ANSI-IEEE 386 1985 Separable Insulated Connector Over 600v
ANSI-IEEE 386 1985 Separable Insulated Connector Over 600v
Sponsor
Transmission and Distribution Committee of the
IEEE Power Engineering Society
Secretariat
National Electrical Manufacturers Association
@ Copyright 1985 by
This standard was developed in response to a need created by the rapid expansion of underground
distribution systems. A key element that allowed this expansion to become a reality is the separable
insulated connector. This device provides for simple and inexpensive connection and switching to
transformers and other equipment used in underground distribution.
When separable insulated connectors become available, the Institute of Electrical and Electronics
Engineers and the National Electrical Manufacturers Association work cooperatively to develop a
document that will define the interfaces, ratings, and test conditions for the device. The success of that
cooperative effort is apparent from both the vast number of these devices now in interchangeable use in
the field and their enviable safety record.
Because the technology within the field of underground distribution is under constant development,
with accompanying new products and distribution schemes, it is necessary to provide for constant
review of these connector requirements and to make participation in this ongoing activity available to
all concerned organizations. To accomplish this purpose and provide a mechanism for development of
additional related standards, American National Standards Committee C119 (now Accredited Standards
Committee C119) was organized with a balanced representation of users, manufacturers, and generd
interest expertise. It is the hope and the expectation of C119 that those who have comments and
additions may assist in the revision activity by forwarding their comments to C119, American National
Standards Institute, 1430 Broadway, New York, NY 10018.
This revision was developed by ANSI Subcommittee C119.2 under auspices of the Distribution
Subcommittee of the Transmission and Distribution Committee of the IEEE Power Engineering Society.
To the extent available, data used in it were gathered from pertinent existing industry standards for
power cable, distribution transformers, and other electrical apparatus.
One of the primary objectives of this standard is to provide a basis for electrical interchangeability of
corresponding 8.3 and 14.4 kV interfaces and mechanical interchangeability of operating interfaces
between connector elements supplied by different manufacturers. However, to avoid exclusion of any
connector design, a multiplicity of interfaces which are not interchangeable with each other is included.
Hence, a purchaser must select a design for his particular need. Users and manufacturers are encour-
aged to use the designs illustrated.
At the time this standard was approved the membership of Accredited Standards Committee C119 was
as follows:
Norman Sacks, Chairman William L. Wagner, Vice Chairman
H. C. Smith, Secretary
Organization Represented Name of Representative
Aluminum Association . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Peter Pollack
Department of the Army . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . John S. Robertson
Department of the Navy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Charles M. Mandeville
Edison Electric Institute . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . J. F. Gillespie
H. L. Hayes
John P. Markey
A. A. Smith
William L. Wagner
Institute of Electrical and Electronics Engineers.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H. D. Thomas
International Brotherhood of Electrical Workers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Robert MasDonald
National Electrical Manufacturers Association . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R. S. Arnold
C. B. DeLuca
M. Kopchik, Jr.
George W. Mayall*
Norman Sacks
Frank Stepniak
- Rural Electrification Administration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tennesse Valley Authority . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Vikramaditya Railan
Jack W. Anderson
Underwriters Laboratories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . J. Killinger
Robert W. Seelback (Alt)
*Liaison to ANSI C.57
At the time this standard was approved the membership of the Working Group of the Distribution
Subcommittee on Separable Connectors was as follows:
At the time this standard was approved, the members of the Distribution Subcommittee were as
follows:
When the IEEE Standards Board approved this standard on September 22, 1983,it had the following
membership:
*Member emeritus
. Contents
SECTION PAGE
1. Scope .................................................................................. 7
2. References .............................................................................. 7
3. Definitions .............................................................................. 7
4. Service Conditions ....................................................................... 10
4.1 Usual Service Conditions ............................................................. 10
4.2 Unusual Service Conditions .......................................................... 10
5. Ratings and Characteristics ............................................................... 10
5.1 Voltage Ratings ..................................................................... 10
5.2 Current Ratings ..................................................................... 10
6. Construction ............................................................................ 11
6.1 Identification ........................................................................ 11
6.2 Operating Means .................................................................... 11
6.3 Shielding ........................................................................... 11
6.4 Interchangeability ................................................................... 11
6.5 Test Point .......................................................................... 11
6.6 HOld-DoW Bails .................................................................... 11
7. Testing ................................................................................. 21
7.1 Production Tests .................................................................... 21
7.2 Design Tests ........................................................................ 21
7.3 Test Conditions ..................................................................... 21
7.4 Corona Voltage Level ................................................................ 21
- 7.5 Dielectric Tests ..................................................................... 21
7.6 Short-Time Current Test ............................................................. 22
7.7 Switching Test ...................................................................... 22
7.8 Fault-Closure Test ................................................................... 24
7.9 Current-Cycling Test for Uninsulated Components of 200 A and 600 A Connectors . . . . . . . . . 25
7.10 Current-Cycling Test for 200 A Insulated Connectors .................................... 25
7.11 Current-Cycling Test for 600 A Insulated Connectors .................................... 26
7.12 Accelerated Sealing Life Test ......................................................... 27
7.13 Cable Pull-out Test .................................................................. 27
7.14 Operating-Force Test ................................................................ 27
7.15 Operating-Eye Test .................................................................. 27
7.16 Test-Point Cap Test ................................................................. 28
7.17 Test-Point Tests ..................................................................... 28
7.18 Shielding Test ....................................................................... 28
FIGURES
.
An American National Standard
1. Scope 3. Definitions
This standard establishes definitions, service The following definitions are the intended
conditions, ratings, interchangeable construction meanings of terms used in this standard or asso-
features and tests for load-break and dead-break ciated with separable insulated connectors sys-
separable insulated connector systems rated tems. Figures 1 and 2 show typical components
601 V and above, 600 A or less, for use on power of separable insulated connectors. The term con-
distribution systems. nector as used in this standard means separable
insulated connector.
ELBOW
I TO EXTERNAL
:
ERATING INTERFACES
BUSHING SURFACE OF
INTEGRAL
INSERT
BUSHING
BUSHING
FOR CONNECTION
WELL TO APPARATUS
Fig 1
Typical Components of 200A Separable
Insulated Connector System
ground bushing. An accessory device de- insulated parking bushing. An accessory de-
signed to electrically ground and mechanically vice designed to electrically insulate and shield
seal a de-energized power cable terminated with and mechanically seal a power cable terminated
an elbow. with an elbow.
grounding elbow. An accessory device de- insulated cap. An accessory device designed to
signed to electrically ground and mechanically electrically insulate and shield and mechanically
seal a bushing insert, or integral bushing. seal a bushing insert or integral bushing.
hold-down bail. An externally mounted device integral bushing. An apparatus bushing de- _-
designed to prevent separation at the operating signed for use with another connector compo-
interface of an elbow and an apparatus bushing. nent, such as an elbow (see Fig 1).
8
ANSI/IEEE
POWER DISTRIBUTION SYSTEMS ABOVE 600 V Std 386-1985
CAP PLUG ELBOW BUSHING
_- A r \ A /-----7
600 AI200 A
BUSHING
WELL PROVISION FOR
CONNECTION TO
APPARATUS
OPERATING INTERFACES
COMPRESSION
Fig 2
Typical Components of 600 A Separable
Insulated Connector System
load-break connector. A connector designed both, so designed that the electrical connection
to close and interrupt current on energized cir- can be readily established or broken by engaging
cuits. or separating the connector at the operating in-
terface (see Figs 1 and 2).
maximum voltage rating. The highest phase-
to-ground or phase-to-ground and phase-to-phase short-time current rating. The designated
voltage (rms) at which a connector is designed rms current which a connector can carry for a
to operate. specified time under specified conditions.
9
ANSI/IEEE
Std 386-1985 IEEE STANDARD FOR SEPARABLE INSULATED CONNECTOR SYSTEMS FOR
Table 1
Voltage Ratings and Characteristics
Withstand Voltages
Maximum Voltage BIL and Alternating Current Direct Current Minimum Corona
Rating Full Wave 60 Hz for 1 min for 15 min Voltage Level
(kV rms)' (kV Crest) (kV rms) (kv> (kV rms)t
8.3$ 95 34 53 11
8.3/14.4§ 95 34 53 11
15.2$ 125 40 78 19
15.2/26.3§ 125 40 78 19
21.1$ 150 50 103 26
2 1.1/36.6§ 150 50 103 26
*The highest steady state voltage across the open contacts that a loadbreak connector is rated to switch is:
(1) The maximum phase-teground rms voltage for phase-teground rated devices
(2) The maximum phase-tephase rms voltage for phase-teground/phase-twphase rated devices
tBased on a sensitivity of 3 pC (see 7.4).
$Phase-teground
§Phase-teground/phase-tephase
Table 2
Current Ratings and Characteristics
* In general, the overload capability of a connector exceeds its continuous current rating. Overload capability varies with
environment, cable sizes, etc. The connector manufacturer's recommendations should be obtained for the particular combination
involved.
t Applicable to loadbreak connectors only. Fault-closure current ratings have not been established for 21.1 kV/36.6 kV load-break ,---
connectors. Equipment to which these assemblies are affixed may have lower safe limits of fault current performance.
$ The manufacturer shall designate the fault-closure duration.
10
ANWIEEE
POWER DISTRIBUTION SYSTEMS ABOVE 600 V Std 386-1985
6.1 Identification. Mating components of a 6.3 Shielding. Connectors shall have an elec-
separable insulated connector shall be perma- trically conductive shield and, where required,
nently (for example, ink stamp, brand, or molded shall have provision for connecting an external
in) and legibly identified with the following infor- ground to the shield. Except for nonelastomeric
mation: components, connectors shall meet the require-
(1) Manufacturer's identification ments of IEEE Std 592-1977 [51.
(a) Company name or logo
(b) Part identification
(c) Date of manufacture 6.4 Interchangeability
(2) Continuous current rating (when applicable) 6.4.1 Complete Interchangeability. Inter-
mixed bushings and elbows of different manufac-
(3) Maximum voltage rating
(4) Cable insulation diameter range (when a p ture shall be considered interchangeable pro-
plicable) vided they meet all applicable requirements of
(5) Whether load-break or dead-break (when this standard.
applicable). In addition, elbows of load-break
6.4.2 Limited Interchangeability. Inter-
connectors shall have the following marking: mixed bushings and elbows of different manu-
(a) Connectors with a phase-to-ground volt- facture meeting all the requirements of this
standard, except 7.7 and 7.8, shall be considered
age rating shall be identified with a removable
interchangeable, except for switching and fault
white band 13 mm - 32 mm (0.5in - 1.25in)
closure.
wide, located on the cable entrance portion of
The dimensions of operating and bushing well
the connector not less than 25 mm (1.00 in) from
the cable entrance. The removable band shall be interfaces shall be in accordance with Figs 3
--
through 11.
clearly visible from the normal operating posi-
tion, and &xed to minimize its accidental dis-
lodgement.
6.5 Test Point. Test points are optional and
(b) Connectors with both phase-to-ground
may be specified on either load-break or dead-
and phase-to-phase voltage ratings shall be iden-
break elbows.
tified with a removable white band 13 mm -
6.5.1 Capacitance. Test points shall be ca-
32 mm (0.5in - 1.25 in) wide, having a centered
pacitively coupled to the conductor system and
black stripe 4.8 mm ~fr 1.6 mm (0.188 in 2 0.062
shield of the connector.
in) in width located on the cable entrance por-
The capacitance between the test point and
tion of the connector not less than 25mm
the conductor system shall be at least 1.0 pF. The
(1.00 in) from the cable entrance. The removable
ratio of the capacitance between test point and
band shall be clearly visible from the normal op-
shield to the capacitance between test point and
erating position, and affixed to minimize its acci-
conductor system shall not exceed 12.0. These
dental dislodgement.
values shall be verified by tests when conducted
in accordance with 7.17.1.
6.5.2 Cap Removal Force. The force re-
quired to remove the test-point cap shall be
6.2 Operating Means. Connectors shall be op- within the range of 36N - 219N (81bf - 491bf).
erable by means of a suitable live-line tool which The cap operating eye shall be capable of with-
clamps the elbow so that operation is along the standing a static operating force of 433 N (100 lbf)
probe axis. The required operating force over the over the environmental temperature range of
+
environmental range of - 20 "C to 65°C shall - 20°C to + 65°C (see 7.16.1).
be as follows (see 7.14):
(1) 225N - WON (501bf - 200Ibf) for connec-
-?
tors without hold-down bails 6.6 Hold-Down Bails. Dimensions, materials,
(2) 45N - WON (1Olbf - 2001bf) for connec- and performance criteria are not specified in this
tors with hold-down bails standard.
11
ANSVIEEE
Std 3861985 IEEE STANDARD FOR SEPARABLE INSULATED CONNECTOR SYSTEMS FOR
40'46 GAUGE
48.26
AT -GAUGE
1 .goo A 2.644 ? 0.010
AT -
48'26 GAUGE
1.900
AT -
12.70 GAUGE+{
0.500 +r
SHIELDING
REQUIRED
R A D REF
NOTES (1) Diameters C, D, E, and F to be concentric with pitch diameter of threads on stud within
025/0.010 TIR (total indicator re-
(2) Clearance for mating parts
m
(3) Dimension: mm/iq -
m
(4) A-alphabetical dimensional identification
(5) The diameter of the shielded portion shall at no point be less than the largest diameter of the
insulated portion
Fig 3
200 A Bushing-Well Interface, 8.3 kV, 15.2 kV, and 21.1 kV
12
ANSI/IEEE
POWER DISTRIBUTION SYSTEMS ABOVE 600 V Std 386-1985
,
48.51 f 0.38
7
*
8 1 . 9 1 0 0.015
*44.45 f 0.38
1.750 f 0.01 5
-
44.45 32.41 f 0.25
AT GAUGE-
1.750 i m 1 . 2 7 6 f 0.0101
6.35
AT --GAUGE-
0.250
7.3710.290 MIN-
n C O N T A C T ID
DATUM
47.88 r 0.25
MIN
1.885 f 0.010
I I CLEARANCE
56.87 ;”,”,”
REQUIRED
%-
M I N SHIELDING
NOTE (4)
T.87
0.310
f
f
0.05
0.002
PROBE
Fig 4
200 A Dead-Break Interface,
8.3 kV and 15.2 kV
13
ANSVIEEE
Std 3861985 IEEE STANDARD FOR SEPARABLE INSULATED CONNECTOR SYSTEMS FOR
- 40.49 f 0.38
~~
~ 1 . 5 9 f40.015
69.85
GAUGE
3.18 f 0.38
RAD
n o . 125 f0.015
EXTl NGUlSH I NG
ZONE
ARC ,\
\
0.227f 0.015
MIN
ANCE
PROBE
66.68f 0.38
2.625 f 0.015
I
M I N SHIELDING
67.31 f 0.76 REQUIRED NOTE (5)
2.650 f 0.030 PROBE
OPTION
Fig 5
200 A Load-Break Interface,
8.3 kV and 8.3 kVD4.4 kV
14
ANSIAEEE
POWER DISTRIBUTION SYSTEMS ABOVE 600 V Std 386-1985
DATUM
(REFERENCE FIG 5)
A A 6.93 f 8
- - 26.14 f 1.80
1.029 f 0.071
b
137.21 f 231
5.402 t 0.091
THREADS
31.54 t 1.83
1.242 t 0.072
MATERIAL
14.12 2 0.99
0.556 f 0.039
r0.494
12.55 f0.10
0.004 r0.500
12.70 t 0.08
0.003
t
-
t
ARC EX TlNGUlSHlNG
ROD
Fig 6
200A Load-Break Probe and Elbow
8.3 kV and 8.3 kVl14.4 kV
15
ANSI/IEEE
Std 386-1985 IEEE STANDARD FOR SEPARABLE INSULATED CONNECTOR SYSTEMS FOR
-ni
46.66 f 0.38
.a37 f 0.01 5
AT-
69.85
2.750
GAUGE
1
38.48 f 0.38
;,5
.15 f O.O:]
35.31 f 0.38
. 1.390 f 0.015
23.88 0.38
' 0.940 f 0.01 5
fl'1-r 1
l l 159.51 MIN
-
97.03
3.820
MIN
w-
r
6.280
CLEARANCE
FOR PROBE
n
ARC
EXTINGUISHING 49
Z-ONE
SPRING LOAD)ED
CONTACT
/
ARC EXTINGUISHING ROD
OPTION
h L C O N T A C T
NOTES (1) Clearance for mating parts
mm
(2) Dimensions: mm/in; -
in
(3) A-alphabetical dimensional identification
(4) The diameter of the shielded portion shall at no point be less than the w e s t diameter of the insulated
portion
Fig 7
200 A Load-Break Interface, 15.2 kV and 15.2 kV/26.3 kV,
200 A Load-Break Interface No 2, 21.1 kV and 21.1 kV/36.6 kV
16
ANSI/IEEE
POWER DISTRIBUTION SYSTEMS ABOVE 600 V Std 3861985
7 1.07 f 0.38
P d -AT- 120.65
4.750 GAUGE
~2.789 f 0.01 5
2.39
0.094
f
f
0.12
0.005
RAD p
-1 60.33 r 0.38
a \ 19.30 f 0.12
3.18 r 0.12
0.1 25 r 0.005
RAD \ eO.760 f 0.005
DATUM
12.70
AiExGAUGE
1.52 f 0.50 136.19
1 I
213.54
8.407
MIN
0.060 f 0.020 A 5.362 CLEARANCE
ARAD MAX
: 0.020
1 /
SPRING-LOADED
I 88.90 r 0.50
~ 3 . 5 0 0f 0.020
REQUIRED NOTE (4)
18.92 f 0.07
PROBE
19.05 f 0.05
0.745 f 0 . 0 0 3 b 0.750 O.Oo2A
I
ARC EXTINGUISHING ROD CONTACT
Fig 8
200A Load-Break Interface No 1,
2L1 kV and 21.1 kV/36.6kV
17
ANSVIEEE
Std 386-1985 IEEE STANDARD FOR SEPARABLE INSULATED CONNECTOR SYSTEMS FOR
- 42.72f 0.25
~ 1 . 6 8 f20.010
AT 88.9'
3.500
GAUGE
1 DATUM
22.22MIN
I
r 7-0.875
88.90
I
95.25
A M 88'90
A 3.500 GAUGE
A;;.3
NOTE (1)
+- REQUl RED
NOTE (4)
-
9.52f 0.05
0.375f 0.002
PROBE
Fig 9
200 A Dead-Break Interface, 21.1 kV
18
ANSI/IEEE
POWER DISTRIBUTION SYSTEMS ABOVE 600 V Std 386-1985
A 2.013f 0.010__
76.20 51.13 f 0.25
AT -
3.000
GAUGE - OPTION 5
1.27f 0.25
0.050f 0.010
2.29 f 0.25 I I
82.30f 0.50
0.090f 0.010
ARAD 76.20 I
~ 3 . 2 4 f0 0.020
3.000
A GAUGE
93.47
pE
3.840
Fig 10
600 A Dead-Break Interface, 8.3 kV and 15.2 kV
19
ANSVIEEE
Std 386-1985 IEEE STANDARD FOR SEPARABLE INSULATED CONNECTOR SYSTEMS FOR
0.25 OPTION
AT 14.000
01.6' GAUGE + 0.010
31.75 t 0.12 /Ai - I I UNC 2B
,-
1.250 * 0.005 I
1.250 * 0.01 5
6.35 MIN
0.250 GAUGE
DATUM
2.29 f 0.38
).090 f 0.01 5
%RAD
101.60
A?=-
.UGE
I ..3.57
y;;
125.'
5 MIN
2.29 * 0.38 I
1.090 f 0.01 5
A NOTE (1 1
REQUIRED 1
(NOTE (4i
Fig 11
600 A Dead-Break Interface, 21.1 kV
20
ANSI/IEEE
POWER DISTRIBUTION SYSTEMS ABOVE 600 V Std 3861985
Table 3
Design Tests
Number of
Design Test Section Samples *
Corona voltage level 7.4 10
Alternating-current withstand voltage 7.5.1 10
Direct-current withstand voltage 7.5.2 10
Impulse withstand voltage 7.5.3 10
Short-time current 7.6 4
Switching
Fault-closure 77:87) 30 (max)
Current cycling 7.9 - 7.11t and 7.12 4
Accelerated sealing life test 7.12 4
Cable pull-out (tensile strength) 7.13 4
Operating force 7.14 4
Operating eye 7.15 4
Test-point cap 7.16 4
Test point 7.17 10
Shielding 7.18 4
* No failures permitted except for switching and fault-closure tests in which none
are permitted in ten consecutive samples of a maximum lot size of 30.
t Option A or Option B. (see 7.10)
21
~
ANSI/IEEE
Std 386-1985 IEEE STANDARD FOR SEPARABLE INSULATED CONNECTOR SYSTEMS FOR
22
ANSI/IEEE
POWER DISTRIBUTION SYSTEMS ABOVE 600 V Std 386-1985
4
ALL NORMALLY
G ROUN D E 0
V
LOAD BREAK
GRFACES
x_3 -- 5 t 0 7
RS
NOTE: Care shall be exercised in the selection and connection of instrument transformers to
ensure that they will not significantly alter the waveshape, magnitude, or duration of transient
voltages or current normally associated with the test circuit.
The switching rating may be achieved with the separating parts in either position.
Series impedance which may include source impedance may appear on either side of the
load-break connector.
Transformer loading which represents normal service conditions can be used for switching.
Fig 12
Circuit Diagrams for Switching Current Tests
23
ANSI/IEEE
Std 3861985 IEEE STANDARD FOR SEPARABLE INSULATED CONNECTOR SYSTEMS FOR
Fig 13
Circuit Diagrams for Fault-Closure Tests
NOTE: Any circuit that duplicates the voltages VI and V , and the conditions in
Table 2 is acceptable for conducting the fault-closure test
VI = required voltage across contacts prior to flow of fault current
V , = required voltage from each contact to all normally grounded surfaces
during flow of fault current
V , (Open-circuit Voltage)
z, +z, =
Rated Fault-Closure Current
z1 rz,
e! 24
z, =
V , (Open-circuit Voltage)
Rated Fault-Closure Current
ANWIEEE
POWER DISTRIBUTION SYSTEMS ABOVE 600 V Std 386-1985
25
ANSI/IEEE
Std 3861985 IEEE STANDARD FOR SEPARABLE INSULATED CONNECTOR SYSTEMS FOR
-*-
FORCE USED TO INSTALL ELBOW
ON BUSHING SHALL BE APPLIED
PARALLEL TO AXIS OF THE PROBE
rqar
2.50 IN
7.10.1 The elbow shall be rotated about the Heat-cycle tests shall be conducted at an am-
probe axis a minimum of 10" in both clockwise bient temperature of 20°C - 35°C in a space
and counterclockwise directions by means of a free of drafts.
suitable live-line tool. The tool shall be approx- The temperature shall be measured by ther-
imately parallel with the axis of the probe. mocouples located at
The connector shall then be opened 5 times (1) The compression lug
with the force applied to the pulling band and (2) The approximate midpoint of the bushing
closed 5 times with the force applied to the oper- contact or as near thereto as practical
ating eye. The force required to open or close the (3) On the conductor surface at the midpoint
elbow shall be parallel to the axis of the probe. of the control cable
The applied force shall be sufficient to com- The temperature at locations (1) and (2) shall
pletely close the connector. not exceed the temperature of the conductor of
7.10.2 A control cable used for the purpose of the cable at location (3).
obtaining conductor temperature, shall be in-
stalled in the heat cycle loop between two equal- 7.11 Current-Cycling Test for 600 A Insu-
izers. Its length shall be 72 in. The control cable lated Connectors. The purpose of this test is
shall be the same type and size as the cable used to demonstrate that 600 A insulated connectors
to join the connectors under test. can carry rated current under usual service con-
The current shall be adjusted so that the tem- ditions. Successful completion of the test listed
perature on the conductor of the control cable is below shall be considered as evidence that the
90°C 5 5°C. The current shall be applied for connector meets its rating.
eight continuous cycles, each cycle consisting of A control cable, used for the purpose of ob-
3 h on and 3 h off. taining conductor temperature, shall be installed .*.
Equalizers used shall be in accordance with in the heat-cycle loop between two equalizers. Its
ANSI/NEMA CC3-1973 141. length shall be 72 in. The control cable shall be
26
ANSIAEEE
POWER DISTRIBUTION SYSTEMS ABOVE 600 V Std 386-1985
the same type and size as the cable used to join conductor of the control cable to 90 "C k 5 "C for
~-
the connectors under test. the following time period:
Four connectors shall be assembled in series on
750 kcmil insulated aluminum conductors having 200 A connectors - 1h
a length of 36in. The cable insulation thickness 600 A connectors -4 h
shall be selected according to its voltage class.
(2) The assemblies shall be de-energized and
Voltage Cable within 3 min, submerged in 25 "C 5 5 "C conduc-
Rating Insulation tive water (5000n, cm maximum) to a depth of
(kV rms) Thickness 30 cm (1 ft) for the following time periods:
27
ANSI/IEEE
Std 386-1985
A rotational force shall be applied with a suit- 7.17 Test-Point Tests ,--
able live-line tool to the operating eye in a clock- 7.17.1 Test-Point Capacitance Test. The
wise direction and in a counter-clockwise purpose of this test is to verify that the capaci-
direction. tance values of the test point meet the require-
Some distortion of the operating eye is accept- ments of 6.5.1.
able provided the connector is serviceable after The connector shall be installed on a cable of
the test and meets the corona voltage-level re- the type which it is designed to operate, and the
quirement specified in Table 1. shielding shall be grounded in the normal man-
ner. The capacitances from test point to cable
7.16 Test-Point Cap Test. The purpose of this and test point to ground shall be measured with
test is to demonstrate that the removal force of suitable instruments and proper shielding tech-
the test-point cap meets the requirements of 6.5.2 niques.
and the cap operating eye is capable of with- The measured values shall be within the toler-
standing the maximum operating force. ances specified in 6.5.1.
7.16.1 Test-Point Cap Operating-Force 7.17.2 Test-Point Voltage Test. The pur-
Test. A tensile force shall be gradually applied pose of this test is to ensure proper operation of
to the test-point cap in the direction parallel with the test point.
+
the probe axis at - 20"C, 25"C, and + 65°C. A test voltage shall be applied to the conduc-
The force required to remove the test-point tor system of the connector. The response of a
cap shall be within the ranges specified in 6.5.2. suitable sensing device on the test point shall in-
7.16.2 Test-Point Cap Operating With- dicate an energized condition.
stand Test. A tensile force of 433N (1OOlb)
shall be applied to the test-point cap operating 7.18 Shielding Test. The purpose of this test
+
eye for 1 min at - 2O"C, 25"C, and 65°C. + is to demonstrate that the shielding meets the re-
Some distortion of the operating eye is accept- quirements of 6.3.
able provided the test-point cap is serviceable af- The test procedure shall be in accordance with
ter the test. IEEE Std 592-1977 [5]. I
28