9550-9555 (Eng - 090714)
9550-9555 (Eng - 090714)
Description
Variable orifice cast iron double regulating valve
Flanged ends according EN1092-2 PN16 (ex DIN2533)
Lengths according EN558-1 series 1 (ex DIN3202 F1)
Alkyd/acrylic single layer waterpaint coating (50-100µm)
Tolerance on nominal Kv for completely open valve ±5%
(test according BS7350)
Available on following versions:
● Fig. 9550, with threaded and plugged drains (¼" ISO 7/1Rp)
(allow later mounting of test points)
● Fig. 9555, with test points (given unmounted)
Gost compliant
Working conditions:
● Water: -10°C to +150°C (Max 130°C for Fig.9555)
below 0°C only for water with added antifreezing fluids
over 100°C only for water with additives avoiding boiling
21
20
Part List 19
18
N. Part Material Norm 17
1 Body Cast iron EN-GJL-250 JL1040 16
2 Seat Stainless steel X12Cr13 (1.4006)
15
3 Cone screw Zinc plated steel -
4 Cone gasket Copper - 14
5 Balancing cone Cast iron EN-GJL-250 JL1040 13
6 Gasket disc PTFE1 - 12
7 Shutter Cast iron EN-GJL-250 JL1040
8 Nut Brass CuZn39Pb2 11
9 Memory stop Brass CuZn40Pb2 10
10 Mem. stop O-ring EPDM Perox - 9
11 Stem Brass CuZn40Pb2 22b
12 Screw Stainless steel - 8
13 Bushing Brass CuZn37 7 For Fig.
14 Washer Brass CuZn37 6 9550 23b
15 Gasket Graphite -
5
16 Bonnet Cast iron EN-GJL-250 JL1040
17 M16 screws Zinc plated steel - 4
18 Int. bushing O-ring EPDM Perox - 3 22a
19 Bushing Brass CuZn37 For Fig.
2
20 Ext. bushing O-ring EPDM Perox - 9555
21 Handwheel Steel2 - 1
22a Test point DZR Brass EN12164 CW602N 23a
23a Tie Polyprop. (blue / red) -
22b Plug O-ring Fiber -
23b Plug Zinc plated steel -
1
EPDM above DN200 (included)
2
Indicator in ABS material
090714
Drawings, photos and data contained in this card are provided for information only. VIR reserves the right to change them without notice.
090714
Dimensions
ØF ØE NxØD L H ØV Weight Flow range1 ØV
DN
(mm) (mm) (mm) (mm) (mm) (mm) (kg) (l/s)
065 185 145 4x19 290 300 150 20,5 3,02-6,95
080 200 160 8x19 310 330 150 25,3 6,40-15,36
100 220 180 8x19 350 335 175 35,0 10,85-26,04 H
S
125 250 210 8x19 400 355 175 50,0 16,85-39,75
150 285 240 8x23 480 405 200 73,5 23,71-56,91
200 340 295 12x23 600 580 300 147,0 41,86-100,47
250 405 355 12x28 730 655 300 215,0 66,58-156,78 ØF ØE
300 460 410 12x28 850 640 300 280,0 94,16-255,99
1
Suggested flow range applicability (BS7350)
NxØD
If used with measuring manometers different from those proposed by VIR please verify that sensibility of the measuring
device is compatible with indicated minimum flow (see flow measurement paragraph)
L
Flow Measurement
Handwheel Kv (m3/h @ 1bar)
position 065 080 100 125 150 200 250 300
1,0 - 14,2 15,3 - - - - -
2,0 16,3 23,3 26,2 36,6 50,0 76 96 124
3,0 22,9 31,5 37,3 52,5 71,4 105 127 -
4,0 29,6 39,6 48,5 69,3 91,0 132 162 226
5,0 36,4 48,3 59,3 87,0 111,4 160 198 -
6,0 43,2 57,0 70,1 103,9 137,0 188 232 328
7,0 48,9 65,4 80,4 120,1 160,0 215 263 -
8,0 54,6 73,9 90,8 137,4 183,1 243 300 411
Low
9,0 62,1 82,4 101,8 156,7 205,7 270 332 -
pressure
10,0 69,5 91,0 112,9 175,2 227,1 296 367 520
test point
11,0 77,6 102,6 127,8 202,5 253,1 327 400 -
12,0 85,7 114,2 142,7 228,1 276,9 355 447 -
13,0 93,5 122,4 157,4 255,9 304,5 382 469 -
14,0 - 130,7 172,1 285,5 332,6 412 506 -
15,0 - 140,5 189,1 313,5 361,7 441 539 680
16,0 - - 206,1 342,6 390,0 477 572 -
17,0 - - 224,2 370,8 417,0 518 608 -
18,0 - - - - 445,7 553 646 -
19,0 - - - - 472,5 590 684 -
20,0 - - - - 500,6 628 721 1111 ∆pTP
21,0 - - - - - 668 762 -
22,0 - - - - - 707 805 -
23,0 - - - - - 750 848 -
24,0 - - - - - 790 891 - Q (flow) High
25,0 - - - - - 825 930 1331 pressure
26,0 - - - - - 867 961 - test point
27,0 - - - - - 910 1031 -
28,0 - - - - - - 1078 -
29,0 - - - - - - 1126 -
30,0 - - - - - - 1173 1592
31,0 - - - - - - 1217 -
32,0 - - - - - - 1257 -
33,0 - - - - - - 1302 17181
1
For handwheel position 33,3
Formula linking flow Q (in l/s) and ∆p measured at test points (in kPa). Kv depends on
handwheel position as indicated on table.
K v ⋅ ∆p TP Minimum flow that can be measured for each diameter may be calculated by using in Via Circonvallazione, 10
Q= the formula minimum ∆p that can be measured by used manometer. 13018 Valduggia (VC), Italy
36 Valves are anyway designed for best performances when used on range previously Tel: +39 0163 47891
suggested and as indicated by BS7350. Fax: +39 0163 47895
www.vironline.com
Drawings, photos and data contained in this card are provided for information only. VIR reserves the right to change them without notice.
DN65
100 Handwheel
position
2,0
3,0
4,0
5,0
[kPa]
6,0
10
TP
7,0
∆p
8,0
9,0
10,0
11,0
12,0
1
0,1 1 10 100 13,0
Flow [l/s]
DN80
100 Handwheel
position
1,0
2,0
3,0
4,0
5,0
[kPa]
6,0
10
7,0
TP
∆p
8,0
9,0
10,0
11,0
12,0
13,0
14,0
1
0,1 1 10 100 15,0
Flow [l/s]
DN100
100 Handwheel
position
1,0
2,0
3,0
4,0
5,0
[kPa]
6,0
10 7,0
TP
8,0
∆p
9,0
10,0
11,0
12,0
13,0
14,0
15,0 Via Circonvallazione, 10
13018 Valduggia (VC), Italy
1 16,0
Tel: +39 0163 47891
0,1 1 10 100 17,0 Fax: +39 0163 47895
Flow [l/s] www.vironline.com
Drawings, photos and data contained in this card are provided for information only. VIR reserves the right to change them without notice.
DN125
100 Handwheel
position
2,0
3,0
4,0
5,0
6,0
[kPa]
7,0
10 8,0
TP
9,0
∆p
10,0
11,0
12,0
13,0
14,0
15,0
1 16,0
1 10 100 17,0
Flow [l/s]
DN150
100 Handwheel
position
2,0
3,0
4,0
5,0
6,0
7,0
[kPa]
8,0
10 9,0
TP
10,0
∆p
11,0
12,0
13,0
14,0
15,0
16,0
17,0
18,0
1 19,0
10 100 20,0
1
Flow [l/s]
DN200
100 Handwheel
position
2,0
3,0
4,0
5,0
[kPa]
6,0
10
7,0
TP
∆p
8,0
9,0
10,0
12,0
15,0 Via Circonvallazione, 10
20,0 13018 Valduggia (VC), Italy
1 Tel: +39 0163 47891
1 10 100 1000 27,0 Fax: +39 0163 47895
Flow [l/s] www.vironline.com
Drawings, photos and data contained in this card are provided for information only. VIR reserves the right to change them without notice.
DN250
100 Handwheel
position
2,0
4,0
6,0
[kPa]
8,0
10
TP
10,0
∆p
12,0
15,0
20,0
25,0
1
1 10 100 1000 33,0
Flow [l/s]
DN300
100 Handwheel
position
2,0
4,0
6,0
[kPa]
8,0
10
TP
10,0
∆p
15,0
20,0
25,0
30,0
1
10 100 1000 33,3
1
Flow [l/s]
Via Circonvallazione, 10
13018 Valduggia (VC), Italy
Tel: +39 0163 47891
Fax: +39 0163 47895
www.vironline.com
Drawings, photos and data contained in this card are provided for information only. VIR reserves the right to change them without notice.
Headloss calculation
Handwheel Kv (m3/h @ 1bar)
position 065 080 100 125 150 200 250 300
1,0 - 14,2 15,3 - - - - -
2,0 16,3 23,3 26,2 36,6 50,0 76 96 124
3,0 22,9 31,5 37,3 52,5 71,4 105 127 -
4,0 29,6 39,6 48,5 69,3 91,0 132 162 226
5,0 36,4 48,3 59,3 87,0 111,4 160 198 -
6,0 43,2 57,0 70,1 103,9 137,0 188 232 328
7,0 48,9 65,4 80,4 120,1 160,0 215 263 -
8,0 54,6 73,9 90,8 137,4 183,1 243 300 411
9,0 62,1 82,4 101,8 156,7 205,7 270 332 -
10,0 69,5 91,0 112,9 175,2 227,1 296 367 520
11,0 77,6 102,6 127,8 202,5 253,1 327 400 -
12,0 85,7 114,2 142,7 228,1 276,9 355 447 -
13,0 93,5 122,4 157,4 255,9 304,5 382 469 -
14,0 - 130,7 172,1 285,5 332,6 412 506 -
15,0 - 140,5 189,1 313,5 361,7 441 539 680
16,0 - - 206,1 342,6 390,0 477 572 -
17,0 - - 224,2 370,8 417,0 518 608 -
18,0 - - - - 445,7 553 646 -
19,0 - - - - 472,5 590 684 -
20,0 - - - - 500,6 628 721 1111
21,0 - - - - - 668 762 -
22,0 - - - - - 707 805 -
23,0 - - - - - 750 848 -
∆p
24,0 - - - - - 790 891 - Q (flow)
(headloss)
25,0 - - - - - 825 930 1331
26,0 - - - - - 867 961 -
27,0 - - - - - 910 1031 -
28,0 - - - - - - 1078 -
29,0 - - - - - - 1126 -
30,0 - - - - - - 1173 1592
31,0 - - - - - - 1217 -
32,0 - - - - - - 1257 -
33,0 - - - - - - 1302 17181
1
For handwheel position 33,3
Copy of the table presented in flow measurement paragraph
∆p (headloss) approximately equal to ∆pTP
2
36 ⋅ Q Formula linking flow Q (in l/s) and theoretical valve headloss ∆p (in kPa).
∆p = Kv depends on handwheel position as indicated on table.
KV
Installation
To obtain the best performances valve must be installed on a pipe with its same
nominal size preceded and followed by straight pipe lengths as per figure
indications.
Min 5xDN
(10xDN if installed Min 2xDN
Via Circonvallazione, 10
on pump outlet))
13018 Valduggia (VC), Italy
Tel: +39 0163 47891
Fax: +39 0163 47895
www.vironline.com
Drawings, photos and data contained in this card are provided for information only. VIR reserves the right to change them without notice.
Presetting