0% found this document useful (0 votes)
76 views2 pages

6sl3224 0be35 5ua0 - Datasheet - en 1

The SINAMICS G120 Power Module PM240 is a three-phase power module with a rated power of 75 kW and a maximum output current of 220 A, designed for efficient operation with a power factor of 0.85 and an efficiency of 0.97. It features internal air cooling and operates within a temperature range of 0 to 50 °C, with overload capabilities for both low and high overload scenarios. The module complies with various standards including UL, cUL, CE, and is suitable for a range of applications with specified mechanical and electrical connections.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
76 views2 pages

6sl3224 0be35 5ua0 - Datasheet - en 1

The SINAMICS G120 Power Module PM240 is a three-phase power module with a rated power of 75 kW and a maximum output current of 220 A, designed for efficient operation with a power factor of 0.85 and an efficiency of 0.97. It features internal air cooling and operates within a temperature range of 0 to 50 °C, with overload capabilities for both low and high overload scenarios. The module complies with various standards including UL, cUL, CE, and is suitable for a range of applications with specified mechanical and electrical connections.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Data sheet for SINAMICS G120 Power Module PM240

Ordering data
6SL3224-0BE35-5UA0

Client order no. : Item no. :


Order no. : Consignment no. :
Offer no. : Project :
Remarks :

Rated data General tech. specifications

Input Power factor λ 0.85

Number of phases 3 AC Offset factor cos φ 0.95

Line voltage 380 ... 480 V ±10 % Efficiency η 0.97

Line frequency 47 ... 63 Hz Sound pressure level (1m) 60 dB

Rated current with line reactor 151.00 A Power loss 1.93 kW

Rated current without line reactor 168.00 A Ambient conditions


Output Cooling Internal air cooling

Number of phases 3 AC Cooling air requirement 0.150 m³/s

Rated voltage 400 V Installation altitude 1000 m

Rated power (LO) 75.00 kW Ambient temperature


Rated power (HO) 55.00 kW Operation LO 0 ... 40 °C (32 ... 104 °F)

Rated current (LO) 145.00 A Operation HO 0 ... 50 °C (32 ... 122 °F)

Rated current (HO) 110.00 A Transport -40 ... 70 °C (-40 ... 158 °F)

Max. output current 220.00 A Storage -25 ... 55 °C (-13 ... 131 °F)

Pulse frequency 4 kHz


Relative humidity
Output frequency for vector control 0 ... 200 Hz
Max. operation 95 % RH, condensation not permitted
Output frequency for V/f control 0 ... 550 Hz

Overload capability

Low Overload (LO)

1.1 × output current rating (i.e., 110 % overload) for 57 s with a cycle time of 300 s 1.5 × output current rating (i.e., 150 % overload) for 3 s with a cycle time of 300 s

High Overload (HO)

1.5 × output current rating (i.e., 150 % overload) for 57 s with a cycle time of 300 s 2 × output current rating (i.e., 200 % overload) for 3 s with a cycle time of 300 s

Technical data are subject to change! There may be discrepancies between calculated and rating plate values.
generiert / generated Tue May 19 14:46:35 CEST 2015
Page 1 of 2
Data sheet for SINAMICS G120 Power Module PM240

Ordering data
6SL3224-0BE35-5UA0

Mechanical data Connections


Degree of protection IP20 Line side

Size FSF Version M8 bolt

Net weight 36.00 kg Conductor cross-section 25.00 ... 120.00 mm²

Width 350.0 mm Motor end

Height 634.0 mm Version M8 bolt

Depth 316.0 mm Conductor cross-section 25.00 ... 120.00 mm²

Converter losses to EN 50598-2 DC link (for braking resistor)

Efficiency class
IE2

Comparison with the reference converter (90% / Conductor cross-section 25.00 ... 120.00 mm²
-59.87 %
100%)

I Max. motor cable length


1401.4 W (1.39 %) 1598.9 W (1.59 %) 1899.8 W (1.89 %)
100% Shielded 50 m

Unshielded 100 m

Standards
786.3 W (0.78 %) 860.5 W (0.86 %) 961.1 W (0.96 %)
50%
Compliance with standards UL, cUL, CE, C-Tick, SEMI F47
577.6 W (0.57 %) 610 W (0.61 %)
25%
According to low-voltage directive
CE marking
2006/95/EC

50% 90% f
The percentage values indicate the losses with reference to the rated apparent power of the
converter.

The diagram shows the losses for the points (as per standard EN 50598) of the relative torque
generating current (I) over the relative motor stator frequency(f). The values are valid for the basic
version of the converter without options/components.

Technical data are subject to change! There may be discrepancies between calculated and rating plate values.
generiert / generated Tue May 19 14:46:35 CEST 2015