01.15 EP-3300-HB-UD 500A Documents Consolidated Approved 21-01-2025

The document provides detailed specifications for the Sineng Electric Co., Ltd. inverter model EP-3300-HB-UD, including input and output data, efficiency ratings, environmental conditions, mechanical design, protection features, grid support capabilities, and user interface options. It also discusses transformer requirements and includes efficiency curves and derating information related to altitude and grid voltage. The inverter is designed for outdoor applications with high efficiency and comprehensive protection features.

Uploaded by

snilesh55
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
322 views29 pages

01.15 EP-3300-HB-UD 500A Documents Consolidated Approved 21-01-2025

The document provides detailed specifications for the Sineng Electric Co., Ltd. inverter model EP-3300-HB-UD, including input and output data, efficiency ratings, environmental conditions, mechanical design, protection features, grid support capabilities, and user interface options. It also discusses transformer requirements and includes efficiency curves and derating information related to altitude and grid voltage. The inverter is designed for outdoor applications with high efficiency and comprehensive protection features.

Uploaded by

snilesh55
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 29

Inverter GTP

Sl. No.
Make Sineng Electric Co.,Ltd
Model EP-3300-HB-UD
A Input Data
1 Nominal DC Input Power @ 50degC 3367kWp
Maximum DC Input Power @
2 5994kWp
50degC
3 MPP Voltage @ 50degC 945Vdc to 1300Vdc
4 Maximum Input Current 4276A
5 DC Short Circuit Current 10kA
6 Number of independent MPPTs 2
7 Maximum voltage DC 1500V
8 No. of Input (with fuse rating) 18( 00A)
9 Input Current Monitoring Yes
10 DC Disconnection Device Motorized LBS (2500Ax2)
B Output Data
Rated AC Output Power @ 20degC/
1 3960kVA/3300kVA
50degC
2 3960kVA
Maximum Active 1
3 3300kW
@ 50degC
4 AC Voltage 660V(561~726V)
5 Power Factor range 0.8lagging~0.8leading
6 Rated Frequency 50Hz/60Hz
2887A@50Degree;
7 Rated Current
3464A@ 20 Degree
8 Current Harmonic Distortion Less than 3% at rated power
9 Voltage Harmonic Distortion Less than 3%
Output Disconnection Device &
10 ACB (2000Ax2)
Rating
C Efficiency
1 Max Efficiency 99%
2 Euro Efficiency 98.7%
Internal Consumption @ Full Load
3 <5000W
and 50degC
4 Standby consumption <300W
5 Night time consumption <200W
D Environment Condition
1 Application Outdoor
2 Ingress Protection IP65
3 Ambient Temperature -30~60degC
4 Derating Temperature 50degC
5 Humidity 0~100%
6 Max Altitude 4500m

Page 1 of 3
7 Cooling Method Temperature controlled forced air cooling
8 Noise <80dB
E Mechanical Design
1 Dimensions(W*H*D) 2205x2200x1760mm
2 Weight 2600kg
3 Ducting Requirement With the cooling air duct
4 Color RAL7035
F Protection
DC Side
1 Over Voltage Protection Yes
2 Over Current Protection Yes
3 Reverse Polarity Yes
4 Anti PID Yes
5 Negative Grounding Yes
6 Ground Fault Monitoring Yes
7 Insulation Monitoring Yes
8 Over Heat Protection Yes
9 Surge Protection Yes, Type II
10 Short Circuit Protection Yes
11 Fan Protection Yes
12 Emergency Switch Yes
AC side
13 Over / Under Voltage Protection Yes
14 Over Current Protection Yes
15 Current Balance Yes
16 Over / Under Frequency Protection Yes
17 Sequence Protection Yes
18 Short Circuit Protection Yes
19 Surge Protection Yes, Type II
20 Earth Fault Yes
G Additional Protection
1 Smoke sensor Yes
2 Heat sensor Yes
H Grid Support Features
1 LVRT Yes
2 HVRT Yes
3 Anti-Islanding Yes
4 Active & Reactive Power Regulation Yes
SVG (Night time reactive power
5 Yes( maximum 2376kVar)
compensation) with capacity
No loss of active power in Normal
6 Yes
Voltage Range (±5%)
7 PF Control Yes
8 Soft Shut-Down Yes
9 Grid synchronization Yes

Page 2 of 3
I User Interface
1 Display / HMI Yes
2 Real Time Clock Yes
3 Trends with Real Time Data Yes
4 Communication RS485 /Ethernet
5 Data Logger Inbuilt
6 Fault/ Alarm History Yes
7 Remote operation and control Yes
8 Local PC access Yes
J Connection
Cu busbar with diameter 17mm hole,14 runs of
1 AC side Termination with cable size
240~400sqmm cable each phase
Cu busbar with diameter 13mm hole;
Maximum cable number: 18 PV+ and 18 PV-
2 DC side Termination with cable size
Maximum 18 runs of 240~400sqmm cable
available.
K Auxiliary Transformer
Built-in transformer 5kVA (The Transformer is
1 Rating
only for inverter power supply)
L Certification
1. IEC 61727, IEC 62116
2. IEC 61683
3. IEC 60068 -2-1, IEC 60068-2-2, IEC 60068-2-14, IEC 60068-2-30
4. IEC 61000-6-2
5. IEC 61000-6-4
1 6. EN 62920
7. IEC 62894
8. IEC-62109
9. IEEE 519
10. IEC60529
11. EN50530

Page 3 of 3
Sineng Electric Co.,ltd.

derating curve VS Temperature


Sineng Electric Co.,Ltd.

EP-3 -HB-UD Efficiency Curve VS Different Load

1.Introduction

This document shows the efficient curve vs different load.

2.Efficiency data

The conversion efficiency of photovoltaic inverter has the following characteristics:

1. When the actual output power of PV inverter is not the same, the conversion efficiency is different;

2. The actual output power is the same, but the input voltage is different, the conversion efficiency is also different.

The max. efficiency of EP-3 -HB-UD central inverter is 99.03%. Efficiency is ahead of the industry.

Table-1 Efficiency data

Power(kW) Max. EURO


Udc Efficiency Efficiency

9 V 98.1 % 98.7 % 98.9 % 99.0 % 98. % 98. % 98. % 99.0 % 98.76%

1100V 97.8 % 98. 0% 98.8 % 98.8 % 98.80% 98.6 % 98.38% 98. % 98. 8%

1300V 97.3 % 98.3 % 98. % 98. % 98 % 98. % 98. % 98. % 98. %

9 V 1100V 1300V

100.00%
99.00%
98.00%
97.00%
96.00%
95.00%
94.00%
93.00%
92.00%
91.00%
90.00%
0 500 1000 1500 2000 2500 3000 3500
PIN(DC)[KW]

Fig-2 Efficiency curve

1
Sineng Electric Co.,Ltd.

Inverter Curve of output Power vs Grid Voltage

The document aims to describe the operating grid voltage range related to the apparent power
of central inverters. The main parameters are as following:

Inverter Nominal AC Max. AC Rated grid Grid voltage Max


Power Power voltage range current

EP-3 -HB-UD kW kVA 660V 561~726V A

The rated voltage is 660V and the voltage range of inverter is 561~726V, which is 15% lower than rated voltage and
10% higher than rated voltage. The inverter has a maximum current . When the grid voltage is low, inverter
will derating the output power to make sure the output current is within the permissible range. When the grid voltage
is between 660~726V, the inverter maximum output power is 1.2 rated power. If the voltage is lower than 561V,
the inverter will stop for low voltage protection. If the voltage is higher than 726V, the inverter will stop with high
voltage protection

1
Sineng Electric Co.,ltd.

Altitude derating curve


Version Data Author

1.0

Introduction
This document shows EP-3 -H -UD altitude derating curve.

This document is intended to be used for specific addressees; no part of this document may be reproduced or

distributed in any form or by any means, without the prior written permission of Sineng.

Altitude derating

Because the PCB board wiring distance in different voltage conditions of creepage distance is not the same, the
higher the altitude, the thinner the air. creepage distance need more length, but the board is fixed. So, as the altitude
rises, it can only load down.

Altitude derating curve

Fig-1 Altitude derating curve

Altitude below 3000m, no dera Altitude below 4000m, % power

operation;

1
Sineng Electric Co.,ltd.

EP-3 -HB-UD P-Q curve

This document describes the P-Q curve at different ambient temperature for EP-3 -HB-UD.

1. P-Q curve
Qmax =PN*sqrt (1- PF2) (PF_max=0.8). So, we can get the Q-t curve (t =P/PN %).

1.1 P-Q curve @30

Power factor Active power(kW) Reactive power(kVar) Apparent power(kVA)


0.8
0.85
0.9
0.95
1 0

1.2 P-Q curve@35

Power factor Active power(kW) Reactive power(kVar) Apparent power(kVA)


0.8 295 36

1
Sineng Electric Co.,ltd.

0.85 31
0.9 332 1608
0.95 35 115
1 36 0

1.3 P-Q curve@40

Power factor Active power(kW) Reactive power(kVar) Apparent power(kVA)


0.8
0.85
0.9
0.95
1 0

1.4 P-Q curve@45

2
Sineng Electric Co.,ltd.

Power factor Active power(kW) Reactive power(kVar) Apparent power(kVA)

0.8 20

0.85

0.9

0.95

1 0

1.5 P-Q curve@50

Power factor Active power(kW) Reactive power(kVar) Apparent power(kVA)

0.8

0.85

0.9

0.95

1 0

1.6 P-Q curve@55

3
Sineng Electric Co.,ltd.

Power factor Active power(kW) Reactive power(kVar) Apparent power(kVA)


0.8
0.85
0.9
0.95
1 0

1.7 P-Q curve@60

Power factor Active power(kW) Reactive power(kVar) Apparent power(kVA)


0.8
0.85
0.9
0.95
1 0

4
Sineng Elctric Co.,ltd.

Transformer Requirement

Introduction
This document shows the request of the MV transformer matching with

The technical specification should be checked as per applicable codes and standards by supplier. Any

deviation/recommendation should be approved in writing from buyer.

MV transformer requirements

The requirement is as following:

2.1 The voltage at the LV and MV side of transformer shall be in line with the inverter AC voltage and MV grid voltage
at the connection point.

2.2 Transformer capacity shall be in line with the Inverters max. output power corresponding to the
ambient temperature

2. The gradient of du/dt to ground at low-voltage side of the transformer should be higher than 1 00V/ s

2. If the negative bus of inverter connecting to ground for anti-PID solution, the impulse voltage of each phase can
be up to 1500V. The low-voltage winding of transformer should be able to handle 1500V impulse voltage and 800V
sine wave voltage to ground (The same for the brush). The phase to phase voltage should be higher than 630V RMS
value
.

2. DC injection capacity of the transformer selected should be % of the fundamental current at nominal power;

2. The transformer is capable of withstanding a certain level of harmonic current; the maximum total harmonic current
is 5% of fundamental current at nominal power output;

2. The transformer is capable of withstanding a certain degree of phase imbalance; 5% of the current at nominal
power;

2. Once inverter is equipped with PV negative ground function device (for short, negative ground device), inverter
AC voltage to earth will rise. Hence compare with inverter without negative ground device, AC surge arrester shall
adopt 690Vac or above device as SPD.

2. If a two winding transformer is selected, Dy11 and YNd11 configurations can be used; In case the Y connection is
on the LV side, the neutral point should not be grounded. Impedance voltage Z(%) of double winding transformer
shall be % with tolerance of +/-10%.

Dy11 YNd11

High-voltage side Low-voltage side High-voltage side Low-voltage side

1
Sineng Elctric Co.,ltd.

2.1 If a three winding transformer is selected, Dy11y11 and Yd11d11 configurations can be used. LV neutral point
cannot be connected to ground. Cross impedance between HV-LV > %.Half cross impedance
> 10% Split coefficient>3.

Dy11y11 Yd11d11

U2
U2
V2
U1 V2 U1
W2
V1 W2 V1
U3 U3
W1 W1
V3 V3
N1
W3
W3

2.1 If a five winding transformer is selected, Dy y y y and Yd d d d configurations can be used. LV


neutral point cannot be connected to ground. Cross impedance > %.Half cross impedance
10% Split coefficient>3.

Dy11y11 Yd11d11

High-voltage Low-voltage High-voltage Low-voltage


side side side side

2
Sineng Electric

EP-3300-HB-UD
Key component list
SI. Name (Quantity) Model Specification Manufacturer
No.

1 IGBT FF600R12ME4_B72 1200V/600A INFINEON

2 690V/2000A/3P
ACB NDW1A-20/20/3 Nader

DC Motorized LBS NDW2GZ-25/25 1500V/2500A/4P Nader


3

2XLPV400U15/PV312- Hollyland
2XLQ400A1500V 1500V/400A / Sinofuse
4 DC FUSE (project
basis) 3LgPV500U15DLB/
PV312XL3Q500A1500V Hollyland /
1500V/500A Sinofuse
-N

FAD85J556023DX8D AiSHi
5 AC filter capacitor 850VAC/3×55.8uF
C67W155HJ010299 Faratronic

DC SPD DS50PVS-1500 12KT1 CITEL


6 1500Vdc\6.25KA\12.5KA
PTV 1500-40M2-21R PTG

7 AC SPD DS44S-690 690Vac\20kA\40kA CITEL

C3B2K757J010854 Faratronic
DC-link capacitor
8 750uF/800V
C30(DCLSY 800-750) Shengye

TMS320F28377 200MHzCore TI
9 DSP

DC current transducer HCK22-2000S/ 2000A/4V Avadi/ CRRC


10 NACF.2000

AC current transducer HCK22-2000S/ 2000A/4V Avadi/ CRRC


11 NACF.2000

SC225A1-068-00E 135W,230V FANSHIDA


12 Fan