Thông số cài đặt biến tần Hitachi J300

The document outlines the function mode settings for a remote operator, detailing initial values and display contents for various functions such as frequency settings, motor input voltage, control methods, and acceleration/deceleration parameters. Each function mode includes specific settings, initialization displays, and the range of values that can be adjusted. Additionally, it provides notes on the implications of certain settings and their operational effects.

Uploaded by

pvanson040482
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
107 views11 pages

Thông số cài đặt biến tần Hitachi J300

The document outlines the function mode settings for a remote operator, detailing initial values and display contents for various functions such as frequency settings, motor input voltage, control methods, and acceleration/deceleration parameters. Each function mode includes specific settings, initialization displays, and the range of values that can be adjusted. Additionally, it provides notes on the implications of certain settings and their operational effects.

Uploaded by

pvanson040482
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

12.

3 Function mode

Function mode list when the remote operator is used

• Function mode initial values and display contents


Initial display contents, initialization, and change ranges are displayed in the table
indicated below.

m
(Function mode 1) (Function mode 2)
Display Setting, change
Function Function Initialization display Initialization Setting contents
sequence contents
No. name contents
1 F-00 Base F-BASE 0060 Hz 60 Hz 30 to 120 (400) • When 120 Hz is switched to
frequency 400 Hz by F-30, a frequency
setting more than 120 Hz can be set.

o
2 F-01 Maximum F-MAX 0060 Hz 60 Hz 30 to 120 (400)
frequency
setting
3 F-02 Start Fmin 0.50 Hz 0.5 Hz 0.1 to 9.9 • The equipment starts running
frequency at this set value.

.c
adjustment
4 F-03 Motor input AVR AC 460 V 230/460 200,215,220,230 • The motor input voltage is set.
Input voltage /380,400,415
voltage setting 440,460,480
AVR AVRDEC OFF OFF ON/OFF • ON or OFF of the AVR
function function for deceleration
for is set. When dynamic
n decelera-
tion
braking torque is necessary
for deceleration, OFF is set.
5 F-04 Control CONTROL VC VC VC, VP1, VP2, • VC, VP1, VP2, VP3:
method VP3, SLV, V2 V/F characteristics
ta
setting SLV:Sensorless vector control
V2:Sensor vector control
6 F-05 Autotuning AUX AUTO NOR NOR NOR/AUT/NRT • At the first running after
Motor setting AUT/NRT is set, the
constant autotuning measurement
(NOTE 1) operation is executed.
Motor data AUX DATA NOR NOR NOR: Old Hitachi • The autotuning motor data
n

selection general purpose before starting autotuning


TMO: New measurement is data
Hitachi general equivalent to NOR.
purpose
AUT: Auto-
ie

tuning data
Motor AUX K 005.50 kW Ratedcapacity 3.7 to 160 • Set a capacity smaller than the
capacity ofeachinverter rated capacity as capacity
setting data.
Motor pole AUX P 4p 4p 2, 4, 6, 8 • The number of poles of the
count motor to be used is set.
setting
b

Motor AUX R1 1.004 Ratedcapacity 0 to 65.535


constant ofeachinverter
R1 setting
Motor AUX R2 0.776 Ratedcapacity 0 to 65.535
constant ofeachinverter
a

R2 setting
Motor AUX L 13.16 mH Ratedcapacity 0 to 655.35
constant ofeachinverter
L setting
NOTE 1: The motor constants R1, R2, L, M, J, Kp, Ti, and KPP vary with the capacity.

12-5
(Function mode 1) (Function mode 2)
Display Setting, change
Function Function Initialization display Initialization Setting contents
sequence No. name contents contents
6 F-05 Motor AUX M 123.60 mH Ratedcapacity 0 to 655.35 • Primary self inductance per
Motor M setting ofeachinverter phase.
constant constant
Motor AUX J 0.44 kgm2 Ratedcapacity 0 to 655.35 • Motor and machine inertia
J setting ofeachinverter
constant

m
Motor AUX Kp 002.00 2.0 0 to 100.00 • Smaller: High response
constant • Larger: Low response
Kp setting
Motor AUX Ti 00100 ms 100 ms 0 to 10000 • Set this item after the
constant feedback option PCB is
Ti setting installed.
Motor AUX KPP 001.00 1.0 0 to 100.00 • Set this item after the
constant feedback option PCB is

o
KPP setting installed.
7 F-06 Accelera- ACC 1 0030.00 s 30.00 s 0.01 to 3000 • When the fuzzy most
Accelera- tion time suitable acceleration and
tion time setting deceleration (F-10) are set,
the time displayed here is

.c
invalid, though it can be
set.
2-stage ACC 2 0015.00 s 15.00 s 0.01 to 3000 • The acceleration time can
acceleration be used when the input
time setting terminal CH1 is shorted.
• For input terminal
selection, refer to F-34
n Curve ACC LINE L L L (Linear),
input terminal.
• The curve pattern is set for
pattern S (S curve), acceleration and
selection U (U curve), deceleration respectively.
ta
for RU (reverse
acceleration U curve)
Accelera- ACC GAIN 02 2 (common to 1 to 10 • When the constant is set
tion and acceleration for one of acceleration and
deceleration and deceleration, it is common
curve deceleration) to both acceleration and
constant deceleration.
n

selection • See appendix 4.


8 F-07 Decelera- DEC 1 0030.00 s 30.00 s 0.01 to 3000S • When the fuzzy most
Decelera- tion time suitable acceleration and
tion time setting deceleration (F-10) are set,
the time displayed here is
ie

invalid, though it can be


set.
2-stage DEC 2 0015.00 s 15.00 s 0.01 to 3000S • The deceleration time can
deceleration be used when the input
time setting terminal CH1 is shorted.
• For input terminal
selection, refer to F-34
b

input terminal.
Curve DEC LINE L L L (Linear), • The curve pattern is set for
pattern S (S curve), acceleration and decelera-
selection U (U curve), tion respectively.
for RU (reverse
a

deceleration U curve)
Accelera- DEC GAIN 02 2 (common to 1 to 10 • When the constant is set
tion and acceleration for one of acceleration and
deceleration and decelera- deceleration, it is common
curve tion) to both acceleration and
constant deceleration.
selection • See appendix 4.

12-6
(Function mode 1) (Function mode 2)
Display Setting, change
Function Function Initialization display Initialization Setting contents
sequence No. name contents contents
9 F-08 Accelera- Fsp F 0000.0 Hz 0 Hz 0 to 400.0 • The frequency at which the
Accelera- tion stop acceleration operation is
tion halt frequency stopped temporarily is set.
setting
Accelera- Fsp TIME 00.0 s 0s 0 to 60.0 • The time that the acceleration
tion stop is stopped temporarily at a

m
time setting certain frequency during
acceleration is set.
10 F-09 Pattern PARAM REM REM REM/ • The parameter setting com-
command- OP1/OP2 manding source is selected.
ing method (Option REM (each operator),
selection connected) OP1 (option 1), OP2 (option
2)
11 F-10

o
Running
mode

Running RUN MODE NOR NOR NOR/OEN/ NOR: Normal running


mode GOD OEN: Energy conservation

.c
selection running
GOD: Fuzzy most suitable
acceleration and
deceleration running
Restarting RUN FRS ZST ZST fST/ZST fST: Restart after frequency
after FRS maching
signal ZST: 0 Hz start

12
n
F-11
selection
Multistage SPD 1 0000.00 Hz 0 Hz 0 to 120.0 (400) • The input terminal CF1 is set
Multistage speed and used.
speed 1 speed
ta
setting
Multistage SPD 2 0000.00 Hz 0 Hz 0 to 120.0 (400) • The input terminal CF2 is set
speed and used.
2-speed
setting
Multistage SPD 3 0000.00 Hz 0 Hz 0 to 120.0 (400) • The input terminals CF1 and
speed CF2 are set and used.
n

3-speed
setting
Multistage SPD 4 0000.00 Hz 0 Hz 0 to 120.0 (400) • The input terminals CF1 and
speed CF3 are set and used.
4-speed
ie

setting
Multistage SPD 5 0000.00 Hz 0 Hz 0 to 120.0 (400) • The input terminals CF2 and
speed CF3 are set and used.
5-speed
setting
Multistage SPD 6 0000.00 Hz 0 Hz 0 to 120.0 (400) • The input terminals CF1, CF2,
speed and CF3 are set and used.
b

6-speed
setting
Multistage SPD 7 0000.00 Hz 0 Hz 0 to 120.0 (400) • The input terminal CF3 is set
speed and used.
7-speed
a

setting

12-7
(Function mode 1) (Function mode 2)
Display Setting, change
Function Function Initialization display Initialization Setting contents
sequence No. name contents contents
13 F-20 DC braking DCB SW OFF OFF ON/OFF • DC braking
DC selection ON: DC braking available
injection OFF: DC braking unavailable
braking DC braking DCB KIND LVL LVL LVL/EDG • DC braking method selection
type LVL: Level operation
selection EDG: Edge operation

m
DC braking DCB F 0000.5 Hz 0.5 Hz 0 to 400.0 Hz • The frequency at which the
frequency DC braking starts is set.
selection
DC braking DCB V-STA 00 0 0 to 20 • The DC braking force at start
force selec- is set.
tion (at start)
DC braking DCB V-STP 00 0 0 to 20 • The DC braking force at stop
force selec- is set.

o
tion (at stop)
DC braking DCB T-STA 000.0 s 0s 0 to 600.0 • The DC braking time at start
time selec- is set.
tion (at start)
DC braking DCB T-STP 000.0 s 0s 0 to 600.0 • The DC braking time at stop

.c
time selec- is set.
tion (at stop)
DC braking DCB STOP-T 0.00 s 0s 0 to 5.00 The output frequency is
output cut- lowered to the DC braking
off time frequency and the free run
n adjustment time during execution of DC
braking is set.
14 F-21 Dynamic BRD-%ED 001.5% 1.5% 0 to 100.0 • The allowable usage ratio of
braking the braking resistor for 100
setting seconds is set. (NOTE 1)
15 F-22 Allowable IPS TIME 1.0 s 1.0 s 0.3 to 25 s • When an instantaneous power
ta
The instantaneous failure occurs, the allowable
allowable powerfailure time until the power failure is
usage time setting recovered is set.
ratio of Reclosing IPS WAIT 001.0 s 1.0 s 0.3 to 100.0 s • The waiting time until the
the standbyafter rerunning starts after an
braking instantaneous instantaneous power failure
resistor powerfailure occurs and is recovered is set.
n

for 100 recovered


seconds Instantaneous IPS POWR ALM ALM ALM/FTP/ ALM: Alarm output
is set. powerfailure RST/ZST ZST: 0 Hz start retry
restart FTP: Retry after frequency
selection matching is stopped
ie

RST: Rerunning start retry


Tripselection IPS TRIP OFF OFF ON/OFF When an instantaneous power
during stop failure occurs:
atunder ON: Trip
voltage OFF: Non-trip
16 F-23 Electronic E-THM CHAR SUB SUB CRT/SUB/FRE • Electronic thermal characteris-
Electronic thermal tic setting CRT: Constant
b

thermal characteristic torque characteristic


selection SUB: Reduced torque charac-
teristic
FRE: Free characteristic
Electronic E-THM LEVEL 100% 100% 20 to 120%
a

thermallevel
setting

NOTE 1: Initial setting of usage ratio 1.5% 055-075L/HF 0% 110-550L/HF

12-8
(Function mode 1) (Function mode 2)
Display Setting, change
Function Function Initialization display Initialization Setting contents
sequence No. name contents contents
16 F-23 Electronic E-THM A1 8.5A Rated capacity of 0 to 600.0 A
Electronic thermal each inverter
thermal characteristic
(NOTE 2) free setting
current (1)
Electronic E-THM F1 0000 Hz Rated capacity of 0 to 400 Hz

m
thermal each inverter
characteristic
free setting
frequency(1)
Electronic E-THM A2 8.5A Rated capacity of 0 to 600.0 A
thermal each inverter
characteristic
free setting

o
current (2)
Electronic E-THM F2 5 Hz Rated capacity of 0 to 400 Hz
thermal each inverter
characteristic
free setting

.c
frequency(2)
Electronic E-THM A3 13.0 A Rated capacity of 0 to 600.0 A
thermal each inverter
characteristic
free setting
current (3)
Electronic E-THM F3 73 Hz Rated capacity of 0 to 400 Hz
n thermal
characteristic
free setting
each inverter

frequency(3)
ta
17 F-24 Overload OLOAD LEVEL125% 125% 50 to 150% Under the sensorless vector
Overload restriction control, an overload is detected
restriction level setting from both the overload restric-
tion and torque limiter.
Overload OLOAD CONST01.0 1.0 0.3 to 31.0 When the setting is 31.0 in SLV
restriction or V2 control mode, the
constant overload restriction has no
setting effect.
n

Valid OLOAD ACC ON ON ON: Valid for Even if the function is set to
selection acceleration OFF, the overload restriction is
for overload Keep the invalid only for the first
restriction function ON acceleration when the forward
ie

acceleration for operation. and reverse run command is


turned on.
18 F-25 Software S-LOCK MD1 MD1 MD0/MD1 MD0, MD1: Terminal software
lock MD2/MD3 lock (SFT)
selection MD2, MD3: Software lock
(NOTE 1)
b

NOTE 1: When MD0 is set and the input terminal SFT is turned ON, the data of all functions is locked. When MD2 is
set (stored), the data of all the functions is locked. During locking, no data can be changed. MD1, MD3
can set only the output frequency.

NOTE 2: Electronic thermal characteristic free setting current and frequency depends on the inverter rating.
a

12-9
(Function mode 1) (Function mode 2)
Display Setting, change
Function Function Initialization display Initialization Setting contents
sequence No. name contents contents
19 F-26 Frequency LIMIT L 0000.0 Hz 0 Hz 0 to 120.0 The lower limit of the frequency
Frequency lower limiter (400) Hz to be set is set. When the lower
limiter setting limit is 0, the setting is invalid.
Frequency LIMIT H 0000.0 Hz 0 Hz 0 to 120.0 The upper limit of the frequency
upper (400) Hz to be set is set. When the upper
limiter limit is 0, the setting is invalid.
setting

m
20 F-27 Jump JUMP F1 0000.0 Hz 0 Hz 0 to 400 Hz • The section where frequencies
Jump frequency are to be jumped is set.
frequency setting (1) • Up to three locations can be
set.
• When the number of locations
is 0, the setting is invalid.
Jump JUMP F2 0000.0 Hz 0 Hz 0 to 400 Hz
frequency

o
setting (2)
Jump JUMP F3 0000.0 Hz 0 Hz 0 to 400 Hz
frequency
setting (3)
Jump JUMP W 0.5 Hz 0.5 Hz 0 to 9.9 Hz • The frequency width where

.c
frequency frequencies are jumped is set.
width setting
21 F-28 STOP key STOP-SW ON ON ON: STOP key Whether or not to make the
validity valid STOP key valid during terminal
selection OFF: STOP key running is selected. In the
during invalid Remote mode, the STOP key is
n terminal always valid.
running
22 F-29 Running F/R SW FRE FRE FWD/REV/ FWD: Only forward run
direction FRE REV: Only reverse run
selection FRE: Both forward run and
reverse run valid
ta
Reverse run F/R PREV OFF OFF ON/OFF Reverse run prevention
prevention ON:
selection OFF:
Reduced F/R RVS 6 6 0 to 6
voltage
soft start
setting
23 F-30 Maximum F-MAX-L 120 Hz 120 Hz 120/400 Hz Maximum frequency switching:
n

frequency 120: 120 Hz 400: 400 Hz


selection
24 F-31 Analog input IN ANA 10 V 10 V 10/5 Input voltage maximum level
External voltage 10: Max. 10 V 5: Max. 5 V
analog selection
ie

frequency External IN EXS 0000.0 Hz 0 Hz 0 to 120.0 (400) • Frequency at which the


command frequency external input starts
start setting
External IN EXE 0000.0 Hz 0 Hz 0 to 120.0 (400) • Frequency at which the
frequency external input is maximized
end setting
External IN EX%S 000% 0% 0 to 100 • Input start level
b

frequency
start setting
rate
External fre- IN EX%E 100% 100% 0 to 100 • Input maximum level
quency end
a

setting rate
External IN LEVEL 0 Hz 0 Hz 0 Hz/ExS EXS: Start at EX%S setting
command rate or less
start point
selection

12-10
(Function mode 1) (Function mode 2)
Display Setting, change
Function Function Initialization display Initialization Setting contents
sequence No. name contents contents
Frequency IN F-SAMP 8 8 1 to 8
command
sampling
frequency
setting
25 F-32 Arrival ARV PTN CST CST CST/PAT/ANY CST: Output at constant

m
Frequency signal output frequency arrival
arrival pattern PAT: Output of more than
output selection set frequency
signal ANY: Output of only set
frequency
Arrival ARV ACC 0.0 Hz 0 Hz 0 to 400.0
frequency
rate setting

o
for
acceleration
Arrival ARV DEC 0.0 Hz 0 Hz 0 to 400.0
frequency
rate setting

.c
for
deceleration
26 F-33 Overtorque OV-TRQ V 100% 100% 0 to 250 • During control of SLV
Over- signal rate and V2: Power running
torque setting overtorque level
signal (for power • During control of VC
(NOTE 1) running)
n and VP1 to VP3:
Warning level for power
running regenerative
overload
• When 0 is set: Any signal
is not output.
ta
Overtorque OV-TRQ R 100% 100% 0 to 250 • During control of SLV
signal rate and V2: Regenerative
setting overtorque level
(for regen- • During control of VC
eration) and VP1 to VP3: No
effect
• When 0 is set: Any signal
n

is not output.
27 F-34 Input IN-TM 1 RS RS reset RS and 17
Intelligent terminal 1 terminal other terminals
terminal setting
input Input IN-TM 2 AT AT current AT and 17
ie

terminal terminal 2 input selection other terminals


setting setting terminal
Input IN-TM 3 JG JG jogging JG and17
terminal 3 terminal other terminals
setting
Input IN-TM 4 FRS FRS free FRS and 17
terminal 4 run other terminals
b

setting terminal
Input IN TM 5 CH1 CH1 2-stage CH1 and 17
terminal 5 acceleration other terminals
setting and
a

deceleration
terminal

NOTE 1: When setting 20% or less, the error will increase (± 20% or more).
Therefore, set 20% or more.

12-11
(Function mode 1) (Function mode 2)
Display Setting, change
Function Function Initialization display Initialization Setting contents
sequence No. name contents contents
27 F-34 Input IN-TM 6 USP USP USP and 17
Intelligent terminal 6 Power-ON other terminals
terminal setting restart
input preventionl
terminal Input IN-TM 7 CF1 CF1 CF1 and 17
setting terminal 7 Multi-stage other terminals
setting input

m
terminal
Input IN-TM 8 REV REV reverse REV and17
terminal 8 run command other terminals
setting input terminal
Input IN-TMO/C-1 NO NO NO/NC • Input terminal setting
terminal 1 NO: ON when short-
NO/NC circuited

o
setting NC: ON when opened
Input IN-TM O/C-2 NO NO NO/NC • Input terminal setting
terminal 2 NO: ON when short-
NO/NC circuited
setting NC: ON when opened

.c
Input IN-TM O/C-3 NO NO NO/NC • Input terminal setting
terminal 3 NO: ON when short-
NO/NC circuited
setting NC: ON when opened
Input IN-TM O/C-4 NO NO NO/NC • Input terminal setting
terminal 4 NO: ON when short-
NO/NC circuited

28
n F-35
setting
Output OUT-TM 1 FA1 FA1 FA1/RUN/OTQ
NC: ON when opened
Output terminal setting
Intelligent terminal FA1: Frequency arrival signal
terminal 11 setting RUN: Signal during run
ta
output OTQ: Overtorque signal
terminal Output OUT-TM 2 RUN RUN FA1/RUN/OTQ Output terminal setting
setting terminal FA1: Frequency arrival signal
12 setting RUN: Signal during run
OTQ: Overtorque signal
Alarm OUT-TM O/C-A NC NC NC/NO • Alarm output terminal
output contacts a and b setting
n

NO/NC NC: b contact


setting NO: a contact
Output OUT-TM O/C-1 NO NO NO/NC • Output terminal 1 contacts
terminal a and b setting
11 NO/NC NO: b contact
ie

setting NC: a contact


Refer to C 21
Output OUT-TM O/C-2 NO NO NO/NC • Output terminal 12 contacts
terminal a and b setting Short-
12 NO/NC NO: a contact
NC: b contact
29 F-36 Carrier CARRIER 16.0 kHz 16.0 kHz 2.0 to 16.0 Hz • The IPM carrier frequency
b

frequency Selectable is set.


setting in 0.1 steps • The setting value varies
with the capacity.
a

12-12
(Function mode 1) (Function mode 2)
Display Setting, change
Function Function Initialization display Initialization Setting contents
sequence contents
No. name contents
30 F-37 Monitor MONITOR A-F A-F A-F/A/T/D-F • The FM terminal monitor
signal signal output is selected.
selection A-F: Analog frequency
T: Torque monitor
A: Current monitor
D-F: Digital frequency

m
31 F-38 Trip history INIT TCNT CNT CNT CNT/CLR • Trip count deletion selection
Initiali- count clear CNT: Trip counting is
zation continued.
CLR: The trip count is cleared.
Debug INIT DEBG OFF OFF ON/OFF • Debug mode setting ON or
mode OFF
display OFF: The debug mode is
selection turned off.

o
NOTE 1 ON: The debug mode is turned
on.
Digital INIT DOPE FWD FWD FWD/REV • The digital operator running
operator direction is set.
rotation FWD: Forward run

.c
direction REV: Reverse run
selection
Selection of INIT RESET ON ON ON/OFF ON: Alarm release when reset
reset on
performance OFF:Alarm release when reset
n off
32 F-39 Encode OP P 01024 pulse 1024 255 to 65535 Effective with option board
Option pulse (J-FB)
setting number
setting
Control OP MODE ASR ASR ASR/APR
ta
mode
selection
Ro-To OP RO-TO OFF OFF OFF/ON Keep OFF. (No use)
option
selection
33 F-40 Stop OR POS IN IN IN/OUT Effective with option board
Orientation position (J-FB)
n

setting setting
switching
Stop OR P 00000 pulse 0 0 to 4095
position
setting
ie

Speedsetting OR FC 0005.0 Hz 5.0 Hz 0 to 400 Hz


Direction OR TURN FWD FWD FWD/REV
setting
Completion OR L 00005 pulse 5 0 to 10000
rangesetting
Completion OR TW 0.00 s 0 0 to 9.99
delay time
b

setting

NOTE 1 : Keep debug mode " OFF " , this is factory use only.
a

12-13
(Function mode 1) (Function mode 2)
Display Setting, change
Function Function Initialization display Initialization Setting contents
sequence contents
No. name contents
34 F-41 Position PO EGRP FB FB FB/REF Effective with option board
Electronic setting (J-FB)
gear switching
setting Numerator PO EGR-N 00001 1 1 to 9999
of ratio
Denominator PO EGR-D 00001 1 1 to 9999

m
Feed for- PO FFWG 000.00 0 0 to 655.35
ward gain
Position PO G 000.50 rad/s 0.5 0 to 100
loop gain rad/s
35 F-42 Torque TRQ LIMIT REM REM REM/OP1/OP2 REM: Each operator
Torque limit PO1: Option 1
limit setting PO2: Option 2

o
setting switching
(Note 1) Plus torque TRQ FWD 150% 150% 20 to 150%
limit
Minus TRQ REV 150% 150% 20 to 150% Regenerative mode
torque limit

.c
36 F-43 PID target PID IN-SEL IN IN IN/OUT
PIDcontrol value input
setting method
switching
selection
PID target PID LVL 000.00% 0% 0 to 200%
n value setting
P gain setting PID P 1.0 1.0 0.1 to 5.0
I gain setting PID I 01.0S 1.0 0 to 15.0
D gain setting PID D 000.0 000.0 0 to 100
Selection PID MODE MD0 MD0 MD0 to 4
ta
37 F-46 Transmission COM BAU 00600 bps 600 300/600/1200/ Effective with option board
Communi- speed 2400/4800/9600/ (J-CM)
cation selection 19200
protocol Station COM NUMBER 01 1 1 to 32
setting number
selection
Transfer bit COM LENGTH 8 8 8/7
n

length
selection
Parity COM PAR-SEL1 ON ON ON/OFF
ON / OFF
selection
ie

Parity COM PAR-SEL2 EVN EVN EVN/ODD


even / odd
selection
Stop bit COM STOPBIT 2 2 2/1
length
selection
b
a

NOTE 1: Smaller levels of torque limit and overload restriction are given top priority and valid for any control
method.

12-14
(Function mode 1) (Function mode 2)
Display Setting, change
Function Function Initialization display Initialization Setting contents
sequence contents
No. name contents
38 F-47 Main body OP-ERR1 STP STP STP/RUN Effective with option board
Option operation
PCB error selection for
setting option PCB
error 1
Main body OP-ERR2 STP STP STP/RUN

m
operation
selection for
option PCB
error 2
39 F-48 Setting for RELAY RYA RUN RUN CST/PAT Effective with option board
Selection RYA /ANY/RUN (J-RY)
of relay terminal /OTQ/NOR
output Setting for RELAY RYB CST CST CST: Arrival signal

o
RYB (constant speed)
terminal PAT: Arrival signal
Setting for RELAY RYC OTQ OTQ (set frequency or more)
RYC ANY: Arrival signal

.c
terminal (set frequency only)
RUN: Running signal
OTQ: Over torque signal at
SLV, SLV2/Overload
signal at V/F control
NOR: No output
n
ta
n
ie
b
a

12-15