0% found this document useful (0 votes)
26 views15 pages

25-08-2021 - 24 - Design Report CWR 100KL SBC 7T Zone 4 Pug 02 - Sample

The document provides detailed RCC design calculations for a clear water reservoir with a capacity of 100 KL, including specifications for materials, dimensions, and load calculations. It outlines the structural requirements such as wall thickness, slab thickness, and reinforcement details based on relevant IS codes. Additionally, it includes calculations for bending moments, hoop tension, and the provision of vertical reinforcement bars.

Uploaded by

Rajendra Mittal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
26 views15 pages

25-08-2021 - 24 - Design Report CWR 100KL SBC 7T Zone 4 Pug 02 - Sample

The document provides detailed RCC design calculations for a clear water reservoir with a capacity of 100 KL, including specifications for materials, dimensions, and load calculations. It outlines the structural requirements such as wall thickness, slab thickness, and reinforcement details based on relevant IS codes. Additionally, it includes calculations for bending moments, hoop tension, and the provision of vertical reinforcement bars.

Uploaded by

Rajendra Mittal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 15

CAPACITY 100 KL

ZONE IV
SBC 7 T/m2
Inner Dia 6.1 m
Dead store 0.1 m
Nos of inner column Yes
provide
Height of live storage 3.5 m
Free board 0.3 m
GRADE OF CONCRETE 35
GRADE OF STEEL 415
Slab thickness 0.15 m
wall thickness top 0.15
wall thickness Base 0.15
Depth below NGL 1.2
THICKNESS FLOOR & WALL 200
FOOTING
RCC DESIGN CALACULATIONS FOR CLEAR WATER RESERVIOR
CAPACITY 100.00 KL SBC 7.00 T/M2 SHAPE
ZONE IV TYPE PUG CIRCULAR
CAPACITY SIZING
Total capacity of cwr = 100 KL
No of cwr = 1
Design Capacity of reservoir,(C). = 100.00 KL
Safe bearing pressure of soil = 7.00 T/Sqm.
Safe bearing pressure of soil adopted = 7.00 T/Sqm.
Assume inner diameter of vertical wall (D1) = 6.10 Meters.
Dead storage provided. = 0.10 Meters.
Volume reduction due to columns supporting stair case head room = 0.00 Cum.
volume reduction by column supporting flat slab = 0.00 Cum.
volume reduction by column head = 0.00 Cum.
Volume reduction due to RCC stair case = 0.00 Cum.
Total volume reduction = 0.00 Cum.
Gross volume of container required in live storage height = 100.00 Cum.
Gross volume of container provided in live storage height = 102.23 Cum.
Net volume of container provided in live storage height = 102.23 Cum.
Height of live storage provided = 3.50 Meters.
Height of water column including dead storage = 3.60 Meters.
Free board adopted = 0.30 Meters.

Depth of edge beam considered in water column 0.00 = 0.00 Meters.


Water Column considered in vertical wall design 3.6+0.3 = 3.900 Meters.
RC DESIGN OF CIRCULAR FLAT ROOF SLAB FOR 100KL CWR
GENERAL DATA
GRADE OF CONCRETE M = 35 N/mm2
GRADE OF STEEL Fe = 415 N/mm2
Permisible Stress in concrete σ
cbc = 11.5 N/mm2
Permisible Stress in steel σ
st = 130 N/mm2
Cover = 45 mm
m = 8.12
kc = 0.42
DESIGN CONSTANT
jc = 0.86
Rc = 2.08
DIA OF CIRCULAR SLAB D = 6.10 M
Radius OF CIRCULAR SLAB R = 3.05 M
LOAD CALCULATIONS
DEAD LOAD = 375.00 Kg/m2
LIVE LOAD = 200.00 Kg/m2
FINISH LOAD = 180.00 Kg/m2
TOTAL LOAD = 755.00 Kg/m2
AREA OF SLAB = 29.21 m2
THK OF SLAB PROVIDED = 150.00 MM
PREMISSIBLE CONCRETE STRESS FOR M35 = 2.20 N/MM2
As per IS-456 Annexure-B clause B-2.3 increase in permissible
stresses due to wind load & secmic = 1.33
UNCRACKED SECTION FACTOR = 4.88
DESIGN CALCULATION OF CIRCULAR SLAB
BOTTOM FACE REINFORCEMENT DETAIL (RADIALS)
DISTANCE (M) BENDING BENDING Ast Req Ast Req Eff. Thk Bar Dia at Spacing req Spacing prov at Ast Prov at
MOMEN MOMENT (mm2) Temp (mm) Bottom(m (mm) (At Bottom bottom(mm2)
COFFICENT Knm/m (mm2) m) Radials Bottom) Face(mm)

DISTANCE
0.0 R 0.000 0.0625 0.00 0.00 360 100 10 218 200 392.50
0.1 R 0.305 0.0606 0.04 0.79 360 100 10 218 200 392.50
0.2 R 0.610 0.0550 0.15 2.86 360 100 10 218 200 392.50
0.3 R 0.915 0.0456 0.29 5.33 360 100 10 218 200 392.50
0.4 R 1.220 0.0325 0.37 6.75 360 100 10 218 200 392.50
0.5 R 1.525 0.0156 0.27 5.06 360 100 10 218 200 392.50
0.6 R 1.830 -0.0050 0.13 2.34 360 100 10 218 200 392.50
0.7 R 2.135 -0.0294 1.01 18.72 360 100 10 218 200 392.50
0.8 R 2.440 -0.0575 2.58 47.93 360 100 10 218 200 392.50
0.9 R 2.745 -0.0894 5.09 94.67 360 100 10 218 200 392.50
1.0 R 3.050 -0.1250 8.78 164.32 360 100 10 218 200 392.50

CIRCUM REINFORCEMENT DETAIL AT BOTTOM COVER:- 45 MM SHEAR CHECK


DISTANCE (M) BENDING BENDING Ast Eff. Thk Ba Dia Spacing Spacing % STEEL ζv ζc
S.NO. DISTANCE MOMEN MOMENT Req (mm) (mm) req (mm) prov (mm) (N/mm2) (N/mm2)
COFFICENT
0.0 R 0.000 0.0625 0.0000 360.0 100 10 218 200 OK 0.39 0.00 0.44

0.1 R 0.305 0.0619 0.0435 360.0 100 10 218 200 OK 0.39 0.00 0.44
0.2 R 0.610 0.0600 0.1686 360.0 100 10 218 200 OK 0.39 0.00 0.44
0.3 R 0.915 0.0569 0.3597 360.0 100 10 218 200 OK 0.39 0.15 0.44
0.4 R 1.220 0.0525 0.5900 360.0 100 10 218 200 OK 0.39 0.08 0.44
0.5 R 1.525 0.0469 0.8235 360.0 100 10 218 200 OK 0.39 0.05 0.44
0.6 R 1.830 0.0400 1.0114 360.0 100 10 218 200 OK 0.39 0.03 0.44
0.7 R 2.135 0.0319 1.0978 360.0 100 10 218 200 OK 0.39 0.01 0.44
0.8 R 2.440 0.0225 1.0114 360.0 100 10 218 200 OK 0.39 0.02 0.44
0.9 R 2.745 -0.0119 0.6770 360.0 100 10 218 200 OK 0.39 0.03 0.44
1.0 R 3.050 0.0000 0.0000 360.0 100 10 218 200 OK 0.39 0.04 0.44
DESIGN OF OUTER VERTICAL WALL (CASE-1 - WATER INSIDE AND NO SOIL OUTSIDE)
CONC. MIX M 35
Assuming thickness of wall at base = 15.00 Cm.
Height of uniform thickness from top = 0.00 M
Assuming thickness of wall at top = 15.00 Cm.
Weghed average thickness = 15.00 Cm.
H^2/Dt = 14.16
cover = 45 mm
The vertical wall shall be design in accordance to the recommendation given in clause 5.4.b.of IS : 3370 (Part II)

The values of the coffecients for moments & Hoop tension shall be calculated by interpretation from the following
tables
Table No.10 IS:3370(part-IV)-1967 for coefficient for bending moment in cylinderical wall with fixed base free
top and subject to tringular load (clause 3.1.1 of IS : 3370 Part IV). IS code have coefficient values for H 2/DT value
only up to 16.

CALCULATION FOR BENDING MOMENT


From the above Two tables, values o coefficient for bending moment and Hoop tension have been interpolated
for the corresponding value of H^2/Dt. The value of bending moment and Hoop tension at different heights in
wall have been shown in the following tables.

Depth Below TWL Coeff. Coeff. Coeff. Bending Requred depth Provided Area of sreel rqd Area of sreel
depth for B.M. rqd for B.M.
for for for Moment

FRACTION METERS B.M. B.M. B.M. Near water Near outer


Face Face
H^2/Dt--> 14.0 16.0 14.16 KNm./m. mm mm sqmm sqmm
0.1H 0.360 0.0000 0.0000 0.0000 0.000 0.00 150 0.000 0.00
0.2H 0.720 0.0000 0.0000 0.0000 0.000 0.00 150 0.000 0.00
0.3H 1.080 0.0000 -0.0001 0.0000 -0.005 4.00 150 0.362 0.00
0.4H 1.440 0.0000 -0.0002 0.0000 -0.009 6.00 150 0.723 0.00
0.5H 1.800 0.0001 -0.0001 0.0001 0.042 11.00 150 0.000 3.26
0.6H 2.160 0.0008 0.0004 0.0008 0.359 32.00 150 0.000 27.85
0.7H 2.520 0.0019 0.0013 0.0019 0.868 49.00 150 0.000 67.27
0.8H 2.880 0.0023 0.0019 0.0023 1.059 54.00 150 0.000 82.10
0.9H 3.240 -0.0001 0.0001 -0.0001 -0.042 11.00 150 3.255 0.00
1.0H 3.600 -0.0090 -0.0079 -0.0089 -4.157 107.00 150 322.252 0.00

Requirement/Provision of Vertical Reinforcement Bars


Depth below Water Face Soil Face
TWL
Meters Min. Temp Area of steel Bar dia Spacing rqd Spacing Area of steel Bar dia Spacing rqd Spacing
Steel reqd. combination provided reqd. combination provided
Rqd Near
Each Face

sqmm mm mm c/c mm c/c mm2 mm mm mm


0.360 240.0 240.0 8.0 209.3 195.0 240.0 8.0 209.3 200.0
0.720 240.0 240.0 8.0 209.3 195.0 240.0 8.0 209.3 200.0
1.080 240.0 240.0 8.0 209.3 195.0 240.0 8.0 209.3 200.0
1.440 240.0 240.0 8.0 209.3 195.0 240.0 8.0 209.3 200.0
1.800 240.0 240.0 8.0 209.3 195.0 240.0 8.0 209.3 200.0
2.160 240.0 240.0 8.0 209.3 195.0 240.0 8.0 209.3 200.0
2.520 240.0 240.0 8.0 209.3 195.0 240.0 8.0 209.3 200.0
2.880 240.0 240.0 10.0 327.1 195.0 240.0 8.0 209.3 200.0
3.240 240.0 240.0 10.0 327.1 195.0 240.0 8.0 209.3 200.0
3.600 240.0 322.3 10.0 243.6 195.0 240.0 8.0 209.3 200.0
Moment
14 16 0.4 0.8 1.2 1.6 2 3 4 5
0.0000 0.0000 0.0005 0.0011 0.0012 0.0011 0.001 0.0006 0.0003 0.0002
0.0000 0.0000 0.0014 0.0037 0.0042 0.0041 0.0035 0.0024 0.0015 0.0008
0.0000 -0.0001 0.0021 0.0063 0.0077 0.0075 0.0068 0.0047 0.0028 0.0016
0.0000 -0.0002 0.0007 0.008 0.0103 0.0107 0.0099 0.0071 0.0047 0.0029
0.0001 -0.0001 -0.0042 0.007 0.0112 0.0121 0.012 0.009 0.0066 0.0046
0.0008 0.0004 -0.015 0.0023 0.009 0.0111 0.0115 0.0097 0.0077 0.0059
0.0019 0.0013 -0.0302 -0.0068 0.0022 0.0058 0.0075 0.0077 0.0069 0.0059
0.0023 0.0019 -0.0529 -0.024 -0.0108 -0.0051 -0.0021 0.0012 0.0023 0.0028
-0.0001 0.0001 -0.0816 -0.0465 -0.0311 -0.0232 -0.0185 -0.0119 -0.008 -0.0058
-0.0090 -0.0079 -0.1205 -0.0795 -0.0602 -0.0505 -0.0436 -0.0333 -0.0268 -0.0222

14 22
19.16372 0.24 0.36

0.32
6 8 10 12 14 16
0.0001 0 0 0 0 0
0.0003 0.0001 0 -0.0001 0 0
0.0008 0.0002 0.0001 0.0001 0 -0.0001
0.0019 0.0008 0.0004 0.0002 0 -0.0002
0.0032 0.0016 0.0007 0.0003 0.0001 -0.0001
0.0046 0.0028 0.0019 0.0013 0.0008 0.0004
0.0051 0.0038 0.0029 0.0023 0.0019 0.0013
0.0029 0.0029 0.0028 0.0026 0.0023 0.0019
-0.0041 -0.0022 -0.0012 -0.0005 -0.0001 0.0001
-0.0187 -0.0146 -0.0122 -0.0104 -0.009 -0.0079
BOTTOM SECTION OF WALL
Coefficient for design of uncracked section = 3.33
Maximum -ve bending moment at the base of wall = -4.16 KN.M/M
Maximum +ve bending moment = 1.06 KN.M/M
Min.overall thickness reqd. for uncracked sec. = 111.77 mm.
(-4.16)/3.33)^0.5
Overall thckness of wall provided at base is OK = 150 mm.
Dia. of bar proposed to be used 10 mm + = 10 mm.
Effective depth of section availablebase = 100.00 mm.
Area of steel required considering B.M. = 322.48 Sq.mm.
Spacing of bars required = 243.43 mm.
Spacing of bars provided = 195.00 mm.
Area of steel actually provided = 0.40 Sq.cm.
BASE SHEAR FOR SIESMIC FORCES
base shear for impulsive mode Vi = 1043.80 Kn
Base shear for convective mode Vc = 192.56 Kn
Resultant Base shear (Vi 2+Vc2) = 1061.41 Kn
Sectional area of wall = 2.87 sqm
Shear stress due to seismic forces = 0.369 n/mm2
% steel available on water face at the base of wall = 0.40 %

corresponding allowable stress = 0.449 n/mm2


OK

Spring mass model for Siesmic analysis as per IS 1893:2014 (Part 2)


For Ground supported tanks : Outer Wall
Type of tank ======> circular
Select Seismic Zone IV
Select Soil Type Medium Soil
Zone Factor, Z = 0.24
Importance Factor, I = (Table:1, IS 1893 (Part-2) 1.5
SBC 7.00 T/m2
Parameters for the circular tank Parameters for the circular tanks can be obtained from Fig 2 and for the rectangular
tanks these parameters can be obtained from the Fig 3, which has been shown as below
Parameters can be determined for impulsive and convective mode by h/D ratio; where "h" is the depth of
water in the tank and the "D" is the diameter of the tank

height of water column in the tank is h= 3.9 m


Dia meter of the tank is D= 6.10 m
height/Diameter, h/D = h/D = 0.639
Diameter/height, D/h = D/h = 1.565
Density of water p= 10 KN/m3
Thickness of wall at top t= 0.15 m
Weight of water in container m= 1139.18 KN
Corresponding to h/D ratio from Fig. 2 of IS 1893 (Part 2) :2014
Kch/mg = 0.806
mi/m = 0.646
mc/m = 0.353
hi/h = 0.375
hc/h = 0.649
hi*/h = 0.649
hc*/h = 0.731
Ci 4.231
Cc 3.305
Depth of the tank below the ground = 1.2 m
Total height of wall of the tank = 3.60 m
Response Reduction Factor (For SMRF) R = = 2.5
Damping For the impulsive mode = 5%
Damping For the convective mode = 0.5 %
As per the clause no 4.5.2 of IS Code 1893:2014 (part-2) the multiplying factors for the following mode for damping
will be
Multiplying factor
For the impulsive mode 1
For the convective mode 1.75

Determination of average response acceleration coefficient

Sa/g
For the impulsive mode 1.954
For the convective mode 0.678

Design of Horizontal seismic coefficient


Ah= Z*I*Sa/(2*R*g)
For the impulsive mode = Ahi 0.141
For the convective mode = Ahi 0.049
Lateral Lateral pressure due vertical
Height of wall Thk of resultant
S.No. Qiw impulsive Qcw convective to wall ground
above base section pressure
pressure pressure inertia accelaration

From To cm Piw (kg) Pcw (kg) Pww Pv Kg

1 3.24 3.60 15 0.000 0 0.5625 14196 517.58 276.04 14208


2 2.88 3.24 15 0.148 2382 0.4560 10358 517.58 607.30 10773
3 2.52 2.88 15 0.280 4011 0.3711 7492 517.58 938.55 8805
4 2.16 2.52 15 0.397 4972 0.3036 5364 517.58 1269.80 7780
5 1.80 2.16 15 0.498 5348 0.2505 3794 517.58 1601.05 7167
6 1.44 1.80 15 0.584 5223 0.2093 2641 517.58 1932.31 6608
7 1.08 1.44 15 0.654 4680 0.1779 1795 517.58 2263.56 5947
8 0.72 1.08 15 0.709 3802 0.1548 1172 517.58 2594.81 5174
9 0.36 0.72 15 0.747 2674 0.1391 702 517.58 2926.06 4386
10 0.00 0.36 15 0.771 1379 0.1300 328 517.58 3257.32 3783

Total steel
Total steel
reqd
Height of wall Thk of Seismic hoop Min temp reqd with Adopted area Actual permissib
Total force without
above base section force forces steel reqd seismic of steel reqd stress le stress
seismic
forces
force

From To cm Kg Kg Kg Sqcm Sqcm Sqcm Sqcm Kg/cm2 Kg/cm2


3.24 3.60 15 14208 2 14210 4.80 0.00 8.22 8.22 9.03 21.28 OK
2.88 3.24 15 10773 1058 11831 4.80 0.81 6.84 6.84 7.52 21.28 OK
2.52 2.88 15 8805 2164 10969 4.80 1.66 6.34 6.34 6.98 21.28 OK
2.16 2.52 15 7780 3283 11063 4.80 2.53 6.40 6.40 7.04 21.28 OK
1.80 2.16 15 7167 4475 11642 4.80 3.44 6.73 6.73 7.40 21.28 OK
1.44 1.80 15 6608 5821 12429 4.80 4.48 7.19 7.19 7.90 21.28 OK
1.08 1.44 15 5947 7228 13174 4.80 5.56 7.62 7.62 8.37 21.28 OK
0.72 1.08 15 5174 8359 13532 4.80 6.43 7.83 7.83 8.60 21.28 OK
0.36 0.72 15 4386 8279 12665 4.80 6.37 7.33 7.33 8.05 21.28 OK
0.00 0.36 15 3783 5653 9437 4.80 4.35 5.46 5.46 6.01 21.28 OK
CALCULATION FOR HOOP REINFORCEMENT FOR HINDGE BASE WITH FREE TOP & FIXED BASE WITH FREE TOP
HINGE BASE WITH FREE TOP
Depth Below (m) Coeff. For Hoop Coeff. For Hoop Coeff. For Hoop Tension for Hoop Reinforcement Hoop Hoop Max Hoop
Tension for Hinge Tension for Hinge Hoop Hinge Base and due to Hoop Tension Reinforcement due Reinforcement due Reinforcement
Base and Free Top Base and Free Top Tension Free Top per "m" per m to Temp. Steel per to seismic force per m
m per m

H^2/Dt--> 14.0 16.0 14.16 0.24


Kg. Sq. cm Sq. cm Sq. cm Sq. cm
0.0H 0.0000 0.002 0.0002 2 0.0014 4.80 5.46 5.46
0.1H 0.0960 0.100 0.0963 1058 0.8136 4.80 7.33 7.33
0.2H 0.1970 0.198 0.1971 2164 1.6647 4.80 7.83 7.83
0.3H 0.2990 0.299 0.2990 3283 2.5254 4.80 7.62 7.62
0.4H 0.4080 0.403 0.4076 4475 3.4427 4.80 7.19 7.19
0.5H 0.5310 0.521 0.5302 5821 4.4781 4.80 6.73 6.73
0.6H 0.6590 0.650 0.6583 7228 5.5598 4.80 6.40 6.40
0.7H 0.7610 0.764 0.7613 8359 6.4296 4.80 6.34 6.34
0.8H 0.7520 0.776 0.7540 8279 6.3681 4.80 6.84 6.84
0.9H 0.5130 0.536 0.5149 5653 4.3488 4.80 8.22 8.22

CALCULATION FOR HOOP REINFORCEMENT


The
Top Hoop force
thickness at different
shall heights
be provided in wall have been calculated in the following table. The table also shows
up to 0.00calculation of Hoop reinforcement and check for thickness of wall
M from top, keeping the direct tensile stress in concrete in permisible limits of 16.00 Kg/Sq.cm.
Depth Below m Dia. Of Hoop bar Spacing of hoop Spacing of Thickness of wall Tensile Stress on Height Above Base No of bars Height covered
chosen bars required per hoop bars avialable Cm equ. Area Kg/Sq.cm. Mtr. provided Nos. by hoop bars
cm Cm C/C provided Cms.
Cm C/C

0.0H 8.00 9.20 9.00 15.00 0.00 3.90 4 387


0.1H 8.00 6.86 6.50 15.00 0.71 3.51 6 351
0.2H 8.00 6.42 6.00 15.00 1.44 3.12 7 312
0.3H 8.00 6.59 6.50 15.00 2.19 2.73 6 270
0.4H 8.00 6.99 6.50 15.00 2.98 2.34 6 231
0.5H 8.00 7.46 7.00 15.00 3.88 1.95 6 192
0.6H 8.00 7.85 7.50 15.00 4.82 1.56 5 150
0.7H 8.00 7.92 7.50 15.00 5.57 1.17 5 112
0.8H 8.00 7.34 7.00 15.00 5.52 0.78 6 75
0.9H 8.00 6.11 6.00 15.00 3.77 0.39 7 36
DESIGN OF WALL FOOTING :
CONCRETE MIX M = 35
THICKNESS OF FOUNDATION SLAB ASSUMED THFS = 20 CM
DEPTH OF FOOTING BELOW GROUND DOF1 = 1.20 M
UNIT WEIGHT OF SOIL = 1700.00 KG / Cu.M
SAFE BEARING PRESSURE SBP = 7000 KG / SQ.M
MAX.ALLOW. GROSS LOADING AT FOOTING LEVEL SLF = 7000 KG / SQ.M
ASSUMING WIDTH OF HEEL SLAB HWID = 0.60 M
ASSUMING WIDTH OF TOE SLAB TWID = 0.30 M
WIDTH OF WALL AT BASE = 0.15
TOTAL WIDTH OF FOOTING SLAB FWID = 1.05 M
THE FOLLOWING TABLE GIVES CALCULATION OF LOAD AND MOMENTS ON THE FOOTING
LOAD DUE TO LOAD PER DISTANCE FROM
ITEM METER EDGE OF HEEL
KG M KG-M
VERTICAL WALL PART 1 1463 0.675 987
VERTICAL WALL PART 2 0 0.000 0
WT. FROM ROOF 1151 0.675 777
WT. OF WATER 2160 0.300 648
WT. OF BASE SLAB 525 0.525 276
NET MOMENT DUE TO WATER 416
TOTAL 5299 3104

DISTANCE OF POINT OF CROSSING OF RESULTANT


WITH BASE FROM EDGE OF HEEL SLAB
Z = 0.59 M
ECCENTICITY OF LOADING
E = 0.061 M
MAX. SOIL PRESSURE NEAR EDGE OF TOE
5096.17*(1+6*0.06/1.05)/1.05 MXP1 = 6798 KG / SQ.M
MIN. SOIL PRESSURE NEAR EDGE OF HEEL
5096.17*(1-6*0.06/1.05)/1.05 MNP1 = 3295 KG / SQ.M
DESIGN OF TOE SLAB :

MAX. PRESSURE AT FREE EDGE = 6798 KG / SQ.M


PRESSURE AT WALL EDGE OF TOE = 5797 KG / SQ.M
MAX. BENDING MOMENT = 290.9 KG-M
DEDUCT MOMENT DUE TO SELF WEIGHT = 22.50 KG-M
NET DESIGN MOMENT FOR TOE SLAB = 268.39 KG-M
COEFFICIENT FOR UNCRACKED SECTION 3.33
MIN. THICKNESS REQUIRED = 8.98 Cm
OVERALL THICKNESS PROVIDED IS OK 20.00 Cm
CHOOSE DIA. OF BARS AS = 10.00 MM
CLEAR COVER TO BE PROVIDED = 50 MM
EFFECTIVE DEPTH AVAILABLE = 14.50 CM
AREA OF STEEL REQUIRED = 1.66 SQ.CM
253.67/(13.00*14.50*0.86)
SPACING OF BARS REQUIRED = 47.41 CM C/C
PROVIDED 10.00 MM VERTICAL BARS 19.50 CM C/C
+ 10 EXTENDED.FROM
OF WALL @ INNER FACE

DESIGN OF HEEL SLAB :


cover = 50
UPWARD SOIL PRESSURE = 3027.93 KG
MOMENT DUE TO UPWARD PRESSURE = 803.31 KG-M
DOWNWARD WATER PRESSURE = 2160.00 KG
DOWNWARD PRESSURE DUE TO SELF WEIGHT = 300.00 KG
MOMENT DUE TO DOWNWARD PRESSURE = 738.00 KG-M
NET DESIGN MOMENT = -65.31 KG-M
coefficient for uncrackes section = 3.33
DEPTH OF SECTION REQUIRED FOR UNCRACKED = 4.43 CM
DIA OF BAR CHOSEN F0R TOP FACE = 8.00 MM
EFFECTIVE DEPTH AVIALABLE = 14.60 CM
AREA STEEL REQUIRED = 0.40 SQ CM
DIA OF BAR CHOSEN F0R LOWER FACE = 8.00 MM
PERCENTAGE TEMPERATURE STEEL REQUIRED = 0.24 %
AREA OF TEMP. STEEL REQD. = 4.80 SQ CM
MIN AREA OF STEEL REQD. NEAR TOP FACE = 2.40 SQ CM
SPACING OF BARS REQD.NEAR TOP FACE = 20.93 CM C\C
SPACING OF BARS PROVIDED = 20.00 CM C\C
Total AREA OF CIRCUM.TEMP.STEEL REQUIRED ON EACH = 2.40 SQ CM
FACE
DIA OF BARS = 8.00 MM
SPACING OF BARS ON EACH FACE = 20.0 CM C\C

FLOOR SLAB
CONCRETE MIX: M = 35.00
The floor slab is directly supported on the ground
and is non structural.As such only temp. steel is reqd.
Provide thickness of floor slab as = 20.00 Cm.
Temperature steel required = 0.240 %
Area of steel required = 2.400 Sq.cm.
Diameter of bar chosen = 8.000 mm.
Spacing of bars near both face required = 20.93 Cm.C/C
3.14/4*8.00^2/2.40
Spacing of bars provided = 20.00 Cm.C/C

DESIGN OF OUTER WALL (CASE 2-NO WATER INSIDE AND SOIL OUTSIDE)
COEFF. FOR EARTH PRESSURE = 0.30
Depth of floor below ground level = 1.2 M
THK. OF WALL AT BASE = 15.00 CM
THK AT 1.2 M ABOVE FLOOR = 15.00 cm
WEGHED THK = 15.00 cm
H2/DT = 1.574
DEPTH BELOW G.L. B.M. B.M. B.M.
COEFF. COEFF. COEFF. BM
FRACTION METER 1.2 1.6 1.57
0.1H 0.12 0.0012 0.0011 0.00111 0.978
0.2H 0.24 0.0042 0.0041 0.00411 3.622
0.3H 0.36 0.0077 0.0075 0.00752 6.627
0.4H 0.48 0.0103 0.0107 0.01068 9.412
0.5H 0.60 0.0112 0.0121 0.01205 10.619
0.6H 0.72 0.0090 0.0111 0.01097 9.668
0.7H 0.84 0.0022 0.0058 0.00557 4.909
0.8H 0.96 -0.0108 -0.0051 -0.00548 -4.829
0.9H 1.08 -0.0311 -0.0232 -0.02372 -20.904
1.0H 1.20 -0.0602 -0.0505 -0.05114 -45.069
COVER = 35.00 mm.
EFFECTIVE DEPTH AVAILABLE AT BASE = 11.10 CM
MAX NEGETIVE B.M. AT BASE = 45.07 KG-M
AREA OF STEEL REQD. = 0.363 SQCM
soil face 8 mm + = 8.00 mm.
Spacing of Bars required = 138.34 cm
Spacing of Bars provided = 20.00 cm
Area of steel actually provided = 5.02 SQCM
DESIGN OF WALL FOOTING :
CONCRETE MIX M = 35
THICKNESS OF FOUNDATION SLAB ASSUMED THFS = 20.00 CM
DEPTH OF FOOTING BELOW GROUND DOF1 = 1.20 M
UNIT WEIGHT OF SOIL = 1700.00 KG / Cu.M
SAFE BEARING PRESSURE SBP = 7000.00 KG / SQ.M
MAX.ALLOW. GROSS LOADING AT FOOTING LEVEL SLF = 7000.00 KG / SQ.M
ASSUMING WIDTH OF HEEL SLAB HWID = 0.30 M
ASSUMING WIDTH OF TOE SLAB TWID = 0.60 M
WIDTH OF WALL AT BASE = 0.15 M
TOTAL WIDTH OF FOOTING SLAB FWID = 1.05 M
THE FOLLOWING TABLE GIVES CALCULATION OF LOAD AND MOMENTS ON THE FOOTING
LOAD DUE TO LOAD PER DISTANCE FROM
ITEM METER EDGE OF HEEL
KG M KG-M
VERTICAL WALL PART 1 1463 0.375 548
VERTICAL WALL PART 2 0 0.000 0
WT. FROM ROOF 1151 0.375 432
WT. OF SOIL 612 0.150 92
WT. OF BASE SLAB 525 0.525 276
NET MOMENT DUE TO SOIL 45
TOTAL 3751 1393

DISTANCE OF POINT OF CROSSING OF RESULTANT


WITH BASE FROM EDGE OF HEEL SLAB
Z = 0.37 M
ECCENTICITY OF LOADING
E = -0.154 M
MAX. SOIL PRESSURE NEAR EDGE OF TOE
5096.17*(1+6*0.06/1.05)/1.05 MXP1 = 434.78 KG / SQ.M
MIN. SOIL PRESSURE NEAR EDGE OF HEEL
5096.17*(1-6*0.06/1.05)/1.05 MNP1 = 6709.75 KG / SQ.M
DESIGN OF TOE SLAB :

MAX. PRESSURE AT FREE EDGE = 435 KG / SQ.M


PRESSURE AT WALL EDGE OF TOE = 4020 KG / SQ.M
MAX. BENDING MOMENT = 293.4 KG-M
DEDUCT MOMENT DUE TO SELF WEIGHT = 90.00 KG-M
NET DESIGN MOMENT FOR TOE SLAB = 203.40 KG-M
COEFFICIENT FOR UNCRACKED SECTION 3.33
MIN. THICKNESS REQUIRED = 7.82 Cm
OVERALL THICKNESS PROVIDED IS OK 20.00 Cm
CHOOSE DIA. OF BARS AS = 10.00 MM
CLEAR COVER TO BE PROVIDED = 50 MM
EFFECTIVE DEPTH AVAILABLE = 14.50 CM
AREA OF STEEL REQUIRED = 1.25 SQ.CM
253.67/(13.00*14.50*0.86)
SPACING OF BARS REQUIRED = 62.56 CM C/C
PROVIDED 10.00 MM VERTICAL BARS 20.00 CM C/C
+ 10 EXTENDED.FROM
OF WALL @ INNER FACE

DESIGN OF HEEL SLAB :


cover = 50
UPWARD SOIL PRESSURE = 1071.68 KG
MOMENT DUE TO UPWARD PRESSURE = 207.81 KG-M
DOWNWARD SOIL PRESSURE = 612.00 KG
DOWNWARD PRESSURE DUE TO SELF WEIGHT = 150.00 KG
MOMENT DUE TO DOWNWARD PRESSURE = 114.30 KG-M
NET DESIGN MOMENT = -93.51 KG-M
coefficient for uncrackes section = 3.33
DEPTH OF SECTION REQUIRED FOR UNCRACKED = 5.30 CM
DIA OF BAR CHOSEN F0R TOP FACE = 8.00 MM
EFFECTIVE DEPTH AVIALABLE = 14.60 CM
AREA STEEL REQUIRED = 0.57 SQ CM
DIA OF BAR CHOSEN F0R LOWER FACE = 8.00 MM
PERCENTAGE TEMPERATURE STEEL REQUIRED = 0.24 %
AREA OF TEMP. STEEL REQD. = 4.80 SQ CM
MIN AREA OF STEEL REQD. NEAR TOP FACE = 2.40 SQ CM
SPACING OF BARS REQD.NEAR TOP FACE = 20.93 CM C\C
SPACING OF BARS PROVIDED = 20.00 CM C\C
Total AREA OF CIRCUM.TEMP.STEEL REQUIRED ON EACH = 2.40 SQ CM
FACE
DIA OF BARS = 8.00 MM
SPACING OF BARS ON EACH FACE = 20.0 CM C\C