25-08-2021 - 24 - Design Report CWR 100KL SBC 7T Zone 4 Pug 02 - Sample
25-08-2021 - 24 - Design Report CWR 100KL SBC 7T Zone 4 Pug 02 - Sample
ZONE IV
SBC 7 T/m2
Inner Dia 6.1 m
Dead store 0.1 m
Nos of inner column Yes
provide
Height of live storage 3.5 m
Free board 0.3 m
GRADE OF CONCRETE 35
GRADE OF STEEL 415
Slab thickness 0.15 m
wall thickness top 0.15
wall thickness Base 0.15
Depth below NGL 1.2
THICKNESS FLOOR & WALL 200
FOOTING
RCC DESIGN CALACULATIONS FOR CLEAR WATER RESERVIOR
CAPACITY 100.00 KL SBC 7.00 T/M2 SHAPE
ZONE IV TYPE PUG CIRCULAR
CAPACITY SIZING
Total capacity of cwr = 100 KL
No of cwr = 1
Design Capacity of reservoir,(C). = 100.00 KL
Safe bearing pressure of soil = 7.00 T/Sqm.
Safe bearing pressure of soil adopted = 7.00 T/Sqm.
Assume inner diameter of vertical wall (D1) = 6.10 Meters.
Dead storage provided. = 0.10 Meters.
Volume reduction due to columns supporting stair case head room = 0.00 Cum.
volume reduction by column supporting flat slab = 0.00 Cum.
volume reduction by column head = 0.00 Cum.
Volume reduction due to RCC stair case = 0.00 Cum.
Total volume reduction = 0.00 Cum.
Gross volume of container required in live storage height = 100.00 Cum.
Gross volume of container provided in live storage height = 102.23 Cum.
Net volume of container provided in live storage height = 102.23 Cum.
Height of live storage provided = 3.50 Meters.
Height of water column including dead storage = 3.60 Meters.
Free board adopted = 0.30 Meters.
DISTANCE
0.0 R 0.000 0.0625 0.00 0.00 360 100 10 218 200 392.50
0.1 R 0.305 0.0606 0.04 0.79 360 100 10 218 200 392.50
0.2 R 0.610 0.0550 0.15 2.86 360 100 10 218 200 392.50
0.3 R 0.915 0.0456 0.29 5.33 360 100 10 218 200 392.50
0.4 R 1.220 0.0325 0.37 6.75 360 100 10 218 200 392.50
0.5 R 1.525 0.0156 0.27 5.06 360 100 10 218 200 392.50
0.6 R 1.830 -0.0050 0.13 2.34 360 100 10 218 200 392.50
0.7 R 2.135 -0.0294 1.01 18.72 360 100 10 218 200 392.50
0.8 R 2.440 -0.0575 2.58 47.93 360 100 10 218 200 392.50
0.9 R 2.745 -0.0894 5.09 94.67 360 100 10 218 200 392.50
1.0 R 3.050 -0.1250 8.78 164.32 360 100 10 218 200 392.50
0.1 R 0.305 0.0619 0.0435 360.0 100 10 218 200 OK 0.39 0.00 0.44
0.2 R 0.610 0.0600 0.1686 360.0 100 10 218 200 OK 0.39 0.00 0.44
0.3 R 0.915 0.0569 0.3597 360.0 100 10 218 200 OK 0.39 0.15 0.44
0.4 R 1.220 0.0525 0.5900 360.0 100 10 218 200 OK 0.39 0.08 0.44
0.5 R 1.525 0.0469 0.8235 360.0 100 10 218 200 OK 0.39 0.05 0.44
0.6 R 1.830 0.0400 1.0114 360.0 100 10 218 200 OK 0.39 0.03 0.44
0.7 R 2.135 0.0319 1.0978 360.0 100 10 218 200 OK 0.39 0.01 0.44
0.8 R 2.440 0.0225 1.0114 360.0 100 10 218 200 OK 0.39 0.02 0.44
0.9 R 2.745 -0.0119 0.6770 360.0 100 10 218 200 OK 0.39 0.03 0.44
1.0 R 3.050 0.0000 0.0000 360.0 100 10 218 200 OK 0.39 0.04 0.44
DESIGN OF OUTER VERTICAL WALL (CASE-1 - WATER INSIDE AND NO SOIL OUTSIDE)
CONC. MIX M 35
Assuming thickness of wall at base = 15.00 Cm.
Height of uniform thickness from top = 0.00 M
Assuming thickness of wall at top = 15.00 Cm.
Weghed average thickness = 15.00 Cm.
H^2/Dt = 14.16
cover = 45 mm
The vertical wall shall be design in accordance to the recommendation given in clause 5.4.b.of IS : 3370 (Part II)
The values of the coffecients for moments & Hoop tension shall be calculated by interpretation from the following
tables
Table No.10 IS:3370(part-IV)-1967 for coefficient for bending moment in cylinderical wall with fixed base free
top and subject to tringular load (clause 3.1.1 of IS : 3370 Part IV). IS code have coefficient values for H 2/DT value
only up to 16.
Depth Below TWL Coeff. Coeff. Coeff. Bending Requred depth Provided Area of sreel rqd Area of sreel
depth for B.M. rqd for B.M.
for for for Moment
14 22
19.16372 0.24 0.36
0.32
6 8 10 12 14 16
0.0001 0 0 0 0 0
0.0003 0.0001 0 -0.0001 0 0
0.0008 0.0002 0.0001 0.0001 0 -0.0001
0.0019 0.0008 0.0004 0.0002 0 -0.0002
0.0032 0.0016 0.0007 0.0003 0.0001 -0.0001
0.0046 0.0028 0.0019 0.0013 0.0008 0.0004
0.0051 0.0038 0.0029 0.0023 0.0019 0.0013
0.0029 0.0029 0.0028 0.0026 0.0023 0.0019
-0.0041 -0.0022 -0.0012 -0.0005 -0.0001 0.0001
-0.0187 -0.0146 -0.0122 -0.0104 -0.009 -0.0079
BOTTOM SECTION OF WALL
Coefficient for design of uncracked section = 3.33
Maximum -ve bending moment at the base of wall = -4.16 KN.M/M
Maximum +ve bending moment = 1.06 KN.M/M
Min.overall thickness reqd. for uncracked sec. = 111.77 mm.
(-4.16)/3.33)^0.5
Overall thckness of wall provided at base is OK = 150 mm.
Dia. of bar proposed to be used 10 mm + = 10 mm.
Effective depth of section availablebase = 100.00 mm.
Area of steel required considering B.M. = 322.48 Sq.mm.
Spacing of bars required = 243.43 mm.
Spacing of bars provided = 195.00 mm.
Area of steel actually provided = 0.40 Sq.cm.
BASE SHEAR FOR SIESMIC FORCES
base shear for impulsive mode Vi = 1043.80 Kn
Base shear for convective mode Vc = 192.56 Kn
Resultant Base shear (Vi 2+Vc2) = 1061.41 Kn
Sectional area of wall = 2.87 sqm
Shear stress due to seismic forces = 0.369 n/mm2
% steel available on water face at the base of wall = 0.40 %
Sa/g
For the impulsive mode 1.954
For the convective mode 0.678
Total steel
Total steel
reqd
Height of wall Thk of Seismic hoop Min temp reqd with Adopted area Actual permissib
Total force without
above base section force forces steel reqd seismic of steel reqd stress le stress
seismic
forces
force
FLOOR SLAB
CONCRETE MIX: M = 35.00
The floor slab is directly supported on the ground
and is non structural.As such only temp. steel is reqd.
Provide thickness of floor slab as = 20.00 Cm.
Temperature steel required = 0.240 %
Area of steel required = 2.400 Sq.cm.
Diameter of bar chosen = 8.000 mm.
Spacing of bars near both face required = 20.93 Cm.C/C
3.14/4*8.00^2/2.40
Spacing of bars provided = 20.00 Cm.C/C
DESIGN OF OUTER WALL (CASE 2-NO WATER INSIDE AND SOIL OUTSIDE)
COEFF. FOR EARTH PRESSURE = 0.30
Depth of floor below ground level = 1.2 M
THK. OF WALL AT BASE = 15.00 CM
THK AT 1.2 M ABOVE FLOOR = 15.00 cm
WEGHED THK = 15.00 cm
H2/DT = 1.574
DEPTH BELOW G.L. B.M. B.M. B.M.
COEFF. COEFF. COEFF. BM
FRACTION METER 1.2 1.6 1.57
0.1H 0.12 0.0012 0.0011 0.00111 0.978
0.2H 0.24 0.0042 0.0041 0.00411 3.622
0.3H 0.36 0.0077 0.0075 0.00752 6.627
0.4H 0.48 0.0103 0.0107 0.01068 9.412
0.5H 0.60 0.0112 0.0121 0.01205 10.619
0.6H 0.72 0.0090 0.0111 0.01097 9.668
0.7H 0.84 0.0022 0.0058 0.00557 4.909
0.8H 0.96 -0.0108 -0.0051 -0.00548 -4.829
0.9H 1.08 -0.0311 -0.0232 -0.02372 -20.904
1.0H 1.20 -0.0602 -0.0505 -0.05114 -45.069
COVER = 35.00 mm.
EFFECTIVE DEPTH AVAILABLE AT BASE = 11.10 CM
MAX NEGETIVE B.M. AT BASE = 45.07 KG-M
AREA OF STEEL REQD. = 0.363 SQCM
soil face 8 mm + = 8.00 mm.
Spacing of Bars required = 138.34 cm
Spacing of Bars provided = 20.00 cm
Area of steel actually provided = 5.02 SQCM
DESIGN OF WALL FOOTING :
CONCRETE MIX M = 35
THICKNESS OF FOUNDATION SLAB ASSUMED THFS = 20.00 CM
DEPTH OF FOOTING BELOW GROUND DOF1 = 1.20 M
UNIT WEIGHT OF SOIL = 1700.00 KG / Cu.M
SAFE BEARING PRESSURE SBP = 7000.00 KG / SQ.M
MAX.ALLOW. GROSS LOADING AT FOOTING LEVEL SLF = 7000.00 KG / SQ.M
ASSUMING WIDTH OF HEEL SLAB HWID = 0.30 M
ASSUMING WIDTH OF TOE SLAB TWID = 0.60 M
WIDTH OF WALL AT BASE = 0.15 M
TOTAL WIDTH OF FOOTING SLAB FWID = 1.05 M
THE FOLLOWING TABLE GIVES CALCULATION OF LOAD AND MOMENTS ON THE FOOTING
LOAD DUE TO LOAD PER DISTANCE FROM
ITEM METER EDGE OF HEEL
KG M KG-M
VERTICAL WALL PART 1 1463 0.375 548
VERTICAL WALL PART 2 0 0.000 0
WT. FROM ROOF 1151 0.375 432
WT. OF SOIL 612 0.150 92
WT. OF BASE SLAB 525 0.525 276
NET MOMENT DUE TO SOIL 45
TOTAL 3751 1393