DCP List Manual LH21 0516 Eng
DCP List Manual LH21 0516 Eng
SINAMICS drives
SINAMICS DCP
DC/DC Power Converter
List Manual
Edition 05/2016
s Foreword
Fundamental safety
instructions 1
Index
Valid for
Firmware version
SINAMICS DCP 1.2
05/2016
Legal information
Warning notice system
This Manual contains information which you must observe to ensure your own personal safety as well as to avoid
material damage. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to equipment damage have no safety alert symbol. Depending on the hazard level,
warnings are indicated in a descending order as follows:
DANGER
indicates that death or serious injury will result if proper precautions are not taken.
WARNING
indicates that death or serious injury could result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one level of danger is simultaneously applicable, the warning notice for the highest level is used. A
notice warning of injury to persons with a triangular safety alert symbol may also include a warning relating to
property damage.
Qualified personnel
The product/system described in this documentation may only be operated by personnel qualified for the specific
task in accordance with the relevant documentation for the specific task, in particular its warning notices and safety
instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying
risks and avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products are only permitted to be used for the applications listed in the catalog and in the associated
technical documentation. If third-party products and components are used, then they must be recommended or
approved by Siemens. These products can only function correctly and safely if they are transported, stored, set
up, mounted, installed, commissioned, operated and maintained correctly. The permissible ambient conditions
must be adhered to. Notes in the associated documentation must be observed.
Trademarks
All names identified with ® are registered trademarks of Siemens AG. Any other names used in this publication may
be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Exclusion of Liability
We have verified that the contents of this document correspond to the hardware and software described. Since
variances cannot be precluded entirely, we cannot guarantee full consistency. The information given in this
document is reviewed at regular intervals and any corrections that might be necessary are made in the subsequent
editions.
Target group
This documentation addresses commissioning engineers and service personnel.
Objective
This manual contains information about all parameters, function diagrams, faults and alarms
required to commission and service the system.
This manual should be used in addition to the other manuals and tools provided for the product.
Search tools
The following tools are provided to help you locate information in this manual:
1. Table of Contents
– Table of contents for the complete manual (Page 7)
– Table of contents for function diagrams (Page 310)
2. List of abbreviations (Page 501)
3. Index (Page 511)
SINAMICS DCP
List Manual (LH21), 05/2016 5
Preface
SINAMICS DCP
6 List Manual (LH21), 05/2016
Table of contents
SINAMICS DCP
List Manual (LH21), 05/2016 7
Table of contents
SINAMICS DCP
8 List Manual (LH21), 05/2016
Fundamental safety instructions 1
Content
SINAMICS DCP
List Manual (LH21), 05/2016 9
1 Fundamental safety instructions
1.1 General safety instructions
WARNING
Risk of death if the safety instructions and remaining risks are not carefully observed
If the safety instructions and residual risks are not carefully observed in the associated
hardware documentation, accidents involving severe injuries or death can occur.
• Observe the safety instructions given in the hardware documentation.
• When assessing the risk, take into account residual risks.
WARNING
Danger to life or malfunctions of the machine as a result of incorrect or changed
parameter assignment
Machines can malfunction as a result of incorrect or changed parameter assignment, which
in turn can lead to injuries or death.
• Protect the parameterization (parameter assignments) against unauthorized access.
• Respond to possible malfunctions by applying suitable measures
(e.g. EMERGENCY-STOP or EMERGENCY-OFF).
SINAMICS DCP
10 List Manual (LH21), 05/2016
1 Fundamental safety instructions
1.2 Industrial security
Note
Industrial security
Siemens provides products and solutions with industrial security functions that support the
secure operation of plants, solutions, machines, devices, and/or networks. They are important
components in a holistic industrial security concept. With this in mind, Siemens products and
solutions undergo continuous development. Siemens recommends strongly that you regularly
check for product updates.
To ensure that Siemens products and solutions are operated securely, suitable preventive
measures (e.g. cell protection concept) and each component must be integrated into a state-
of-the-art holistic industrial security concept. Any third-party products that may be in use must
also be taken into account. You will find more information about industrial security at:
http://www.siemens.com/industrialsecurity
To receive information about product updates on a regular basis, register for our product
newsletter. You will find more information at:
http://support.automation.siemens.com
WARNING
Danger due to unsafe operating states caused by software manipulation
Software manipulation (e.g. by viruses, Trojan horses, malware, worms) can cause unsafe
operating states to develop in your installation which can result in death, severe injuries
and/or material damage.
• Update your software regularly.
You can find information and newsletters on this subject at:
http://support.automation.siemens.com
• Integrate the automation and drive components into a holistic, state-of-the-art industrial
security concept for the plant or machine.
For more information, visit:
http://www.siemens.com/industrialsecurity
• Make sure that you include all installed products into the holistic industrial security
concept.
WARNING
Danger to life due to software manipulation when using exchangeable storage media
Storing files onto exchangeable storage media amounts to an increased risk of infection, e.g.
with viruses and malware. As a result of incorrect parameterization, machines can
malfunction, which in turn can lead to injuries or death.
• Protect files stored on exchangeable storage media from malicious software by taking
suitable protection measures, e.g. virus scanners.
SINAMICS DCP
List Manual (LH21), 05/2016 11
1 Fundamental safety instructions
1.2 Industrial security
SINAMICS DCP
12 List Manual (LH21), 05/2016
Parameters 2
Content
SINAMICS DCP
List Manual (LH21), 05/2016 13
2 Parameters
2.1 Overview of parameters
- - - - - - - - - - - - Start of example - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - End of example - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
SINAMICS DCP
14 List Manual (LH21), 05/2016
2 Parameters
2.1 Overview of parameters
Note
The parameter list can contain parameters that are not visible in the expert lists of the particular
commissioning software (e.g. parameters for trace functions).
The value for the factory setting can deviate from the value shown in the list as a result of
specific customer requirements.
SINAMICS DCP
List Manual (LH21), 05/2016 15
2 Parameters
2.1 Overview of parameters
Note
A connector input (CI) cannot be just interconnected with any connector output (CO, signal
source).
When interconnecting a connector input using the commissioning software, only the
corresponding possible signal sources are listed.
SINAMICS DCP
16 List Manual (LH21), 05/2016
2 Parameters
2.1 Overview of parameters
Can be changed
The "-" sign indicates that the parameter can be changed in any object state and that the
change will be effective immediately.
The information "C1(x), C2(x), T, U" ((x): optional) means that the parameter can be changed
only in the specified drive unit state and that the change will not take effect until the unit
switches to another state. This can be a single state or multiple states.
The following states are available:
• C1(x) Device commissioning C1: Commissioning 1
Device is being commissioned (p0009 > 0).
Pulses cannot be enabled.
The parameter can only be changed for the following device commissioning
settings (p0009 > 0):
• C1: Can be changed for all settings p0009 > 0.
• C1(x): Can be changed only when p0009 = x.
A modified parameter value does not take effect until the device commissioning
mode is exited with p0009 = 0.
• C2(x) Drive object commissioning C2: Commissioning 2
Drive commissioning is in progress (p0009 = 0 and p0010 > 0).
Pulses cannot be enabled.
The parameter can only be changed in the following drive commissioning settings
(p0010 > 0):
• C2: Can be changed for all settings p0010 > 0.
• C2(x): Can only be changed for the settings p0010 = x.
A modified parameter value does not take effect until drive commissioning mode is
exited with p0010 = 0.
• U Operation U: Run
Pulses are enabled.
• T Ready T: Ready to run
The pulses are not enabled and the state "C1(x)" or "C2(x)" is not active.
Note
Parameter p0009 is CU-specific (belongs to the Control Unit).
Parameter p0010 is drive-specific (belongs to each drive object).
The operating state of individual drive objects is displayed in r0002.
SINAMICS DCP
List Manual (LH21), 05/2016 17
2 Parameters
2.1 Overview of parameters
Access level
Specifies the minimum access level required to be able to display and change the relevant
parameter. The required access level can be set using p0003.
The system uses the following access levels:
• 1: Standard
• 2: Extended
• 3: Expert
• 4: Service
Parameters with this access level are password protected.
Note
Parameter p0003 is CU-specific (belongs to the Control Unit).
A higher access level will also include the functions of the lower levels.
Data type
The information on the data type can consist of the following two items (separated by a slash):
• First item
Data type of the parameter.
• Second item (for binector or connector input only)
Data type of the signal source to be interconnected (binector/connector output).
Parameters can have the following data types:
• Integer8 I8 8-bit integer number
• Integer16 I16 16-bit integer number
• Integer32 I32 32-bit integer number
• Unsigned8 U8 8 bits without sign
• Unsigned16 U16 16 bits without sign
• Unsigned32 U32 32 bits without sign
• FloatingPoint32 Float 32-bit floating point number
Depending on the data type of the BICO input parameter (signal sink) and BICO output
parameter (signal source), the following combinations are possible when creating BICO
interconnections:
SINAMICS DCP
18 List Manual (LH21), 05/2016
2 Parameters
2.1 Overview of parameters
CI parameter BI parameter
CO: Unsigned8 x x – –
CO: Unsigned16 x x – –
CO: Integer16 x x r2050, r8850 –
CO: Unsigned32 x x – –
CO: Integer32 x x r2060, r8860 –
CO: FloatingPoint32 x x x –
BO: Unsigned8 – – – x
BO: Unsigned16 – – – x
BO: Integer16 – – – x
BO: Unsigned32 – – – x
BO: Integer32 – – – x
BO: FloatingPoint32 – – – –
Legend: x : BICO interconnection permitted
–: BICO interconnection not permitted
rxxxx: BICO interconnection is only permitted for the specified CO parameters
Function diagram
The parameter is included in this function diagram. The structure of the parameter function and
its relationship with other parameters is shown in the specified function diagram.
Parameter values
Min. Minimum value of the parameter [unit]
Max Maximum value of the parameter [unit]
Factory setting Value when delivered [unit]
In the case of a binector/connector input, the signal source of the
default BICO interconnection is specified. A non-indexed connector
output is assigned the index [0].
Description
Explanation of the function of a parameter.
Values
Lists the possible values of a parameter.
SINAMICS DCP
List Manual (LH21), 05/2016 19
2 Parameters
2.1 Overview of parameters
Recommendation
Information about recommended settings.
Index
The name and meaning of each individual index is specified for indexed parameters.
The following applies to the values (Min, Max, Factory setting) for indexed adjustable
parameters:
• Min, Max:
The adjustment range and unit apply to all indices.
• Factory setting:
When all indices have the same factory setting, index 0 is specified with the unit to
represent all indices.
When the indices have different factory settings, they are all listed individually with the unit.
Bit field
For parameters with bit fields, the following information is provided about each bit:
• Bit number and signal name
• Meaning for signal states 1 and 0
• Function diagram (optional)
The signal is shown on this function diagram.
Dependency
Conditions that must be fulfilled in conjunction with this parameter. Also includes special effects
that can occur between this parameter and others.
See also: List of other parameters to be additionally considered.
SINAMICS DCP
20 List Manual (LH21), 05/2016
2 Parameters
2.1 Overview of parameters
Safety instructions
Important information that must be observed to avoid the risk of physical injury or material
damage.
Information that must be observed to avoid any problems.
Information that the user may find useful.
Danger The description of this safety notice can be found at the beginning of this
manual, see "Legal information" (Page 4).
Warning The description of this safety notice can be found at the beginning of this
manual, see "Legal information" (Page 4).
Caution The description of this safety notice can be found at the beginning of this
manual, see "Legal information" (Page 4).
Notice The description of this safety notice can be found at the beginning of this
manual, see "Legal information" (Page 4).
SINAMICS DCP
List Manual (LH21), 05/2016 21
2 Parameters
2.2 List of parameters
SINAMICS DCP
22 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 23
2 Parameters
2.2 List of parameters
Value: 1: Standard
2: Extended
3: Expert
4: Service
Note: A higher set access level also includes the lower one.
Access level 1 (standard):
Parameters for simplest possible operations.
Access level 2 (extended):
Parameters to operate the basic functions of the drive unit.
Access level 3 (experts):
Expert know-how is required for these parameters (e.g. BICO parameterization).
Access level 4 (service):
For these parameters, it is necessary that authorized service personnel enter the appropriate password (p3950).
SINAMICS DCP
24 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
Note: Procedure:
1.
The parameter number to be displayed should be set in index 0. Only the monitoring parameters (read-only
parameters) can be set that actually exist for the actual drive object.
If the set parameter number is not indexed, or if there is an index in index 1 that lies outside the valid range of the set
parameter, then index 1 is automatically set to 0.
2.
The index that belongs to the parameter set in index 0 should be set in index 1. The permissible changes in index 1
always depend on the parameter number set in index 0.
SINAMICS DCP
List Manual (LH21), 05/2016 25
2 Parameters
2.2 List of parameters
SINAMICS DCP
26 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 27
2 Parameters
2.2 List of parameters
SINAMICS DCP
28 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 29
2 Parameters
2.2 List of parameters
SINAMICS DCP
30 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 31
2 Parameters
2.2 List of parameters
h = reserved
if the value 0 is displayed in all indices, then components are not detected via DRIVE-CLiQ.
If a value F hex occurs at a position of the coding (abcd efgh hex), then an overflow has occurred.
SINAMICS DCP
32 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 33
2 Parameters
2.2 List of parameters
SINAMICS DCP
34 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
Note: Re value = 0, 2:
When a drive object is deactivated it no longer outputs any errors.
If value = 0:
All components of the drive object were completely commissioned and are deactivated using this value. They can be
removed from the DRIVE-CLiQ without any error.
If a component has been deactivated, only the component with the correct serial number may be inserted, or none at
all.
If value = 1:
All components of the drive object must be available for error-free operation.
If value = 2:
Components of a drive object in a project generated offline and set to this value must never be inserted in the actual
topology from the very start. This means that the components are marked to be bypassed in the DRIVE-CLiQ line.
For components that comprise several individual components (e.g. Double Motor Modules), it is not permissible to
set just one subset to this value.
SINAMICS DCP
List Manual (LH21), 05/2016 35
2 Parameters
2.2 List of parameters
Note: The number (p0101) and the associated drive object type are in the same index.
SINAMICS DCP
36 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 37
2 Parameters
2.2 List of parameters
Note: A "function module" is a functional expansion of a drive object that can be activated when commissioning.
SINAMICS DCP
38 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
Note: For p0112 = 0 (expert) the individual sampling times in p0115 can be adjusted.
p0115[0...6] Sampling times for internal control loops / t_sample int ctrl
DCP_CTRL Can be changed: C1(3) Access level: 3
Data type: FloatingPoint32 Func. diagram: -
Min Max Factory setting
1000.00 [µs] 16000.00 [µs] [0] 1000.00 [µs]
[1] 2000.00 [µs]
[2] 8000.00 [µs]
[3] 4000.00 [µs]
[4] 8000.00 [µs]
[5] 8000.00 [µs]
[6] 8000.00 [µs]
Description: Sets the sampling times for the control loops.
The default setting is made using p0112 and can only be individually changed for p0112 = 0 (expert).
Index: [0] = Current controller
[1] = Speed controller
[2] = -
[3] = Setpoint channel
[4] = -
[5] = -
[6] = Techn controller
Dependency: The sampling times can only be separately set if p0112 is 0 (expert). If a sampling time is modified in the expert
mode, then all of the sampling times with higher indices are automatically changed in the same ratio as the sampling
time itself was changed. Slower time slices are only taken if the calculated sampling time is also permitted. Upper
limit is 8 ms.
Higher-level controls must be calculated in integral ratios to lower-level controls (e.g. p0115[1] = N * p0115[0]; where
N is an integer number). The sampling time of the speed controller (p0115[1]) can have as a maximum a value of
800% of the current controller sampling time (p0115[0]).
Refer to: r0110, r0111, p0112
Note: For function modules that can be activated (e.g. technology controller), the parameters values are pre-assigned.
The current controller sampling time (p0115[0]) is permanently set to 1 ms and cannot be changed.
SINAMICS DCP
List Manual (LH21), 05/2016 39
2 Parameters
2.2 List of parameters
SINAMICS DCP
40 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 41
2 Parameters
2.2 List of parameters
SINAMICS DCP
42 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 43
2 Parameters
2.2 List of parameters
SINAMICS DCP
44 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
p0804 = 1001:
The parameter backup set in p0802 as the source on the memory card does not exist or there is not sufficient
memory space available on the memory card.
p0804 = 1002:
The parameter backup set in p0803 as the source in the device memory does not exist or there is not sufficient
memory space available in the device memory.
p0804 = 1003:
No memory card has been inserted.
SINAMICS DCP
List Manual (LH21), 05/2016 45
2 Parameters
2.2 List of parameters
p0810 BI: Command data set selection CDS bit 0 / CDS select., bit 0
DCP_CTRL Can be changed: T Access level: 3
Data type: Unsigned32 / Binary Func. diagram: 8560
Min Max Factory setting
- - 0
Description: Sets the signal source to select the Command Data Set bit 0 (CDS bit 0).
Dependency: Refer to: r0050, r0836
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: The Command Data Set selected using the binector inputs is displayed in r0836.
The currently effective command data set is displayed in r0050.
A Command Data Set can be copied using p0809.
p0820[0...n] BI: Drive Data Set selection DDS bit 0 / DDS select., bit 0
DCP_CTRL Can be changed: C2(15), T Access level: 3
Data type: Unsigned32 / Binary Func. diagram: 8565, 8570
Min Max Factory setting
- - 0
Description: Sets the signal source to select the Drive Data Set, bit 0 (DDS, bit 0).
Dependency: Refer to: r0051, r0837
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p0821[0...n] BI: Drive Data Set selection DDS bit 1 / DDS select., bit 1
DCP_CTRL Can be changed: C2(15), T Access level: 3
Data type: Unsigned32 / Binary Func. diagram: 8565, 8570
Min Max Factory setting
- - 0
Description: Sets the signal source to select the Drive Data Set, bit 1 (DDS, bit 1).
Dependency: Refer to: r0051, r0837
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
SINAMICS DCP
46 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
Notice: For binector input p0840 = 0 signal, the motor can be moved, jogging using binector input p1055 or p1056.
The command "ON/OFF (OFF1)" can be issued using binector input p0840 or p1055/p1056.
For binector input p0840 = 0 signal, the switch-on inhibit is acknowledged.
Only the signal source that originally powered up can also power down again.
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: For drives with closed-loop speed control (p50084 = 1), the following applies:
- BI: p0840 = 0 signal: OFF1 (braking with the ramp-function generator, then pulse suppression and switch-on inhibit)
For drives with closed-loop torque control (p50084 = 2), the following applies:
- BI: p0840 = 0 signal: immediate pulse suppression
For drives with closed-loop speed/torque control, the following applies:
- BI: p0840 = 0/1 signal: ON (pulses can be enabled)
SINAMICS DCP
List Manual (LH21), 05/2016 47
2 Parameters
2.2 List of parameters
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p0848[0...n] BI: No Quick Stop / Quick Stop (OFF3) signal source 1 / OFF3 S_src 1
DCP_CTRL Can be changed: T Access level: 3
Data type: Unsigned32 / Binary Func. diagram: 2580
Min Max Factory setting
- - 1
Description: Sets the first signal source for the command "No quick stop/quick stop (OFF3)".
The following signals are AND'ed:
- BI: p0848 "No quick stop / quick stop (OFF3) signal source 1"
- BI: p0849 "No quick stop / quick stop (OFF3) signal source 2"
For the PROFIdrive profile, the result of the AND logic operation corresponds to control word 1 bit 2 (STW1.2).
BI: p0848 = 0 signal or BI: p0849 = 0 signal
- OFF3 (braking along the OFF3 ramp (p50296), then pulse suppression and switch on inhibit)
BI: p0848 = 1 signal and BI: p0849 = 1 signal
- No OFF3 (enable is possible)
Caution: When "master control from PC" is activated, this binector input is ineffective.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
SINAMICS DCP
48 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
p0849[0...n] BI: No Quick Stop / Quick Stop (OFF3) signal source 2 / OFF3 S_src 2
DCP_CTRL Can be changed: T Access level: 3
Data type: Unsigned32 / Binary Func. diagram: 2580
Min Max Factory setting
- - 1
Description: Sets the second signal source for the command "No quick stop/quick stop (OFF3)".
The following signals are AND'ed:
- BI: p0848 "No quick stop / quick stop (OFF3) signal source 1"
- BI: p0849 "No quick stop / quick stop (OFF3) signal source 2"
For the PROFIdrive profile, the result of the AND logic operation corresponds to control word 1 bit 2 (STW1.2).
BI: p0848 = 0 signal or BI: p0849 = 0 signal
- OFF3 (braking along the OFF3 ramp (p50296), then pulse suppression and switch on inhibit)
BI: p0848 = 1 signal and BI: p0849 = 1 signal
- No OFF3 (enable is possible)
Caution: When "master control from PC" is activated, this binector input is effective.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: This bit is used to initiate a response for the drives when the control fails (F07220). If there is no control available,
then binector input p0854 should be set to 1.
If a control is available, then STW1.10 must be set to 1 (PZD1) so that the received data is updated. This applies
regardless of the setting in p0854 and even in the case of free telegram configuration (p0922 = 999).
SINAMICS DCP
List Manual (LH21), 05/2016 49
2 Parameters
2.2 List of parameters
SINAMICS DCP
50 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
r0944 CO: Counter for fault buffer changes / Fault buff change
All objects Can be changed: - Access level: 2
Data type: Unsigned16 Func. diagram: 8060
Min Max Factory setting
- - -
Description: Displays fault buffer changes. This counter is incremented every time the fault buffer changes.
Recommendation: Used to check whether the fault buffer has been read out consistently.
Dependency: Refer to: r0945, r0947, r0948, r0949, r2109
SINAMICS DCP
List Manual (LH21), 05/2016 51
2 Parameters
2.2 List of parameters
Dependency: Refer to: r0947, r0948, r0949, r2109, r2130, r2133, r2136, r3120, r3122
Notice: The properties of the fault buffer should be taken from the corresponding product documentation.
Note: The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
Fault buffer structure (general principle):
r0945[0], r0949[0], r0948[0], r2109[0], r3115[0] --> actual fault case, fault 1
...
r0945[7], r0949[7], r0948[7], r2109[7], r3115[7] --> actual fault case, fault 8
r0945[8], r0949[8], r0948[8], r2109[8], r3115[8] --> 1st acknowledged fault case, fault 1
...
r0945[15], r0949[15], r0948[15], r2109[15], r3115[15] --> 1st acknowledged fault case, fault 8
...
r0945[56], r0949[56], r0948[56], r2109[56], r3115[56] --> 7th acknowledged fault case, fault 1
...
r0945[63], r0949[63], r0948[63], r2109[63], r3115[63] --> 7th acknowledged fault case, fault 8
SINAMICS DCP
52 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 53
2 Parameters
2.2 List of parameters
SINAMICS DCP
54 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 55
2 Parameters
2.2 List of parameters
Notice: The Control Unit power supply may only be powered down after data has been saved (i.e. after data save has been
started, wait until the parameter again has the value 0).
Writing to parameters is inhibited while saving.
The progress while saving is displayed in r3996.
SINAMICS DCP
56 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
Note: Starting from the particular drive object, the following parameters are saved:
CU3xx: Device-specific parameters and PROFIBUS device parameters.
Other objects: Parameters of the actual object and PROFIBUS device parameters.
Prerequisite:
In order that the parameter of a drive object, saved with p0971 = 1, is read the next time that the Control Unit is
booted, then all parameters must, as a minimum, have first been saved once with p0977 = 1.
Note: If value = 1:
Reset is immediately executed and communications interrupted.
After communications have been established, check the reset operation (refer below).
If value = 2:
Help to check the reset operation.
Firstly, set p0972 = 2 and then read back. Secondly, set p0972 = 1 (it is possible that this request is possibly no
longer acknowledged). The communication is then interrupted.
After communications have been established, check the reset operation (refer below).
If value = 3:
The reset is executed after interrupting cyclic communication. This setting is used to implement a synchronized reset
by a control for several drive units.
If cyclic communication is not active, then the reset is immediately executed.
If the cyclic communication is active for both PROFIdrive interfaces, then the reset is executed after completing both
cycle communications.
After communications have been established, check the reset operation (refer below).
SINAMICS DCP
List Manual (LH21), 05/2016 57
2 Parameters
2.2 List of parameters
SINAMICS DCP
58 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
p0976 Reset and load all parameters / Reset load all par
CU_DCP Can be changed: C1(30) Access level: 1
Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
0 1013 0
Description: Resets or downloads all parameters of the drive system.
Value: 0: Inactive
1: Start reset of all parameters to factory setting
2: Start dnload of param. saved in non-volatile mem w/ p0977=1
3: Start download of volatile parameters from RAM
10: Start dnload of param. saved in non-volatile mem w/ p0977=10
11: Start dnload of param. saved in non-volatile mem w/ p0977=11
12: Start dnload of param. saved in non-volatile mem w/ p0977=12
20: Start download Siemens internal setting 20
100: Start resetting of all BICO interconnections
200: Start deleting all user data
1011: Start dnload of param. saved in volatile mem w/ p0977=1011
1012: Start dnload of param. saved in volatile mem w/ p0977=1012
1013: Start dnload of param. saved in volatile mem w/ p0977=1013
Notice: After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
After executing p0976 = 200, the Control Unit is powered on automatically.
Note: After all of the parameters have been reset to their factory setting, the system must be commissioned for the first time
again.
Resetting or loading is realized in the non-volatile memory.
Procedure:
1. Set p0009 = 30 (parameter reset).
2. Set p0976 to "required value". The system is rebooted.
p0976 is automatically set to 0 after execution.
SINAMICS DCP
List Manual (LH21), 05/2016 59
2 Parameters
2.2 List of parameters
Notice: The Control Unit power supply may only be powered down after data has been saved (i.e. after data save has been
started, wait until the parameter again has the value 0).
Writing to parameters is inhibited while saving.
The progress while saving is displayed in r3996.
Note: Parameters saved with p0977 = 10, 11 or 12 can be downloaded again with p0976 = 10, 11 or 12.
Identification and maintenance data (I&M data, p8806 and following) are only saved for p0977 = 1.
SINAMICS DCP
60 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
Note: The existing parameters are displayed in indices 0 to 298. If an index contains the value 0, then the list ends here. In
a long list, index 299 contains the parameter number at which position the list continues.
This list consists solely of the following parameters:
r0980[0...299], r0981[0...299] ... r0989[0...299]
The parameters in this list are not displayed in the expert list of the commissioning software. However, they can be
read from a higher-level control system (e.g. PROFIBUS master).
SINAMICS DCP
List Manual (LH21), 05/2016 61
2 Parameters
2.2 List of parameters
Note: Modified parameters are displayed in indices 0 to 98. If an index contains the value 0, then the list ends here.
This list consists solely of the following parameters:
r0990[0...99], r0991[0...99] ... r0999[0...99]
The parameters in this list are not displayed in the expert list of the commissioning software. However, they can be
read from a higher-level control system (e.g. PROFIBUS master).
p1000[0...n] Macro Connector Inputs (CI) for speed setpoints / Macro CI n_set
DCP_CTRL Can be changed: C2(1), T Access level: 1
Data type: Unsigned32 Func. diagram: -
Min Max Factory setting
0 999999 0
Description: Runs the corresponding macro files.
The Connector Inputs (CI) for the speed setpoints of the appropriate Command Data Set (CDS) are appropriately
interconnected.
The selected macro file must be available on the memory card/device memory.
Example:
p1000 = 6 --> the macro file PM000006.ACX is run.
Dependency: Refer to: p0015, p0700, p1500, r8572
Notice: No errors were issued during quick commissioning (p3900 = 1) when writing to parameters of the QUICK_IBN group!
When executing a specific macro, the corresponding programmed settings are made and become active.
Note: The macros in the specified directory are displayed in r8572. r8572 is not in the expert list of the commissioning
software.
Macros available as standard are described in the technical documentation of the particular product.
CI: Connector Input
p1500[0...n] Macro Connector Inputs (CI) for torque setpoints / Macro CI M_set
DCP_CTRL Can be changed: C2(1), T Access level: 1
Data type: Unsigned32 Func. diagram: -
Min Max Factory setting
0 999999 0
Description: Runs the corresponding macro files.
The Connector Inputs (CI) for the torque setpoints of the appropriate Command Data Set (CDS) are appropriately
interconnected.
The selected macro file must be available on the memory card/device memory.
Example:
p1500 = 6 --> the macro file PM000006.ACX is run.
Dependency: Refer to: p0015, p0700, p1000, r8573
Notice: No errors were issued during quick commissioning (p3900 = 1) when writing to parameters of the QUICK_IBN group!
When executing a specific macro, the corresponding programmed settings are made and become active.
Note: The macros in the specified directory are displayed in r8573. r8573 is not in the expert list of the commissioning
software.
Macros available as standard are described in the technical documentation of the particular product.
CI: Connector Input
SINAMICS DCP
62 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 63
2 Parameters
2.2 List of parameters
p2022 Field bus int USS PZD no. / Field bus USS PZD
CU_DCP Can be changed: T Access level: 2
Data type: Unsigned16 Func. diagram: 9310
Min Max Factory setting
0 16 2
Description: Sets the number of 16-bit words in the PZD part of the USS telegram for the field bus interface.
Dependency: Refer to: p2030
Note: The parameter is not influenced by setting the factory setting.
p2023 Field bus int USS PKW no. / Field bus USS PKW
CU_DCP Can be changed: T Access level: 2
Data type: Integer16 Func. diagram: 9310
Min Max Factory setting
0 127 127
Description: Sets the number of 16-bit words in the PKW part of the USS telegram for the field bus interface.
Value: 0: PKW 0 words
3: PKW 3 words
4: PKW 4 words
127: PKW variable
Dependency: Refer to: p2030
Note: The parameter is not influenced by setting the factory setting.
SINAMICS DCP
64 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
p2035 Fieldbus interface USS PIV drive object number / Fieldbus USS DO_no
CU_DCP Can be changed: U, T Access level: 2
Data type: Integer16 Func. diagram: -
Min Max Factory setting
1 62 2
Description: Sets the drive object number for communication via the field bus interface (USS).
Dependency: Refer to: p0978
Note: p2035 defines the destination for USS parameter requests (PIV).
p0978[0] defines the destination for USS process data (PZD).
The parameter is available globally on all drive objects.
The parameter is not influenced by setting the factory setting.
SINAMICS DCP
List Manual (LH21), 05/2016 65
2 Parameters
2.2 List of parameters
SINAMICS DCP
66 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
r2050[0...19] CO: IF1 PROFIdrive PZD receive word / IF1 PZD recv word
CU_DCP Can be changed: - Access level: 3
Data type: Integer16 Func. diagram: -
Min Max Factory setting
- - -
Description: Connector output to interconnect PZD (setpoints) with word format received from the fieldbus controller.
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
[12] = PZD 13
[13] = PZD 14
[14] = PZD 15
[15] = PZD 16
[16] = PZD 17
[17] = PZD 18
[18] = PZD 19
[19] = PZD 20
Note: IF1: Interface 1
SINAMICS DCP
List Manual (LH21), 05/2016 67
2 Parameters
2.2 List of parameters
r2050[0...63] CO: IF1 PROFIdrive PZD receive word / IF1 PZD recv word
DCP_CTRL Can be changed: - Access level: 3
Data type: Integer16 Func. diagram: 2440
Min Max Factory setting
- - -
Description: Connector output to interconnect PZD (setpoints) with word format received from the fieldbus controller.
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
[12] = PZD 13
[13] = PZD 14
[14] = PZD 15
[15] = PZD 16
[16] = PZD 17
[17] = PZD 18
[18] = PZD 19
[19] = PZD 20
[20] = PZD 21
[21] = PZD 22
[22] = PZD 23
[23] = PZD 24
[24] = PZD 25
[25] = PZD 26
[26] = PZD 27
[27] = PZD 28
[28] = PZD 29
[29] = PZD 30
[30] = PZD 31
[31] = PZD 32
[32] = PZD 33
[33] = PZD 34
[34] = PZD 35
[35] = PZD 36
[36] = PZD 37
[37] = PZD 38
[38] = PZD 39
[39] = PZD 40
[40] = PZD 41
[41] = PZD 42
[42] = PZD 43
[43] = PZD 44
[44] = PZD 45
[45] = PZD 46
[46] = PZD 47
[47] = PZD 48
[48] = PZD 49
[49] = PZD 50
[50] = PZD 51
[51] = PZD 52
[52] = PZD 53
[53] = PZD 54
[54] = PZD 55
[55] = PZD 56
[56] = PZD 57
SINAMICS DCP
68 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
[57] = PZD 58
[58] = PZD 59
[59] = PZD 60
[60] = PZD 61
[61] = PZD 62
[62] = PZD 63
[63] = PZD 64
Dependency: Refer to: r2060
Notice: Where there is a multiple interconnection of a connector output, all the connector inputs must either have Integer or
FloatingPoint data types.
A BICO interconnection for a single PZD can only take place either on r2050 or r2060.
Note: IF1: Interface 1
r2050[0...4] CO: IF1 PROFIdrive PZD receive word / IF1 PZD recv word
TM150, TM15DI_DO, Can be changed: - Access level: 3
TM31 Data type: Integer16 Func. diagram: -
Min Max Factory setting
- - -
Description: Connector output to interconnect PZD (setpoints) with word format received from the fieldbus controller.
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
Note: IF1: Interface 1
p2051[0...24] CI: IF1 PROFIdrive PZD send word / IF1 PZD send word
CU_DCP Can be changed: U, T Access level: 3
Data type: Unsigned32 / Integer16 Func. diagram: 2450, 2483
Min Max Factory setting
- - 0
Description: Selects the PZD (actual values) with word format to be sent to the fieldbus controller.
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
[12] = PZD 13
[13] = PZD 14
[14] = PZD 15
[15] = PZD 16
[16] = PZD 17
[17] = PZD 18
[18] = PZD 19
[19] = PZD 20
[20] = PZD 21
[21] = PZD 22
[22] = PZD 23
[23] = PZD 24
[24] = PZD 25
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: IF1: Interface 1
SINAMICS DCP
List Manual (LH21), 05/2016 69
2 Parameters
2.2 List of parameters
p2051[0...63] CI: IF1 PROFIdrive PZD send word / IF1 PZD send word
DCP_CTRL Can be changed: U, T Access level: 3
Data type: Unsigned32 / Integer16 Func. diagram: 2450, 2470,
2483
Min Max Factory setting
- - 0
Description: Selects the PZD (actual values) with word format to be sent to the fieldbus controller.
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
[12] = PZD 13
[13] = PZD 14
[14] = PZD 15
[15] = PZD 16
[16] = PZD 17
[17] = PZD 18
[18] = PZD 19
[19] = PZD 20
[20] = PZD 21
[21] = PZD 22
[22] = PZD 23
[23] = PZD 24
[24] = PZD 25
[25] = PZD 26
[26] = PZD 27
[27] = PZD 28
[28] = PZD 29
[29] = PZD 30
[30] = PZD 31
[31] = PZD 32
[32] = PZD 33
[33] = PZD 34
[34] = PZD 35
[35] = PZD 36
[36] = PZD 37
[37] = PZD 38
[38] = PZD 39
[39] = PZD 40
[40] = PZD 41
[41] = PZD 42
[42] = PZD 43
[43] = PZD 44
[44] = PZD 45
[45] = PZD 46
[46] = PZD 47
[47] = PZD 48
[48] = PZD 49
[49] = PZD 50
[50] = PZD 51
[51] = PZD 52
[52] = PZD 53
[53] = PZD 54
[54] = PZD 55
[55] = PZD 56
SINAMICS DCP
70 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
[56] = PZD 57
[57] = PZD 58
[58] = PZD 59
[59] = PZD 60
[60] = PZD 61
[61] = PZD 62
[62] = PZD 63
[63] = PZD 64
Dependency: Refer to: p2061
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: IF1: Interface 1
p2051[0...4] CI: IF1 PROFIdrive PZD send word / IF1 PZD send word
TM150, TM15DI_DO, Can be changed: U, T Access level: 3
TM31 Data type: Unsigned32 / Integer16 Func. diagram: -
Min Max Factory setting
- - 0
Description: Selects the PZD (actual values) with word format to be sent to the fieldbus controller.
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: IF1: Interface 1
r2053[0...24] IF1 PROFIdrive diagnostics PZD send word / IF1 diag send word
CU_DCP Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: 2483
Min Max Factory setting
- - -
Description: Displays the PZD (actual values) with word format sent to the fieldbus controller.
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
[12] = PZD 13
[13] = PZD 14
[14] = PZD 15
[15] = PZD 16
[16] = PZD 17
[17] = PZD 18
[18] = PZD 19
[19] = PZD 20
[20] = PZD 21
[21] = PZD 22
[22] = PZD 23
[23] = PZD 24
[24] = PZD 25
Bit field: Bit Signal name 1 signal 0 signal FP
00 Bit 0 ON OFF -
01 Bit 1 ON OFF -
SINAMICS DCP
List Manual (LH21), 05/2016 71
2 Parameters
2.2 List of parameters
02 Bit 2 ON OFF -
03 Bit 3 ON OFF -
04 Bit 4 ON OFF -
05 Bit 5 ON OFF -
06 Bit 6 ON OFF -
07 Bit 7 ON OFF -
08 Bit 8 ON OFF -
09 Bit 9 ON OFF -
10 Bit 10 ON OFF -
11 Bit 11 ON OFF -
12 Bit 12 ON OFF -
13 Bit 13 ON OFF -
14 Bit 14 ON OFF -
15 Bit 15 ON OFF -
Note: IF1: Interface 1
r2053[0...63] IF1 PROFIdrive diagnostics PZD send word / IF1 diag send word
DCP_CTRL Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: 2450, 2470
Min Max Factory setting
- - -
Description: Displays the PZD (actual values) with word format sent to the fieldbus controller.
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
[12] = PZD 13
[13] = PZD 14
[14] = PZD 15
[15] = PZD 16
[16] = PZD 17
[17] = PZD 18
[18] = PZD 19
[19] = PZD 20
[20] = PZD 21
[21] = PZD 22
[22] = PZD 23
[23] = PZD 24
[24] = PZD 25
[25] = PZD 26
[26] = PZD 27
[27] = PZD 28
[28] = PZD 29
[29] = PZD 30
[30] = PZD 31
[31] = PZD 32
[32] = PZD 33
[33] = PZD 34
[34] = PZD 35
[35] = PZD 36
[36] = PZD 37
[37] = PZD 38
[38] = PZD 39
[39] = PZD 40
[40] = PZD 41
SINAMICS DCP
72 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
[41] = PZD 42
[42] = PZD 43
[43] = PZD 44
[44] = PZD 45
[45] = PZD 46
[46] = PZD 47
[47] = PZD 48
[48] = PZD 49
[49] = PZD 50
[50] = PZD 51
[51] = PZD 52
[52] = PZD 53
[53] = PZD 54
[54] = PZD 55
[55] = PZD 56
[56] = PZD 57
[57] = PZD 58
[58] = PZD 59
[59] = PZD 60
[60] = PZD 61
[61] = PZD 62
[62] = PZD 63
[63] = PZD 64
Bit field: Bit Signal name 1 signal 0 signal FP
00 Bit 0 ON OFF -
01 Bit 1 ON OFF -
02 Bit 2 ON OFF -
03 Bit 3 ON OFF -
04 Bit 4 ON OFF -
05 Bit 5 ON OFF -
06 Bit 6 ON OFF -
07 Bit 7 ON OFF -
08 Bit 8 ON OFF -
09 Bit 9 ON OFF -
10 Bit 10 ON OFF -
11 Bit 11 ON OFF -
12 Bit 12 ON OFF -
13 Bit 13 ON OFF -
14 Bit 14 ON OFF -
15 Bit 15 ON OFF -
Dependency: Refer to: p2051, p2061
Note: IF1: Interface 1
r2053[0...4] IF1 PROFIdrive diagnostics PZD send word / IF1 diag send word
TM150, TM15DI_DO, Can be changed: - Access level: 3
TM31 Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
- - -
Description: Displays the PZD (actual values) with word format sent to the fieldbus controller.
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
Bit field: Bit Signal name 1 signal 0 signal FP
00 Bit 0 ON OFF -
01 Bit 1 ON OFF -
02 Bit 2 ON OFF -
03 Bit 3 ON OFF -
04 Bit 4 ON OFF -
05 Bit 5 ON OFF -
06 Bit 6 ON OFF -
SINAMICS DCP
List Manual (LH21), 05/2016 73
2 Parameters
2.2 List of parameters
07 Bit 7 ON OFF -
08 Bit 8 ON OFF -
09 Bit 9 ON OFF -
10 Bit 10 ON OFF -
11 Bit 11 ON OFF -
12 Bit 12 ON OFF -
13 Bit 13 ON OFF -
14 Bit 14 ON OFF -
15 Bit 15 ON OFF -
Note: IF1: Interface 1
r2060[0...62] CO: IF1 PROFIdrive PZD receive double word / IF1 PZD recv DW
DCP_CTRL Can be changed: - Access level: 3
Data type: Integer32 Func. diagram: 2440, 2460
Min Max Factory setting
- - -
Description: Connector output to interconnect PZD (setpoints) with double word format received from the fieldbus controller.
Index: [0] = PZD 1 + 2
[1] = PZD 2 + 3
[2] = PZD 3 + 4
[3] = PZD 4 + 5
[4] = PZD 5 + 6
[5] = PZD 6 + 7
[6] = PZD 7 + 8
[7] = PZD 8 + 9
SINAMICS DCP
74 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
[8] = PZD 9 + 10
[9] = PZD 10 + 11
[10] = PZD 11 + 12
[11] = PZD 12 + 13
[12] = PZD 13 + 14
[13] = PZD 14 + 15
[14] = PZD 15 + 16
[15] = PZD 16 + 17
[16] = PZD 17 + 18
[17] = PZD 18 + 19
[18] = PZD 19 + 20
[19] = PZD 20 + 21
[20] = PZD 21 + 22
[21] = PZD 22 + 23
[22] = PZD 23 + 24
[23] = PZD 24 + 25
[24] = PZD 25 + 26
[25] = PZD 26 + 27
[26] = PZD 27 + 28
[27] = PZD 28 + 29
[28] = PZD 29 + 30
[29] = PZD 30 + 31
[30] = PZD 31 + 32
[31] = PZD 32 + 33
[32] = PZD 33 + 34
[33] = PZD 34 + 35
[34] = PZD 35 + 36
[35] = PZD 36 + 37
[36] = PZD 37 + 38
[37] = PZD 38 + 39
[38] = PZD 39 + 40
[39] = PZD 40 + 41
[40] = PZD 41 + 42
[41] = PZD 42 + 43
[42] = PZD 43 + 44
[43] = PZD 44 + 45
[44] = PZD 45 + 46
[45] = PZD 46 + 47
[46] = PZD 47 + 48
[47] = PZD 48 + 49
[48] = PZD 49 + 50
[49] = PZD 50 + 51
[50] = PZD 51 + 52
[51] = PZD 52 + 53
[52] = PZD 53 + 54
[53] = PZD 54 + 55
[54] = PZD 55 + 56
[55] = PZD 56 + 57
[56] = PZD 57 + 58
[57] = PZD 58 + 59
[58] = PZD 59 + 60
[59] = PZD 60 + 61
[60] = PZD 61 + 62
[61] = PZD 62 + 63
[62] = PZD 63 + 64
Dependency: Refer to: r2050
Notice: Where there is a multiple interconnection of a connector output, all the connector inputs must either have Integer or
FloatingPoint data types.
A BICO interconnection for a single PZD can only take place either on r2050 or r2060.
A maximum of 4 indices of the "trace" function can be used.
Note: IF1: Interface 1
SINAMICS DCP
List Manual (LH21), 05/2016 75
2 Parameters
2.2 List of parameters
p2061[0...62] CI: IF1 PROFIdrive PZD send double word / IF1 PZD send DW
DCP_CTRL Can be changed: U, T Access level: 3
Data type: Unsigned32 / Integer32 Func. diagram: 2450, 2470
Min Max Factory setting
- - 0
Description: Selects the PZD (actual values) with double word format to be sent to the fieldbus controller.
Index: [0] = PZD 1 + 2
[1] = PZD 2 + 3
[2] = PZD 3 + 4
[3] = PZD 4 + 5
[4] = PZD 5 + 6
[5] = PZD 6 + 7
[6] = PZD 7 + 8
[7] = PZD 8 + 9
[8] = PZD 9 + 10
[9] = PZD 10 + 11
[10] = PZD 11 + 12
[11] = PZD 12 + 13
[12] = PZD 13 + 14
[13] = PZD 14 + 15
[14] = PZD 15 + 16
[15] = PZD 16 + 17
[16] = PZD 17 + 18
[17] = PZD 18 + 19
[18] = PZD 19 + 20
[19] = PZD 20 + 21
[20] = PZD 21 + 22
[21] = PZD 22 + 23
[22] = PZD 23 + 24
[23] = PZD 24 + 25
[24] = PZD 25 + 26
[25] = PZD 26 + 27
[26] = PZD 27 + 28
[27] = PZD 28 + 29
[28] = PZD 29 + 30
[29] = PZD 30 + 31
[30] = PZD 31 + 32
[31] = PZD 32 + 33
[32] = PZD 33 + 34
[33] = PZD 34 + 35
[34] = PZD 35 + 36
[35] = PZD 36 + 37
[36] = PZD 37 + 38
[37] = PZD 38 + 39
[38] = PZD 39 + 40
[39] = PZD 40 + 41
[40] = PZD 41 + 42
[41] = PZD 42 + 43
[42] = PZD 43 + 44
[43] = PZD 44 + 45
[44] = PZD 45 + 46
[45] = PZD 46 + 47
[46] = PZD 47 + 48
[47] = PZD 48 + 49
[48] = PZD 49 + 50
[49] = PZD 50 + 51
[50] = PZD 51 + 52
[51] = PZD 52 + 53
[52] = PZD 53 + 54
[53] = PZD 54 + 55
[54] = PZD 55 + 56
[55] = PZD 56 + 57
[56] = PZD 57 + 58
SINAMICS DCP
76 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
[57] = PZD 58 + 59
[58] = PZD 59 + 60
[59] = PZD 60 + 61
[60] = PZD 61 + 62
[61] = PZD 62 + 63
[62] = PZD 63 + 64
Dependency: Refer to: p2051
Notice: A BICO interconnection for a single PZD can only take place either on p2051 or p2061.
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: IF1: Interface 1
r2063[0...62] IF1 PROFIdrive diagnostics PZD send double word / IF1 diag send DW
DCP_CTRL Can be changed: - Access level: 3
Data type: Unsigned32 Func. diagram: 2450, 2470
Min Max Factory setting
- - -
Description: Displays the PZD (actual values) with double word format sent to the fieldbus controller.
Index: [0] = PZD 1 + 2
[1] = PZD 2 + 3
[2] = PZD 3 + 4
[3] = PZD 4 + 5
[4] = PZD 5 + 6
[5] = PZD 6 + 7
[6] = PZD 7 + 8
[7] = PZD 8 + 9
[8] = PZD 9 + 10
[9] = PZD 10 + 11
[10] = PZD 11 + 12
[11] = PZD 12 + 13
[12] = PZD 13 + 14
[13] = PZD 14 + 15
[14] = PZD 15 + 16
[15] = PZD 16 + 17
[16] = PZD 17 + 18
[17] = PZD 18 + 19
[18] = PZD 19 + 20
[19] = PZD 20 + 21
[20] = PZD 21 + 22
[21] = PZD 22 + 23
[22] = PZD 23 + 24
[23] = PZD 24 + 25
[24] = PZD 25 + 26
[25] = PZD 26 + 27
[26] = PZD 27 + 28
[27] = PZD 28 + 29
[28] = PZD 29 + 30
[29] = PZD 30 + 31
[30] = PZD 31 + 32
[31] = PZD 32 + 33
[32] = PZD 33 + 34
[33] = PZD 34 + 35
[34] = PZD 35 + 36
[35] = PZD 36 + 37
[36] = PZD 37 + 38
[37] = PZD 38 + 39
[38] = PZD 39 + 40
[39] = PZD 40 + 41
[40] = PZD 41 + 42
[41] = PZD 42 + 43
[42] = PZD 43 + 44
[43] = PZD 44 + 45
[44] = PZD 45 + 46
[45] = PZD 46 + 47
SINAMICS DCP
List Manual (LH21), 05/2016 77
2 Parameters
2.2 List of parameters
[46] = PZD 47 + 48
[47] = PZD 48 + 49
[48] = PZD 49 + 50
[49] = PZD 50 + 51
[50] = PZD 51 + 52
[51] = PZD 52 + 53
[52] = PZD 53 + 54
[53] = PZD 54 + 55
[54] = PZD 55 + 56
[55] = PZD 56 + 57
[56] = PZD 57 + 58
[57] = PZD 58 + 59
[58] = PZD 59 + 60
[59] = PZD 60 + 61
[60] = PZD 61 + 62
[61] = PZD 62 + 63
[62] = PZD 63 + 64
Bit field: Bit Signal name 1 signal 0 signal FP
00 Bit 0 ON OFF -
01 Bit 1 ON OFF -
02 Bit 2 ON OFF -
03 Bit 3 ON OFF -
04 Bit 4 ON OFF -
05 Bit 5 ON OFF -
06 Bit 6 ON OFF -
07 Bit 7 ON OFF -
08 Bit 8 ON OFF -
09 Bit 9 ON OFF -
10 Bit 10 ON OFF -
11 Bit 11 ON OFF -
12 Bit 12 ON OFF -
13 Bit 13 ON OFF -
14 Bit 14 ON OFF -
15 Bit 15 ON OFF -
16 Bit 16 ON OFF -
17 Bit 17 ON OFF -
18 Bit 18 ON OFF -
19 Bit 19 ON OFF -
20 Bit 20 ON OFF -
21 Bit 21 ON OFF -
22 Bit 22 ON OFF -
23 Bit 23 ON OFF -
24 Bit 24 ON OFF -
25 Bit 25 ON OFF -
26 Bit 26 ON OFF -
27 Bit 27 ON OFF -
28 Bit 28 ON OFF -
29 Bit 29 ON OFF -
30 Bit 30 ON OFF -
31 Bit 31 ON OFF -
Notice: A maximum of 4 indices of the "trace" function can be used.
Note: IF1: Interface 1
SINAMICS DCP
78 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
r2065 PB/PN controller sign of life diagnostics / PB/PN ctr SoL diag
CU_DCP Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
- - -
Description: Displays how often the sign-of-life from the clock synchronous PROFIBUS/PROFINET controller last failed.
p2072 Response receive value after PZD failure / Resp aft PZD fail
DCP_CTRL Can be changed: T Access level: 3
Data type: Unsigned32 Func. diagram: -
Min Max Factory setting
- - 0000 bin
Description: Sets the response for the receive value (r2090) after PZD failure.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Unconditionally open holding brake (p0855) Freeze value Zero the value -
r2074[0...19] IF1 PROFIdrive diagnostics bus address PZD receive / IF1diag addr recv
CU_DCP Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
- - -
Description: Displays the PROFIBUS address of the sender from which the process data (PZD) is received.
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
[12] = PZD 13
[13] = PZD 14
[14] = PZD 15
[15] = PZD 16
[16] = PZD 17
[17] = PZD 18
SINAMICS DCP
List Manual (LH21), 05/2016 79
2 Parameters
2.2 List of parameters
[18] = PZD 19
[19] = PZD 20
Note: IF1: Interface 1
Value range:
0 - 125: Bus address of the sender
65535: Not assigned
r2074[0...63] IF1 PROFIdrive diagnostics bus address PZD receive / IF1diag addr recv
DCP_CTRL Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
- - -
Description: Displays the PROFIBUS address of the sender from which the process data (PZD) is received.
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
[12] = PZD 13
[13] = PZD 14
[14] = PZD 15
[15] = PZD 16
[16] = PZD 17
[17] = PZD 18
[18] = PZD 19
[19] = PZD 20
[20] = PZD 21
[21] = PZD 22
[22] = PZD 23
[23] = PZD 24
[24] = PZD 25
[25] = PZD 26
[26] = PZD 27
[27] = PZD 28
[28] = PZD 29
[29] = PZD 30
[30] = PZD 31
[31] = PZD 32
[32] = PZD 33
[33] = PZD 34
[34] = PZD 35
[35] = PZD 36
[36] = PZD 37
[37] = PZD 38
[38] = PZD 39
[39] = PZD 40
[40] = PZD 41
[41] = PZD 42
[42] = PZD 43
[43] = PZD 44
[44] = PZD 45
[45] = PZD 46
[46] = PZD 47
[47] = PZD 48
[48] = PZD 49
[49] = PZD 50
SINAMICS DCP
80 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
[50] = PZD 51
[51] = PZD 52
[52] = PZD 53
[53] = PZD 54
[54] = PZD 55
[55] = PZD 56
[56] = PZD 57
[57] = PZD 58
[58] = PZD 59
[59] = PZD 60
[60] = PZD 61
[61] = PZD 62
[62] = PZD 63
[63] = PZD 64
Note: IF1: Interface 1
Value range:
0 - 125: Bus address of the sender
65535: Not assigned
r2074[0...4] IF1 PROFIdrive diagnostics bus address PZD receive / IF1diag addr recv
TM150, TM15DI_DO, Can be changed: - Access level: 3
TM31 Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
- - -
Description: Displays the PROFIBUS address of the sender from which the process data (PZD) is received.
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
Note: IF1: Interface 1
Value range:
0 - 125: Bus address of the sender
65535: Not assigned
r2075[0...19] IF1 PROFIdrive diagnostics telegram offset PZD receive / IF1 diag offs recv
CU_DCP Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: 2410
Min Max Factory setting
- - -
Description: Displays the PZD byte offset in the PROFIdrive receive telegram (controller output).
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
[12] = PZD 13
[13] = PZD 14
[14] = PZD 15
[15] = PZD 16
[16] = PZD 17
[17] = PZD 18
SINAMICS DCP
List Manual (LH21), 05/2016 81
2 Parameters
2.2 List of parameters
[18] = PZD 19
[19] = PZD 20
Note: IF1: Interface 1
Value range:
0 - 242: Byte offset
65535: Not assigned
r2075[0...63] IF1 PROFIdrive diagnostics telegram offset PZD receive / IF1 diag offs recv
DCP_CTRL Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: 2410
Min Max Factory setting
- - -
Description: Displays the PZD byte offset in the PROFIdrive receive telegram (controller output).
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
[12] = PZD 13
[13] = PZD 14
[14] = PZD 15
[15] = PZD 16
[16] = PZD 17
[17] = PZD 18
[18] = PZD 19
[19] = PZD 20
[20] = PZD 21
[21] = PZD 22
[22] = PZD 23
[23] = PZD 24
[24] = PZD 25
[25] = PZD 26
[26] = PZD 27
[27] = PZD 28
[28] = PZD 29
[29] = PZD 30
[30] = PZD 31
[31] = PZD 32
[32] = PZD 33
[33] = PZD 34
[34] = PZD 35
[35] = PZD 36
[36] = PZD 37
[37] = PZD 38
[38] = PZD 39
[39] = PZD 40
[40] = PZD 41
[41] = PZD 42
[42] = PZD 43
[43] = PZD 44
[44] = PZD 45
[45] = PZD 46
[46] = PZD 47
[47] = PZD 48
[48] = PZD 49
[49] = PZD 50
SINAMICS DCP
82 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
[50] = PZD 51
[51] = PZD 52
[52] = PZD 53
[53] = PZD 54
[54] = PZD 55
[55] = PZD 56
[56] = PZD 57
[57] = PZD 58
[58] = PZD 59
[59] = PZD 60
[60] = PZD 61
[61] = PZD 62
[62] = PZD 63
[63] = PZD 64
Note: IF1: Interface 1
Value range:
0 - 242: Byte offset
65535: Not assigned
r2075[0...4] IF1 PROFIdrive diagnostics telegram offset PZD receive / IF1 diag offs recv
TM150, TM15DI_DO, Can be changed: - Access level: 3
TM31 Data type: Unsigned16 Func. diagram: 2410
Min Max Factory setting
- - -
Description: Displays the PZD byte offset in the PROFIdrive receive telegram (controller output).
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
Note: IF1: Interface 1
Value range:
0 - 242: Byte offset
65535: Not assigned
r2076[0...24] IF1 PROFIdrive diagnostics telegram offset PZD send / IF1 diag offs send
CU_DCP Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: 2410
Min Max Factory setting
- - -
Description: Displays the PZD byte offset in the PROFIdrive send telegram (controller input).
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
[12] = PZD 13
[13] = PZD 14
[14] = PZD 15
[15] = PZD 16
[16] = PZD 17
[17] = PZD 18
[18] = PZD 19
SINAMICS DCP
List Manual (LH21), 05/2016 83
2 Parameters
2.2 List of parameters
[19] = PZD 20
[20] = PZD 21
[21] = PZD 22
[22] = PZD 23
[23] = PZD 24
[24] = PZD 25
Note: IF1: Interface 1
Value range:
0 - 242: Byte offset
65535: Not assigned
r2076[0...63] IF1 PROFIdrive diagnostics telegram offset PZD send / IF1 diag offs send
DCP_CTRL Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: 2410
Min Max Factory setting
- - -
Description: Displays the PZD byte offset in the PROFIdrive send telegram (controller input).
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
[12] = PZD 13
[13] = PZD 14
[14] = PZD 15
[15] = PZD 16
[16] = PZD 17
[17] = PZD 18
[18] = PZD 19
[19] = PZD 20
[20] = PZD 21
[21] = PZD 22
[22] = PZD 23
[23] = PZD 24
[24] = PZD 25
[25] = PZD 26
[26] = PZD 27
[27] = PZD 28
[28] = PZD 29
[29] = PZD 30
[30] = PZD 31
[31] = PZD 32
[32] = PZD 33
[33] = PZD 34
[34] = PZD 35
[35] = PZD 36
[36] = PZD 37
[37] = PZD 38
[38] = PZD 39
[39] = PZD 40
[40] = PZD 41
[41] = PZD 42
[42] = PZD 43
[43] = PZD 44
[44] = PZD 45
[45] = PZD 46
SINAMICS DCP
84 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
[46] = PZD 47
[47] = PZD 48
[48] = PZD 49
[49] = PZD 50
[50] = PZD 51
[51] = PZD 52
[52] = PZD 53
[53] = PZD 54
[54] = PZD 55
[55] = PZD 56
[56] = PZD 57
[57] = PZD 58
[58] = PZD 59
[59] = PZD 60
[60] = PZD 61
[61] = PZD 62
[62] = PZD 63
[63] = PZD 64
Note: IF1: Interface 1
Value range:
0 - 242: Byte offset
65535: Not assigned
r2076[0...4] IF1 PROFIdrive diagnostics telegram offset PZD send / IF1 diag offs send
TM150, TM15DI_DO, Can be changed: - Access level: 3
TM31 Data type: Unsigned16 Func. diagram: 2410
Min Max Factory setting
- - -
Description: Displays the PZD byte offset in the PROFIdrive send telegram (controller input).
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
Note: IF1: Interface 1
Value range:
0 - 242: Byte offset
65535: Not assigned
r2077[0...15] PROFIBUS diagnostics peer-to-peer data transfer addresses / PB diag peer addr
CU_DCP Can be changed: - Access level: 3
Data type: Unsigned8 Func. diagram: -
Min Max Factory setting
- - -
Description: Displays the addresses of the slaves (peers) where peer-to-peer data transfer has been configured via PROFIBUS.
p2079 IF1 PROFIdrive PZD telegram selection extended / IF1 PZD telegr ext
CU_DCP Can be changed: T Access level: 3
Data type: Integer16 Func. diagram: -
Min Max Factory setting
390 999 999
Description: Sets the send and receive telegram.
Contrary to p0922, a telegram can be selected using p2079 and subsequently expanded.
Value: 390: SIEMENS telegram 390, PZD-2/2
391: SIEMENS telegram 391, PZD-3/7
392: SIEMENS telegram 392, PZD-3/15
393: SIEMENS telegram 393, PZD-4/21
394: SIEMENS telegram 394, PZD-3/3
SINAMICS DCP
List Manual (LH21), 05/2016 85
2 Parameters
2.2 List of parameters
p2079 IF1 PROFIdrive PZD telegram selection extended / IF1 PZD telegr ext
DCP_CTRL Can be changed: T Access level: 3
Data type: Integer16 Func. diagram: -
Min Max Factory setting
1 999 999
Description: Sets the send and receive telegram.
Contrary to p0922, a telegram can be selected using p2079 and subsequently expanded.
Value: 1: Standard telegram 1, PZD-2/2
3: Standard telegram 3, PZD-5/9
4: Standard telegram 4, PZD-6/14
20: Standard telegram 20, PZD-2/6
220: SIEMENS telegram 220, PZD-10/10
352: SIEMENS telegram 352, PZD-6/6
999: Free telegram configuration with BICO
Dependency: Refer to: p0922
Note: For p0922 < 999 the following applies:
p2079 has the same value and is inhibited. All of the interconnections and extensions contained in the telegram are
inhibited.
For p0922 = 999 the following applies:
p2079 can be freely set. If p2079 is also set to 999, then all of the interconnections can be set.
For p0922 = 999 and p2079 < 999 the following applies:
The interconnections contained in the telegram are inhibited. However, the telegram can be extended.
SINAMICS DCP
86 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
SINAMICS DCP
List Manual (LH21), 05/2016 87
2 Parameters
2.2 List of parameters
SINAMICS DCP
88 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
r2089[0...4] CO: Send binector-connector converter status word / Bin/con ZSW send
All objects Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: 2472
Min Max Factory setting
- - -
Description: Connector output to interconnect the status words to a PZD send word.
Index: [0] = Status word 1
[1] = Status word 2
[2] = Free status word 3
[3] = Free status word 4
[4] = Free status word 5
Bit field: Bit Signal name 1 signal 0 signal FP
00 Bit 0 ON OFF -
01 Bit 1 ON OFF -
02 Bit 2 ON OFF -
03 Bit 3 ON OFF -
04 Bit 4 ON OFF -
05 Bit 5 ON OFF -
06 Bit 6 ON OFF -
07 Bit 7 ON OFF -
08 Bit 8 ON OFF -
09 Bit 9 ON OFF -
10 Bit 10 ON OFF -
11 Bit 11 ON OFF -
12 Bit 12 ON OFF -
13 Bit 13 ON OFF -
14 Bit 14 ON OFF -
15 Bit 15 ON OFF -
Dependency: Refer to: p2051, p2080, p2081, p2082, p2083
Note: r2089 together with p2080 to p2084 forms five binector-connector converters.
SINAMICS DCP
List Manual (LH21), 05/2016 89
2 Parameters
2.2 List of parameters
r2090.0...15 BO: IF1 PROFIBUS PZD1 receive bit-serial / IF1 PZD1 recv bitw
CU_DCP, DCP_CTRL Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: 2440, 2460,
2481
Min Max Factory setting
- - -
Description: Binector output for bit-serial interconnection of PZD1 (normally control word 1) received from the PROFIdrive
controller.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Bit 0 ON OFF -
01 Bit 1 ON OFF -
02 Bit 2 ON OFF -
03 Bit 3 ON OFF -
04 Bit 4 ON OFF -
05 Bit 5 ON OFF -
06 Bit 6 ON OFF -
07 Bit 7 ON OFF -
08 Bit 8 ON OFF -
09 Bit 9 ON OFF -
10 Bit 10 ON OFF -
11 Bit 11 ON OFF -
12 Bit 12 ON OFF -
13 Bit 13 ON OFF -
14 Bit 14 ON OFF -
15 Bit 15 ON OFF -
Note: IF1: Interface 1
r2090.0...15 BO: IF1 PROFIBUS PZD1 receive bit-serial / IF1 PZD1 recv bitw
TM150, TM15DI_DO, Can be changed: - Access level: 3
TM31 Data type: Unsigned16 Func. diagram: 2468
Min Max Factory setting
- - -
Description: Binector output for bit-serial interconnection of PZD1 (normally control word 1) received from the PROFIdrive
controller.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Bit 0 ON OFF -
01 Bit 1 ON OFF -
02 Bit 2 ON OFF -
03 Bit 3 ON OFF -
04 Bit 4 ON OFF -
05 Bit 5 ON OFF -
06 Bit 6 ON OFF -
07 Bit 7 ON OFF -
08 Bit 8 ON OFF -
09 Bit 9 ON OFF -
10 Bit 10 ON OFF -
11 Bit 11 ON OFF -
12 Bit 12 ON OFF -
13 Bit 13 ON OFF -
14 Bit 14 ON OFF -
15 Bit 15 ON OFF -
Note: IF1: Interface 1
SINAMICS DCP
90 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
r2091.0...15 BO: IF1 PROFIdrive PZD2 receive bit-serial / IF1 PZD2 recv bitw
CU_DCP, DCP_CTRL Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: 2460, 2481
Min Max Factory setting
- - -
Description: Binector output for bit-serial interconnection of PZD2 received from the PROFIdrive controller.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Bit 0 ON OFF -
01 Bit 1 ON OFF -
02 Bit 2 ON OFF -
03 Bit 3 ON OFF -
04 Bit 4 ON OFF -
05 Bit 5 ON OFF -
06 Bit 6 ON OFF -
07 Bit 7 ON OFF -
08 Bit 8 ON OFF -
09 Bit 9 ON OFF -
10 Bit 10 ON OFF -
11 Bit 11 ON OFF -
12 Bit 12 ON OFF -
13 Bit 13 ON OFF -
14 Bit 14 ON OFF -
15 Bit 15 ON OFF -
Note: IF1: Interface 1
r2091.0...15 BO: IF1 PROFIdrive PZD2 receive bit-serial / IF1 PZD2 recv bitw
TM150, TM15DI_DO, Can be changed: - Access level: 3
TM31 Data type: Unsigned16 Func. diagram: 2468
Min Max Factory setting
- - -
Description: Binector output for bit-serial interconnection of PZD2 received from the PROFIdrive controller.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Bit 0 ON OFF -
01 Bit 1 ON OFF -
02 Bit 2 ON OFF -
03 Bit 3 ON OFF -
04 Bit 4 ON OFF -
05 Bit 5 ON OFF -
06 Bit 6 ON OFF -
07 Bit 7 ON OFF -
08 Bit 8 ON OFF -
09 Bit 9 ON OFF -
10 Bit 10 ON OFF -
11 Bit 11 ON OFF -
12 Bit 12 ON OFF -
13 Bit 13 ON OFF -
14 Bit 14 ON OFF -
15 Bit 15 ON OFF -
Note: IF1: Interface 1
r2092.0...15 BO: IF1 PROFIdrive PZD3 receive bit-serial / IF1 PZD3 recv bitw
CU_DCP Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: 2468
Min Max Factory setting
- - -
Description: Binector output for bit-serial interconnection of PZD3 received from the PROFIdrive controller.
SINAMICS DCP
List Manual (LH21), 05/2016 91
2 Parameters
2.2 List of parameters
r2092.0...15 BO: IF1 PROFIdrive PZD3 receive bit-serial / IF1 PZD3 recv bitw
DCP_CTRL Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: 2460
Min Max Factory setting
- - -
Description: Binector output for bit-serial interconnection of PZD3 received from the PROFIdrive controller.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Bit 0 ON OFF -
01 Bit 1 ON OFF -
02 Bit 2 ON OFF -
03 Bit 3 ON OFF -
04 Bit 4 ON OFF -
05 Bit 5 ON OFF -
06 Bit 6 ON OFF -
07 Bit 7 ON OFF -
08 Bit 8 ON OFF -
09 Bit 9 ON OFF -
10 Bit 10 ON OFF -
11 Bit 11 ON OFF -
12 Bit 12 ON OFF -
13 Bit 13 ON OFF -
14 Bit 14 ON OFF -
15 Bit 15 ON OFF -
Note: IF1: Interface 1
r2093.0...15 BO: IF1 PROFIdrive PZD4 receive bit-serial / IF1 PZD4 recv bitw
CU_DCP Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: 2468
Min Max Factory setting
- - -
Description: Binector output for bit-serial interconnection of PZD4 (normally control word 2) received from the PROFIdrive
controller.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Bit 0 ON OFF -
01 Bit 1 ON OFF -
02 Bit 2 ON OFF -
03 Bit 3 ON OFF -
04 Bit 4 ON OFF -
05 Bit 5 ON OFF -
06 Bit 6 ON OFF -
07 Bit 7 ON OFF -
08 Bit 8 ON OFF -
SINAMICS DCP
92 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
09 Bit 9 ON OFF -
10 Bit 10 ON OFF -
11 Bit 11 ON OFF -
12 Bit 12 ON OFF -
13 Bit 13 ON OFF -
14 Bit 14 ON OFF -
15 Bit 15 ON OFF -
Note: IF1: Interface 1
r2093.0...15 BO: IF1 PROFIdrive PZD4 receive bit-serial / IF1 PZD4 recv bitw
DCP_CTRL Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: 2460
Min Max Factory setting
- - -
Description: Binector output for bit-serial interconnection of PZD4 (normally control word 2) received from the PROFIdrive
controller.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Bit 0 ON OFF -
01 Bit 1 ON OFF -
02 Bit 2 ON OFF -
03 Bit 3 ON OFF -
04 Bit 4 ON OFF -
05 Bit 5 ON OFF -
06 Bit 6 ON OFF -
07 Bit 7 ON OFF -
08 Bit 8 ON OFF -
09 Bit 9 ON OFF -
10 Bit 10 ON OFF -
11 Bit 11 ON OFF -
12 Bit 12 ON OFF -
13 Bit 13 ON OFF -
14 Bit 14 ON OFF -
15 Bit 15 ON OFF -
Note: IF1: Interface 1
SINAMICS DCP
List Manual (LH21), 05/2016 93
2 Parameters
2.2 List of parameters
SINAMICS DCP
94 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 95
2 Parameters
2.2 List of parameters
SINAMICS DCP
96 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 97
2 Parameters
2.2 List of parameters
Notice: For the following cases, it is not possible to re-parameterize the fault response to a fault:
- Fault number does not exist (exception value = 0).
- Message type is not "fault" (F).
- Fault response is not permissible for the set fault number.
Note: Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
The fault response can only be changed for faults with the appropriate identification (see the List Manual, chapter
"Faults and alarms").
Example:
F12345 and fault response = OFF3 (OFF1, OFF2, NONE)
--> The default fault response OFF3 can be changed to OFF1, OFF2 or NONE.
Re value = 1 (OFF1):
Braking along the ramp-function generator down ramp followed by a pulse inhibit.
Re value = 2 (OFF2):
Internal/external pulse inhibit.
Re value = 3 (OFF3):
Braking along the OFF3 down ramp followed by a pulse inhibit.
Parameter values designated as "reserved", act just like the value = 2 (OFF2)
SINAMICS DCP
98 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 99
2 Parameters
2.2 List of parameters
SINAMICS DCP
100 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 101
2 Parameters
2.2 List of parameters
SINAMICS DCP
102 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 103
2 Parameters
2.2 List of parameters
r2120 CO: Sum of fault and alarm buffer changes / Sum buffer changed
All objects Can be changed: - Access level: 4
Data type: Unsigned16 Func. diagram: 8065
Min Max Factory setting
- - -
Description: Displays the sum of all of the fault and alarm buffer changes in the drive unit.
Dependency: Refer to: r0944, r2121
SINAMICS DCP
104 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 105
2 Parameters
2.2 List of parameters
Dependency: Refer to: r2110, r2114, r2122, r2124, r2125, r2134, r2145, r2146, r3121, r3123
Notice: The time comprises r2145 (days) and r2123 (milliseconds).
Note: The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the alarm buffer and the assignment of the indices is shown in r2122.
SINAMICS DCP
106 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
Dependency: Selects the faults and sets the required acknowledge mode realized under the same index
Refer to: p2127
Note: Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
SINAMICS DCP
List Manual (LH21), 05/2016 107
2 Parameters
2.2 List of parameters
Note: Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
The acknowledge mode can only be changed for faults with the appropriate identification.
Example:
F12345 and acknowledge mode = IMMEDIATELY (POWER ON)
--> The acknowledge mode can be changed from IMMEDIATELY to POWER ON.
SINAMICS DCP
108 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 109
2 Parameters
2.2 List of parameters
SINAMICS DCP
110 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 111
2 Parameters
2.2 List of parameters
p2147 Delete fault buffer of all drive objects / Del fault buffer
CU_DCP Can be changed: U, T Access level: 4
Data type: Integer16 Func. diagram: 8060
Min Max Factory setting
0 1 0
Description: Setting to delete the fault buffer of all existing drive objects.
Value: 0: Inactive
1: Start to delete the fault buffer of all drive objects
Dependency: Refer to: r0945, r0947, r0948, r0949, r2109, r2130, r2133, r2136
Note: p2147 is automatically set to 0 after execution.
SINAMICS DCP
112 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 113
2 Parameters
2.2 List of parameters
SINAMICS DCP
114 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 115
2 Parameters
2.2 List of parameters
p3109 RTC real time synchronization tolerance window / RTC sync tol
CU_DCP Can be changed: U, T Access level: 3
Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
0 [ms] 1000 [ms] 100 [ms]
Description: Sets the tolerance window for time synchronization.
When this tolerance window is exceeded, an appropriate alarm is output.
Dependency: Refer to: A01099
p3112 BI: External fault 3 enable negated / Ext flt 3 enab neg
CU_DCP, TM150, Can be changed: U, T Access level: 3
TM15DI_DO, TM31 Data type: Unsigned32 / Binary Func. diagram: 2546
Min Max Factory setting
- - 0
Description: Sets the signal source for the negated enable signal of external fault 3.
SINAMICS DCP
116 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
p3112[0...n] BI: External fault 3 enable negated / Ext flt 3 enab neg
DCP_CTRL Can be changed: U, T Access level: 3
Data type: Unsigned32 / Binary Func. diagram: -
Min Max Factory setting
- - 0
Description: Sets the signal source for the negated enable signal of external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency: Refer to: p2108, p3110, p3111
Refer to: F07862
SINAMICS DCP
List Manual (LH21), 05/2016 117
2 Parameters
2.2 List of parameters
Re bit 04:
The temperature in the component has exceeded the highest permissible limit. Check the ambient temperature /
control cabinet cooling.
Re bit 05:
A ground fault / inter-phase short-circuit was detected in the power cables or in the motor windings. Check the power
cable (connection). Check the motor.
Re bit 06:
The motor was operated outside the permissible limits (temperature, current, torque, ...). Check the load cycles and
limits that have been set. Check the ambient temperature / motor cooling.
Re bit 07:
The communication to the higher-level control system (internal coupling, PROFIBUS, PROFINET, ...) is faulted or
interrupted. Check the state of the higher-level control system. Check the communication connection/wiring. Check
the bus configuration / clock cycles.
Re bit 08:
A safety operation monitoring function (Safety) has detected an error.
Re bit 09:
When evaluating the encoder signals (track signals, zero marks, absolute values, ...) an illegal signal state was
detected. Check the encoder / state of the encoder signals. Observe the maximum frequencies.
Re bit 10:
The internal communication between the SINAMICS components is faulted or interrupted. Check the DRIVE-CLiQ
wiring. Ensure an EMC-compliant design. Observe the maximum permissible quantity structure / clock cycles.
Re bit 11:
The infeed is faulted or has failed. Check the infeed and the surroundings (line supply, filter, reactors, fuses, ...).
Check the closed-loop infeed control.
Re bit 15:
Group fault. Determine the precise cause of the fault using the commissioning tool.
SINAMICS DCP
118 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 119
2 Parameters
2.2 List of parameters
SINAMICS DCP
120 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 121
2 Parameters
2.2 List of parameters
SINAMICS DCP
122 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 123
2 Parameters
2.2 List of parameters
SINAMICS DCP
124 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
r4021 TM15DI/DO digital inputs terminal actual value / TM15D DI act val
TM15DI_DO Can be changed: - Access level: 2
Data type: Unsigned32 Func. diagram: 9400, 9401,
9402
Min Max Factory setting
- - -
Description: Displays the actual value at the digital inputs.
This means that the actual input signal can be checked at terminal DI x or DI/DO x prior to switching from the
simulation mode (p4095.x = 1) to terminal mode (p4095.x = 0).
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI/DO 0 (X520.2) High Low -
01 DI/DO 1 (X520.3) High Low -
02 DI/DO 2 (X520.4) High Low -
03 DI/DO 3 (X520.5) High Low -
04 DI/DO 4 (X520.6) High Low -
05 DI/DO 5 (X520.7) High Low -
06 DI/DO 6 (X520.8) High Low -
07 DI/DO 7 (X520.9) High Low -
08 DI/DO 8 (X521.2) High Low -
09 DI/DO 9 (X521.3) High Low -
10 DI/DO 10 (X521.4) High Low -
11 DI/DO 11 (X521.5) High Low -
12 DI/DO 12 (X521.6) High Low -
13 DI/DO 13 (X521.7) High Low -
14 DI/DO 14 (X521.8) High Low -
15 DI/DO 15 (X521.9) High Low -
16 DI/DO 16 (X522.2) High Low -
17 DI/DO 17 (X522.3) High Low -
18 DI/DO 18 (X522.4) High Low -
19 DI/DO 19 (X522.5) High Low -
20 DI/DO 20 (X522.6) High Low -
21 DI/DO 21 (X522.7) High Low -
22 DI/DO 22 (X522.8) High Low -
23 DI/DO 23 (X522.9) High Low -
Note: If a DI/DO is parameterized as output (p4028.x = 1), then r4021.x = 0 is displayed.
DI/DO: Bidirectional Digital Input/Output
r4021 TM31 digital inputs terminal actual value / TM31 DI act value
TM31 Can be changed: - Access level: 2
Data type: Unsigned32 Func. diagram: 9549, 9550,
9552, 9560, 9562
Min Max Factory setting
- - -
Description: Displays the actual value at the digital inputs.
This means that the actual input signal can be checked at terminal DI x or DI/DO x prior to switching from the
simulation mode (p4095.x = 1) to terminal mode (p4095.x = 0).
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X520.1) High Low -
01 DI 1 (X520.2) High Low -
02 DI 2 (X520.3) High Low -
03 DI 3 (X520.4) High Low -
04 DI 4 (X530.1) High Low -
05 DI 5 (X530.2) High Low -
06 DI 6 (X530.3) High Low -
07 DI 7 (X530.4) High Low -
08 DI/DO 8 (X541.2) High Low -
09 DI/DO 9 (X541.3) High Low -
10 DI/DO 10 (X541.4) High Low -
11 DI/DO 11 (X541.5) High Low -
SINAMICS DCP
List Manual (LH21), 05/2016 125
2 Parameters
2.2 List of parameters
SINAMICS DCP
126 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
r4023.0...23 CO/BO: TM15DI/DO digital inputs status inverted / TM15D DI stat inv
TM15DI_DO Can be changed: - Access level: 1
Data type: Unsigned32 Func. diagram: 9399, 9400,
9401, 9402
Min Max Factory setting
- - -
Description: Displays the inverted status of the digital inputs of Terminal Module 15 (TM15).
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI/DO 0 (X520.2) High Low -
01 DI/DO 1 (X520.3) High Low -
02 DI/DO 2 (X520.4) High Low -
03 DI/DO 3 (X520.5) High Low -
04 DI/DO 4 (X520.6) High Low -
05 DI/DO 5 (X520.7) High Low -
06 DI/DO 6 (X520.8) High Low -
07 DI/DO 7 (X520.9) High Low -
08 DI/DO 8 (X521.2) High Low -
09 DI/DO 9 (X521.3) High Low -
10 DI/DO 10 (X521.4) High Low -
11 DI/DO 11 (X521.5) High Low -
12 DI/DO 12 (X521.6) High Low -
13 DI/DO 13 (X521.7) High Low -
14 DI/DO 14 (X521.8) High Low -
15 DI/DO 15 (X521.9) High Low -
16 DI/DO 16 (X522.2) High Low -
17 DI/DO 17 (X522.3) High Low -
18 DI/DO 18 (X522.4) High Low -
19 DI/DO 19 (X522.5) High Low -
20 DI/DO 20 (X522.6) High Low -
21 DI/DO 21 (X522.7) High Low -
22 DI/DO 22 (X522.8) High Low -
23 DI/DO 23 (X522.9) High Low -
Dependency: Refer to: r4022, r4024, r4025
Notice: For the BICO interconnection of the connector output (CO) only bit 00 ... 15 are transferred.
Note: DI/DO: Bidirectional Digital Input/Output
r4023.0...11 CO/BO: TM31 digital inputs status inverted / TM31 DI status inv
TM31 Can be changed: - Access level: 1
Data type: Unsigned32 Func. diagram: 9549, 9550,
9552, 9560, 9562
Min Max Factory setting
- - -
Description: Displays the inverted status of the digital inputs of Terminal Module 31 (TM31).
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X520.1) High Low -
01 DI 1 (X520.2) High Low -
02 DI 2 (X520.3) High Low -
03 DI 3 (X520.4) High Low -
04 DI 4 (X530.1) High Low -
05 DI 5 (X530.2) High Low -
06 DI 6 (X530.3) High Low -
07 DI 7 (X530.4) High Low -
08 DI/DO 8 (X541.2) High Low -
09 DI/DO 9 (X541.3) High Low -
10 DI/DO 10 (X541.4) High Low -
11 DI/DO 11 (X541.5) High Low -
SINAMICS DCP
List Manual (LH21), 05/2016 127
2 Parameters
2.2 List of parameters
r4025 CO: TM15DI/DO digital inputs 16 ... 23 status inverted / TM15D DI 16-23 inv
TM15DI_DO Can be changed: - Access level: 1
Data type: Unsigned16 Func. diagram: 9402
Min Max Factory setting
- - -
Description: Displays the inverted status of digital inputs 16 ... 23 of Terminal Module 15 (TM15).
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI/DO 16 (X522.2) ON OFF -
01 DI/DO 17 (X522.3) ON OFF -
02 DI/DO 18 (X522.4) ON OFF -
03 DI/DO 19 (X522.5) ON OFF -
04 DI/DO 20 (X522.6) ON OFF -
05 DI/DO 21 (X522.7) ON OFF -
06 DI/DO 22 (X522.8) ON OFF -
07 DI/DO 23 (X522.9) ON OFF -
Dependency: Refer to: r4022, r4023, r4024
Note: DI: Digital Input
SINAMICS DCP
128 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
p4030 BI: TM15DI/DO signal source for terminal DI/DO 0 / TM15D S_src DI/DO0
TM15DI_DO Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9399, 9400
Min Max Factory setting
- - 0
Description: Sets the signal source for terminal DI/DO 0 (X520.2) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.0 = 1).
DI/DO: Bidirectional Digital Input/Output
SINAMICS DCP
List Manual (LH21), 05/2016 129
2 Parameters
2.2 List of parameters
p4031 BI: TM15DI/DO signal source for terminal DI/DO 1 / TM15D S_src DI/DO1
TM15DI_DO Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9400
Min Max Factory setting
- - 0
Description: Sets the signal source for terminal DI/DO 1 (X520.3) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.1 = 1).
DI/DO: Bidirectional Digital Input/Output
p4032 BI: TM15DI/DO signal source for terminal DI/DO 2 / TM15D S_src DI/DO2
TM15DI_DO Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9400
Min Max Factory setting
- - 0
Description: Sets the signal source for terminal DI/DO 2 (X520.4) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.2 = 1).
DI/DO: Bidirectional Digital Input/Output
p4033 BI: TM15DI/DO signal source for terminal DI/DO 3 / TM15D S_src DI/DO3
TM15DI_DO Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9400
Min Max Factory setting
- - 0
Description: Sets the signal source for terminal DI/DO 3 (X520.5) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.3 = 1).
DI/DO: Bidirectional Digital Input/Output
p4034 BI: TM15DI/DO signal source for terminal DI/DO 4 / TM15D S_src DI/DO4
TM15DI_DO Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9400
Min Max Factory setting
- - 0
Description: Sets the signal source for terminal DI/DO 4 (X520.6) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.4 = 1).
DI/DO: Bidirectional Digital Input/Output
SINAMICS DCP
130 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
p4035 BI: TM15DI/DO signal source for terminal DI/DO 5 / TM15D S_src DI/DO5
TM15DI_DO Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9400
Min Max Factory setting
- - 0
Description: Sets the signal source for terminal DI/DO 5 (X520.7) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.5 = 1).
DI/DO: Bidirectional Digital Input/Output
p4036 BI: TM15DI/DO signal source for terminal DI/DO 6 / TM15D S_src DI/DO6
TM15DI_DO Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9400
Min Max Factory setting
- - 0
Description: Sets the signal source for terminal DI/DO 6 (X520.8) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.6 = 1).
DI/DO: Bidirectional Digital Input/Output
p4037 BI: TM15DI/DO signal source for terminal DI/DO 7 / TM15D s_src DI/DO7
TM15DI_DO Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9400
Min Max Factory setting
- - 0
Description: Sets the signal source for terminal DI/DO 7 (X520.9) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.7 = 1).
DI/DO: Bidirectional Digital Input/Output
p4038 BI: TM15DI/DO signal source for terminal DI/DO 8 / TM15D s_src DI/DO8
TM15DI_DO Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9401
Min Max Factory setting
- - 0
Description: Sets the signal source for terminal DI/DO 8 (X521.2) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.8 = 1).
DI/DO: Bidirectional Digital Input/Output
p4038 BI: TM31 signal source for terminal DI/DO 8 / TM31 S_src DI/DO8
TM31 Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9549, 9560
Min Max Factory setting
- - 0
Description: Sets the signal source for terminal DI/DO 8 (X541.2) of Terminal Module 31 (TM31).
Note: Prerequisite: The DI/DO must be set as an output (p4028.8 = 1).
DI/DO: Bidirectional Digital Input/Output
p4039 BI: TM15DI/DO signal source for terminal DI/DO 9 / TM15D s_src DI/DO9
TM15DI_DO Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9401
Min Max Factory setting
- - 0
Description: Sets the signal source for terminal DI/DO 9 (X521.3) of Terminal Module 15 (TM15).
SINAMICS DCP
List Manual (LH21), 05/2016 131
2 Parameters
2.2 List of parameters
p4039 BI: TM31 signal source for terminal DI/DO 9 / TM31 S_src DI/DO9
TM31 Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9560
Min Max Factory setting
- - 0
Description: Sets the signal source for terminal DI/DO 9 (X541.3) of Terminal Module 31 (TM31).
Note: Prerequisite: The DI/DO must be set as an output (p4028.9 = 1).
DI/DO: Bidirectional Digital Input/Output
p4040 BI: TM15DI/DO signal source for terminal DI/DO 10 / TM15D s_srcDI/DO10
TM15DI_DO Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9401
Min Max Factory setting
- - 0
Description: Sets the signal source for terminal DI/DO 10 (X521.4) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.10 = 1).
DI/DO: Bidirectional Digital Input/Output
p4040 BI: TM31 signal source for terminal DI/DO 10 / TM31 S_src DI/DO10
TM31 Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9562
Min Max Factory setting
- - 0
Description: Sets the signal source for terminal DI/DO 10 (X541.4) of Terminal Module 31 (TM31).
Note: Prerequisite: The DI/DO must be set as an output (p4028.10 = 1).
DI/DO: Bidirectional Digital Input/Output
p4041 BI: TM15DI/DO signal source for terminal DI/DO 11 / TM15D s_srcDI/DO11
TM15DI_DO Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9401
Min Max Factory setting
- - 0
Description: Sets the signal source for terminal DI/DO 11 (X521.5) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.11 = 1).
DI/DO: Bidirectional Digital Input/Output
p4041 BI: TM31 signal source for terminal DI/DO 11 / TM31 S_src DI/DO11
TM31 Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9549, 9562
Min Max Factory setting
- - 0
Description: Sets the signal source for terminal DI/DO 11 (X541.5) of Terminal Module 31 (TM31).
Note: Prerequisite: The DI/DO must be set as an output (p4028.11 = 1).
DI/DO: Bidirectional Digital Input/Output
SINAMICS DCP
132 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
p4042 BI: TM15DI/DO signal source for terminal DI/DO 12 / TM15D s_srcDI/DO12
TM15DI_DO Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9401
Min Max Factory setting
- - 0
Description: Sets the signal source for terminal DI/DO 12 (X521.6) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.12 = 1).
DI/DO: Bidirectional Digital Input/Output
p4043 BI: TM15DI/DO signal source for terminal DI/DO 13 / TM15D s_srcDI/DO13
TM15DI_DO Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9401
Min Max Factory setting
- - 0
Description: Sets the signal source for terminal DI/DO 13 (X521.7) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.13 = 1).
DI/DO: Bidirectional Digital Input/Output
p4044 BI: TM15DI/DO signal source for terminal DI/DO 14 / TM15D s_srcDI/DO14
TM15DI_DO Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9401
Min Max Factory setting
- - 0
Description: Sets the signal source for terminal DI/DO 14 (X521.8) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.14 = 1).
DI/DO: Bidirectional Digital Input/Output
p4045 BI: TM15DI/DO signal source for terminal DI/DO 15 / TM15D s_srcDI/DO15
TM15DI_DO Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9401
Min Max Factory setting
- - 0
Description: Sets the signal source for terminal DI/DO 15 (X521.9) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.15 = 1).
DI/DO: Bidirectional Digital Input/Output
SINAMICS DCP
List Manual (LH21), 05/2016 133
2 Parameters
2.2 List of parameters
SINAMICS DCP
134 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
r4052[0...1] CO: TM31 analog inputs current input voltage/current / TM31 AI U/I_inp
TM31 Can be changed: - Access level: 1
Data type: FloatingPoint32 Func. diagram: 9566, 9568
Min Max Factory setting
- - -
Description: Displays the actual input voltage in V when set as voltage input.
SINAMICS DCP
List Manual (LH21), 05/2016 135
2 Parameters
2.2 List of parameters
Displays the actual input current in mA when set as current input and with the load resistor switched in.
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency: The type of analog input AI x (voltage or current input) is set using p4056.
Refer to: p4056
Note: AI: Analog Input
r4055[0...1] CO: TM31 analog inputs actual value in percent / TM31 AI value in %
TM31 Can be changed: - Access level: 1
Data type: FloatingPoint32 Func. diagram: 9549, 9566,
9568
Min Max Factory setting
- [%] - [%] - [%]
Description: Displays the currently referred input value of the analog inputs of Terminal Module 31 (TM31).
When interconnected, the signals are referred to the reference quantities p200x and p205x.
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Note: AI: Analog Input
SINAMICS DCP
136 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
Note: When changing p4056, the parameters of the scaling characteristic (p4057, p4058, p4059, p4060) are overwritten
with the following default values:
For p4056 = 0, 4, p4057 is set to 0.0 V, p4058 to 0.0 %, p4059 to 10.0 V and p4060 to 100.0 %.
For p4056 = 2, 5, p4057 is set to 0.0 mA, p4058 to 0.0 %, p4059 to 20.0 mA and p4060 to 100.0 %.
For p4056 = 3, p4057 is set to 4.0 mA, p4058 to 0.0 %, p4059 to 20.0 mA and p4060 to 100.0 %.
SINAMICS DCP
List Manual (LH21), 05/2016 137
2 Parameters
2.2 List of parameters
p4062[0...1] TM31 analog inputs wire breakage monitoring delay time / TM31 wirebrk t_del
TM31 Can be changed: U, T Access level: 2
Data type: Unsigned16 Func. diagram: 9566, 9568
Min Max Factory setting
0 [ms] 1000 [ms] 100 [ms]
Description: Sets the delay time for wire-breakage monitoring of the analog inputs on Terminal Module 31 (TM31).
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
p4066[0...1] TM31 analog inputs activate absolute value generation / TM31 AI absVal act
TM31 Can be changed: U, T Access level: 3
Data type: Integer16 Func. diagram: 9566, 9568
Min Max Factory setting
0 1 0
Description: Activates the absolute value generation for the analog input signals of Terminal Module 31 (TM31).
Value: 0: No absolute value generation
1: Absolute value generation switched in
SINAMICS DCP
138 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
p4067[0...1] BI: TM31 analog inputs invert signal source / TM31 AI inv s_src
TM31 Can be changed: U, T Access level: 3
Data type: Unsigned32 / Binary Func. diagram: 9566, 9568
Min Max Factory setting
- - 0
Description: Sets the signal source to invert the analog inputs signals of Terminal Module 31 (TM31).
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
p4069[0...1] BI: TM31 analog inputs signal source for enable / TM31 AI enable
TM31 Can be changed: U, T Access level: 3
Data type: Unsigned32 / Binary Func. diagram: 9566, 9568
Min Max Factory setting
- - 1
Description: Sets the signal source for the enable signal of the analog inputs of Terminal Module 31 (TM31).
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
r4072[0...1] TM31 analog outputs output value currently referred / TM31 AO outp_val
TM31 Can be changed: - Access level: 1
Data type: FloatingPoint32 Func. diagram: 9572
Min Max Factory setting
- [%] - [%] - [%]
Description: Displays the actual referred output value of the analog outputs of Terminal Module 31 (TM31).
Index: [0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
SINAMICS DCP
List Manual (LH21), 05/2016 139
2 Parameters
2.2 List of parameters
p4075[0...1] TM31 analog outputs activate absolute value generation / TM31 AO absVal act
TM31 Can be changed: T Access level: 3
Data type: Integer16 Func. diagram: 9572
Min Max Factory setting
0 1 0
Description: Activates the absolute value generation for the analog outputs of Terminal Module 31 (TM31).
Value: 0: No absolute value generation
1: Absolute value generation switched in
Index: [0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
SINAMICS DCP
140 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 141
2 Parameters
2.2 List of parameters
p4082[0...1] BI: TM31 analog outputs invert signal source / TM31 AO inv s_src
TM31 Can be changed: U, T Access level: 3
Data type: Unsigned32 / Binary Func. diagram: 9572
Min Max Factory setting
- - 0
Description: Sets the signal source to invert the analog output signals of Terminal Module 31 (TM31).
Index: [0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
p4086 BI: TM15DI/DO signal source for terminal DI/DO 16 / TM15D s_srcDI/DO16
TM15DI_DO Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9402
Min Max Factory setting
- - 0
Description: Sets the signal source for terminal DI/DO 16 (X522.2) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.16 = 1).
DI/DO: Bidirectional Digital Input/Output
p4087 BI: TM15DI/DO signal source for terminal DI/DO 17 / TM15D s_srcDI/DO17
TM15DI_DO Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9402
Min Max Factory setting
- - 0
Description: Sets the signal source for terminal DI/DO 17 (X522.3) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.17 = 1).
DI/DO: Bidirectional Digital Input/Output
p4088 BI: TM15DI/DO signal source for terminal DI/DO 18 / TM15D s_srcDI/DO18
TM15DI_DO Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9402
Min Max Factory setting
- - 0
Description: Sets the signal source for terminal DI/DO 18 (X522.4) of Terminal Module 15 (TM15).
SINAMICS DCP
142 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
p4089 BI: TM15DI/DO signal source for terminal DI/DO 19 / TM15D s_srcDI/DO19
TM15DI_DO Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9402
Min Max Factory setting
- - 0
Description: Sets the signal source for terminal DI/DO 19 (X522.5) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.19 = 1).
DI/DO: Bidirectional Digital Input/Output
p4090 BI: TM15DI/DO signal source for terminal DI/DO 20 / TM15D S_srcDI/DO20
TM15DI_DO Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9402
Min Max Factory setting
- - 0
Description: Sets the signal source for terminal DI/DO 20 (X522.6) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.20 = 1).
DI/DO: Bidirectional Digital Input/Output
p4091 BI: TM15DI/DO signal source for terminal DI/DO 21 / TM15D S_srcDI/DO21
TM15DI_DO Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9402
Min Max Factory setting
- - 0
Description: Sets the signal source for terminal DI/DO 21 (X522.7) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.21 = 1).
DI/DO: Bidirectional Digital Input/Output
p4092 BI: TM15DI/DO signal source for terminal DI/DO 22 / TM15D S_srcDI/DO22
TM15DI_DO Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9402
Min Max Factory setting
- - 0
Description: Sets the signal source for terminal DI/DO 22 (X522.8) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.22 = 1).
DI/DO: Bidirectional Digital Input/Output
p4093 BI: TM15DI/DO signal source for terminal DI/DO 23 / TM15D S_srcDI/DO23
TM15DI_DO Can be changed: U, T Access level: 1
Data type: Unsigned32 / Binary Func. diagram: 9402
Min Max Factory setting
- - 0
Description: Sets the signal source for terminal DI/DO 23 (X522.9) of Terminal Module 15 (TM15).
Note: Prerequisite: The DI/DO must be set as an output (p4028.23 = 1).
DI/DO: Bidirectional Digital Input/Output
SINAMICS DCP
List Manual (LH21), 05/2016 143
2 Parameters
2.2 List of parameters
r4094.0...23 BO: TM15 digital inputs status inverted raw data internal / TM15 DI st raw dat
TM15DI_DO Can be changed: - Access level: 4
Data type: Unsigned32 Func. diagram: -
Min Max Factory setting
- - -
Description: Displays the inverted status of the raw data of the digital inputs of the Terminal Module 15 (TM15).
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI/DO 0 (X520.2) High Low -
01 DI/DO 1 (X520.3) High Low -
02 DI/DO 2 (X520.4) High Low -
03 DI/DO 3 (X520.5) High Low -
04 DI/DO 4 (X520.6) High Low -
05 DI/DO 5 (X520.7) High Low -
06 DI/DO 6 (X520.8) High Low -
07 DI/DO 7 (X520.9) High Low -
08 DI/DO 8 (X521.2) High Low -
09 DI/DO 9 (X521.3) High Low -
10 DI/DO 10 (X521.4) High Low -
11 DI/DO 11 (X521.5) High Low -
12 DI/DO 12 (X521.6) High Low -
13 DI/DO 13 (X521.7) High Low -
14 DI/DO 14 (X521.8) High Low -
15 DI/DO 15 (X521.9) High Low -
16 DI/DO 16 (X522.2) High Low -
17 DI/DO 17 (X522.3) High Low -
18 DI/DO 18 (X522.4) High Low -
19 DI/DO 19 (X522.5) High Low -
20 DI/DO 20 (X522.6) High Low -
21 DI/DO 21 (X522.7) High Low -
22 DI/DO 22 (X522.8) High Low -
23 DI/DO 23 (X522.9) High Low -
Notice: The raw data of the digital inputs is directly displayed (e.g. without any debounce).
Note: Should only used for internal Siemens purposes (alternative r4022, r4023).
SINAMICS DCP
144 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
Note: This parameter is not saved when data is backed-up (p0971, p0977).
DI/DO: Bidirectional Digital Input/Output
Note: This parameter is not saved when data is backed-up (p0971, p0977).
DI: Digital Input
DI/DO: Bidirectional Digital Input/Output
p4096 TM15DI/DO digital inputs simulation mode, setpoint / TM15D DI sim setp
TM15DI_DO Can be changed: U, T Access level: 2
Data type: Unsigned32 Func. diagram: 9400, 9401,
9402
Min Max Factory setting
- - 0000 0000 0000 0000 0000
0000 0000 0000 bin
Description: Sets the setpoint for the input signals in the simulation mode of the digital inputs of Terminal Module 15 (TM15).
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI/DO 0 (X520.2) High Low -
01 DI/DO 1 (X520.3) High Low -
02 DI/DO 2 (X520.4) High Low -
03 DI/DO 3 (X520.5) High Low -
04 DI/DO 4 (X520.6) High Low -
05 DI/DO 5 (X520.7) High Low -
SINAMICS DCP
List Manual (LH21), 05/2016 145
2 Parameters
2.2 List of parameters
p4096 TM31 digital inputs simulation mode setpoint / TM31 DI sim setp
TM31 Can be changed: U, T Access level: 2
Data type: Unsigned32 Func. diagram: 9549, 9550,
9552, 9560, 9562
Min Max Factory setting
- - 0000 0000 0000 0000 bin
Description: Sets the setpoint for the input signals in the simulation mode of the digital inputs of Terminal Module 31 (TM31).
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X520.1) High Low -
01 DI 1 (X520.2) High Low -
02 DI 2 (X520.3) High Low -
03 DI 3 (X520.4) High Low -
04 DI 4 (X530.1) High Low -
05 DI 5 (X530.2) High Low -
06 DI 6 (X530.3) High Low -
07 DI 7 (X530.4) High Low -
08 DI/DO 8 (X541.2) High Low -
09 DI/DO 9 (X541.3) High Low -
10 DI/DO 10 (X541.4) High Low -
11 DI/DO 11 (X541.5) High Low -
Dependency: The simulation of a digital input is selected using p4095.
Refer to: p4095
Note: This parameter is not saved when data is backed-up (p0971, p0977).
DI: Digital Input
DI/DO: Bidirectional Digital Input/Output
SINAMICS DCP
146 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
Dependency: The setpoint for the input voltage is specified via p4098.
Refer to: p4098
Note: This parameter is not saved when data is backed-up (p0971, p0977).
AI: Analog Input
p4098[0...1] TM31 analog inputs simulation mode setpoint / TM31 AI sim setp
TM31 Can be changed: U, T Access level: 2
Data type: FloatingPoint32 Func. diagram: 9566, 9568
Min Max Factory setting
-20.000 20.000 0.000
Description: Sets the setpoint for the input value in simulation mode of the analog inputs of Terminal Module 31 (TM31).
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency: The simulation of an analog input is selected using p4097.
If AI x is parameterized as voltage input (p4056), then the setpoint is a voltage in V.
If AI x is parameterized as current input (p4056), then the setpoint is a current in mA.
Refer to: p4056, p4097
Note: This parameter is not saved when data is backed-up (p0971, p0977).
AI: Analog Input
SINAMICS DCP
List Manual (LH21), 05/2016 147
2 Parameters
2.2 List of parameters
Note: The changed sampling time is immediately effective after a completed sub-boot (p0009 -> 0).
Parameter p4099[0] must never be equal to zero.
SINAMICS DCP
148 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 149
2 Parameters
2.2 List of parameters
SINAMICS DCP
150 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
Note: For p4103 = 0 s and sensor type "KTY84", "PT100", "PT1000" (p4100[0...11] = 2, 5, 6) the following applies:
- The corresponding fault can only be initiated via the fault threshold (output of the timer is always a logical 0).
For p4103 = 0 s and sensor type "PTC thermistor", "Bimetallic NC contact" (p4100[0...11] = 1, 4), the following
applies:
- The corresponding alarm and fault are simultaneously output (delay time = 0 s).
Note: With p4103 = 0 ms, the timer is de-activated and only the fault threshold is effective.
SINAMICS DCP
List Manual (LH21), 05/2016 151
2 Parameters
2.2 List of parameters
SINAMICS DCP
152 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 153
2 Parameters
2.2 List of parameters
SINAMICS DCP
154 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 155
2 Parameters
2.2 List of parameters
Notice: When forming groups, it must be ensured that in one particular group, only temperature channels with the following
sensor types are included:
- "KTY84", "PT100", "PT1000" (p4100[0...11] = 2, 5, 6), real temperature actual value
or alternatively
- "PTC thermistor", "bimetallic NC contact" (p4100[0...11] = 1, 4), fictitious temperature actual value (-50 °C, 250 °C)
If these sensor types are combined within one group, then the calculated values for maximum, minimum and average
value will be falsified.
Note: Active and inactive temperature channels can be included in one group. However, when calculating the values
(r4112, r4113, r4114) only the active temperature channels with valid actual value are taken into account
(r4105[0...11] not equal to -300 °C).
r4112[0...2] CO: TM150 group temperature actual value maximum value / TM150 grp temp max
TM150 Can be changed: - Access level: 1
Data type: FloatingPoint32 Func. diagram: 9625
Min Max Factory setting
- [°C] - [°C] - [°C]
Description: Display and connector output for the maximum value of each group for the Terminal Module 150 (TM150).
This value is calculated from the actual temperature values (r4105[0...11]) of each group.
Recommendation: The following connector inputs can use these connector outputs for interconnection:
- CI: p0603
- CI: p0608[0...3]
- CI: p0609[0...3]
- CI: p2051
Index: [0] = Group 0
[1] = Group 1
[2] = Group 2
Dependency: Refer to: r4105, p4111, r4113, r4114
r4113[0...2] CO: TM150 group temperature actual value minimum value / TM150 grp temp min
TM150 Can be changed: - Access level: 1
Data type: FloatingPoint32 Func. diagram: 9625
Min Max Factory setting
- [°C] - [°C] - [°C]
Description: Display and connector output for the minimum value of each group for the Terminal Module 150 (TM150).
This value is calculated from the actual temperature values (r4105[0...11]) of each group.
Recommendation: The following connector inputs can use these connector outputs for interconnection:
- CI: p0603
- CI: p0608[0...3]
- CI: p0609[0...3]
- CI: p2051
Index: [0] = Group 0
[1] = Group 1
[2] = Group 2
Dependency: Refer to: r4105, p4111, r4112, r4114
r4114[0...2] CO: TM150 group temperature average actual value / TM150 grp temp av
TM150 Can be changed: - Access level: 1
Data type: FloatingPoint32 Func. diagram: 9625
Min Max Factory setting
- [°C] - [°C] - [°C]
Description: Display and connector output for the average value of each group for the Terminal Module 150 (TM150).
This value is calculated from the actual temperature values (r4105[0...11]) of each group.
SINAMICS DCP
156 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
Recommendation: The following connector inputs can use these connector outputs for interconnection:
- CI: p0603
- CI: p0608[0...3]
- CI: p0609[0...3]
- CI: p2051
Index: [0] = Group 0
[1] = Group 1
[2] = Group 2
Dependency: Refer to: r4105, p4111, r4112, r4113
Note: If one group is assigned sensor type "PTC" or "bimetal NC contact", then the average value -300 °C is output.
SINAMICS DCP
List Manual (LH21), 05/2016 157
2 Parameters
2.2 List of parameters
p4641[0...2] OEM encoder diagnostic signal selection / OEM enc diag sel
DCP_CTRL Can be changed: U, T Access level: 3
Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
0 65535 0
Description: Trace functionality for OEM encoder manufacturers.
Index: [0] = Encoder 1
[1] = Encoder 2
[2] = Encoder 3
SINAMICS DCP
158 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 159
2 Parameters
2.2 List of parameters
r4709[0...1] Trace memory space required for measuring functions / Trace mem required
CU_DCP Can be changed: - Access level: 3
Data type: Unsigned32 Func. diagram: -
Min Max Factory setting
- - -
Description: Displays the required memory in bytes for the actual parameterization.
This applies, if the trace for the measurement functions is used.
Index: [0] = Trace 0
[1] = Trace 1
Dependency: Refer to: r4799
SINAMICS DCP
160 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 161
2 Parameters
2.2 List of parameters
p4715[0...1] Trace bit mask trigger, bit mask / Trace trig mask
CU_DCP Can be changed: U, T Access level: 3
Data type: Unsigned32 Func. diagram: -
Min Max Factory setting
0 4294967295 0
Description: Sets the bit mask for the bit mask trigger.
Index: [0] = Trace 0
[1] = Trace 1
Dependency: Only effective when p4710 = 6.
SINAMICS DCP
162 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 163
2 Parameters
2.2 List of parameters
SINAMICS DCP
164 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 165
2 Parameters
2.2 List of parameters
SINAMICS DCP
166 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 167
2 Parameters
2.2 List of parameters
r4750[0...16383] Trace 1 trace buffer signal 0 floating point / Trace 1 trace sig0
CU_DCP Can be changed: - Access level: 3
Data type: FloatingPoint32 Func. diagram: -
Min Max Factory setting
- - -
Description: Displays the trace buffer (record buffer) for trace 1 and signal 0.
Dependency: Refer to: r4740, p4795
SINAMICS DCP
168 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 169
2 Parameters
2.2 List of parameters
SINAMICS DCP
170 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 171
2 Parameters
2.2 List of parameters
SINAMICS DCP
172 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 173
2 Parameters
2.2 List of parameters
SINAMICS DCP
174 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 175
2 Parameters
2.2 List of parameters
SINAMICS DCP
176 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
p4813 Function generator physical address reference value / FG phys addr ref
CU_DCP Can be changed: U, T Access level: 3
Data type: FloatingPoint32 Func. diagram: -
Min Max Factory setting
1.00 1000000.00 1.00
Description: Sets the reference value for 100 % for referred inputs.
Dependency: Only effective when p4810 = 99.
p4816 Function generator output signal integer number scaling / FG outp integ scal
CU_DCP Can be changed: U, T Access level: 4
Data type: Integer32 Func. diagram: -
Min Max Factory setting
-2147483648 2147483647 0
Description: Sets the scaling for the integer number of the output signal for the function generator.
Dependency: Refer to: r4805, r4817
Note: The parameter can only be changed in the following operating states:
r4805 = 0, 4, 6
r4817 CO: Function generator output signal integer number / FG outp integ no.
CU_DCP Can be changed: - Access level: 4
Data type: Integer32 Func. diagram: -
Min Max Factory setting
- - -
Description: Display and connector output for the integer number of the output signal for the function generator.
Dependency: Refer to: p4816
Note: The value is output independent of the function generator operating mode.
SINAMICS DCP
List Manual (LH21), 05/2016 177
2 Parameters
2.2 List of parameters
Value: 1: Square-wave
2: Staircase
3: Delta
4: Binary noise - PRBS (Pseudo Random Binary Signal)
5: Sine-wave
SINAMICS DCP
178 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 179
2 Parameters
2.2 List of parameters
r4834[0...4] CO: Function generator free measurement output signal / FG fr MeasFct outp
CU_DCP Can be changed: - Access level: 3
Data type: FloatingPoint32 Func. diagram: -
Min Max Factory setting
- [%] - [%] - [%]
Description: Displays the output signal for the free measurement function.
Index: [0] = Signal 1
[1] = Signal 2
[2] = Signal 3
[3] = Signal 4
[4] = Signal 5
Dependency: Refer to: p4810
Note: The signals are only output in the "free measurement function" operating mode (p4810 = 6)
SINAMICS DCP
180 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
p4844[0...1] MTrace ring buffer files number / Ring buff file qty
CU_DCP Can be changed: T Access level: 3
Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
5 5 5
Description: Sets the number of ring buffer files for the measurement results of the multiple trace.
Index: [0] = Trace 0
[1] = Trace 1
Dependency: Refer to: p4840, r4841
SINAMICS DCP
List Manual (LH21), 05/2016 181
2 Parameters
2.2 List of parameters
Dependency: Refer to: r4950, r4951, r4955, p4956, r4957, r4958, r4959, r4960
Note: The GUID of an OA application comprises 16 characters plus 1 character major information plus 1 character, minor
information.
GUID: Globally Unique IDentifier
SINAMICS DCP
182 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
r4985 OA number / OA no
CU_DCP Can be changed: - Access level: 4
Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
0 16 -
Description: Displays the number of OA applications installed on the memory card/device memory.
Dependency: Refer to: r4986, r4987, r4988, r4989, r4990, r4991, r4992, r4993, r4994
Note: OA: Open Architecture (OA application)
SINAMICS DCP
List Manual (LH21), 05/2016 183
2 Parameters
2.2 List of parameters
Dependency: Refer to: r4985, r4987, r4988, r4989, r4990, r4991, r4992, r4993, r4994
Note: The identifier of an OA application comprises a maximum of 8 characters plus separator.
r4988[0...n] OA identifier / OA ID
CU_DCP Can be changed: - Access level: 4
Data type: Unsigned8 Func. diagram: -
Min Max Factory setting
- - -
Description: Displays the IDs of all the OA applications installed on the memory card/device memory.
r4988[0...8]: Identifier of OA application 1
r4988[9...17]: Identifier of OA applications 2, ...
Dependency: Refer to: r4985, r4986, r4987, r4989, r4990, r4991, r4992, r4993, r4994
Notice: If there is no OA application, then it is not possible to access an index.
SINAMICS DCP
184 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 185
2 Parameters
2.2 List of parameters
p7763 KHP OEM exception list number of indices for p7764 / KHP OEM qty p7764
CU_DCP, TM150, Can be changed: U, T Access level: 3
TM15DI_DO, TM31 Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
1 500 1
Description: Sets the number of parameters for the OEM exception list (p7764[0...n]).
p7764[0...n], with n = p7763 - 1
Dependency: Refer to: p7764
SINAMICS DCP
186 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 187
2 Parameters
2.2 List of parameters
r7843[19] = 0 dec --> ASCII characters = " " --> serial number, character 20
r7843[20] = 0 dec
Serial number = 111923E
SINAMICS DCP
188 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 189
2 Parameters
2.2 List of parameters
Re index 3:
Drive object safety messages. When changing r9744, the value in this index is incremented.
r8572[0...39] Macro Connector Inputs (CI) for speed setpoints / Macro CI n_set
DCP_CTRL Can be changed: - Access level: 1
Data type: Unsigned32 Func. diagram: -
Min Max Factory setting
- - -
Description: Displays the ACX file saved in the appropriate directory in the non-volatile memory.
Dependency: Refer to: p1000
Note: For a value = 9999999, the following applies: The read operation is still running.
SINAMICS DCP
190 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
r8573[0...39] Macro Connector Inputs (CI) for torque setpoints / Macro CI M_set
DCP_CTRL Can be changed: - Access level: 1
Data type: Unsigned32 Func. diagram: -
Min Max Factory setting
- - -
Description: Displays the ACX file saved in the appropriate directory in the non-volatile memory.
Dependency: Refer to: p1500
Note: For a value = 9999999, the following applies: The read operation is still running.
SINAMICS DCP
List Manual (LH21), 05/2016 191
2 Parameters
2.2 List of parameters
SINAMICS DCP
192 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 193
2 Parameters
2.2 List of parameters
SINAMICS DCP
194 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
Note: The system only permits certain sampling times and after writing to this parameter, displays the value that has
actually been set.
For clock cycle synchronous operation, the specified bus cycle time applies (Tdp).
r8850[0...4] CO: IF2 PZD receive word / IF2 PZD recv word
TM150, TM15DI_DO, Can be changed: - Access level: 3
TM31 Data type: Integer16 Func. diagram: 2491
Min Max Factory setting
- - -
Description: Connector output for interconnecting the PZD (setpoints) received via interface 2 in the word format.
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
Note: IF2: Interface 2
PZD1 to PZD2 are displayed bit-serially in r8890 to r8891.
p8851[0...63] CI: IF2 PZD send word / IF2 PZD send word
DCP_CTRL Can be changed: U, T Access level: 3
Data type: Unsigned32 / Integer16 Func. diagram: 2487, 9208
Min Max Factory setting
- - 0
Description: Selects the PZD (actual values) to be sent via interface 2 in the word format.
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
[12] = PZD 13
[13] = PZD 14
[14] = PZD 15
[15] = PZD 16
[16] = PZD 17
[17] = PZD 18
[18] = PZD 19
[19] = PZD 20
[20] = PZD 21
[21] = PZD 22
[22] = PZD 23
[23] = PZD 24
[24] = PZD 25
[25] = PZD 26
[26] = PZD 27
[27] = PZD 28
SINAMICS DCP
List Manual (LH21), 05/2016 195
2 Parameters
2.2 List of parameters
[28] = PZD 29
[29] = PZD 30
[30] = PZD 31
[31] = PZD 32
[32] = PZD 33
[33] = PZD 34
[34] = PZD 35
[35] = PZD 36
[36] = PZD 37
[37] = PZD 38
[38] = PZD 39
[39] = PZD 40
[40] = PZD 41
[41] = PZD 42
[42] = PZD 43
[43] = PZD 44
[44] = PZD 45
[45] = PZD 46
[46] = PZD 47
[47] = PZD 48
[48] = PZD 49
[49] = PZD 50
[50] = PZD 51
[51] = PZD 52
[52] = PZD 53
[53] = PZD 54
[54] = PZD 55
[55] = PZD 56
[56] = PZD 57
[57] = PZD 58
[58] = PZD 59
[59] = PZD 60
[60] = PZD 61
[61] = PZD 62
[62] = PZD 63
[63] = PZD 64
Dependency: Refer to: p8861
Note: IF2: Interface 2
p8851[0...4] CI: IF2 PZD send word / IF2 PZD send word
TM150, TM15DI_DO, Can be changed: U, T Access level: 3
TM31 Data type: Unsigned32 / Integer16 Func. diagram: 2493, 9210
Min Max Factory setting
- - 0
Description: Selects the PZD (actual values) to be sent via interface 2 in the word format.
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
Note: IF2: Interface 2
SINAMICS DCP
196 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 197
2 Parameters
2.2 List of parameters
SINAMICS DCP
198 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
5: Non-cyclic communication
6: Cyclic communications but no setpoints (stop/no clock cycle)
255: Cyclic communication
r8860[0...62] CO: IF2 PZD receive double word / IF2 PZD recv DW
DCP_CTRL Can be changed: - Access level: 3
Data type: Integer32 Func. diagram: 2485, 9204,
9206
Min Max Factory setting
- - -
Description: Connector output for interconnecting the PZD (setpoints) received via interface 2 in the double word format.
Index: [0] = PZD 1 + 2
[1] = PZD 2 + 3
[2] = PZD 3 + 4
[3] = PZD 4 + 5
[4] = PZD 5 + 6
[5] = PZD 6 + 7
[6] = PZD 7 + 8
SINAMICS DCP
List Manual (LH21), 05/2016 199
2 Parameters
2.2 List of parameters
[7] = PZD 8 + 9
[8] = PZD 9 + 10
[9] = PZD 10 + 11
[10] = PZD 11 + 12
[11] = PZD 12 + 13
[12] = PZD 13 + 14
[13] = PZD 14 + 15
[14] = PZD 15 + 16
[15] = PZD 16 + 17
[16] = PZD 17 + 18
[17] = PZD 18 + 19
[18] = PZD 19 + 20
[19] = PZD 20 + 21
[20] = PZD 21 + 22
[21] = PZD 22 + 23
[22] = PZD 23 + 24
[23] = PZD 24 + 25
[24] = PZD 25 + 26
[25] = PZD 26 + 27
[26] = PZD 27 + 28
[27] = PZD 28 + 29
[28] = PZD 29 + 30
[29] = PZD 30 + 31
[30] = PZD 31 + 32
[31] = PZD 32 + 33
[32] = PZD 33 + 34
[33] = PZD 34 + 35
[34] = PZD 35 + 36
[35] = PZD 36 + 37
[36] = PZD 37 + 38
[37] = PZD 38 + 39
[38] = PZD 39 + 40
[39] = PZD 40 + 41
[40] = PZD 41 + 42
[41] = PZD 42 + 43
[42] = PZD 43 + 44
[43] = PZD 44 + 45
[44] = PZD 45 + 46
[45] = PZD 46 + 47
[46] = PZD 47 + 48
[47] = PZD 48 + 49
[48] = PZD 49 + 50
[49] = PZD 50 + 51
[50] = PZD 51 + 52
[51] = PZD 52 + 53
[52] = PZD 53 + 54
[53] = PZD 54 + 55
[54] = PZD 55 + 56
[55] = PZD 56 + 57
[56] = PZD 57 + 58
[57] = PZD 58 + 59
[58] = PZD 59 + 60
[59] = PZD 60 + 61
[60] = PZD 61 + 62
[61] = PZD 62 + 63
[62] = PZD 63 + 64
Dependency: Refer to: r8850
Notice: Where there is a multiple interconnection of a connector output, all the connector inputs must either have Integer or
FloatingPoint data types.
A BICO interconnection for a single PZD can only take place either on r8850 or r8860.
A maximum of 4 indices of the "trace" function can be used.
Note: IF2: Interface 2
SINAMICS DCP
200 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
p8861[0...62] CI: IF2 PZD send double word / IF2 PZD send DW
DCP_CTRL Can be changed: U, T Access level: 3
Data type: Unsigned32 / Integer32 Func. diagram: 2487, 9208,
9210
Min Max Factory setting
- - 0
Description: Selects the PZD (actual values) to be sent via interface 2 in the double word format.
Index: [0] = PZD 1 + 2
[1] = PZD 2 + 3
[2] = PZD 3 + 4
[3] = PZD 4 + 5
[4] = PZD 5 + 6
[5] = PZD 6 + 7
[6] = PZD 7 + 8
[7] = PZD 8 + 9
[8] = PZD 9 + 10
[9] = PZD 10 + 11
[10] = PZD 11 + 12
[11] = PZD 12 + 13
[12] = PZD 13 + 14
[13] = PZD 14 + 15
[14] = PZD 15 + 16
[15] = PZD 16 + 17
[16] = PZD 17 + 18
[17] = PZD 18 + 19
[18] = PZD 19 + 20
[19] = PZD 20 + 21
[20] = PZD 21 + 22
[21] = PZD 22 + 23
[22] = PZD 23 + 24
[23] = PZD 24 + 25
[24] = PZD 25 + 26
[25] = PZD 26 + 27
[26] = PZD 27 + 28
[27] = PZD 28 + 29
[28] = PZD 29 + 30
[29] = PZD 30 + 31
[30] = PZD 31 + 32
[31] = PZD 32 + 33
[32] = PZD 33 + 34
[33] = PZD 34 + 35
[34] = PZD 35 + 36
[35] = PZD 36 + 37
[36] = PZD 37 + 38
[37] = PZD 38 + 39
[38] = PZD 39 + 40
[39] = PZD 40 + 41
[40] = PZD 41 + 42
[41] = PZD 42 + 43
[42] = PZD 43 + 44
[43] = PZD 44 + 45
[44] = PZD 45 + 46
[45] = PZD 46 + 47
[46] = PZD 47 + 48
[47] = PZD 48 + 49
[48] = PZD 49 + 50
[49] = PZD 50 + 51
[50] = PZD 51 + 52
[51] = PZD 52 + 53
[52] = PZD 53 + 54
[53] = PZD 54 + 55
[54] = PZD 55 + 56
[55] = PZD 56 + 57
SINAMICS DCP
List Manual (LH21), 05/2016 201
2 Parameters
2.2 List of parameters
[56] = PZD 57 + 58
[57] = PZD 58 + 59
[58] = PZD 59 + 60
[59] = PZD 60 + 61
[60] = PZD 61 + 62
[61] = PZD 62 + 63
[62] = PZD 63 + 64
Dependency: Refer to: p8851
Notice: A BICO interconnection for a single PZD can only take place either on p8851 or p8861.
Note: IF2: Interface 2
r8863[0...62] IF2 diagnostics PZD send double word / IF2 diag send DW
DCP_CTRL Can be changed: - Access level: 3
Data type: Unsigned32 Func. diagram: 2487
Min Max Factory setting
- - -
Description: Displays the PZD sent via interface 2 (actual values) with double word format.
Index: [0] = PZD 1 + 2
[1] = PZD 2 + 3
[2] = PZD 3 + 4
[3] = PZD 4 + 5
[4] = PZD 5 + 6
[5] = PZD 6 + 7
[6] = PZD 7 + 8
[7] = PZD 8 + 9
[8] = PZD 9 + 10
[9] = PZD 10 + 11
[10] = PZD 11 + 12
[11] = PZD 12 + 13
[12] = PZD 13 + 14
[13] = PZD 14 + 15
[14] = PZD 15 + 16
[15] = PZD 16 + 17
[16] = PZD 17 + 18
[17] = PZD 18 + 19
[18] = PZD 19 + 20
[19] = PZD 20 + 21
[20] = PZD 21 + 22
[21] = PZD 22 + 23
[22] = PZD 23 + 24
[23] = PZD 24 + 25
[24] = PZD 25 + 26
[25] = PZD 26 + 27
[26] = PZD 27 + 28
[27] = PZD 28 + 29
[28] = PZD 29 + 30
[29] = PZD 30 + 31
[30] = PZD 31 + 32
[31] = PZD 32 + 33
[32] = PZD 33 + 34
[33] = PZD 34 + 35
[34] = PZD 35 + 36
[35] = PZD 36 + 37
[36] = PZD 37 + 38
[37] = PZD 38 + 39
[38] = PZD 39 + 40
[39] = PZD 40 + 41
[40] = PZD 41 + 42
[41] = PZD 42 + 43
[42] = PZD 43 + 44
[43] = PZD 44 + 45
[44] = PZD 45 + 46
[45] = PZD 46 + 47
SINAMICS DCP
202 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
[46] = PZD 47 + 48
[47] = PZD 48 + 49
[48] = PZD 49 + 50
[49] = PZD 50 + 51
[50] = PZD 51 + 52
[51] = PZD 52 + 53
[52] = PZD 53 + 54
[53] = PZD 54 + 55
[54] = PZD 55 + 56
[55] = PZD 56 + 57
[56] = PZD 57 + 58
[57] = PZD 58 + 59
[58] = PZD 59 + 60
[59] = PZD 60 + 61
[60] = PZD 61 + 62
[61] = PZD 62 + 63
[62] = PZD 63 + 64
Bit field: Bit Signal name 1 signal 0 signal FP
00 Bit 0 ON OFF -
01 Bit 1 ON OFF -
02 Bit 2 ON OFF -
03 Bit 3 ON OFF -
04 Bit 4 ON OFF -
05 Bit 5 ON OFF -
06 Bit 6 ON OFF -
07 Bit 7 ON OFF -
08 Bit 8 ON OFF -
09 Bit 9 ON OFF -
10 Bit 10 ON OFF -
11 Bit 11 ON OFF -
12 Bit 12 ON OFF -
13 Bit 13 ON OFF -
14 Bit 14 ON OFF -
15 Bit 15 ON OFF -
16 Bit 16 ON OFF -
17 Bit 17 ON OFF -
18 Bit 18 ON OFF -
19 Bit 19 ON OFF -
20 Bit 20 ON OFF -
21 Bit 21 ON OFF -
22 Bit 22 ON OFF -
23 Bit 23 ON OFF -
24 Bit 24 ON OFF -
25 Bit 25 ON OFF -
26 Bit 26 ON OFF -
27 Bit 27 ON OFF -
28 Bit 28 ON OFF -
29 Bit 29 ON OFF -
30 Bit 30 ON OFF -
31 Bit 31 ON OFF -
Notice: A maximum of 4 indices of the "trace" function can be used.
Note: IF2: Interface 2
SINAMICS DCP
List Manual (LH21), 05/2016 203
2 Parameters
2.2 List of parameters
p8870[0...15] SINAMICS Link receive telegram word PZD / Recv link word
DCP_CTRL Can be changed: T Access level: 3
(PROFINET CBE20), Data type: Unsigned16 Func. diagram: -
TM150 (PROFINET
Min Max Factory setting
CBE20), TM15DI_DO
(PROFINET CBE20), 0 16 0
TM31 (PROFINET
CBE20)
Description: Assignment of a PZD to a telegram word from a SINAMICS Link receive telegram.
For p8839[0] = 2 (COMM BOARD via interface 1), the following applies:
- PZD p2050[index] is assigned by means of p8870[index], p8872[index].
For p8839[1] = 2 (COMM BOARD via interface 2), the following applies:
- PZD p8850[index] is assigned by means of p8870[index], p8872[index].
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
[12] = PZD 13
[13] = PZD 14
[14] = PZD 15
[15] = PZD 16
Dependency: Refer to: p8872
Note: Value range:
0: Not used
1 ... 16: Telegram word
A pair of values p8870[index], p8872[index] may only be used once in single a device.
A change only becomes effective after POWER ON, reset, project download or p8842 = 1.
p8871[0...15] SINAMICS Link send telegram word PZD / Send link word
TM150 (PROFINET Can be changed: T Access level: 3
CBE20), TM15DI_DO Data type: Unsigned16 Func. diagram: -
(PROFINET CBE20),
Min Max Factory setting
TM31 (PROFINET
CBE20) 0 16 0
Description: Assigns a PZD to a telegram word in the SINAMICS Link send telegram.
For p8839[0] = 2 (COMM BOARD via interface 1), the following applies:
- p8871[index] assigns PZD p2051[index].
For p8839[1] = 2 (COMM BOARD via interface 2), the following applies:
- p8871[index] assigns PZD p8851[index].
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
[12] = PZD 13
SINAMICS DCP
204 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
[13] = PZD 14
[14] = PZD 15
[15] = PZD 16
Dependency: Refer to: p2051, p8851
Refer to: A50002
Note: Value range:
0: Not used
1 ... 16: Send telegram word
A specific telegram word send may only be used once within a single device.
A change only becomes effective after POWER ON, reset, project download or p8842 = 1.
r8874[0...63] IF2 diagnostics bus address PZD receive / IF2 diag addr recv
DCP_CTRL Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
- - -
Description: Displays the bus address of sender from which the PZD is received.
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
[12] = PZD 13
[13] = PZD 14
SINAMICS DCP
List Manual (LH21), 05/2016 205
2 Parameters
2.2 List of parameters
[14] = PZD 15
[15] = PZD 16
[16] = PZD 17
[17] = PZD 18
[18] = PZD 19
[19] = PZD 20
[20] = PZD 21
[21] = PZD 22
[22] = PZD 23
[23] = PZD 24
[24] = PZD 25
[25] = PZD 26
[26] = PZD 27
[27] = PZD 28
[28] = PZD 29
[29] = PZD 30
[30] = PZD 31
[31] = PZD 32
[32] = PZD 33
[33] = PZD 34
[34] = PZD 35
[35] = PZD 36
[36] = PZD 37
[37] = PZD 38
[38] = PZD 39
[39] = PZD 40
[40] = PZD 41
[41] = PZD 42
[42] = PZD 43
[43] = PZD 44
[44] = PZD 45
[45] = PZD 46
[46] = PZD 47
[47] = PZD 48
[48] = PZD 49
[49] = PZD 50
[50] = PZD 51
[51] = PZD 52
[52] = PZD 53
[53] = PZD 54
[54] = PZD 55
[55] = PZD 56
[56] = PZD 57
[57] = PZD 58
[58] = PZD 59
[59] = PZD 60
[60] = PZD 61
[61] = PZD 62
[62] = PZD 63
[63] = PZD 64
Note: IF2: Interface 2
Value range:
0 - 125: Bus address of the sender
255: Not assigned
r8874[0...4] IF2 diagnostics bus address PZD receive / IF2 diag addr recv
TM150, TM15DI_DO, Can be changed: - Access level: 3
TM31 Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
- - -
Description: Displays the bus address of sender from which the PZD is received.
SINAMICS DCP
206 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
r8875[0...63] IF2 diagnostics telegram offset PZD receive / IF diag offs recv
DCP_CTRL Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
- - -
Description: Displays the byte offset of the PZD in the receive telegram.
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
[12] = PZD 13
[13] = PZD 14
[14] = PZD 15
[15] = PZD 16
[16] = PZD 17
[17] = PZD 18
[18] = PZD 19
[19] = PZD 20
[20] = PZD 21
[21] = PZD 22
[22] = PZD 23
[23] = PZD 24
[24] = PZD 25
[25] = PZD 26
[26] = PZD 27
[27] = PZD 28
[28] = PZD 29
[29] = PZD 30
[30] = PZD 31
[31] = PZD 32
[32] = PZD 33
[33] = PZD 34
[34] = PZD 35
[35] = PZD 36
[36] = PZD 37
[37] = PZD 38
[38] = PZD 39
[39] = PZD 40
[40] = PZD 41
[41] = PZD 42
[42] = PZD 43
[43] = PZD 44
[44] = PZD 45
[45] = PZD 46
[46] = PZD 47
[47] = PZD 48
[48] = PZD 49
[49] = PZD 50
[50] = PZD 51
[51] = PZD 52
SINAMICS DCP
List Manual (LH21), 05/2016 207
2 Parameters
2.2 List of parameters
[52] = PZD 53
[53] = PZD 54
[54] = PZD 55
[55] = PZD 56
[56] = PZD 57
[57] = PZD 58
[58] = PZD 59
[59] = PZD 60
[60] = PZD 61
[61] = PZD 62
[62] = PZD 63
[63] = PZD 64
Note: IF2: Interface 2
Value range:
0 - 242: Byte offset
255: Not assigned
r8875[0...4] IF2 diagnostics telegram offset PZD receive / IF diag offs recv
TM150, TM15DI_DO, Can be changed: - Access level: 3
TM31 Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
- - -
Description: Displays the byte offset of the PZD in the receive telegram.
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
r8876[0...63] IF2 diagnostics telegram offset PZD send / IF2 diag offs send
DCP_CTRL Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
- - -
Description: Displays the byte offset of the PZD in the send telegram.
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
[12] = PZD 13
[13] = PZD 14
[14] = PZD 15
[15] = PZD 16
[16] = PZD 17
[17] = PZD 18
[18] = PZD 19
[19] = PZD 20
[20] = PZD 21
[21] = PZD 22
[22] = PZD 23
[23] = PZD 24
[24] = PZD 25
[25] = PZD 26
SINAMICS DCP
208 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
[26] = PZD 27
[27] = PZD 28
[28] = PZD 29
[29] = PZD 30
[30] = PZD 31
[31] = PZD 32
[32] = PZD 33
[33] = PZD 34
[34] = PZD 35
[35] = PZD 36
[36] = PZD 37
[37] = PZD 38
[38] = PZD 39
[39] = PZD 40
[40] = PZD 41
[41] = PZD 42
[42] = PZD 43
[43] = PZD 44
[44] = PZD 45
[45] = PZD 46
[46] = PZD 47
[47] = PZD 48
[48] = PZD 49
[49] = PZD 50
[50] = PZD 51
[51] = PZD 52
[52] = PZD 53
[53] = PZD 54
[54] = PZD 55
[55] = PZD 56
[56] = PZD 57
[57] = PZD 58
[58] = PZD 59
[59] = PZD 60
[60] = PZD 61
[61] = PZD 62
[62] = PZD 63
[63] = PZD 64
Note: IF2: Interface 2
Value range:
0 - 242: Byte offset
255: Not assigned
r8876[0...4] IF2 diagnostics telegram offset PZD send / IF2 diag offs send
TM150, TM15DI_DO, Can be changed: - Access level: 3
TM31 Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
- - -
Description: Displays the byte offset of the PZD in the send telegram.
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
SINAMICS DCP
List Manual (LH21), 05/2016 209
2 Parameters
2.2 List of parameters
SINAMICS DCP
210 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
[10] = Bit 10
[11] = Bit 11
[12] = Bit 12
[13] = Bit 13
[14] = Bit 14
[15] = Bit 15
Dependency: Refer to: p8888, r8889
SINAMICS DCP
List Manual (LH21), 05/2016 211
2 Parameters
2.2 List of parameters
p8888[0...4] IF2 invert binector-connector converter status word / Bin/con ZSW inv
DCP_CTRL Can be changed: U, T Access level: 3
Data type: Unsigned16 Func. diagram: 2489
Min Max Factory setting
- - 0000 0000 0000 0000 bin
Description: Setting to invert the individual binector inputs of the binector connector converter.
Index: [0] = Status word 1
[1] = Status word 2
[2] = Free status word 3
[3] = Free status word 4
[4] = Free status word 5
Bit field: Bit Signal name 1 signal 0 signal FP
00 Bit 0 Inverted Not inverted -
01 Bit 1 Inverted Not inverted -
02 Bit 2 Inverted Not inverted -
03 Bit 3 Inverted Not inverted -
04 Bit 4 Inverted Not inverted -
05 Bit 5 Inverted Not inverted -
06 Bit 6 Inverted Not inverted -
07 Bit 7 Inverted Not inverted -
08 Bit 8 Inverted Not inverted -
09 Bit 9 Inverted Not inverted -
10 Bit 10 Inverted Not inverted -
11 Bit 11 Inverted Not inverted -
12 Bit 12 Inverted Not inverted -
13 Bit 13 Inverted Not inverted -
14 Bit 14 Inverted Not inverted -
15 Bit 15 Inverted Not inverted -
Dependency: Refer to: p8880, p8881, p8882, p8883, p8884, r8889
r8889[0...4] CO: IF2 send binector-connector converter status word / Bin/con ZSW send
DCP_CTRL Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
- - -
Description: Connector output to interconnect the status words to a PZD send word.
Index: [0] = Status word 1
[1] = Status word 2
[2] = Free status word 3
[3] = Free status word 4
[4] = Free status word 5
Bit field: Bit Signal name 1 signal 0 signal FP
00 Bit 0 ON OFF -
01 Bit 1 ON OFF -
02 Bit 2 ON OFF -
03 Bit 3 ON OFF -
04 Bit 4 ON OFF -
05 Bit 5 ON OFF -
06 Bit 6 ON OFF -
07 Bit 7 ON OFF -
08 Bit 8 ON OFF -
09 Bit 9 ON OFF -
10 Bit 10 ON OFF -
11 Bit 11 ON OFF -
12 Bit 12 ON OFF -
13 Bit 13 ON OFF -
14 Bit 14 ON OFF -
15 Bit 15 ON OFF -
Dependency: Refer to: p8851, p8880, p8881, p8882, p8883, p8884, p8888
SINAMICS DCP
212 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
Note: r8889 together with p8880 to p8884 forms five binector-connector converters.
r8890.0...15 BO: IF2 PZD1 receive bit-serial / IF2 PZD1 recv bitw
DCP_CTRL, TM150, Can be changed: - Access level: 3
TM15DI_DO, TM31 Data type: Unsigned16 Func. diagram: 2485, 2491,
9204, 9206
Min Max Factory setting
- - -
Description: Binector output for bit-serial interconnection of PZD1 (normally control word 1) received via interface 2.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Bit 0 ON OFF -
01 Bit 1 ON OFF -
02 Bit 2 ON OFF -
03 Bit 3 ON OFF -
04 Bit 4 ON OFF -
05 Bit 5 ON OFF -
06 Bit 6 ON OFF -
07 Bit 7 ON OFF -
08 Bit 8 ON OFF -
09 Bit 9 ON OFF -
10 Bit 10 ON OFF -
11 Bit 11 ON OFF -
12 Bit 12 ON OFF -
13 Bit 13 ON OFF -
14 Bit 14 ON OFF -
15 Bit 15 ON OFF -
Dependency: Refer to: r8850
Note: IF2: Interface 2
r8891.0...15 BO: IF2 PZD2 receive bit-serial / IF2 PZD2 recv bitw
DCP_CTRL, TM150, Can be changed: - Access level: 3
TM15DI_DO, TM31 Data type: Unsigned16 Func. diagram: 2485, 2491,
9204, 9206
Min Max Factory setting
- - -
Description: Binector output for bit-serial interconnection of PZD2 received via interface 2.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Bit 0 ON OFF -
01 Bit 1 ON OFF -
02 Bit 2 ON OFF -
03 Bit 3 ON OFF -
04 Bit 4 ON OFF -
05 Bit 5 ON OFF -
06 Bit 6 ON OFF -
07 Bit 7 ON OFF -
08 Bit 8 ON OFF -
09 Bit 9 ON OFF -
10 Bit 10 ON OFF -
11 Bit 11 ON OFF -
12 Bit 12 ON OFF -
13 Bit 13 ON OFF -
14 Bit 14 ON OFF -
15 Bit 15 ON OFF -
Dependency: Refer to: r8850
Note: IF2: Interface 2
SINAMICS DCP
List Manual (LH21), 05/2016 213
2 Parameters
2.2 List of parameters
r8892.0...15 BO: IF2 PZD3 receive bit-serial / IF2 PZD3 recv bitw
DCP_CTRL Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: 2485, 9204,
9206
Min Max Factory setting
- - -
Description: Binector output for bit-serial interconnection of PZD3 received via interface 2.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Bit 0 ON OFF -
01 Bit 1 ON OFF -
02 Bit 2 ON OFF -
03 Bit 3 ON OFF -
04 Bit 4 ON OFF -
05 Bit 5 ON OFF -
06 Bit 6 ON OFF -
07 Bit 7 ON OFF -
08 Bit 8 ON OFF -
09 Bit 9 ON OFF -
10 Bit 10 ON OFF -
11 Bit 11 ON OFF -
12 Bit 12 ON OFF -
13 Bit 13 ON OFF -
14 Bit 14 ON OFF -
15 Bit 15 ON OFF -
Dependency: Refer to: r8850
Note: IF2: Interface 2
r8893.0...15 BO: IF2 PZD4 receive bit-serial / IF2 PZD4 recv bitw
DCP_CTRL Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: 2485, 9204,
9206
Min Max Factory setting
- - -
Description: Binector output for bit-serial interconnection of PZD4 (normally control word 2) received via interface 2.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Bit 0 ON OFF -
01 Bit 1 ON OFF -
02 Bit 2 ON OFF -
03 Bit 3 ON OFF -
04 Bit 4 ON OFF -
05 Bit 5 ON OFF -
06 Bit 6 ON OFF -
07 Bit 7 ON OFF -
08 Bit 8 ON OFF -
09 Bit 9 ON OFF -
10 Bit 10 ON OFF -
11 Bit 11 ON OFF -
12 Bit 12 ON OFF -
13 Bit 13 ON OFF -
14 Bit 14 ON OFF -
15 Bit 15 ON OFF -
Dependency: Refer to: r8850
Note: IF2: Interface 2
SINAMICS DCP
214 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 215
2 Parameters
2.2 List of parameters
p8898[0...1] IF2 invert connector-binector converter binector output / Con/bin outp inv
DCP_CTRL Can be changed: U, T Access level: 3
Data type: Unsigned16 Func. diagram: 2485, 2491
Min Max Factory setting
- - 0000 0000 0000 0000 bin
Description: Setting to invert the individual binector outputs of the connector-binector converter.
Using p8898[0], the signals of CI: p8899[0] are influenced.
Using p8898[1], the signals of CI: p8899[1] are influenced.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Bit 0 Inverted Not inverted -
01 Bit 1 Inverted Not inverted -
02 Bit 2 Inverted Not inverted -
03 Bit 3 Inverted Not inverted -
04 Bit 4 Inverted Not inverted -
05 Bit 5 Inverted Not inverted -
06 Bit 6 Inverted Not inverted -
07 Bit 7 Inverted Not inverted -
08 Bit 8 Inverted Not inverted -
09 Bit 9 Inverted Not inverted -
10 Bit 10 Inverted Not inverted -
11 Bit 11 Inverted Not inverted -
12 Bit 12 Inverted Not inverted -
13 Bit 13 Inverted Not inverted -
14 Bit 14 Inverted Not inverted -
15 Bit 15 Inverted Not inverted -
Dependency: Refer to: r8894, r8895, p8899
SINAMICS DCP
216 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 217
2 Parameters
2.2 List of parameters
Notice: When the DHCP mode is active (p8944 > 0), then PROFINET communication via this interface is no longer possible!
However, the interface can be used by the STARTER/SCOUT commissioning tool.
Note: The active DHCP mode is displayed in parameter r8954.
The interface configuration (p8940 and following) is activated with p8945.
The parameter is not influenced by setting the factory setting.
If value = 0:
DHCP deactivated.
If value = 1:
Reserved.
If value = 2:
DHCP activated. The MAC address of this interface is used for client identification.
If value = 3:
DHCP activated. The station name of this interface is used for client identification.
SINAMICS DCP
218 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
r8953[0...3] CBE2x Subnet Mask of Station active / CBE2x Sub Mask act
CU_DCP (PROFINET Can be changed: - Access level: 3
CBE20) Data type: Unsigned8 Func. diagram: -
Min Max Factory setting
0 255 -
Description: Displays the active subnet mask for the Communication Board Ethernet 20/25 (CBE20/CBE25).
SINAMICS DCP
List Manual (LH21), 05/2016 219
2 Parameters
2.2 List of parameters
SINAMICS DCP
220 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
Re index 2:
7: Name (r9208)
8: Component type (r9207)
9: Number of DRIVE-CLiQ connections (r9207)
11: Manufacturer (upper byte) and version (lower byte) (r9207)
12: Serial number (r9208)
13: Index (r9207)
15: Comparison level (r9207)
23: Order number (r9207)
24: Hardware serial number (r9208)
25: Collective order number (r9207)
28: Firmware version (r9207)
29: EEPROM version (r9207)
30: Hardware version (r9207)
1000: Name of DRIVE-CLiQ connection 0 (r9208)
1001: Name of DRIVE-CLiQ connection 1 (r9208)
...
1015: Name of DRIVE-CLiQ connection 15 (r9208)
Index: [0] = Actual topology/target topology
[1] = Component number
[2] = Identifier/property
Dependency: Refer to: r9207, r9208
SINAMICS DCP
List Manual (LH21), 05/2016 221
2 Parameters
2.2 List of parameters
Index 0: Parameter Id
Index 1: Number of messages sent.
Index 2: Minimum time of all acyclic requests referred to the parameter Id (index 0).
Index 3: Maximum time of all acyclic requests referred to the parameter Id (index 0).
Index 4: Average of all acyclic requests referred to the parameter Id (index 0).
SINAMICS DCP
222 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
rdp 1 9222 5 5
or
rdpa 1 9222 5 5.
SINAMICS DCP
List Manual (LH21), 05/2016 223
2 Parameters
2.2 List of parameters
SINAMICS DCP
224 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
Note: All indices from r9406 to r9408 designate the same parameter.
r9406[x] parameter number, parameter not accepted
r9407[x] parameter index, parameter not accepted
r9408[x] fault code, parameter not accepted
SINAMICS DCP
List Manual (LH21), 05/2016 225
2 Parameters
2.2 List of parameters
r9485 BICO interconnections signal source search count / BICO S_src srchQty
All objects Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
- - -
Description: Displays the number of BICO interconnections to the signal sink being searched for.
Dependency: Refer to: r9481, r9482, r9483, p9484, r9486
Note: The signal source to be searched is set in p9484 (BICO-coded).
The search result is contained in r9482 and r9483 and is specified by the count (r9485) and the first index (r9486).
r9486 BICO interconnections signal source search first index / BICO S_src srchIdx
All objects Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
- - -
Description: Displays the first index of the signal source being searched for.
Dependency: Refer to: r9481, r9482, r9483, p9484, r9485
Note: The signal source to be searched is set in p9484 (BICO-coded).
The search result is contained in r9482 and r9483 and is specified by the count (r9485) and the first index (r9486).
SINAMICS DCP
226 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
p9495 BICO behavior for de-activated drive objects / Behav for deact DO
All objects Can be changed: T Access level: 3
Data type: Integer16 Func. diagram: -
Min Max Factory setting
0 2 0
Description: Sets the behavior for BICO interconnections to drive objects that are either not capable of operation or have been
deactivated.
BO/CO parameters are on the drive object that is either not capable of operation or has been deactivated (signal
source).
Value: 0: Inactive
1: Save interconnections
2: Save interconnections and establish the factory setting
Dependency: Refer to: p9496, p9497, p9498, p9499
Refer to: A01318, A01507
Note: For p9495 = 0, the following applies:
- the number of interconnections is zero (p9497 = 0).
For p9495 not equal to 0, the following applies:
- the BI/CI parameters involved are listed in p9498[0...29] (signal sink).
- the associated BO/CO parameters are listed in p9499[0...29] (signal source).
SINAMICS DCP
List Manual (LH21), 05/2016 227
2 Parameters
2.2 List of parameters
p9496 BICO behavior when activating drive objects / Behav when act DO
All objects Can be changed: T Access level: 3
Data type: Integer16 Func. diagram: -
Min Max Factory setting
0 2 0
Description: Sets the behavior when activating BICO interconnections to drive objects that are either not capable of operation or
have been deactivated.
Value: 0: Inactive
1: Restore the interconnections from the list
2: Delete the interconnections from the list
Dependency: Refer to: p9495, p9497, p9498, p9499
Refer to: A01318, A01507
Note: The BI/CI parameters involved are listed in p9498[0...29] (signal sink).
The associated BO/CO parameters are listed in p9499[0...29] (signal source).
After p9496 = 1, 2 the following applies:
- p9497 = 0
- p9496 = 0
p9497 BICO interconnections to de-activated drive objects number / Interconn obj qty
All objects Can be changed: T Access level: 3
Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
0 65535 0
Description: Displays the number of saved BICO interconnections to drive objects that are either not capable of operation or have
been deactivated.
BO/CO parameters are on the drive object that is either not capable of operation or has been deactivated (signal
source).
Dependency: Refer to: p9495, p9496, p9498, p9499
Refer to: A01318, A01507
p9498[0...29] BICO BI/CI parameters to de-activated drive objects / BI/CI to deact obj
All objects Can be changed: T Access level: 3
Data type: Unsigned32 Func. diagram: -
Min Max Factory setting
- - 0
Description: Displays the saved BI/CI parameters (signal sink), whose source is located on drive objects that are either not
capable of operation or have been deactivated.
Dependency: Refer to: p9495, p9496, p9497, p9499
Refer to: A01318, A01507
Note: A BICO interconnection (signal sink, signal source) is displayed in the same index of p9498 and p9499.
p9499[0...29] BICO BO/CO parameters to de-activated drive objects / BO/CO to deact obj
All objects Can be changed: T Access level: 3
Data type: Unsigned32 Func. diagram: -
Min Max Factory setting
- - 0
Description: Displays the saved BO/CO parameters (signal source), which are located on drive objects that are either not capable
of operation or have been deactivated.
Dependency: Refer to: p9495, p9496, p9497, p9498
Refer to: A01318, A01507
Note: A BICO interconnection (signal sink, signal source) is displayed in the same index of p9498 and p9499.
SINAMICS DCP
228 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 229
2 Parameters
2.2 List of parameters
SINAMICS DCP
230 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 231
2 Parameters
2.2 List of parameters
SINAMICS DCP
232 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 233
2 Parameters
2.2 List of parameters
SINAMICS DCP
234 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 235
2 Parameters
2.2 List of parameters
Note: The corresponding sampling times can be read out in parameter r7901.
Net utilization:
Computing time load that is only called by the sampling time involved.
Total utilization:
Computing time load of sampling time involved including load from higher-priority sampling times (interrupts).
SINAMICS DCP
236 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
p9990 DO memory usage actual value determination selection / Mem_use ActVal sel
CU_DCP Can be changed: U, T Access level: 4
Data type: Unsigned16 Func. diagram: -
Min Max Factory setting
0 65535 0
Description: The meaning of the parameter differs for reading and writing.
Read:
- Returns the number of memory areas monitored.
Write:
- Memory usage of a drive object: Enter drive object number
- Memory usage of the complete system: Enter value 65535
r9992[0...4] Memory usage drive object reference value / Mem_use DO ref val
CU_DCP Can be changed: - Access level: 4
Data type: Unsigned32 Func. diagram: -
Min Max Factory setting
- - -
Description: Displays the memory usage for each drive object as reference value.
SINAMICS DCP
List Manual (LH21), 05/2016 237
2 Parameters
2.2 List of parameters
SINAMICS DCP
238 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 239
2 Parameters
2.2 List of parameters
SINAMICS DCP
240 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 241
2 Parameters
2.2 List of parameters
SINAMICS DCP
242 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 243
2 Parameters
2.2 List of parameters
Dependency: The parameter is only valid for the following temperature sensors with a continuous characteristic:
- KTY84 (p50490 = 1)
- PT100 (p50490 = 6).
- NTC thermistor K227 (p50490 = 7)
- PT1000 (p50490 = 8)
SINAMICS DCP
244 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
p50706 BI: CUD analog input 0 signal source for enable / CUD AI 0 ena s_src
DCP_CTRL Can be changed: T Access level: 3
Data type: Unsigned32 / Binary Func. diagram: 2075
Min Max Factory setting
- - 1
Description: Sets the signal source to enable analog input 0 (AI 0, X177.25/26) on the CUD.
Note: AI: Analog Input
SINAMICS DCP
List Manual (LH21), 05/2016 245
2 Parameters
2.2 List of parameters
SINAMICS DCP
246 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
p50716 BI: CUD analog input 1 signal source for enable / CUD AI 1 ena s_src
DCP_CTRL Can be changed: T Access level: 3
Data type: Unsigned32 / Binary Func. diagram: 2080
Min Max Factory setting
- - 1
Description: Sets the signal source to enable analog input 1 (AI 1, X177.27/28) on the CUD.
Note: AI: Analog Input
SINAMICS DCP
List Manual (LH21), 05/2016 247
2 Parameters
2.2 List of parameters
p50726 BI: CUD analog input 2 signal source for enable / CUD AI 2 ena s_src
DCP_CTRL Can be changed: T Access level: 3
Data type: Unsigned32 / Binary Func. diagram: 2080
Min Max Factory setting
- - 1
Description: Sets the signal source to enable analog input 2 (AI 2, X177.29/30) on the CUD.
Note: AI: Analog Input
SINAMICS DCP
248 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
p50736[0...3] BI: Signal source to enable fast analog inputs / Fast AI ena sig s
DCP_CTRL Can be changed: T Access level: 3
Data type: Unsigned32 / Binary Func. diagram: 2085, 2090
Min Max Factory setting
- - 1
Description: Sets the signal source for enabling fast analog inputs "Select input 3 ... 6".
Index: [0] = Select input 3 (X177.1/2)
[1] = Select input 4 (X177.3/4)
[2] = Select input 5 (X177.5/6)
[3] = Select input 6 (X177.7/8)
Note: AI: Analog Input
SINAMICS DCP
List Manual (LH21), 05/2016 249
2 Parameters
2.2 List of parameters
p50743 Analog input main actual value signal processing / AI m act sig
DCP_CTRL Can be changed: T Access level: 4
Data type: Integer16 Func. diagram: 2075
Min Max Factory setting
0 3 0
Description: Sets the mode for signal processing for the "main actual value" analog input (XT1.103/104).
Value: 0: Signal not influenced
1: Signal absolute value generation
2: Signal inverted
3: Signal absolute value generation inverted
Notice: This analog input cannot be externally accessed. It is reserved for subsequent use.
Note: AI: Analog Input
p50744 BI: Analog input main actual value inversion / AI m act inv
DCP_CTRL Can be changed: T Access level: 4
Data type: Unsigned32 / Binary Func. diagram: 2075
Min Max Factory setting
- - 0
Description: Sets the signal source for inverting the signal from the "main actual value" analog input (XT1.103/104).
0 signal: no inversion
1 signal: inversion
Notice: This analog input cannot be externally accessed. It is reserved for subsequent use.
Note: AI: Analog Input
p50745 Analog input main actual value smoothing time constant / AI m act T
DCP_CTRL Can be changed: U, T Access level: 4
Data type: FloatingPoint32 Func. diagram: 2075
Min Max Factory setting
0 [ms] 10000 [ms] 0 [ms]
Description: Sets the time constant for smoothing the signal from the "main actual value" analog input (XT1.103/104).
Notice: This analog input cannot be externally accessed. It is reserved for subsequent use.
Note: AI: Analog Input
p50746 BI: Signal source to enable analog input main actual value / AI m act ena s_src
DCP_CTRL Can be changed: T Access level: 4
Data type: Unsigned32 / Binary Func. diagram: 2075
Min Max Factory setting
- - 1
Description: Sets the signal source for enabling the analog input for the "main actual value (XT1.103/104).
Notice: This analog input cannot be externally accessed. It is reserved for subsequent use.
Note: AI: Analog Input
SINAMICS DCP
250 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 251
2 Parameters
2.2 List of parameters
SINAMICS DCP
252 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 253
2 Parameters
2.2 List of parameters
SINAMICS DCP
254 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
p50781 BI: CUD digital input/output 4 signal source / CUD DI/DO 4 s_src
DCP_CTRL Can be changed: U, T Access level: 3
Data type: Unsigned32 / Binary Func. diagram: 2060
Min Max Factory setting
- - 0
Description: Sets the signal source for digital input/output 4 (DI/DO 4, X177.15) on the CUD.
Dependency: The terminal must be set as an output (p50789[0] = 1).
Refer to: p50789
Note: DI/DO: bidirectional digital input/digital output
p50782 BI: CUD digital input/output 5 signal source / CUD DI/DO 5 s_src
DCP_CTRL Can be changed: U, T Access level: 3
Data type: Unsigned32 / Binary Func. diagram: 2060
Min Max Factory setting
- - 0
Description: Sets the signal source for digital input/output 5 (DI/DO 5, X177.16) on the CUD.
Dependency: The terminal must be set as an output (p50789[1] = 1).
Refer to: p50789
Note: DI/DO: bidirectional digital input/digital output
p50783 BI: CUD digital input/output 6 signal source / CUD DI/DO 6 s_src
DCP_CTRL Can be changed: U, T Access level: 3
Data type: Unsigned32 / Binary Func. diagram: 2065
Min Max Factory setting
- - 0
Description: Sets the signal source for digital input/output 6 (DI/DO 6, X177.17) on the CUD.
Dependency: The terminal must be set as an output (p50789[2] = 1).
Refer to: p50789
Note: DI/DO: bidirectional digital input/digital output
p50784 BI: CUD digital input/output 7 signal source / CUD DI/DO 7 s_src
DCP_CTRL Can be changed: U, T Access level: 3
Data type: Unsigned32 / Binary Func. diagram: 2065
Min Max Factory setting
- - 0
Description: Sets the signal source for digital input/output 7 (DI/DO 7, X177.18) on the CUD.
SINAMICS DCP
List Manual (LH21), 05/2016 255
2 Parameters
2.2 List of parameters
SINAMICS DCP
256 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 257
2 Parameters
2.2 List of parameters
SINAMICS DCP
258 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 259
2 Parameters
2.2 List of parameters
p50832 Diagnostics memory copy recorded file to memory card / Diag_mem copy file
DCP_CTRL Can be changed: U, T Access level: 2
Data type: Integer16 Func. diagram: 8056
Min Max Factory setting
0 2 0
Description: Setting for starting the procedure to copy the diagnostics file to the memory card.
Value: 0: Inactive
1: Start copying
2: Copy file to User\Data folder
SINAMICS DCP
260 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
p51807 Parallel interface telegram monitoring failure time / Telegr mon t_fail
DCP_CTRL Can be changed: U, T Access level: 2
Data type: FloatingPoint32 Func. diagram: 9350
Min Max Factory setting
0.000 [s] 100.000 [s] 0.100 [s]
Description: Sets the permissible telegram failure time for the parallel interface.
This setting means that every device connected to the parallel interface can monitor whether it is connected to the
parallel interface.
If a telegram is not received from other devices connected to the parallel interface for longer than the set time, then
BICO output r53310.0 is set = 1 - and for the factory setting, fault F60014 is also output.
Value = 0.0:
Telegram monitoring is deactivated.
Value = 0.001 ... 100.000:
Telegram monitoring is activated.
Note: Telegram monitoring is active in the following cases:
- from the first telegram received error-free after switching on the electronics power supply. The telegram can be
received from any device.
- from the first telegram received error-free after the telegram monitoring responds (as the failure time has expired).
SINAMICS DCP
List Manual (LH21), 05/2016 261
2 Parameters
2.2 List of parameters
p51808 BI: Parallel interface signal source for F60014 / P_IF F60014 s_src
DCP_CTRL Can be changed: T Access level: 2
Data type: Unsigned32 / Binary Func. diagram: 9350
Min Max Factory setting
- - 53310.0
Description: Sets the signal source to initiate fault F60014 - "Telegram monitoring time expired".
The fault is triggered for a 1 signal.
SINAMICS DCP
262 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 263
2 Parameters
2.2 List of parameters
r52010 CO: CUD analog input main setpoint raw value / CUD AI m set raw
DCP_CTRL Can be changed: - Access level: 3
Data type: FloatingPoint32 Func. diagram: 2075
Min Max Factory setting
- [%] - [%] - [%]
Description: Display and connector output for the raw value at the "Main setpoint" analog input (X177.25/26).
Note: AI: Analog Input
r52012 CO: CUD analog input main actual value raw value / CUD AI m act raw
DCP_CTRL Can be changed: - Access level: 4
Data type: FloatingPoint32 Func. diagram: 2075
Min Max Factory setting
- [%] - [%] - [%]
Description: Display and connector output for the raw value at the "Main actual value" analog input (XT1.103/104).
Note: AI: Analog Input
SINAMICS DCP
264 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
r52013 CO: CUD analog input main actual value / CUD AI m act
DCP_CTRL Can be changed: - Access level: 4
Data type: FloatingPoint32 Func. diagram: 2075
Min Max Factory setting
- [%] - [%] - [%]
Description: Display and connector output for the "Main actual value" analog input (XT1.103/104).
Notice: This analog input cannot be externally accessed. It is reserved for subsequent use.
Note: AI: Analog Input
r52014 CO: CUD analog input select input 1 raw value / CUD AI sel 1 raw
DCP_CTRL Can be changed: - Access level: 3
Data type: FloatingPoint32 Func. diagram: 2080
Min Max Factory setting
- [%] - [%] - [%]
Description: Display and connector output for the raw value at the analog "Select input 1" (X177.27/28).
Note: AI: Analog Input
r52016 CO: CUD analog input select input 2 raw value / CUD AI sel 2 raw
DCP_CTRL Can be changed: - Access level: 3
Data type: FloatingPoint32 Func. diagram: 2080
Min Max Factory setting
- [%] - [%] - [%]
Description: Display and connector output for the raw value at the analog "Select input 2" (X177.29/30).
Note: AI: Analog Input
SINAMICS DCP
List Manual (LH21), 05/2016 265
2 Parameters
2.2 List of parameters
SINAMICS DCP
266 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
r52026 CO: CUD analog output 0 value after smoothing / CUD AO 0 val af sm
DCP_CTRL Can be changed: - Access level: 3
Data type: FloatingPoint32 Func. diagram: 2095
Min Max Factory setting
- [%] - [%] - [%]
Description: Display and connector output for analog output 0 (X177.49/50) of the CUD.
Dependency: Refer to: p50750
Note: AO: Analog Output
r52027 CO: CUD analog output 1 value after smoothing / CUD AO 1 val af sm
DCP_CTRL Can be changed: - Access level: 3
Data type: FloatingPoint32 Func. diagram: 2095
Min Max Factory setting
- [%] - [%] - [%]
Description: Display and connector output for analog output 1 (X177.51/52) of the CUD.
Dependency: Refer to: p50755
Note: AO: Analog Output
SINAMICS DCP
List Manual (LH21), 05/2016 267
2 Parameters
2.2 List of parameters
SINAMICS DCP
268 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 269
2 Parameters
2.2 List of parameters
r53030.0...1 CO/BO: CUD analog inputs wire break signal / CUD AI wire brk
DCP_CTRL Can be changed: - Access level: 3
Data type: Unsigned16 Func. diagram: 2075, 2080
Min Max Factory setting
- - -
Description: Display and connector output for the "Wire break" signal in the case of the CUD analog inputs.
Bit field: Bit Signal name 1 signal 0 signal FP
00 AI "Main setpoint" wire break monitoring Yes No 2075
responded
01 AI 1 (X177.27/28) wire break monitoring Yes No 2080
responded
Dependency: Refer to: F60046, F60047
Note: AI: Analog Input
r53310.0...3 CO/BO: Parallel interface telegram monitoring state / Par_IF mon state
DCP_CTRL Can be changed: - Access level: 2
Data type: Unsigned16 Func. diagram: 9350
Min Max Factory setting
- - -
Description: Display and BICO output for the state of the telegram monitoring for the parallel interface.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Telegram monitoring timeout - continuous Yes No 9350
signal
01 Telegram monitoring timeout - pulse Yes No 9350
02 OFF1 from master 1 0 9350
03 Pulse enable from the master 1 0 9350
SINAMICS DCP
270 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
p54000 CI: MPP tracker current setpoint manual signal source / MPPT I_s man s_src
DCP_CTRL Can be changed: T Access level: 2
Data type: Unsigned32 / FloatingPoint32 Func. diagram: 6700
Min Max Factory setting
- - 2050[1]
Description: Sets the signal source for the current setpoint for manual operation.
Manual operation is selected via binector input p54001 = 0 signal.
Dependency: Refer to: p54001
Note: MPP: maximum power point (point along the characteristic with the maximum power)
p54001 BI: MPP tracker manual/automatic signal source / MPPT man/aut s_src
DCP_CTRL Can be changed: T Access level: 2
Data type: Unsigned32 / Binary Func. diagram: 6700
Min Max Factory setting
- - 1
Description: Sets the signal source for switching over between manual and automatic operation.
BI: p54001 = 1 signal:
Automatic operation is selected.
BI: p54001 = 0 signal:
Manual operation is selected.
Dependency: Refer to: p54000
Note: MPP: maximum power point (point along the characteristic with the maximum power)
p54002 CI: MPP tracker current limit signal source / MPPT I_limit s_src
DCP_CTRL Can be changed: T Access level: 2
Data type: Unsigned32 / FloatingPoint32 Func. diagram: 6700
Min Max Factory setting
- - 1
Description: Sets the signal source for the current limit of the MPP tracker.
Note: MPP: maximum power point (point along the characteristic with the maximum power)
p54003 CI: MPP tracker current start value signal source / MPPT I stVal s_src
DCP_CTRL Can be changed: T Access level: 2
Data type: Unsigned32 / FloatingPoint32 Func. diagram: 6700
Min Max Factory setting
- - 55112[0]
Description: Sets the signal source for the start value of the MPP tracker current.
Note: MPP: maximum power point (point along the characteristic with the maximum power)
SINAMICS DCP
List Manual (LH21), 05/2016 271
2 Parameters
2.2 List of parameters
p54010 CI: MPP tracker actual power signal source / MPPT act P s_src
DCP_CTRL Can be changed: T Access level: 2
Data type: Unsigned32 / FloatingPoint32 Func. diagram: 6700
Min Max Factory setting
- - 55540[0]
Description: Sets the signal source for the actual power of the MPP tracker.
Dependency: Refer to: p54011, r54015
Note: MPP: maximum power point (point along the characteristic with the maximum power)
p54011 MPP tracker actual power smoothing time constant / MPPT act P T
DCP_CTRL Can be changed: U, T Access level: 3
Data type: FloatingPoint32 Func. diagram: 6700
Min Max Factory setting
0.00 [s] 100.00 [s] 0.05 [s]
Description: Sets the time constant for smoothing the actual power value.
Dependency: Refer to: p54010, r54015
Note: MPP: maximum power point (point along the characteristic with the maximum power)
SINAMICS DCP
272 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
p54013 BI: MPP tracker lower voltage threshold reached signal source / MPPT U_min rch s_s
DCP_CTRL Can be changed: T Access level: 2
Data type: Unsigned32 / Binary Func. diagram: 6700
Min Max Factory setting
- - 55125.11
Description: Sets the signal source for the "undervoltage limited reached" signal of the MPP tracker.
Note: MPP: maximum power point (point along the characteristic with the maximum power)
p54014[0...3] BI: MPP tracker enable signal source / MPPT enable s_src
DCP_CTRL Can be changed: T Access level: 2
Data type: Unsigned32 / Binary Func. diagram: 6700
Min Max Factory setting
- - [0] 899.11
[1] 1
[2] 55125.7
[3] 0
Description: Sets the signal source for the "enable" signal of the MPP tracker.
BI: p54014[0, 1] = 1 signal:
- the MPP tracker is enabled.
BI: p54014[0, 1] = 0 signal:
- the MPP tracker is inhibited.
BI: p54014[2, 3] = 1 signal:
- the MPP tracker is inhibited.
BI: p54014[2, 3] = 0 signal:
- the MPP tracker is enabled.
Note: MPP: maximum power point (point along the characteristic with the maximum power)
r54015 CO: MPP tracker actual power smoothed / MPPT act P smooth
DCP_CTRL Can be changed: - Access level: 2
Data type: FloatingPoint32 Func. diagram: 6700
Min Max Factory setting
- [%] - [%] - [%]
Description: Display and connector output for the smoothed actual power.
Dependency: Refer to: p54010, p54011
Note: MPP: maximum power point (point along the characteristic with the maximum power)
SINAMICS DCP
List Manual (LH21), 05/2016 273
2 Parameters
2.2 List of parameters
SINAMICS DCP
274 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
p54100 CI: Voltage controller setpoint signal source / U_ctrl setp s_src
DCP_CTRL Can be changed: T Access level: 2
Data type: Unsigned32 / FloatingPoint32 Func. diagram: 6818
Min Max Factory setting
- - 1
Description: Sets the signal source for the voltage controller setpoint.
p54102 Voltage controller actual value selection / U_ctrl act val sel
DCP_CTRL Can be changed: T Access level: 2
Data type: Integer16 Func. diagram: 6818
Min Max Factory setting
1 4 3
Description: Selects the signal source for the voltage actual value.
Value: 1: Actual value voltage side 1
2: Actual value voltage side 2
3: Actual value voltage inner side 1
4: Actual value voltage inner side 2
SINAMICS DCP
List Manual (LH21), 05/2016 275
2 Parameters
2.2 List of parameters
r54103 CO: Voltage controller setpoint after the ramp-function generator / U_ctr U_set af RFG
DCP_CTRL Can be changed: - Access level: 2
Data type: FloatingPoint32 Func. diagram: 6818
Min Max Factory setting
- [%] - [%] - [%]
Description: Display and connector output for the voltage setpoint after the ramp-function generator.
p54105 BI: Voltage controller activation signal source / U_ctrl act s_src
DCP_CTRL Can be changed: T Access level: 2
Data type: Unsigned32 / Binary Func. diagram: 6818
Min Max Factory setting
- - 0
Description: Sets the signal source for activating the voltage controller.
p54121 Voltage controller actual value rate time / U_ctr act val Tv
DCP_CTRL Can be changed: U, T Access level: 2
Data type: FloatingPoint32 Func. diagram: 6818
Min Max Factory setting
0.00 [ms] 100.00 [ms] 10.00 [ms]
Description: Sets the rate time in the voltage actual value channel of the voltage controller.
p54122 Voltage controller actual value smoothing time constant / U_ctrl act val T
DCP_CTRL Can be changed: U, T Access level: 2
Data type: FloatingPoint32 Func. diagram: 6818
Min Max Factory setting
0.00 [ms] 100.00 [ms] 2.00 [ms]
Description: Sets the smoothing time constant for the voltage actual value channel of the voltage controller.
p54124 Voltage controller DC link buffering dead range / U_ctr VDC dead rng
DCP_CTRL Can be changed: U, T Access level: 2
Data type: FloatingPoint32 Func. diagram: 6818
Min Max Factory setting
0.00 [%] 100.00 [%] 0.00 [%]
Description: Sets the width of the dead range in the setpoint-actual value difference channel for the "DC link buffering" function.
Dependency: Refer to: p54146
Note: The set value refers to the rated voltage of the SINAMICS DCP.
SINAMICS DCP
276 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
p54141 CI: Voltage controller positive current limit signal source / U_ctr I_lim posS_s
DCP_CTRL Can be changed: T Access level: 2
Data type: Unsigned32 / FloatingPoint32 Func. diagram: 6818
Min Max Factory setting
- - 52002[0]
Description: Sets the signal source for the positive current limit of the voltage controller.
SINAMICS DCP
List Manual (LH21), 05/2016 277
2 Parameters
2.2 List of parameters
p54142 CI: Voltage controller negative current limit signal source / U_ctr I_lim negS_s
DCP_CTRL Can be changed: T Access level: 2
Data type: Unsigned32 / FloatingPoint32 Func. diagram: 6818
Min Max Factory setting
- - 52004[0]
Description: Sets the signal source for the negative current limit of the voltage controller.
p54145 BI: Voltage controller enable signal source / U_ctrl enab s_src
DCP_CTRL Can be changed: T Access level: 2
Data type: Unsigned32 / Binary Func. diagram: 6818
Min Max Factory setting
- - 1
Description: Sets the signal source to enable the voltage controller.
p54146 Voltage controller DC link buffering minimum time / U_ctrl Vdc t_min
DCP_CTRL Can be changed: U, T Access level: 2
Data type: FloatingPoint32 Func. diagram: 6818
Min Max Factory setting
0.00 [ms] 100000.00 [ms] 0.00 [ms]
Description: Sets the minimum time to enable the voltage controller for the "DC link buffering" function.
Dependency: Refer to: p54124
p54200 CI: Battery charging char. manual current setpoint signal source / Batt man I_s s_src
DCP_CTRL Can be changed: T Access level: 2
Data type: Unsigned32 / FloatingPoint32 Func. diagram: 6720
Min Max Factory setting
- - 2050[1]
Description: Sets the signal source for the current setpoint for manual operation of the battery charging characteristic.
Manual operation:
Binector input p54201 = 1 signal
Dependency: Refer to: p54201
p54201 BI: Battery charging characteristic manual/auto signal source / Batt man/aut s_src
DCP_CTRL Can be changed: T Access level: 2
Data type: Unsigned32 / Binary Func. diagram: 6720
Min Max Factory setting
- - 1
Description: Sets the signal source for switching over between manual and automatic operation for the battery charging
characteristic.
BI: p54201 = 1 signal:
Automatic operation.
BI: p54201 = 0 signal:
Manual operation.
p54203 CI: Battery charging char. voltage actual value signal source / Batt U_act s_src
DCP_CTRL Can be changed: T Access level: 2
Data type: Unsigned32 / FloatingPoint32 Func. diagram: 6720
Min Max Factory setting
- - 55506[0]
Description: Sets the signal source for the voltage actual value of the battery charging characteristic.
SINAMICS DCP
278 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
p54204 BI: Battery charging characteristic enable signal source / Batt enab s_src
DCP_CTRL Can be changed: T Access level: 2
Data type: Unsigned32 / Binary Func. diagram: 6720
Min Max Factory setting
- - 899.11
Description: Sets the signal source for the "enable" signal of the battery charging characteristic.
SINAMICS DCP
List Manual (LH21), 05/2016 279
2 Parameters
2.2 List of parameters
r54221 CO: Battery charging characteristic total output / Batt outp total
DCP_CTRL Can be changed: - Access level: 2
Data type: FloatingPoint32 Func. diagram: 6720
Min Max Factory setting
- [%] - [%] - [%]
Description: Display and connector output for the output of the battery charging characteristic after manual/automatic switchover.
SINAMICS DCP
280 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
p54985 = 0:
--> the internal control for the LEDs is active.
p54985.x = 1 (x = 0...3):
--> the internal control for the two LEDs is not active.
--> the appropriate LED for diagnostics is switched on.
--> if both colors of an LED are switched on, then orange is output.
Bit field: Bit Signal name 1 signal 0 signal FP
00 LED H1000 green On Off 8055
01 LED H1000 red On Off 8055
02 LED H1010 green On Off 8055
03 LED H1010 red On Off 8055
SINAMICS DCP
List Manual (LH21), 05/2016 281
2 Parameters
2.2 List of parameters
Value: 0: Deactivated
1: Activated
Dependency: Refer to: p54990, p54991, p54992, r54994
SINAMICS DCP
282 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
If value = 12:
The current at side 2 is specified as setpoint.
If U1 <= U2: reactor current setpoint = setpoint * U2/U1
If U1 > U2: reactor current setpoint = setpoint (no conversion)
If value = 20:
The power is specified as setpoint.
If U1 <= U2: reactor current setpoint = setpoint/U1
If U1 > U2: reactor current setpoint = setpoint/U2
Explanation:
U1: voltage at side 1
U2: voltage at side 2
All values are referred to rated device quantities (rated current, rated voltage, rated power).
r55070 CO: Current setpoint after the ramp-function generator / I_set after RFG
DCP_CTRL Can be changed: - Access level: 2
Data type: FloatingPoint32 Func. diagram: 6805
Min Max Factory setting
- [%] - [%] - [%]
Description: Display and connector output for the current setpoint after the ramp-function generator.
r55072 CO: Current setpoint after limiting to the minimum / I_set aft lim min
DCP_CTRL Can be changed: - Access level: 2
Data type: FloatingPoint32 Func. diagram: 6805
Min Max Factory setting
- [%] - [%] - [%]
Description: Display and connector output for the current setpoint after suppressing low setpoints.
SINAMICS DCP
List Manual (LH21), 05/2016 283
2 Parameters
2.2 List of parameters
SINAMICS DCP
284 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
r55084[0...8] CO: Dynamic overload power loss calculated / Dyn overld P_loss
DCP_CTRL Can be changed: - Access level: 3
Data type: FloatingPoint32 Func. diagram: 6808
Min Max Factory setting
- [W] - [W] - [W]
Description: Display and connector output for various calculated power losses.
Index: [0] = Power loss at IGBT T1A
[1] = Power loss at IGBT T1B
[2] = Power loss at IGBT T2A
[3] = Power loss at IGBT T2B
[4] = Power loss at free-wheeling diode D1A
[5] = Power loss at free-wheeling diode D1B
[6] = Power loss at free-wheeling diode D2A
[7] = Power loss at free-wheeling diode D2B
[8] = Total power loss in the power unit
Note: For index 0 ... 7:
These power losses refer to a component.
For index 8:
Total power loss in the power unit = sum of the power losses for all components x number of B6 bridges.
30 kW device: 2 B6 bridges
120 kW device: 3 B6 bridges
SINAMICS DCP
List Manual (LH21), 05/2016 285
2 Parameters
2.2 List of parameters
r55091 CO: Dynamic overload load cycle monitoring signal / Dyn overload t_sig
DCP_CTRL Can be changed: - Access level: 3
Data type: FloatingPoint32 Func. diagram: 6808
Min Max Factory setting
- [%] - [%] - [%]
Description: Display and connector output for the output of the load cycle monitoring.
This signal indicates the percentage of the permissible overload duration that has already been utilized.
p55102 Heat sink temperature threshold exceeded response / Heat sink_tmp resp
DCP_CTRL Can be changed: U, T Access level: 3
Data type: Integer16 Func. diagram: 6810
Min Max Factory setting
1 4 2
Description: Sets the response when the maximum permissible heat sink temperature is exceeded.
Value: 1: Pulse frequency and current reduction
2: Current reduction
3: Pulse frequency reduction
4: Immediate shutdown with fault
SINAMICS DCP
286 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
r55120 CO: Current/power limit reactor current setpoint output / I/P_lim I_reac_set
DCP_CTRL Can be changed: - Access level: 2
Data type: FloatingPoint32 Func. diagram: 6810
Min Max Factory setting
- [%] - [%] - [%]
Description: Display and connector output for the reactor current setpoint after the current/power limiting.
r55122 CO: Voltage limiting reactor current setpoint output / U_lim I_react_set
DCP_CTRL Can be changed: - Access level: 2
Data type: FloatingPoint32 Func. diagram: 6812
Min Max Factory setting
- [%] - [%] - [%]
Description: Display and connector output for the reactor current setpoint after the voltage limiting.
SINAMICS DCP
List Manual (LH21), 05/2016 287
2 Parameters
2.2 List of parameters
SINAMICS DCP
288 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
r55150 CO: Voltage limiting reactor current setpoint output / U_lim I_react_set
DCP_CTRL Can be changed: - Access level: 2
Data type: FloatingPoint32 Func. diagram: 6812
Min Max Factory setting
- [%] - [%] - [%]
Description: Display and connector output for the reactor current setpoint after the voltage limiting.
SINAMICS DCP
List Manual (LH21), 05/2016 289
2 Parameters
2.2 List of parameters
p55155 Current actual value external activation / I_act val ext act
DCP_CTRL Can be changed: T Access level: 3
Data type: Integer16 Func. diagram: 6806
Min Max Factory setting
0 1 0
Description: Setting to activate the external current actual value
Value: 0: Not activated
1: Activated
p55156 CI: Current actual value external signal source / I_act ext s_src
DCP_CTRL Can be changed: T Access level: 3
Data type: Unsigned32 / FloatingPoint32 Func. diagram: 6806
Min Max Factory setting
- - 0
Description: Sets the signal source for the external current actual value.
r55170 CO: Limiting the reactor current setpoint after U dyn / Lim I_ re_sp U dyn
DCP_CTRL Can be changed: - Access level: 2
Data type: FloatingPoint32 Func. diagram: 6817
Min Max Factory setting
- [%] - [%] - [%]
Description: Display and connector output for the reactor current setpoint after dynamic voltage limiting.
r55172 CO: Main current controller reactor current setpoint / Mn ctr I_react_set
DCP_CTRL Can be changed: - Access level: 2
Data type: FloatingPoint32 Func. diagram: 6820
Min Max Factory setting
- [%] - [%] - [%]
Description: Display and connector output for the reactor current setpoint of the main current controller.
SINAMICS DCP
290 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
p55180 CI: Limiting side 1 U dyn signal source / Lim S1 U dyn s_src
DCP_CTRL Can be changed: U, T Access level: 2
Data type: Unsigned32 / FloatingPoint32 Func. diagram: 6817
Min Max Factory setting
- - 52002[0]
Description: Sets the signal source for the dynamic voltage limiting on side 1.
p55185 CI: Limiting side 2 U dyn signal source / Lim S2 U dyn s_src
DCP_CTRL Can be changed: U, T Access level: 2
Data type: Unsigned32 / FloatingPoint32 Func. diagram: 6817
Min Max Factory setting
- - 52002[0]
Description: Sets the signal source for the dynamic voltage limiting on side 2.
SINAMICS DCP
List Manual (LH21), 05/2016 291
2 Parameters
2.2 List of parameters
r55210 CO: Main current controller precontrol output / Mn ctr prctr outp
DCP_CTRL Can be changed: - Access level: 2
Data type: FloatingPoint32 Func. diagram: 6820
Min Max Factory setting
- [%] - [%] - [%]
Description: Display and connector output for the output of the main current controller precontrol.
p55226 Main current controller voltage lower limit / Main ctr U low lim
DCP_CTRL Can be changed: U, T Access level: 2
Data type: FloatingPoint32 Func. diagram: 6820
Min Max Factory setting
1.0 [%] 50.0 [%] 10.0 [%]
Description: Sets the lower limit of the voltage actual values for precontrol and adaptation of the main current controller.
SINAMICS DCP
292 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 293
2 Parameters
2.2 List of parameters
p55305 Modulator control angle limiting positive / Mod ctrAng lim pos
DCP_CTRL Can be changed: U, T Access level: 2
Data type: FloatingPoint32 Func. diagram: 6825
Min Max Factory setting
0.00 [%] 200.00 [%] 200.00 [%]
Description: Sets the positive limiting for the control angle.
In conjunction with p55306, it is possible to restrict the operating range of the SINAMICS DCP.
Dependency: Refer to: p55306
Note: Examples:
Control angle limited to:
0 ... +200 %: only positive current possible
-200 ... 0 %: only negative current possible
-100 ... +100 %: only step-down possible
p55306 Modulator control angle limiting negative / Mod ctrAng lim neg
DCP_CTRL Can be changed: U, T Access level: 2
Data type: FloatingPoint32 Func. diagram: 6825
Min Max Factory setting
-200.00 [%] 0.00 [%] -200.00 [%]
Description: Sets the negative limiting for the control angle.
In conjunction with p55305, it is possible to restrict the operating range of the SINAMICS DCP.
Dependency: Refer to: p55305
Note: Examples:
Control angle limited to:
0 ... +200 %: only positive current possible
-200 ... 0 %: only negative current possible
-100 ... +100 %: only step-down possible
SINAMICS DCP
294 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 295
2 Parameters
2.2 List of parameters
p55352 CI: Precharging target value signal source / Pre targ_val s_src
DCP_CTRL Can be changed: U, T Access level: 2
Data type: Unsigned32 / FloatingPoint32 Func. diagram: 6835
Min Max Factory setting
- - 2050[2]
Description: Sets the signal source for the target value for precharging using the "pulsing up" technique.
When precharging, the voltage is pulsed up to this target value.
p55355[0...1] Precharging wait time after precharging contactor close / Prchg t prchg_cont
DCP_CTRL Can be changed: U, T Access level: 2
Data type: FloatingPoint32 Func. diagram: 6835
Min Max Factory setting
0 [ms] 1000000 [ms] 100 [ms]
Description: Sets the wait time for closing the precharging contactor.
Index: [0] = Side 1
[1] = Side 2
SINAMICS DCP
296 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 297
2 Parameters
2.2 List of parameters
SINAMICS DCP
298 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
SINAMICS DCP
List Manual (LH21), 05/2016 299
2 Parameters
2.2 List of parameters
r55505 CO: Actual value voltage inner side 1 / Act val U inner S1
DCP_CTRL Can be changed: - Access level: 2
Data type: FloatingPoint32 Func. diagram: 6818, 6850
Min Max Factory setting
- [%] - [%] - [%]
Description: Display and connector output for the inner voltage on side 1.
SINAMICS DCP
300 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
r55506 CO: Actual value voltage inner side 2 / Act val U inner S2
DCP_CTRL Can be changed: - Access level: 2
Data type: FloatingPoint32 Func. diagram: 6818, 6850
Min Max Factory setting
- [%] - [%] - [%]
Description: Display and connector output for the inner voltage on side 2.
r55510 CO: Actual value reactor current sum / Act val I_re sum
DCP_CTRL Can be changed: - Access level: 2
Data type: FloatingPoint32 Func. diagram: 6850
Min Max Factory setting
- [%] - [%] - [%]
Description: Display and connector output for the sum of the reactor currents.
The value is the sum of r55511 and r55512.
Dependency: Refer to: r55511, r55512
r55511 CO: Actual value reactor current power unit 1 / ActVal I_react PU1
DCP_CTRL Can be changed: - Access level: 2
Data type: FloatingPoint32 Func. diagram: 6850
Min Max Factory setting
- [%] - [%] - [%]
Description: Display and connector output for the reactor current of power unit 1.
Dependency: Refer to: r55510
r55512 CO: Actual value reactor current power unit 2 / ActVal I_react PU2
DCP_CTRL Can be changed: - Access level: 2
Data type: FloatingPoint32 Func. diagram: 6850
Min Max Factory setting
- [%] - [%] - [%]
Description: Display and connector output for the reactor current of power unit 2.
Dependency: Refer to: r55510
SINAMICS DCP
List Manual (LH21), 05/2016 301
2 Parameters
2.2 List of parameters
r55513 CO: Actual value reactor current power unit 3 / ActVal I_react PU3
DCP_CTRL Can be changed: - Access level: 2
Data type: FloatingPoint32 Func. diagram: 6850
Min Max Factory setting
- [%] - [%] - [%]
Description: Display and connector output for the reactor current of power unit 3.
Dependency: Refer to: r55510
r55520 CO: Actual value reactor current sum averaged / ActVal I_re SumAvg
DCP_CTRL Can be changed: - Access level: 2
Data type: FloatingPoint32 Func. diagram: 6850
Min Max Factory setting
- [%] - [%] - [%]
Description: Display and connector output for the sum of the averaged reactor currents.
The value is the sum of r55521, r55522 and r55523.
Dependency: Refer to: r55521, r55522
SINAMICS DCP
302 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
r55521 CO: Actual value reactor current power unit 1 averaged / ActVal I_re PU1avg
DCP_CTRL Can be changed: - Access level: 2
Data type: FloatingPoint32 Func. diagram: 6850
Min Max Factory setting
- [%] - [%] - [%]
Description: Display and connector output for the averaged reactor current of power unit 1.
Dependency: Refer to: r55520
r55522 CO: Actual value reactor current power unit 2 averaged / ActVal I_re PU2avg
DCP_CTRL Can be changed: - Access level: 2
Data type: FloatingPoint32 Func. diagram: 6850
Min Max Factory setting
- [%] - [%] - [%]
Description: Display and connector output for the averaged reactor current of power unit 2.
Dependency: Refer to: r55520
r55523 CO: Actual value reactor current power unit 3 averaged / ActVal I_re PU3avg
DCP_CTRL Can be changed: - Access level: 2
Data type: FloatingPoint32 Func. diagram: 6850
Min Max Factory setting
- [%] - [%] - [%]
Description: Display and connector output for the averaged reactor current of power unit 3.
Dependency: Refer to: r55520
r55530 Actual value reactor current sum averaged / ActVal I_re SumAvg
DCP_CTRL Can be changed: - Access level: 1
Data type: FloatingPoint32 Func. diagram: 6850
Min Max Factory setting
- [A] - [A] - [A]
Description: Displays the sum of the averaged reactor currents.
The value is the sum of r55531, r55532 and r55533.
Dependency: Refer to: r55531, r55532
SINAMICS DCP
List Manual (LH21), 05/2016 303
2 Parameters
2.2 List of parameters
r55531 Actual value reactor current power unit 1 averaged / ActVal I_re PU1avg
DCP_CTRL Can be changed: - Access level: 2
Data type: FloatingPoint32 Func. diagram: 6850
Min Max Factory setting
- [A] - [A] - [A]
Description: Displays the actual value for the averaged reactor current of power unit 1.
Dependency: Refer to: r55530
r55532 Actual value reactor current power unit 2 averaged / ActVal I_re PU2avg
DCP_CTRL Can be changed: - Access level: 2
Data type: FloatingPoint32 Func. diagram: 6850
Min Max Factory setting
- [A] - [A] - [A]
Description: Displays the actual value for the averaged reactor current of power unit 2.
Dependency: Refer to: r55530
r55533 Actual value reactor current power unit 3 averaged / ActVal I_re PU3avg
DCP_CTRL Can be changed: - Access level: 2
Data type: FloatingPoint32 Func. diagram: 6850
Min Max Factory setting
- [A] - [A] - [A]
Description: Displays the actual value for the averaged reactor current of power unit 3.
Dependency: Refer to: r55530
SINAMICS DCP
304 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
For index 4:
P = U2 * I_ext (I_ext = value according to p55156)
The power is calculated from the voltage measured at side 2 and the externally measured current at side 2.
The result is the power that is either issued or fed in at side 2.
For index 3 ... 4:
These indices only supply sensible values if there is an external current measurement at the appropriate side and
p55156 is correspondingly set.
SINAMICS DCP
List Manual (LH21), 05/2016 305
2 Parameters
2.2 List of parameters
SINAMICS DCP
306 List Manual (LH21), 05/2016
2 Parameters
2.2 List of parameters
p55551 BI: Power unit fault acknowledge signal source / PU F ackn s_src
DCP_CTRL Can be changed: U, T Access level: 2
Data type: Unsigned32 / Binary Func. diagram: 6855
Min Max Factory setting
- - 2139.0
Description: Sets the signal source for "acknowledge fault" of the power unit.
SINAMICS DCP
List Manual (LH21), 05/2016 307
2 Parameters
2.2 List of parameters
SINAMICS DCP
308 List Manual (LH21), 05/2016
Function diagrams 3
Content
SINAMICS DCP
List Manual (LH21), 05/2016 309
3 Function diagrams
3.1 Table of contents
SINAMICS DCP
310 List Manual (LH21), 05/2016
3 Function diagrams
3.1 Table of contents
SINAMICS DCP
List Manual (LH21), 05/2016 311
3 Function diagrams
3.1 Table of contents
SINAMICS DCP
312 List Manual (LH21), 05/2016
3 Function diagrams
3.2 Explanations on the function diagrams
Function diagrams
SINAMICS DCP
List Manual (LH21), 05/2016 313
314
Data Set (PDS) (Def.w) Not relevant A static state is represented here. The
sampling time data is not relevant.
[1020.7]
[aaaa.b]
SINAMICS DCP
1 2 3 4 5 6 7 8
DO: All Objects fp_1020_89.vsd Function diagram
- Explanation of the symbols (part 1) 03.06.2014 v 1.2 SINAMICS DCP
List Manual (LH21), 05/2016
SINAMICS DCP
Fig. 3-2
S
pxxxx
1
is displayed (in this case, the delivery Outputs a logical "1" at output y if x < S.
state is switch position 1). & 0
1
S
x 1 y
S Q Outputs a logical "1" at output y if x > S.
S = Input for setting 0
R = Input for resetting
R Q Q = Non-inverted output S
Q = Inverted output
Axxxxx
Monitoring or
x1 y 1
Fxxxxx Positioning in sheet at bottom right. =1 x y
x2 y = 1 if x1 != x2.
Outputs a logical "1" at output y if x < S.
0 If x >= S + H, y returns to 0.
x y 1
-1 x y
Outputs a logical "1" at output y if x > S.
y = -x If x <= S - H, y returns to 0.
0
dx y SET
x
3 Function diagrams
dt
y=
dx x S&H y
Sample and hold element.
dt
y = x if SET = 1
(no retentive memory during
POWER OFF)
1 2 3 4 5 6 7 8
DO: All Objects fp_1021_89.vsd Function diagram
- Explanation of the symbols (part 2) 03.06.2014 v 1.2 SINAMICS DCP
315
316
x T 0 y
y
pxxxx
Digital signal x must retain the value "1" without interruption during time
T, before output y switches to "1". t
pxxxx
x y pxxxx pxxxx pyyyy
x y
0 T
T1 T2
x 0 T y
x T1 T2 y x y
pxxxx
pxxxx pxxxx
Digital signal x must retain the value "0" without interruption during time Digital signal x must retain the value "1" without interruption during
T, before output y switches to "0". time T1 or the value "0" during time T2, before output y switches its The rising edge of a pulse at input X sets output Y to
signal state. 1 for pulse duration T. The pulse generator
T T T T cannot be retriggered. At T=0, a pulse duration of one cycle applies.
T1 T1 T2 T2
x
y
List Manual (LH21), 05/2016
y
SINAMICS DCP
1 2 3 4 5 6 7 8
DO: All Objects fp_1022_89.vsd Function diagram
- Explanation of the symbols (part 3) 03.06.2014 v 1.2 SINAMICS DCP
List Manual (LH21), 05/2016
SINAMICS DCP
Fig. 3-4
r0723.15 Binectors are binary signals that can be freely interconnected (BO = Binector Output).
They represent a bit of a "BO:" display parameter (e.g. bit 15 of r0723).
1030 – Handling BICO technology
r0723 Connectors are "analog signals" that can be freely interconnected (e.g. percentages, speeds, or torques).
Connectors are simultaneously "CO:" display parameters (CO = Connector Output).
At the signal destination, the required binector/connector is selected using the appropriate parameters:
"BI:" parameters for binectors (BI = Binector Input)
or
"CI:" parameters for connectors (CI = Connector Input)
The main setpoint for the speed controller (CI: p1070) should come from the motorized potentiometer output (CO: r1050) and the "Jog"
command (BI: p1055) from digital input DI 0 (BO: r0722.0, terminal X122.1) on the CU320.
[2460] [2580]
Setpoint channel
2
Motorized potentiometer Sollwert
p55050
[2460] [6805]
3 Function diagrams
1 p840[0] = 2090.0 Terminal X122.1 acts as "Jog bit 0".
2 p55050] = 2050[1] The motorized potentiometer output acts as the main setpoint for the speed controller.
1 2 3 4 5 6 7 8
DO: All Objects fp_1030_89.vsd Function diagram
- Handling BICO technology 03.06.2014 v 1.2 SINAMICS DCP
317
3 Function diagrams
3.3 CUD input/output terminals
Function diagrams
SINAMICS DCP
318 List Manual (LH21), 05/2016
List Manual (LH21), 05/2016
SINAMICS DCP
Fig. 3-5
4000 μs
[1020.7]
2050 – Digital inputs (DI 0 ... DI 3)
CUD
X177.9
P24_S
p50765 (0 ms)
X177.11 DI 0 24 V T 0
+ + r53010.00
5V
1 r53010.01
M p50766 (0 ms)
X177.12 DI 1 24 V T 0
+ + r53010.02
5V
1 r53010.03
M p50767 (0 ms)
X177.13 DI 2 24 V T 0
+ + r53010.04
5V
1 r53010.05
M p50768 (50 ms)
X177.14 DI 3 24 V T 0
+ r53010.06
5V
3 Function diagrams
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_2050_89.vsd Function diagram
- 2050 -
- Digital inputs (DI 0 ... DI 3) 03.06.2014 v 1.2 SINAMICS DCP
319
320
+
(0) +
+ DO 0 X177.19
1 + +
1
Short-circuit
A60018
CUD DO 1 t_del r53020.01 monitoring M
0...10000 [ms] CUD DO inv DO overload
p50776 (0 ms) p50770[1]
r53021.00
CUD DO 1 s_src
p50772 0 <1>
T T +
(0) +
+ DO 1 X177.20
1 + + +
1
Short-circuit M +
A60018
monitoring X177.23
DO overload
CUD DO 2 t_del r53020.02
0...10000 [ms] CUD DO inv
p50777 (0 ms) p50770[2] r53021.01
CUD DO 2 s_src
p50773 0 <1>
T T +
(0) +
+ DO 2 X177.21
1 + +
1
Short-circuit
A60018
CUD DO 3 t_del r53020.03 monitoring M
0...10000 [ms] CUD DO inv DO overload
p50778 (0 ms) p50770[3]
r53021.02
CUD DO 3 s_src
p50774 0 <1>
T T
(0) +
+ DO 3 X177.22
1 + + +
1
Short-circuit M +
A60018
monitoring X177.24
DO overload
List Manual (LH21), 05/2016
r53021.03
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_2055_89.vsd Function diagram
- 2055 -
- Digital outputs (DO 0 ... DO 3) 03.06.2014 v 1.2 SINAMICS DCP
List Manual (LH21), 05/2016
SINAMICS DCP
Fig. 3-7
4000 μs
[1020.7]
CUD
2060 – Digital inputs/outputs, bidirectional (DI/DO 4 ... DI/DO 5)
X177.10 P24_S
DI/DO 4 t_del_inp
CUD DI/DO typ p50790 (0 ms)
0...1
p50789[0] (0) 1 r53010.09 [8020.1]
DI T 0
DI + r53010.08 [5812.1]
0
X177.15 DI/DO 4
+ +
+
1 DO
DO + r53020.04
24 V
Short-circuit CUD DI/DO inv DI/DO 4 t_del_out
<1> M 0...1 0...10000 [ms]
monitoring p50780[0] (0) p50785 (0 ms)
(0)
1
1
A60018
DI/DO 5 t_del_inp
CUD DI/DO typ p50791 (0 ms)
0...1
p50789[1] (0) 1 r53010.11 [8020.1]
5V DI T 0
DI + r53010.10 [5812.1]
0
X177.16 DI/DO 5
+
+
1 DO
DO + r53020.05
+
Short-circuit CUD DI/DO inv DI/DO 5 t_del_out
<1> M 0...1 0...10000 [ms]
monitoring p50780[1] (0) p50786 (0 ms)
X177.23 M
M CUD DI/DO 5 s_src
3 Function diagrams
<1> The wiring represented as a dashed line applies during use as a digital output (p50789[x] = 1)
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_2060_89.vsd Function diagram
- 2060 -
- Digital inputs/outputs bidirectional (DI/DO 4 ... DI/DO 5) 03.06.2014 v 1.2 SINAMICS DCP
321
322
[1020.7]
CUD
2065 – Digital inputs/outputs, bidirectional (DI/DO 6 ... DI/DO 7)
X177.10 P24_S
DI/DO 6 t_del_inp
CUD DI/DO typ p50792 (0 ms)
0...1
p50789[2] (0) 1 r53010.13
DI T 0
DI + r53010.12
0
X177.17 DI/DO 6
+ +
+
1 DO
DO + r53020.06
24 V
Short-circuit CUD DI/DO inv DI/DO 6 t_del_out
<1> M 0...1 0...10000 [ms]
monitoring p50780[2] (0) p50787 (0 ms)
(0)
1
1
A60018
DI/DO 7 t_del_inp
CUD DI/DO typ p50793 (0 ms)
0...1
p50789[3] (0) 1 r53010.15 [8002.1]
5V DI T 0
DI + r53010.14 [8020.1]
0
X177.18 DI/DO 7
+
+
1 DO
DO + r53020.07
+
Short-circuit CUD DI/DO inv DI/DO 7 t_del_out
<1> M 0...1 0...10000 [ms]
monitoring p50780[3] (0) p50788 (0 ms)
X177.24 M
M CUD DI/DO 7 s_src
r53021.07 0 p50784
T T
+
(0)
1
1
A60018
List Manual (LH21), 05/2016
<1> The wiring represented as a dashed line applies during use as a digital output (p50789[x] = 1)
SINAMICS DCP
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_2065_89.vsd Function diagram
- 2065 -
- Digital inputs/outputs bidirectional (DI/DO 6 ... DI/DO 7) 03.06.2014 v 1.2 SINAMICS DCP
List Manual (LH21), 05/2016
SINAMICS DCP
Fig. 3-9
4,000 μs
1
± 10V ±20mA
+ -1
1 1
X177.26 + 10V=100% 0
20mA=100% r52010
21 0 CUD AI 0 type
0...2 + r53030.00 CUD AI wire brk
p50700 (0)
F60046
Wire brk at AI 0 AI m act inv AI m act ena s_src
p50744 p50746
(0) (1)
AI m act sig
0...3
AI m act offs p50743 (0)
AI m act scal -200.00...200.00 [%] AI m act T
-270.00...270.00 [V] p50742 (0.00) 0...10000 [ms]
p50741[D] (60.00) p50745 (0)
<1> 1ms -1 3 0
0 0%
r52013
+ + -1 2 +
1
-1
3 Function diagrams
<1> This analog input is not accessible.
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_2075_89.vsd Function diagram
- 2075 -
- Analog inputs (AI 0) 03.06.2014 v 1.2 SINAMICS DCP
323
324
X177.27 1ms -1 3
+ 0
0 0%
p50711 r52015
u i AI 1 + + -1 2
* 100% +
1
± 10V ±20mA
+ -1
1 1
X177.28 + 10V=100% 0
20mA=100% r52014
21 0 CUD AI 1 type
0...2 + r53030.01 CUD AI wire brk
p50710 (0)
(i 2mA)
F60047
Wire brk at AI 1 CUD AI 2 inv CUD AI 2 ena s_src
p50724 p50726
(0) (1)
CUD AI 2 offs CUD AI 2 sig proc
-200.00...200.00 [%] 0...3
p50722 (0.00) p50723 (0)
CUD AI 2 scal CUD AI 2 T
-1000.0...1000.0 [%] 0...10000 [ms]
10V=100% p50721[D] (100.0) p50725 (0)
X177.29 1ms -1 3 0
0 0%
p50721 r52017
u AI 2 + + -1 2
* 100% +
1
± 10V
-1 [5884.1]
1 1
X177.30 0
r52016
List Manual (LH21), 05/2016
SINAMICS DCP
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_2080_89.vsd Function diagram
- 2080 -
- Analog inputs (AI 1 ... AI 2) 03.06.2014 v 1.2 SINAMICS DCP
List Manual (LH21), 05/2016
SINAMICS DCP
Fig. 3-11
4,000 μs
[1020.7]
2085 – Analog inputs (AI 3 ... AI 4)
X177.1 100μs -1 3 0
0 0%
p50731 r52019
u AI 3 + + -1 2
* 100% +
1
± 10V
-1
1 1
X177.2
0
r52018
X177.3 100μs
-1 3 0
0 0%
p50731 r52021
u AI 4 + + -1 2
* 100% +
1
-1
3 Function diagrams
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_2085_89.vsd Function diagram
- 2085 -
- Analog inputs (AI 3 ... AI 4) 03.06.2014 v 1.2 SINAMICS DCP
325
326
[1020.7]
2090 – Analog inputs (AI 5 ... AI 6)
X177.5 100μs -1 3 0
0 0%
p50731 r52023
u AI 5 + + -1 2
* 100% +
1
± 10V
-1
1 1
X177.6
0
r52022
X177.7 100μs
-1 3 0
0 0%
p50731 r52025
u AI 6 + + -1 2
* 100% +
1
± 10V
-1
1 1
X177.8 0
r52024
List Manual (LH21), 05/2016
SINAMICS DCP
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_2090_89.vsd Function diagram
- 2090 -
- Analog inputs (AI 5 ... AI 6) 03.06.2014 v 1.2 SINAMICS DCP
List Manual (LH21), 05/2016
SINAMICS DCP
Fig. 3-13
4000 μs
[1020.7]
CUD
2095 – Analog outputs (AO 0 ... AO 1)
r52026
Uout [V] = * p50753 + p50754
CUD AO 0 s_src -1 3 100%
p50750 x x y X177.49
(0) -1 2 + y [V] = * p50753 +
100%
1 AO 0
0
r52026 X177.50
M
r52027
CUD AO 1 s_src -1 3 Uout [V] = * p50758 + p50759
100%
p50755 x x y X177.51
(0) -1 2 + y [V] = * p50758 +
100%
1 AO 1
0
r52027 X177.52
M
3.4 PROFIdrive
Function diagrams
2460 – IF1 receive telegram, free interconnection via BICO (p0922 = 999) 330
2470 – IF1 send telegram, free interconnection via BICO (p0922 = 999) 331
SINAMICS DCP
328 List Manual (LH21), 05/2016
List Manual (LH21), 05/2016
SINAMICS DCP
Fig. 3-14
USS settings PROFIdrive sampling time
Set PROFIBUS address
Field bus baud Field bus USS PZD Fieldbus USS DO_no
p02020 Field bus address p02022 Field bus USS PKW p02035 [1020.7]
PB address Current p02021 p02023 PROFINET address
1...126 PROFIBUS
p00918 (126) Memory address PN IP of Station
PROFIBUS r61001[0...3]
2410 – PROFIBUS (PB)/PROFINET (PN)/USS, addresses and diagnostics
3 Function diagrams
Field bus error <4> Only one of the two interfaces -
r02029[0...7] RS 485 (X178-3, 4) or RS 232 (X179-3, 4) - may be used.
Diagnostic parameters <5> Bus termination can be switched on/off with p50820
3.4 PROFIdrive
<6> Not with CPU stop
1 2 3 4 5 6 7 8
DO: CU_DCP;DCP_CTRL fp_2410_89.vsd Function diagram
- 2410 -
- PROFIBUS (PB) / PROFINET (PN) / USS, addresses and diagnostics 03.06.2014 v 1.2 SINAMICS DCP
329
330
3.4 PROFIdrive
3 Function diagrams
Fig. 3-15
r02090.00
... PROFIdrive sampling time
r02090.15
<1> PZD receive word 1 + + r02050[0] [1020.7]
r02091.00
+ r02060[0] IF1 PZD recv DW ...
r02091.15
PZD receive word 2 + + r02050[1]
2460 – IF1 receive telegram, free interconnection via BICO (p0922 = 999)
r02092.00
PROFIBUS
PROFINET
+ r02060[1] IF1 PZD recv DW ...
r02092.15
USS PZD receive word 3 + + r02050[2]
r02093.00
+ r02060[2] IF1 PZD recv DW ...
r02093.15
PZD receive word 4 + + r02050[3]
+ r02060[3] IF1 PZD recv DW
PROFIdrive
receive telegram PZD receive word 5 + r02050[4]
2 connector-binector converters p2048
+ r02060[4] IF1 PZD recv DW
Header
<4>
PZD receive word 6 + r02050[5] Con/bin outp inv
Drive object 1 p02098[0].0
+ r02060[5] IF1 PZD recv DW
Drive object 2 <2>
Con/bin S_src
p02099 [0] 0
. (0) +
r02094.00
. + + 1
1
. + +
Con/bin outp inv
+
+ +
p02098[0].15 +
Drive object n
+
0
. r02094.15
.
+
1
. PZD receive word 29 + r02050[28]
1
+
<1> To comply with the PROFIdrive profile, receive word 1 must be used as control word 1 (STW1) (due to bit 10, "Control request"). 0
+
r02095.15
List Manual (LH21), 05/2016
<2> Using the two connector-binector converters, the bits from two of the PZD receive words (5 to 32) can be extracted and used as binectors.
1
<3> For words and double words, the 4000 hex = 100% and 4000 0000 hex = 100% representations apply respectively. 1
<4> The connector-binector converter only ever converts the lower 16 bits, regardless of the input variable.
SINAMICS DCP
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_2460_89.vsd Function diagram
- 2460 -
- IF1 receive telegram, free interconnection via BICO (p0922 = 999) 03.06.2014 v 1.2 SINAMICS DCP
List Manual (LH21), 05/2016
SINAMICS DCP
Fig. 3-16
IF1 diag send DW
r02063[0...30] PROFIdrive sampling time
<3> IF1 diag send word 1...16
<2> p02051 [0] r02053[0...31] [1020.7]
<2> <1> (0) ... <1>
+ + PZD send word 1
IF1 PZD send DW p02061 [0]
p02051 [1]
(0) + +
2470 – IF1 send telegram, free interconnection via BICO (p0922 = 999)
(0)
+ PZD send word 2
IF1 PZD send DW p02061 [1]
p02051 [2]
(0) +
(0)
+ PZD send word 3
IF1 PZD send DW p02061 [2]
p02051 [3]
(0) +
(0)
+ PZD send word 4
IF1 PZD send DW p02061 [3]
p02051 [4]
(0) +
(0)
+ PZD send word 5
IF1 PZD send DW p02061 [4]
p02051 [5]
(0) +
(0)
+ PZD send word 6
IF1 PZD send DW p02061 [5] PROFIdrive
p02051 [6]
(0) +
send telegram
(0)
+ PZD send word 7
IF1 PZD send DW p02061 [6] Header
p02051 [7]
(0) +
(0) Drive object 1
+ PZD send word 8
IF1 PZD send DW p02061 [7]
p02051 [8] Drive object 2
(0) +
(0)
+ + PZD send word 9 .
+ .
+
+
+ + .
+ + Drive object n
IF1 PZD send DW p02061 [27]
(0) +
p02051 [28]
+
.
(0) .
IF1 PZD send DW p02061 [28]
p02051 [29]
+ PZD send word 29
.
(0) +
Drive object m
(0)
+ PZD send word 30
IF1 PZD send DW p02061 [29]
p02051 [30] Trailer
(0) +
(0)
+ PZD send word 31
IF1 PZD send DW p02061 [30]
p02051 [31]
(0) +
(0)
+ + PZD send word 32 PROFIBUS
<4>
PROFINET
USS
<1> To comply with the PROFIdrive profile, send word 1 must be used as status word 1 (ZSW1) rather than as the DWORD.
<2> Each PZD word can be assigned a word or a double word.
Only one of the 2 interconnection parameters (p2051 or p2061) can have a value <> 0 for a PZD word.
3 Function diagrams
<3> Using the two connector-binector converters at [2472], the bits from 5 of the send words can be interconnected with any binectors.
<4> Physical word and double word values are inserted in the telegram as referenced variables.
3.4 PROFIdrive
(Telegram content = 4000 hex or 4000 0000 hex for double words if the input variable has the value 100%.)
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_2470_89.vsd Function diagram
- 2470 -
- IF1 send telegram, free interconnection via BICO (p0922 = 999) 03.06.2014 v 1.2 SINAMICS DCP
331
332
3.4 PROFIdrive
3 Function diagrams
Fig. 3-17
Bin/con ZSW inv p2048
5 binector-connector converters p02088[2].0
[1020.7]
[1] 1
Bin/con ZSW inv (0) 1
p02088[0].0
1
1 p02083 [0...15] 0 Bin/con ZSW send
[0]
(0) +
r02089[3]
[1] 1
(0) 1
0
p02081 [0...15] 0 Bin/con ZSW send [15]
[0] (0) +
(0) +
r02089[1] 1
[1] 1
(0) 1
1
1 (0) 1
1 1
0
[15]
(0) +
1
1
SINAMICS DCP
1 2 3 4 5 6 7 8
DO: DCP_CTRL;CU_DCP fp_2472_89.vsd Function diagram
- 2472 -
- IF1 status words, free interconnection 03.06.2014 v 1.2 SINAMICS DCP
3 Function diagrams
3.5 Internal control/status words
Function diagrams
SINAMICS DCP
List Manual (LH21), 05/2016 333
334
[1020.7]
STW fault/alarm
<1> This parameter belongs to the Control Unit and serves as the source for Bit no. Control word faults/alarms r02138
simultaneous acknowledgment of all faults on all drive objects.
2546 – Control word, faults/alarms
p02116 [C]
<2> (1) 1 11 r02138.11 Ext alarm 2 eff [8065.1]
Ext fault 3 t_on
p02108 [C] p03110 [ms] p02117 [C]
<2> (1) <2> (1) 1 12 r02138.12 Ext alarm 3 eff [8065.1]
p02106 [C]
p03111 [C] T 0 <2> (1) 1 13 r02138.13 Ext fault 1 eff [8060.1]
<2> (1) &
p02107 [C]
<2> (1) 1 14 r02138.14 Ext fault 2 eff [8060.1]
p03112 [C]
List Manual (LH21), 05/2016
<2> (0)
1 15 r02138.15 Ext fault 3 eff [8060.1]
SINAMICS DCP
1 2 3 4 5 6 7 8
DO: All Objects fp_2546_89.vsd Function diagram
- 2546 -
- Control word faults/alarms 03.06.2014 v 1.2 SINAMICS DCP
List Manual (LH21), 05/2016
SINAMICS DCP
Fig. 3-19
Original sampling time
[1020.7]
2548 – Status word, faults/alarms 1
ZSW fault/alarm 1
Bit no. Status word, faults/alarms 1 r02139
0 r02139.00
5 r02139.05
6 r02139.06
8 r02139.08
10
11 r02139.11
12 r02139.12
13
14
15
5
OC / OFF3
<2> 1
p03982.02 6
OFF3 S_src 1 0
p00848 [C] 7
(1)
OFF3 S_src 2 8
p00849 [C]
&
[8020.3] (1) 9
<1> <2> 1
p00854 [C] p03982.10
10 r00898.10
(1) 0
<2>
p03982.03 11
Operation enable 1
p00852 [C] 12
[5830.3] (2090.1;1) 0
13
List Manual (LH21), 05/2016
14
<1> Bit 10 must be set in the first PZD word of <2> p3982 is for setting the control word from
the telegram received from the serial STARTER or from the AOP30. It must not be used 15
interfaces, so that the by the user. Therefore it is not
drive can accept the process data. included in the List Manual.
SINAMICS DCP
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_2580_89.vsd Function diagram
- 2580 -
- Control word sequence control 08.05.2014 v 1.2 SINAMICS DCP
List Manual (LH21), 05/2016
SINAMICS DCP
Fig. 3-21
PROFIdrive bit
16,000 μs
[1020.7]
r00899
0 r00899.0
1 r00899.01
2 r00899.02
4 r00899.04
5 r00899.05
6 r00899.06
Sequence control
[2650]
7 r00899.07
8 r00899.08
1 9 <1> r00899.09
10
11 r00899.11
12
14
3 Function diagrams
15
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_2585_89.vsd Function diagram
- 2585 -
- Status word sequence control 03.06.2014 v 1.2 SINAMICS DCP
337
3 Function diagrams
3.6 Sequence control
Function diagrams
SINAMICS DCP
338 List Manual (LH21), 05/2016
List Manual (LH21), 05/2016
SINAMICS DCP
Fig. 3-22
16,000 μs
[1020.7]
S1 : Switching On Inhibited S1 : Switching On Inhibited
2650 – Sequencer
Fault
acknowledgement
[2546.7] OFF 1 = 0
OFF 2 = 0
OFF 3=1 OFF 1 = 1
and
n=0
S1 : Switching On Inhibited
Voltage-
enable
S1 : Switching On Inhibited
S3: Switched On
Drv op_display
Enable ramp-function generator, Control of +
r00002
speed generator, Ia controller operating state Op_display
OFF 3 = 0 r50000
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_2650_89.vsd Function diagram
- 2650 -
- Sequencer 25.04.2016 v 1.2 SINAMICS DCP
339
3 Function diagrams
3.7 Auxiliary functions
Function diagrams
SINAMICS DCP
340 List Manual (LH21), 05/2016
List Manual (LH21), 05/2016
SINAMICS DCP
[1020.7]
Setting range
-200.00 to +200.00%
+0% r02902[0] 0,00 % r52000
3100 – Fixed values
Square
3102 – Function generator
p4829
p4824
p4826
p4827
p4821
p4828
FG amplitude scal
p4822 0.00000...200.00000 [%]
p04831 (100.00000)
Staircase Binary noise
FG outp_sig [%]
p4829 p4829 r04818[0]
p4824 p4824
p4826 p4826
p4827 p4827
p4821 p4821
p4828 p4828
List Manual (LH21), 05/2016
p04824 (5.00) p04825 (7.00) p04826 (0.00) p04827 (32.00) p04828 (-100.00) p04829 (100.00)
-1600.00...1600.00 [%] -1600.00...1600.00 [%] -1600.00...1600.00 [%] 0.00...100000.00 [ms] -10000.00...0.00 [%] 0.00...10000.00 [%]
FG amplitude FG 2nd amplitude FG offset FG ramp-up offset FG lower limit FG upper limit Only value "0" meaningful for
p4810
SINAMICS DCP
1 2 3 4 5 6 7 8
DO: CU_DC fp_3102_89.vsd Function diagram
- 3102 -
- Function generator 03.06.2014 v 1.2 SINAMICS DCP
3 Function diagrams
3.8 Superimposed closed-loop control
Function diagrams
SINAMICS DCP
List Manual (LH21), 05/2016 343
344
p54005 p54030
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_6700_89.vsd Function diagram
- 6700 -
- MPP tracker 25.04.2016 v 1.2 SINAMICS DCP
List Manual (LH21), 05/2016
SINAMICS DCP
Fig. 3-26
16,000 μs
I_batt
Batt Status
r54225.0
r54225
r54225.00 Batt U < p54210[0]
p54211[0] r54225.01 Batt U < p54210[1]
r54225.02 Batt U < p54210[2]
r54225.03 Batt U < p54210[3]
r54225.04 Batt U > p54210[3]
r54225.08 Batt U in hys_rng
p54211[1]
Batt U_act s_src
p54211[2]
p54203 p54211[3] U_batt 1
(55506) +
3 Function diagrams
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_6720_89.vsd Function diagram
- 6720 -
- Battery charging characteristic 25.04.2016 v 1.2 SINAMICS DCP
345
3 Function diagrams
3.9 Closed-loop control
Function diagrams
SINAMICS DCP
346 List Manual (LH21), 05/2016
List Manual (LH21), 05/2016
SINAMICS DCP
Fig. 3-27
6800 – Overview
Voltage 2
+ + + Voltage actual
Voltage 1 value
+ + + measurement
[6820]
+
PWM 1
+
Precontrol
[6830]
+
+
Setpoint
Ramp- +
Set- function
+ --->
Limits Limits 0
+ +
+
Reactor Main current + PWM 2
point generator +
current 1
+
- controller +
[6818]
[6805] [6806] [6808] [6817] [6830]
[6820]
[6810]
[6812]
Residual
current +
PWM 3
controller +
+ Correction
current [6825] [6830]
- controller
+
[6806] [6850]
externally measured
actual current 3 3
+
Current
Set- Voltage actual
controller value
point
3 Function diagrams
[6818] 3 ent
+ + +
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_6800_89.vsd Function diagram
- 6800 -
- Overview 25.04.2016 v 1.2 SINAMICS DCP
347
348
I_set t_RU/t_RD
p55055 (0.050 s)
I_set after RFG [%]
r55070
I_set s_src
p55050
1
(2050[1]) 1 I_set aft lim min [%]
+
[2460.5] 0% r55072
0
0% 0
Enable 1+
ON/OFF1
r00898.00
[2580.8]
I_set min thresh Setp very low
OC / OFF2 I_set sign t_del p55056 (0.40 %) r55075.00
r00898.01 p55065 (100.000 ms)
[2580.8] Setp positive
& r55075.01
OC / OFF3
r00898.02
+ +
[2580.8]
Setp negative
Operation enable r55075.02
r00898.03
[2580.8] stop
a limit has been reached
[6810.7] [6812.8]
[6812.5] [6817.7]
[6820.6] [6825.8]
List Manual (LH21), 05/2016
SINAMICS DCP
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_6805_89.vsd Function diagram
- 6805 -
- Setpoint processing 25.04.2016 v 1.2 SINAMICS DCP
List Manual (LH21), 05/2016
SINAMICS DCP
Fig. 3-29
500 μs
I_set significance
p55060
6806 – Correction current controller
Setpoint
I_set aft lim min [%] I_set reactor [%]
+ --->
r55072 + + r55071 [6810.1]
+ Reactor
[6805.7]
current
Pulses enab
stop a limit has been reached
[2585.8] r00899.11
I_act ext s_src
p55156 [6810.7] [6812.8]
(0) + [6812.5] [6817.7]
[6820.6] [6825.8]
3 Function diagrams
F60058
Par not consistent
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_6806_89.vsd Function diagram
- 6806 -
- Correction current controller 25.04.2016 v 1.2 SINAMICS DCP
349
350
[8048.2] r52051[1]
+ Temp diode D2B
+
+ r55082[7]
Temp PU3
[8048.2] r52051[2]
Maximum
> 45° A60502
Air intake temperature sensor ±2°C
AirIntTmp too high
p55101[0]
Reduce temp_thresh CondA60039 fulfill
r55085.1
SET
+ Q + A60039
(Q=1)
Dyn overload T too high
I_set reactor [%]
[6805.7] r55071 A RESET
& (Q=0)
Q
B>A
B
Priority:
1. RESET
2. SET
basic current 1 Dyn overld I_lim [%]
+
short-time current r55083
0
[6810.4]
DynOverld t_overld
p55090
Dyn overload prof porperties
p55080
of
maximum temperature
List Manual (LH21), 05/2016
Fig. 3-31
500 μs
PU property U
r55600[0...n]
Volt min
p55105 (30.00 V) U_lim t_recovery
p55145 (0.500 s)
3 Function diagrams
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_6810_89.vsd Function diagram
- 6810 -
- Current/power limitation 27.04.2016 v 1.2 SINAMICS DCP
351
352
100% 100%
-100% -100%
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_6812_89.vsd Function diagram
- 6812 -
- Voltage limiting 25.04.2016 v 1.2 SINAMICS DCP
List Manual (LH21), 05/2016
SINAMICS DCP
(52002) 0
Boost current
[6835.2] y Dyn U_lim S2 rch
p55186 (10.00 V) r55125.13
1
Lim S2 U dyn dU Lim I_ re_sp U dyn [%]
U_lim I_react_set [%] x
r55170
r55150 0 Lim S1 U dyn dU Dyn U_lim S1 rch
[6812.7] p55181 (10.00 V) r55125.12
Boost side 1
[6835.2] _
>1
Boost side 2
[6835.2]
3 Function diagrams
(52002) 0
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_6817_89.vsd Function diagram
- 6817 -
- Voltage limitation, dynamic 25.04.2016 v 1.2 SINAMICS DCP
353
354
I_set significance
6818 – Voltage controller
buffering 1 [6818.7]
r55506 [6850.2]
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_6818_89.vsd Function diagram
- 6818 -
- Voltage controller 25.04.2016 v 1.2 SINAMICS DCP
List Manual (LH21), 05/2016
SINAMICS DCP
Fig. 3-35
Pulse frequency
Mn ctr prctr Tv
p55222[0]
Mn ctr prctr Tv
6820 – Main current controller
Discontinuous lim
r55235
y
Act val U S1 [%]
r55501 + x Main ctrl Kp
p55220[0] (0.2000 )
[6850.2]
3 Function diagrams
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_6820_89.vsd Function diagram
- 6820 -
- Main current controller 27.04.2016 v 1.2 SINAMICS DCP
355
356
+ + 1 PU 2 3 ctrl_angle [%]
Control factor +
x
+ + r55251[0]
[6820.7] +
0
I_diff_ctrl_outp [%]
x
+ + r55252[0] p55306 (-200.00)
Mod ctrAng lim neg
-
ActVal I_re PU2avg [%]
y
r55522 [6850.2]
I_diff_ctrl_outp [%]
x
+ + + r55252[1]
ActVal I_re PU1avg [%]
r55521 [6850.2]
List Manual (LH21), 05/2016
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_6825_89.vsd Function diagram
- 6825 -
- Differential current controller 25.04.2016 v 1.2 SINAMICS DCP
List Manual (LH21), 05/2016
SINAMICS DCP
Fig. 3-37
Pulse frequency
Mod indiv br enab PU property f Modulator freq Mod opt step-dn/up Mod f_sw op_mode
p55310 (3 ) r55603 p55320 (100.000 %) p55321 p55322
6830 – Pulse width modulation
Setp positive
[6805.5] r55075.01 Enable direction DC2 --> DC1
& +
Decision
+
Direction
+
PU 2 3 ctrl_angle [%]
[6825.7] r55251[0] + PWM 2 Control signal jumper 2
+
[6850.5]
+
PU 2 3 ctrl_angle [%]
[6825.7] r55251[1] + PWM 3 Control signal jumper 3
Setp negative [6850.5]
& +
[6805.5] r55075.02 Enable direction DC1 --> DC2 +
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_6830_89.vsd Function diagram
- 6830 -
- Pulse width modulation 25.04.2016 v 1.2 SINAMICS DCP
357
358
10
Pre targ_val s_src
r55600[0]
p55352 PU property U Prechrg_cont S2
[2460.5] (2050[2])
r55375.02
DC cont S2
r55375.03 +
Boost side 1
[6817.2] F60501
Prechrg fault det
Boost side 2
[6817.2] Act val U S1 [%]
Boost current r55501 [6850.2]
[6817.2] Act val U S2 [%]
Target voltage r55502 [6850.2]
List Manual (LH21), 05/2016
[6817.2]
SINAMICS DCP
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_6835_89.vsd Function diagram
- 6835 -
- Contactor control/pre-charging 25.04.2016 v 1.2 SINAMICS DCP
List Manual (LH21), 05/2016
SINAMICS DCP
Fig. 3-39
16,000 μs
Fan ON
r55460.00 [1020.7]
Fan ON inv
Dev fan test + 1 r55460.01
6845 – Fan control
p55455
Device fan n
r55480[0]
p55456 (20 %) Device fan n
Dev fan min_speed Fan speed detection
r55480[1]
Device fan n
r55480[2]
F60067
Fault PU temp exc
Dev_fan serv life Dev_fan reset h Fault value = 10
p55471 (30000 h) p55472
Dev_fan h disp
r55470
3 Function diagrams
A60510
Fan end serv life reach
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_6845_89.vsd Function diagram
- Fan control 25.04.2016 v 1.2 SINAMICS DCP
359
360
+/-80%
Act val I_re sum [%] ActVal I offs adj
r55510 + F60503 p55525
PU overcurrent ActVal I gain adj
p55526
ActVal I_react PU1 [%]
Reactor
r55511 + +
current 1
ActVal I_react PU2 [%] Reactor
+
r55512 current 2 +
Current
actual
ActVal I_re PU1avg [%] value
r55531 r55521 +
measurem
ActVal I_re PU2avg [%]
ent
r55532 r55522 +
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_6850_89.vsd Function diagram
- 6850 -
- Actual value acquisition 02.05.2016 v 1.2 SINAMICS DCP
List Manual (LH21), 05/2016
SINAMICS DCP
Fig. 3-41
16,000 μs
F60505
6855 – Power unit monitoring
F60506
PU monit status PU overcurrent 2 signals "Overcurrent has occurred"
r55550
Evaluation + Q S
r55550.8
r55550.9 H1700 Q R +
H1503
F60508
PU monit status PU overtemp
2 signals "Overtemperature has occurred"
r55550
r55550.12
r55550.13
PU F ackn s_src
Being ackn p55551
[2548.6] r02139.00 (2139.0) Reset
_
>1
3 Function diagrams
A>B
o12.0 B
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_6855_89.vsd Function diagram
- 6855 -
- Power unit monitoring 25.04.2016 v 1.2 SINAMICS DCP
361
362
PU property P Options
r55602 r50068[0]
PU property f
r55603
U_rated
r50071
I_rated
r50072
Power unit
List Manual (LH21), 05/2016
SINAMICS DCP
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_6860_89.vsd Function diagram
- 6860 -
- Power unit, properties 25.04.2016 v 1.2 SINAMICS DCP
3 Function diagrams
3.10 Signals and monitoring functions
Function diagrams
SINAMICS DCP
List Manual (LH21), 05/2016 363
364
<2> A...KTY84 (p50490=1), PT100 (p50490=6), NTC thermistor (p50490=7) or PT1000 (p50490=8)
B...PTC thermistor (p50490 = 2,3,4,5)
<3> Lay shielded cable,
with shield connected to ground at both ends
<4> Terminal 54 (sense) is used for compensating Temp_sens ext disp [°C]
cable resistances; for this, the cable from terminal 53 to the r52052
temperature sensor and the cable from connection 54 to the <1>
temperature sensor should be around the same length.
Shutdown temperature
<5> If terminal 54 (sense) is not required, then
0...200 [°C]
terminal 54 must be connected to terminal 55. p50492 (0)
+
Temp_sens ext typ >1 + F60029
p50490 (0) Ext temp high F
Ext temp_fault
CUD Alarm temperature r53130.1
+ +
0...200 [°C]
p50491 (0)
<3> X177.53
0,6 s <2>
Character
A
<3> <4> X177.54 + istic +
>1 + A60032
+
<5> B Ext temp high A
Ext temp_alarm
<3> X177.55 r53130.0
Operating temperature
(dependent on type of PTC
thermistor)
Monitoring
(short-circuit/
F60096
wire break)
Temp_sensor faulty
List Manual (LH21), 05/2016
SINAMICS DCP
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_8030_89.vsd Function diagram
- 8030 -
- Temperature sensor 25.04.2016 v 1.2 SINAMICS DCP
List Manual (LH21), 05/2016
SINAMICS DCP
Fig. 3-44
8,000 μs
Temperature sensor 1 Supply voltage [1020.7]
+ > Schwelle F60067
X202 Fault PU temp exc
=
8048 – Monitoring functions in the device
3 Function diagrams
Note:
The temperature sensors are monitored for wire breaks and F60096 is triggered if necessary.
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_8048_89.vsd Function diagram
- 8048 -
- Monitoring functions in the device 25.04.2016 v 1.2 SINAMICS DCP
365
366
[1020.7]
8054 – Internal diagnostics
F60065
Properties r50812 Mainb calib_values
SW update TMS320 failed
of electronics module F60163 F60165
CalVal mainb incor SW upd mainb fail
Internal communication
r50810 Mainb serial no. monitoring
F60523
r50811 Mainb part no. Mainb I2C bus error
F60525
Mainb watchdog err
A60526
r50060[0] Device version ext Mainb PwrSup sw-off A
r50060[1] Device version int
Int diag
r50060[2] DSAC Bootloader r50827[0..1]
r50060[3] BIOS version
r50060[4] Config EEPROM
r50060[5] Base system A60098
A SysUtil too high
r50060[6] DC/DC converter
Monitoring of
Software version r50060[7] TMS version
computing time capacity F60099
r50060[8] TMS image utilization F SysUtil too high
r50060[9] TMS bootloader TMS320 util [%]
r50060[10] TMS bootloader im r50820[0...1]
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_8054_89.vsd Function diagram
- 8054 -
- Diagnostics, internal 25.04.2016 v 1.2 SINAMICS DCP
List Manual (LH21), 05/2016
SINAMICS DCP
Fig. 3-46
8,000 μs
Diagnostic LEDs [1020.7]
orange Initialization
Mainb LED test
p54985 (0 )
green 0.5 Operation, pulses disabled
Hz
3 Function diagrams
red 2.0 Hz Overvoltage range
p54993 (1 )
EEPROM write_prot
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_8055_89.vsd Function diagram
- 8055 -
- General diagnostics 25.04.2016 v 1.2 SINAMICS DCP
367
368
[1020.7]
0 ... no action
1 ... trigger immediately \USER\SINAMICS\
8056 – Diagnostic memory
Sampling values:
Memory
- Reactor currents
200 ms long Diag_mem copy file
- Voltage side 1 p50832
- Voltage side 2
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_8056_89.vsd Function diagram
- 8056 -
- Diagnostic memory 25.04.2016 v 1.2 SINAMICS DCP
3 Function diagrams
3.11 Faults and alarms
Function diagrams
SINAMICS DCP
List Manual (LH21), 05/2016 369
370
Fault code Fault value Fault time Fault time Fault Component Diagnostic
"active" "inactive" drive object number attributes
initiating fault fault
+ Fault times
III Counter
16 bits
32 bit counter, + + + Incoming
r0945[0] r0949[0] [I32] r0948[0] [ms] r2109[0] [ms] fault
freewheeling Fault 1 r3115[0] r3120[0] r3122[0] Fault cases qty
r0947[0] r2133[0] [Float] r2130[0] [d] r2136[0] [d] III +
[8065.1] p00952
Operating time r0945[1] r0949[1] [I32] r0948[1] [ms] r2109[1] [ms] RESET
Fault 2 r3115[1] r3120[1] r3122[1]
r0947[1] r2133[1] [Float] r2130[1] [d] r2136[1] [d]
p0952 = 0:
Current
Faults ackn DO
fault RESET + Fault buffer is cleared
p3981 p03981 Clear fault buffer
p3981 r0945 =0
r0947 =0 p2147 (CU) = 1
r0945[7] r0949[7] [I32] r0948[7] [ms] r2109[7] [ms]
>1
Fault 8 r3115[7] r3120[7] r3122[7] r0948 =0 Automatic
POWER ON r0947[7] r2133[7] [Float] r2130[7] [d] r2136[7] [d] r0949 =0
>1 <1> <2>
Faults r2109 =0
p2102...p2105 Ackn fault acknowledg r2130 =0
p2102...p2105 ement r0945[8] r0949[8] [I32] r0948[8] [ms] r2109[8] [ms]
[2546.1] r02138.07 Fault 1 r3115[8] r3120[8] r3122[8] r2133 =0
r0947[8] r2133[8] [Float] r2130[8] [d] r2136[8] [d]
r2136 =0
r0945[9] r0949[9] [I32] r0948[9] [ms] r2109[9] [ms] r3115 =0
Fault 2 r3115[9] r3120[9] r3122[9]
1. r0947[9] r2133[9] [Float] r2130[9] [d] r2136[9] [d] r3120 =0
Acknowledg r3122 =0
ed
p2106 Ext fault 1 eff 16 bit counter,
fault
p2106r02138.13
[2546.3] Incoming fault freewheeling
Fault buff change
r0945[15] r0949[15] [I32] r0948[15] [ms] r2109[15] [ms] Outgoing fault
Fault 8 r3115[15] r3120[15] r3122[15] >1 + III r00944
r0947[15] r2133[15] [Float] r2130[15] [d] r2136[15] [d] Fault
p2107 Ext fault 2 eff RESET
p2107r02138.14
[2546.3] acknowledged
r0945[56] r0949[56] [I32] r0948[56] [ms] r2109[56] [ms]
Fault 1 r3115[56] r3120[56] r3122[56] POWER ON
p2108, r0947[56] r2133[56] [Float] r2130[56] [d] r2136[56] [d]
p3110...p3112
p2108, Ext fault 3 eff r0945[57] r0949[57] [I32] r0948[57] [ms] r2109[57] [ms]
p3110...p3112 7. Fault 2 r3115[57] r3120[57] r3122[57] Fault buffer change [8065.6]
[2546.1] r02138.15 r0947[57] r2133[57] [Float] r2130[57] [d] r2136[57] [d]
Acknowledg
ed
fault Msg ZSW global
[oldest] Group fault pres
r03114.10
r0945[63] r0949[63] [I32] r0948[63] [ms] r2109[63] [ms]
Fault 8 r3115[63] r3120[63] r3122[63]
List Manual (LH21), 05/2016
<1> This fault is overwritten by "more recent" faults (except "safety faults"). Fault reactions to sequence control [2610]
<2> Refer to "Fault buffer - Saving on switching off" in the List Manual. Fault pres
<3> The buffer parameters are cyclically updated in the background (refer to status signal in r2139). r02139.03 [5811.1, 5838.1]
SINAMICS DCP
1 2 3 4 5 6 7 8
DO: All Objects fp_8060_89.vsd Function diagram
- 8060 -
- Fault buffer 03.06.2014 v 1.2 SINAMICS DCP
List Manual (LH21), 05/2016
SINAMICS DCP
Fig. 3-49
Actual alarm code
r02132 0 = "No alarm present" Background
<1>
[1020.7]
Alarm code Alarm value Alarm time Alarm time Component Diagnostic
"active" "inactive" number attributes
warning warning
Operating time
8065 – Alarm buffer
16 bit counter,
freewheeling
Incoming alarm Alrm buff changed
r02110
Alarm number Outgoing alarm >1 + III r02121
RESET
3 Function diagrams
other drive objects RESET
<1> The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
POWER ON
1 2 3 4 5 6 7 8
DO: All Objects fp_8065_89.vsd Function diagram
- 8065 -
- Alarm buffer 03.06.2014 v 1.2 SINAMICS DCP
371
372
[1020.7]
8070 – Fault/alarm trigger word (r2129)
0. Message present
[0] 0. Fault/alarm code r02129.00
1. Message present
[1] 1. Fault/alarm code r02129.01
1 2 3 4 5 6 7 8
DO: All Objects fp_8070_89.vsd Function diagram
- 8070 -
- Fault/alarm trigger word (r2129) 03.06.2014 v 1.2 SINAMICS DCP
List Manual (LH21), 05/2016
SINAMICS DCP
Fig. 3-51
Background
<1> <1>
[1020.7]
Change fault reaction for a maximum of 20 faults Change fault message type <==> Alarm for a maximum of 20 faults/alarms
[0] 0. Fault code [0] Fault reaction 0 = NONE [0] 0. Fault/alarm code [0] Fault/alarm type 1 = Fault
[1] 1. Fault code [1] Fault reaction 1 = OFF1 [1] 1. Fault/alarm code [1] Fault/alarm type 2 = Alarm
3 = No message
2 = OFF2
3 = OFF3
reserved
reserved
reserved
[19] 19. Fault code [19] Fault reaction reserved [19] 19. Fault/alarm code [19] Fault/alarm type
<1>
Change acknowledge mode for a maximum of 20 faults
p02126 p02127
[0] 0. Fault code [0] Acknowledge mode 1 = Acknowledgement only using POWER ON.
[1] 1. Fault code [1] Acknowledge mode 2 = IMMEDIATE acknowledgment after removal of fault cause.
3 = Acknowledgement only for PULSE INHIBIT
1 2 3 4 5 6 7 8
DO: All Objects fp_8075_89.vsd Function diagram
- 8075 -
- Fault/alarm configuration 03.06.2014 v 1.2 SINAMICS DCP
373
3 Function diagrams
3.12 Data sets
Function diagrams
SINAMICS DCP
374 List Manual (LH21), 05/2016
List Manual (LH21), 05/2016
SINAMICS DCP
Fig. 3-52
Not relevant
Example:
Switching Command Data Sets [1020.7]
CDS0 --> CDS1
8560 – Command Data Sets (CDS)
t t
CDS selected
+ r00836
t CDS count
p00170 (2) r00836.0
CDS0
CDS effective
+ r00050
r00050.0
3 Function diagrams
3.12 Data sets
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_8560_89.VSD Function diagram
- Command Data Sets (CDS) 03.06.2014 v 1.2 SINAMICS DCP
375
3 Function diagrams
3.13 Communication between devices
Function diagrams
SINAMICS DCP
376 List Manual (LH21), 05/2016
List Manual (LH21), 05/2016
SINAMICS DCP
Fig. 3-53
500 μs
[1020.7]
CUD
9350 – Paralleling interface
X165
PU topo pos
p51800 (0)
Monitoring
r51809 Par_IF diag info
Telegr mon t_fail
p51807
r51810 Par_IF act disp
3 Function diagrams
r51811 Par_IF CAN diag
1 2 3 4 5 6 7 8
DO: DCP_CTRL fp_9350_89.VSD Function diagram
- Parallel connection interface 25.04.2016 v 1.2 SINAMICS DCP
377
3 Function diagrams
3.14 Basic Operator Panel 20 (BOP20)
Function diagrams
SINAMICS DCP
378 List Manual (LH21), 05/2016
List Manual (LH21), 05/2016
SINAMICS DCP
Interconnection
[1020.7]
Signal Meaning
parameter
9912 – Control word interconnection
STW BOP.3 -
STW BOP.4 -
STW BOP.5 -
STW BOP.6 -
STW BOP.8 -
STW BOP.9 -
STW BOP.10 -
STW BOP.11 -
STW BOP.13 -
STW BOP.14 -
3 Function diagrams
STW BOP.15 -
<1> The BICO interconnection is just an example and may be changed by the user.
1 2 3 4 5 6 7 8
DO: CU_DCP fp_9912_89.vsd Function diagram
- Control word interconnection 03.06.2014 v 1.2 SINAMICS DCP
379
3 Function diagrams
3.14 Basic Operator Panel 20 (BOP20)
SINAMICS DCP
380 List Manual (LH21), 05/2016
Faults and alarms 4
Content
SINAMICS DCP
List Manual (LH21), 05/2016 381
4 Faults and alarms
4.1 Overview of faults and alarms
Type Description
SINAMICS DCP
382 List Manual (LH21), 05/2016
4 Faults and alarms
4.1 Overview of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 383
4 Faults and alarms
4.1 Overview of faults and alarms
- - - - - - - - - - - - Start of example - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - End of example - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
Note
You can change the default properties of a fault or alarm by setting parameters.
References: SINAMICS DCP operating instructions
The "List of faults and alarms" (Page 386) supplies information referred to the properties of a
message set as default. If the properties of a specific message are changed, the corresponding
information may have to be modified in this list.
SINAMICS DCP
384 List Manual (LH21), 05/2016
4 Faults and alarms
4.1 Overview of faults and alarms
Drive object:
Each message (fault/alarm) specifies the drive object in which it can be found.
A message can belong to either one, several, or all drive objects.
Cause:
Describes the possible causes of the fault or alarm. A fault or alarm value can also be specified
(optional).
Fault value (r0949, format):
The fault value is entered in the fault buffer in r0949[0...63] and specifies additional, more
precise information about a fault.
Alarm value (r2124, format):
The alarm value specifies additional, more precise information about an alarm.
The alarm value is entered in the alarm buffer in r2124[0...7] and specifies additional, more
precise information about an alarm.
Remedy:
Provides a general description of the methods available for eliminating the cause of the active
fault/alarm.
WARNING
Service and maintenance personnel are responsible for choosing a suitable method for
eliminating the cause of faults on a case-for-case basis.
SINAMICS DCP
List Manual (LH21), 05/2016 385
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
386 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 387
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
388 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 389
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
390 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 391
4 Faults and alarms
4.2 List of faults and alarms
Remedy: - If you have saved the project data using the commissioning software, download the project again. Save using the
function "Copy RAM to ROM" or with p0977 = 1 so that all of the parameter files are again completely written to the
non-volatile memory.
- replace the memory card or Control Unit.
Re byte 2 = 255:
- Correct the drive object type (see p0107).
F01039 (A) ACX: Writing to the parameter back-up file was unsuccessful
Drive object: All objects
Cause: Writing to at least one parameter back-up file PSxxxyyy.*** in the non-volatile memory was unsuccessful.
- In the directory /USER/SINAMICS/DATA/ at least one parameter back-up file PSxxxyyy.*** has the "read only" file
attribute and cannot be overwritten.
- There is not sufficient free memory space available.
- The non-volatile memory is defective and cannot be written to.
Fault value (r0949, interpret hexadecimal):
dcba hex
a = yyy in the file names PSxxxyyy.***
a = 000 --> consistency back-up file
a = 001 ... 062 --> drive object number
a = 070 --> FEPROM.BIN
a = 080 --> DEL4BOOT.TXT
a = 099 --> PROFIBUS parameter back-up file
b = xxx in the file names PSxxxyyy.***
b = 000 --> data save started with p0977 = 1 or p0971 = 1
b = 010 --> data save started with p0977 = 10
b = 011 --> data save started with p0977 = 11
b = 012 --> data save started with p0977 = 12
d, c:
Only for internal Siemens troubleshooting.
Remedy: - check the file attribute of the files (PSxxxyyy.***, CAxxxyyy.***, CCxxxyyy.***) and, if required, change from "read
only" to "writeable".
- check the free memory space in the non-volatile memory. Approx. 80 kbyte of free memory space is required for
every drive object in the system.
- replace the memory card or Control Unit.
SINAMICS DCP
392 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 393
4 Faults and alarms
4.2 List of faults and alarms
126: Write access only in the commissioning state, device ready (device: p0009 = 0).
127: Write access only in the commissioning state, device (device: p0009 not equal to 0).
129: Parameter may not be written in download.
130: Transfer of the master control is inhibited via binector input p0806.
131: Required BICO interconnection not possible because BICO output does not supply floating value
132: Free BICO interconnection inhibited via p0922.
133: Access method not defined.
200: Below the valid values.
201: Above the valid values.
202: Cannot be accessed from the Basic Operator Panel (BOP).
203: Cannot be read from the Basic Operator Panel (BOP).
204: Write access not permitted.
Remedy: - enter the correct value in the specified parameter.
- identify the parameter that restricts the limits of the specified parameter.
SINAMICS DCP
394 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
F01055 CU: Internal error (SYNO of port and application not identical)
Drive object: DCP_CTRL, TM150
Cause: All applications that operate with slaves at one port must be derived from the same SYNO clock cycle.
The first application whose registration (log-on) connects a slave to a port defines the SYNO clock cycle that will be
used as basis for the port.
SINAMICS DCP
List Manual (LH21), 05/2016 395
4 Faults and alarms
4.2 List of faults and alarms
F01056 CU: Internal error (clock cycle of parameter group already assigned differently)
Drive object: DCP_CTRL, TM150
Cause: The requested parameter group (IREG, NREG, ...) is already being used in a different clock cycle.
Fault value (r0949, interpret hexadecimal):
Method ID.
Note:
Only for internal Siemens troubleshooting.
Remedy: Contact the Hotline.
F01057 CU: Internal error (different DRIVE-CLiQ type for the slave)
Drive object: DCP_CTRL, TM150
Cause: The requested DRIVE-CLiQ type (hps_ps, hps_enc, ...) has been specified differently for the same slave component.
Fault value (r0949, interpret hexadecimal):
Method ID.
Note:
Only for internal Siemens troubleshooting.
Remedy: Contact the Hotline.
SINAMICS DCP
396 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 397
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
398 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 399
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
400 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
Remedy: - check the sampling time setting (p0112, p0115, p4099, p9500, p9511).
- contact the Hotline.
F01222 CU: Basic clock cycle too low (computing time for communication not available)
Drive object: DCP_CTRL, TM150
Cause: A time slice has not been defined that fulfills the requirements.
The port cannot be correctly operated as the alternating cyclic clock cycle cannot be maintained.
Fault value (r0949, interpret hexadecimal):
Method ID.
Note:
Only for internal Siemens troubleshooting.
Remedy: Contact the Hotline.
SINAMICS DCP
List Manual (LH21), 05/2016 401
4 Faults and alarms
4.2 List of faults and alarms
41: A chassis unit was identified on the DRIVE-CLiQ line as a node. Further, the highest common denominator of the
sampling times of all of the nodes connected to the line is less than 250 µs.
42: An Active Line Module was identified on the DRIVE-CLiQ line as a node. Further, the highest common
denominator of the sampling times of all of the nodes connected to the line is less than 125 µs.
43: A Voltage Sensing Module (VSM) was identified on the DRIVE-CLiQ line as a node. Further, the highest common
denominator of the sampling times of all of the nodes connected to the line is not equal to the current controller
sampling time of the drive object of the VSM.
44: The highest common denominator of the sampling times of all of the components connected to the DRIVE-CLiQ
line is not the same for all components of this drive object (e.g. there are components on different DRIVE-CLiQ lines
on which different highest common denominators are generated).
45: A chassis parallel unit was identified on the DRIVE-CLiQ line as a node. Further, the highest common
denominator of the sampling times of all of the nodes connected to the line is less than 162.5 µs or 187.5 µs (for a 2
or 3x parallel connection).
46: A node has been identified on the DRIVE-CLiQ line whose sampling time is not a multiple of the lowest sampling
time on this line.
52: Nodes have been identified on the DRIVE-CLiQ line whose highest common denominator of the sampling times
is less than 31.25 µs.
54: Nodes have been identified on the DRIVE-CLiQ line whose highest common denominator of the sampling times
is less than 62.5 µs.
56: Nodes have been identified on the DRIVE-CLiQ line whose highest common denominator of the sampling times
is less than 125 µs.
58: Nodes have been identified on the DRIVE-CLiQ line whose highest common denominator of the sampling times
is less than 250 µs.
99: Inconsistency of cross drive objects detected.
116: Recommended clock cycle in r0116[0...1].
General note:
The topology rules should be noted when connecting up DRIVE-CLiQ (refer to the appropriate product
documentation).
The parameters of the sampling times can also be changed with automatic calculations.
Example for highest common denominator: 125 s, 125 µs, 62.5 µs --> 62.5 µs
Remedy: - check the DRIVE-CLiQ cables.
- set a valid sampling time.
See also: p0115, p4099
SINAMICS DCP
402 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 403
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
404 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
Remedy: The alarm automatically disappears again with the following actions:
- de-activate the drive object involved (p0105 = 0).
- de-activate the components involved (p0125 = 0, p0145 = 0, p0155 = 0, p0165 = 0).
- re-insert the components involved.
See also: p0105 (Activate/de-activate drive object)
SINAMICS DCP
List Manual (LH21), 05/2016 405
4 Faults and alarms
4.2 List of faults and alarms
- only 2 partial lists are permitted. After the second 0, all values must be 0.
- dummy drive object numbers (255) are only permitted in the first partial list.
SINAMICS DCP
406 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 407
4 Faults and alarms
4.2 List of faults and alarms
aa = 07 hex = 7 dec:
The actual topology contains an illegal combination of components.
- bb = 01 hex = 1 dec: Active Line Module (ALM) and Basic Line Module (BLM).
- bb = 02 hex = 2 dec: Active Line Module (ALM) and Smart Line Module (SLM).
- bb = 03 hex = 3 dec: SIMOTION control (e.g. SIMOTION D445) and SINUMERIK component (e.g. NX15).
- bb = 04 hex = 4 dec: SINUMERIK control (e.g. SINUMERIK 730.net) and SIMOTION component (e.g. CX32).
- cccc: Not used.
Note:
Connection type and connection number are described in F01375.
See also: p0097 (Select drive object type), r0098 (Actual device topology), p0099 (Device target topology)
Remedy: - adapt the output topology to the permissible requirements.
- carry out commissioning using the commissioning software.
- for motors with DRIVE-CLiQ, connect the power and DRIVE-CLiQ cable to the same Motor Module (Single Motor
Module: DRIVE-CLiQ at X202, Double Motor Module: DRIVE-CLiQ from motor 1 (X1) to X202, from motor 2 (X2) to
X203).
Re aa = 06 hex = 6 dec and bb = 01 hex = 1 dec:
Correct the order number when commissioning using the commissioning software.
See also: p0097 (Select drive object type), r0098 (Actual device topology), p0099 (Device target topology)
SINAMICS DCP
408 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
6yy:
Internal buffer overflow for receive data of a DRIVE-CLiQ connection.
7yy:
Internal buffer overflow for send data of a DRIVE-CLiQ connection.
8yy:
The component clock cycles cannot be combined with one another
900:
The lowest common multiple of the clock cycles in the system is too high to be determined.
901:
The lowest common multiple of the clock cycles in the system cannot be generated with the hardware.
Remedy: - check the DRIVE-CLiQ wiring.
- Reduce the number of components on the DRIVE-CLiQ line involved and distribute these to other DRIVE-CLiQ
sockets of the Control Unit. This means that communication is uniformly distributed over several lines.
Re fault value = 1yy - 4yy in addition:
- increase the sampling times (p0112, p0115, p4099). If necessary, for DCC or FBLOCKS, change the assignment of
the run-time group (p21000, p20000) so that the sampling time (r21001, r20001) is increased.
- if necessary, reduce the number of cyclically calculated blocks (DCC) and/or function blocks (FBLOCKS).
- reduce the function modules (r0108).
- establish the conditions for operation with a current controller sampling time of 31.25 µs (at the DRIVE-CLiQ line,
only operate Motor Modules and Sensor Modules with this sampling time and only use a permitted Sensor Module
(e.g. SMC20, this means a 3 at the last position of the order number)).
- For an NX, the corresponding Sensor Module for a possibly existing second measuring system should be
connected to a free DRIVE-CLiQ socket of the NX.
Re fault value = 8yy in addition:
- check the clock cycles settings (p0112, p0115, p4099). Clock cycles on a DRIVE-CLiQ line must be perfect integer
multiples of one another. As clock cycle on a line, all clock cycles of all drive objects in the previously mentioned
parameters apply, which have components on the line involved.
Re fault value = 9yy in addition:
- check the clock cycles settings (p0112, p0115, p4099). The lower the numerical value difference between two clock
cycles, the higher the lowest common multiple. This behavior has a significantly stronger influence, the higher the
numerical values of the clock cycles.
SINAMICS DCP
List Manual (LH21), 05/2016 409
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
410 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 411
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
412 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
12: Only certain Motor Modules may be used for expansion axes.
13: For an S120 Combi with 3 axes, nothing must be connected at the DRIVE-CLiQ Hub Module at X503.
Remedy: Evaluate the alarm value and ensure compliance with the corresponding topology rule(s).
SINAMICS DCP
List Manual (LH21), 05/2016 413
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
414 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
Note:
The component is described in dd, cc and bb, where the component involved is incorrectly inserted.
Component class and connection number are described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy: Adapting topologies:
- insert the components involved at the right connection (correct the actual topology).
- adapt the project/parameterization in the commissioning software (correct the target topology).
- automatically remove the topology error (p9904).
Note:
Under "Topology --> Topology view" the commissioning software where relevant offers improved diagnostics
capability (e.g. setpoint/actual value comparison).
SINAMICS DCP
List Manual (LH21), 05/2016 415
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
416 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
Note:
The component class of the additional component is contained in bb.
The component is described in dd, cc and aa, where the additional component is inserted.
Component class and connection number are described in F01375.
Remedy: Adapting topologies:
- remove the additional component (correct the actual topology).
- adapt the project/parameterization in the commissioning software (correct the target topology).
Note:
Under "Topology --> Topology view" the commissioning software where relevant offers improved diagnostics
capability (e.g. setpoint/actual value comparison).
SINAMICS DCP
List Manual (LH21), 05/2016 417
4 Faults and alarms
4.2 List of faults and alarms
Note:
The component class is described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy: Adapting topologies:
- change over the actual topology to match the target topology.
- download the target topology that matches the actual topology (commissioning software).
Re byte cc:
cc = 1 --> can be acknowledged using p9904 or p9905.
cc > 1 --> can be acknowledged using p9905 and can be de-activated using p9906 or p9907/p9908.
Note:
Under "Topology --> Topology view" the commissioning software where relevant offers improved diagnostics
capability (e.g. setpoint/actual value comparison).
SINAMICS DCP
418 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 419
4 Faults and alarms
4.2 List of faults and alarms
Note:
The component is described in dd, cc and bb, where the component has not been inserted.
Component class and connection number are described in F01375.
Remedy: Adapting topologies:
- insert the components involved at the right connection (correct the actual topology).
- adapt the project/parameterization in the commissioning software (correct the target topology).
Check the hardware:
- check the 24 V supply voltage.
- check DRIVE-CLiQ cables for interruption and contact problems.
- check that the component is working properly.
Note:
Under "Topology --> Topology view" the commissioning software where relevant offers improved diagnostics
capability (e.g. setpoint/actual value comparison).
SINAMICS DCP
420 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 421
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
422 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 423
4 Faults and alarms
4.2 List of faults and alarms
Example 2:
BICO output with voltage normalized unit in drive object 1 (DO1), BICO input with voltage normalized unit in drive
object 2 (DO2). The reference values for voltage (p2001) of the two drive objects have different values. This means
that the factor p2001(DO1)/p2001(DO2) is calculated between the BICO output and the BICO input.
p2001: contains the reference value for voltage, drive objects 1, 2
Fault value (r0949, interpret decimal):
Parameter number of the BICO input (signal sink).
Remedy: Not necessary.
F01515 (A) BICO: Writing to parameter not permitted as the master control is active
Drive object: DCP_CTRL
Cause: When changing the number of CDS or when copying from CDS, the master control is active.
Remedy: If required, return the master control and repeat the operation.
SINAMICS DCP
424 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 425
4 Faults and alarms
4.2 List of faults and alarms
Remedy: Check the bus configuration on the master and the slave sides.
Re alarm value = 1, 2:
- Check the list of the drive objects with process data exchange (p0978).
Note:
With p0978[x] = 0, all of the following drive objects in the list are excluded from the process data exchange.
Re alarm value = 2:
- Check the number of data words for output and input to a drive object.
Re alarm value = 211:
- Ensure offline version <= online version.
Re alarm value = 223, 500:
- Check the setting in p8839 and p8815.
- Check for inserted but not configured CBE20.
- Ensure that only one PZD interface is operated in clock synchronism or with PROFIsafe.
Re alarm value = 255:
- Check configured drive objects.
Re alarm value = 501:
- Check the set PROFIsafe address (p9610).
Re alarm value = 502:
- Check the set PROFIsafe telegram (p60022, p9611).
SINAMICS DCP
426 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
Remedy: Restore the bus connection and set the controller to RUN.
Note regarding PROFIBUS slave redundancy:
For operation on a Y link, it must be ensured that "DP alarm mode = DPV1" is set in the slave parameterization.
F01911 (N, A) PB/PN clock cycle synchronous operation clock cycle failure
Drive object: DCP_CTRL, TM150, TM15DI_DO, TM31
Cause: The global control telegram to synchronize the clock cycles has failed - in cyclic operation - for several DP clock
cycles or has violated the time grid specified in the parameterizing telegram over several consecutive DP clock
cycles (refer to the bus cycle time, Tdp and Tpllw).
Remedy: - check the physical bus configuration (cable, connector, terminating resistor, shielding, etc.).
- check whether communication was briefly or permanently interrupted.
- check the bus and controller for utilization level (e.g. bus cycle time Tdp was set too short).
PB: PROFIBUS
PN: PROFINET
F01915 (N, A) PB/PN clock cycle synchronous operation sign-of-life failure drive object 1
Drive object: All objects
Cause: Group display for problems with the sign-of-life of the master (clock-cycle synchronous operation) on the drive object
1 (Control Unit).
For central measurements, synchronism with the central master is lost.
Remedy: Note:
PB: PROFIBUS
PN: PROFINET
A01930 PB/PN current controller sampling time clock cycle synch. not equal
Drive object: All objects
Cause: The current controller sampling time of all drives must be set the same for the clock cycle synchronous operation.
Alarm value (r2124, interpret decimal):
Number of the drive object with different current controller sampling time.
Remedy: Set current controller sampling time to identical values (p0115[0]).
Note:
PB: PROFIBUS
PN: PROFINET
See also: p0115
SINAMICS DCP
List Manual (LH21), 05/2016 427
4 Faults and alarms
4.2 List of faults and alarms
A01931 PB/PN speed controller sampling time clock cycle synch. not equal
Drive object: All objects
Cause: The speed controller sampling time of all drives must be set the same for the clock cycle synchronous operation.
Alarm value (r2124, interpret decimal):
Number of the drive object with the different speed controller sampling time.
Remedy: Set the speed controller sampling times to identical values (p0115[1]).
Note:
PB: PROFIBUS
PN: PROFINET
See also: p0115
A01941 PB/PN clock cycle signal missing when establishing bus communication
Drive object: All objects
Cause: The bus is in the data exchange state and clock synchronous operation has been selected using the parameterizing
telegram. The global control telegram for synchronization is not being received.
Remedy: Check the master application and bus configuration.
Note:
PB: PROFIBUS
PN: PROFINET
A01943 PB/PN clock cycle signal error when establishing bus communication
Drive object: All objects
Cause: The bus is in the data exchange state and clock synchronous operation has been selected using the parameterizing
telegram.
The global control telegram for synchronization is being irregularly received.
-.the master is sending an irregular global control telegram.
- the master is using another clock synchronous DP clock cycle than was transferred to the slave in the
parameterizing telegram.
Remedy: - check the master application and bus configuration.
- check the consistency between the clock cycle input when configuring the slave and clock cycle setting at the
master.
Note:
PB: PROFIBUS
PN: PROFINET
SINAMICS DCP
428 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 429
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
430 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
Remedy: Use the existing drive object with the corresponding number.
Note:
The alarm is reset as follows:
- remove the cause of this alarm.
- restart the function generator.
A02010 Function generator: Speed setpoint from the drive is not zero
Drive object: All objects
Cause: The speed setpoint of a drive selected for connection is greater than the value for the standstill detection set using
p1226.
Remedy: For all of the drives specified for connection, set the speed setpoints to zero.
Note:
The alarm is reset as follows:
- remove the cause of this alarm.
- restart the function generator.
SINAMICS DCP
List Manual (LH21), 05/2016 431
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
432 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 433
4 Faults and alarms
4.2 List of faults and alarms
A02058 Trace: Time slice clock cycle for endless trace not valid
Drive object: All objects
Cause: The selected time slice clock cycle cannot be used for the endless trace
See also: p4723 (Trace time slice cycle)
Remedy: Enter the clock cycle of an existing time slice with a cycle time >= 2 ms for up to 4 recording channels or >= 4 ms
from 5 recording channels per trace.
The existing time slices can be read out via p7901.
SINAMICS DCP
434 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
A02059 Trace: Time slice clock cycle for 2 x 8 recording channels not valid
Drive object: All objects
Cause: The selected time slice clock cycle cannot be used for more than 4 recording channels.
See also: p4723 (Trace time slice cycle)
Remedy: Enter the clock cycle of an existing time slice with a cycle time >= 4 ms or reduce the number of recording channels
to 4 per trace.
The existing time slices can be read out via p7901.
SINAMICS DCP
List Manual (LH21), 05/2016 435
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
436 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 437
4 Faults and alarms
4.2 List of faults and alarms
Remedy: - change the configuration on this Control Unit (e.g. fewer drives, function modules, data sets, OA applications,
blocks, etc).
- use an additional Control Unit.
Note:
OA: Open Architecture
SINAMICS DCP
438 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 439
4 Faults and alarms
4.2 List of faults and alarms
A03550 TM: Speed setpoint filter natural frequency > Shannon frequency
Drive object: CU_DCP, TM150, TM15DI_DO, TM31
Cause: The natural filter frequency of the speed setpoint filter (p1417) is greater than or equal to the Shannon frequency.
The Shannon frequency is calculated according to the following formula:
0.5 / p4099[3]
Remedy: Reduce the natural frequency of the speed setpoint filter (PT2 low pass) (p1417).
SINAMICS DCP
440 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
36: Check, writing to a parameter unsuccessful, parameter can only be read, not available, incorrect data type, value
range or assignment incorrect.
37: Source parameter for a BICO interconnection was not able to be determined.
38: An index was set for a non-indexed (or CDS-dependent) parameter.
39: No index was set for an indexed parameter.
41: A bit operation is only permissible for parameters with the parameter format DISPLAY_BIN.
42: A value not equal to 0 or 1 was set for a BitOperation.
43: Reading the parameter to be changed by the BitOperation was unsuccessful.
51: Factory setting for DEVICE may only be executed on the DEVICE.
61: The setting of a value was unsuccessful.
Remedy: - check the parameter involved.
- check the macro file and BICO interconnection.
See also: p0015, p0700, p1000 (Macro Connector Inputs (CI) for speed setpoints), p1500 (Macro Connector Inputs
(CI) for torque setpoints)
A07089 Changing over units: Function module activation is blocked because the units have
been changed over
Drive object: CU_DCP, TM150, TM15DI_DO, TM31
Cause: An attempt was made to activate a function module. This is not permissible if the units have already been changed
over.
Remedy: Restore units that have been changed over to the factory setting.
F07110 Drive: Sampling times and basic clock cycle do not match
Drive object: All objects
Cause: The parameterized sampling times do not match the basic clock cycle.
Fault value (r0949, interpret decimal):
The fault value specifies the parameter involved.
See also: r0110, r0111, p0115
Remedy: Enter the current controller sampling times so that they are identical to the basic clock cycle, e.g. by selecting p0112.
Note which basic clock cycle is selected in p0111.
The sampling times in p0115 can only be changed manually in the sampling times pre-setting "Expert" (p0112).
See also: r0110, r0111, p0112, p0115
SINAMICS DCP
List Manual (LH21), 05/2016 441
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
442 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
Remedy: The index of the encoder data set associated with the drive data set should be entered into p0187 (1st encoder),
p0188 (2nd encoder) and p0189 (3rd encoder).
SINAMICS DCP
List Manual (LH21), 05/2016 443
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
444 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 445
4 Faults and alarms
4.2 List of faults and alarms
4: Setting data for synchronization not accepted. For more information, see A01902.
5: Cyclic operation not active.
17: CBE20 Shared Device: Configuration of the F-CPU has been changed.
223: Illegal clock synchronization for the PZD interface set in p8815[0].
500: Illegal PROFIsafe configuration for the interface set in p8815[1].
501: PROFIsafe parameter error (e.g. F_dest).
503: PROFIsafe connection is rejected as long as there is no isochronous connection (p8969).
Additional values:
Only for internal Siemens troubleshooting.
Remedy: Check the receive configuration data.
Re alarm value = 1, 2:
- Check the list of the drive objects with process data exchange (p0978). With p0978[x] = 0, all of the following drive
objects in the list are excluded from the process data exchange.
Re alarm value = 2:
- Check the number of data words for output and input to a drive object.
Re alarm value = 17:
- CBE20 Shared Device: Unplug/plug A-CPU.
Re alarm value = 223, 500:
- Check the setting in p8839 and p8815.
- Ensure that only one PZD interface is operated in clock synchronism or with PROFIsafe.
Re alarm value = 501:
- Check the set PROFIsafe address (p9610).
SINAMICS DCP
446 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 447
4 Faults and alarms
4.2 List of faults and alarms
4:
An internal error occurred when checking the license.
Remedy: Re alarm value = 0:
Additional licenses are required and these must be activated (p9920, p9921).
Re alarm value = 1:
With the system powered down, re-insert the memory card that matches the system.
Re alarm value = 2:
Enter and activate the license key (p9920, p9921).
Re alarm value = 3:
Compare the license key (p9920) entered with the license key on the certificate of license.
Re-enter the license key and activate (p9920, p9921).
Re alarm value = 4:
- carry out a POWER ON.
- upgrade firmware to later version.
- contact the Hotline.
SINAMICS DCP
448 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
Note:
In general, the copy protection can only be changed when know-how protection is deactivated.
KHP: Know-How Protection
See also: p3981 (Faults acknowledge drive object)
SINAMICS DCP
List Manual (LH21), 05/2016 449
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
450 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 451
4 Faults and alarms
4.2 List of faults and alarms
4 (= 04 hex):
The length of the receive telegram does not match the receive list.
5 (= 05 hex):
The type of the receive telegram does not match the receive list.
6 (= 06 hex):
The address of the power unit in the telegram and in the receive list do not match.
9 (= 09 hex):
The error bit in the receive telegram is set.
16 (= 10 hex):
The receive telegram is too early.
17 (= 11 hex):
CRC error and the receive telegram is too early.
18 (= 12 hex):
The telegram is shorter than that specified in the length byte or in the receive list and the receive telegram is too
early.
19 (= 13 hex):
The telegram is longer than that specified in the length byte or in the receive list and the receive telegram is too early.
20 (= 14 hex):
The length of the receive telegram does not match the receive list and the receive telegram is too early.
21 (= 15 hex):
The type of the receive telegram does not match the receive list and the receive telegram is too early.
22 (= 16 hex):
The address of the power unit in the telegram and in the receive list does not match and the receive telegram is too
early.
25 (= 19 hex):
The error bit in the receive telegram is set and the receive telegram is too early.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy: - carry out a POWER ON (power off/on).
- check the electrical cabinet design and cable routing for EMC compliance
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
SINAMICS DCP
452 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
33 (= 21 hex):
The cyclic telegram has not been received.
34 (= 22 hex):
Timeout in the telegram receive list.
64 (= 40 hex):
Timeout in the telegram send list.
98 (= 62 hex):
Error at the transition to cyclic operation.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy: - check the power supply voltage of the component involved.
- carry out a POWER ON.
- replace the component involved.
SINAMICS DCP
List Manual (LH21), 05/2016 453
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
454 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
Remedy: - allow the temperature sensor to cool down to below p4102[1] - hysteresis (5 K, for TM150, can be set using
p4118[0]).
- if required, set the fault response to NONE (p2100, p2101).
See also: p4102
SINAMICS DCP
List Manual (LH21), 05/2016 455
4 Faults and alarms
4.2 List of faults and alarms
Note:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[3] = 1, 4), the following applies:
- if r4101[3] > 1650 ohms, the temperature r4105[3] = 250 °C
- if r4101[3] <= 1650 ohms, the temperature r4105[3] = -50 °C
The temperature actual value is displayed via connector output r4105[3] and can be interconnected.
Notice:
This fault only causes the drive to shut down if there is at least one BICO interconnection between the drive and the
Terminal Module.
Fault value (r0949, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
Remedy: - allow the temperature sensor to cool down to below p4102[7] - hysteresis (5 K, for TM150, can be set using
p4118[3]).
- if required, set the fault response to NONE (p2100, p2101).
See also: p4102
SINAMICS DCP
456 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
F35221 (N, A) TM: Setpoint - actual value deviation outside the tolerance range
Drive object: DCP_CTRL, TM15DI_DO, TM31
Cause: The deviation between the setpoint and the output signals (track A/B) exceeds the tolerance of +/-3 %. The deviation
between the internal and external measured value is too high (> 1000 pulses).
Remedy: - reduce the basic clock cycle (p0110, p0111).
- if required, replace the component (e.g. internal short-circuit).
SINAMICS DCP
List Manual (LH21), 05/2016 457
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
458 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 459
4 Faults and alarms
4.2 List of faults and alarms
Notice:
This fault only causes the drive to shut down if there is at least one BICO interconnection between the drive and the
Terminal Module.
Fault value (r0949, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
Remedy: - allow the temperature sensor to cool down to below p4102[15] - hysteresis (p4118[7]).
- if required, set the fault response to NONE (p2100, p2101).
See also: p4102
SINAMICS DCP
460 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 461
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
462 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 463
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
464 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
16 (= 10 hex):
The receive telegram is too early.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy: - carry out a POWER ON (power off/on).
- check the electrical cabinet design and cable routing for EMC compliance
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
SINAMICS DCP
List Manual (LH21), 05/2016 465
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
466 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
16 (= 10 hex):
The receive telegram is too early.
17 (= 11 hex):
CRC error and the receive telegram is too early.
18 (= 12 hex):
The telegram is shorter than that specified in the length byte or in the receive list and the receive telegram is too
early.
19 (= 13 hex):
The telegram is longer than that specified in the length byte or in the receive list and the receive telegram is too early.
20 (= 14 hex):
The length of the receive telegram does not match the receive list and the receive telegram is too early.
21 (= 15 hex):
The type of the receive telegram does not match the receive list and the receive telegram is too early.
22 (= 16 hex):
The address of the power unit in the telegram and in the receive list does not match and the receive telegram is too
early.
25 (= 19 hex):
The error bit in the receive telegram is set and the receive telegram is too early.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy: - carry out a POWER ON (power off/on).
- check the electrical cabinet design and cable routing for EMC compliance
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
SINAMICS DCP
List Manual (LH21), 05/2016 467
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
468 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 469
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
470 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 471
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
472 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 473
4 Faults and alarms
4.2 List of faults and alarms
21 (= 15 hex):
The type of the receive telegram does not match the receive list and the receive telegram is too early.
22 (= 16 hex):
The address of the power unit in the telegram and in the receive list does not match and the receive telegram is too
early.
25 (= 19 hex):
The error bit in the receive telegram is set and the receive telegram is too early.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy: - carry out a POWER ON (power off/on).
- check the electrical cabinet design and cable routing for EMC compliance
- check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
SINAMICS DCP
474 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 475
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
476 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 477
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
478 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
64 (= 40 hex):
Timeout in the telegram send list.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy: - carry out a POWER ON (power off/on).
- replace the component involved.
SINAMICS DCP
List Manual (LH21), 05/2016 479
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
480 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 481
4 Faults and alarms
4.2 List of faults and alarms
35 (= 23 hex):
Receive error: The telegram buffer memory contains an error.
66 (= 42 hex):
Send error: The telegram buffer memory contains an error.
67 (= 43 hex):
Send error: The telegram buffer memory contains an error.
96 (= 60 hex):
Response received too late during runtime measurement.
97 (= 61 hex):
Time taken to exchange characteristic data too long.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy: - check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
- check the electrical cabinet design and cable routing for EMC compliance
- if required, use another DRIVE-CLiQ socket (p9904).
- replace the component involved.
SINAMICS DCP
482 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 483
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
484 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 485
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
486 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 487
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
488 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 489
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
490 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 491
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
492 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
List Manual (LH21), 05/2016 493
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
494 List Manual (LH21), 05/2016
4 Faults and alarms
4.2 List of faults and alarms
F60511 (N, A) Deviation between the internal and external current actual value too high
Drive object: DCP_CTRL
Cause: The deviation between the internal and external current actual value is too high.
Note:
The signal source for the external current actual value was set in p55156.
Remedy: - check the external current transformer for the current actual value.
- if necessary increase the threshold to identify the deviation (p55161).
See also: p55161 (Correction current controller limiting)
SINAMICS DCP
List Manual (LH21), 05/2016 495
4 Faults and alarms
4.2 List of faults and alarms
Note:
r50047[1]: Temperature power unit 1 (in °C)
r50047[2]: Temperature power unit 2 (in °C)
r50047[3]: Temperature power supply module (in °C)
r50047[4]: Temperature mainboard module (in °C)
r50047[5]: Temperature CUD module (in °C)
r50047[6]: Air intake temperature (in °C)
r50047[7]: Reference voltage +10 V (in Volt)
r50047[8]: Reference voltage -10 V (in Volt)
r50047[9]: Temperature power unit 3 (in °C)
Remedy: - check the ambient temperature and reduce if necessary.
- check the function of the device fan.
SINAMICS DCP
496 List Manual (LH21), 05/2016
Appendix A
Content
SINAMICS DCP
List Manual (LH21), 05/2016 497
A Appendix
A.1 ASCII table (characters that can be displayed)
32 20 Space
! 33 21 Exclamation mark
" 34 22 Quotation mark
# 35 23 Number sign
$ 36 24 Dollar
% 37 25 Percent
& 38 26 Ampersand
’ 39 27 Apostrophe, closing single quotation mark
( 40 28 Opening parenthesis
) 41 29 Closing parenthesis
* 42 2A Asterisk
+ 43 2B Plus
, 44 2C Comma
- 45 2D Hyphen, minus
. 46 2E Period, decimal point
/ 47 2F Slash, slant
0 48 30 Digit 0
1 49 31 Digit 1
2 50 32 Digit 2
3 51 33 Digit 3
4 52 34 Digit 4
5 53 35 Digit 5
6 54 36 Digit 6
7 55 37 Digit 7
8 56 38 Digit 8
9 57 39 Digit 9
: 58 3A Colon
; 59 3B Semicolon
< 60 3C Less than
= 61 3D Equals
> 62 3E Greater than
? 63 3F Question mark
@ 64 40 Commercial At
SINAMICS DCP
498 List Manual (LH21), 05/2016
A Appendix
A.1 ASCII table (characters that can be displayed)
A 65 41 Capital letter A
B 66 42 Capital letter B
C 67 43 Capital letter C
D 68 44 Capital letter D
E 69 45 Capital letter E
F 70 46 Capital letter F
G 71 47 Capital letter G
H 72 48 Capital letter H
I 73 49 Capital letter I
J 74 4A Capital letter J
K 75 4B Capital letter K
L 76 4C Capital letter L
M 77 4D Capital letter M
N 78 4E Capital letter N
O 79 4F Capital letter O
P 80 50 Capital letter P
Q 81 51 Capital letter Q
R 82 52 Capital letter R
S 83 53 Capital letter S
T 84 54 Capital letter T
U 85 55 Capital letter U
V 86 56 Capital letter V
W 87 57 Capital letter W
X 88 58 Capital letter X
Y 89 59 Capital letter Y
Z 90 5A Capital letter Z
[ 91 5B Opening bracket
\ 92 5C Backslash
] 93 5D Closing bracket
^ 94 5E Circumflex
_ 95 5F Underline
‘ 96 60 Opening single quotation mark
a 97 61 Small letter a
b 98 62 Small letter b
c 99 63 Small letter c
d 100 64 Small letter d
SINAMICS DCP
List Manual (LH21), 05/2016 499
A Appendix
A.1 ASCII table (characters that can be displayed)
SINAMICS DCP
500 List Manual (LH21), 05/2016
A Appendix
A.2 List of abbreviations
Note
The following list of abbreviations includes all abbreviations and their meanings used in the
entire SINAMICS family of drives.
SINAMICS DCP
List Manual (LH21), 05/2016 501
A Appendix
A.2 List of abbreviations
SINAMICS DCP
502 List Manual (LH21), 05/2016
A Appendix
A.2 List of abbreviations
SINAMICS DCP
List Manual (LH21), 05/2016 503
A Appendix
A.2 List of abbreviations
SINAMICS DCP
504 List Manual (LH21), 05/2016
A Appendix
A.2 List of abbreviations
SINAMICS DCP
List Manual (LH21), 05/2016 505
A Appendix
A.2 List of abbreviations
SINAMICS DCP
506 List Manual (LH21), 05/2016
A Appendix
A.2 List of abbreviations
SINAMICS DCP
List Manual (LH21), 05/2016 507
A Appendix
A.2 List of abbreviations
SINAMICS DCP
508 List Manual (LH21), 05/2016
A Appendix
A.2 List of abbreviations
SINAMICS DCP
List Manual (LH21), 05/2016 509
A Appendix
A.2 List of abbreviations
SINAMICS DCP
510 List Manual (LH21), 05/2016
Index
Numbers 2585
1020 Status word, sequence control, 337
Explanation of the symbols (part 1), 314 2650
1021 Sequencer, 339
Explanation of the symbols (part 2), 315 3100
1022 Fixed values, 341
Explanation of the symbols (part 3), 316 3102
1030 Function generator, 342
Handling BICO technology, 317 6700
2050 MPP Tracker, 344
Digital inputs (DI 0 ... DI 3), 319 6720
2055 Battery charging characteristic, 345
Digital outputs (DO 0 ... DO 3), 320 6800
2060 Closed-loop control, overview, 347
Digital inputs/outputs, bidirectional 6805
(DI/DO 4 ... DI/DO 5), 321 Setpoint processing, 348
2065 6806
Digital inputs/outputs, bidirectional Correction current controller, 349
(DI/DO 6 ... DI/DO 7), 322 6808
2075 Dynamic overload, 350
Analog inputs (AI 0), 323 6810
2080 Current/power limitation, 351
Analog inputs (AI 1 ... AI 2), 324 6812
2085 Voltage limitation, 352
Analog inputs (AI 3 ... AI 4), 325 6817
2090 Voltage limitation, dynamic, 353
Analog inputs (AI 5 ... AI 6), 326 6818
2095 Voltage controller, 354
Analog outputs (AO 0 ... AO 1), 327 6820
2410 Main current controller, 355
PROFIBUS (PB) / PROFINET (PN) / USS, 6825
addresses and diagnostics, 329 Residual current controller, 356
2460 6830
IF1 receive telegram, free interconnection via BICO Pulse width modulation, 357
(p0922 = 999), 330 6835
2470 Contactor control/precharging, 358
IF1 send telegram, free interconnection via BICO 6845
(p0922 = 999), 331 Fan control, 359
2472 6850
IF1 status words, free interconnection, 332 Actual value acquisition, 360
2546 6855
Control word, faults/alarms, 334 Power unit monitoring, 361
2548 6860
Status word, faults/alarms 1, 335 Power unit, properties, 362
2580 8030
Control word, sequence control, 336 Temperature sensor, 364
SINAMICS DCP
List Manual (LH21), 05/2016 511
Index
8048 Binector
Monitoring functions in the device, 365 Input (BI), 16
8054 Output (BO), 16
Internal diagnostics, 366 Binector-connector converter, 332
8055 Bit field (parameter), 20
General diagnostics, 367 BO, Binector Output, 16
8056
Diagnostic memory, 368 C
8060 C1(x) - State commissioning device, 17
Fault buffer, 370 C2(x) - State commissioning drive, 17
8065 Can be changed (parameter, C1(x), C2(x), U, T), 17
Alarm buffer, 371 CDS, (Command Data Set), 374, 375
8070 CI, Connector Input, 16
Fault/alarm trigger word (r2129), 372 Closed-loop control overview, 347
8075 CO, Connector Output, 16
Fault/alarm configuration, 373 CO/BO, Connector/Binector Output, 16
8560 Command data sets, 374
Command Data Sets (CDS), 375 Connector
9350 Input (CI), 16
Paralleling interface, 377 Output (CO), 16
9912 Connector-binector converter, 330
BOP20 control word interconnection, 379 Contactor control, 358
Converter
A Binector-connector converter, 332
Access level (parameter), 18 Connector-binector converter, 330
Active (parameter, C1(x), C2(x), U, T), 17 Correction current controller, 349
Actual value acquisition, 360 CUD
Adjustable parameters, 15 Input/output terminals, 318
Alarm Current limitation, 348, 351
Cause, 385
Display, 382 D
Drive object, 385 Data set, 374
Explanation of list, 384 Data type (parameter, signal source), 18
Fault location, 384 DC link buffer, 354
General information, 382 Dependency (parameter), 20
How to distinguish an alarm from a fault, 382 Description (parameter), 19
List of all alarms, 386 Diagnostics
Name, 384 Diagnostic memory, 368
Number, 384 General diagnostics, 367
Remedy, 385 Internal diagnostics, 366
Alarm buffer, 371 Digital inputs (DI), 318
Alarm value, 385 Digital inputs/outputs (DI/DO), 318
Analog inputs (AI), 318 Digital outputs (DO), 318
Analog outputs (AO), 318 Directory
ASCII table, 498 ASCII table, 498
Auxiliary functions, 340 Display
Axxxx, 384 Alarms, 382
Faults, 382
B Display parameters, 15
Basic Operator Panel (BOP), 378 DO, Drive Object, 16
Battery charging characteristic, 345 Drive object, 16
BI, Binector Input, 16 Dynamic overload, 350
BICO technology, 317
SINAMICS DCP
512 List Manual (LH21), 05/2016
Index
SINAMICS DCP
List Manual (LH21), 05/2016 513
Index
G P
General information Paralleling interface, 377
about parameters, 14 Parameters
on faults and alarms, 382 Access level, 18
on function diagrams, 313 Can be changed, 17
Data type, 18
I Description, 19
Index Full name, 16
Factory setting, 20 Function, 19
Parameters, 15, 20 Index, 15, 20
Industrial security, 11 Linked parameters, 15
Input/output terminals List of all parameters, 22
CUD, 318 Name, 16
Number, 15
L Safety instructions, 21
Linked parameters, 15 Short name, 16
List Values, 19
Abbreviations, 501 Password for access level 4, 18
ASCII table, 498 Power limitation, 348, 351
Complete table of contents, 7 Power unit
Faults and alarms, 386 Monitoring, 361
Function diagrams, 309 Properties, 362
Index, 511 Trace, 368
List of abbreviations, 501 Precharging, 358
Parameters, all, 22 PROFIBUS (PB), 328
Table of contents, function diagrams, 310 PROFIdrive, 328
List of abbreviations, 501 PROFINET (PN), 328
Pulse width modulation (PWM), 357
M
pxxxx, 15
Main current controller, 355
Monitoring functions in the device, 365 R
MPP Tracker, 344 Residual current controller, 356
rxxxx, 15
N
Name S
Alarm, 384 Safety instructions
Fault, 384 Fundamental, 9
Parameters, 16 General, 10
Number Industrial security, 11
Alarm, 384 Safety instructions (parameter), 21
Fault, 384 Search tools for this manual, 5
Parameters, 15 Sequence control, 338
Setpoint processing, 348
O
Signal path for function diagrams, 314
Object, 16
Symbols
Objective of this manual, 5
Explanation, Part 1, 314
Explanation, Part 2, 315
Explanation, Part 3, 316
T
T - Ready state, 17
Target group for this manual, 5
Temperature sensor, 364
Trace, power unit:, 366
SINAMICS DCP
514 List Manual (LH21), 05/2016
Index
U Version
U - Operation state, 17 List of all parameters, 22
List of faults and alarms, 386
V Voltage controller, 354
Values (parameter), 19 Voltage limitation, 352
Voltage limitation, dynamic, 353
SINAMICS DCP
List Manual (LH21), 05/2016 515
Index