 21 2 5.2 1.1 8.6
11125 7.9 1 21.9 56 60 60 54 136 57.1 60 60 55 139
11625 12 1 33.3 70.2 80 80 67 148 71.3 80 80 69 150
None - - - 28.9 30 40 29 117 29.9 30 40 30 120
10625 6.5 1 15.6 48.4 50 50 47 133 49.4 50 50 48 135
230-3-60 13.7 83.1 21 2.3 5.2 1 8.6
11125 10.5 1 25.3 60.5 70 70 58 143 61.5 70 70 60 145
05
11625 16 1 38.5 77 80 80 74 156 78 80 80 75 158
(4)
None - - - 13.9 15 20 14 59 14.4 15 20 15 60
10646 6 1 7.2 22.9 25 25 22 66 23.4 25 25 23 67
460-3-60 6.2 41 10 1.3 2.6 0.5 8.6
11146 11.5 1 13.8 31.2 35 35 30 72 31.7 35 35 31 73
11446 14 1 16.8 34.9 35 35 33 75 35.4 40 40 34 76
None - - - 10.7 15 15 11 47 11.1 15 15 11 48
575-3-60 4.8 33 8 1 2 0.4 8.6 11058 9.2 1 8.9 21.8 25 25 21 56 22.2 25 25 22 57
11458 13.8 1 13.3 27.3 30 30 26 60 27.7 30 30 27 61
None - - - 35.2 40 50 36 196 36.3 40 50 37 198
10625 4.9 1 13.6 52.2 60 60 52 209 53.3 60 60 53 212
208-3-60 16 110 25 2 8.9 1.1 8.6
11125 7.9 1 21.9 62.6 70 70 61 217 63.7 70 70 62 220
11625 12 1 33.3 76.8 80 80 74 229 77.9 80 80 75 231
None - - - 34.8 35 50 35 198 35.8 40 50 37 201
10625 6.5 1 15.6 54.3 60 60 53 214 55.3 60 60 55 216
230-3-60 16 110 25 2.3 8.2 1 8.6
11125 10.5 1 25.3 66.4 70 70 65 224 67.4 70 70 66 226
06
11625 16 1 38.5 82.9 90 90 80 237 83.9 90 90 81 239
(5)
None - - - 17.4 20 25 18 92 17.9 20 25 18 93
10646 6 1 7.2 26.4 30 30 26 99 26.9 30 30 27 100
460-3-60 7.8 52 12 1.3 4.1 0.5 8.6
11146 11.5 1 13.8 34.7 35 35 34 105 35.2 40 40 34 106
11446 14 1 16.8 38.4 40 40 37 108 38.9 40 40 38 109
None - - - 13 15 15 13 69 13.4 15 15 14 70
575-3-60 5.7 38.9 9 1 3.2 0.4 8.6 11458 13.8 1 13.3 29.6 30 30 29 82 30 30 30 29 83
12358 23 1 22.1 40.6 45 45 39 91 41 45 45 39 92
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field-installed
electric heat kits may exceed the factory-installed disconnect amperage rating.
110 Johnson Controls Ducted Systems
5147362-YTG-R-0323
Typical wiring diagrams
XYE04-09, XXEA7-12, XQE04-06 typical wiring diagrams
Typical XYE04-06, XQE04-06 heat pump w/o heat 208/230-1-60 direct drive elementary diagram power circuit
Johnson Controls Ducted Systems 111
5147362-YTG-R-0323
Typical XYE04-06, XQE04-06 heat pump w/o heat 208/230, 460-3-60 direct drive elementary diagram power circuit
112 Johnson Controls Ducted Systems
5147362-YTG-R-0323
Typical XYE04-06, XQE04-06 cooling unit w/o heat 575-3-60 direct drive elementary diagram power circuit
Johnson Controls Ducted Systems 113
5147362-YTG-R-0323
Typical XYE04-06, XQE04-06 heat pump unit w/o heat 208/230-1-60 belt drive elementary diagram power circuit
114 Johnson Controls Ducted Systems
5147362-YTG-R-0323
Typical XYE04-06, XQE04-06 unit w/o heat 208/230, 460, 575-3-60 belt drive elementary diagram power circuit
Johnson Controls Ducted Systems 115
5147362-YTG-R-0323
Typical XYE04-06, XQE04-06 heat pump unit direct drive elementary diagram control circuit
116 Johnson Controls Ducted Systems
5147362-YTG-R-0323
Typical XYE04-06, XXEA7, XQE04-06 heat pump unit belt drive elementary diagram control circuit
Johnson Controls Ducted Systems 117
5147362-YTG-R-0323
Typical XXEA7 heat pump unit w/o heat 208/230, 460, 575-3-60 belt drive with VFD elementary diagram power circuit
118 Johnson Controls Ducted Systems
5147362-YTG-R-0323
Typical FDD elementary wiring diagram
Johnson Controls Ducted Systems 119
5147362-YTG-R-0323
Typical XYEA7 heat pump unit w/wo electric heat w/wo vfd 208/230-3-60, 460-3-60 belt drive - elementary diagram power
circuit
120 Johnson Controls Ducted Systems
5147362-YTG-R-0323
Typical XYEA7 heat pump unit w/wo electric heat w/wo vfd 575v-3-60 belt drive - elementary diagram power circuit
Johnson Controls Ducted Systems 121
5147362-YTG-R-0323
Typical XYEA7 heat pump unit w/wo electric heat w/wo vfd - elementary diagram control circuit
122 Johnson Controls Ducted Systems
5147362-YTG-R-0323
Typical XYE08-09, XXE08-12 heat pump unit w/o heat 208/230, 460, 575-3-60 belt drive with VFD elementary diagram power
circuit
Johnson Controls Ducted Systems 123
5147362-YTG-R-0323
Typical XYE08-09, XXE08-12 heat pump unit belt drive elementary diagram control circuit
124 Johnson Controls Ducted Systems
5147362-YTG-R-0323
Weights and dimensions
XYE04-09, XXEA7-12, XQE04-06 unit weights
Unit 4 point load weight Unit 6 point load weight
Unit center of gravity
X
Y
FRONT
LEFT
XYE04-09 corner weights
Size Weight (lb) Center of Gravity 4 Point Load Location (lb) 6 Point Load Location (lb)
Model
(ton) Shipping Operating X Y A B C D A B C D E F
04
XYE 563 535 37.4 24.2 130 133 138 135 86 88 89 92 91 89
(3)
05
XYE 643 614 38.1 25.1 151 161 155 146 100 104 109 105 100 96
(4)
06
XYE 682 653 37.4 23.1 151 155 176 171 100 102 104 118 116 114
(5)
A7
XYE 915 898 44.3 34.9 249 257 197 191 165 169 172 132 130 127
(6)
08
XYE 1090 1060 48.5 34.1 260 326 264 210 167 193 226 183 156 135
(7.5)
09
XYE 1091 1061 48.5 34.1 260 326 264 211 167 193 226 183 156 135
(8.5)
Johnson Controls Ducted Systems 125
5147362-YTG-R-0323
XXEA7-12 corner weights
Size Weight (lb) Center of Gravity 4 Point Load Location (lb) 6 Point Load Location (lb)
Model
(ton) Shipping Operating X Y A B C D A B C D E F
A7
XXE 665 652 35.8 23.9 163 153 163 173 110 105 101 107 112 117
(6)
08
XXE 1006 976 46.9 35.7 261 304 221 190 170 187 208 151 136 124
(7.5)
09
XXE 1055 1025 48.0 35.7 267 326 238 194 172 196 225 164 143 125
(8.5)
12
XXE 1090 1060 49.5 33.3 247 325 277 211 158 188 227 193 160 135
(10)
XQE04-06 corner weights
Weight (lb) Center of Gravity 4 point Load Location (lb) 6 point Load Location (lb)
Size
Model
(ton) Shipping Operating X Y A B C D A B C D E F
04
XQE 542 529 38.0 24.4 127 135 137 130 84 87 91 92 89 86
(3)
05
XQE 641 628 35.0 24.5 164 148 150 166 111 104 97 98 105 113
(4)
06
XQE 640 627 34.7 24.4 165 146 149 168 112 103 95 97 105 114
(5)
XYE04-09, XYEA7, XXEA7-12, XQE04-06 unit accessory weights
Unit Accessory Weights (lb)
Vertical Flow Dry Bulb Economizer Small Footprint 63
Horizontal Flow Dry Bulb Economizer Small Footprint Short 96
Horizontal Flow Dry Bulb Economizer Small Footprint Short 75
Horizontal Flow Dry Bulb Economizer Small Footprint Tall 81
Horizontal Flow Dry Bulb Economizer Large Footprint Short 105
Horizontal Flow Dry Bulb Economizer Large Footprint Tall 102
Power Exhaust Vert Flow Small Footprint 38
Power Exhaust Vert Flow Large Footprint 38
Power Exhaust Horiz Flow Small Footprint 38
Power Exhaust Horiz Flow Large Footprint 38
Hail Guard Kit Small Short Factory-installed 19
Hail Guard Kit Small Tall Factory-installed 24
Hail Guard Kit Large Short Factory-installed 50
Hail Guard Kit Large Tall Factory-installed 50
Curb Rigid 14 in. Small Footprint 145
Curb Rigid 24 in. Small Footprint 135
Curb Rigid 14 in. Large Footprint 135
Curb Rigid 24 in. Large Footprint 135
126 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XYE04-09, XQE04-06, XXEA7-12 unit dimensions
XYE/XQE04
Johnson Controls Ducted Systems 127
5147362-YTG-R-0323
XYE/XQE05 - 06 And XXEA7
128 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XYEA7
Johnson Controls Ducted Systems 129
5147362-YTG-R-0323
XXE08-09
130 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XYE08, 09 and XXE12
Johnson Controls Ducted Systems 131
5147362-YTG-R-0323
XYE04-06, XQE04-06, and XXEA7 unit clearances
Direction Distance (in.) Direction Distance (in.)
Top1 72 Right 18
Front 36 Left 12
Rear 182/363 Bottom4 1
1. Units must be installed outdoors. Over hanging structure or
shrubs should not obscure condenser air discharge outlet.
2. Units without economizer or power exhaust.
3. Units equipped with an Economizer or Power Exhaust. Flue
products must not be discharged within 10 Feet of the rear of
the unit.
4. Units may be installed on combustible floors made from
wood or class A, B or C roof covering materials.
XYE04-06, XXEA7, XQE04-06 unit roof curb dimensions
1RC0456, 1RC0458 roof curb dimensions
70.875 O.D.
67.375 I.D.
RN
32.188
RETU
RN
TU
RE
13.781
3.000
LY
37.188
PP
I.D.
SU
RIGHT
LY
23.591 11.961 20.406
PP
FRONT
SU
RIGHT
4.961 14.000
5.422 FRONT
17.781
40.688 O.D.
70.871 40.684
1RC0456 X= 14" Height
1RC0458 X= 24" Height
Notes:
1. Sides, ends and cross support are 18-G90. Deck pans, R/A & S/A supports are 20-G90.
2. Full perimeter wood nailer.
3. Insulated deck pans.
Note: If utilities are required through the base of the unit or
Unit models used with 1RC0456, 1RC0458 roof curb through the roof curb the following field-installed
XYEA7 accessories can be purchased through your dealer or
contractor:
XYE/XQE04
1TB0401 - Through the base electrical
XYE/XQE05 1TB0402 - Through the base electrical
XYE/XQE06/XXEA7 1TB0403 - Through the base electrical
1TB0404 - Through the base electrical
132 Johnson Controls Ducted Systems
5147362-YTG-R-0323
XYEA7-09 and XXE08-12 unit clearances
Direction Distance (in.) Direction Distance (in.)
Top1 72 Right 18
Front 48 Left 12
Rear 182/363 Bottom4 1
1. Units must be installed outdoors. Over hanging structure or
shrubs should not obscure condenser air discharge outlet.
2. Units without economizer or power exhaust.
3. Units equipped with an Economizer or Power Exhaust. Flue
products must not be discharged within 10 Feet of the rear of
the unit.
4. Units may be installed on combustible floors made from wood
or class A, B or C roof covering materials.
XYEA7-09, XXE08-09 and XXE12 unit roof curb dimensions
1RC0457, 1RC0459 roof curb dimensions
81.750 O.D.
78.250 I.D.
40.188
RN
RN
TU
RETU
RE
15.469
3.000
50.000
I.D. RIGHT
LY
LY
PP
PP
34.313 31.531
SU
SU
11.417
15.813
FRONT
6.043 RIGHT
4.173
26.000
FRONT 24.813
84.000 O.D. 53.500 O.D.
81.746 53.496
1RC0457 X= 14" Height
1RC0459 X= 24" Height
Notes:
1. Sides, ends, unit locator and cross support are 18-G90. Deck pans, R/A & S/A supports are 20-G90.
2. Full perimeter wood nailer.
3. Insulated deck pans.
Note: If utilities are required through the base of the unit or
Unit models used with 1RC0457, 1RC0459 roof curb through the roof curb the following field-installed
XYEA7 accessories can be purchased through your dealer or
contractor:
XYE08/XXE08
XYE09/XXE09 1TB0404 - Through the base electrical
XXE12
Johnson Controls Ducted Systems 133
5147362-YTG-R-0323
Economizer options
Economizer usage
Application Description Accessory kit number
Econ, DB, Vertical Flow, Small Footprint 2EE04706724
Economizer Vertical Flow
Econ, DB, Vertical Flow, Large Footprint 2EE04706824
Econ, DB, Horizontal Flow, Small Footprint, Short Cabinet 2EE04707024
Econ, DB, Horizontal Flow, Small Footprint, Tall Cabinet 2EE04707124
Economizer Horizontal Flow
Econ, DB, Horizontal Flow, Large Footprint, Short Cabinet 2EE04707224
Econ, DB, Horizontal Flow, Large Footprint, Tall Cabinet 2EE04707324
Power Exhaust Vert Flow Small Footprint 208V-230V 1-ph 2PE04704206
Power Exhaust Vert Flow Small Footprint 208V-230V 3-ph 2PE04704225
Power Exhaust Vert Flow Small Footprint 460V 3-ph 2PE04704246
Power Exhaust Vert Flow Small Footprint 575V 3-ph 2PE04704258
Power Exhaust Vertical Flow
Power Exhaust Vert Flow Large Footprint 208V-230V 1-ph 2PE04704306
Power Exhaust Vert Flow Large Footprint 208V-230V 3-ph 2PE04704325
Power Exhaust Vert Flow Large Footprint 460V 3-ph 2PE04704346
Power Exhaust Vert Flow Large Footprint 575V 3-ph 2PE04704358
Power Exhaust Horiz Flow Small Footprint 208V-230V 1-ph 2PE04704406
Power Exhaust Horiz Flow Small Footprint 208V-230V 3-ph 2PE04704425
Power Exhaust Horiz Flow Small Footprint 460V 3-ph 2PE04704446
Power Exhaust Horiz Flow Small Footprint 575V 3-ph 2PE04704458
Power Exhaust Horizontal Flow
Power Exhaust Horiz Flow Large Footprint 208V-230V 1-ph 2PE04704506
Power Exhaust Horiz Flow Large Footprint 208V-230V 3-ph 2PE04704525
Power Exhaust Horiz Flow Large Footprint 460V 3-ph 2PE04704546
Power Exhaust Horiz Flow Large Footprint 575V 3-ph 2PE04704558
Field-installed vertical flow economizer
134 Johnson Controls Ducted Systems
5147362-YTG-R-0323
Field-installed vertical flow economizer w/power exhaust
Field-installed horizontal flow economizer
Johnson Controls Ducted Systems 135
5147362-YTG-R-0323
Field-installed horizontal flow economizer w/power exhaust
136 Johnson Controls Ducted Systems
5147362-YTG-R-0323
Guide specifications
YORK® guide mechanical specifications
Single package heat pumps
3 through 10 nominal tons
York® Sun™ Core Series
Size range:3 to 10 tons nominal cooling
Model series: XYE/XXE/XQE
Division 23 – heating, ventilating, and air-conditioning (HVAC)
Number Title
23 00 00 Heating, ventilating, and air-conditioning (HVAC)
23 06 00 Schedules for HVAC
23 06 80 Schedules for Decentralized HVAC Equipment
23 06 80.13 Decentralized Unitary HVAC Equipment Schedule
23 06 80.13.A. Rooftop unit schedule
23 07 00 HVAC Insulation
23 07 16 HVAC Equipment Insulation
23 07 16.13 Decentralized, Rooftop Units:
23 07 16.13.A. Evaporator fan compartment:
1. Interior cabinet surfaces shall be insulated with a minimum 1/2- in. thick, minimum 1 1/2 lb density, flexible
fiberglass insulation coated on the air side.
2. Insulation and adhesive shall meet NFPA 90A requirements for flame spread and smoke generation.
23 07 16.13.B. Gas heat compartment:
1. Aluminum foil- faced fiberglass insulation shall be used.
2. Insulation and adhesive shall meet NFPA 90A requirements for flame spread and smoke generation.
23 09 00 Instrumentation and Control for HVAC
23 09 13 Instrumentation and Control Devices for HVAC
23 09 13.23 Sensors and Transmitters
Johnson Controls Ducted Systems 137
5147362-YTG-R-0323
23 09 13.23.A. Thermostats
48HC
1. Thermostat must
a. energize “G” when calling for fan only or continuous fan.
b. have capability to energize 2 different stages of cooling, and 2 different stages of heating.
c. include capability for occupancy scheduling.
23 09 23 Direct- digital Control system for HVAC
23 09 23.13 Decentralized, Rooftop Units:
23 09 23.13.A. Smart Equipment™ (Unit based microprocessor control)
1. Shall be ASHRAE 62 compliant.
2. Shall include an integrated economizer controller to support an economizer with 2 to 10 v DC actuator input.
3. Controller shall accept the following inputs: space temperature, setpoint adjustment, outdoor air temperature,
indoor air quality, outdoor air quality, indoor relative humidity, compressor lockout, fire shutdown, enthalpy,
fan status, remote time clock/door switch.
4. Shall accept a CO2 sensor in the conditioned space, and be Demand Control Ventilation ready.
5. Unit shall provide surge protection for the controller through a circuit breaker.
6. Shall have an LED display independently showing the status of activity on the communication bus, and
processor operation.
7. Software upgrades will be accomplished by local download. Software upgrades through chip replacements
are not allowed.
A. Unit shall be complete with self-contained low-voltage control circuit protected by a resettable circuit breaker
on the 24-volt transformer side.
B. Unit shall incorporate a lockout circuit which provides reset capability at the space thermostat or base unit
should any of the following standard safety devices trip and shut off compressor:
C. Loss-of-charge/Low-pressure switch.
D. High-pressure switch.
E. Freeze-protection temperature sensor, evaporator coil. If any of the above safety devices trip, an LED (light-
emitting diode) indicator shall flash a diagnostic code that indicates which safety switch has tripped.
F. Unit shall incorporate “AUTO RESET” compressor over temperature, over current protection.
G. Unit shall operate with conventional thermostat designs and have a low voltage terminal strip for easy hook-up.
H. Unit control board shall have on-board diagnostics and fault code display.
I. Standard controls shall include anti-short cycle and low voltage protection, and permit cooling operation down
to 45 ºF.
J. Control board shall monitor each refrigerant safety switch independently.
K. Control board shall retain last 5 fault codes in non-volatile memory, which will not be lost in the event of a
power loss.
23 09 23.13.B. RTU Open - multi- protocol, direct digital controller:
1. Shall be ASHRAE 62 compliant.
2. Shall include built- in protocol for BACNET , Modbus , and Johnson N2.
3. Shall allow access of up to 62 network variables (SNVT). Shall be compatible with all open controllers
4. Baud rate Controller baud rate setting shall be selected in the Smart Equipment control.
5. Shall have an LED display independently showing the status of serial communication, running, errors, power,
all digital outputs, and all analog inputs.
138 Johnson Controls Ducted Systems
5147362-YTG-R-0323
6. Shall accept the following inputs: space temperature, setpoint adjustment, outdoor air temperature, indoor air
quality, outdoor air quality, compressor lock- out, fire shutdown, enthalpy switch, and fan status/filter status/
humidity/ remote occupancy.
7. Software upgrades will be accomplished by local download. No software upgrades through chip
replacements are allowed.
23 09 33 Electric and Electronic Control System for HVAC
23 09 33.13 Decentralized, Rooftop Units:
23 09 33.13.A. General:
1. Shall be complete with self- contained low- voltage control circuit protected by a resettable circuit breaker on
the 24- v transformer side. Transformer shall have 75VA capability.
2. Shall utilize color- coded wiring.
3. Shall include a central control terminal board to conveniently and safely provide connection points for vital
control functions such as: smoke detectors, phase monitor, gas controller, economizer, thermostat, DDC
control options, and low and high pressure switches.
23 09 33.23.B. Safeties:
1. Compressor over- temperature, over- current. High internal pressure differential.
2. Low- pressure switch.
a. Low pressure switch shall use different color wire than the high pressure switch. The purpose is to assist
the installer and service technician to correctly wire and or troubleshoot the rooftop unit.
3. High- pressure switch.
a. High pressure switch shall use different color wire than the low pressure switch. The purpose is to assist
the installer and service technician to correctly wire and or troubleshoot the rooftop unit.
4. Automatic reset, motor thermal overload protector.
23 09 93 Sequence of Operations for HVAC Controls
23 09 93.13 Decentralized, Rooftop Units:
23 09 93.13 INSERT SEQUENCE OF OPERATION
23 40 13 Panel Air Filters
23 40 13.13 Decentralized, Rooftop Units:
23 40 13.13.A. Standard filter section
1. Shall consist of factory- installed, low velocity, disposable 2 in. thick fiberglass filters of commercially
available sizes.
2. Units can accept 2 in. filters
3. Filters shall be accesible through an access panel with toolless removal as described in the unit cabinet
section of this specification (23 81 19.13.H).
23 81 19 Self- Contained Air Conditioners
23 81 19.13 Small- Capacity Self- Contained Air Conditioners
23 81 19.13.A. General
1. Outdoor, rooftop mounted, electrically controlled, heating and cooling unit utilizing a fully hermetic scroll
compressor(s) for cooling duty and gas combustion for heating duty.
2. Factory assembled, single- piece heating and cooling rooftop unit. Contained within the unit enclosure shall
be all factory wiring, piping, controls, and special features required prior to field start- up.
3. Unit shall use environmentally sound, R-410A refrigerant.
Johnson Controls Ducted Systems 139
5147362-YTG-R-0323
4. Unit shall be installed in accordance with the manufacturer’s instructions.
5. Unit must be selected and installed in compliance with local, state, and federal codes.
23 81 19.13.B. Quality Assurance
1. Unit meets ASHRAE 90.1 minimum efficiency requirements.
2. XYE units are Energy Star certified.
3. Unit shall be rated in accordance with AHRI Standards 210/240 or 340/360.
4. Unit shall be designed to conform to ASHRAE 15.
5. Unit shall be UL- tested and certified in accordance with ANSI Z21.47 -2012/CSA 2.3-2012, CSA C22.2 No.
236-11 (UL 1995) 4th edition and CSA C22.2 No. 3 - M 1988.
6. Insulation and adhesive shall meet NFPA 90A requirements for flame spread and smoke generation.
7. Unit casing shall be capable of withstanding 750- hour salt spray exposure per ASTM B117 (scribed
specimen).
8. Unit shall be designed in accordance with ISO 9001, and shall be manufactured in a facility registered by ISO
9001.
9. Roof curb shall be designed to conform to NRCA Standards.
10. Unit shall be subjected to a completely automated run test on the assembly line. The data for each unit will
be stored at the factory, and must be available upon request.
11. Unit shall be designed in accordance with UL Standard 1995 Fourth Edition, including tested to withstand
rain.
12. Unit shake tested to assurance level 1, ASTM D4169 to ensure shipping reliability.
13. High Efficient Motors listed shall meet section 313 of the Energy Independence and Security Act of 2007
(EISA 2007).
23 81 19.13.C. Delivery, Storage, and Handling
1. Unit shall be stored and handled per manufacturer’s recommendations.
23 81 19.13.E. Project Conditions
1. As specified in the contract.
23 81 19.13.F. Operating Characteristics
1. Unit shall be capable of starting and running at 125°_F (52°_C) ambient outdoor temperature, meeting
maximum load criteria of AHRI Standard 210/240 or 340/360 at ± 10% voltage.
2. Compressor with standard controls shall be capable of operation down to 40°_F (4°_C), ambient outdoor
temperatures. See below for head pressure control package or winter start kit.
3.Unit shall discharge supply air vertically or horizontally as shown on contract drawings.
4.Unit shall be factory configured for vertical supply and return configurations.
5.Unit shall be field convertible from vertical to horizontal airflow on all models.
6.Unit shall be capable of mixed operation: vertical supply with horizontal return or horizontal supply with vertical
return.
23 81 19.13.G. Electrical Requirements
1. Main power supply voltage, phase, and frequency must match those required by the manufacturer.
23 81 19.13.H. Unit Cabinet
1. Unit cabinet shall be constructed of galvanized steel with exterior surfaces coated with a non-chalking,
powder paint finish, certified at 750 hour salt spray test per ASTM-B117 standards.
2. Evaporator fan compartment interior cabinet insulation shall conform to AHRI Standards 210/240 or 340/360
minimum exterior sweat criteria. Interior surfaces shall be insulated with a minimum 1/2- in. thick, 1 1/2 lb
density, flexible fiberglass insulation, neoprene coated on the air side. Aluminum foil- faced fiberglass
insulation shall be used in the electric heat compartment. Fan shall be a direct drive or belt drive assembly and
include an adjustable pitch motor pulley. Job site selected brake horsepower shall not exceed the motors
140 Johnson Controls Ducted Systems
5147362-YTG-R-0323
nameplate horsepower rating plus the service factor (Only premium efficiency motors have hp rating on the
nameplate). Units shall be designed to operate within the service factor. Fan wheel shall be double inlet type
with forward curve blades, dynamically balanced to operate smoothly throughout the entire range of operation.
Airflow design shall be constant volume. Bearings shall be sealed and permanently lubricated for longer life
and no maintenance.
Condenser Fan Assembly: The outdoor fans shall be of the direct drive type, discharge air vertically, have
aluminum blades riveted to corrosion resistant steel spider brackets and shall be dynamically balanced for
smooth operation. The outdoor fan motors shall have permanently lubricated bearings internally protected
against overload conditions and staged independently.
3. Base of unit shall have a minimum of four locations for through- the- base gas and electrical connections (field-
installed), standard.
4. Base Rail
a. Unit shall have base rails on a minimum of 4 sides.
b. Holes shall be provided in the base rails for rigging shackles to facilitate maneuvering and overhead
rigging.
c. Holes shall be provided in the base rail for moving the rooftop by fork truck.
d. Base rail shall be a minimum of 16 gauge thickness.
5. Condensate pan and connections:
a. Shall be an internally sloped condensate drain pan made of a non- corrosive material. b. Shall comply with
ASHRAE Standard 62.
c. Shall use a 3/4 in. - 14 NPT drain connection, possible either through the bottom or side of the drain pan.
Connection shall be made per manufacturer’s recommendations.
6. Top panel:
a. Shall be a single piece top panel.
7. Electrical Connections
a. All unit power wiring shall enter unit cabinet at a single, factory- prepared, knockout location. b. through-
the- base capability.
(1.) Standard unit shall have a through- the- base electrical location (s) using a raised, embossed portion of
the unit base-pan.
(2.) Optional, factory- approved, water- tight connection method must be used for through- the- base
electrical connections.
(3.) No base-pan penetration, other than those authorized by the manufacturer, is permitted.
8. Component access panels (standard)
a. Cabinet panels shall be easily removable for servicing.
b. Unit shall have one factory-installed, toolless, removable, filter access panel.
c. Panels covering control box, indoor fan, indoor fan motor, gas components (where applicable), and
compressors shall have a molded composite handles.
d. Handles shall be UV modified, composite. They shall be permanently attached, and recessed into the
panel.
e. Screws on the vertical portion of all removable access panel shall engage into heat resistant, molded
composite collars.
f. Collars shall be removable and easily replaceable using manufacturer recommended parts.
23 81 19.13.J. Coils
1. Standard Aluminum Fin/Copper Tube Coils:
a. Standard evaporator and condenser coils shall have aluminum lanced plate fins mechanically bonded to
seamless internally grooved copper tubes with all joints brazed.
Johnson Controls Ducted Systems 141
5147362-YTG-R-0323
b. Evaporator coils shall be leak tested to 150 psig, pressure tested to 450 psig, and qualified to CSA C22.2
No. 236-11 (UL 1995) 4th edition burst test at 1775 psig.
c. Condenser coils shall be leak tested to 150 psig, pressure tested to 650 psig, and qualified to CSA C22.2
No. 236-11 (UL 1995) 4th edition burst test at 1980 psig.
2. Optional E-Coat- coated aluminum- fin evaporator and condenser coils:
a. Shall have a durable epoxy- phenolic coating to provide protection in mildly corrosive coastal
environments.
b. Coating shall be applied to the aluminum fin stock prior to the fin stamping process to create an inert barrier
between the aluminum fin and copper tube.
c. Epoxy- phenolic barrier shall minimize galvanic action between dissimilar metals.
23 81 19.13.K. Refrigerant Components
1. Refrigerant circuit shall include the following control, safety, and maintenance features:
a. Thermostatic Expansion Valve (TXV) shall help provide optimum performance across the entire operating
range. Shall contain removable power element to allow change out of power element and bulb without
removing the valve body. (Orifice on 3 - 5 Ton Units)
b. Refrigerant filter drier - Solid core design.
c. Service gauge connections on suction and discharge lines.
d. Pressure gauge access through a specially designed access port in the top panel of the unit.
2. There shall be gauge line access port in the skin of the rooftop, covered by a black, removable plug.
a. The plug shall be easy to remove and replace.
b. When the plug is removed, the gauge access port shall enable maintenance personnel to route their
pressure gauge lines.
c. This gauge access port shall facilitate correct and accurate condenser pressure readings by enabling the
reading with the compressor access panel on.
d. The plug shall be made of a leak proof, UV- resistant, composite material.
3. Compressors
a. Unit shall use fully hermetic, scroll compressor for each independent refrigeration circuit.
b. Compressor motors shall be cooled by refrigerant gas passing through motor windings.
c. Compressors shall be internally protected from high discharge temperature conditions.
d. Compressors shall be protected from an over- temperature and over- amperage conditions by an internal,
motor overload device.
e. Compressor shall be factory mounted on rubber grommets.
f. Compressor motors shall have internal line break thermal, current overload and high pressure differential
protection.
g. Crankcase heaters shall not be required for normal operating range, unless provided by the factory.
23 81 19.13.L. Filter Section
1. Filters access is specified in the unit cabinet section of this specification.
3. Shall consist of factory- installed, low velocity, throw- away 2 in. thick fiberglass filters.
3. Units can accept 2 in. filters
23 81 19.13.M. Evaporator Fan and Motor
1. Evaporator fan motor:
a. Shall have permanently lubricated bearings.
b. Shall have inherent automatic reset thermal protection (Only on single-phase, belt-drive motors, three -
phase, belt-drive motors have internal thermostat used for external line-break control.).
2. Electric Drive (Direct Drive) X13 – 5 Speed/Torque Evaporator Fan:
a. Multi- speed motor with easy quick adjustment settings.
142 Johnson Controls Ducted Systems
5147362-YTG-R-0323
b. Blower fan shall be double- inlet type with forward- curved blades.
48HC
c. Shall be constructed from steel with a corrosion resistant finish and dynamically balanced.
3. Belt- driven Evaporator Fan:
a. Belt drive shall include an adjustable- pitch motor pulley.
b. Shall use sealed, permanently lubricated ball- bearing type.
c. Blower fan shall be double- inlet type with forward- curved blades.
d. Shall be constructed from steel with a corrosion resistant finish and dynamically balanced.
23 81 19.13.N. Condenser Fans and Motors
The outdoor fans shall be of the direct drive type, discharge air vertically, have aluminum blades riveted to corrosion
resistant steel spider brackets and shall be dynamically balanced for smooth operation. The outdoor fan motors shall
have permanently lubricated 60°C ball bearings internally protected against overload conditions and staged
independently.
1. Condenser fan motors:
a. Shall be a totally enclosed motor.
b. Shall use permanently lubricated bearings.
c. Shall have inherent thermal overload protection with an automatic reset feature.
d. All models shall use a shaft- down design.
2. Condenser Fans:
a. Shall be a direct- driven propeller type fan.
b. Shall have galvanized steel blades riveted to corrosion- resistant steel spiders and shall be dynamically
balanced.
23 81 19.13.O. Special Features Options and Accessories
1. Standard Integrated Economizers:
a. Integrated, gear- driven opposing modulating blade design type capable of simultaneous economizer and
compressor operation.
b. Independent modules for vertical or horizontal return configurations shall be available. Vertical return
modules shall be available as a factory-installed option.
c. Damper blades shall be galvanized steel with composite gears. Plastic or composite blades on intake or
return shall not be acceptable.
d. Shall include all hardware and controls to provide free cooling with outdoor air when temperature and/or
humidity are below set-points.
e. Shall be equipped with gear driven dampers for both the outdoor ventilation air and the return air for
positive air stream control.
f. Standard models shall be equipped with low- leakage dampers, not to exceed 2% leakage at 1 in. wg pres-
sure differential. Economizers will come with Actuator and module that is tied to Smart Equipment™:
(1.) Combined minimum and DCV maximum damper position potentiometers with compressor staging re-
lay.
(2.) Functions with solid state analog enthalpy or dry bulb changeover control sensing.
(3.) Contain LED indicates for: when free cooling is available when module is in DCV mode when exhaust
fan contact is closed
2. Two- Position Damper
a. Damper shall be a Two- Position Damper. Damper travel shall be from the full closed position to the field
adjustable %- open setpoint.
b. Damper shall include adjustable damper travel from 25% to 100% (full open).
c. Damper shall include single or dual blade, gear driven dampers and actuator motor.
d. Actuator shall be direct coupled to damper gear. No linkage arms or control rods shall be acceptable. e.
Damper will admit up to 100% outdoor air for applicable rooftop units.
Johnson Controls Ducted Systems 143
f. Damper shall close upon indoor (evaporator) fan shutoff and/or loss of power.
g. The damper actuator shall plug into the rooftop unit’s wiring harness plug. No hard wiring shall be required.
h. Outside air hood shall include aluminum water entrainment filter.
3. Manual damper
a. Manual damper package shall consist of damper, air inlet screen, and rain hood which can be preset to admit
up to 25 or 50% outdoor air for year round ventilation.
4. Condenser Coil Hail Guard Assembly (factory and field-installed on all models):
a. Shall protect against damage from hail.
b. Shall be of louvered style.
5. Unit- Mounted, Non- Fused Disconnect Switch:
a. Switch shall be factory- installed, internally mounted.
b. National Electric Code (NEC) and UL approved non- fused switch shall provide unit power shutoff.
c. Shall be accessible from outside the unit.
d. Shall provide local shutdown and lockout capability.
6. through- the- Base Connectors:
a. Kits shall provide connectors to permit gas and electrical connections to be brought to the unit through the unit
base-pan.
b. Minimum of four connection locations per unit.
7. Propeller Power Exhaust:
a. Power exhaust shall be used in conjunction with an integrated economizer.
b. Independent modules for vertical or horizontal return configurations shall be available.
c. Horizontal power exhaust shall be mounted in return ductwork.
d. Power exhaust shall be controlled by economizer controller operation. Exhaust fans shall be energized when
dampers open past the 0- 100% adjustable setpoint on the economizer control.
8. Roof Curbs (Vertical):
a. Full perimeter roof curb with exhaust capability providing separate air streams for energy recovery from the
exhaust air without supply air contamination.
b. Formed galvanized steel with wood nailer strip and shall be capable of supporting entire unit weight.
c. Permits installation and securing of ductwork to curb prior to mounting unit on the curb.
9. Outdoor Air Enthalpy Sensor:
a. The outdoor air enthalpy sensor shall be used to provide single enthalpy control. When used in conjunction
with a return air enthalpy sensor, the unit will provide differential enthalpy control. The sensor allows the unit
to determine if outside air is suitable for free cooling.
10. Return Air Enthalpy Sensor:
a. The return air enthalpy sensor shall be used in conjunction with an outdoor air enthalpy sensor to provide
differential enthalpy control.
11. Indoor Air Quality (CO2) Sensor:
a. Shall be able to provide demand ventilation indoor air quality (IAQ) control.
b. The IAQ sensor shall be available in duct mount, wall mount, or wall mount with LED display. The set- point
shall have adjustment capability.
c. Shall be environmental compensated with differential sensing for reliable, stable, and drift- free sensitivity.
d. Shall use magnet- activated test/reset sensor switches.
e. Shall have tool- less connection terminal access.
Subject to change without notice. Printed in U.S.A. 5147362-YTG-R-0323
Copyright © 2023 by Johnson Controls, Inc. All rights reserved. Supersedes: 5147362-YTG-Q-0722
York International Corporation
5005 York Drive
Norman, OK 73069