0% found this document useful (0 votes)
46 views18 pages

3 Measurementss

The document outlines the curriculum for Unit 3 of the ADNOC Technical Institute's instrumentation course, focusing on pressure transmitters. It covers the operation of pneumatic devices such as flapper-nozzles, pneumatic relays, and transmitters, as well as the transition to electrical pressure transmitters. Key objectives include understanding the components, functions, and calibration of these instruments in pressure measurement systems.

Uploaded by

waleed El-azab
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
46 views18 pages

3 Measurementss

The document outlines the curriculum for Unit 3 of the ADNOC Technical Institute's instrumentation course, focusing on pressure transmitters. It covers the operation of pneumatic devices such as flapper-nozzles, pneumatic relays, and transmitters, as well as the transition to electrical pressure transmitters. Key objectives include understanding the components, functions, and calibration of these instruments in pressure measurement systems.

Uploaded by

waleed El-azab
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 18

Abu Dhabi National Oil Co.

ADNOC Technical Institute

INSTRUMENTATION
INSTRUMENTATION 1

UNIT 3

THE PRESSURE TRANSMITTER

PAGE 1 OF 18 INST 1 - THE PRESSURE TRANSMITTER


DATE OF ISSUE 6/17/2013 REV O
IN-01-03.DOC
ADNOC - Technical Institute

PAGE 2 OF 18 INST 1 - THE PRESSURE TRANSMITTER


DATE OF ISSUE 6/17/2013 REV O
IN-01-03.DOC
ADNOC - Technical Institute

UNITS IN THIS COURSE

UNIT 1 INTRODUCTION TO INSTRUMENTATION

UNIT 2 PRESSURE MEASUREMENT

UNIT 3 THE PRESSURE TRANSMITTER

UNIT 4 FLOW MEASUREMENT

UNIT 5 MEASUREMENT OF LEVEL

UNIT 6 PRACTICAL TASKS

INST 1 - THE PRESSURE TRANSMITTER PAGE 3 OF 18


REV 0 DATE OF ISSUE 6/17/2013
IN-01-03.DOC
ADNOC - Technical Institute

PAGE 4 OF 18 INST 1 - THE PRESSURE TRANSMITTER


DATE OF ISSUE 6/17/2013 REV O
IN-01-03.DOC
ADNOC - Technical Institute

TABLE OF CONTENTS
Para Page

3.0 COURSE OBJECTIVES 7


3.1 INTRODUCTION 8
3.2 THE FLAPPER-NOZZLE 9
3.3 THE PNEUMATIC RELAY 10
3.4 THE PNEUMATIC TRANSMITTER 11
3.5 THE PNEUMATIC SIGNAL LOOP 14
3.6 THE AIR PRESSURE REGULATOR 14
3.7 THE ELECTRICAL PRESSURE TRANSMITTER 16

INST 1 - THE PRESSURE TRANSMITTER PAGE 5 OF 18


REV 0 DATE OF ISSUE 6/17/2013
IN-01-03.DOC
ADNOC - Technical Institute

PAGE 6 OF 18 INST 1 - THE PRESSURE TRANSMITTER


DATE OF ISSUE 6/17/2013 REV O
IN-01-03.DOC
ADNOC - Technical Institute

3.0 COURSE OBJECTIVES

The student will be able to:

 Explain the operation of a simple flapper nozzle.

 Explain the function of a pneumatic relay.

 Using a diagram, name the parts of a typical pneumatic transmitter.

 Explain the need for the feedback (positioning) bellows.

 State the standard signals produced by a pneumatic transmitter.

 Draw the layout of a typical electrical transmission loop.

 State the standard signals produced by an electrical transmitter

INST 1 - THE PRESSURE TRANSMITTER PAGE 7 OF 18


REV 0 DATE OF ISSUE 6/17/2013
IN-01-03.DOC
ADNOC - Technical Institute

3.1 INTRODUCTION

The previous unit (Unit 2) explained the basic devices used to measure
and indicate pressure. This unit will describe the methods used to
convert the pressure measurement to an instrument signal for the
controller.

PAGE 8 OF 18 INST 1 - THE PRESSURE TRANSMITTER


DATE OF ISSUE 6/17/2013 REV O
IN-01-03.DOC
ADNOC - Technical Institute

3.2 THE FLAPPER-NOZZLE

The flapper-nozzle is the primary device for all pneumatic instruments


which convert a measurement to a pneumatic signal. Figure 3-1 shows
the layout of the device.
PIVOT

RESTRICTOR APPLIED
MEASURED VALUE

FLAPPER
AIR SUPPLY V x
INPUT

NOZZLE

AIR SIGNAL
OUTPUT

Figure 3-1 The Flapper-Nozzle

Operation:

The air supply input (20 psi (1.4 bar)) passes through a restrictor (small
hole). It then goes out of the nozzle or down the air signal output line. If
the flapper is placed against the nozzle, no air can escape through it. So,
the air signal output shows full pressure. If the flapper is pulled away
from the nozzle, most of the air flows out of the nozzle, so the air signal
output pressure is very small. The back pressure output signal depends
on how near the flapper is to the nozzle. A simple graph of the output
pressure (P) against flapper distance (X) is shown below.

P
MAXIMUM A

OUTPUT
PRESSUR
E
B

X FLAPPER
DISTANCE
0 MAXIMUM
The graph is linear (straight) over the distance A B. This reflects only a
few millimetres of travel of the flapper. This part of the curve is used to
convert a change in a measured value connected to the flapper into an
output signal. The restrictor increases the speed of operation. The small
volume (V) can change pressure quickly before the air supply can pass
through the small hole in the restrictor.

INST 1 - THE PRESSURE TRANSMITTER PAGE 9 OF 18


REV 0 DATE OF ISSUE 6/17/2013
IN-01-03.DOC
ADNOC - Technical Institute

The change in output pressure due to flapper movement is very small. It


must be enlarged (amplified) using a device called a PNEUMATIC
RELAY.

3.3 THE PNEUMATIC RELAY

Different manufacturers make pneumatic relays in different ways.


However, they all work on the same principle. A simplified explanation of
this device is given in Figure 3-2.

FLAPPER NOZZLE
OUTPUT PRESSURE

DIAPHRAGM

VENT
AMPLIFIED
OUTPUT SIGNAL

BALL VALVE AIR SUPPLY


CONTROLLING
SPRING

Figure 3-2 The Pneumatic Relay

Operation:

The output pressure from the flapper-nozzle goes to the top of the
diaphragm. The diaphragm moves down against the controlling spring
and opens the ball valve. The air supply now enters the area under the
diaphragm and goes into the output.

At some point, the pressure from the air supply under the diaphragm will
equal the pressure above. The diaphragm moves up and the ball valve
closes and they hold momentarily at that pressure. If the flapper-nozzle
pressure increases, the ball valve will open and hold momentarily at the
new higher output pressure. If the pressure on the diaphragm decreases,
the ball valve stays closed and the output signal falls as air escapes
through the vent. When the output pressure has fallen enough the ball
valve opens again to maintain the output at the new lower pressure. This
kind of relay is called a continuous bleed device because it controls the
output signal pressure by slowly venting the air supply all the time.

The standard amplified signal from the relay is:


(a) 3 -15 psi imperial (b) 0.2 -1 bar ISO.

PAGE 10 OF 18 INST 1 - THE PRESSURE TRANSMITTER


DATE OF ISSUE 6/17/2013 REV O
IN-01-03.DOC
ADNOC - Technical Institute

Remember that these standards are not the same. The control system
can work on (a) or (b). It must never work on a mixture of the two
standards.

3.4 THE PNEUMATIC TRANSMITTER

There are many different types of pneumatic pressure transmitters.


However, they are not used much nowadays.

One of the few types still in use is the Foxboro type 11. This is shown
below as an example of the pneumatic transmitter.

RESTRICTION AIR SUPPLY

RELAY

NOZZLE
FLAPPER
FLEXURE CONNECTOR
OUTPUT SIGNAL

RANGE WHEEL
(SPAN ADJUSTMENT)

FORCE BAR

RANGE ROD

FEEDBACK BELLOWS

ZERO SETTING
DIAPHRAGM SEAL

PRESSURE
DIAPHRAGM CAPSULE

Figure 3-3 The Pneumatic Pressure Transmitter

Figure 3-3 shows the basic design of a Foxboro pressure transmitter.

Operation:

INST 1 - THE PRESSURE TRANSMITTER PAGE 11 OF 18


REV 0 DATE OF ISSUE 6/17/2013
IN-01-03.DOC
ADNOC - Technical Institute

 The process pressure to be measured and transmitted as a standard


signal is applied to a diaphragm capsule.

 The pressure moves the capsule. This movement is applied to one


end of a force bar pivoted about the diaphragm seal.

 The force bar moves the flexible connector. The connector pulls the
flapper to and from the nozzle.

 The back pressure from the nozzle is amplified by the relay. This
gives the standard output signal.

The system is not stable. The flapper will go either full on or full off. So a
feedback bellows is added. The output signal goes to the bellows. The
bellows applies a force to the range rod in opposition to the force bar.
The system balances to give an output signal which depends on the
position of the range wheel.

FLAPPER

APPLIED FEEDBACK
PRESSURE MOVEMENT
MOVEMENT

B C
RANGE ROD
FORCE BAR

DIAPHRAGM RANGE WHEEL


SEAL

A D
FEEDBACK
BELLOWS
PRESSURE
APPLIED

Figure 3-4 Balancing action

Figure 3-4 shows the balancing action of the transmitter. The movement
of the flapper is the pressure applied times B over A (B:A). The feedback
movement is the output pressure times the ratio D:C.

The ratio B:A is fixed but D:C can be changed by the range wheel. If the
D:C ratio is large the feedback is small. This makes the range larger.

Calibration Adjustments

PAGE 12 OF 18 INST 1 - THE PRESSURE TRANSMITTER


DATE OF ISSUE 6/17/2013 REV O
IN-01-03.DOC
ADNOC - Technical Institute

 When there is no pressure (zero gauge), the zero spring, which sets
the force on the range rod, is adjusted for a 3 psi or 0.2 bar output
signal.

 With the maximum pressure (range) applied, the range wheel is


adjusted to give 15 psi or 1 bar output signal.

Note : Figure 3-3 shows a gauge pressure transmitter. This


transmitter can easily be adapted to measure differential
pressure. This is done by adding an extra input to the
diaphragm capsule as shown below. The force bar now
moves according to the differential pressure applied.
Remember the device must be connected correctly to the high
and low pressure connections. It will not read correctly if it is
connected the wrong way round.

HIGH PRESSURE LOW


PRESSURE

DIFFERENTIAL PRESSURE APPLIED TO THE


CAPSULE

DIAPHRAGM CAPSULE
ABSOLUTE PRESSURE
REFERENCE PRESSURE TO
BE MEASURED.

ABSOLUTE PRESSURE APPLIED TO THE CAPSULE

INST 1 - THE PRESSURE TRANSMITTER PAGE 13 OF 18


REV 0 DATE OF ISSUE 6/17/2013
IN-01-03.DOC
ADNOC - Technical Institute

3.5 THE PNEUMATIC SIGNAL LOOP

20 psi AIR PRESSURE


REGULATOR MAIN AIR SUPPLY 100 psi

SIGNAL LINE
ISOLATION VALVE 3-15 psi
PROCESS LINE RECEIVER CONTROLLER
PRESSURE
TRANSMITTER
CONNECTIO
N
DRAIN VALVE

Figure 3-5 The Pneumatic Signal Loop

Figure 3-5 shows a block diagram of the pneumatic signal loop :-

 The process line to the pressure transmitter (usually 3/8” or 1/4”


stainless steel tubing) has an isolation valve and a drain valve so it
can be disconnected.

 The pressure transmitter has an air supply set at 20 psi. This comes
through the air pressure regulator from the main air supply (usually
about 100 psi).

 There is a signal line (usually 1/4” stainless steel tubing) which


transmits the signal (3-15 psi) to the receiver in the controller.

3.6 THE AIR PRESSURE REGULATOR

The air pressure regulator is a simple device. It is used to lower the main
instrument air supply of a plant to a pressure suitable for an air-operated
instrument; eg, a transmitter, control valve, etc.

Normally, each air operated instrument has its own regulator. So an air
regulator is one of the most common devices in the plant. There are
various manufacturers of air regulators, eg, Masoneilan and Fisher.
However, they all work in much the same way. The example given is
manufactured by Fisher (see Figure 3-6).

PAGE 14 OF 18 INST 1 - THE PRESSURE TRANSMITTER


DATE OF ISSUE 6/17/2013 REV O
IN-01-03.DOC
ADNOC - Technical Institute

ADJUSTING SCREW

RANGE SPRING
DIAPHRAGM
VENT
AIR PASSAGE
IN OUT

VALVE ASSEMBLY

FILTER

INLET CHAMBER

DRAIN

Figure 3-6 The Air Pressure Regulator

Operation:

 The main air supply is connected to the IN port. Air passes into the
inlet chamber at the bottom of the regulator.

 Air passes through the filter which removes dirt particles in the
incoming air which may block nozzles etc. It then goes into the valve
assembly.

 The valve assembly is moved by the range spring pressing on the


diaphragm.

 The range spring will hold the valve assembly down until the output
pressure is high enough to lift the diaphragm (via the air passage
shown). At this point the small spring in the valve assembly closes the
valve.

 Air is allowed to pass through a hole at the centre of the diaphragm


and out of the vent. This maintains balanced pressure across the
diaphragm.

 If the outlet pressure is above the pressure set by the range spring,
the air will go out through the vent above the diaphragm. When the
outlet pressure is correct, the valve assembly opens to set the correct
pressure.

 If the outlet pressure is below the pressure set by the range spring the
valve assembly will stay open until the set pressure is reached.

INST 1 - THE PRESSURE TRANSMITTER PAGE 15 OF 18


REV 0 DATE OF ISSUE 6/17/2013
IN-01-03.DOC
ADNOC - Technical Institute

Note :-

 The drain valve should be opened regularly to drain any moisture


in the inlet chamber.

 Range springs come in various sizes. The most common is from


5-35 psi (0.34-2.4 Bar). This is set to give an output of 20 psi for
transmitters, etc.

3.7 THE ELECTRICAL PRESSURE TRANSMITTER

Electrical transmitters have replaced pneumatic transmitters in most


petrochemical plants. This is because they are cheaper to install and
maintain. The transmission of the signal is also cheaper and easier to
install. This is because an electrical transmitter has one pair of wires
instead of expensive stainless steel signal tubing and air supply lines.

There are three main types of transmitters. They use three kinds of
capsules: capacitive (Rosemount), strain gauge (Honeywell) or vibrating
wire (Foxboro). The output from the capsule is electronically converted to
a STANDARD 4-20 mA SIGNAL for transmission to the control room.

An electrical transmitter is calibrated with an instrument screwdriver or


push buttons. There are two adjustments, zero and span (range).

The calibration and servicing depends on the manufacturer. It must be


carried out using the manual. Modern transmitters have become throw
away items. If they cannot be calibrated they are not serviced. They are
thrown away and replaced with a new transmitter.

Figure 3-7 below shows, as an example, a Rosemount electrical


transmitter.

PAGE 16 OF 18 INST 1 - THE PRESSURE TRANSMITTER


DATE OF ISSUE 6/17/2013 REV O
IN-01-03.DOC
ADNOC - Technical Institute

ZERO AND SPAN


ADJUSTMENTS UNDER
COVER

ELECTRICAL TWO WIRE


CONNECTIONS

LOCAL PRESSURE READING


IN % OF SPAN

PROCESS PRESSURE
CONNECTION

Figure 3-7 The Rosemount Electrical Transmitter.

Any electrical transmitter uses an electrical series loop and it acts as a


variable resistor. The basic diagram of the loop is shown in figure 3-8.

PLANT CONTROL ROOM

SAFETY
+ POWER
SUPPLY
4-20 mA BARRIER

RB 4-20 mA
TRANSMITTER TX
RT

4-20 mA SAFETY

RC
BARRIER 4-20 mA CONTROLLER

RB

Figure 3-8 The Electrical Series Loop

The power supply provides the EMF, around 24V d.c., to drive the series
loop. This loop consists of:

 Two safety barriers(RB) which protect the plant from dangerous


voltages in the case of a fault.

INST 1 - THE PRESSURE TRANSMITTER PAGE 17 OF 18


REV 0 DATE OF ISSUE 6/17/2013
IN-01-03.DOC
ADNOC - Technical Institute

 The transmitter, whose resistance (RT) changes with the measured


pressure changes.

 The controller with a resistance RC. The voltage across the


resistance provides the signal for the controller electronics.

The current around the circuit () will be

V SUPPLY
I
RT  2RB  RC

RB and RC are constant. So, the current changes as the resistance in the
transmitter (RT) changes.

The system is set so that with zero pressure, the current is 4 mA and 20
mA at the maximum value of the measured pressure.

Note : Both pneumatic and electrical transmitter signals have a live


zero. This means that a broken circuit can easily be detected.

PAGE 18 OF 18 INST 1 - THE PRESSURE TRANSMITTER


DATE OF ISSUE 6/17/2013 REV O
IN-01-03.DOC

You might also like