Hydrogen Fires Notes 읽어보기
Hydrogen Fires Notes 읽어보기
Contents
Introduction ............................................................................................................................................ 4
Objectives of the lecture......................................................................................................................... 4
Main terminology.................................................................................................................................... 5
Types of hydrogen fires/flames .............................................................................................................. 7
Microflames ............................................................................................................................................ 7
Hydrogen flames quenching ............................................................................................................... 7
Leaky fittings ....................................................................................................................................... 9
Hydrogen jet fires and flame length ..................................................................................................... 10
The dimensional correlation ............................................................................................................. 13
The dimensionless correlation for hydrogen flame length ............................................................... 17
How to determine the flame length? ............................................................................................... 21
The jet flame tip location .................................................................................................................. 21
Deterministic separation distances from hydrogen jet fire .............................................................. 23
The effect of jet attachment on flame length................................................................................... 27
The effect of nozzle size and shape on flame length ........................................................................ 27
The effect of buoyancy on deterministic separation distances ........................................................ 29
The effect of barriers ........................................................................................................................ 29
Radiation heat fluxes from jet fires ...................................................................................................... 30
Hydrogen jet fires versus jet fires of common fuels ............................................................................. 33
Hydrogen fireballs ................................................................................................................................. 34
Pressure effects of hydrogen jet fires ................................................................................................... 35
The effect of an orifice diameter on overpressure ........................................................................... 35
The effect of the ignition delay on overpressure ............................................................................. 36
The effect of ignition source location on overpressure .................................................................... 37
Detection of hydrogen fires .................................................................................................................. 37
UV detectors ..................................................................................................................................... 39
IR detectors ....................................................................................................................................... 39
Thermal detectors............................................................................................................................. 40
Imaging systems ................................................................................................................................ 40
Fires of FC vehicles ................................................................................................................................ 40
Mitigation and extinction of hydrogen fires ......................................................................................... 46
Control of the jet flow direction ....................................................................................................... 46
Shielding or barriers .......................................................................................................................... 46
3
Introduction
Frequently, the term ‘safety’ is referred to as a ‘non-technical’ barrier to the emerging FCH
technologies. However, there is a number of engineering challenges to be addressed before rolling
out these technologies to the market. One of them is the reduction of hydrogen jet flame length from
the current value of 10-15 m from FC vehicle on-board storage to allow the evacuation and rescue of
passengers and their safeguarding by First Responders, when relevant [1]. Another important
unresolved problem is to increase the fire resistance rating of on-board hydrogen storage tanks from
1-7 minutes (current value for type IV vessels) to allow the longer time for blow-down of tanks. This,
in turn, would prevent severe damage of civil structures such as garages during accidental hydrogen
release. Additionally, it would exclude even a chance of large hydrogen-air clouds formation inside the
tunnels, which can lead to fatalities throughout the entire length of the tunnel in the case of fires. The
higher fire resistance rating of hydrogen storage tanks would permit safe evacuation of civilians from
an accident scene, providing life safety of passengers and First Responders [1].
First Responders, without a doubt, will have to deal with incidents or accidents involving hydrogen
flames because hydrogen fire is a typical scenario of many accidents. Knowledge of the hydrogen
flame length and related separation distances are of the key importance for First Responders. There
will also be a thermal radiation from a fire, which can cause harm to humans and damage to structures,
buildings, equipment, etc. at the distances beyond the flame length. A number of factors that affect
the extent of a jet fire and the associated radiative heat flux, including hydrogen storage pressure and
a leak size, will be discussed in the present lecture. Methods of hydrogen fire detection, the techniques
of hydrogen fires mitigation and extinction are considered in this lecture as well.
Main terminology
In order to fully understand hydrogen fires and other related phenomena (such expanded and under-
expanded jet flames, microflames, quenching and blow-off, surface effects on flame jet propagation,
lift-off, blow-off and blow-out phenomena, thermal radiation, flame visibility, flame length and speed,
impinging jet fires, etc.) it will be useful to learn a few definitions listed below. Please pay attention
to the dimensionless numbers, which will be frequently used in the present and further lectures.
Blow-down is a process where the storage pressure decreases with time during a leak [1].
Blow-out limit is a fuel flow velocity limit beyond which a lifted flame blows out [2].
Deflagration is the process following the weak ignition in a combustible mixture, which propagates at
a subsonic speed into fresh, unburned mixture [3].
Detonation is the process, in which the combustion wave propagates with a supersonic velocity in the
unreacted medium [3].
Drop-back is the reattachment to the nozzle of a lifted flame by a decrease of lift-off velocity [2].
Effective diameter is the jet diameter at the location where expansion down to 1 bar takes place, in
an under-expanded jet [4].
Expanded jet is the jet with a pressure at the nozzle exit equal to atmospheric pressure [1].
Fire-resistance rating is a measure of time for which a passive fire protection system can withstand a
standard fire resistance test [1].
Flame lift-off is the condition, in which the flame and a burner become separated.
Flame speed is the velocity of the flame with the respect to a fixed observer [3]
Flammability range is the range of concentrations between the lower and the upper flammability
limits. The lower flammability limit (LFL) is the lowest concentration of a combustible substance in a
gaseous oxidizer that will propagate a flame. The upper flammability limit (UFL) is the highest
concentration of a combustible substance in a gaseous oxidizer that will propagate a flame [1].
Flashpoint is the lowest temperature, at which the fuel produces enough vapours to form a flammable
mixture with air at its surface [1].
Froude number (Fr) is the dimensionless number equal to the ratio of inertial to gravity force
(multiplied by the product of density by area A). Fr=U2/gd, where U – velocity; d – characteristic size;
g – acceleration due to gravity [1].
Hazard distance is a distance from the (source of) hazard to a determined (by physical or numerical
modelling, or by a regulation) physical effect value (normally, thermal or pressure) that may lead to a
harm condition (ranging from “no harm” to “max harm”) to people, equipment or environment (as
6
Laminar burning velocity is the rate of flame propagation relative to the velocity of the unburned gas
that is ahead of it, under stated conditions of composition, temperature, and pressure of the unburned
gas [1].
Lift-off height is the height from the nozzle exit to the base of a lifted flame [2].
Lift-off velocity is the fuel flow velocity causing a flame to be detached from the nozzle [2].
Mach number (M) is the dimensionless number equal to the ratio of the local flow velocity to the local
speed of sound. M=U/C, where U – velocity; C – speed of sound [1].
Maximum Allowable Working Pressure (MAWP) is the maximum pressure, to which any component
or portion of the pressure system can be subjected over the entire range of design temperatures. This
value is 1.11.25the service pressure [5].
Normal Temperature and Pressure (NTP) conditions are: temperature 293.15 K and pressure 101.325
kPa [1].
Non-premixed flame (often called a diffusion flame) is the flame, in which the oxidiser and the fuel are
not mixed prior to reaching a flame front. During combustion oxidiser combines with a fuel by
diffusion. The flame speed is limited by the rate of diffusion.
Overpressure is the pressure in a blast wave above the atmospheric pressure, or the pressure within
a containment structure that exceeds the maximum allowable working pressure of the containment
structure [5].
Premixed flame is the flame, in which the oxidiser has been mixed with the fuel prior to the reaching
the flame front. Combustion of premixed fuel and oxidiser forms a thin flame front due to the
reactants being readily available.
Quenching gap is the spark gap between two flat parallel-plate electrodes at which ignition of
combustible fuel-air mixtures is suppressed. The quenching gap is the passage gap dimension
requirement to prevent propagation of an open flame through a flammable fuel-air mixture that fills
the passage [1].
Reynolds number (Re) is the dimensionless number that gives a measure of the ratio of inertial to
viscous forces. Re=Ud /, where U – velocity; d – characteristic size; – density; – viscosity [1].
Separation (or safety) distance is a minimum distance, which separates “specific targets (e.g. people,
structures or equipment) from the consequences of potential accidents related to the operation a
hydrogen facility” [6].
Under-expanded jet is the jet with a pressure at the nozzle exit above the atmospheric pressure [1].
Visible flame length is the centreline distance from the tip of the nozzle to the flame end [2].
7
Hydrogen may burn in different combustion modes, which include flash fire, jet fire, deflagration,
detonation, etc. Hydrogen fires can range from microflames with the mass flow rate of 10-9 kg/s to the
high mass flow rate flames (hundreds of kg/s). Hydrogen releases may burn as laminar diffusion or
turbulent non-premixed flames depending on the Reynolds number (Re) at a leak exit. Flames can be
buoyancy-controlled and momentum-dominated. Most of hazardous hydrogen releases will be in a
momentum-dominated regime. The jet fires can be, depending on the leak exit conditions, subsonic
(the Mach number M<1), sonic and highly under-expanded supersonic. In the scenarios, where a
failure of storage tank is possible with the immediate release of hydrogen into the surrounding
atmosphere large size fireballs (tens of meters) can be formed. The presence of obstacles, surfaces
and enclosures affect the jet flame significantly. A special case is the fires involving liquefied hydrogen
(LH2). Currently, there is a little knowledge available on LH2 fires. There is a knowledge gap with an
indication that condensation and solidification of oxygen (from the atmosphere) in the case of LH2
leak/spill at certain condition may lead to explosive mixtures.
Microflames
Hydrogen flames quenching
There is generally a limited range of flow rates, for which a flame can be established on a burner
nozzle. Below this range, the flow is said to be below the quenching limit [1]. Quenching of any flame
occurs when the heat losses from flame are comparable with the heat generated through combustion,
and thus the chemical reactions cannot be sustained. Hydrogen flames are difficult to quench. For
example, premixed hydrogen-air combustion can be aggravated by heavy sprays of water due to
induced turbulence and the ability of mixture to burn around the droplets. Hydrogen has the lowest
quenching distance compared to other flammable gases.
The quenching distance is the maximum distance between two parallel plates that will extinguish a
flame passing between them. The quenching distance decreases with the increase of pressure and
temperature. It also depends on the mixture composition [1]. The quenching gap is the spark gap
between two flat parallel-plate electrodes, at which the ignition of combustible fuel-air mixtures is
suppressed [1]. For the pre-mixed hydrogen-air mixtures two methods are often used:
A circular tube, with the aid of which the quenching diameter is measured;
A slot, through which the quenching distance is measured by referring to the width of the slot
[10].
8
There is another term used to describe quenching of hydrogen flames: a blow-off limit corresponding
to the flow rate reached, beyond which the flame blows off the nozzle [1]. Quenching and blow-off
limits bound the leak flow rates that can support combustion.
The quenching and blow-off limits of different gases were measured by Kalghatgi [11], Matta et al.
[12], Cheng et al. [13] for a variety of fuels including propane, methane and hydrogen on circular
burners (Figure 1). As it follows from Figure 1 the quenching limits are nearly independent of diameter.
Hydrogen has the lowest quenching limit and the highest blow-off limit.
These studies showed that hydrogen mass flow rate blow-off limits are higher than those for methane
and propane. For a given leak size, there is a range of mass flow rates where hydrogen is able to
support a stable flame but methane and propane would be blown off [1]. The topic of microflames
(flow rate 1 mg/s) is discussed in detail in the lecture ‘Hydrogen properties relevant to safety’. Butler
et al. [14] studied the quenching limits for diffusion microflames controlled by the momentum. The
quenching at such a small scale depends on the mass flow rate rather than the nozzle diameter. The
experimental data defined the minimum mass flow rate needed for sustained ignition as 0.028 mg/s
[14]. The diffusion flame below this value will be quenched. Figure 2 transposes the mass flow rate as
a function of a burner diameter and upstream pressure, assuming choked flow, for three different
fuels within a range of pressures. This graph confirms that quenching also depends on the pressure.
Each line in Figure 2 begins at the minimum upstream pressure for choked flow and ends at the
maximum pressure anticipated in FC vehicles. This plot predicts that for a given storage pressure,
hydrogen is susceptible to leak flames for hole diameters that are smaller than those for methane or
propane. Furthermore, at storage pressure of 69 MPa (690 bar) a hole with the diameter of just 0.4
µm is predicted to support a flame [1].
9
Leaky fittings
The compression fittings are often used for gases stored at high pressure. Figure 3 shows the
measured mass flow rates for hydrogen, methane, and propane for a 6 mm leaky fitting in the vertical
orientation [14]. The minimum flow rate necessary for sustained ignition is plotted versus pressure.
For all three fuels limits are independent of pressure and hydrogen has the lowest values of quenching
limits. Although hydrogen has the lowest mass flow rate necessary to sustain fittings micro-flames,
propane has the lowest volumetric flow rate to sustain fittings micro-flames [3]. More details on leaky
fitting can be found in [1].
Figure 3. Quenching limits (mass flow rates) as function of upstream pressure in the vertical
orientation of fittings [14].
10
Figure 4 shows images of flames from leaky fittings at quenching limits for hydrogen, methane and
propane [15]. The top, middle and the bottom sets involve tube diameters of 3, 6 and 12 mm,
respectively. Each fuel was flowing at the minimum flow rate needed to sustain flame.
Figure 4. The images of flames at the quenching limits for hydrogen, methane and propane [15].
Figure 5. Progression from laminar diffusion to fully developed turbulent non-premixed flames [17].
11
Figure 5 shows the change of the flame height with the increase in nozzle velocity during transition
from laminar diffusion to fully developed turbulent non-premixed flame as observed by Hawthorne et
al. [16]. In the beginning the increase of nozzle velocity leads to the increase of flame length for
laminar flames. Then, at some velocity the laminar flame height reaches its maximum and starts to
decline as the flame becomes turbulent at its tip first. The transition from vertical laminar diffusion
flame to turbulent flame starts to occur at Reynolds number of around Re=2000 if the release of
hydrogen into still air is considered.
It is not obvious that the conclusion made by Hawthorne et al. [16] on expanded jet fires regarding
the independence of flame length on the nozzle velocity for turbulent jets can be extended to under-
expanded jet fires. For instance, the turbulence and velocity fluctuation at the under-expanded jet
axis downstream of the Mach disk is known to be quite high compared to sub-sonic flows [1]. This high
level of turbulence in under-expanded jets has been confirmed recently by the application of the large
eddy simulation (LES) technique by Brennan et al. [18] during processing the experimental data on
large-scale hydrogen jet fires by Sandia National Laboratories.
Baev and Yasakov [19] theoretically showed that depending on the burner diameter D (Froude number
Fr) there will be a characteristic peak in the function LF= f (Re) mentioned by Hottel and Hawthorne
[17], or there will be no peak for nozzles of the larger diameters (Figure 6).
Figure 6. The theoretical flame length to diameter ratio (LF/D) as a function of Reynolds number (Re)
for different nozzle diameters D. The dotted horizontal line corresponds to a turbulent flame length
limit Lt [19].
These theoretical predictions were confirmed by the experiments of Shevyakov and Komov [20]
shown in Figure 7. The experimental dependence of LF/D on Re up to Re=20,000 is presented for nine
stainless steel tubular burners of diameter 1.45-51.7 mm. The burner length to diameter ratio was
changing from 50 for smaller diameter burners to 10 for the largest one. The visual length of subsonic
flames was measured in a darkened room. The hydrogen density of 0.0899 kg/m3 and the temperature
of 273 K were assumed in the nozzle exit during the processing of Shevyakov and Komov data [20] in
our studies.
The experimental dependence of LF/D on Re for smaller diameter (below 6 mm) burners has a
characteristic peak predicted theoretically by Baev and Yasakov [19]. This peak height is decreasing
with the increase of burner diameter in the area of transition from laminar to turbulent flow
(Re<2,300). Then LF/D increases again with Re approaching a limit LF/D=220-230 at high Reynolds
12
numbers. This experimental data is above a turbulent jet flame limit LF/D=190 measured by Baev and
Yasakov [19]. It is worth noting that for the same Reynolds number LF/D decreases with the diameter
increase.
Figure 7. The experimental flame length to diameter ratio (LF/D) as a function of Reynolds number
(Re) for different nozzle diameters, D, mm: 1 – 1.45; 2 – 1.9; 3 – 2.9; 4 – 4.0; 5 – 6.0; 6 – 10.75; 7 –
15.5; 8 – 21; 9 – 51.7 [20].
Until recently all studies on hydrogen flames were limited to expanded jet flames or flames with high
Reynolds number to conclude on functional dependence of jet flame length at Reynolds numbers
characteristic for releases at pressures up to 100 MPa. While studies of Baev and Yasakov [19] and
Shevyakov and Komov [20] answered the question on the existence of flame length peak during
transition from laminar to turbulent flame, the question on the stabilisation or further increase of
dimensionless flame length LF/D with Reynolds number is yet to be answered [21]. A chronological
and detailed review of hydrogen jet flame research can be found in Molkov [1].
Kalghatgi [22] published the experimental data of more than 70 tests with nozzle diameters in the
range of 1.08-10.1 mm, both with subsonic and sonic hydrogen jet flames. Two important conclusions
can be drawn from this research. The conclusions are valid for both subsonic and sonic flows: 1) the
flame length grows with the mass flow rate at a fixed pipe diameter D (D-constant), and 2) the flame
length grows with the diameter at fixed mass flow rate ṁ (ṁ - constant). These conclusions put under
doubt the generality of the statement by Hawthorne et al. [16] made by the analysis of expanded
subsonic jets only, that jet flame length is proportional to nozzle diameter only and hydrogen flow
rate is not a factor.
Dimensionless flame length correlations suggested by different authors are based on the use of the
Froude number (Fr) only, in one form or another. Recently Fr-based correlations were expanded to
high pressure hydrogen jet fires (under-expanded jets). The general idea of this technique is to
correlate experimental data with the modified Fr number that is built on so-called notional or effective
nozzle diameter instead of real nozzle diameter. However, the size of the notional nozzle diameter
and the velocity in the notional nozzle are dependent on the theory applied, including a number of
simplifying assumptions. To include the under-expanded jet fires into the dimensionless correlation
Schefer et al. [23] substituted actual nozzle diameter by effective (notional) nozzle diameter. In the
subsequent study Schefer et al. [24] the effective diameter was taken in the form
13
Deff=D(ρNUN/ρeffUeff)0.5 (where “N” denotes actual nozzle exit parameters and “eff” effective (notional)
nozzle parameter) and is accepted here to build a correlation presented in Figure 8.
Figure 8. The Fr-based flame length correlation in coordinates used by Schefer et al. [24] with the
extended range of experimental data on under-expanded jet fires.
Figure 8 demonstrates that flame length data is unacceptably scattered in the momentum-dominated
area of the correlation with large Froude numbers, which are typical for leaks from high pressure
hydrogen equipment. It is clear that the simplification of flame length correlations to functional
dependence on Froude number only, i.e. with ignoring the theoretically predicted and experimentally
observed dependence on Reynolds and Mach numbers, does not make it work well when under-
expanded jets are included [1].
The experimental data obtained by different research groups are collapsed onto the same curve, with
the best fit line in Figure 9 being described by the following dimensional equation:
where D is the actual nozzle diameter, m; and ṁ is the mass flow rate, kg/s. This equation requires
knowledge of the actual leak diameter and the mass flow rate only. The mass flow rate can be
calculated using any validated under-expanded jet theory. The advantage of this methodology is that
it does not require substituting the actual nozzle diameter by the notional nozzle diameter. This
excludes additional uncertainty in determination of parameters at notional nozzle exit related to
14
Figure 9. The dimensional correlation for hydrogen jet flame length [1].
The upper limit curve for the experimental flame lengths in Figure 9 (conservative estimate), is
represented by the following equation:
𝐿𝐹 = 116 ∙ (𝑚̇ ∙ 𝐷)0.347 , (2)
that yields 50% longer flame length compared to the best fit line described by the equation (1). The
correlations (1) and (2) give practically a linear dependence of the flame length on the nozzle diameter,
LF D. In contrast, the correlation shows a weaker dependence of the flame length on the density and
the velocity in the nozzle, LF (ρNUN)1/3.
The predictive capability of the dimensional correlation in Figure 9 is quite good for high debit jet fires
(20%), and yet it is only about 50% for smaller debit flames, where the characteristic peak in the
dependence LF/D=f(Re) for small diameters is one of possible reasons of the larger scattering in the
experimental data. While the correlation is a convenient and reliable tool for hydrogen safety
engineering at large mass flow rate leaks it is not shedding a light on the underlying the correlation
physics, and it has a low predictive capability at smaller leaks [1].
Figure 10 presents a nomogram designed to simplify the use of the dimensional correlation (1). The
graphical estimation of jet flame length using the nomogram requires only two parameters of a leak,
e.g. storage pressure and the actual diameter of the leak, which are usually available and do not
require any calculations [1].
15
Figure 10. The nomogram for hydrogen jet flame length [1].
The nomogram on Figure 10 is derived from the best fit line of the dimensional flame length
correlation shown in Figure 9. Please note that the conservative estimate of the flame length is 50%
longer, and thus the value obtained from this nomogram should be multiplied by 1.5. The use of the
nomogram for calculation of flame length is demonstrated in Figure 10 by thick lines with arrows.
Firstly, an actual nozzle diameter of a leak, e.g. D=3 mm in this example, and a storage pressure, e.g.
35 MPa, are chosen. Secondly, a horizontal line is drawn from the diameter axis at point 3 mm to the
right until it intersects with the pressure line denoted as 35 MPa. Thirdly, a vertical line is drawn from
the intersection point upward until the second intersection with the only line available in coordinates
(LF - (ṁD)1/2). Finally, to get a flame length a horizontal line is drawn from the second intersection to
the left until the final intersection with the axis denoted “Hydrogen flame length LF, m”. In the example
considered, the leak of hydrogen at pressure 35 MPa through the orifice of 3 mm diameter will result
in the flame length of 5 m. The conservative estimate of the flame length, as discussed above, is 50%
longer, i.e. 7.5 m [1].
16
It should be noted that the nomogram does not account for conditions when flow losses in a leakage
pathway cannot be ignored. In such cases, a straightforward use of the nomogram gives a conservative
result. A more accurate prediction of the flame length in equipment with essential friction and minor
losses can be obtained if a method is available allowing calculation of the density in the nozzle exit
affected by the losses. The nomogram can be used for a quick estimate of the hydrogen jet flame
length. However, the use of the novel dimensionless flame correlation is recommended for more
accurate calculation of the flame length.
Most of previously described and reviewed by Molkov [1] studies on hydrogen jet flames were
performed with the extended jets, with the exception of recent studies aiming to underpin safe
introduction of hydrogen as a new energy carrier. The majority of leaks from high-pressure hydrogen
equipment will be in the form of under-expanded jet (i.e. the jet with the pressure at the nozzle exit
above the atmospheric pressure. This means that in order to predict accurately the parameters of
hydrogen leaks at storage pressures above 10 MPa non-ideal behaviour of hydrogen should be taken
into consideration.
As mentioned earlier, the earlier notional nozzle model was developed by Schefer et al. [24]. Molkov
and Saffers [25] had applied an alternative theory of under-expanded jet, which under-expanded jet
conceptual scheme is shown in Figure 11. The parameters with sub-script 1 correspond to high-
pressure storage where the assumption of zero flow velocity is made. The flow parameters at the
entrance to the leak channel (i.e. nozzle) are referred to by sub-script 2, and at the nozzle exit – by
sub-script 3. It is assumed that the flow is choked at the nozzle/channel exit and therefore the exit
velocity is equal to the speed of sound. The notional nozzle exit, where parameters correspond to a
fully expanded jet (pressure is equal to ambient), is referred to by sub-script 4. It is assumed that at
the notional nozzle the flow velocity is uniform and locally sonic. It is also assumed that there is no air
entrainment to the jet through the notional nozzle boundary (between 3 and 4) [25].
Theoretical and experimental results indicate that the flame length has to be a function of not only
the Froude number (Fr) but also the Reynolds (Re) number and the Mach (M) number [1]. The
dimensional correlations similar to those depicted in Figure 9 are convenient engineering tools, yet
they do not make a distinction between different jet fire regimes. This section of the lecture aims to
advance the understanding of hydrogen jet flame behaviour. A dimensionless correlation for non-
premixed flames that will differentiate between traditional buoyancy-controlled and momentum-
dominated jet flames, as well as between expanded and under-expanded jet fires will be discussed
below.
The dimensional correlation (1) can be approximated as LF (ṁD)1/3. The mass flow rate is by
definition ṁ D2. Thus, a conclusion can be drawn after substitution of ṁ D2 into the above
relationship for LF that the dimensionless flame length, LF/D, does not depend explicitly on the
diameter, D. This is a basic hypothesis behind the development of a novel dimensionless correlation
for the jet flame length, which is supported by the experimental data analysis. The only dependence
of the dimensionless flame length, LF/D, is then on the “residual” parameters in the mass flow rate,
i.e. density ρN and velocity UN at the nozzle exit, which are assumed uniform for the simplicity [25].
The density and velocity can be normalized as ρN/ρS and UN/CN respectively, where CN is the speed of
sound at conditions of gas in the nozzle and ρS is the density of the surrounding gas (air). In assumption
of the kinetic energy flux in the nozzle exit to be a conserved scalar of the process a relation between
the density and the velocity in the dimensional group can be suggested as (ρN/ρS)(UN/CN)3.
Figure 12 presents a novel dimensionless hydrogen flame length correlation. In this correlation the
experimental data on flame length are normalized by the actual (not notional) nozzle diameter, and
are correlated with the product of the dimensionless density ratio ρN/ρS and the Mach number (ratio
of the flow velocity to the speed of sound at the actual nozzle exit) to the power of three M3=(UN/CN)3.
18
Figure 12. The dimensionless correlation for hydrogen jet flames (in formulas “X” denotes the
similarity group (ρN/ρS)(UN/CN)3).
One of the advantages of this correlation is the absence of parameters at the notional nozzle exit. The
parameters needed to predict the flame length are those at the actual nozzle exit only: diameter,
hydrogen density and flow velocity, the speed of sound at pressure and temperature at the nozzle
exit. There is lesser uncertainty in calculation of flow parameters in the actual nozzle exit compared
to uncertainties at the notional nozzle. Indeed, it is well known that there is a strong non-uniformity
of velocity immediately downstream of the Mach disk that deviates from the common for all under-
expanded jet theories assumption of uniform velocity at the notional nozzle exit. By this fact, the
developed methodology excludes from consideration the questionable issue of use of flow
parameters at the notional nozzle exit [1].
The correlation covers the whole spectrum of hydrogen reacting leaks, including laminar and turbulent
flames, buoyancy- and momentum-controlled fires, expanded (subsonic and sonic) and under-
expanded (sonic and supersonic) jet flames in the range of leak source pressures from 0.1 to 90 MPa
and leak diameters from 0.4 to 51.7 mm.
The dimensionless group derived for correlating the dimensionless flame length can be rewritten in
terms of Re and Fr numbers as follows:
3
N U g N
N Re Fr , (3)
S CN S CN3
19
N d N U N
Re , (4)
N
U N2
Fr (5)
dN g .
The form of the dimensionless group in the left hand side of the equation (3) suggests that for subsonic
flows, when Mach number M<1 and the density ratio ρN/ρS is a constant for expanded jets (in
assumption of constant temperature in the nozzle), the dimensionless flame length depends on the
nozzle Mach number only. For choked flows in the nozzle exit (M=1) the dimensionless flame length
depends only on the hydrogen density in the nozzle exit ρN. The density increases with the increase of
storage pressure and the decrease of hydrogen temperature.
The form of the right hand side of the equation (3) indicates that at a constant temperature of
hydrogen in the nozzle exit (that provides the constancy of the speed of sound CN) the dimensionless
flame length depends on both Fr and Re numbers. This is contrary to the former correlations built on
Fr number only.
There are three distinct parts in the novel dimensionless correlation in Figure 12 (from the left to the
right): traditional buoyancy-controlled, traditional momentum-dominated “plateau” (expanded jets),
and a new momentum-dominated under-expanded jet fire “slope”. These three parts can be
approximated by the following equations (conservative curves) respectively:
(6)
There is a saturation of LF/D for expanded jet fires as the flow velocity in the actual nozzle exit is
approaching the speed of sound. The value of this saturation limit LF/D =230 reproduces results of a
number of previous studies with expanded jets, though in the new coordinates. However, there is no
saturation of the dimensionless flame length for choked under-expanded jet flames. Reported in
recent under-expanded jet fire experiments Proust et al. [26] values up to LF/D=3000 are significantly
higher compared to the limit LF/D =230 for expanded jets.
20
The shape of the correlation in Figure 12 has a physical meaning based on the knowledge of jet flame
behaviour. For example, the dimensionless flame length, LF/D, increases for laminar and transitional
flames (usually identified as “buoyancy-controlled” regime, low Re), then it is practically constant for
transitional and fully developed turbulent expanded flames (traditionally named as “momentum-
dominated” regime, moderate Re), and it increases again for under-expanded jets (momentum-
controlled under-expanded jet regime, high Re). The growth of dimensionless flame length in the
under-expanded regime is due to the fact that the dimensionless flame length is defined through the
actual nozzle exit diameter, which is a constant, while in reality the under-expanded jet expands to
atmospheric pressure at the notional nozzle exit which increases with the increase of density in the
nozzle [1].
Figure 13 demonstrates changes of dimensionless numbers Re, Fr, M, for the experiments used for
the development of the dimensionless correlation, as a function of the similarity group (ρN/ρS)(UN/CN)3.
The analysis of Re, Fr, M functional dependence on the similarity group shows that for under-
expanded jets the dimensionless flame length growth depends practically on Re only. Indeed, the
nozzle flow for under-expanded jets is choked, i.e. local M=1, and the nozzle Fr number is practically
constant also (the scattering of Fr is due to the difference in nozzle diameters of about one order of
magnitude).
Figure 13. Dimensionless numbers Re, Fr, M as a function of the similarity group (ρN/ρS)(UN/CN)3 for
the experiments used to build the dimensionless correlation.
There are five dashed lines in Figure 13. Line Re=2000 indicates the start of transition from laminar to
turbulent nozzle flow. Close to (or immediately above) this line there are experimental points
representing laminar jet flames and jet flames in the transitional regime. Horizontal line M=1 indicates
a choked flow limit. Subsonic expanded jets have M<1 and sonic and supersonic (the last is relevant
to notional nozzle flows only) under-expanded jets have M=1 in the nozzle exit. There is some
scattering of data around M=1 due to measurements and data processing errors. Horizontal line
21
In log-log coordinates in Figure 13 the Fr number increases linearly with the similarity group
(ρN/ρS)(UN/CN)3 for expanded jet fires. There is practically no change of Fr for under-expanded jets in
this new system of coordinates (scattering is mainly due to difference in nozzle sizes). There is a slight
growth of Re with the similarity group for buoyant jets, moderate increase in traditional momentum-
dominated area, and comparatively steep growth of Re number in the area of under-expanded jet
fires that are all momentum-dominated [1].
In Figure 12, Y axis corresponds to the ratio, Lf/D, where Lf is the flame length (in m), D is the nozzle
diameter (in m); X axis corresponds to (ρN/ρS)(UN/CN)3 , where ρN is the density of hydrogen at the
nozzle exit, which can be found in the same way as with similarity law for unignited jets (see the
Lecture on Unignited hydrogen releases). It is equal to 0.0838 kg/m3 at NTP for sub-sonic and
expanded sonic jets. If the jet is under-expanded then the density is calculated by the under-expanded
jet theory developed by UU. ρS is the density of the surroundings (air), which equals to 1.205 kg/m3.
CN is the speed of sound in hydrogen at the nozzle exit, which can be calculated using the equation
(7):
P RT
C (7)
M
UN is the velocity of the hydrogen at the jet exit. UN = CN for sonic and supersonic jets,
for sub-sonic jets the velocity is calculated as:
P
UN 2 (8)
N D
m
C ax 5.4 (9),
S x
22
m
where Cax is the axial mass fraction of hydrogen in the jet at the distance x from the nozzle,
S is the density of the surrounding gas, i.e. air (1.205 kg/m3 at NTP),
D is the real nozzle diameter exit,
N is hydrogen density in the nozzle exit.
The similarity law allows deriving a functional dependence x/D=f(p) between the dimensionless
distance from the leak source x/D and the storage pressure p (that is unambiguously related with the
density at the nozzle exit, N) for any particular mass fraction of hydrogen on the jet axis, Cax [1].
Figure 14 presents a correlation between the location of hydrogen jet flame tip (i. e. flame length) and
the location of hydrogen concentration in unignited jet originating from the same leak source. The
points in Figure 14 represent the dimensionless experimental flame length, LF/D. The diagonal curves
in the graph correspond to the dimensionless distance x/D to the location of particular axial hydrogen
concentration, Cax, as a function of the density in the nozzle exit, ρN, (recalculated to the storage
pressure, p in atmospheres, in Figure 14) and calculated using the similarity law (9).
Figure 14. The correlation between the dimensionless flame length, LF/D, and the distance to a
particular concentration in a non-reacting jet, x/D, from the same leak source for different storage
pressures, p.
The conclusion can be drawn from Figure 14 that for momentum-controlled round jet fires the flame
tip is located where the axial concentration of hydrogen in an unignited jet, from the same leak source,
is in the interval between 8 vol. % and 16 vol. %, depending on experimental conditions. The best fit
line of 70 experimental points for hydrogen flame length of momentum-dominated jet fires is close to
11 vol. % of hydrogen in air in an unignited jet. These concentrations (8% to 16%) are far below the
stoichiometric concentration of 29.5 vol. % of hydrogen in air. The distances to these concentrations
from the nozzle are longer by 2.2 times (16%) to 4.7 times (8%) than the distance to the axial
23
concentration of 29.5% (stoichiometric hydrogen-air mixture). This obviously could have serious safety
and economic implications [1].
The nomogram developed originally for unignited releases, e.g. the hazard distance to the
concentration in unignited jet 4 vol. % can be applied now to graphically evaluate the flame length
(Figure 15). This is due to the knowledge that flame tip location is in the place where the concentration
in unignited jet from the same source decays to 8-16 vol. % of hydrogen with the average flame length
located where unignited release concentration decays to 11 vol. % [21].
Figure 15. The nomogram for graphical evaluation of the flame length by concentration decay in
unignited jet from the same source to 11 vol. %.
The example with 11 vol. % of hydrogen (red arrowed lines in Figure 15) shows that the average flame
length for 1 mm diameter leak from storage at pressure of 70 MPa and temperature of 300 K would
give flame length of about 2.7 m [21].
As per draft ISO TC197 definition, hazard distance is a distance from the (source of) hazard to a
determined (by physical or numerical modelling, or by a regulation) physical effect value (normally,
thermal or pressure) that may lead to a harm condition (ranging from “no harm” to “max harm”) to
people, equipment or environment.
The separation distance (SD) is also known as a safety distance or setback distance is a subject of
international debate.
According to LaChance (2009) SD is “a minimum distance, which separates specific targets (e.g.
people, structures or equipment) from the consequences of potential accidents related to the
operation a hydrogen facility” [27].
European Industrial Gases Association [28] defines SD as “a minimum separation between a hazard
source and an object (human, equipment or environment) which will mitigate the effect of a likely
foreseeable incident and prevent a minor incident escalating into a larger incident”.
Different engineering tools to calculate hydrogen jet flame length are developed and described above.
They include the dimensional and dimensionless correlations for the jet flame length, as well as the
methodology to calculate hydrogen axial concentration decay to 11 vol. % in an unignited jet to
evaluate the flame tip location (flame length). However, the question about separation distances from
a leak source based on a comparative analysis of hazards from unignited jet and jet fire is not yet
finalised [1].
Before calculating the hazard distance, it is necessary to consider what you would like to protect
against. In the case of free fires this would be the temperature and the heat flux (in the case of
enclosure fires - asphyxiation and overpressure may also be relevant). For people direct flame contact
as a result of a jet fire is generally assumed to result in third degree burns. For people not in the flame,
there is still potential for exposure to high radiation heat fluxes.
Harm criteria for people can be expressed in terms of injury or death [27]. It is possible to use a “no
harm” criterion, which limits the level of acceptable consequences, to a low enough level that no injury
would occur. Temperature 70 oC is taken as “no harm” criterion in this study. The exposures to flames,
hot air or radiant heat fluxes can result in first, second, or third degree burns. The resulting level of
harm is dependent upon several factors: the amount and location of exposed skin, the person’s age,
the exposure time, the speed and type of medical treatment, etc. [1].
British standard [29] recommends 115 °C as a threshold for pain from an elevated air temperature for
an exposure that lasts longer than 5 minutes. This is in line with the previously published classification
by DNV [30] of elevated temperature effects on occupants: below 70 °C, no fatal issue in a closed
space except uncomfortable situation; between 70°C and 150°C, the impact is dominated by
difficulties to breath; above 150°C, skin burns occur in less than 5 minutes and this is a limiting
25
temperature for escape [30]. Time to incapacitation in minutes as a function of air temperature (oC)
can be estimated by the following equations recommended by DNV [30] and BSI [31], respectively:
−3.66
𝑡𝑖𝑛𝑐 = 5.33 × 108 × 𝑇𝑎𝑖𝑟 , (10)
−3.4
𝑡𝑖𝑛𝑐 = 5 × 107 × 𝑇𝑎𝑖𝑟 . (11)
For temperature 115 oC the equation (10) gives the incapacitation time 5 minutes of exposure and the
equation (11) gives 15 minutes. Temperature 115 oC is assumed here as the acceptance criteria for
pain limit in hot air when considering an escape from an elevated temperature gas flow generated by
a hydrogen jet fire. More details on physiological response of humans to air at elevated temperature
are discussed in the Lecture on Harm criteria.
Figure 16 shows measured axial temperature of hydrogen flame [27, 32, 33] as a function of distance
from the nozzle, x, normalised by the flame length, LF. Three accepted here criteria are presented by
horizontal lines: 70 oC - “no harm” limit; 115 oC - pain limit for 5 min exposure; 309 oC - third degree
burns for a 20 s exposure (“death” limit). A comparison between the axial temperature profile and
named criteria provides the hazard distances: x=3.5LF for “no harm” separation (70 oC), x=3LF for pain
limit (115 oC, 5 min), x=2LF for third degree burns (309 oC, 20 s).
Figure 16. Measured axial temperature as a function of distance expressed in flame calibres, and
three criteria for jet fire effects (horizontal lines).
A comparison of three hazard distances for momentum-controlled jet fire and a hazard distance for
momentum-dominated unignited release (distance to the lower flammability limit, LFL, of 4 vol. % of
hydrogen in air) for the same leak source was carried out. It is demonstrated above that the
statistically averaged flame length is equal to the distance from the nozzle to an axial location where
hydrogen concentration decays to 11 vol. % in unignited jet (data are scattered from 8 to 16 vol. %).
The similarity law (9) for concentration decay in unignited momentum-controlled jets requires the use
of hydrogen mass fraction and not volumetric fraction as mistakenly applied in some published work.
26
The mass fraction (CM) can be calculated by the volumetric (mole) fraction (CV) by equation
1/CM=1+(1/CV -1)MS/MN, where MS and MN are the molecular mass of surrounding gas and nozzle gas
respectively. For air composition of 21 vol. % of oxygen and 79 vol. % of nitrogen the mass fraction of
hydrogen Cax=0.002881 corresponds to 4 vol. % of hydrogen in air, 0.008498 corresponds to 11 vol. %
of hydrogen (Cax=0.005994 – to 8 vol. %, Cax=0.013037 – to 16 vol. %), and mass fraction of hydrogen
in stoichiometric mixture (29.5 H2 vol. %) is Cax=0.0282 [1].
The ratio of distances from the nozzle to axial concentration 11 H2 vol. % (correct flame tip location)
and to 29.5 H2 vol. % (incorrect location of the flame tip suggested in some studies) can be estimated
by dividing the similarity laws (9) for these two concentrations by each other (in assumption that the
similarity law is applicable up to concentrations as high as stoichiometric), i.e.
x11%/x29.5%=Cax(29.5%)/Cax(11%)=0.0282/0.008498= 3.3. This increases calculated flame length by an order
of magnitude compared to that based on the previous incorrect knowledge (attributing flame length
tip location to location of 29.5 H2 vol. % in unignited jet from the same source) [1].
The ratio of distances to LFL of 4 vol. % and to the averaged flame tip location of 11 vol. % is (it has to
be stressed that flame length is not equal to hazard distance from the flame source):
x4%/x11%=0.008498/0.002881=2.95 (LFL distance to longest flame length ratio is x4%/x8%=2.08, and LFL
to shortest flame ratio is x4%/x16%=4.53). Thus, ratios of the hazard distance to LFL (unignited jet) to
three hazard distances based on the choice of harm criteria from reacting hydrogen jet are (for
average flame tip location at concentration in unignited jet of 11 vol. %):
x4%/xT=70C=x4%/(3.5x11%)=2.95/3.5=0.84,
x4%/xT=115C= =2.95/3=0.98,
x4%/xT=309C =2.95/2=1.48.
However, in the conservative case of the flame tip location at the concentration of 8 H2 vol. % in
unignited jet, these three ratios will change to the following values respectively:
x4%/xT=70C=x4%/(3.5x8%)=0.005994/0.002881/3.5=2.08/3.5=0.59;
x4%/xT=115C(8%)=2.08/3=0.69;
x4%/xT=309C(8%) =2.08/2=1.04.
As a result, an “unexpected” conclusion can be drawn from the performed analysis that in the
conservative case all three hazard distances for reacting release (jet fire) are either longer or equal to
the hazard distance based on the LFL (unignited release). In particular, the hazard distance from a
hydrogen leak source to a location with axial concentration equal to the LFL, e.g. to prevent ingress of
flammable mixture into a ventilation system of a building, is practically equal to the “death” separation
distance for reacting release (exposure to 309 oC during 20 s). Two other SDs for jet fires (“no harm”
and “pain” limits) are longer than the hazard distance to LFL (unignited release) [1].
The revealed “longest” location of the hydrogen jet flame tip at axial distances from the nozzle
corresponding to 8 vol. % of hydrogen in unignited jet is a physically sound result. Indeed, this value
is within the measurements and theoretical assumptions error to the LFL for downward and
spherically propagating premixed hydrogen-air flames of 8.5-9.5 vol. %. Thus, any combustion beyond
27
this distance (at smaller concentrations) is “detached” from the area of “continuous” vertical flame
[1].
Radial separation distance from hydrogen jet fire requires an analysis of radiative heat transfer rather
than flow temperature. Relevant information can be found elsewhere [24].
3.2 9 6 x1.50
6.4 11 9 x1.22
9.5 13 11 x1.18
For attached jet from the nozzle located only 0.11 m above the ground the flame length increases as
follows by: 1.83 for nozzle diameter 1.5 mm, 1.50 - nozzle diameter 3.2 mm, 1.22 - nozzle diameter
6.4 mm, and 1.18 nozzle diameter 9.5 mm. The effect of nozzle location above ground on its length
growth decreases with the increase of the nozzle diameter.
Mogi and Horiguchi [35] also have carried a series of experiments, at release pressure of 40 MPa,
studying effect of the nozzle shape on hydrogen flame length and width. Three nozzles of the same
cross-section area were tested: the round nozzle 1 mm in diameter, the plane nozzle with size
LxW=2x0.4 mm (aspect ratio (AR)=5), the plane nozzle of LxW=3.2x0.25 mm (AR=12.8). All three
nozzles had the same cross section area. Figure 18 shows nozzles images (left), pictures of side view
of hydrogen flame from each of three nozzles (centre), and front view of these jet flames (right). The
28
round nozzle flame shape is axisymmetric as in many other experiments. The reacting flow is in the
momentum-dominated regime as the effect of buoyancy is not pronounced. However, flames from
plane nozzles are flattened in the direction perpendicular to the major axis due to the so called
“switch-of-axis” phenomenon [36].
1m 1m
(a) d = 0.0004 m
(b) d = 0.0008 m
(c) d = 0.002 m
Figure 17. The effect of nozzle diameter on flame length (pressure 35 MPa) [35].
Figure 18. Photographs of three nozzles shape (left), side view of hydrogen flame (centre), and front
view of hydrogen flame (right) for release pressure of 40 MPa and different nozzle shapes [35].
29
The measured flame lengths and widths are presented in Figure 19 [35]. Within tested range of
pressures and nozzle sizes the flame length decreased with increase of aspect ratio: for AR=5 the flame
length is approximately twice less compare to the flame from round nozzle, and for AR=12.8 the flame
length is about 2.5 time less. In the same time the maximum flame width for plane nozzles was
approximately twice of that for the round nozzle.
Figure 19. Flame length (left) and flame width (right) for three different nozzles of the same cross-
section area: round nozzle of 1 mm diameter, plane nozzle with aspect ratio AR=5, plane nozzle with
AR=12.8 [35].
Figure 20 shows a sequence of snapshots (from top to bottom) after the delayed ignition of hydrogen
jet impinging a 90o barrier. Before the jet flame reaches the quasi-steady state conditions (bottom
snapshot) there is a deflagrative combustion of the non-uniform mixture in the confined space
between the barrier and ground (see top and middle snapshots). The inclined to 60o barrier increases
overpressure further to 57 kPa. Figure 21 shows two snapshots after the delayed ignition of hydrogen
jet impinging a 60o barrier.
30
Figure 20. The delayed (0.8 s) ignition of hydrogen jet (20.5 MPa pressure storage, 9.5 mm diameter
nozzle) impinging a 90 degree barrier: deflagration stage (top and middle snapshot), steady-state
impinging jet fire stage (bottom snapshot), HSL test [38].
Figure 21. The delayed (0.8 s) ignition of hydrogen jet (20.5 MPa pressure storage, 9.5 mm diameter
nozzle) impinging a 60o barrier: deflagration stage (top snapshot), steady-state impinging jet fire
stage (bottom snapshot), HSL test [38].
environment where the hydrogen flame is practically invisible. However, hydrogen combustion and
hot currents will cause changes in the surroundings that can be used to detect the flame. Although
the non-luminous hydrogen flame makes visual detection difficult, there is a strong effect of heat and
turbulence on the surrounding atmosphere and raising plume of hot combustion products. These
changes are called the signature of the fire.
The following section is based on recent work performed at Ulster in HySAFER centre [7]. Before
discussing radiative heat flux it is worth noting that a hydrogen flame emits minimal infrared radiation
and virtually no visible radiation. As discussed in the previous Lecture, due to the absence of CO2
radiation bands and the strong absorption by ambient water vapour, the ratio of visible to infrared
hydrogen jet flames is 0.88 and the ratio of ultraviolet to infrared flame length is 0.78 [39].
Nevertheless, convective and radiative heat fluxes still remain important and must be assessed for the
protection of life, property and the environment.
Molina et al. [40] and Schefer et al. [23] developed a model to predict the heat fluxes at any radial (r)
and axial (x) position from under-expanded jet fires (see Figure 22) [40].
The use of nominal values nevertheless under-predicts experimental radiative heat flux. To determine
radiant heat flux, the following steps have to be followed. It is first necessary to calculate the air
density in the flame using the following equation:
(12)
where 𝜌𝑓 is the air density in the flame (kg/m ), Pamb is the ambient pressure, Msto is the mean
3
molecular weight of the stoichiometric products of hydrogen combustion in air (24.54 kg/kmol), R is
the universal gas constant (8314.47 kJ/kmol·K), and Tad is the adiabatic flame temperature of hydrogen
in air. The flame length, width and density are then used in the equation (13) to determine the flame
residence time
(13)
where f is the residence time (s), Wf is the flame width (assume ratio to length is 0.17), Lf is the flame
length, fs is the mass fraction of fuel at stoichiometric conditions (0.0283), nozz is the density of flow
in the nozzle, dnozz is the jet discharge diameter and Unozz is the velocity of flow in the nozzle.
32
Once the flame residence time is known then it is possible to extract the radiant fraction, Xrad, from a
figure given by Schefer et al. [23] reproduced in Figure 23 where Xrad is the fraction of total chemical
heat release that is radiated to the surroundings. It should be noted that for a small flame, the
approach suggested by Schefer et al. could not be used because L is small and then the radiant fraction
is negative.
The radiant fraction is then implemented in the equation (14) to extract Srad, the total emitted radiative
power:
(14)
where Srad is the total emitted radiative power (W), ṁnozz ̇ is the mass flow rate at the nozzle and ΔHc
is the heat of combustion of hydrogen. The coordinates x and r can be chosen in two ways:
Option 1: The coordinates can be chosen. In that case they can correspond to the location of
possible targets of a jet fire: occupants, building, escape routes, other source of potential hazards
like storage of flammable or toxic substance, etc. When coordinates are chosen, the first step is
to calculate Lf. Then, it is easy to calculate the non-dimensional radiant power C* using the
desired value of x (m), the position on the jet axis from the nozzle. This can be done using the
Figure 24. Finally, by setting the r value, qrad (x,r) is calculated with the equation (15).
Option 2: The coordinates can be calculated for a chosen value of radiative heat flux. It means
that the calculated coordinates form contour around the jet fire corresponding to a particular iso-
value of radiative heat flux. The value of the radiative heat flux can be defined e.g. as acceptance
criteria. The flame length, flame width, residence time, radiant fraction and the total emitted
radiative power have to be calculated. Then, the value of the non-dimensional radiant power can
be calculated using appropriate equation for each value of x in the desired range. Finally, r can be
calculated for each axial position by implementing in the equation (15) the corresponding value
of C* and the chosen radiant heat flux:
(15)
where qrad (x, r) is the radiative heat flux at the location (x, r) (W/m2), C* is the non-dimensional radiant
power from Figure 24, and r is the radial position from the jet centreline (m).
It should be noted that the above analysis is based on a vertical flame. It is not clear yet what the
effects will be when a flame is horizontal. Buoyancy may influence the flame and thus at this stage it
is hard to estimate how the downstream hot currents will behave. Thus, the approach described above
may be somewhat conservative in the case of a horizontal flame.
Effect of radiative heat flux on people, environment and structures is discussed in detail in the Lecture
on Harm criteria.
Figure 25. Infrared image of jet fires showing thermal radiation produced by combustion of:
hydrogen (200 bar), CNG (200 bar) and LPG (10 bar).
34
As it is shown in Figure 26, for the same flow rate, due to the oxygen consumption, which is 4 times
higher for CNG and 5 times higher for LPG than for hydrogen, the flame lengths of CNG and LPG jet
fires are longer than the hydrogen flame length.
Figure 26. Comparison of the flame lengths for jet fires of: hydrogen (orifice diameter 3.1 mm), CNG
(orifice diameter 3.1 mm), and LPG.
It is important to remember that hydrogen flame is not visible in a pure environment. However, for
FCH systems and infrastructure applications there are always combustible materials present, which
will colour the flame as it shown in Figure 26.
Hydrogen fireballs
Hydrogen fireballs can be produced as a result of a hydrogen storage tank catastrophic failure. The
case for safety published on “h2safe.net” resource (http://h2safe.net/case_safety.html) [41] analyses
relative frequencies of failure modes and states that only about 10-27% of pressurised gas releases
are classified as catastrophic. Nevertheless, it must be stressed that the malfunction of the tank safety
device, TPRD, can lead to a catastrophic rupture of the hydrogen storage tank. UU is currently working
on the catastrophic rupture consequences and effects, focusing on heat radiation and blast waves. At
the moment, sizes of fireball reported by Zalosh [42] can be used as a guidance. The experiments
related to a catastrophic failure of hydrogen storage tank were carried out on a stand-alone vessel
(type IV tank; volume 72.4 L; storage pressure 34.3 MPa; no TPRD) and the vessel installed underneath
a sport utility vehicle (type III tank, volume 88 L; storage pressure 31.8 MPa, no TPRD). Type III stand-
alone tank catastrophically failed after 6 min 27 s from the start of the fire. It was followed by a fireball
of 7.7 m in diameter, 45 ms after tank rupture. This fireball was lifted in 1 s [42].
After approximately 4 minutes of exposure to the propane bonfire, flames and gases entered the
passenger compartment. The catastrophic tank rupture occurred after 12 minutes 8 seconds of fire
exposition, generating a fireball with maximum diameter of 24 m and lasting 4.5 seconds. Various
parts of the test vehicle and storage tank were found at distances up to 107 m. It must be stressed
that the above mentioned distances can be even longer for the hydrogen storage tanks pressurized to
70 MPa [42].
35
The UK Health and Safety Laboratory (HSL) of the Health and Safety Executive performed a series of
over 40 experiments with high pressure releases of hydrogen as a part of the project HYPER [38] and
published later by Royle and Willoughby [34]. The effects on overpressure of the varying jet exit
diameter, the ignition delay and position were determined.
Hydrogen was stored in two 50 litres cylinders at pressure 20.5 MPa. There was a stainless steel tubing
of internal diameter 11.9 mm, and a series of ball valves with internal bore diameter of 9.5 mm
between the storage and the nozzle exit. Restrictors of the same 2 mm length and different diameter
of 1.5, 3.2, and 6.4 mm were used in the nozzle to vary the jet exit diameter. The release point is 1.2
m above the ground. The jet was ignited by a match head with small amount of pyrotechnic material
1.2 m above the ground. The ignition point location varied in the range 2-10 m from the release point.
Piezo-resistive transducers were pointed out upwards except for wall mounted. Three transducers
were located at perpendicular to the axis distance 1.5 m, 2.6 and 3.7 m, at height 0.5 m [34]; axial
distance of all transducers was 2.8 m from the nozzle and height was 0.5 m.
Time 260 ms was needed to fully open the valve, 140 ms for hydrogen to reach 2 m. Thus, 400 ms is
the shortest possible ignition delay of the unsteady jet. Jets from hydrogen storage at 20.5 MPa were
predominantly momentum-controlled, i.e. the flow was relatively non-buoyant up to the lower
flammability limit [34].
There was no overpressure for release through the nozzle of 1.5 mm diameter. The overpressure for
400 ms ignition delay, when jet just reached the ignition point located 2 m downstream from the
nozzle, is always below the overpressure for the ignition delay of 800 ms corresponding to a larger
turbulent flammable hydrogen-air cloud formed. It is worth noting that there is a wall in the
experiments behind the nozzle. The maximum registered overpressure of free hydrogen jet was
16.5 kPa.
36
Table 2. The effect of an orifice diameter and the ignition delay on the maximum overpressure
generated by deflagrating jet [34].
Orifice diameter, mm Ignition delay, ms Max overpressure, kPa
There is an important conclusion from this series of experiments: the leak diameter has to be reduced
as low as reasonably possible (ALARP) for a particular FCH technology. The inclusion of flow restrictors
in hydrogen supply lines reduces the flame lengths observed, therefore reducing safety distances
required. This is thought due to reduction of mass flow rate and pressure losses on the restrictor and
thus lower pressure at the jet exit from the pipe.
It was concluded that the jet turbulence and the size had a greater effect on a deflagration pressure
than the total amount of hydrogen leaked. The total amount of hydrogen released is not always
important, especially at open atmosphere, as buoyancy continues to drive dilution of hydrogen by
entrained air until it reaches the LFL of 4 vol. % and beyond. Thus, portions of hydrogen released in
the beginning in many practical scenarios will not contribute to the combustion as they form a part of
cloud which is below the LFL [34].
It can be assumed, based on the presented results, that the spontaneous ignition of a sudden
hydrogen release by the diffusion mechanism could reduce overpressure of self-ignited release
compared to the delayed ignition (the ignition delay is minimised in this case). It is worth noting that
the spontaneous ignition was observed during sudden release in case of rupture disk burst and author
is not familiar with any results of spontaneous ignition of jet by the diffusion mechanism when valves
were used to initiate the high pressure hydrogen release [1].
Table 3. The effect of ignition delay on the maximum overpressure generated by deflagrating jet
[34].
Ignition delay, ms Max overpressure, kPa
400 3.7
500 18.4
600 19.4
800 15.2
1000 11.7
1200 12.5
2000 9.5
Table 4. The effect of the ignition source position on the maximum overpressure generated by
deflagrating jet [34].
Ignition position, m Max overpressure, kPa
3 5.0
4 2.1
5 2.1
6 Not recordable
8 Not recordable
10 No ignition
As stated earlier hydrogen burns with a pale-blue flame (in clean environments) and emits neither
visible light in day time (sun radiation can overpower the hydrogen flame light) nor smoke unless e.g.
sodium is added or dust particles are entrained and burned along with the combustible mixture.
Compared to hydrocarbon combustion, hydrogen flames radiate significantly less heat and so human
physical perception of this heat does not occur until direct contact is made with the flame. Therefore,
hydrogen fire may remain undetected and propagate in spite of any human direct monitoring in the
areas where hydrogen can leak, spill or accumulate, forming potentially combustible mixtures.
Hydrogen fire detectors can help to take immediate actions in these situations. Hydrogen fire
detectors can be either fixed for continuous monitoring of remote operations or portable for field
operations.
Some most common types of hydrogen detectors are summarised in Table 5 and described in detail
in the following sections.
For an efficient and a reliable use, a hydrogen fire detector should fulfil the following criteria:
pick up every true alarm;
avoid false alarms;
be specific and pick up hydrogen fire signals among various ones that become even more
numerous when detector sensitivity is increased;
a limited response time especially if it triggers a safety action.
Hydrogen fires tend to emit radiation over a broad range of wavelengths and are not characterised by
extreme peaks for particular frequencies. Hydrogen fire detectors can also rely on UV and IR light
detection. Besides the radiation itself, hydrogen flames can be indirectly visible by their strong heat
39
effect and turbulence, so called “heat ripples” of the surrounding atmosphere. Optical flame detectors
detect specific spectral radiation emitted during the combustion process by the various chemical
species (ions, radicals, molecules) that are either intermediates or final products of combustion.
Chemical species emit radiation at wavelengths characteristic to the particular species.
The hydroxyl radical (OH) and water (H2O) are the main emitting chemical species in the hydrogen
combustion process. These species emit radiation at specific spectral bands, according to their
electronic structure and the typical energy (translation, vibration, rotation) of the process.
OH (being an active intermediate radical with an available free electron) emits strongly in the
UV spectral band at the 0.306 and 0.282 μm peak and additional weaker emission peaks at
0.180 - 0.240 μm. It also emits infrared energy in the near IR band (vibration and rotation of
the molecule) with several peaks within the 1-3 μm spectral band.
H2O emits mainly in the near IR band (vibration and rotation) with strong peaks at 2.7; 1.9 and
1.4 μm, ranging from the highest to the lowest intensity.
These detection techniques assume that no interfering shield is placed between the flame and the UV
/ IR detector. Though optical techniques are available to pick up these various wavelengths, the main
challenge consists in discriminating hydrogen flame emitted signals with other potential sources that
emit similar signals in frequency and intensity.
UV detectors
UV systems are favoured to IR because they are extremely sensitive. In addition, the probability of
encountering an interfering signal is lower as long as UV detectors are shaded from sun light. Their
drawbacks are the cost and their reduced efficiency with liquid hydrogen flames as fog blocks UV rays.
The same remark applies whenever fog is present. False alarms can be released by random UV sources
such as lightening or arc welding. The ability of the detector to discriminate sunlight induced UV
radiation from hydrogen flames to avoid false alarms is the main challenge. Various techniques can be
applied:
The use of a filter to cut any wavelength above 0.29 μm to keep those wavelengths
attributable only to a hydrogen fire accident. Indeed, even on a sunny day, the atmosphere
filters sunray wavelengths below the proposed threshold of 0.29 μm. As a drawback, this
solution also cuts down nearly 2/3 of the UV band and therefore decreases the detector
accuracy.
The use of two concomitant cells that watch the same zone. One of the cells mostly analyses
the visible spectrum where the sunlight signal is predominant in comparison with hydrogen
flame emitted signal whereas the other one focuses on the UV band. The UV signal from the
UV cell is only taken into account if it diverges from the signal from the concomitant cell.
The flickering behaviour of a flame can also be taken into account. In that case, the modulated
part of the UV signal would be looked at. This technique may not be compatible with a fast
response need.
Finally, if parasitic signals are known to be minor, a positive signal may be assumed whenever
a given threshold is reached.
IR detectors
It has been mentioned how fog may hinder UV transmission to the sensor cell. IR detectors are not
sensitive to these issues. Besides, hydrogen flames emit significant IR to use them for hydrogen flame
40
detection. The main challenge remains the same as before that is to say to discriminate IR related to
hydrogen fire from those of the sun, any light sources or any hot materials. IR sources powered with
alternative electric currents can be filtered due to their own 100 Hz modulated signal. However,
neither hot bodies nor sunlight display a modulated signal that can be picked up and filtered.
The solution consists in focussing on the 1.7 μm wavelength that corresponds to a peak emission of
steam.
Thermal detectors
Thermal detectors, e.g. temperature sensors, detect the heat of the flame. Thermal detectors work as
rate-of-temperature-rise or overheat devices to pick up radiative, convective or conductive heat.
These reliable detectors of various types are suitable hydrogen fire detection means as long as they
are located very near where the fire breaks out. Such detectors need to be located very close to or at
the site of a fire and are not specific to hydrogen flames.
Imaging systems
Imaging systems mainly are available in the thermal IR region and do not provide continuous
monitoring with alarm capability. A trained operator is required to interpret whether the image being
viewed is a flame. UV imaging systems require special optics and are very expensive.
Other common fire detectors type like those with ionising cells are not appropriate to detect hydrogen
fires.
Fires of FC vehicles
Fuel Cell Vehicles (FCVs) are one of the main fast developing applications of FCH technologies. Similar
to a battery-electric car, a fuel cell car does not have the internal combustion engine. Fuel cells convert
the energy stored in chemical form directly into electrical energy that powers the cars. Worldwide,
several hundred FCV prototypes have been developed, and small fleets of fuel cell cars are being used
by companies and government agencies. These include the Mercedes-Benz 'F-Cell' cars based on the
A-Class car (in Berlin) and the Honda FCX Clarity (in California). One of the first FCVs sold commercially
is Toyota Mirai.
According to fire statistics in Great Britain [43], in the UK, 28,800 road vehicle fires were registered in
2011-2012. For comparison, in USA 172,500 automobile fires occurred in the same period. Different
types of vehicles were affected: motor cars, heavy goods vehicles, light goods vehicles, public
transport vehicles etc. The majority (65 %) of fires occurred in cars, 10 % were in vans, 4 % were in
lorries and 2 % in buses or mini-buses [43]. Fire causes can be accidental, deliberate or unknown. The
majority of deliberate fires (43 %) involved road vehicles: 13,900 fires. The number of fatalities in road
vehicle fires in 2011-12 was 37 [43].
During period from 2000 to 2006, 20 catastrophic CNG tank failures were documented, 11 of them
have been attributed to vehicle fires [44]. Of these 11 incidents, the evidence suggests that the
majority of the PRDs failed to activate (in case of a localized fire). “Testing has shown that all fuel tanks
(both CNG and hydrogen) regardless of working pressure are highly susceptible to rapid degradation
due to localized fires” [44]. This means that catastrophic failure cannot be ruled out of the risk
assessment [41]. Therefore, due to more severe consequences, the risk is higher for FCVs compared
to conventional cars.
41
Hazards and associated risks for FCVs should be understood and interpreted in a professional way,
with the full comprehension of consequences by all stakeholders, starting from FC system designers
through regulators to users. The first comparison of the “severity” of a hydrogen and gasoline (petrol)
fuel leaks and ignitions was performed by Swain [45]. Figure 27 shows the snapshots of hydrogen jet
fire and gasoline fire at 3 s (left) and 60 s (right) after a car fire initiation.
Figure 27. Hydrogen jet fire and gasoline fire: 3 s (left) and 60 s (right) after a car fire initiation [45].
The scenario with a hydrogen-powered car presented in Figure 27 is rare. (Please note in FCV vehicles
the release of hydrogen will not be oriented vertically upward.) It can be realised at a false self-
initiation of a pressure relief device (PRD). Indeed, a release of hydrogen through the PRD from the
on-board storage would be in majority of cases initiated by an external fire. A scenario with the
external fire drastically changes hazards and associated risks compared to the situation shown in
Figure 27.
Figures 28 and 29 demonstrate the results of a study on hydrogen-powered cars fire performed in
Japan [46]. The FCV was equipped with a thermal pressure relief device (TPRD) with a vent pipe
internal diameter of 4.2 mm. In a test shown in Figure 28 the compressed hydrogen tank was installed
exactly at the position of the removed gasoline tank. By this reason, there was no chance to install a
larger storage vessel and a small tank of 36 L at pressure 70 MPa was used. The fire spread from a
gasoline vehicle to FCV was investigated to address scenarios when different types of vehicles are
catching fire in car collision or natural disaster like earthquake. The experiment revealed that when
the TPRD of FCV’s storage tank is activated by gasoline fire a fireball of more than 10 m diameter is
formed (Figure 28, right).
Figure 28. A FCV gasoline pool fire test: left – gasoline fire just before initiation of TPRD, right – 1
second after TPRD initiation [46].
42
In another test of Tamura et al. [46] two vehicles were parked approximately 0.85 m apart and the
spread of fire from FCV to the gasoline vehicle was investigated. Figure 29 shows two vehicles after
the TPRD initiation in the FCV. It can be concluded that self-evacuation from the car or safeguarding
by First Responders with such design of hydrogen release system is impossible and car manufacturers
yet have to address this customer safety issue.
Figure 29. The HFCV with initiated TPRD (on the left) and the gasoline car (on the right) [46].
In the test conditions the cause of fire spread from the FCV to the adjacent gasoline vehicle is the
flame spreading from the interior and exterior fittings of the FCV but not the hydrogen flame from the
TPRD (it is worth noting that the small storage tank of only 36 litres with a shorter hydrogen release
time was used in the study by Tamura et al. [46] instead of a larger tank that is needed to provide
competitive driving range). The authors concluded that in car carrier ships and other similar situations
with closely parked FCVs, the test results point to the possibilities of a fire in an FCV to activate its
TPRD and thereby to generate hydrogen flames which in turn may cause the under floor TPRD
activation in adjoining FCV.
To minimize the damage by FCV fire authors of [46] suggested that it is important to early detect and
extinguish fire before the TPRD activation. It is known that hydrogen fire is difficult if not possible to
extinguish in many practical situations. Hopefully, car manufacturers will develop appropriate safety
engineering solutions, including reduction of flame length from hydrogen-powered vehicle in a
mishap, thus excluding the possible “domino” effect in accident development and assisting first
responders to control such fires and successfully perform rescue operations. The experiments carried
out by Tamura et al. have clearly demonstrated that FCV’s fire consequences can be very “challenging”
both from life, safety and property loss points of view [46].
As it was mentioned earlier, compressed gaseous hydrogen is currently the mainstream technology
for on-board hydrogen storage. The pressure for on-board storage varies from 35 to 70 MPa. Type III
tanks (with aluminium liner) and type IV tanks (with polymeric liner) are normally used. Unfortunately,
the fire resistance of these tanks is low. For example, Stephenson [47] have reported the time to
catastrophic failure in the range from 3.5 to 6.5 minutes. Current “solution” to prevent the
catastrophic of failure of these tanks in fire conditions is to release hydrogen quickly, through a TPRD
with an orifice of a comparatively large diameter (up to about 5 mm) before the failure. However, this
“solution” is unacceptable, even in the open atmosphere, due to the long flames, preventing safe
evacuation and rescue operations (Figure 30). Additionally, it creates a serious problem for life safety
43
and property protection when FCV is located in a confined space like garages, tunnels or car parks
[21].
Figure 30. Hydrogen jet flame from a PRD of an FCV oriented upwards (left – back view; right – side
view) [48].
The fire, shown in Figure 30, was initiated on the ashtray of the instrumentation panel [48]. The PRD
was directed upwards and activated 14 min 36 s after the fire initiation (upward scenario). Tested FCV
was equipped with two 34 L capacity cylinders at 35 MPa each and PRD diameter of 5 mm (to allow
blow-down on hydrogen in 5 min before the catastrophic rupture).
The scenario with a downward hydrogen release from a PRD is represented in Figure 31. The PRD was
activated, in this case, at 16 min 16 s after fire initiation [48].
Figure 31. Hydrogen jet flame from a PRD of an FCV oriented downwards (left – car back view; right
– car side view) [48].
Figures 30 and 31 demonstrate that current design of TPRD in case of hydrogen release and jet fire
does not allow self-evacuation of car driver and passengers, prohibits intervention of first responders
and create hazards for public The release of hydrogen from a TPRD can be considered as a typical
accident scenario. When the temperature reaches more than 110 oC, the TPRD activates and hydrogen
is released. TPRDs are commonly located on storage tanks, underneath of FCVs. The release is
orientated vertically downwards and the hydrogen flame will impinge on the ground. An ignited
release from a TPRD is most likely to occur in an event of a car fire, independent of whether the car is
parked or driven on a road. The hazards associated with this scenario depend on the ignition time. In
the case of immediate ignition, the impinging hydrogen jet flame (under the car) will spread outwards
and create a high temperature fire environment, which is hazardous to people and property. Without
immediate ignition, the released hydrogen will form a flammable cloud that has a potential to result
in a delayed ignition.
44
In the most recent study at Ulster the deterministic separation distances for ignited releases in the
open atmosphere are evaluated [49]. For ignited releases, three temperature limits were adopted as
harm criteria for different vulnerable targets. For the general public, a temperature of 70 °C was taken
as an acceptance criterion for no harm. For the First Responders without thermal protective clothing,
a temperature of 115 °C was assumed to be the pain limit. For First Responders with thermal
protective clothing, it was conservatively assumed that they should not work in an environment where
the temperature is higher than 260 °C, as the bunker gear is designed not to ignite, melt, drip, or
separate when exposed to such temperatures for five minutes [50].
In real-world conditions, a hydrogen release from a high pressure tank is not a steady-state one but a
blow-down process, with pressure decaying in the reservoir until the tank is empty. The notional
nozzle model mentioned above can be applied to simulate pressure dynamics in the hydrogen storage
tank during an under-expanded jet release. Figure 32 shows pressure and mass dynamics during
blowdown from two hydrogen storage tanks: 171 l volume, 35 MPa storage pressure (Figure 32 left),
and 101 l, 70 MPa storage pressure (Figure 32 right). Both tanks contain initially the same amount of
hydrogen - 4.05 kg, and have the same TPRD orifice diameter 4.2 mm. As it follows from Figure 32 the
total blow-down time even for 35 MPa storage pressure is less than 110 s, and the transition from an
under-expanded jet to an expanded one occurs at 85 s. For the release from 70 MPa storage tank the
total blow-down time is less than 75 s, with the transition from an under-expanded jet to an expanded
jet occurring at about 58 s [49].
Figure 32. Pressure and mass dynamics in a hydrogen storage tank during blow-down through 4.2
mm TPRD orifice: 171 l tank, initial pressure 35 MPa (left), and 101 l tank, initial pressure 70 MPa
(right) [49].
Figure 33 shows a snapshot of the largest flame envelope resulting from hydrogen release via a
4.2 mm orifice TPRD installed under a car and directed downwards. The flame envelope was obtained
in CFD simulations and visualised using temperature iso-surface T=1,300 °C. The longest flame tip
location is about 5.2 m and 8.4 m for releases from storage with pressures 35 MPa and 70 MPa
respectively. The flame length for the 70 MPa release increases more than 60% compared with that
of the 35 MPa release. For both cases the largest flame envelopes near the ground occur at about 1.3
s after the opening of the TPRD. Afterwards, the flame will shrink and the separation distances will
decrease. Figure 33 also shows the longest flame propagation for unobstructed free jet fires calculated
using analytical correlation (6) (also shown in Figure 12). Realistic release from under-car TPRD results
in a significant reduction of the flame envelope - more than 50% and nearly 40% for releases from
storage with pressure 35 MPa and 70 MPa respectively [49].
45
Flame length of free jet: 10.9 m Flame length of free jet: 13.8 m
35 MPa 70 MPa
Figure 33. Side view of the largest hydrogen flame envelope (iso-surface of temperature T=1,300 °C)
[49].
Figure 34 shows temperature iso-surface T=260 °C corresponding to the safety threshold for operation
of First Responders in thermal protective clothes. The longest hazard distance is about 5.8 m and 9.2
m for releases from storage with pressures 35 MPa and 70 MPa respectively. The hazard distance for
the 70 MPa release increases more than 58% compared to that of 35 MPa release. For both cases the
largest 260 °C temperature envelopes near the ground occur at about 1.5 s after the opening of the
TPRD. Afterwards the envelopes will shrink and the separation distances will decrease [49].
35 MPa 70 MPa
Figure 34. Side view of the largest envelop for safe operation of First Responders in protecting
clothing (iso-surface of temperature T=260 °C) cut off at 2 m height [49].
35 MPa 70 MPa
Figure 35. Side view of the largest envelop for safe operation of First Responders without protecting
clothing (iso-surface of temperature T=115 °C) cut-off at 2 m height [49].
It can be seen from Figure 36 that for the general public, the longest separation distance is about 6 m
and 9.5 m, for the 35 MPa and 70 MPa releases, respectively. The separation distance for the 70 MPa
release increases more than 58% compared with that of the 35 MPa release. For both cases the largest
70 °C temperature envelopes near the ground occur at about 1.5 seconds after the opening of the
TPRD. Afterwards, the envelopes will shrink and the hazard distances will decrease [49].
35 MPa 70 MPa
Figure 36. Side view of the largest envelop for public safety (iso-surface of temperature T=70 °C),
cut-off at 2 m height [49].
Shielding or barriers
The main idea here is to reduce the rate of heat transfer to the potential targets in the vicinity of a
hydrogen jet fire. The effect of barriers and walls was discussed earlier in this lecture. Flame shields
are specifically designed to reduce the incident radiant heat flux by preventing direct flame
47
The general rule applied for the selection of the flow restrictor is as follows:
(16)
Recently, Yamazaki and Tamura [52] developed a simple method of verifying TPRD activation at post-
fire accident sites. The verification technique is based on the measurement of hydrogen concentration
at the TPRD gas release port, using a hydrogen densitometer. It was found that with the aid of a
contact burning hydrogen densitometer, hydrogen concentrations exceeding 3,000 ppm could be
measured continuously for about a month for Type III tanks and for about 24 hours for Type IV
cylinders, even under the hostile test conditions of a vehicle burn-down fire accident [52].
Flame arrestors are safety devices that allow flow of combustible gases while preventing ignition. The
flame arrestor prevents the flame from transferring to a different area of a device by cooling or
quenching a flame front or dampening a combustion wave. It is designed to absorb and dissipate the
heat of a flame for specific operating and flow conditions.
A flame arrester, or flame trap, is a device used to prevent the passage of a flame along a pipe or duct.
A flame arrester is generally an assembly of narrow passages, through which gas or vapour can flow,
but which are too small to allow the passage of flame. Flame arresters are generally distinguished as
end-of-line or in-line arresters [8].
The size of the aperture through the arrester is determined by the quenching distance of the
flammable mixture. The diameter of the aperture of an arrester should be smaller than the quenching
diameter by at least 50%. The performance of an arrester is affected by the temperature. The
quenching distance increases as the temperature increases. It is approx. inversely proportional to the
square root of the absolute temperature. Hydraulic or liquid seal, arresters contain a liquid, usually
water, which serves to break up the gas stream into bubbles and so prevents passage of the flame [8].
Velocity flame stoppers are arresters used in end-of-line applications. Their function is to prevent a
flame passing from downstream to the upstream side. The principle of their operation is to assure that
the velocity of the upstream gas passing through the arrester is sufficiently high to prevent a flame
propagating through the arrester from the downstream side [8].
Fire protection coatings (intumescent materials) providing thermal insulation can be a part of the
fire protection strategy of compressed gaseous hydrogen vessels [21].
Summary
Present lecture is focused in ignited hydrogen releases (microflames, jet fires, fireballs) and has the
high importance for First Responders. A useful terminology has been introduced at the start. Then a
classification of different types of hydrogen fires was provided. The hydrogen jet fires (most typical
for compressed gaseous storage) are discussed in detail. A significant part on the lecture is devoted to
the evaluation of flame length and separation distances. Harm criteria for hydrogen technologies have
been described. The effect of different factors on hydrogen flame length was discussed. The radiative
heat fluxes and the flame lengths for jet fires of hydrogen, CNG and LPG was presented in this lecture.
An overview of detection, mitigation techniques of hydrogen fires has been given. This information
will be very useful not only for virtual reality and operational exercises but in decision making at a
scene of an accident involving fires.
References
1. Molkov, V (2012). Fundamentals of hydrogen safety engineering, Part I and Part II. Available
from: www.bookboon.com, free download e-book.
2. Cheng, TS, Chiou, CR (1998). Experimental investigation of the characteristics of turbulent
hydrogen jet flames. Combustion Science and Technology. Col. 136, p. 81-84.
3. Dorofeev, SB (2009). Evaluation of hydrogen explosion hazards: phenomenology and potential
flame acceleration and DDT. 4th European Summer School on Hydrogen Safety.
4. Birch, AD, Brown, MG, Dodson, MG, Swaffield, F (1984). The structure and concentration
decay of high pressure jets of natural gas. Combustion Science and Technology. Vol. 36, p.
249-261.
5. NFPA (2009). Compressed Natural Gas (CNG) Vehicular Fuel Systems Code, 52.
51
6. LaChance, J, Tchouvelev, A and Engebo, A (2011). Development of uniform harm criteria for
use in quantitative risk analysis of the hydrogen infrastructure. International Journal of
Hydrogen Energy. Vol. 36 p. 2381-2388.
7. Saffers, JB (2010). Principles of hydrogen safety engineering. PhD thesis. University of Ulster.
8. BRHS, Biannual Report on Hydrogen Safety (2007). Network of Excellence HySAFE. Available
from: http://www.hysafe.org/BRHS [accessed on 12.02.15].
9. Kanury, AM (1975). Introduction to combustion phenomena: (for fire, incineration, pollution
and energy applications). New York; London: Gordon and Breach.
10. Teodorczyk, A (2006). Fast deflagration, deflagration to detonation transition (DDT) and direct
detonation of hydrogen-air mixtures. Teaching Materials of European Summer School on
Hydrogen Safety, 2006.
11. Kalghatgi, GT (1981). Blow-out stability of gaseous jet diffusion flames. Part I: in still air.
Combustion Science and Technology. Vol. 26(5), pp. 233-239.
12. Matta, LM, Neumeier, Y, Lemon, B and Zinn, BT (2002). Characteristics of microscale diffusion
flames. Proceedings of the Combustion Institute, vol. 29, pp. 933-938.
13. Cheng, TS, Chen, CP, Chen, CS, Li, YH, Wu, CY and Chao, YC (2006). Characteristics of microjet
methane diffusion flames. Combustion Theory and Modelling, 10, pp. 861-881.
14. Butler, MS, Moran, CW, Suderland, PB and Axelbaum, RL (2009). Limits for hydrogen leaks that
can support stable flames. International Journal of Hydrogen Energy. Vol. 34. pp. 5174-5182.
15. Sunderland, PB (2010). Hydrogen microflame hazards, Proceedings of the 8th International
Short Course and Advanced Research Workshop in the series “Progress in Hydrogen Safety”,
Hydrogen and Fuel Cell Early Market Applications, 11 - 15 October 2010, University of Ulster,
Belfast.
16. Hawthorne, WR, Weddell, DS and Hottel HC (1949). Mixing and combustion in turbulent gas
jets, Third International Symposium on Combustion, Flame and Explosion Phenomena, pp.
266-288, Baltimore, USA.
17. Hottel, HC and Hawthorne, WR (1949). Diffusion in laminar flame jets. Proceedings of the
Combustion Institute. Vol. 3, pp. 254-266.
18. Brennan, S, Makarov, D and Molkov, V (2009). LES of high pressure hydrogen jet fire.
Journal of Loss Prevention in the Process Industries. Vol. 22 (3), pp.353-359.
19. Baev, VK and Yasakov, VA (1974). Effect of lifting forces on the length of diffusion flames.
Combustion, Explosion and Shock Waves. Vol. 10, pp. 752-758.
20. Shevyakov, GG and Komov, VF (1977). Effect of non-combustible admixtures on length of an
axisymmetric on-port turbulent diffusion flame. Combustion, Explosion and Shock Waves.
Vol. 13, pp. 563-566.
21. HyFacts Project. Chapter F. Hydrogen fires. Available from:
http://hyfacts.eu/category/education-training/ [accessed on 04.01.16].
22. Kalghatgi, GT (1984). Lift-off heights and visible lengths of vertical turbulent jet diffusion
flames in still air. Combustion Science and Technology. Vol. 41, pp. 17-29.
23. Schefer, RW, Houf, WG, Bourne, B and Colton, J (2006). Spatial and radiative properties of an
open-flame hydrogen plume. International Journal of Hydrogen Energy. Vol. 31, pp. 1332-
1340.
24. Schefer, RW, Houf, WG, Williams, TC, Bourne, B and Colton, J (2007). Characterization of high
pressure, underexpanded hydrogen-jet flames. International Journal of Hydrogen Energy. Vol.
32, pp. 2081-2093.
52
25. Molkov, V and Saffers, J-B (2013). Hydrogen jet flames. International Journal of Hydrogen
Energy. Vol. 38, pp. 8141-8158.
26. Proust, C, Jamois, D and Studer, E (2009). High pressure hydrogen fires. Proceedings of the
Third International Conference on Hydrogen Safety. 16-18 September 2009, Ajaccio, France,
paper 214.
27. LaChance, J, Tchouvelev, A and Engebo, A (2011). Development of uniform harm criteria for
use in quantitative risk analysis of the hydrogen infrastructure. International Journal of
Hydrogen Energy. Vol. 36 pp. 2381-2388.
28. EIGA, European Industrial Gases Association (2007). Determination of safety distances. IGC
Doc 75/07/E.
29. BSI British Standards Institution (2004). Published Document PD 7974-6:2004. The application
of fire safety engineering principles to fire safety design of buildings - Part 6: Human factors:
Life safety strategies - Occupants evacuation, behaviour and condition (Sub-system 6).
30. DNV Technica (2001). Human resistance against thermal effects, explosion effects, toxic
effects and obscuration of vision. DNV Technica, Scandpower A/S, Det Norske Veritas, Oslo,
Norway.
31. BSI British Standards Institution (1997). British Standard 7899:1997. Code of practice for
assessment of hazard to life and health from fire. Guidance on methods for the quantification
of hazards to life and health and estimation of time to incapacitation and death in fires.
32. Barlow, RS and Carter, CD (1996.) Relationships among Nitric Oxide, Temperature, and
Mixture Fraction in Hydrogen Jet Flames. Combustion and Flame. Vol. 104, pp. 288-299.
33. Imamura, T, Hamada, S, Mogi, T, Wada, Y, Horiguchi, S, Miyake, A and Ogawa, T (2008).
Experimental investigation on the thermal properties of hydrogen jet flame and hot currents
in the downstream region. International Journal of Hydrogen Energy. Vol. 33, pp. 3426-3435.
34. Royle, M and Willoughby, DB (2009). Consequences of catastrophic releases of ignited and
unignited hydrogen jet releases. 3rd International Conference on Hydrogen Safety, Ajaccio,
France.
35. Mogi, T and Horiguchi, S (2009). Experimental study on the hazards of high-pressure hydrogen
jet diffusion flames. Journal of Loss Prevention in the Process Industries. Vol. 22, pp. 45-51.
36. Makarov, D and Molkov, V. (2013). Plane hydrogen jets. International Journal of Hydrogen
Energy. Vol. 38 (19), pp. 8068–8083.
37. Shevyakov, GG and Savelieva, NI (2004). Dispersion and combustion of hydrogen jet in the
open atmosphere. International Scientific Journal for Alternative Energy and Ecology. Vol.
1(9), pp. 23-27 (in Russian).
38. HYPER (2008) FP6 STREP project “Installation Permitting Guidance for Hydrogen and Fuel Cells
Stationary Applications”. Deliverable 4.3 Releases, Fires and Explosions. WP4 Final Report.
39. Houf, WG and Schefer, RW (2007). Predicting radiative heat fluxes and flammability envelopes
from unintended releases of hydrogen. International Journal of Hydrogen Energy. Vol. 32, pp.
136-151.
40. Molina, A, Schefer, RW and Houf, WG (2007). Radiative fraction and optical thickness in large-
scale hydrogen-jet fires. Proceedings of the Combustion Institute. Vol. 31, pp. 2565-2572.
41. Case for safety. Relative frequency of failure modes. Available from:
http://h2safe.net/case_safety.html [accessed on 14.01.16].
53
42. Zalosh, R (2007). Blast waves and fireballs generated by hydrogen fuel tank rupture during
fire exposure. Proceedings on the 5th Seminar on Fire and Explosion Hazard, Edinburgh, UK,
23-27 April 2007, pp. 2154-2161.
43. Fire statistics, Great Britain, 2011-2012. Department of Communities and Local Government.
44. Gambone, LR and Wong, JY (2007). Fire protection strategy for compressed hydrogen-
powered vehicles. 2nd International Conference on Hydrogen Safety, San Sebastian, Spain, 11-
13 September, 2007.
45. Swain, MR (2001). Fuel leak simulation. Available from:
http://evworld.com/library/swainh2vgasVideo.pdf [Accessed 24.12.15].
46. Tamura, Y, Takabayashi, M, Takeuchi, M and Mitsuishi, H (2011). The spread of fire from
adjoining vehicles to a hydrogen fuel cell vehicle. In: Proceedings of the Fourth International
Conference on Hydrogen Safety, 12-14 September 2011, San Francisco, USA.
47. Stephenson, RR (2005) Fire safety of hydrogen-fuelled vehicles: system-level bonfire test.
Proceedings of the 1st International Conference on Hydrogen Safety, Pisa, Italy, 2005. Available
from: http://conference.ing.unipi.it/ichs2005. [Accessed 15.04.15].
48. Watanabe, S, Tamura, Y, Suzuki, J (2007). The new facility for hydrogen and fuel cell vehicle
safety evaluation. International Journal of Hydrogen Energy. Vol. 32 (13), pp. 2154-2161.
49. Li, Z, Makarov, D, Keenan, J, Molkov, V (2015). CFD study of the unignited and ignited hydrogen
releases from TPRD under a fuel cell car. 6th International Conference on Hydrogen Safety, 19-
21 October 2015, Yokohama, Japan.
50. NFPA 1971, Standard on Protective Ensembles for Structural Fire Fighting and Proximity Fire
Fighting, 2007 Edition. National Fire Prevention Association, 2007, Boston, Massachusetts.
51. HyIndoor Deliverable D4.2 – First intermediate report on analytical, numerical and
experimental studies (2014).
52. Yamazaki, K and Tamura, Y (2015). Study of a Post-fire Verification Method for the Activation
Status of Hydrogen Cylinder Pressure Relief Devices. 6th International Conference on Hydrogen
Safety, 19-21 October 2015, Yokohama, Japan.
53. US DoE, US Department of Energy (2008). Hydrogen safety training for first responders.
Available from: http://hydrogen.pnl.gov/FirstResponders/ [accessed on 13.05.14].