0% found this document useful (0 votes)
115 views32 pages

Raxton CV M20 Ex e Breather PAGE 14-15

Raxton Limited specializes in electrical thread conversions and cable installation solutions for hazardous areas, offering a wide range of certified products for industries such as oil and gas, mining, and power generation. The company emphasizes quality standards, environmental compliance, and custom design capabilities, ensuring high reliability and performance in critical applications. Their product offerings include adaptors, reducers, stopping plugs, cable glands, and various fittings, all designed to meet stringent safety certifications.

Uploaded by

melek.kharrat
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
115 views32 pages

Raxton CV M20 Ex e Breather PAGE 14-15

Raxton Limited specializes in electrical thread conversions and cable installation solutions for hazardous areas, offering a wide range of certified products for industries such as oil and gas, mining, and power generation. The company emphasizes quality standards, environmental compliance, and custom design capabilities, ensuring high reliability and performance in critical applications. Their product offerings include adaptors, reducers, stopping plugs, cable glands, and various fittings, all designed to meet stringent safety certifications.

Uploaded by

melek.kharrat
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 32

ELECTRICAL THREAD CONVERSIONS & CABLE INSTALLATION

SOLUTIONS FOR HAZARDOUS AREAS


CONTENTS

Page
About Us / Custom Design and Manufacturing 3
Quality Standards / Material Specifications 4

Certification Matrix 5

Adaptors & Reducers


Adaptors 6
Reducers 7
Adaptors - Insulated 8
Adaptors - Male to Male & Female to Female 9
Adaptors - Right Angle 10
Adaptors - Swivel 11

Stopping Plugs & Breather Drains


Stopping Plugs 12 - 13
Breather Drains 14 - 15

Specialised Fittings & Cable Gland Accessories


Barrier Stopper Boxes for Cable Glands and Rigid Conduit 16
Unions 17
Nipples, Couplers & Bushes 18
Locknuts, Washers & Serrated Washers 19
Earth Lead Adaptors & Threaded Earth Plates 20
Earthing Locknuts & Earth Tags 21
Shrouds 22

Cable Glands
Nylon Ex e & Ex i Glands 23

Flexible Conduit & Accessories


Barrier Stopper Boxes for Flexible Conduit 24
Flexible Conduit 25 - 26

Technical Information
Thread Selection Dimensions 27
Product Coding 28
Hazardous Areas 29
Ingress Protection 30

2
ABOUT US

Raxton Limited is a subsidary of Cooper Industries plc. Cooper


Industries is a global leader in the manufacturing of electrical products
and energy safety solutions.
Established in 1976, Raxton Limited is an industry leader for the
supply of electrical thread conversion and accessory products that
provide solutions for cable and enclosure installations fitted within
Adaptors & potentially explosive or hazardous environments, (Ex certified
Reducers products). With extensive applications within the oil and gas
industries, Raxton products are also certified for dust and mining
applications.
Industries Served
! Refining ! Mining
! Offshore Exploration & Production ! Power Generation
Stopping Plugs & ! Landbased Drilling & Production ! Dust Environments
Breather Drains
Standard Products
Through the proven quality and high reliability of our products and
a reputation for providing superior customer service within our key
markets, Raxton is recognised as a leading international premium
Specialized fittings brand for thread conversion products. Our standard product range
& Cable Gland includes extensive material options on all industry thread types and
accessories sizes.

Custom Design & Manufacturing


As well as being a renowned market leader for the development of
thread conversion products, Raxton’s capability extends to offering
design and manufacturing expertise to many types of specialist
requirements for products and components across a wide range of
industry sectors.
At our UK factory, the Raxton engineering design team has extensive
experience in providing solutions for many types of applications
requiring machined or cast components in all types of materials,
for both hazardous areas and non-hazardous areas. With over 30
years of experience in designing products for the oil & gas and
petrochemical industries, we understand the value of high quality
products required to be used in both critical and
environmentally harsh applications. In
addition, our wide knowledge of materials
enables us to offer solutions in metallic
or plastic nylon designs.
To support our engineering
team, our comprehensive
workshop facilities can
provide quick turn-around
samples, prototypes and full
production models.
For specific advice or consultation on
your application, our engineered product sales department is
ready to assist.
3
QUALITY STANDARDS & MATERIAL SPECIFICATIONS

Quality Standards
Raxton Limited holds the International Quality Assurance Standard,
ISO9001, which covers all company activities from design and
development, to manufacture, sales and after sales service.
Bureau Veritas EN ISO 9001:2008

Environmental
Raxton Limited is committed to continual improvement in its
environmental performance, and to operate in full compliance with
all applicable current and future legislation and regulations. This is
achieved by the implementation of an Environmental Management
System which satisfies as a minimum the standards included in
ISO14001: 2004, and the adoption of best practices in all its
operations. The Environmental Management System is based
upon the following principles:
! The company’s facilities, processes, products and operations
shall be managed in such a way that waste scrap, pollution and
natural resource consumption are controlled, reduced or
eliminated year on year.
! The environmental impact of the company’s operations shall be
monitored and adverse effects minimized or eliminated.

Material Specifications and Plating


Raxton’s manufacturing capabilities enable us to offer an extensive
range of material options on all our products.
Our standard range of material includes:
! Brass: BS2874: 1985 CZ121
! Stainless Steel: BS970 PT3 316 S11
! Nylon: 30% Glass Filled Nylon 66
! Aluminium: BS1474/1 6082 T4 or T6
! Aluminium Bronze: BS1400 1985 AB2 or BS2874:1986 CA104
! Mild Steel: BS970 PT3 230M07
! Metallic products are also available in a variety of finishes
including Nickel, Electro Zinc, Zinc Passivated, Chromatised,
Electroless Nickel and Anodised.
Thread Specifications
Isometric (ISO) to BS3643:1981 and ISO 965 Pts 1 & 3
Imperial (ET) to BS31:1940 (1979)
National Pipe Thread (NPT) to ANSI/ASME:1983
British Standard Pipe (BSP) to BS21:1985
Pg to DIN 40430:1971

4
PRODUCT CERTIFICATION

Product Type Certifying Approvals

All products Metric and NPT


IECEx ATEX Gas & Dust ATEX Mining North America Brazil Russia

Adaptors &
Reducers
" " " " " "

Insulated
Adaptors
" " " " "

Male to Male and


Female to Female " " " " "
Adaptors

Right Angle
Adaptors
" " " " "

Swivel
Adaptors
" " "

Stopping
Plugs
" " " " " "

Stopping
Plugs
" " " " "

Breather Drains
Exd
" " " " "

Breather Drains
Exe " " " " "

Barrier Stopper Boxes


for Cable Glands " " " " "
and Rigid Conduit

Unions " " " " "

Earth Lead
Adaptors/ Threaded " " " " "
Earth Plates

Nylon Cable
Glands
" "

Barrier Stopper
Boxes for " " "
Flexible Conduit

5
ADAPTORS

Raxton Exd/Exe Adaptors provide a means of connection between dissimilar thread forms
or sizes. Certified Adaptors should be used following the basic rules in line with good
engineering practice:- no more than one conversion Adaptor should be used at one time
on any given cable entry. Stopping Plugs should be fitted directly into unused entries of
Type AJ Round the equipment and not into an Adaptor.
Metallic Adaptors have a hexagonal body. Where space is a critical factor, Adaptors can be
offered with a round body with a diameter equal to the A/F dimension of the standard item.
Nylon Adaptors are Exe only and are produced with a round body.
Exe Adaptors are supplied fitted with an ‘O’ ring to maintain the IP integrity of the
installation.
Type AB Hex
Raxton Adaptors are marked with the applicable approval number and size.
Independently tested to IP68.

Product Dimensions Certification


Thread Metallic Nylon Male Metallic Nylon Head Code of Protection Categories
Male Thread Thread Max Thread A/F Dia. (mm) ATEX: I M2, Ex d IMb, Ex e I Mb, or II G, Ex d IIC Gb, Ex e IIC Gb, Ex tb IIIC Db
Max Bore Bore (mm) IECEx: Ex d I/IIC, Ex e I/IIC, Ex tb IIIC Db,
M16 11.0 8.0 20.8 24.0 CSA: Ex d IIC Class 1, Zone 1, AEx d IIC (Brass and Stainless only)
M20 14.3 12.5 23.4 27.5 GOST: ExdeI/IICU, ExdeIICU, ExeIIU
M25 20.5 17.5 27.9 35.5 INMETRO: BR-Ex de 1/IIC Mb/Gb, BR-Ex tD A21 IP 66/67
M32 26.8 24.5 37.6 41.0 Nylon Adaptors only:
M40 33.5 32.5 47.2 50.0 ATEX: II 2 GD, Ex e IIC Gb, Ex tb IIIC Db
M50 44.0 42.5 56.4 60.0 IECEx: Ex e IIC Gb, Ex tb IIIC Db
M63 55.2 53.0 70.1 75.0 GOST: ExeIIU
M75 66.7 64.0 80.0 85.0 INMETRO: BR-Ex e IIC Gb, BR-Ex tD A21 IP 66/67
M90 80.0 76.0 105.0 100.0 Compliance Standards
ATEX / INMETRO / GOST: EN 60079-0:2009, EN 60079-1: 2007, EN 60079-7: 2007, EN
60079-31:2008
IECEx: IEC 60079-0:2004, IEC 60079-1:2003, IEC 60079-7:2006-07
CSA : CAN/CSA-E79-0-95, CAN/CSA-E79-1-95, UL 2279 1997, IEC 60079-0:1998, IEC 60079-1:1998
(Brass and Stainless only)
Nylon Adaptors only:
ATEX / INMETRO / GOST: EN 60079-0:2009, EN 60079-7: 2007, EN 60079-31:2009
IECEx: IEC 60079-0:2007, IEC 60079-7:2006, IEC 60079-31:2008
* Certificate Details
ATEX: SIRA10ATEX1225X, SIRA10ATEX3335U
IECEx: IEC Ex SIR 07.0010X, IEC Ex SIR 10.0164U
CSA: CSA 200455-1003277 (Brass and Stainless only)
GOST: POCC GB.ГБ06.B01060

*
INMETRO: NCC 5871/09 U
TEMPERATURE

*Minimum 8 full threads parallel 5 full threads taper


The item is classified as a component and is therefore not given a temperature rating.
Nylon temperature range -20ºC to 65ºC, 'O' ring -30ºC to 125ºC
GF Nylon is UL rated @ H.B. @ 1.5mm.

Product Codes
DIGIT 1+2 DIGIT 3 DIGIT 4 & 5 Male DIGIT 6 & 7 Female DIGIT 8 DIGIT 9 DIGIT 10
Description Code Code
Material Thread Reference Approval Special Plating
(Adaptors)
M-F HEX AB BRASS A M16 11 ½" NPT 42 ATEX Exde A None (standard) X or blank None Blank
M-F ROUND AJ ALUMINIUM B M20 12 ¾" NPT 43 IECEx Exde R Customer Special S Nickel N
MILD STEEL C M25 13 1" NPT 44 Zinc Z
STAINLESS STEEL E M32 14 1¼" NPT 45 For other Chromatised C
GLASS FILLED NYLON M M40 15 1½" NPT 46 approvals Special S
please see
M50 16 2" NPT 47
product
M63 17 2½" NPT 48 coding list on
M75 18 3" NPT 49 page 28
M90 81 3½" NPT 86
M100 82 4" NPT 87 Industrial X or Blank
Other sizes / threads are available on request

Adaptors Brass 1” NPT(M) M32(F) Exde PART NUMBER


PRODUCT CODING EXAMPLE
AB A 44 14 A = ABA4414A

6
REDUCERS

Raxton Exd/Exe Reducers effectively reduce the threaded entry diameter of an enclosure to
accept a gland or fitting with a smaller thread. Reducers may also be supplied to accept
smaller glands of alternative threads.
Following the basic rules in line with good engineering practices, no more than one
Type BJ Round Reducer should be used at any one time. Stopping Plugs should be fitted directly into
unused entries of the equipment and not into a Reducer.
Metallic Reducers are supplied with a hexagonal head as standard. Where space is a
critical factor, Reducers with a circular head can be offered with a diameter equal to the
A/F dimension of the hexagonal head.
Type BB Hex
Nylon Reducers are Exe only and designed with a circular head. Exe Reducers are supplied
with an ‘O’ ring to maintain the IP integrity of the installation.
Raxton Reducers are marked with the applicable approval number and size.
Independently tested to IP68.

Product Dimensions Certification


Thread Metallic Nylon Head Code of Protection Categories
Thread A/F Dia. (mm) ATEX: I M2, Ex d IMb, Ex e I Mb, or II G, Ex d IIC Gb, Ex e IIC Gb, Ex tb
(mm) IIIC Db
M16 20.8 22.0 IECEx: Ex d I/IIC, Ex e I/IIC, Ex tb IIIC Db
M20 23.4 25.0 CSA: Ex d IIC Class 1, Zone 1, AEx d IIC (Brass and Stainless only)
M25 27.9 30.0 GOST: ExdeI/IICU, ExdeIICU, ExeIIU
M32 37.6 38.0 INMETRO: BR-Ex de 1/IIC Mb/Gb, BR-Ex tD A21 IP 66/67
M40 47.2 46.0 Nylon Reducers only:
M50 56.4 56.0 ATEX: II 2 GD, Ex e IIC Gb, Ex tb IIIC Db
M63 70.1 70.0 IECEx:Ex e IIC Gb, Ex tb IIIC Db
M75 80.0 81.0 GOST: ExeIIU
M90 105.0 96.0 INMETRO: BR-Ex e IIC Gb, BR-Ex tD A21 IP 66/67
Compliance Standards
ATEX / INMETRO / GOST: EN 60079-0:2009, EN 60079-1: 2007, EN
60079-7: 2007, EN 60079-31:2008
IECEx: IEC 60079-0:2004, IEC 60079-1:2003, IEC 60079-7:2006-07
CSA : CAN/CSA-E79-0-95, CAN/CSA-E79-1-95, UL 2279 1997, IEC
60079-0:1998, IEC 60079-1:1998
Nylon Reducers only:
ATEX / INMETRO / GOST: EN 60079-0:2009, EN 60079-7: 2007, EN
60079-31:2009
IECEx: IEC 60079-0:2007, IEC 60079-7:2006, IEC 60079-31:2008
Certificate Details
ATEX : SIRA10ATEX1225X, SIRA10ATEX3335U
IECEx: IEC Ex SIR 07.0010X, IEC Ex SIR 10.0164U
CSA: CSA 200455-1003277 (Brass and Stainless only)

*
GOST: POCC GB.ГБ06.B01060
INMETRO: NCC 5871/09 U

*Minimum length of thread 10mm


TEMPERATURE
The item is classified as a component and is therefore not given a temperature rating. Nylon temperature
range -20ºC to 65ºC, 'O' ring -30ºC to 125ºC
GF Nylon is UL rated @ H.B. @ 1.5mm.

Product Codes
DIGIT 1+2 DIGIT 3 DIGIT 4 & 5 Male DIGIT 6 & 7 Female DIGIT 8 DIGIT 9 DIGIT 10
Description Code Code
Material Thread Reference Approval Special Plating
(Reducers)
M-F HEX BB BRASS A M16 11 ½" NPT 42 ATEX Exde A None (standard) X or blank None Blank
M-F ROUND BJ ALUMINIUM B M20 12 ¾" NPT 43 IECEx Exde R Customer Special S Nickel N
MILD STEEL C M25 13 1" NPT 44 Zinc Z
STAINLESS STEEL E M32 14 1¼" NPT 45 For other Chromatised C
GLASS FILLED NYLON M M40 15 1½" NPT 46 approvals Special S
please see
M50 16 2" NPT 47
product
M63 17 2½" NPT 48 coding list on
M75 18 3" NPT 49 page 28
M90 81 3½" NPT 86
M100 82 4" NPT 87 Industrial X or Blank
Other sizes / threads are available on request

Reducer Stainless Steel 1” NPT(M) M32(F) Exde PART NUMBER


PRODUCT CODING EXAMPLE
BB E 14 13 A = BBE1413A

7
INSULATED ADAPTORS

Raxton Insulated Adaptors provide a means to isolate the earth of the supply cable from
the load equipment thus reducing the risk of damage to electronic equipment within the
enclosure in the event of a short circuit to ground through the enclosure. Insulated
Type DB
Adaptors also reduce the problems of electrical noise on the armour affecting the clean
earth required by some sensitive instruments. Single point grounding can reduce the
circulating current that can cause heating of high capacity cables.
Cable gland and cable can still be earthed externally with the use of an earth tag fitted
between the cable gland and the Insulated Adaptor.
Raxton Insulated Adaptors are marked with the appropriate approval number and size.

Certification
Code of Protection Categories
ATEX: Ex d IIC
IECEx: Ex d IIC
GOST: Ex d IICU
INMETRO: BR-Ex d IIC Gb, BR-Ex tD A21 IP 66/67
Compliance Standards
ATEX / INMETRO / GOST: EN 50014:1997, EN
Product Dimensions 50018:2000, EN 50019: 2000, EN 5081-1-1:1998
IECEx: IEC 60079-0:2007, IEC 60079-1:2007, IEC 60079-31:2008
Thread Protrusion Bore Dia. Certificate Details
(mm) (mm) (mm)
ATEX: SIR 11ATEX1219X
M16 45.0 11.0 30.0 IECEx: SIR 11.0099X
M20 45.0 14.3 42.0
GOST: POCC GB.ГБ06.B01060
M25 45.0 20.5 47.0 INMETRO: NCC 5871/09 U
M32 45.0 26.8 54.0
TEMPERATURE
M40 45.0 33.5 62.0
The item is classified as a component and is therefore
M50 45.0 44.0 77.0
not given a temperature rating.
M63 45.0 55.2 87.0
Nylon temperature range -20ºC to 130ºC.
M75 45.0 66.7 102.0
GF Nylon is UL rated @ H.B. @ 1.5mm

* Enclosure

* Insulated Adaptor
Cable Gland
Connection
Device

Cable / Conduit

Bonding Point

Ground

*Minimum 8 full threads parallel 5 full threads taper

Product Codes
DIGIT 1+2 DIGIT 3 DIGIT 4 & 5 Male DIGIT 6 & 7 Female DIGIT 8 DIGIT 9 DIGIT 10
Description Code Code
Material Thread Reference Approval Special Plating
(Insulated Adaptors)
INSULATED M-F DB BRASS A M16 11 ½" NPT 42 ATEX Exde A None (standard) X or blank None Blank
INSULATED M-M DD ALUMINIUM B M20 12 ¾" NPT 43 IECEx Exde R Customer Special S Nickel N
INSULATED F-F DE MILD STEEL C M25 13 1" NPT 44 For other Zinc Z
STAINLESS STEEL E M32 14 1¼" NPT 45 approvals Chromatised C
GLASS FILLED NYLON M M40 15 1½" NPT 46 please see Special S
M50 16 2" NPT 47 product
M63 17 2½" NPT 48 coding list on
page 28
M75 18 3" NPT 49

Ins. Adaptors Brass M32(M) M32(F) Exde PART NUMBER


PRODUCT CODING EXAMPLE
DB A 14 14 A = DBA1414A

8
MALE TO MALE / FEMALE TO FEMALE ADAPTORS

Type AU Hex (F-F) Male to Male Adaptors provide a connection between two female threads of the same or
dissimilar thread forms.
Female to Female Adaptors provide a connection between two male threads of the same or
dissimilar thread forms.
Type BJ Round
In each case, thread combinations can reduce by one size of the same thread form or to
the equivalent of another form:
e.g. M25 x M20 or M25 x 1/2"NPT
Both Male to Male and Female to Female Adaptors are marked with the appropriate
approval number and size.
Type AR (M-M)

Type AX Round (F-F)

Product Dimensions Certification


Thread Length Bore Dia. A/F Code of Protection Categories
(mm) (mm) (mm) ATEX: I M2, Ex d IMb, Ex e I Mb, or II GD, Ex d IIC Gb,
M16 38.0 11.0 18.0 Ex e IIC Gb, Ex tb IIIC Db
M20 38.0 14.3 23.4 IECEx: Ex d I/IIC Mb/Gb Ex e I/IIC Mb/Gb, Ex tb IIIC Db
M25 38.0 20.5 28.0 GOST: ExdIICU
M32 38.0 26.8 37.6 INMETRO: BR-Ex d IIC Gb, BR-Ex tD A21 IP 66/67
Compliance Standards
ATEX / INMETRO / GOST: EN 60079-0:2009, EN 60079-1:
2007, EN 60079-7: 2007, EN 60079-31:2008
IECEx: IEC 60079-0:2007-10, IEC 60079-1:2007-04, IEC
* * 60079-7:2006-07, IEC 61241-1:2004
Certificate Details
ATEX : SIRA10ATEX1226U
IECEx: IEC Ex SIR09.0084U
GOST: POCC GB.ГБ06.B01060
INMETRO: NCC 5871/09 U
TEMPERATURE
The item is classified as a component and is therefore not given a temperature rating.

*Minimum 6 full threads parallel 5 full threads taper

Product Codes
DIGIT 1+2 DIGIT 3 DIGIT 4 & 5 Male DIGIT 6 & 7 Female DIGIT 8 DIGIT 9 DIGIT 10
Description Code Code
Material Thread Reference Approval Special Plating
(Adaptors)
M-M AR BRASS A M16 11 ½" NPT 42 ATEX Exde A None (standard) X or blank None Blank
F-F HEX AU ALUMINIUM B M20 12 ¾" NPT 43 IECEx Exde R Customer Special S Nickel N
F-F ROUND AX MILD STEEL C M25 13 1" NPT 44 For other Zinc Z
STAINLESS STEEL E M32 14 1¼" NPT 45 approvals Chromatised C
GLASS FILLED NYLON M M40 15 1½" NPT 46 please see Special S
M50 16 2" NPT 47 product
M63 17 2½" NPT 48 coding list on
page 28
M75 18 3" NPT 49

M-M Adp Brass M20(M) M20(F) Exde PART NUMBER


PRODUCT CODING EXAMPLE
AR A 12 12 A = ARA1212A

9
RIGHT ANGLE ADAPTORS

Raxton Right Angle Adaptors provide a means of connection where protrusion space is
Type FG (M-F) limited whilst simultaneously, if necessary, converting the entry thread to that of a different
type or reducing size and/or gender of the female thread.
Right Angle Adaptors can be supplied either with male or female thread entries, or
alternatively with female to female thread entries and are marked with the applicable
approval number and size.
Protrusion dimensions are shown in the table below.

Type FG (M-F)

Product Dimensions Certification


Thread Height Bore Male Bore Size Code of Protection Categories
Assembly (mm) (mm) (mm) ATEX: I M2, Ex d IMb, Ex e I Mb or II GD, Ex d IIC Gb,
M16 45.0 11.0 9.0 Ex e IIC Gb, Ex tb IIIC Db
M20 51.0 14.3 15.0 IECEx: Ex d I/IIC Mb/Gb, Ex e I/IIC Mb/Gb, Ex tb IIIC Db
M25 57.0 20.5 20.8 GOST: ExdIICU
M32 66.0 26.8 26.8 INMETRO: BR-Ex d IIC Gb, BR-Ex tD A21, IP66/67
M40 75.0 33.5 33.5 Compliance Standards
M50 86.0 44.0 44.0 ATEX / INMETRO / GOST: EN 60079-0:2009 EN60079-1:2007 EN 60079-7:2007 EN 60079-31:2008
M63 101.5 55.2 55.0 IECEx: IEC Ex SIR 09.0086U
M75 119.0 66.7 66.5 60079-7:2006-07
Certificate Details
ATEX: SIRA 10ATEX1228U
IECEx: IEC Ex SIR.09.086U

* GOST: POCC GB.ГБ06.B01060


INMETRO: NCC 5871/09 U
TEMPERATURE
The item is classified as a component and is therefore not given a temperature rating.
*

*Minimum 6 full threads parallel 5 full threads taper


Product Codes
DIGIT 1+2 DIGIT 3 DIGIT 4 & 5 Male DIGIT 6 & 7 Female DIGIT 8 DIGIT 9 DIGIT 10
Description Code Code
Material Thread Reference Approval Special Plating
(Adaptors)
RIGHT ANGLE M-F FG BRASS A M16 11 ½" NPT 42 ATEX Exde A None (standard) X or blank None Blank
RIGHT ANGLE F-F FN ALUMINIUM B M20 12 ¾" NPT 43 IECEx Exde R Customer Special S Nickel N
RIGHT ANGLE M-M FK MILD STEEL C M25 13 1" NPT 44 Zinc Z
STAINLESS STEEL E M32 14 1¼" NPT 45 For other Chromatised C
M40 15 1½" NPT 46 approvals Special S
please see
M50 16 2" NPT 47
product
M63 17 2½" NPT 48 coding list on
M75 18 3" NPT 49 page 28
M90 81 3½" NPT 86
M100 82 4" NPT 87 Industrial X or Blank
Other sizes / threads are available on request

R.A. M-F Brass M20(M) M20(F) Exde PART NUMBER


PRODUCT CODING EXAMPLE
FG A 12 12 A = FGA1212A

10
SWIVEL ADAPTORS

NEW P
The Raxton Swivel Adaptor has the advantages of the standard inline and fixed 90º
RO CT

RO CT

Adaptors, with the addition of the ‘swivel’ feature.


DU

DU

Type FA
NEW P
The 90º Swivel Adaptor (Types FP, FQ, FR) has been designed to allow a full 360º choice
of cable entry/exit positions. This enables the installer to run the cable in any direction
which greatly improves ease of installation in confined or difficult situations. The cable
entry/exit can be aligned without the over or under torque compromise imposed by the
NEW P direction of cable. The inline type (Types FA, FC, FD) allows independent connection at
both ends.

RO CT

RO CT
DU

DU
NEW P The temperature range of -50ºC to +230ºC is governed by the use of an internal silicone
‘O’ ring which maintains the integrity of the product ensuring that it conforms to the over
pressure requirement of the latest standard.

Type FP

Product Dimensions Certification


Thread X Thread Y Length (L) Width (W) Depth (D) Min Wall Code of Protection Categories
(mm) (mm) (mm) (mm) ATEX: I M2, Ex d IMb, Ex e I Mb, (not Alum) or IIGd
M16 M20 17.0 4.0 17.0 2.25 Ex d IIC Gb, Ex e IIC Gb, Ex tb IIIC Db
M25 M25-M20 17.0 4.0 17.0 2.75 IECEx: Ex d Ex e IIC Gb, Ex d Ex e IM (Not
M32 M32-M20 17.0 5.0 17.0 3.00 Alum), Ex tb IIIC Db, IP 6X
M40 M40-M20 17.0 5.0 17.0 3.00 Compliance Standards
M50 M50-M20 17.0 5.0 17.0 3.00 ATEX EN 60079-0:2009, EN
M63 M63-M20 17.0 5.0 17.0 3.25 60079-1:2007, EN 60079-7:2007, EN 60079-
M75 M75-M20 17.0 5.0 17.0 3.25 31:2008
IECEx: IEC 60079-0:2007, IEC 60079-1:2007, IEC
L 60079-7:2006, IEC 60079-31:2008
D
Certificate Details
ATEX : SIRA 10ATEX1056U
IECEx: IEC Ex SIR.10.0025U
TEMPERATURE
Temperature range: -50ºC to +180ºC
Y
X

L
X

Product Codes
DIGIT 1+2 DIGIT 3 DIGIT 4 & 5 Male DIGIT 6 & 7 Female DIGIT 8 DIGIT 9 DIGIT 10
Description Code Code
Material Thread Reference Approval Special Plating
(Swivel Adaptors)
SWIVEL INLINE M-F FA BRASS A M16 11 ½" NPT 42 ATEX Exde A None (standard) X or blank None Blank
SWIVEL INLINE F-F FC ALUMINIUM B M20 12 ¾" NPT 43 IECEx Exde R Customer Special S Nickel N
SWIVEL INLINE M-M FD MILD STEEL C M25 13 1" NPT 44 Zinc Z
SWIVEL 90º M-F FP STAINLESS STEEL E M32 14 1¼" NPT 45 For other Chromatised C
SWIVEL 90º F-F FQ M40 15 1½" NPT 46 approvals Special S
please see
SWIVEL 90º M-M FR M50 16 2" NPT 47
product
M63 17 2½" NPT 48 coding list on
M75 18 3" NPT 49 page 28
M90 81 3½" NPT 86
M100 82 4" NPT 87 Industrial X or Blank
Other sizes / threads are available on request

Swivel Brass M20(M) M20(F) Exde PART NUMBER


PRODUCT CODING EXAMPLE
FA A 12 12 A = FAA1212A

11
STOPPING PLUGS
NEW P

RO CT

RO CT
Raxton's comprehensive range of Stopping Plugs are designed to close any unused entries

DU

DU
in electrical equipment without revoking existing certification.
NEW P

Following the basic rules in line with good engineering practice Raxton Stopping Plugs
should be inserted directly into the unused entry and not into a thread Reducer or thread
Adaptor.
Raxton Stopping Plugs are marked with the appropriate approval number and size. Tested
Type CK Type CY
to IP68.

RX Plug Type CB
RX Plugs are inserted with the allen key pointing away from the box and tightened from the
outside.

Tamperproof Plug Type CF


Tamperproof Plugs are inserted from the outside with the allen key towards the enclosure
Type CF Type CB and then tightened from the inside to leave a flush finish to prevent unauthorised removal.

Hexagon Head Plug Type CK


Product Dimensions Hexagon Headed Plugs are inserted from the outside and fastened by means of a spanner.
(Across flats dimensions are listed below).
Thread RX & Tamper- Hex Head A/F
proof Allen Key (mm)
Type CF & CB Type CK & CY Hollow Hexagon Head Plug Type CY
M16 6.0 19.0 A hollow version of the Hexagon Head Plug but still with Exd/Exe certification.
M20 10.0 23.3 Not suitable for mining applications.
M25 10.0 28.0
M32 10.0 37.5
M40 10.0 47.0 Certification
M50 10.0 56.0 Code of Protection Categories
M63 10.0 70.0 ATEX: I M2 (not CY), Ex d IMb, Ex e I Mb, or II GD, Ex d IIC Gb, Ex e IIC Gb, Ex tb IIIC Db
M75 10.0 80.0 IECEx: Ex d I/IIC Mb/Gb, Ex e I/IIC Mb/Gb, Ex tb IIIC Db, (Group I not for CY)
CSA: Ex d IIC Class 1, Zone 1, AEx d IIC Brass and Stainless only
GOST: ExdeI/IICU, ExdeIICU, ExeIIU
Type CK & CY
INMETRO: BR-Ex de 1/IIC Mb/Gb, BR-Ex tD A21 IP 66/67
*Minimum 6 full
threads parallel 5
Compliance Standards
ATEX / INMETRO / GOST: EN 60079-0:2009, EN 60079-1: 2007, EN 60079-7: 2007, EN 60079-31:2008
full threads taper IECEx: 60079-0:2004, IEC 60079-1:2003, IEC 60079-7:2006-07
CSA: CAN/CSA-E79-0-95, CAN/CSA-E79-1-95, UL 2279 1997, IEC 60079-0:1998, IEC 60079-1:1998
Certificate Details
ATEX: SIRA10ATEX1224X
IECEx: IECEx SIR07.0009X

*
CSA: CSA 200455-1003277
GOST: POCC GB.ГБ06.B01060
Type CF Type CB INMETRO: NCC 5871/09 U
TEMPERATURE
The item is classified as a component and is therefore not given a temperature rating.

* *
Product Codes
DIGIT 1+2 DIGIT 3 DIGIT 4 & 5 Male DIGIT 6 & 7 Female DIGIT 8 DIGIT 9 DIGIT10
Description Code Code
Material Thread Reference Approval Special Plating
(Stopper Plugs)
RX (External Access) CB BRASS A M16 11 ½" NPT 42 ATEX Exde A None (standard) X or blank None Blank
TAMPERPROOF CF ALUMINIUM B M20 12 ¾" NPT 43 IECEx Exde R Customer Special S Nickel N
HEX HEAD CK MILD STEEL C M25 13 1" NPT 44 Zinc Z
HOLLOW HEX HEAD CY STAINLESS STEEL E M32 14 1¼" NPT 45 For other Chromatised C
GLASS FILLED NYLON M M40 15 1½" NPT 46 approvals Special S
please see
M50 16 2" NPT 47
product
M63 17 2½" NPT 48 coding list on
M75 18 3" NPT 49 page 28
M90 81 3½" NPT 86
M100 82 4" NPT 87 Industrial X or Blank
Other sizes / threads are available on request

Hex Head Brass M25(M) - Exde PART NUMBER


PRODUCT CODING EXAMPLE
CB A 13 00 A = CBA1300A

12
STOPPING PLUGS

NEW P
Raxton's comprehensive range of Stopping Plugs are designed to close any unused entries

RO CT

RO CT
DU

DU
in electrical equipment without revoking existing certification. Exe plugs (CQ/CS) are
supplied complete with an ‘O’ ring to ensure that the IP rating of the installation is maintained.
NEW P

Following the basic rules in line with good engineering practice Raxton Stopping Plugs
should be inserted directly into the unused entry and not into a thread Reducer or thread
Adaptor.
Raxton Stopping Plugs are marked with the appropriate approval number and size. Tested to
Type CQ
IP68.

Type CS Dome Head Plug Type CQ


Can be offered as an alternative to the Hexagon Headed version and are fastened by means
of an allen key. Type CQ are available as a metallic Exde or nylon Exe product.

Type CQ Slotted Head Plug Type CS


Hexagon Slotted Head Plugs with are fastened by means of a screwdriver. Type CS are
available as nylon Exe only.

Product Dimensions Certification


Thread Dome Head Dome Head Slotted Head Code of Protection Categories
Allen Key Dia (mm) A/F (mm) Type CQ metallic only:
Type CQ Type CQ Type CS ATEX: I M2, Ex d IMb, Ex e I Mb, or II GD, Ex d IIC Gb, Ex e IIC Gb, Ex tb IIIC Db
M16 6.0 20.5 19.0 IECEx: Ex d I/IIC Mb/Gb, Ex e I/IIC Mb/Gb, Ex tb IIIC Db
M20 10.0 25.0 23.0 CSA: Ex d IIC Class 1, Zone 1, AEx d IIC
M25 10.0 30.0 28.0 GOST: ExdeI/IICU, ExdeIICU, ExeIIU
M32 10.0 38.0 36.0 INMETRO: BR-Ex de 1/IIC Mb/Gb, BR-Ex tD A21 IP 66/67
M40 10.0 46.0 44.0 Type CQ/CS Nylon only:
M50 10.0 56.0 54.0 ATEX: II 2 GD, Ex e IIC Gb, Ex tb IIIC Db (not Type CS)
M63 10.0 69.0 67.0 IECEx: Ex e IIC Gb, Ex tb IIIC Db
M75 10.0 81.0 N/A GOST: ExeIIU (not Type CS)
INMETRO: BR-Ex e IIC Gb, BR-Ex tD A21 IP 66/67 (not Type CS)
Compliance Standards
Type CQ metallic only:
ATEX / INMETRO / GOST: EN 60079-0:2009, EN 60079-1:2007, EN 60079-7:2007 EN 60079-31:2008
*Minimum 6 full
threads parallel 5
Type CS
IECEx: IEC 60079-0:2004, IEC 60079-1:2003, IEC 60079-7:2006-07
CSA: AN/CSA-E79-0-95, CAN/CSA-E79-1-95, UL 2279, 1997, IEC 60079-0:1998, IEC60079-1:1998
full threads taper Type CQ Nylon only:
ATEX / INMETRO / GOST: EN 60079-0:2009 ,EN 60079-7:2007 EN 60079-31:2009
IECEx: IEC 60079-0:2007, IEC 60079-7:2006, IEC 60079-31:2008
Type CS only:
IECEx: IEC 60079-0:2007-10, IEC 60079-7:2006-07, IEC 60079-31:2008
Certificate Details
Type CQ
Type CQ metallic only: Type CQ Nylon only:
ATEX: SIRA10ATEX1224X ATEX : SIRA10ATEX3335U
IECEx: IECExSIR07.0009X IECEx: IECExSIR10.0164U
CSA: CSA 200455-1003277
Type CQ metallic/Nylon: Type CS only:
GOST: POCC GB.ГБ06.B010600 IECEx: IECEx LCI 08.0035X
INMETRO: NCC 5871/09 U

*
TEMPERATURE
The item is classified as a component and is therefore not given a temperature rating. Nylon
* temperature range -20ºC to 65ºC, 'O' ring -30ºC to 125ºC
Product Codes
DIGIT 1+2 DIGIT 3 DIGIT 4 & 5 Male DIGIT 6 & 7 Female DIGIT 8 DIGIT 9 DIGIT10
Description Code Code
Material Thread Reference Approval Special Plating
(Stopper Plugs)
DOME HEAD CQ BRASS A M16 11 ½" NPT 42 ATEX Exde A None (standard) X or blank None Blank
SLOTTED HEAD CS ALUMINIUM B M20 12 ¾" NPT 43 IECEx Exde R Customer Special S Nickel N
MILD STEEL C M25 13 1" NPT 44 Zinc Z
STAINLESS STEEL E M32 14 1¼" NPT 45 For other Chromatised C
GLASS FILLED NYLON M M40 15 1½" NPT 46 approvals Special S
please see
M50 16 2" NPT 47
product
M63 17 2½" NPT 48 coding list on
M75 18 3" NPT 49 page 28
M90 81 3½" NPT 86
M100 82 4" NPT 87 Industrial X or Blank
Other sizes / threads are available on request

Dome Head Nylon M25(M) - Exde PART NUMBER


PRODUCT CODING EXAMPLE
CQ M 13 00 A = CQM1300A

13
BREATHER DRAINS

Electrical enclosures used outdoors with IP protection to prevent water and dust ingress
Type CT
can be subject to moisture build up inside the enclosure, which can damage or affect
performance of the electrical equipment. Moisture build up can be caused by several
conditions:
! Major changes in ambient temperatures
! Major changes in ambient pressures
! Heat generated by electrical equipment inside the enclosure
Installed at the bottom of the enclosure, the primary function is to effectively drain any
water present within the enclosure, whilst allowing air in the enclosure to breath with the
surrounding atmosphere, minimizing moisture build up within the enclosure.
The Type CV - Ex e Increased Safety model utilizes an internal dust filter, whilst the Type
Type CV CT – Ex d Flameproof model incorporates a metallic dust seal manufactured from
sintered copper/bronze alloy to also prevent a flame path in the event of an explosion
within the enclosure.

Moisture Drain and


Pressure Equaliser Castellated Locknut
(To allow drainage)
Hole in Plug
DUST FILTER
(To allow drainage
at low level)
Enclosure

Moisture Drain and


Pressure Equaliser

O Ring
(For I.P. Protection)

Ex e Increased Safety Application Ex d Flameproof Application


Cooper Crouse-Hinds MTL Fieldbus Barrier Modules mounted in 316 St. St. Cooper Crouse-Hinds CEAG EJB12A Flameproof Control Station.

Model CVE Breather Drain Model CTE Breather Drain

14
BREATHER DRAINS

The Raxton Exde (Type CT) and Exe Breather/Drain Plugs (Type CV) effectively drain
Type CT moisture from an enclosure and allow air from the enclosure to vent into the surrounding
atmosphere thereby minimising moisture build up.
The Plug is fastened to the lowest point of the enclosure by means of a spanner or allen
key. The 'O' ring will seal against the enclosure face enhancing the I.P. rating of the Plug.
The Drain Plug can be supplied with either a serrated washer and locknut allowing the
condensation to drain whilst ensuring the Plug is shakeproof or with a castellated locknut.
The Exde (Type CT) Breather/Drain Plug is an assembled item and must not be taken apart
at any stage of installation. The Exde plug has an impact resistance of 20 Nm and can
operate at temperatures between -50ºC to +230ºC.
Raxton Drain Plugs are marked with the appropriate approval number and size. Tested to
IP66.

Type CV
Type CV

Product Dimensions - Exe (Type CV) Certification


Thread Dia. Allen Key Head Protrusion Code of Protection Categories
(mm) (mm) (mm) Type CT Breather Drain Plugs
M20 25.4 10 14 ATEX: II 2 GD, Ex e IIC Gb, Ex tb IIIC Db
M25 30.5 10 14 IECEx: Ex d I/IIC Mb/Gb, Ex e I/IIC Mb/Gb, Ex tb IIIC Db, IP 6X
M32 38.0 10 14 Type CV Breather Drain Plugs
1/2" NPT 25.4 10 14 ATEX: I M2, Ex e I Mb or II GD, Ex e IIC Gb, Ex tb IIIC Db. Nylon: - II 2 GD, Ex e II only.
3/4" NPT 30.5 10 14 IECEx: Ex e IIC Mb/Gb, Ex IIIC tb Db (metallic only)
1" NPT 38.0 10 14 GOST: ExdeIICU, ExeIIU. Nylon: - ExeIIU only.
INMETRO: BR-Ex e I/IIC Gb, BR-Ex tD A21, IP 66
Compliance Standards
Product Dimensions - Exde (Type CT) Type CT Breather Drain Plugs
ATEX / INMETRO / GOST: EN 60079-0:2007 EN 60079-1:2007 EN 60079-7:2007 EN 61241-0:2006
Thread Hex AF Thread Length OAL EN 61241-1:2004
(mm) (mm) (mm) IECEx: IEC 60079-0:2007-10, IEC 60079-1:2007-04, IEC 60079-7:2006-07, IEC 61241-1:2004
M20 27.0 16.0 31 Type CV Breather Drain Plugs
M25 31.8 16.0 31 ATEX / INMETRO / GOST: EN 60079-0:2009 EN 60079-1:2007 EN 60079-7:2007 EN 60079-31:2008
1/2" NPT 27.0 20.0 35 (Metallic only); EN 50014:1997,
3/4" NPT 27.9 20.0 35 EN 50019:1994, EN 50281-1-1:1998 (Nylon only)
IECEx: IEC 60079-0:2007-10, IEC 60079-7:2006-07, IEC 61241-1:2004 (Metallic only)
Certificate Details
Type CV Type CT
ATEX: SIRA 10ATEX1288U, SIRA 10ATEX3279U, SIRA 00ATEX3074U
IECEx: IECExSIR08.0127U, IECExSIR09.0096U
GOST: POCC GB.ГБ06.B01060
INMETRO: NCC 5871/09 U
TEMPERATURE
The Exde Type CT Breather/Drain plug: -50ºC to 230ºC
The Exe Breather/Drain plug is classified as a component and is therefore not given a temperature
rating. Nylon temperature range -20ºC to 65ºC, 'O' ring -30ºC to 125ºC

* *
*Minimum 6 full threads parallel 5 full threads taper
Product Codes
DIGIT 1+2 DIGIT 3 DIGIT 4 & 5 Male DIGIT 6 & 7 Female DIGIT 8 DIGIT 9 DIGIT 10
Description Code Code
Material Thread Reference Approval Special Plating
(Breather Drains)
B.DRAIN Exde CT BRASS A M16 11 ½" NPT 42 ATEX Exde A None (standard) X or blank None Blank
B.DRAIN Exe CV STAINLESS STEEL E M20 12 ¾" NPT 43 IECEx Exde R Customer Special S Nickel N
GLASS FILLED NYLON M M25 13 1" NPT 44 For other Zinc Z
M32 14 approvals Chromatised C
please see Special S
product
coding list on
page 28
Other sizes / threads are available on request

Breather Drain Brass M25(M) - Exde PART NUMBER


PRODUCT CODING EXAMPLE
CT A 13 00 A = CTA1300A

15
BARRIER STOPPER BOXES FOR CABLE GLANDS & RIGID CONDUIT

Raxton Compound Stopper Box is designed to seal conductors at the entry to the
enclosure via conduit or to enable an existing compression gland to be converted to a
barrier gland. This is achieved by forming a barrier between the individual insulated
conductors within the cable to prevent an explosion within the enclosure. The
Compound Stopper Box allows compound to be packed around individual insulated
conductors. Assembly of the component compresses the packing material and
distributes the compound evenly to effect a barrier at point of entry into the enclosure.
The Compound Stopper Box is supplied with compound in a pack, complete with making
off instructions and gloves.
Raxton Compound Stopper Box is marked with the appropriate approval number and size.

Type EG

Product Dimensions Certification


Thread Bore MN Thread Length Protrusion Code of Protection Categories
(mm) (mm) (mm) ATEX: II 2 GD, Ex de IIC
M16 7.2 15.0 32.0 IECEx: Ex d I/IIC, Ex e I/IIC, Ex tb IIIC Db
M20 12.5 15.0 34.5 GOST: ExdIICU
M25 18.3 15.0 34.5 INMETRO: BR-Ex d IIC Gb, BR-Ex tD A21 IP 66/67
M32 24.3 15.0 34.5 Compliance Standards
M40 30.0 17.0 35.0 ATEX / INMETRO / GOST: EN 50014:1997,
M50 41.6 17.0 37.0 EN 50018:2000, EN 50019:2000, EN 5081-1-1:1998
M63 53.3 17.0 37.0 IECEx: IEC 60079-0:2004, IEC 60079 - 1:2003, IEC 60079-7:2006-07
M75 65.0 17.0 37.0 Certificate Details
ATEX: SIRA 11ATEX1301X
IECEx: IECEx SIR 11.0144X
GOST: POCC GB.ГБ06.B01060
INMETRO: NCC 5871/09 U

Type EG
TEMPERATURE
The item is classified as a component and is therefore not given a temperature rating.

Barrier Stopper Box used


with a rigid steel conduit.

*
*Minimum 6 full threads parallel 5 full threads taper

Barrier Stopper Box used with a


compression type cable gland to
provide a barrier gland assembly.

Product Codes
DIGIT 1+2 DIGIT 3 DIGIT 4 & 5 Male DIGIT 6 & 7 Female DIGIT 8 DIGIT 9 DIGIT10
Description Code Code
Material Thread Reference Approval Special Plating
(Stopper Boxes)
STOPPER BOX M-F EG BRASS A M16 11 ½" NPT 42 ATEX Exde A None (standard) X or blank None Blank
STOPPER BOX F-F EK ALUMINIUM B M20 12 ¾" NPT 43 IECEx Exde R Customer Special S Nickel N
MILD STEEL C M25 13 1" NPT 44 For other Zinc Z
STAINLESS STEEL E M32 14 1¼" NPT 45 approvals Chromatised C
M40 15 1½" NPT 46 please see Special S
M50 16 2" NPT 47 product
M63 17 2½" NPT 48 coding list on
page 28
M75 18 3" NPT 49
Other sizes / threads are available on request

Box M-F Brass M20(M) M20(F) Exde PART NUMBER


PRODUCT CODING EXAMPLE
EG A 12 12 A = EGA1212A

16
UNIONS

Raxton Unions are designed to provide a running joint whilst eliminating exposed threads
Type FL (F-F) and are particularly suitable for use where a coupler would be impractical.
Unions are available in a variety of thread forms and can be supplied with male to female
or female to female thread entries. The female connection thread of the Union shall step
not more than one size up from the male connection thread, or equal to one size up in the
case of a thread gender change: e.g M20(M) to M25(F) or M20(M) to 3/4 NPT(F).
Raxton Unions are marked with the appropriate approval number and size.

Type FB (M-F)

Product Dimensions Certification


Thread Protrusion Bore Dia Code of Protection Categories
(mm) (mm) (mm) ATEX: I M2, Ex d IMb, Ex e I Mb or II GD, Ex d IIC Gb, Ex e IIC Gb, Ex tb IIIC Db
M16 45.0 11.0 30.0 IECEx: Ex d I/IIC Mb/Gb , Ex e I/IIC Mb/Gb, Ex tb, IIIC Db
M20 45.0 14.3 42.0 GOST: ExdIICU
M25 45.0 20.5 47.0 INMETRO: BR-Ex d IIC Gb
M32 45.0 26.8 54.0 Compliance Standards
M40 45.0 33.5 62.0 ATEX / INMETRO / GOST: EN 60079-0:2009, EN60079-1:2007, EN 60079-7:2007, EN 60079-31:2008
M50 45.0 44.0 77.0 IECEx: IEC 60079-0:2007-10, IEC 60079-1:2007-04, IEC 60079-7:2006-07, IEC 61241-1:2004
M63 45.0 55.2 87.0 Certificate Details
M75 45.0 66.7 102.0 ATEX: SIRA 10ATEX1227U
IECEx: IECEx SIR09.0085U
GOST: POCC GB.ГБ06.B01060
INMETRO: NCC 5871/09 U
# TEMPERATURE
The item is classified as a component and is therefore not given a temperature rating.

*
*#Flamepath
Minimum 8 full threads parallel 5 full threads taper
in accordance with appropriate standards

Product Codes
DIGIT 1+2 DIGIT 3 DIGIT 4 & 5 Male DIGIT 6 & 7 Female DIGIT 8 DIGIT 9 DIGIT 10
Description Code Code
Material Thread Reference Approval Special Plating
(Unions)
UNION M-F FB BRASS A M16 11 ½" NPT 42 ATEX Exde A None (standard) X or blank None Blank
UNION F-F FL ALUMINIUM B M20 12 ¾" NPT 43 IECEx Exde R Customer Special S Nickel N
UNION M-M FE MILD STEEL C M25 13 1" NPT 44 For other Zinc Z
STAINLESS STEEL E M32 14 1¼" NPT 45 approvals Chromatised C
M40 15 1½" NPT 46 please see Special S
M50 16 2" NPT 47 product
M63 17 2½" NPT 48 coding list on
page 28
M75 18 3" NPT 49
Other sizes / threads are available on request

Union Brass M32(M) M32(F) Exde PART NUMBER


PRODUCT CODING EXAMPLE
FB A 14 14 A = FBA1414A

17
NIPPLES / COUPLERS / BUSHES

Screwed Nippling
Supplied 50mm long as standard, alternative lengths can be supplied as required.
Available in a variety of thread forms (see page 27). Materials include Brass, Mild Steel,
Stainless Steel, Aluminium and Nylon.
Metallic finishes can be plated to requirements.

Couplers
Available in round or hexagonal. Manufactured in Brass as standard in a wide combination
of thread forms and sizes.

Bushes
Male and Female Bushes are available in a variety of thread forms (see page 27). Materials
include Brass, Mild Steel, Stainless Steel, Aluminium and may be plated to requirements.

TEMPERATURE
The item is classified as a component and is therefore not given a temperature rating.

Product Codes
DIGIT 1+2 DIGIT 3 DIGIT 4 & 5 Male DIGIT 6 & 7 Female DIGIT 8 DIGIT 9 DIGIT 10
Code Code
Description Material Thread Reference Approval Special Plating
MALE BUSH LONG JA BRASS A M12 04 ½" NPT 42 Industrial X or Blank None (standard) X or blank None Blank
MALE BUSH SHORT JB ALUMINIUM B M16 11 ¾" NPT 43 Customer Special S Nickel N
FEMALE BUSH JC MILD STEEL C M20 12 1" NPT 44 Zinc Z
NIPPLE JD STAINLESS STEEL E M25 13 1¼" NPT 45 Chromatised C
NIPPLE LONG JE NYLON BLACK G M32 14 1½" NPT 46 Special S
No Hazardous
NIPPLE BARREL JF M40 15 2" NPT 47
Area Approval
COUPLER ROUND JG M50 16 2½" NPT 48
COUPLER HEX JH M63 17 3" NPT 49
COUPLER FLANGE JJ M75 18 3½" NPT 86
M90 81 4" NPT 87
Other sizes / threads are available on request

Male Bush Brass M25(M) - - PART NUMBER


PRODUCT CODING EXAMPLE
JA A 13 00 = JAA1300

18
LOCKNUTS, WASHERS & SERRATED WASHERS

Locknuts & Lockrings (Type GA, GB)


Raxton offer a large variety of Locknuts/Lockrings which are often recommended for
securing cable glands, thread Adaptors or thread Reducers to a gland plate or into
equipment. Locknuts are available in Brass, Mild Steel, Stainless Steel, Aluminium or
Nylon.

TEMPERATURE
The item is classified as a component and is therefore not given a temperature rating.

Product Dimensions
Female Thread A/F Dims Female Thread A/F Dims
Thread Coding (mm) Thread Coding (mm)
M16 0011 19.0 ¾" NPT 0043 33.0
Types GA
M20 0012 25.4 1" NPT 0044 40.0
M25 0013 30.0 1¼" NPT 0045 50.0
M32 0014 46.0 1½" NPT 0046 56.0
M40 0015 46.0 2" NPT 0047 70.0
M50 0016 65.0 2½" NPT 0048 90.0
M63 0017 80.0 3" NPT 0049 105.0
M75 0018 95.0 3½" NPT 0050 115.0
Types HA M90 0019 105.0 4" NPT 0051 130.0
Based on metallic products

Serrated Washers
Raxton Serrated (Shakeproof) Washers are available in both Mild Steel Zinc plated and
Stainless Steel and prevent the risk of attachments becoming loose when used in
conjunction with a Locknut.

TEMPERATURE
The item is classified as a component and is therefore not given a temperature rating.

Washers
To maintain the IP rating of the equipment Raxton offer a wide variety of entry thread
sealing Washers and ‘O’ rings. Materials include Nylon, Teflon, Neoprene, Fibre and
Rubber. In addition Raxton can offer a non setting universal jointing sealant.

TEMPERATURE
The item is classified as a component and is therefore not given a temperature rating.
Types GC

Product Codes
DIGIT 1+2 DIGIT 3 DIGIT 4 & 5 Male DIGIT 6 & 7 Female DIGIT 8 DIGIT 9 DIGIT 10
Description Code Code
Material Thread Reference Approval Special Plating
(Earth Accessories)
LOCKNUTS GA BRASS A M16 11 ½" NPT 42 Industrial X or Blank None (standard) X or blank None Blank
LOCKRINGS GB ALUMINIUM B M20 12 ¾" NPT 43 Customer Special S Nickel N
SERRATED WASHERS GC MILD STEEL C M25 13 1" NPT 44 Zinc Z
CASTELLATED LOCKNUTS GD STAINLESS STEEL E M32 14 1¼" NPT 45 Chromatised C
WASHERS HA NYLON BLACK G M40 15 1½" NPT 46 Special S
No Hazardous
‘O’ RINGS HB TEFLON P M50 16 2" NPT 47
Area Approval
EPDM Q M63 17 2½" NPT 48
NEOPRENE T M75 18 3" NPT 49
NYLON WHITE R M90 81 3½" NPT 86
RED FIBRE U M100 82 4" NPT 87
Other sizes / threads are available on request

Washer Fibre (M) M40(F) - PART NUMBER


PRODUCT CODING EXAMPLE
HA U 00 15 - = HAU0015

19
EARTH LEAD ADAPTORS & THREADED EARTH PLATES

Raxton Exe Earth Lead Adaptors (Type DG) allow for earth continuity to be maintained by
providing an earth lead which can be terminated inside the enclosure.
Earth Lead Adaptors are produced with an undercut and supplied complete with an ‘O’ring
to maintain the IP integrity of the installation.
Earth Lead Adaptors are marked with the appropriate approval number and size.
Type DG Raxton Exe Threaded Earth Plates are designed to ensure earth continuity when terminating
brass glands into non-metallic enclosures. The additional use of a locknut is
recommended to ensure pressure is maintained with the wall enclosure. Threaded Earth
Plates are marked with the appropriate approval number and size.

Type DK

Product Dimensions - Earth Lead Adaptors Certification - Earth Lead Adaptors


Thread Length Earth Lead x Code of Protection Categories
Earth Lead (mm) 300mm (mm2) ATEX: I M2, Ex e I Mb or II G D, Ex e IIC Gb, ExIIIC tb Db
M16 38.0 2.5 IECEx: Ex d I/IIC Mb/Gb, Ex E I/IIC Mb/Gb, Ex IIIC tb Db
M20 38.0 2.5 GOST: ExeIIU
M25 38.0 4.0 INMETRO: BR-Ex e II Gb (DG/DN/DK) BR-Ex tD A21 IP66/67
M32 38.0 6.0 Compliance Standards
M40 39.0 10.0 ATEX / INMETRO / GOST: EN 60079-0:2009, EN 60079-7:2007, IEC 60079-31:2008
M50 39.0 16.0 IECEx: IEC 60079-0:2007-10, IEC 60079-1:2007-04,
M63 39.0 25.0 IEC 60079-7:2006-07, IEC 61241-1:2004
M75 39.0 25.0 Certificate Details
ATEX: Sira 10ATEX3229U
IECEx: IECEx SIR 09.0087U
GOST: POCC GB.ГБ06.B01060
INMETRO: NCC 5871/09 U
TEMPERATURE
The item is classified as a component and is therefore not given a temperature rating,
'O' ring - 30ºC to 125ºC.

Product Dimensions - Threaded Earth Plates Certification - Threaded Earth Plates


Threaded Material Earth Lead x Code of Protection Categories
Earth Plate Size (mm) 300mm (mm2) ATEX: II 2GD, EEx e II
M16 22.0 2.5 GOST: ExdIICU
M20 30.0 2.5 INMETRO: BR-Ex e II Gb
M25 32.0 4.0 Compliance Standards
M32 38.0 6.0 ATEX / INMETRO / GOST: EN 50014:1997, EN50018:2000, EN 50019:2000, EN50281-1-1:1998
M40 50.8 10.0 Certificate Details
M50 63.5 16.0 ATEX: SIRA 00ATEX1073U
M63 76.0 25.0 GOST: POCC GB.ГБ06.B01060
M75 102.0 25.0 INMETRO: NCC 5871/09 U
TEMPERATURE
The item is classified as a component and is therefore not given a temperature rating.

Product Codes
DIGIT 1+2 DIGIT 3 DIGIT 4 & 5 Male DIGIT 6 & 7 Female DIGIT 8 DIGIT 9 DIGIT 10
Description Code Code
Material Thread Reference Approval Special Plating
(Earth Accessories)
ADAPTOR M-F DG BRASS A M16 11 ½" NPT 42 ATEX Exe E None (standard) X or blank None Blank
PLATE DK ALUMINIUM B M20 12 ¾" NPT 43 IECEx Exe I/II P Customer Special S Nickel N
MILD STEEL C M25 13 1" NPT 44 Zinc Z
STAINLESS STEEL E M32 14 1¼" NPT 45 For other Chromatised C
approvals
M40 15 1½" NPT 46 Special S
please see
M50 16 2" NPT 47 product
M63 17 2½" NPT 48 coding list on
M75 18 3" NPT 49 page 28
M90 81 3½" NPT 86
M100 82 4" NPT 87 Industrial X or Blank
Other sizes / threads are available on request

EL Adaptor Brass M20(M) M20(F) Exe PART NUMBER


PRODUCT CODING EXAMPLE
DG A 12 12 E = DGA1212E

20
EARTHING LOCKNUTS & EARTH TAGS

NEW P Earthing Locknuts


RO CT

RO CT

Raxton Earthing Locknuts offer an alternative to the standard Earth Tag when terminating a
DU

DU

NEW P metallic cable gland into a thin wall steel enclosure. The Earthing Locknut design includes
a number of cutting teeth formed on one surface of the nut. When tightened, these teeth
cut into the enclosure wall, preventing the nut from turning and enabling the gland to be
tightened to the nut from the outside with only one tool. This allows all connections of the
gland to be made within the enclosure, away from the corrosive or flammable atmosphere
and away from possible mechanical damage, and results in a neater appearance. The nut
may also be fitted with the plain side facing the enclosure where this is preferred.

TEMPERATURE
The item is classified as a component and is therefore not given a temperature rating.

Type DN

A Product Dimensions

* Female
Thread
Thread
Coding
A/F Dims
(mm)
Female
Thread
Thread
Coding
A/F Dims
(mm)
M12 0010 14.0 ½" NPT 0042 30.0
M16 0011 18.0 ¾" NPT 0043 36.0
M20 0012 23.0 1" NPT 0044 42.0
M25 0013 28.0 1¼" NPT 0045 50.0
M32 0014 36.0 1½" NPT 0046 55.0
M40 0015 44.0 2" NPT 0047 70.0
M50 0016 54.0 2½" NPT 0048 80.0
M63 0017 70.0 3" NPT 0049 98.0
M75 0018 3½" NPT 0050 115.0
M90 0019 4" NPT 0051 130.0
A

Earth Tags
Raxton Earth Tags provide a means of connecting a flexible earth bond with the gland,
thread Adaptor or thread Reducer in any required position whilst ensuring suitable earth
continuity. Available in Brass, Aluminium and Stainless Steel and supplied self colour as
standard, additional plating is available if required.

TEMPERATURE
The item is classified as a component and is therefore not given a temperature rating.

Type DM

Product Codes
DIGIT 1+2 DIGIT 3 DIGIT 4 & 5 Male DIGIT 6 & 7 Female DIGIT 8 DIGIT 9 DIGIT 10
Description Code Code
Material Thread Reference Approval Special Plating
(Earth Accessories)
EARTH TAG DM BRASS A M16 11 ½" NPT 42 Industrial X or Blank None (standard) X or blank None Blank
EARTHING LOCKNUT DN ALUMINIUM B M20 12 ¾" NPT 43 Customer Special S Nickel N
STAINLESS STEEL E M25 13 1" NPT 44 Zinc Z
M32 14 1¼" NPT 45 Chromatised C
M40 15 1½" NPT 46 Special S
No Hazardous
M50 16 2" NPT 47
Area Approval
M63 17 2½" NPT 48
M75 18 3" NPT 49
M90 81 3½" NPT 86
M100 82 4" NPT 87
Other sizes / threads are available on request

Earth Tag Brass (M) M20(F) - PART NUMBER


PRODUCT CODING EXAMPLE
DM A 00 12 - = DMA0012

21
SHROUDS

Raxton offer a range of push on Shrouds which are used to minimise the risk of dirt or
foreign substances gathering on the cable gland body and/or point of cable to the gland
interface.
Supplied as standard in black PVC they are suitable for all leading makes of glands.
Raxton also offer coloured PVC shrouds (blue, grey, red), Flame Retardant (FR) black PVC
shrouds, Low Smoke and Fume (LSF) Halogen free PVC shrouds in black, white, red, blue,
and PCP shrouds in black.
It should be noted that shrouds do not necessarily improve the ingress protection (IP) of
the installed gland and may in certain conditions retain unwanted moisture.

TEMPERATURE
Type HC The item is classified as a component and is therefore not given a temperature rating.
Also available in other colours

Product Dimensions
TO BE CUT AWAY TO
SIZE ØA ØB ØC X Y L1
SUIT DIAMETER OF
CABLE BEING USED 5 19.9 16.5 2.5 40.0 9.0 57.0
ØC
5A 23.8 20.0 2.5 50.0 10.0 60.0
6 25.2 20.0 2.5 50.0 10.0 78.0
7 31.5 26.0 8.0 50.0 10.0 80.0
8 43.0 36.0 11.0 50.0 12.0 78.0
8 38.8 32.0 11.0 50.0 12.0 80.0
9 49.5 40.0 15.0 50.0 12.0 83.0
10 57.8 48.0 20.0 60.0 14.0 91.0
x

11 67.2 60.0 25.0 70.0 14.0 105.0


12 75.6 68.0 31.0 75.0 13.0 90.0
12E 84.0 70.0 34.0 75.0 13.0 115.0
Y
13 89.3 75.0 37.0 75.0 13.0 110.0
L1

øB

øA

Product Codes
SHROUD PDM 100 PDM 100 FR PDM 100 PDM 100 PDM 100 PDM 100 LSF PDM 100 LSF PDM 100 LSF PDM 100 LSF
NUMBER BLACK BLACK BLUE GREY RED BLACK WHITE RED BLUE

5 HCY 5 HCY FR 5 HCB 5 HCG 5 HCR 5 HCB LSF 5 HCW LSF 5 HCR LSF 5 HCL LSF 5
5A HCY 5A HCY FR 5A HCB 5A HCG 5A HCR 5A HCB LSF 5A HCW LSF 5A HCR LSF 5A HCL LSF 5A
6 HCY 6 HCY FR 6 HCB 6 HCG 6 HCR 6 HCB LSF 6 HCW LSF 6 HCR LSF 6 HCL LSF 6
7 HCY 7 HCY FR 7 HCB 7 HCG 7 HCR 7 HCB LSF 7 HCW LSF 7 HCR LSF 7 HCL LSF 7
8 HCY 8 HCY FR 8 HCB 8 HCG 8 HCR 8 HCB LSF 8 HCW LSF 8 HCR LSF 8 HCL LSF 8
8B HCY 8B HCY FR 8B HCB 8B HCG 8B HCR 8B HCB LSF 8B HCW LSF 8B HCR LSF 8B HCL LSF 8B
9 HCY 9 HCY FR 9 HCB 9 HCG 9 HCR 9 HCB LSF 9 HCW LSF 9 HCR LSF 9 HCL LSF 9
10 HCY 10 HCY FR 10 HCB 10 HCG 10 HCR 10 HCB LSF 10 HCW LSF 10 HCR LSF 10 HCL LSF 10
11 HCY 11 HCY FR 11 HCB 11 HCG 11 HCR 11 HCB LSF 11 HCW LSF 11 HCR LSF 11 HCL LSF 11
12 HCY 12 HCY FR 12 HCB 12 HCG 12 HCR 12 HCB LSF 12 HCW LSF 12 HCR LSF 12 HCL LSF 12
12E HCY 12E HCY FR 12E HCB 12E HCG 12E HCR 12E HCB LSF 12E HCW LSF 12E HCR LSF 12E HCL LSF 12E
13 HCY 13 HCY FR 13 HCB 13 HCG 13 HCR 13 HCB LSF 13 HCW LSF 13 HCR LSF 13 HCL LSF 13

22
NYLON GLANDS

Raxton Ex e and Ex i Cable Glands are designed with an outer seal and cable grip for use
with unarmoured cable. Cabe Glands are designed for direct installation to the threaded
entry of an enclosure or used with a locknut into a clearance hole. Unused entries require
the use of a certified stopping plug.
Raxton Cable Glands which comprise of a body, clamping ring, sealing ring and capnut
have a sealing range as shown in the table below.
It is recommended that brass locknuts are used with PG threads.

Certification
Code of Protection Categories
ATEX: LCIE 97 ATEX 6007X /Exe II/Ex tD/Ex II 2 GD, IP68
Compliance Standards
ATEX: EN 50262, EN60529 (IP68)
Certificate Details
ATEX; LCIE 97ATEX 6007X
TEMPERATURE
ATEX temperature range -20ºC to 80ºC.

L E L E

A x 1.10
A x 1.10

A x 1.10
A x 1.10

A A A A

Type EB Ex e Gland (Black) Type EB Ex i Gland (Blue)

Product Codes
PRODUCT CODE OUTER SEAL A/F DIMENSIONS
Size Thread E L
Ex e Ex i Min Max A B
EBG0400E EBK0400E 4 M12 9 3.5 6 18 15 15
EBG1100EXS EBK1100EXS 5 M16S 12 5 8 22 19 19
EBG1100E EBK1100E 6 M16 9 6 10 22 22 22
EBG1200EXS EBK1200EXS 7 M20S 12 8 13 23 24 24
EBG1200E EBK1200E 8 M20 10 10 15 23 26 26
EBG1300E EBK1300E 9 M25 13 13 19 29 32 32
EBG1400E EBK1400E 10 M32 15 18 25 29 41 41
EBG1500E EBK1500E 11 M40 15 24 32 35 52 52
EBG1600E EBK1600E 12 M50 16 29 38 40 59 59
EBG1700E EBK1700E 13 M63 16 36 44 42 65 65
EBG2000E EBK2000E 4 PG7 9 3.5 6 18 15 15
EBG2100E EBK2100E 5 PG9 9 5 8 22 19 19
EBG2200E EBK2200E 6 PG11 9 6 10 22 22 22
EBG2300E EBK2300E 7 PG13.5 10 8 13 23 24 24
EBG2400E EBK2400E 8 PG16 10 10 15 23 23 23
EBG2500E EBK2500E 9 PG21 11 13 19 29 32 32
EBG2600E EBK2600E 10 PG29 12 18 25 29 41 41
EBG2700E EBK2700E 11 PG36 14 24 32 35 52 52
EBG2800E EBK2800E 12 PG42 16 29 38 40 59 59
Other sizes / threads are available on request

Gland Ex M20(M) - Exe PART NUMBER


PRODUCT CODING EXAMPLE
EB K 12 00 E = EBK1200E

23
BARRIER STOPPER BOXES FOR FLEXIBLE CONDUIT

The Raxton Barrier Stopper Box for flexible conduit is designed to provide a flameproof
connection for liquid tight and braided flexible conduit in hazardous area applications. This
is achieved by forming a barrier between the individual insulated conductors of a cable
inside the conduit that are to be terminated within an enclosure.
NEW P
The barrier is formed by using a setting compound packed around individual insulated
RO CT

RO CT
DU

DU

NEW P conductors. Assembly of the component compresses the packing material and distributes
the compound evenly to effect a barrier at point of entry into the enclosure.
The Barrier Stopper Box is supplied with compound in a pack, complete with making off
Type EF
instructions and gloves.

Product Dimensions Certification


Stopper Thread A ØB Length Code of Protection Categories
Box Size Min Nominal H ATEX: I M2, Ex d IMb, Ex e IMB, or II G, Ex d IIC Gb, Ex e IIC Gb, Ex tb IIIC Db
M20 15 21.1 44.5 IECEx: Ex d I/IIC, Ex e I/IIC, Ex tb IIIC Db
M25 15 26.4 46.0 Compliance Standards
M32 15 33.1 51.5 ATEX: EN 60079-0: 2009, EN 60079-1: 2007, EN 60079-7: 2007, EN 60079-31: 2008
M40 15 41.8 52.5 IECEx: IEC 60079-0: 2004, IEC 60079-1: 2003, IEC 60079-7: 2006-07
M50 15 47.9 58.5 Certificate Details
M63 15 59.7 61.5 ATEX: SIRA 11ATEX1301X
IECEx: SIR 11.0144X
TEMPERATURE
The item is classified as a component and is therefore not given a temperature rating.
H

A
ØB

Product Codes
DIGIT 1+2 DIGIT 3 DIGIT 4 & 5 Male DIGIT 6 & 7 Female DIGIT 8
Description Code Code
Material Thread Reference Approval
(Stopper Boxes)
BARRIER STOPPER EF BRASS A M16 11 ½" NPT 42 ATEX Exde A
BOX (FLEXIBLE ALUMINIUM B M20 12 ¾" NPT 43 ATEX Exd D
CONDUIT) M-F MILD STEEL C M25 13 1" NPT 44 ATEX Exe E
STAINLESS STEEL E M32 14 1¼" NPT 45 IECEx Exd I/IIC N
M40 15 1½" NPT 46 IECEx Exe I/II P
M50 16 2" NPT 47
M63 17 2½" NPT 48
M75 18 3" NPT 49
Other sizes / threads are available on request

Box M-F Brass M20(M) M20(F) Exde PART NUMBER


PRODUCT CODING EXAMPLE
EF A 12 12 A = EFA1212A

24
FLEXIBLE CONDUIT

NEW P
Raxton now offer a range of flexible conduit, all of which feature a high mechanical
RO CT

RO CT
DU

strength and are suitable for various applications.


DU

NEW P

Type MXS
Conduit Type MXS
Description: Stainless steel (316), helically wound, flexible conduit with oil resistant
and high temperature pvc smooth cover. ONLY AVAILABLE IN BLACK
Application: Food processing machinery or outdoor applications where high
corrosion resistance and liquid tight are a requirement
Features: High mechanical strength and resistant to oils and greases
UV resistant (black) and good flexibility
Smooth wipe clean outer cover
Type MXB Cover does not wrinkle when bent
IP Rating: IP66 + IP67+ IP68 (5 bar)
Temp range: -20ºC to +105ºC

Product Dimensions - MXS Conduit Type MXB


Description: Galvanised steel, helically wound, flexible conduit with thermoplastic
Nominal Outside Dia. Inside Dia. Inside Bend
Size (mm) (mm) Rad (mm)
rubber cover and stainless steel (316) overbraid
10 11.8 7.0 35 Application: Very arduous industrial environments such as steel works
12 14.2 10.0 40
Features: High mechanical strength
16 17.8 12.6 45
20 21.1 16.0 65 High abrasion resistance and very high tensile strength
25 26.4 21.0 100 EMC Screening Performance
32 33.1 26.5 135
40 41.8 35.4 175
IP Rating: IP66 + IP67+ IP68 (5 bar)
50 47.9 40.4 230 Temp range: -45ºC to +135ºC
63 59.7 51.6 280

Conduit Support P Clips Type MYV


Product Dimensions - MXB Description: Type MYV plated steel P clip with pvc liner
Nominal Outside Dia. Inside Dia. Inside Bend Application: P Clips to support flexible conduit Types MXB, MXH and MXP
Size (mm) (mm) Rad (mm)
16 19.3 12.6 45
20 22.6 16.0 65
Conduit Support P Clips Type MYT
25 27.9 21.0 100 Description: Type MYT stainless steel P clip
32 34.6 26.5 135
Application: P Clips to support flexible conduit Type MXB, MXH, MXP, MXR and MXS

Type MYV

Type MYT

Product Codes
DIGIT 1+2 DIGIT 3 DIGIT 4 & 5 DIGIT 6 DIGIT 7 & 8
Description Code Type Code Size mm Code Colour Code Reel Length Code
(Flexible Conduit)
FLEXIBLE CONDUIT MX TYPE MXP P M10 09 Black B 10 metres 10
SUPPORT CLIP MY TYPE MXS S M12 10 Grey G 25 metres 25
TYPE MXH H M16 11 Orange O 50 metres 50
TYPE MXB B M20 12
TYPE MXR R M40 15
PVC/STEEL CLIP V M25 13
STAINLESS STEEL CLIP T M32 14
M50 16
M63 17 Clips Blank Clips Blank
Other sizes / threads are available on request

Conduit MXP M20 Black 10m PART NUMBER


PRODUCT CODING EXAMPLE
MX P 12 B 10 = MXP12B10

25
FLEXIBLE CONDUIT

Raxton now offer a range of flexible conduit, all of which feature a high mechanical
Type MXH strength and are suitable for various applications.
Type MXP

Conduit Type MXP


Description: Galvanised steel, helically wound, flexible conduit with smooth oil
resistant and high temperature pvc cover
Application: Machine tools or outdoor installations where liquid tight is a requirement
NEW P Features : High mechanical strength and resistant to oils and greases
RO CT

RO CT

UV resistant (black) and good flexibility


DU

DU

NEW P

Smooth wipe clean outer cover


Cover does not wrinkle when bent
IP Rating: IP66 + IP67+ IP68 (5 bar)
Type MXR
Temp range: -20ºC to +105ºC
Approvals: Lloyd's Register Type Approval

Product Dimensions - MXP, MXH & MXR Conduit Type MXH


Nominal Outside Dia. Inside Dia. Inside Bend Inside Bend Rad Description: Galvanised steel, helically wound, flexible conduit with smooth
Size (mm) (mm) Rad (mm) (mm) MXR only thermoplastic rubber cover. ONLY AVAILABLE IN BLACK
10 11.8 7.0 35 - Application: Machine tools or outdoor installations where liquid tight together with a
12 14.2 10.0 40 -
low or high temperature rating is a requirement
16 17.8 12.6 45 -
20 21.1 16.0 65 65 Features : High mechanical strength and resistant to oils and greases
25 26.4 21.0 100 100 UV resistant (black) and good flexibility
32 33.1 26.5 135 120
40 41.8 35.4 175 140
Smooth wipe clean outer cover
50 47.9 40.4 230 180 Cover does not wrinkle when bent
63 59.7 51.6 280 -
IP Rating: IP66 + IP67+ IP68 (5 bar)
Temp range: -45ºC to +135ºC

Conduit Type MXR


Description: Galvanised steel, helically wound, flexible conduit with galvanised steel
braid and oil resistant and high temperature pvc smooth cover.
ONLY AVAILABLE IN BLACK
Application: Machinery or outdoor installations where high corrosion resistance and
liquid tight are a requirement combined with EMC screening.
Features : High mechanical strength and resistant to oils and greases
UV resistant (black) and good flexibility
Smooth wipe clean outer cover
Cover does not wrinkle when bent
IP Rating: IP66 + IP67+ IP68 (5 bar)
Temp range: -20ºC to +105ºC

Product Codes
DIGIT 1+2 DIGIT 3 DIGIT 4 & 5 DIGIT 6 DIGIT 7 & 8
Description Code Type Code Size mm Code Colour Code Reel Length Code
(Flexible Conduit)
FLEXIBLE CONDUIT MX TYPE MXP P M10 09 Black B 10 metres 10
TYPE MXS S M12 10 Grey G 25 metres 25
TYPE MXH H M16 11 Orange O 50 metres 50
TYPE MXB B M20 12
TYPE MXR R M25 13
M32 14
M40 15
M50 16
M63 17
Other sizes / threads are available on request

Conduit MXP M20 Black 10m PART NUMBER


PRODUCT CODING EXAMPLE
MX P 12 B 10 = MXP12B10

26
THREAD SELECTION / DIMENSIONS

Isometric to BS 3643:1981 National Pipe Thread to British Standard Pipe to


ANSI / ASME: 1983 BS 3643:1981
MAJOR MAJOR MAJOR
SIZE DIAMETER THREADS PITCH SIZE DIAMETER THREADS PITCH SIZE DIAMETER THREADS PITCH
(mm) PER INCH (mm) PER INCH (mm) PER INCH
16mm (M16) 16 16.93 1.50 / " NPT
1 8 10.30 27 0.94 / " BSP
1 8 9.73 28 0.91
20mm (M20) 20 16.93 1.50 / " NPT
1 4 13.72 18 1.41 / " BSP
1 4 13.16 19 1.34
25mm (M25) 25 16.93 1.50 3/8" NPT 17.15 18 1.41 3/8" BSP 16.66 19 1.34
32mm (M32) 32 16.93 1.50 1/2" NPT 21.34 14 1.81 1/2" BSP 20.96 14 1.81
40mm (M40) 40 16.93 1.50 3/4" NPT 26.67 14 1.81 3/4" BSP 26.44 14 1.81
50mm (M50) 50 16.93 1.50 1" NPT 33.40 111/2 2.20 1" BSP 33.25 11 2.31
63mm (M63) 63 16.93 1.50 11/4" NPT 42.16 111/2 2.20 11/4" BSP 41.91 11 2.31
75mm (M75) 75 16.93 1.50 11/2" NPT 48.26 111/2 2.20 11/2" BSP 47.80 11 2.31
2" NPT 60.33 111/2 2.20 2" BSP 59.61 11 2.31
21/2" NPT 73.03 8 3.175 21/2" BSP 75.18 11 2.31
3" NPT 88.90 8 3.175 3" BSP 87.88 11 2.31
4" NPT 114.30 8 3.175 4" BSP 113.03 11 2.31

Certified Products

FEMALE THREAD

11/4" NPT / BSP

11/2" NPT / BSP

21/2" NPT / BSP


NPT / BSP

NPT / BSP

1" NPT / BSP

2" NPT / BSP

3" NPT / BSP

4" NPT
M16

M20

M25

M32

M40

M50

M63

M75

1/2"

3/4"

M16

M20

M25

M32

M40

M50

M63

M75
1/2" NPT
3/4" NPT

1" NPT
MALE THREAD

1 1/4" NPT

1 1/2" NPT

2" NPT

2 1/2" NPT

3" NPT

4" NPT
1/2" BSP
3/4" BSP

1" BSP

1 1/4" BSP

1 1/2" BSP

2" BSP

2 1/2" BSP

3" BSP

Adaptors Reducers Not Certified

27
PRODUCT CODING

DIGIT 1 + 2 CODE THREAD REFERENCES


Product Description MALE DIGIT 4 + 5 FEMALE 6 + 7
M-F HEX AB
M-F ROUND AJ ISOMETRIC NPT PG
ADAPTORS M-M AR
F-F HEX AU
SIZE CODE SIZE CODE SIZE CODE
F-F ROUND AX M6 01 1/2” 42 7 20
M-F INLINE FA M8 02 3/4” 43 9 21
M-M INLINE FD M10 03 1” 44 11 22
SWIVEL F-F INLINE FC M12 04 11/4” 45 13.5 23
ADAPTORS M-F RIGHT ANGLE FP M16 11 11/2” 46 16 24
M-M RIGHT ANGLE FR M20 12 2” 47 21 26
F-F RIGHT ANGLE FQ M22 07 21/2” 48 29 26
UNION M-F FB M24 08 3” 49 36 27
UNION F-F FL M25 13 31/2” 86 42 28
UNION M-M FE M28 09 4” 87 48 29
ADAPTING M32 14 5” 88
RIGHT ANGLE M-F FG
AIDS
RIGHT ANGLE F-F FN M38 05 SPECIAL 40
RIGHT ANGLE M-M FK M40 15
45º ELBOW FM M50 16
Normally Male thread is specified first (digits 4+5), Female thread second
M-F HEX BB M63 17
REDUCERS M75 18 (digits 6+7), with all digits used for M-M and F-F products. BSP P, BSP T
M-F ROUND BJ
RX (Externally Accessible) CB M80 80 & ET thread components are still available, please consult sales department
TAMPERPROOF (Internally Accessible) CF M90 81 for advice.
HEX HEAD CK M100 82
HEX HEAD (Hollow) CY SPECIAL 10
PLUGS
DOME HEAD CQ
SLOTTED CS
DIGIT 3 CODE DIGIT 8 CODE
DRAIN Exe CV
DRAIN Exde CT Material Approval
INSULATED M-F DB BRASS A Atex Exde A
INSULATED M-M DD ALUMINIUM B Atex Exd D
INSULATED F-F DE STEEL C Atex Exe E
INSULATING EARTH LEAD M-F DG COPPER & NON-ASB D Mining Group 1 M
& EARTHING EARTH PLATE DK STAINLESS STEEL E CSA ©Exd IIC J
EARTH TAG DM PVC F CSA (US) Class 1 Zone 1 K
EARTHING LOCK NUTS DN NYLON BLACK G AExd IIC L
GLANDS EB NYLON GREY H IECEx Exd I/IIC N
CABLE STOPPER BOX M-F EG SILICONE J IECEx Exe I/II P
RETENTION STOPPER BOX F-F EK NYLON BLUE K IECEx Exde I/II R
FLEXIBLE CONDUIT EF LEAD L Gost Exde IICU T
LOCKNUTS GA GLASS FILLED NYLON M Gost Exde I/IICU U
LOCKRINGS GB NYLON 66 N Gost Exd IICU V
LOCKING RED FIBRE U Gost Exe IICU W
SERRATED WASHERS GC
LOCKNUTS CASTELLATED GD TEFLON P INMETRO Exd G
WASHERS HA EPDM Q INMETRO Exe H
INGRESS
PROTECTION O RINGS HB NYLON WHITE R INMETRO Exde F
(IP) AIDS SHROUDS HC SPECIAL S Atex/IECEx Exde B
MALE BUSH LONG JA Atex/IECEx Exd C
MALE BUSH STD 17 JB Atex/IECEx Exe Q
DIGIT 9 CODE Industrial X or Blank
MALE BUSH ROUND JQ
FEMALE BUSH JC Special
NIPPLE THREADED 30mm JD None (standard) X or Blank Product Coding Notes
ACCESSORIES Customer Special S
NIPPLE LONG THREADED JE Male thread is always quoted first (digits 4+5)
NIPPLE BARREL JF followed by the Female thread (digits 6+7)
COUPLER ROUND JG
DIGIT 10 CODE Other threads are available, please consult the sales
COUPLER HEX JH department
COUPLER FLANGE JJ Plating
None Blank Digit 8 (No approval) is blank if digits 9 & 10 are not
Nickel N required, otherwise use X
Zinc Z Digit 9 (Not Customer specific) is blank if digit 10 is
Products shaded are not certified and not required, otherwise use X
Chromatised C
do not have any associated approvals
Special S Digit 10 (Plating) is blank if no plating is required

PRODUCT MATERIAL MALE THREAD FEMALE THREAD APPROVAL SPECIAL PLATING PART NUMBER
PRODUCT CODING Adaptor Brass ½" NPT(M) M20(F) Exd None Nickel
= ABA4212DXN
EXAMPLE AB A 42 12 D X N

PRODUCT CODING Hex Head Plug ST/ST 2" BSPT(M) (F) Gost Exd IICU Yes None
= CKE5700VS
EXAMPLE CK E 57 00 V S Blank

28
HAZARDOUS AREAS

GROUPING OF ELECTRICAL APPARATUS FOR POTENTIALLY EXPLOSIVE ATMOSPHERES


GROUP I: ELECTRICAL APPARATUS FOR MINING, TYPIFIED BY THE GAS METHANE (FIREDAMP)
GROUP II: ELECTRICAL APPARATUS FOR SURFACE INDUSTRY
Group II may be further divided into three gas groups:
IIA - Representative Gas Propane
IIB - Representative Gas Ethylene
IIC - Representative Gas Hydrogen
Gas Group IIC covers the most hazardous gases and as such, apparatus marked IIC may be used in IIA and IIB applications.

CLASSIFICATIONS
GAS DUST

ZONE 0 20 Zone in which an explosive atmosphere is constantly present, or present for long periods. (Rough guide: hazard present for more than 1000 hours/year).

ZONE 1 21 Zone in which an explosive atmosphere is likely to occur in normal operation. (Rough guide: hazard present between 10 & 1000 hours/year).

ZONE 2 22 Zone in which an explosive atmosphere is not likely to occur in normal operation and if it occurs it will exist only for a short time. (Rough guide: hazard present for less
than 10 hours/year).
Guidance in the classification of hazardous areas is given in BS EN 60079-10-1:2009, IEC79-10.

PROTECTION CONCEPTS
STANDARD IEC/EN CODE PROTECTION CONCEPT ZONE

GAS DUST GAS DUST GAS DUST

60079-0 61241-0 General Requirements

60079-1 Ex d Flameproof 1

61241-1 Ex tD Enclosure 20/21/22

60079-2 61241-2 Ex p Ex pD Pressurised 1 21/22

60079-5 Ex q Powder Filled 1

60079-6 Ex o Oil Filled 1

60079-7 Ex e Increased Safety 1

Ex ia Ex iaD 0 20
60079-11 61241-11 Intrinsic Safety
Ex ib Ex ibD 1 21

Ex nA Non Sparking

Ex nL Energy Limited

60079-15 Ex nR Restricted Breathing 2

Ex nC Enclosed Break

Ex nP Pressurisation

Ex ma Ex maD 0 20
60079-18 61241-18 Encapsulation
Ex mb Ex mbD 1 21

*In some countries the methods of protection a & q are allowed in Zone 1.

TEMPERATURE CLASS
Explosion protected electrical apparatus must be designed and tested to ensure that the maximum surface MAXIMUM SURFACE
temperature of any part(s) of the products are below the ignition temperature of the explosive atmosphere TEMPERATURE CLASS TEMPERATURE
concerned. Group II electrical apparatus is divided into temperature classes according to the maximum (DEGREES CELSIUS)
permissible surface temperature of the apparatus. The preferable classification of temperatures is given in the T1 450
table on the right. T2 300
Unless otherwise specified the maximum ambient temperature is taken to be 400ºC. T3 200
T4 135
T5 100
T6 85

29
INGRESS PROTECTION INFORMATION

FIRST NUMBER - DUST SECOND NUMBER - WATER

0 Non-protected 0 Non-protected

1 Protected against solid foreign objects of 50mm ø and 1 Protected against vertically falling water drops.
greater. Vertically falling drops shall have no harmful effects.
The object probe, sphere of 50mm ø, shall not fully
50 penetrate†

2 Protected against solid foreign objects of 12.5mm ø and 2 Protected against vertically falling water drops when
greater. enclosure tilted up to 15º
The object probe, sphere of 12.5mm ø, shall not fully Vertically falling drops shall have no harmful effects when
12.5 penetrate† the enclosure is tilted at any angle up to 15º on either side
of the vertical.

3 Protected against solid foreign objects of 2.5mm ø and 3 Protected against spraying water.
greater. Water sprayed at an angle up to 60º on either side of the
The object probe, sphere of 2.5mm ø, shall not fully vertical shall have no harmful effects.
penetrate† at all

4 Protected against solid foreign objects of 1.0mm ø and 4 Protected against splashing water.
greater. Water splashed against the enclosure from any direction
The object probe, sphere of 1.0mm ø, shall not fully shall have no harmful effects.
penetrate† at all

5 Dust Protected. 5 Protected against water jets.


Ingress of dust is not totally prevented, but dust shall not Water projected in jets against the enclosure from any
penetrate in a quantity to interfere with satisfactory direction shall have no harmful effects.
operation of apparatus or to impair safety.

6 Dust-tight. 6 Protected against powered water jets.


No ingress of dust. Water projected in jets against the enclosure from any
direction shall have no harmful effects.

7 Protected against the effect of temporary immersion in


water.
15CM MIN
Ingress of water in quantities causing harmful effects shall
1M not be possible when enclosure is temporarily immersed
in water under standardised conditions of pressure and
time.

8 Protected against the effect of continuous immersion in


water.
Ingress of water in quantities causing harmful effects shall
not be possible when enclosure is continuously immersed
in water under conditions which shall be agreed between
† The full diameter of the object manufacturer and user but which are more severe than for
probe shall not pass through an numeral 7.
opening of the enclosure.

30
31
29
CONTACT INFORMATION

Raxton Limited
Westgate, Aldridge, West Midlands, WS9 8FS

T: +44 (0) 1922 450400


F: +44 (0) 1922 450401
E: [email protected]
W: www.raxton.co.uk

RXBR-GNXX-1201