SG0180 Drawings For Customer Approval 11.10.2022
SG0180 Drawings For Customer Approval 11.10.2022
REV 0
F F
SG0180
E E
FILE NAME:
DRG. NO.
D D
IF IN DOUBT, ASK
C C
CG Power and Industrial Solutions Limited
B B
All information contained in this document
is confidential and should not be used
without prior consent of
3 4 5
A 4 NAME DATE
CUSTOMER : SSV ELECTRICALS & CONSULTANTS COVER SHEET W.O.NO. SG0180
DRN. SRR 11.10.2022
3 END CUSTOMER : NAMAMI GANGE FOR 11KV, 3WAY EXTENSIBLE,
TITLE
0
REV TECHNICAL SPECIFICATIONS
F F
B B
CG Power and Industrial Solutions Limited
All information contained in this document
is confidential and should not be used
without prior consent of
3 4 5
A 4 NAME DATE
CUSTOMER : SSV ELECTRICALS & CONSULTANTS TECHNICAL SPECIFICATION W.O.NO. SG0180
DRN. SRR 11.10.2022
3 END CUSTOMER : NAMAMI GANGE
TITLE
0
REV
F F
21 DISTANCE PROTECTION RELAY NORMALLY CLOSED PUSH BUTTON FI1,FI2 INDICATION CIRCUIT FUSES
25 CHECK SYNCHRONIZING RELAY M MOTOR T TRIP CKT HEALTHY TEST PUSH BUTTON MTTB METERING TEST TERMINAL BLOCK FAN1,FAN2 ANNUNCIATION CIRCUIT FUSES
27 UNDER VOLTAGE RELAY CURRENT TRANSFORMER DA DC FAIL ACCEPT PUSH BUTTON RTTB RELAY TEST TERMINAL BLOCK FCA1,FCA2 COMMON ALARM CIRCUIT FUSES
32 DIRECTIONAL POWER RELAY VOLTAGE TRANSFORMER AA AC FAIL ACCEPT PUSH BUTTON FSY1,FSY2 SYNCHRONIZING CIRCUIT FUSES
37 UNDER CURRENT/POWER RELAY THERMOSTAT EPB EMERGENCY PUSH BUTTON ADF AC DC FAIL RELAY (WITH ALARM LOGIC) FAX1,FAX2 AUXILLARY RELAY CKT FUSES
46 NEGATIVE SEQUENCE VOLTAGE RELAY BUZZER/HOOTER PA/PR ACCEPT/RESET PUSH BUTTON DCF DC FAIL RELAY (WITH ALARM LOGIC) FM/LKM FUSE/LINK FOR MOTOR CIRCUIT
47 NEGATIVE SEQUENCE CURRENT RELAY LAMP PM/PT MUTE/TEST PUSH BUTTON CAR COMMON ALARM SCHEME FH/LKH FUSE/LINK FOR HEATER CIRCUIT
SG0180_L
49 THERMAL RELAY SWITCH(TNC,LR,AUTO MANUAL) VSS VOLTAGE SELECTION SCHEME FS/LKS FUSE/LINK FOR SOCKET CIRCUIT
E 50 HIGHSET OVER CURRENT RELAY TOGGLE SWITCH Z OPENS WHEN SPRINGS ARE CHARGED FV1-4 FUSES FOR VOLT SEL SCHEME E
50N HIGHSET EARTH FAULT RELAY COIL ZZ CLOSES WHEN SPRINGS ARE CHARGED SS SURGE SUPPRESSOR MCB MINIATURE CIRCUIT BREAKER
FILE NAME:
51 IDMTL OVER CURRENT RELAY CC CURRENT COIL OF METER LS CLOSES WHEN VCB IS MECH.FREE TO CLOSE LA LIGHTNING ARRESTOR
DRG. NO.
51N IDMTL EARTH FAULT RELAY PC PRESSURE COIL OF METER TNC BREAKER CONTROL SWITCH LLI LINE LINE INDICATOR TS CONTACTOR SENSING TEST POSITION
51S SENSITIVE EARTH FAULT RELAY (52a)VCB OPERATED NO CONTACT LR LOCAL REMOTE SWITCH ANN ANNUNCIATOR CS CONTACTOR SENSING SERVICE POSITION
51G STAND-BY EARTH FAULT RELAY (52b)VCB OPERATED NC CONTACT SS SYNCHRONIZING SELECT SWITCH HCA HOOTER FOR COMMON ALARM CLS CONTACTOR SENSING SERVICE /TEST POSITION
59 OVER VOLTAGE RELAY 3PIN SOCKET ASS/VSS AMMETER/VOLTMETER SELECTOR SWITCH HAN HOOTER FOR ANNUNCIATOR 98X AUX CONTACTOR FOR VCBCONTACT MULT.
59N VOLTAGE BALANCE RELAY (NDR) TSS TRIP SEL SWITCH(USED IN SYNCHRO.CKT) HAF HOOTER FOR AC FAIL ALARM 98U AUX CONTACTOR FOR 27 RELAY CONT MULT
61 CURRENT BALANCE RELAY (NDR) TAG TAG DESCRIPTION BSS CB SEL SWITCH(USED IN SYNCHRO. CKT) HDF HOOTER FOR DC FAIL ALARM 98M AUX CONTACTOR FOR 86 RELAY CONT MULT
63R TRANSFORMER FAULT RELAY ACS AC SOURCE SEL SWITCH HET HOOTER FOR EARTHING TRUCK 98S AUX CONTACTOR FOR SPRING CHARGE STATUS
D D
64R REF RELAY VCB52 CIRCUIT BREAKER DSS DC SOURCE SEL SWITCH HNTA HOOTER FOR NON TRIP ALARM CA/CB AUX CONTACTORS USED IN VSS
64N GROUND FAULT RELAY PL PLUG & SOCKET LSS LIMIT SWITCH FOR SERVICE POSITION PP POWERPACK 98D AUX CONTACTOR FOR DC SUPERVISION
67 LST LIMIT SWITCH FOR TEST POSITION HE SPACE HEATER 98A AUX CONTACTOR FOR AC SUPERVISION
AC DIRECTIONAL CURRENT RELAY
IF IN DOUBT, ASK
79 AUTO RECLOSING RELAY HSW/PSW TOGGLE SWITCH FOR HEATER/PANEL LAMP TH THERMOSTAT 98O AUX CONTACTOR FOR 59 RELAY CONT MULT
80 DC SUPPLY SUPERVISION RELAY SSW TOGGLE SWITCH FOR SOCKET T1,T2... TIMER
81U UNDER FREQUENCY RELAY DS DOOR SWITCH R1,R2... RESISTOR CTX CURRENT TRANSDUCER
81O OVER FREQUENCY RELAY AMS AUTO MANUAL SELECTOR SWITCH VTX VOLTAGE TRANSDUCER
85 PILOT WIRE RECEIVER RELAY FR,FY,FB PT SECONDARY(Y SIDE) FUSES KWX KW TRANSDUCER
86 MASTER TRIP(LOCK OUT) RELAY CT CURRENT TRANSFORMER AM ANALOG/DIGITAL AMMETER F1,F2 PT SECONDARY(V SIDE) FUSES KVARX KVAR TRANSDUCER
C C
94 ANTI PUMPING RELAY VT / PT VOLTAGE TRANSFORMER VM ANALOG/DIGITAL VOLTMETER FC1,FC2 CLOSING CIRCUIT FUSES TEMX TEMPERATURE TRANSDUCER
95 TRIP CKT. SUPERVISION RELAY CBCT CORE BALANCED CURRENT.TRANSFORMER HZ FREQUENCY METER FT1,FT2 TRIPPING CIRCUIT FUSES
TERMINAL BLOCK -DISCONNECTING TYPE R BREAKER ON INDICATION(RED) KVA VOLT AMP METER
1. THESE ARE THE FREQUENTLY USED ABBREVIATIONS AS PER CGL STANDARD DRAWINGS
G
2. REFERENCES IEV-440 , IS-5578, IEC-60050
TERMINAL BLOCK FOR WITHIN PANEL WIRE BREAKER OFF INDICATION(GREEN) PF POWER FACTOR METER
TERMINAL BLOCK FOR WITHIN BOARD WIRE A AUTO TRIP INDICATION(AMBER) KWH WATTHOUR METER
TERMINAL BLOCK FOR REMOTE FEEDBACK W TRIP CKT HEALTHY INDICATION(WHITE) TVM TRIVECTOR METER
HRC FUSE B SPRING CHARGED INDICATION (BLUE) MDC MAXIMUM DEMAND CONTROLLER
B LINK SP SERVICE POSITION INDICATION (AMBER) LM LOAD MANAGER B
CG Power and Industrial Solutions Limited
3 POSITION DISCONNECTOR SWITCH TP TEST POSITION INDICATION (CLEAR) MFM MULTIFUNCTION METER
All information contained in this document
3 4 5
A 4 NAME DATE
CUSTOMER : SSV ELECTRICALS & CONSULTANTS LEGENDS/SYMBOL FOR W.O.NO. SG0180
DRN. SRR 11.10.2022
3 END CUSTOMER : NAMAMI GANGE FOR 11KV, 3WAY EXTENSIBLE,
TITLE
GENERAL ARRANGEMENT FOR 11KV, 630A, 21KA, 3 WAY, OUTDOOR, SF6 INSULATED,MOTORISED,
RING MAIN UNIT, 3 VCB + PT PANEL (+VVV+M)
SG0180_GA1
1691
974
1091 470
945
RATING
1806
PLATE
810
NTS SG0180_GA1 0
0
LEGENDS:-
VM HAN-1 HAN-2
86-1 86-2
27/59 86-3
ANN-2 ANN-2
GREEN ZONE
Gas pressure Healthy
RED ZONE
Gas pressure Unhealthy
NTS SG0180_GA2 0
0
A B
2 2
SG0180_GA3
7 7
9
8
1 1
6 6
5 5
3 3
4 4
LEGENDS :
01: VCB (GAS COMPARTMENT)
02: 3 POSITION DISCONNECTOR (GAS COMPARTMENT)
03: CURRENT TRANSFORMER
04: POWER CABLE
05: CABLE BUSHING (OUTER CONE TYPE)
06: BURSTING DISC(PRESSURE RELIEF SAFETY DEVICE)
07 : PRESSURE GAUGE
08 : VCB OPERATING MECHANISM
09: POTENTIAL TRANSFORMER
NTS SG0180_GA3 0
0
LEGENDS :
5
1. OFF- LOAD DISCONNECTOR ON / OFF INDICATION
2. OFF- LOAD DISCONNECTOR EARTH INDICATION
9 1 3. SPRING CHARGING HANDLE LOCATION
4. BREAKER TRIP PUSH BOTTON
SG0180_GA4
3 NOTE:
CUSTOMER : SSV ELECTRICALS & CONSULTANTS MIMIC DRAWING FOR BREAKER SG0180
SRR 11.10.2022
END CUSTOMER : NAMAMI GANGE FOR 11KV, 3WAY EXTENSIBLE, VAC 11.10.2022
4 4
OUTDOOR RING MAIN UNIT
NTS SG0180_GA4 0
0
13 M12 GROUND
1054 464 FIXING
(Ø14 HOLES 6
NOS.)
396
995
792
792
256
426
396
396
265
TOP VIEW CABLE
GLAND PLATE TRENCH
201 341 341
41.3
M12 FOUNDATION
FRONT SIDE BOLT
PLINTH LEVEL
300
500
GROUND LEVEL
NOTES :
1. ALL DIMENSIONS ARE SUBJECTED TO MANUFACTURING TOLERANCE
±5% UNLESS OTHERWISE STATED.
2. THIS DRAWING IS FOR REFERENCE PURPOSE ONLY,MODIFICATION
FRONT VIEW
MAY BE REQUIRED DURING DETAIL MANUFACTURING/AS PER
SITE/GEOGRAPHICAL CONDITION.
NTS SG0180_F 0
1 2 3 4 5 6 7 8 9 10
0
REV
F F
SINGLE LINE DIAGRAM FOR 11KV, 3 WAY, OUTDOOR, SF6 INSULATED, MANUAL, EXTENSIBLE,
RING MAIN UNIT ,+VVV+M, ( 3 VCB + PT PANEL )
SG0180_SLD
E E
FILE NAME:
DRG. NO.
D D
IF IN DOUBT, ASK
C C
B B
CG Power and Industrial Solutions Limited
All information contained in this document
is confidential and should not be used
without prior consent of
3 4 5
A 4 NAME DATE
CUSTOMER : SSV ELECTRICALS & CONSULTANTS SLD DRAWING W.O.NO. SG0180
DRN. SRR 11.10.2022
3 END CUSTOMER : NAMAMI GANGE FOR 11KV, 3WAY EXTENSIBLE,
TITLE
R
F Y ALL WIRE FERRULES WITH PREFIX F
B "1" FOR VCB-1
S1 S2 S3 "2" FOR VCB-2
3 POSITION
3PDIS "3" FOR VCB-3
OFF LOAD
S4
DISCONNECTOR
S5 S6 5051
1r 2r 3y 3O\C+ 1 E\F PROTECTION
VCB SELF POWER RELAY
SG0180_SC1
VCB52 630AMP
4y 5b 6b
50-51
#D111 213 27
P1
E E
#D131 214 28 29 #L71
110 OUTPUT CONTACT
#D151 215 #L73
FILE NAME:
111
DRG. NO.
#D10 216
#D30 217 50-51
24
#D50 218 #D70
METERING CORE
2.5VA BURDEN
25 26 #K31
CT11 CT12 CT13 104 OUTPUT CONTACT
D90
105
ET
CL: 1.0
#C111 204
IF IN DOUBT, ASK
#C131
TRIPPER COIL
205 VCB52
50-51 VCB52
#C151 206 - 12 13 + #K37 3 4 #K38 MX1 MX2
#C10 207
#C30 208 #K36
PROTECTION CORE
ET 50-51 31 30 E95
1S2 1S2 1S2 16 17
1S1 1S1 1S1
#C71
R-PHASE ET
#C11 201 #C13
50-51
CT INPUTS FOR
PROTECTION
#C31 202 #C33 18 19
50-51
Y-PHASE 11 8 #H5
FOR
#C51 203 #C53
50-51
VPIS 20 21 108
B-PHASE TRIP COMMAND
FROM PT PANEL
#H3 109
SC1 3 R 50-51
B 22 23 1 B
CG Power and Industrial Solutions Limited
NEUTRAL F1
50-51 1 2 H1 101
All information contained in this document
SC2
is confidential and should not be used
4 Y E 6A
#H4 1 F2 2 H2 102
without prior consent of
2
RS485 PORT
E92
6A
230V AC INPUT
SC3 5 B
(CUSTOMER SCOPE)
ET
R Y B
COMMUNICATION
RS485 PORT 3 4 5
VOLTAGE PRESENT
A 4 NAME DATE
1X3CX300Sqmm, CABLE. INDICATORCUSTOMER
SYSTEM : SSV ELECTRICALS & CONSULTANTS SCHEMATIC DRAWING FOR W.O.NO. SG0180
DRN. SRR 11.10.2022
3 END CUSTOMER : NAMAMI GANGE BREAKER RELAY & CT CIRCUIT
TITLE
0
REV
N n1
DRG. NO.
MFM-2
E90A
VR
PC
ET ET
VY
PC
MULTIFUNCTION METER
VB FOR VCB-2
PC
D N D
MFM-3
AM-1 MFM-1 AM-2 MFM-2 VR
505 1D11RS1 509 2D11 RS1 PC
RS2 1D13 RS1 RS2 RS2 2D13 RS1 RS2
VY
AM-1 MFM-1 AM-2 MFM-2 PC
506 1D31 YS1 YS2 1D33 YS1 YS2 510 2D31 YS1 YS2 2D33 YS1 YS2
MULTIFUNCTION METER
VB FOR VCB-3
AM-1 MFM-1 AM-2 MFM-2 PC
C 507 1D51 BS1 BS2 1D53 BS1 BS2 511 2D51 BS1 BS2 2D53 BS1 BS2 C
N
AM-3 MFM-3
514 N
CG Power and Industrial Solutions Limited
AM-3 MFM-3
E13
All information contained in this document
E33
TO NEXT PAGE
without prior consent of
516 3D70
E53
E71 3
3
44 5
5
A 4 NAME DATE
CUSTOMER : SSV ELECTRICALS & CONSULTANTS SCHEMATIC DRAWING FOR W.O.NO. SG0180
DRN. SRR 11.10.2022
3 END CUSTOMER : NAMAMI GANGE
TITLE
0
REV
E71
F F
E53
E33
E13
OVER / UNDER VOLTAGE RELAY
27/59
SG0180_SC3
27/59 517
1 2 20 21 K31
518
TRIP COMMAND TO
27/59 K32
4 5 MASTER TRIP RELAY
E E
27/59 517
27/59 16 17 L72
7 8
FILE NAME:
27/59
18 19 COMMAND TO ANNUNCIATOR
L74 518
D MFM-1 D
P1 N1
+ -
MFM-2
P1 N1
+ -
IF IN DOUBT, ASK
MFM-3
P1 N1
+ -
AM-1
B A
+ -
AUX. SUPPLY FOR METERS
AM-2
B A
+ -
C C
AM-3
B A
+ -
VM
B A
+ -
B B
CG Power and Industrial Solutions Limited
All information contained in this document
is confidential and should not be used
without prior consent of
3 4 5
A 4 NAME DATE
CUSTOMER : SSV ELECTRICALS & CONSULTANTS SCHEMATIC DRAWING FOR W.O.NO. SG0180
DRN. SRR 11.10.2022
3 END CUSTOMER : NAMAMI GANGE
TITLE
0
REV
F F
24V DC SUPPLY
FROM CUSTOMER
401 402
J3
J4
SG0180_SC4
DRG. NO.
TRIP COMMAD TO
MASTER TRIP RELAY 86-2
405 406 2K32 5 14 MASTER TRIP RELAY
FOR VCB-2
TRIP COMMAD TO
MASTER TRIP RELAY 86-3
D 407 408 3K32 5 14 D
MASTER TRIP RELAY
FOR VCB-3
IF IN DOUBT, ASK
1
FM2 2 K34
C C
MASTER TRIP RELAY O/P TO VCB-1 MASTER TRIP RELAYO/P TO VCB-2 MASTER TRIP RELAY O/P TO VCB-3
B B
All information contained in this document
J4
is confidential and should not be used
without prior consent of
J3
3 4 5
A 4 NAME DATE
CUSTOMER : SSV ELECTRICALS & CONSULTANTS SCHEMATIC DRAWING FOR W.O.NO. SG0180
DRN. SRR 11.10.2022
3 END CUSTOMER : NAMAMI GANGE MEATRING PANEL- CONTROL CIRCUIT APPD.
TITLE
VAC 11.10.2022
2 SHEET 4 OF 6
THIRD ANGLE PROJECTION
1 ALL DIMENSIONS ARE IN mm
No REVISION DATE DRAWN 4 5 6 7 8 SCALE- NTS DRG. NO. SG0180_SC4 REV 0
1 2 3 4 5 6 7 8 9 10
0
REV
F F
J3
J4
SG0180_SC5
ANN-1
DRG. NO.
POWER MODULE
COMMON1
COMMON2
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
P COM1 F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11 F12 C1 C2 I1 I2 COM2 N
D D
1L85
1L83
1L87
1L81
1L78
1L79
1L80
1L76
1L77
L74
1L73
1L75
1L72
IF IN DOUBT, ASK
419 420 421 422 423 424 425 426 427 428 429 430
1L63
C HAN-1 C
1
FAN1 2 1L71 1 2 1L62 2 FAN2 1
6A 6A
B B
CG Power and Industrial Solutions Limited
All information contained in this document
is confidential and should not be used
J3
J4
without prior consent of
3 4 5
A 4 NAME DATE
CUSTOMER : SSV ELECTRICALS & CONSULTANTS SCHEMATIC DRAWING FOR W.O.NO. SG0180
DRN. SRR 11.10.2022
3 END CUSTOMER : NAMAMI GANGE MEATRING PANEL- ANNUNCIATOR
TITLE
J3
J4
ANN-2
POWER MODULE
FILE NAME:
DRG. NO.
COMMON1
COMMON2
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
P COM1 F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11 F12 C1 C2 I1 I2 COM2 N
2L85
2L83
2L87
2L81
2L78
2L79
2L80
2L76
2L77
2L73
L74
2L75
2L72
D D
419 420 421 422 423 424 425 426 427 428 429 430
IF IN DOUBT, ASK
L63
HAN-2
C C
1
FAN3 2 1L71 1 2 L62 2 FAN4 1
6A 6A
B B
CG Power and Industrial Solutions Limited
All information contained in this document
is confidential and should not be used
without prior consent of
3 4 5
A 4 NAME DATE
CUSTOMER : SSV ELECTRICALS & CONSULTANTS SCHEMATIC DRAWING FOR W.O.NO. SG0180
DRN. SRR 11.10.2022
3 END CUSTOMER : NAMAMI GANGE MEATRING PANEL- ANNUNCIATOR
TITLE
REV 0
F F
SG0180_RT
E E
FILE NAME:
DRG. NO.
##
D D
IF IN DOUBT, ASK
C C
CG Power and Industrial Solutions Limited
B B
All information contained in this document
is confidential and should not be used
without prior consent of
3 4 5
A 4 NAME DATE
CUSTOMER : SSV ELECTRICALS & CONSULTANTS RATING PLATE W.O.NO. SG0180
DRN. SRR 11.10.2022
3 END CUSTOMER : NAMAMI GANGE
TITLE
1 CIRCUIT BREAKER 3 3
MAKE-CGPISL
MANUAL OPERATION
RATING- 12KV,630A,21 kA FOR 3SECS
5 PRESSURE GUAGE 1 1
MAKE : CGPSIL/EQ,
6 HOOTER 2 2
MAKE - ALAN/EQ
AUX SUPPLY - 24V DC
PURPOSE - ANNUNCIATOR
RELAY
R1 SELF POWERED OVERCURRENT & EARTH FAULT RELAY 3 3
3O/C + 1E/F CGI 14S Relay
MAKE - CGPISL
COMMUNICATION- MODBUS RS 485 -IEC 60870-5-103
FUNCTIONS -PHASE FAULT I> (51)
PHASE FAULT I>> (50)
EARTH FAULT Io> (51N)
EARTH FAULT Io>> (50N)
SETTINGS - PF I>: 10-250% (IN STEPS OF 1%)
PF I>>: 50-3200% STEP 1% (IN STEPS OF 1%)
EF Io>: 5-250% STEP 1% (IN STEPS OF 1%)
INPUT 230 VAC for REMOTE TRIP
AUXILIARY INPUT - 230V AC
METER
M1 MULTIFUNCTION METER 3 3
MAKE - L&T/SECURE / ELMEASURE / AE/ EQ.
OVERALL SIZE :96X96 (FLUSH MTG)
CT SEC - 1A
PT SEC - PROGRAMMABLE
CONNECTIONS- 3PHASE 4 WIRE 3 ELEMENT TYPE
ACCURACY- CLASS 0.5
AUX SUPPLY - 80-270VAC
CT & PT
CT1 LT CURRENT TRANSFORMER 9 9
TYPE-TAPE WOUND / RESIN CAST
MAKE- G&M/ECS/VIDYUT/PRAGATI/NARAYAN POWERTECH/PRECISE
CTR: 100-50/1+1A
CORE-1: METERING
ACC. CLASS 1.0,
BURDEN – 2.5VA
CORE-2: PROTECTION
ACC. CLASS : 5P10 FOR 100A & 10P5 FOR 50A
BURDEN – 2.5VA
SHORT TIME CURRENT- 21KA/3SEC
HSV:0.72KV
BIL : 0.72/ 3 KVp
FREQUENCY:50Hz
INSULATION CLASS: E OR BETTER