GEL9-12
SPECIFICATION
Cell per unit 6
Nominal Voltage (V) 12
Nominal Capacity (Ah) C20 9Ah at 20hour rate F.V(1.75/cell)
Weight ±3% Approx 2.50kg
Internal Resistance ≤ 18mΩ
Max Discharge Current (5s) 135A
Battery Design Life Standby: 5 years
Terminal Type F1/F2
Container Material ABS(94-HB & 94V-0 flame retardant case)
Ambient temperature Charge 0℃(32℉) to 40℃ (104℉)
Discharge -15℃(5℉) to 50℃ (122℉)
Storage -15℃(5℉) to 40℃ (104℉)
Charging Instruction (25°C):
Max charge current: Max charge current:2.7A
Cycle use : Charge voltage: 14.4 to 15.0V
Standby : Charge voltage: 13.50 to 13.80V
Short circuit current 225A
DIMENSIONS Length Width Height Total Height
Unit: mm 151±2 65±2 94±2 100±2
Unit: inch 5.94±0.08 2.56±0.08 3.70±0.08 3.94±0.08
Constant current discharge characteristics Unit:A(25℃77℉)
F.V/Time 5MIN 15MIN 30MIN 60MIN 2HR 3HR 5HR 8HR 10HR 20HR
1.60V 40.2 19.9 10.88 6.11 4.35 2.45 1.65 1.10 0.89 0.47
1.67V 38.0 18.9 10.32 5.94 4.25 2.39 1.61 1.09 0.88 0.46
1.70V 36.6 18.5 10.20 5.87 4.20 2.38 1.59 1.07 0.87 0.45
1.75V 35.1 18.0 9.99 5.67 4.10 2.35 1.58 1.06 0.86 0.45
1.80V 33.3 17.0 9.70 5.61 4.05 2.30 1.55 1.04 0.85 0.44
Constant power discharge characteristics Unit:W/cell(25℃77℉)
F.V/Time 5MIN 15MIN 30MIN 60MIN 2HR 3HR 5HR 8HR 10HR 20HR
1.60V 71.5 36.1 21.0 11.59 6.50 4.81 3.25 2.19 1.77 0.95
1.67V 68.9 35.8 20.5 11.29 6.40 4.70 3.20 2.15 1.75 0.94
1.70V 66.2 35.5 20.0 11.15 6.35 4.61 3.10 2.12 1.72 0.93
1.75V 64.0 34.1 19.5 10.10 6.30 4.57 3.05 2.09 1.70 0.90
1.80V 62.0 33.1 19.0 10.80 6.15 4.50 3.02 2.05 1.68 0.89
APPLICATIONS GENERAL FEATURES STANDARDS
● All purpose ● 5 years design life (25℃) Compliance with IEC 60896 standards
● Lead calcium alloy, sealed design.
● Non spillable and maintenance free
● AGM separator application
● Designed for a wide range of applications
Battery Discharge Characteristics (25℃/77℉) Battery Charge Characteristic for standby use
Temperature Effects in Relation to Battery Capacity Temperature Effects on Long Term Float Life
Cycle Service Life Self Discharge Characteristics
Charging Procedures Discharge Current VS. Discharge Voltage