Temp
Temp
4/1/2025 8:14 AM
Comments:
Kyaw Zin Lin
PowerWizard 2.1
Parameter                        Value
ECM Part Number                  4509632-01
ECM Serial Number                3104E026TX
Software Group Part Number       5058813-00
Software Group Release Date      OCT2016
Software Group Description       EMCP 4.2 English, v4.4.2 PROD, 14 Oct 2016
Description                                          Value                            TT
PowerWizard 2.1
Analog Inputs
Analog Input #1 Signal Type                          Voltage
Analog Input #1 Signal Range                         0.5 to 4.5 V
Analog Input #1 Data Identification                  Engine Oil Pressure
Analog Input #1 Minimum Data Range                   0.000
Analog Input #1 Maximum Data Range                   3494.000
Analog Input #1 Low Warning Event Threshold          250
Analog Input #1 Low Warning Event Delay Time         0.0 sec
Analog Input #1 Low Shutdown Event Threshold         100
Analog Input #1 Low Shutdown Event Delay Time        0.0 sec
Analog Input #2 Signal Type                          Resistive Sender
Analog Input #2 Configuration Code                   Map #3
Analog Input #2 Data Identification                  Engine Coolant Temperature
Analog Input #2 High Warning Event Threshold         95
Analog Input #2 High Warning Event Delay Time        0.0 sec
Analog Input #2 High Shutdown Event Threshold        120
Analog Input #2 High Shutdown Event Delay Time       0.0 sec
Analog Input #2 Low Warning Event Threshold          0
Analog Input #2 Low Warning Event Delay Time         0.0 sec
                                                                           Page 2 of 29
Time
Crank Attempt/Successful Start Counter
Customer Password Security Level to Reset Crank/Start
                                                        3-Factory, Single Use
Counters
Data Link: RS-485 SCADA
SCADA Data Link Baud Rate                               9600 baud
SCADA Data Link Parity                                  None
SCADA Data Link Slave Address                           1
SCADA Data Link Access Password                         00000000
RS-485 Bias Resistor Enable Status                      Enabled
SCADA Port Enable Status                                Enabled
Data Link: RS-485 Annunciator
RS-485 Annunciator Port Enable Status                   Enabled
Digital Inputs
Digital Input #1 Usage Type                             System Event
Digital Input #1 Active State Configuration             Low
Event Input Function #1 Event Notification Delay Time   0 sec
Event Input Function #1 Suspect Parameter Number        Engine Coolant Temperature
Event Input Function #1 Failure Mode Identifier         High Shutdown
Digital Input #2 Usage Type                             System Event
Digital Input #2 Active State Configuration             Low
Event Input Function #2 Event Notification Delay Time   0 sec
Event Input Function #2 Suspect Parameter Number        Engine Oil Pressure
Event Input Function #2 Failure Mode Identifier         Low Shutdown
Digital Input #3 Usage Type                             System Event
Digital Input #3 Active State Configuration             Low
Event Input Function #3 Event Notification Delay Time   0 sec
Event Input Function #3 Suspect Parameter Number        Exhaust Temperature
Event Input Function #3 Failure Mode Identifier         High Shutdown
Digital Input #4 Usage Type                             System Event
Digital Input #4 Active State Configuration             Low
Event Input Function #4 Event Notification Delay Time   0 sec
Event Input Function #4 Suspect Parameter Number        Air Damper Closed
Event Input Function #4 Failure Mode Identifier         Condition Exists
Digital Input #5 Usage Type                             System Event
Digital Input #5 Active State Configuration             High
Event Input Function #5 Event Notification Delay Time   240 sec
Event Input Function #5 Suspect Parameter Number        Battery Charger Failure
                                                                                 Page 4 of 29
High Engine Oil Level Shutdown Event Response            Activate Hard Shutdown
                                                                                Page 8 of 29
Configuration                                             Condition
High Engine Oil Level Shutdown Event Audible Alert        Yes
High Engine Oil Level Shutdown Event Breaker #1 Trip      No
High Engine Oil Level Shutdown Event Breaker #2 Trip      No
Low Engine Oil Level Warning Event Response
                                                          Activate Warning Condition
Configuration
Low Engine Oil Level Warning Event Audible Alert          Yes
Low Engine Oil Level Warning Event Breaker #1 Trip        No
Low Engine Oil Level Warning Event Breaker #2 Trip        No
Low Engine Oil Level Shutdown Event Response              Activate Hard Shutdown
Configuration                                             Condition
Low Engine Oil Level Shutdown Event Audible Alert         Yes
Low Engine Oil Level Shutdown Event Breaker #1 Trip       No
Low Engine Oil Level Shutdown Event Breaker #2 Trip       No
Low Engine Oil Pressure Warning Event Response
                                                          Activate Warning Condition
Configuration
Low Engine Oil Pressure Warning Event Audible Alert       Yes
Low Engine Oil Pressure Warning Event Breaker #1 Trip     No
Low Engine Oil Pressure Warning Event Breaker #2 Trip     No
Low Engine Oil Pressure Warning Event Fault Protection
                                                          Yes
Timer
Low Engine Oil Pressure Shutdown Event Response           Activate Hard Shutdown
Configuration                                             Condition
Low Engine Oil Pressure Shutdown Event Audible Alert      Yes
Low Engine Oil Pressure Shutdown Event Breaker #1 Trip    No
Low Engine Oil Pressure Shutdown Event Breaker #2 Trip    No
Low Engine Oil Pressure Shutdown Event Fault Protection
                                                          Yes
Timer
High Engine Oil Temperature Warning Event Response
                                                          Activate Warning Condition
Configuration
High Engine Oil Temperature Warning Event Audible Alert   Yes
High Engine Oil Temperature Warning Event Breaker #1
                                                          No
Trip
High Engine Oil Temperature Warning Event Breaker #2
                                                          No
Trip
High Engine Oil Temperature Warning Event Fault
                                                          No
Protection Timer
High Engine Oil Temperature Shutdown Event Response       Activate Hard Shutdown
Configuration                                             Condition
                                                          Yes
High Engine Oil Temperature Shutdown Event Audible
                                                                               Page 9 of 29
Alert
High Engine Oil Temperature Shutdown Event Breaker #1
                                                         No
Trip
High Engine Oil Temperature Shutdown Event Breaker #2
                                                         No
Trip
High Engine Oil Temperature Shutdown Event Fault
                                                         No
Protection Timer
Low Engine Oil Temperature Warning Event Response
                                                         Disable Condition
Configuration
Low Engine Oil Temperature Warning Event Audible Alert   Yes
Low Engine Oil Temperature Warning Event Breaker #1
                                                         No
Trip
Low Engine Oil Temperature Warning Event Breaker #2
                                                         No
Trip
Low Engine Oil Temperature Warning Event Fault
                                                         Yes
Protection Timer
Low Engine Oil Temperature Shutdown Event Response
                                                         Disable Condition
Configuration
Low Engine Oil Temperature Shutdown Event Audible
                                                         No
Alert
Low Engine Oil Temperature Shutdown Event Breaker #1
                                                         No
Trip
Low Engine Oil Temperature Shutdown Event Breaker #2
                                                         No
Trip
Low Engine Oil Temperature Shutdown Event Fault
                                                         No
Protection Timer
Unexpected Engine Shutdown Event Response                Activate Hard Shutdown
Configuration                                            Condition
Unexpected Engine Shutdown Event Audible Alert           Yes
Unexpected Engine Shutdown Event Breaker #1 Trip         No
Unexpected Engine Shutdown Event Breaker #2 Trip         No
Engine Overspeed Shutdown Event Response                 Activate Hard Shutdown
Configuration                                            Condition
Engine Overspeed Shutdown Event Audible Alert            Yes
Engine Overspeed Shutdown Event Breaker #1 Trip          No
Engine Overspeed Shutdown Event Breaker #2 Trip          No
Engine Underspeed Warning Event Response
                                                         Activate Warning Condition
Configuration
Engine Underspeed Warning Event Audible Alert            Yes
Engine Underspeed Warning Event Breaker #1 Trip          No
Engine Underspeed Warning Event Breaker #2 Trip          No
                                                                             Page 10 of 29
External Tank Low Fuel Level Shutdown Event Response     Activate Hard Shutdown
                                                                                Page 12 of 29
Configuration                                              Condition
External Tank Low Fuel Level Shutdown Event Audible
                                                           Yes
Alert
External Tank Low Fuel Level Shutdown Event Breaker #1
                                                           No
Trip
External Tank Low Fuel Level Shutdown Event Breaker #2
                                                           No
Trip
Fuel Leak Event Response Configuration                     Activate Warning Condition
Fuel Leak Event Audible Alert                              Yes
Fuel Leak Event Breaker #1 Trip                            No
Fuel Leak Event Breaker #2 Trip                            No
Service Maintenance Interval Warning Event Response
                                                           Disable Condition
Configuration
Service Maintenance Interval Warning Event Audible Alert   No
High Gas Pressure Warning Event Response Configuration     Disable Condition
High Gas Pressure Warning Event Audible Alert              No
High Gas Pressure Warning Event Breaker #1 Trip            No
High Gas Pressure Warning Event Breaker #2 Trip            No
High Gas Pressure Shutdown Event Response
                                                           Disable Condition
Configuration
High Gas Pressure Shutdown Event Audible Alert             No
High Gas Pressure Shutdown Event Breaker #1 Trip           No
High Gas Pressure Shutdown Event Breaker #2 Trip           No
Low Gas Pressure Warning Event Response Configuration      Activate Warning Condition
Low Gas Pressure Warning Event Audible Alert               Yes
Low Gas Pressure Warning Event Breaker #1 Trip             No
Low Gas Pressure Warning Event Breaker #2 Trip             No
Low Gas Pressure Shutdown Event Response                   Activate Hard Shutdown
Configuration                                              Condition
Low Gas Pressure Shutdown Event Audible Alert              Yes
Low Gas Pressure Shutdown Event Breaker #1 Trip            No
Low Gas Pressure Shutdown Event Breaker #2 Trip            No
Engine Intake Manifold Charge Combustion Event
                                                           Activate Warning Condition
Response Configuration
Engine Intake Manifold Charge Combustion Event Audible
                                                           Yes
Alert
Engine Intake Manifold Charge Combustion Event Breaker
                                                           No
#1 Trip
Engine Intake Manifold Charge Combustion Event Breaker
                                                           No
#2 Trip
                                                                            Page 13 of 29
#2 Trip                                                   No
Generator Reverse Reactive Power Shutdown Event
                                                          Disable Condition
Response Configuration
Generator Reverse Reactive Power Shutdown Event
                                                          Yes
Audible Alert
Generator Reverse Reactive Power Shutdown Event
                                                          No
Breaker #1 Trip
Generator Reverse Reactive Power Shutdown Event
                                                          No
Breaker #2 Trip
Programmable Trip Point #1 Condition Exists Event
                                                          Disable Condition
Response Configuration
Programmable Trip Point #1 Condition Exists Event
                                                          No
Audible Alert
Programmable Trip Point #1 Condition Exists Event
                                                          No
Breaker #1 Trip
Programmable Trip Point #1 Condition Exists Event
                                                          No
Breaker #2 Trip
Programmable Trip Point #1 Condition Exists Event Fault
                                                          No
Protection Timer
Programmable Trip Point #2 Condition Exists Event
                                                          Disable Condition
Response Configuration
Programmable Trip Point #2 Condition Exists Event
                                                          No
Audible Alert
Programmable Trip Point #2 Condition Exists Event
                                                          No
Breaker #1 Trip
Programmable Trip Point #2 Condition Exists Event
                                                          No
Breaker #2 Trip
Programmable Trip Point #2 Condition Exists Event Fault
                                                          No
Protection Timer
Event Response Configuration - Other System
Events
High Battery Voltage Warning Event Response
                                                          Activate Warning Condition
Configuration
High Battery Voltage Warning Event Audible Alert          Yes
High Battery Voltage Warning Event Breaker #1 Trip        No
High Battery Voltage Warning Event Breaker #2 Trip        No
High Battery Voltage Shutdown Event Response              Activate Soft Shutdown
Configuration                                             Condition
High Battery Voltage Shutdown Event Audible Alert         Yes
High Battery Voltage Shutdown Event Breaker #1 Trip       No
High Battery Voltage Shutdown Event Breaker #2 Trip       No
                                                                              Page 18 of 29
Breaker #1 Trip                                          No
Analog Input #1 Custom   Parameter Low Shutdown Event
                                                         No
Breaker #2 Trip
Analog Input #1 Custom   Parameter Low Shutdown Event
                                                         No
Fault Protection Timer
Analog Input #2 Custom   Parameter High Warning Event
                                                         Activate Warning Condition
Response Configuration
Analog Input #2 Custom   Parameter High Warning Event
                                                         Yes
Audible Alert
Analog Input #2 Custom   Parameter High Warning Event
                                                         No
Breaker #1 Trip
Analog Input #2 Custom   Parameter High Warning Event
                                                         No
Breaker #2 Trip
Analog Input #2 Custom   Parameter High Warning Event
                                                         No
Fault Protection Timer
Analog Input #2 Custom   Parameter High Shutdown Event Activate Hard Shutdown
Response Configuration                                 Condition
Analog Input #2 Custom   Parameter High Shutdown Event
                                                       Yes
Audible Alert
Analog Input #2 Custom   Parameter High Shutdown Event
                                                         No
Breaker #1 Trip
Analog Input #2 Custom   Parameter High Shutdown Event
                                                         No
Breaker #2 Trip
Analog Input #2 Custom   Parameter High Shutdown Event
                                                         No
Fault Protection Timer
Analog Input #2 Custom   Parameter Low Warning Event
                                                         Activate Warning Condition
Response Configuration
Analog Input #2 Custom   Parameter Low Warning Event
                                                         Yes
Audible Alert
Analog Input #2 Custom   Parameter Low Warning Event
                                                         No
Breaker #1 Trip
Analog Input #2 Custom   Parameter Low Warning Event
                                                         No
Breaker #2 Trip
Analog Input #2 Custom   Parameter Low Warning Event
                                                         No
Fault Protection Timer
Analog Input #2 Custom   Parameter Low Shutdown Event Activate Hard Shutdown
Response Configuration                                Condition
Analog Input #2 Custom   Parameter Low Shutdown Event
                                                      Yes
Audible Alert
Analog Input #2 Custom   Parameter Low Shutdown Event
                                                         No
Breaker #1 Trip
Analog Input #2 Custom Parameter Low Shutdown Event
                                                                              Page 21 of 29
Breaker #2 Trip                                          No
Analog Input #2 Custom   Parameter Low Shutdown Event
                                                         No
Fault Protection Timer
Analog Input #3 Custom   Parameter High Warning Event
                                                         Activate Warning Condition
Response Configuration
Analog Input #3 Custom   Parameter High Warning Event
                                                         Yes
Audible Alert
Analog Input #3 Custom   Parameter High Warning Event
                                                         No
Breaker #1 Trip
Analog Input #3 Custom   Parameter High Warning Event
                                                         No
Breaker #2 Trip
Analog Input #3 Custom   Parameter High Warning Event
                                                         No
Fault Protection Timer
Analog Input #3 Custom   Parameter High Shutdown Event Activate Hard Shutdown
Response Configuration                                 Condition
Analog Input #3 Custom   Parameter High Shutdown Event
                                                       Yes
Audible Alert
Analog Input #3 Custom   Parameter High Shutdown Event
                                                         No
Breaker #1 Trip
Analog Input #3 Custom   Parameter High Shutdown Event
                                                         No
Breaker #2 Trip
Analog Input #3 Custom   Parameter High Shutdown Event
                                                         No
Fault Protection Timer
Analog Input #3 Custom   Parameter Low Warning Event
                                                         Activate Warning Condition
Response Configuration
Analog Input #3 Custom   Parameter Low Warning Event
                                                         Yes
Audible Alert
Analog Input #3 Custom   Parameter Low Warning Event
                                                         No
Breaker #1 Trip
Analog Input #3 Custom   Parameter Low Warning Event
                                                         No
Breaker #2 Trip
Analog Input #3 Custom   Parameter Low Warning Event
                                                         No
Fault Protection Timer
Analog Input #3 Custom   Parameter Low Shutdown Event Activate Hard Shutdown
Response Configuration                                Condition
Analog Input #3 Custom   Parameter Low Shutdown Event
                                                      Yes
Audible Alert
Analog Input #3 Custom   Parameter Low Shutdown Event
                                                         No
Breaker #1 Trip
Analog Input #3 Custom   Parameter Low Shutdown Event
                                                         No
Breaker #2 Trip
Analog Input #3 Custom Parameter Low Shutdown Event
                                                                                  Page 22 of 29
Threshold                                                  100 %
Generator Inverse Definite Minimum Time Curve Type
                                                           Normal Inverse Curve
Configuration
Generator Over/Under Frequency
Generator Over Frequency Warning Event Percentage
                                                           105.0 %
Threshold
Generator Over Frequency Warning Event Notification
                                                           10 sec
Delay Time
Generator Over Frequency Shutdown Event Percentage
                                                           110.0 %
Threshold
Generator Over Frequency Shutdown Event Notification
                                                           2 sec
Delay Time
Generator Under Frequency Warning Event Percentage
                                                           95.0 %
Threshold
Generator Under Frequency Warning Event Notification
                                                           10 sec
Delay Time
Generator Under Frequency Shutdown Event Percentage
                                                           90.0 %
Threshold
Generator Under Frequency Shutdown Event Notification
                                                           4 sec
Delay Time
Generator Over/Under Voltage
Generator Over Voltage Warning Event Percentage
                                                           105 %
Threshold
Generator Over Voltage Warning Event Notification Delay
                                                           10 sec
Time
Generator Over Voltage Shutdown Event Percentage
                                                           110 %
Threshold
Generator Over Voltage Shutdown Event Notification
                                                           2 sec
Delay Time
Generator Under Voltage Warning Event Percentage
                                                           95 %
Threshold
Generator Under Voltage Warning Event Notification Delay
                                                           10 sec
Time
Generator Under Voltage Shutdown Event Percentage
                                                           90 %
Threshold
Generator Under Voltage Shutdown Event Notification
                                                           4 sec
Delay Time
Generator Reverse Power
Generator Reverse Power Warning Event Percentage
                                                           5%
Threshold
Generator Reverse Power Warning Event Notification
                                                           10 sec
Delay Time
                                                                           Page 25 of 29
Configuration
Programmable    Cycle Timer #2 Output #2 Activation
                                                                    Inactive
Configuration
Programmable    Cycle   Timer   #3   Activation   Day   - Sunday    Deactivate
Programmable    Cycle   Timer   #3   Activation   Day   - Monday    Deactivate
Programmable    Cycle   Timer   #3   Activation   Day   - Tuesday   Deactivate
Programmable    Cycle   Timer   #3   Activation   Day   -
                                                                    Deactivate
Wednesday
Programmable    Cycle   Timer   #3   Activation Day - Thursday      Deactivate
Programmable    Cycle   Timer   #3   Activation Day - Friday        Deactivate
Programmable    Cycle   Timer   #3   Activation Day - Saturday      Deactivate
Programmable    Cycle   Timer   #3   Activation Start Time          0 min
Programmable    Cycle   Timer   #3   Active Time                    1 min
Programmable    Cycle   Timer   #3   Output #1 Activation
                                                                    Inactive
Configuration
Programmable    Cycle Timer #3 Output #2 Activation
                                                                    Inactive
Configuration
Programmable    Cycle   Timer   #4   Activation   Day   - Sunday    Deactivate
Programmable    Cycle   Timer   #4   Activation   Day   - Monday    Deactivate
Programmable    Cycle   Timer   #4   Activation   Day   - Tuesday   Deactivate
Programmable    Cycle   Timer   #4   Activation   Day   -
                                                                    Deactivate
Wednesday
Programmable    Cycle   Timer   #4   Activation Day - Thursday      Deactivate
Programmable    Cycle   Timer   #4   Activation Day - Friday        Deactivate
Programmable    Cycle   Timer   #4   Activation Day - Saturday      Deactivate
Programmable    Cycle   Timer   #4   Activation Start Time          0 min
Programmable    Cycle   Timer   #4   Active Time                    1 min
Programmable    Cycle   Timer   #4   Output #1 Activation
                                                                    Inactive
Configuration
Programmable    Cycle Timer #4 Output #2 Activation
                                                                    Inactive
Configuration
Programmable    Cycle   Timer   #5   Activation   Day   - Sunday    Deactivate
Programmable    Cycle   Timer   #5   Activation   Day   - Monday    Deactivate
Programmable    Cycle   Timer   #5   Activation   Day   - Tuesday   Deactivate
Programmable    Cycle   Timer   #5   Activation   Day   -
                                                                    Deactivate
Wednesday
Programmable    Cycle   Timer   #5   Activation   Day - Thursday    Deactivate
Programmable    Cycle   Timer   #5   Activation   Day - Friday      Deactivate
Programmable    Cycle   Timer   #5   Activation   Day - Saturday    Deactivate
Programmable    Cycle   Timer   #5   Activation   Start Time        0 min
                                                                           Page 27 of 29