Thông số cài đặt biến tần Hitachi J300
Thông số cài đặt biến tần Hitachi J300
3 Function mode
                 m
              (Function mode 1)         (Function mode 2)
  Display                                                                          Setting, change
           Function      Function      Initialization display    Initialization                              Setting contents
  sequence                                                                            contents
              No.          name             contents
      1      F-00      Base          F-BASE           0060 Hz       60 Hz          30 to 120 (400)   • When 120 Hz is switched to
                       frequency                                                                       400 Hz by F-30, a frequency
                       setting                                                                         more than 120 Hz can be set.
               o
      2      F-01      Maximum       F-MAX          0060 Hz         60 Hz          30 to 120 (400)
                       frequency
                       setting
      3      F-02      Start         Fmin            0.50 Hz        0.5 Hz           0.1 to 9.9      • The equipment starts running
                       frequency                                                                       at this set value.
            .c
                       adjustment
      4      F-03      Motor input   AVR AC           460 V        230/460         200,215,220,230   • The motor input voltage is set.
             Input     voltage                                                      /380,400,415
            voltage setting                                                          440,460,480
                       AVR           AVRDEC             OFF          OFF              ON/OFF         • ON or OFF of the AVR
                       function                                                                        function for deceleration
                       for                                                                             is set. When dynamic
           n           decelera-
                       tion
                                                                                                       braking torque is necessary
                                                                                                       for deceleration, OFF is set.
      5      F-04      Control       CONTROL             VC           VC           VC, VP1, VP2,     • VC, VP1, VP2, VP3:
                       method                                                      VP3, SLV, V2        V/F characteristics
        ta
                       setting                                                                         SLV:Sensorless vector control
                                                                                                       V2:Sensor vector control
     6       F-05     Autotuning     AUX AUTO          NOR          NOR            NOR/AUT/NRT       • At the first running after
                      Motor          setting                                                                    AUT/NRT is set, the
           constant                                                                                    autotuning measurement
          (NOTE 1)                                                                                     operation is executed.
                      Motor data     AUX DATA          NOR          NOR           NOR: Old Hitachi   • The autotuning motor data
      n
                                                                                   tuning data
                      Motor          AUX K        005.50 kW      Ratedcapacity        3.7 to 160     • Set a capacity smaller than the
                      capacity                                   ofeachinverter                        rated capacity as capacity
                                     setting                                                                   data.
                      Motor pole     AUX P                  4p        4p              2, 4, 6, 8     • The number of poles of the
                      count                                                                            motor to be used is set.
                      setting
  b
                      R2 setting
                      Motor          AUX L      13.16 mH         Ratedcapacity        0 to 655.35
                       constant                                  ofeachinverter
                      L setting
     NOTE 1: The motor constants R1, R2, L, M, J, Kp, Ti, and KPP vary with the capacity.
                                                                 12-5
              (Function mode 1)        (Function mode 2)
  Display                                                                       Setting, change
           Function     Function      Initialization display   Initialization                             Setting contents
  sequence    No.         name             contents                                contents
      6      F-05      Motor         AUX M        123.60 mH    Ratedcapacity     0 to 655.35      • Primary self inductance per
             Motor     M setting                               ofeachinverter                       phase.
           constant constant
                       Motor         AUX J        0.44 kgm2    Ratedcapacity     0 to 655.35      • Motor and machine inertia
                       J setting                               ofeachinverter
                       constant
                 m
                       Motor         AUX Kp          002.00         2.0          0 to 100.00      • Smaller: High response
                       constant                                                                   • Larger: Low response
                       Kp setting
                       Motor         AUX Ti       00100 ms       100 ms           0 to 10000      • Set this item after the
                       constant                                                                     feedback option PCB is
                       Ti setting                                                                   installed.
                       Motor         AUX KPP         001.00         1.0          0 to 100.00      • Set this item after the
                       constant                                                                     feedback option PCB is
               o
                       KPP setting                                                                  installed.
      7      F-06      Accelera-     ACC 1        0030.00 s      30.00 s         0.01 to 3000     • When the fuzzy most
           Accelera- tion time                                                                      suitable acceleration and
           tion time setting                                                                        deceleration (F-10) are set,
                                                                                                    the time displayed here is
            .c
                                                                                                    invalid, though it can be
                                                                                                    set.
                      2-stage        ACC 2        0015.00 s      15.00 s         0.01 to 3000     • The acceleration time can
                      acceleration                                                                  be used when the input
                      time setting                                                                  terminal CH1 is shorted.
                                                                                                  • For input terminal
                                                                                                    selection, refer to F-34
           n         Curve           ACC LINE             L          L       L (Linear),
                                                                                                    input terminal.
                                                                                                  • The curve pattern is set for
                     pattern                                                 S (S curve),           acceleration and
                     selection                                               U (U curve),           deceleration respectively.
        ta
                     for                                                     RU (reverse
                     acceleration                                                 U curve)
                     Accelera-       ACC GAIN            02    2 (common to       1 to 10         • When the constant is set
                     tion and                                  acceleration                       for one of acceleration and
                     deceleration                              and                                  deceleration, it is common
                     curve                                     deceleration)                        to both acceleration and
                     constant                                                                       deceleration.
      n
                                                                                                    input terminal.
                      Curve        DEC LINE               L          L          L (Linear),       • The curve pattern is set for
                      pattern                                                   S (S curve),        acceleration and decelera-
                      selection                                                 U (U curve),        tion respectively.
                      for                                                       RU (reverse
a
                      deceleration                                                   U curve)
                      Accelera-    DEC GAIN              02    2 (common to         1 to 10       • When the constant is set
                      tion and                                 acceleration                       for one of acceleration and
                      deceleration                             and decelera-                        deceleration, it is common
                      curve                                    tion)                                to both acceleration and
                      constant                                                                      deceleration.
                      selection                                                                   • See appendix 4.
                                                               12-6
             (Function mode 1)          (Function mode 2)
  Display                                                                        Setting, change
           Function     Function       Initialization display   Initialization                              Setting contents
  sequence    No.         name              contents                                contents
      9      F-08     Accelera-      Fsp F          0000.0 Hz       0 Hz           0 to 400.0       • The frequency at which the
           Accelera- tion stop                                                                        acceleration operation is
           tion halt frequency                                                                        stopped temporarily is set.
                      setting
                      Accelera-      Fsp TIME          00.0 s        0s             0 to 60.0       • The time that the acceleration
                      tion stop                                                                       is stopped temporarily at a
                 m
                      time setting                                                                    certain frequency during
                                                                                                      acceleration is set.
    10       F-09     Pattern        PARAM             REM         REM           REM/               • The parameter setting com-
                      command-                                                   OP1/OP2              manding source is selected.
                      ing method                                                 (Option              REM (each operator),
                      selection                                                  connected)           OP1 (option 1), OP2 (option
                                                                                                      2)
    11      F-10
               o
           Running
            mode
            .c
                      selection                                                                               running
                                                                                                    GOD:      Fuzzy most suitable
                                                                                                              acceleration and
                                                                                                              deceleration running
                     Restarting      RUN FRS            ZST         ZST             fST/ZST         fST:      Restart after frequency
                     after FRS                                                                                maching
                     signal                                                                         ZST:      0 Hz start
    12
           n
           F-11
                     selection
                     Multistage      SPD 1       0000.00 Hz         0 Hz         0 to 120.0 (400)   • The input terminal CF1 is set
          Multistage speed                                                                            and used.
           speed     1 speed
        ta
                     setting
                     Multistage      SPD 2       0000.00 Hz         0 Hz         0 to 120.0 (400)   • The input terminal CF2 is set
                     speed                                                                            and used.
                     2-speed
                     setting
                     Multistage      SPD 3       0000.00 Hz         0 Hz         0 to 120.0 (400)   • The input terminals CF1 and
                     speed                                                                            CF2 are set and used.
      n
                     3-speed
                     setting
                     Multistage      SPD 4       0000.00 Hz         0 Hz         0 to 120.0 (400)   • The input terminals CF1 and
                     speed                                                                            CF3 are set and used.
                     4-speed
    ie
                     setting
                     Multistage      SPD 5       0000.00 Hz         0 Hz         0 to 120.0 (400)   • The input terminals CF2 and
                     speed                                                                            CF3 are set and used.
                     5-speed
                     setting
                     Multistage      SPD 6       0000.00 Hz         0 Hz         0 to 120.0 (400)   • The input terminals CF1, CF2,
                     speed                                                                            and CF3 are set and used.
  b
                     6-speed
                     setting
                     Multistage      SPD 7       0000.00 Hz         0 Hz         0 to 120.0 (400)   • The input terminal CF3 is set
                     speed                                                                            and used.
                     7-speed
a
setting
                                                                12-7
              (Function mode 1)           (Function mode 2)
  Display                                                                            Setting, change
           Function      Function        Initialization display     Initialization                               Setting contents
  sequence    No.         name                contents                                  contents
     13      F-20      DC braking DCB SW                    OFF         OFF            ON/OFF            • DC braking
              DC       selection                                                                           ON: DC braking available
           injection                                                                                       OFF: DC braking unavailable
            braking DC braking DCB KIND                     LVL         LVL            LVL/EDG           • DC braking method selection
                       type                                                                                LVL: Level operation
                       selection                                                                           EDG: Edge operation
                 m
                       DC braking DCB F               0000.5 Hz        0.5 Hz        0 to 400.0 Hz       • The frequency at which the
                       frequency                                                                           DC braking starts is set.
                       selection
                       DC braking DCB V-STA                   00          0              0 to 20         • The DC braking force at start
                       force selec-                                                                        is set.
                       tion (at start)
                       DC braking DCB V-STP                   00          0              0 to 20         • The DC braking force at stop
                       force selec-                                                                        is set.
               o
                       tion (at stop)
                       DC braking DCB T-STA              000.0 s         0s            0 to 600.0        • The DC braking time at start
                       time selec-                                                                         is set.
                       tion (at start)
                       DC braking DCB T-STP              000.0 s         0s            0 to 600.0        • The DC braking time at stop
            .c
                       time selec-                                                                         is set.
                       tion (at stop)
                       DC braking DCB STOP-T               0.00 s        0s            0 to 5.00         The output frequency is
                       output cut-                                                                       lowered to the DC braking
                       off time                                                                          frequency and the free run
           n                           adjustment                                                          time during execution of DC
                                                                                                         braking is set.
     14       F-21      Dynamic         BRD-%ED         001.5%         1.5%            0 to 100.0        • The allowable usage ratio of
                        braking                                                                            the braking resistor for 100
                        setting                                                                            seconds is set. (NOTE 1)
     15        F-22     Allowable       IPS TIME            1.0 s       1.0 s          0.3 to 25 s       • When an instantaneous power
        ta
            The         instantaneous                                                                      failure occurs, the allowable
            allowable   powerfailure                                                                       time until the power failure is
            usage       time setting                                                                       recovered is set.
            ratio of    Reclosing       IPS WAIT          001.0 s       1.0 s        0.3 to 100.0 s      • The waiting time until the
            the         standbyafter                                                                       rerunning starts after an
            braking     instantaneous                                                                      instantaneous power failure
            resistor    powerfailure                                                                       occurs and is recovered is set.
      n
                        thermallevel
                        setting
                                                                    12-8
               (Function mode 1)            (Function mode 2)
  Display                                                                              Setting, change
            Function      Function         Initialization display     Initialization                             Setting contents
  sequence     No.          name                contents                                  contents
     16        F-23     Electronic       E-THM A1          8.5A Rated capacity of         0 to 600.0 A
           Electronic thermal                                     each inverter
             thermal characteristic
           (NOTE 2) free setting
                        current (1)
                        Electronic       E-THM F1 0000 Hz         Rated capacity of       0 to 400 Hz
                 m
                        thermal                                   each inverter
                        characteristic
                        free setting
                        frequency(1)
                        Electronic       E-THM A2        8.5A     Rated capacity of       0 to 600.0 A
                        thermal                                   each inverter
                        characteristic
                        free setting
               o
                        current (2)
                        Electronic       E-THM F2         5 Hz    Rated capacity of       0 to 400 Hz
                        thermal                                   each inverter
                        characteristic
                        free setting
            .c
                        frequency(2)
                        Electronic       E-THM A3      13.0 A     Rated capacity of       0 to 600.0 A
                        thermal                                   each inverter
                        characteristic
                        free setting
                        current (3)
                        Electronic       E-THM F3       73 Hz     Rated capacity of       0 to 400 Hz
           n            thermal
                        characteristic
                        free setting
                                                                  each inverter
                        frequency(3)
        ta
     17        F-24     Overload         OLOAD LEVEL125%                 125%             50 to 150%     Under the sensorless vector
            Overload restriction                                                                         control, an overload is detected
           restriction level setting                                                                     from both the overload restric-
                                                                                                         tion and torque limiter.
                         Overload     OLOAD CONST01.0                      1.0             0.3 to 31.0   When the setting is 31.0 in SLV
                         restriction                                                                     or V2 control mode, the
                         constant                                                                        overload restriction has no
                         setting                                                                         effect.
      n
                         Valid        OLOAD ACC ON                        ON            ON: Valid for    Even if the function is set to
                         selection                                                      acceleration     OFF, the overload restriction is
                         for overload                                                   Keep the         invalid only for the first
                         restriction                                                    function ON      acceleration when the forward
    ie
  NOTE 1: When MD0 is set and the input terminal SFT is turned ON, the data of all functions is locked. When MD2 is
          set (stored), the data of all the functions is locked. During locking, no data can be changed. MD1, MD3
          can set only the output frequency.
  NOTE 2: Electronic thermal characteristic free setting current and frequency depends on the inverter rating.
a
                                                                     12-9
               (Function mode 1)      (Function mode 2)
  Display                                                                       Setting, change
            Function      Function   Initialization display    Initialization                              Setting contents
  sequence     No.          name          contents                                 contents
     19       F-26      Frequency  LIMIT L        0000.0 Hz        0 Hz           0 to 120.0       The lower limit of the frequency
           Frequency lower limiter                                                (400) Hz         to be set is set. When the lower
             limiter    setting                                                                    limit is 0, the setting is invalid.
                        Frequency  LIMIT H        0000.0 Hz        0 Hz           0 to 120.0       The upper limit of the frequency
                        upper                                                     (400) Hz         to be set is set. When the upper
                        limiter                                                                    limit is 0, the setting is invalid.
                        setting
                 m
     20       F-27      Jump       JUMP F1        0000.0 Hz        0 Hz          0 to 400 Hz       • The section where frequencies
              Jump      frequency                                                                    are to be jumped is set.
           frequency setting (1)                                                                   • Up to three locations can be
                                                                                                     set.
                                                                                                   • When the number of locations
                                                                                                     is 0, the setting is invalid.
                      Jump            JUMP F2    0000.0 Hz         0 Hz          0 to 400 Hz
                      frequency
               o
                      setting (2)
                      Jump            JUMP F3    0000.0 Hz         0 Hz          0 to 400 Hz
                      frequency
                      setting (3)
                      Jump            JUMP W        0.5 Hz        0.5 Hz          0 to 9.9 Hz      • The frequency width where
            .c
                      frequency                                                                      frequencies are jumped is set.
                      width setting
    21       F-28     STOP key        STOP-SW          ON          ON           ON: STOP key       Whether or not to make the
                      validity                                                      valid          STOP key valid during terminal
                      selection                                                 OFF: STOP key      running is selected. In the
                      during                                                       invalid         Remote mode, the STOP key is
           n          terminal                                                                     always valid.
                      running
    22       F-29     Running         F/R SW          FRE          FRE           FWD/REV/          FWD: Only forward run
                      direction                                                    FRE             REV: Only reverse run
                      selection                                                                    FRE: Both forward run and
                                                                                                   reverse run valid
        ta
                    Reverse run       F/R PREV        OFF          OFF             ON/OFF          Reverse run prevention
                    prevention                                                                     ON:
                    selection                                                                      OFF:
                    Reduced           F/R RVS            6           6              0 to 6
                    voltage
                    soft start
                    setting
    23       F-30   Maximum           F-MAX-L      120 Hz        120 Hz          120/400 Hz        Maximum frequency switching:
      n
                    frequency
                    start setting
                    rate
                    External fre-     IN EX%E        100%         100%             0 to 100        • Input maximum level
                    quency end
a
                    setting rate
                    External          IN LEVEL        0 Hz         0 Hz           0 Hz/ExS         EXS: Start at EX%S setting
                    command                                                                             rate or less
                    start point
                    selection
                                                              12-10
             (Function mode 1)       (Function mode 2)
  Display                                                                         Setting, change
           Function    Function     Initialization display      Initialization                              Setting contents
  sequence No.            name           contents                                    contents
                      Frequency   IN F-SAMP                8          8                1 to 8
                      command
                      sampling
                      frequency
                      setting
     25      F-32     Arrival     ARV PTN              CST          CST           CST/PAT/ANY       CST: Output at constant
                 m
          Frequency signal output                                                                   frequency arrival
            arrival   pattern                                                                       PAT: Output of more than
            output    selection                                                                     set frequency
            signal                                                                                  ANY: Output of only set
                                                                                                    frequency
                   Arrival            ARV ACC        0.0 Hz         0 Hz             0 to 400.0
                   frequency
                   rate setting
               o
                   for
                   acceleration
                   Arrival            ARV DEC        0.0 Hz         0 Hz             0 to 400.0
                   frequency
                   rate setting
            .c
                   for
                   deceleration
     26      F-33  Overtorque         OV-TRQ V        100%         100%               0 to 250      • During control of SLV
            Over-  signal rate                                                                        and V2: Power running
            torque setting                                                                            overtorque level
            signal (for power                                                                       • During control of VC
          (NOTE 1) running)
           n                                                                                          and VP1 to VP3:
                                                                                                      Warning level for power
                                                                                                      running regenerative
                                                                                                      overload
                                                                                                    • When 0 is set: Any signal
                                                                                                      is not output.
        ta
                        Overtorque    OV-TRQ R        100%         100%               0 to 250      • During control of SLV
                        signal rate                                                                   and V2: Regenerative
                        setting                                                                        overtorque level
                        (for regen-                                                                 • During control of VC
                        eration)                                                                      and VP1 to VP3: No
                                                                                                      effect
                                                                                                    • When 0 is set: Any signal
      n
                                                                                                      is not output.
     27      F-34       Input         IN-TM 1           RS      RS reset          RS and 17
          Intelligent   terminal 1                              terminal          other terminals
           terminal     setting
             input      Input         IN-TM 2           AT      AT current        AT and 17
    ie
                        setting                                 terminal
                        Input         IN TM 5          CH1      CH1 2-stage       CH1 and 17
                        terminal 5                              acceleration      other terminals
                        setting                                 and
a
                                                                deceleration
                                                                terminal
  NOTE 1: When setting 20% or less, the error will increase (± 20% or more).
          Therefore, set 20% or more.
                                                               12-11
               (Function mode 1)        (Function mode 2)
  Display                                                                         Setting, change
            Function     Function      Initialization display    Initialization                            Setting contents
  sequence     No.          name            contents                                 contents
     27       F-34      Input        IN-TM 6              USP    USP              USP and 17
           Intelligent terminal 6                                Power-ON         other terminals
            terminal setting                                     restart
              input                                              preventionl
            terminal Input           IN-TM 7            CF1      CF1              CF1 and 17
             setting    terminal 7                               Multi-stage      other terminals
                        setting                                  input
                 m
                                                                 terminal
                       Input         IN-TM 8           REV       REV reverse       REV and17
                       terminal 8                                run command      other terminals
                       setting                                   input terminal
                       Input         IN-TMO/C-1          NO           NO             NO/NC          • Input terminal setting
                       terminal 1                                                                     NO: ON when short-
                       NO/NC                                                                          circuited
               o
                       setting                                                                        NC: ON when opened
                       Input         IN-TM O/C-2         NO          NO              NO/NC          • Input terminal setting
                       terminal 2                                                                     NO: ON when short-
                       NO/NC                                                                          circuited
                       setting                                                                        NC: ON when opened
            .c
                       Input         IN-TM O/C-3         NO          NO              NO/NC          • Input terminal setting
                       terminal 3                                                                     NO: ON when short-
                       NO/NC                                                                          circuited
                       setting                                                                        NC: ON when opened
                       Input         IN-TM O/C-4         NO          NO              NO/NC          • Input terminal setting
                       terminal 4                                                                     NO: ON when short-
                       NO/NC                                                                          circuited
    28
           n  F-35
                       setting
                       Output        OUT-TM 1           FA1          FA1          FA1/RUN/OTQ
                                                                                                      NC: ON when opened
                                                                                                    Output terminal setting
           Intelligent terminal                                                                     FA1: Frequency arrival signal
            terminal 11 setting                                                                     RUN: Signal during run
        ta
             output                                                                                 OTQ: Overtorque signal
            terminal Output          OUT-TM 2          RUN          RUN           FA1/RUN/OTQ       Output terminal setting
             setting   terminal                                                                     FA1: Frequency arrival signal
                       12 setting                                                                   RUN: Signal during run
                                                                                                    OTQ: Overtorque signal
                       Alarm         OUT-TM       O/C-A NC           NC              NC/NO          • Alarm output terminal
                       output                                                                         contacts a and b setting
      n
                                                                12-12
             (Function mode 1)           (Function mode 2)
  Display                                                                           Setting, change
           Function    Function         Initialization display     Initialization                             Setting contents
  sequence                                                                             contents
             No.         name                contents
     30     F-37      Monitor          MONITOR              A-F        A-F          A-F/A/T/D-F       • The FM terminal monitor
                      signal                                                                            signal output is selected.
                      selection                                                                         A-F: Analog frequency
                                                                                                        T: Torque monitor
                                                                                                        A: Current monitor
                                                                                                        D-F: Digital frequency
                 m
     31      F-38       Trip history   INIT TCNT         CNT          CNT             CNT/CLR         • Trip count deletion selection
            Initiali-   count clear                                                                     CNT: Trip counting is
             zation                                                                                     continued.
                                                                                                        CLR: The trip count is cleared.
                        Debug          INIT DEBG          OFF          OFF            ON/OFF          • Debug mode setting ON or
                        mode                                                                            OFF
                        display                                                                         OFF: The debug mode is
                        selection                                                                       turned off.
               o
                                                                     NOTE 1                             ON: The debug mode is turned
                                                                                                        on.
                        Digital        INIT DOPE         FWD          FWD            FWD/REV          • The digital operator running
                        operator                                                                        direction is set.
                        rotation                                                                        FWD: Forward run
            .c
                        direction                                                                       REV: Reverse run
                        selection
                        Selection of   INIT RESET          ON          ON             ON/OFF          ON: Alarm release when reset
                        reset                                                                              on
                        performance                                                                   OFF:Alarm release when reset
           n                                                                                               off
     32      F-39     Encode           OP P        01024 pulse         1024         255 to 65535      Effective with option board
            Option    pulse                                                                           (J-FB)
            setting   number
                      setting
                      Control          OP MODE            ASR          ASR            ASR/APR
        ta
                      mode
                      selection
                      Ro-To            OP RO-TO           OFF          OFF            OFF/ON          Keep OFF. (No use)
                      option
                      selection
     33      F-40     Stop             OR POS               IN          IN             IN/OUT         Effective with option board
          Orientation position                                                                        (J-FB)
      n
            setting   setting
                      switching
                      Stop             OR P        00000 pulse           0            0 to 4095
                      position
                      setting
    ie
setting
  NOTE 1 : Keep debug mode " OFF " , this is factory use only.
a
                                                                  12-13
              (Function mode 1)            (Function mode 2)
  Display                                                                             Setting, change
            Function     Function         Initialization display     Initialization                             Setting contents
  sequence                                                                               contents
               No.         name                contents
     34       F-41     Position         PO EGRP                FB         FB             FB/REF         Effective with option board
           Electronic setting                                                                           (J-FB)
              gear     switching
             setting   Numerator        PO EGR-N          00001            1            1 to 9999
                       of ratio
                       Denominator      PO EGR-D         00001             1            1 to 9999
                 m
                       Feed for-        PO FFWG          000.00            0           0 to 655.35
                       ward gain
                       Position         PO G        000.50 rad/s         0.5             0 to 100
                       loop gain                                        rad/s
     35       F-42     Torque           TRQ LIMIT          REM          REM           REM/OP1/OP2       REM: Each operator
             Torque limit                                                                               PO1: Option 1
              limit    setting                                                                          PO2: Option 2
               o
             setting   switching
            (Note 1) Plus torque        TRQ FWD            150%         150%           20 to 150%
                       limit
                       Minus            TRQ REV           150%          150%           20 to 150%       Regenerative mode
                       torque limit
            .c
     36       F-43     PID target       PID IN-SEL            IN          IN             IN/OUT
           PIDcontrol value input
             setting   method
                       switching
                       selection
                       PID target       PID LVL        000.00%            0%            0 to 200%
           n           value setting
                       P gain setting   PID P         1.0                1.0            0.1 to 5.0
                       I gain setting   PID I       01.0S                1.0             0 to 15.0
                       D gain setting   PID D       000.0               000.0            0 to 100
                       Selection        PID MODE    MD0                 MD0             MD0 to 4
        ta
     37       F-46     Transmission     COM BAU 00600 bps                600          300/600/1200/     Effective with option board
           Communi- speed                                                             2400/4800/9600/   (J-CM)
             cation    selection                                                          19200
            protocol Station            COM NUMBER            01           1              1 to 32
             setting   number
                       selection
                       Transfer bit     COM LENGTH             8           8               8/7
      n
                       length
                       selection
                       Parity           COM PAR-SEL1         ON          ON             ON/OFF
                       ON / OFF
                       selection
    ie
  NOTE 1: Smaller levels of torque limit and overload restriction are given top priority and valid for any control
          method.
                                                                    12-14
              (Function mode 1)           (Function mode 2)
  Display                                                                            Setting, change
            Function    Function         Initialization display     Initialization                             Setting contents
  sequence                                                                              contents
              No.         name                contents
     38       F-47     Main body       OP-ERR1               STP        STP            STP/RUN         Effective with option board
             Option operation
           PCB error selection for
             setting   option PCB
                       error 1
                       Main body       OP-ERR2             STP          STP            STP/RUN
                 m
                       operation
                       selection for
                       option PCB
                       error 2
     39       F-48     Setting for     RELAY RYA          RUN          RUN             CST/PAT         Effective with option board
           Selection RYA                                                              /ANY/RUN         (J-RY)
            of relay terminal                                                         /OTQ/NOR
             output    Setting for     RELAY RYB           CST          CST                            CST:   Arrival signal
               o
                       RYB                                                                                    (constant speed)
                       terminal                                                                        PAT:   Arrival signal
                       Setting for     RELAY RYC          OTQ          OTQ                                    (set frequency or more)
                       RYC                                                                             ANY:   Arrival signal
            .c
                       terminal                                                                               (set frequency only)
                                                                                                       RUN:   Running signal
                                                                                                       OTQ:   Over torque signal at
                                                                                                              SLV, SLV2/Overload
                                                                                                              signal at V/F control
                                                                                                       NOR:   No output
           n
        ta
      n
    ie
  b
a
12-15