1 2 3 4 5 6 7 8
Revision Revision text
D Drawing template has been updated.
OUTER TERMINAL INNER TERMINAL
FOR STRANDED CABLE
The released document has a date entered in the "Approved"-field.
A Bushing Data: A
M8
This document is issued by means of a computerized system.
Rated Voltage 52 kV
The digitally stored original is electronically released.
D
Phase to Ground Voltage 30 kV
Dry Lightning Impulse 1,2/50µs 250 kV
140
( n20) Wet power frequency AC 105 kV
L
170
Routine test 1min dry 50Hz 120 kV
A manual signature is not required.
Rated Current 800 A
35
B B
Creepage Distance 1690±50 mm
695 (Draw Lead Length)
Creepage Distance Protected 580 mm
18
Mass 33 kg
n 230 Ordering Data:
END SHIELD SOLID ROD CONNECTOR
730
BUSHING COLOUR AIR INSULATOR
1188
480
LF123171-M BROWN
M8
86 -N LIGHT GREY
C C
LF123171-HM BROWN Horizontal45 $ -90 $
LF123171-HN LIGHT GREY Horizontal 45 $ - 90 $
R6 20 OUTER TERMINAL Material D L
LF 170 002-A Cu Alloy
LF 170 001-A Al
16
110
OTHER TYPES ON REQUEST
65
Alt.1
70
INNER TERMINAL FOR STRANDED CABLE
For brazing Conductor area D1
a patent,
D D
communication
will be held
LF 170 011-S up to 150mm²
of its content to others without express authorization is prohibited. Offenders
of grant
46
as the
R8
Earthed
LF 170 011-U Undrilled with pilot hole n 5
65
layer
n 86 25
liable for the payment of damages. All rights reservedin the event of the
22
27
For crimping or brazing
Conductor area D1
The reproduction, distribution and utilization of this document as well
290
utility model or design. © 2024 Hitachi Energy. All rights reserved
LF 170 010-M 50mm²
LF 170 010-N 70mm²
The solid rod can be divided either:
Alt.1: 20mm below the bushing flange LF 170 010-L 95mm²
SOLID ROD CONNECTOR Material
225 Note: LF 170 019 -AMfor Alt.1 Cu
E E
1) M12 (For Earthing) TERMINAL PLATE Material
185 2) n 4 oil connection hole (only valid for horizontal mounting)
LF 170 014-A Aluminium
1) LF 170 021-A Nickel-Platted Copper
2) PREPARED DOCUMENT KIND TITLE / SUPPLEMENTARY TITLE
Engineering Department2024-11-28 Dimension Drawing GOB 250-800-0
6 mounting APPROVED SECURITY LEVEL
WITH OIL LEVEL GAUGE
LANG.
Engineering Manager 2024-12-16 Public EN
F holes n 16 RESPONSIBLE DEPARTMENT STATUS
LONG END SHIELD SHEET F
SECOM-9AAE300824 Released 1/1
Test tap DOCUMENT ID REVISION
60 D Hitachi Energy Ltd, CHTEC
2751369-170 D
$
1 2 3 4 5 6 7 8
DRAWING SHEET ISO 5457:1999-A3T