American Standard 4tec Installation Instructions
American Standard 4tec Installation Instructions
JOIStS JOISt
ONE INCH DUCT SPACERS
HEADER
B
fROnt Of
UnIt
A
UnIt
SUBBASE
APPROX. 3/4" FLANGES ON FIELD
FABRICATED DUCT OR PLENUM flOOR
HEADER
JOISt
JOIStS
nAIlS nAIlS
18-GE08D1-9 3
Installer’s Guide
! CAUtIOn
▲
When installing the narrow coil baffle, make sure to
align the baffle up with the holes so not to puncture
the coil tubing.
c. Position unit on Pedestal or other suitable foun-
SCREWS 5-8 dation. If Pedestal is not used, a frame strong
LOCATED ON
LEFT SIDE enough to support the total weight must be pro-
vided. Provide a minimum height of 14 inches
for proper unrestricted airflow.
24
1
3
18-GE08D1-9 5
Installer’s Guide
k. If a return duct is connected to the air handler, The factory installed filter should then
it must be the same dimensions as the return be removed from the unit. Remove the fac-
opening shown in the outline drawing. tory installed baffle assembly from the apex of
l. On units with sheet metal returns: Return ple- the coil by using a 5/16" nutdriver to remove
num should be flanged. Sheetmetal screws must the hex head screws. Replace this baffle with
be 1/2" in length or shorter. the factory supplied narrow coil baffle using
the screws removed previously. See Figure 5.
m. No sheetmetal screws may be used to attach
return ductwork on the side of the unit.
! CAUtIOn
▲
n. Openings where field wiring enters the cab-
inet must be completely sealed. Location of When installing the narrow coil baffle, make sure to
power entry is shown on the outline drawing. align the baffle up with the holes so not to puncture
Use 2.5" clear stickers to seal all unused electri- the coil tubing.
cal knockouts. See Figure 11. c. The coil is then inserted back into the cabinet on
o. After ductwork connections are made, seal air- the opposite side coil channel supports. The unit
tight and per local codes. is now horizontal left with front access. Do not
HORIZONTAL LEFT reattach coil support tab.
a. To convert the unit to horizontal left, front ac- d . If the unit is suspended, it must be supported
cess, slide the coil out on the coil channel sup- from the bottom near both ends as well as the
ports and rotate the complete coil 180 degrees. middle to prevent sagging. The service access
must remain unobstructed. If the unit is sup-
b. For maximum efficiency and Customer ease
ported along the length of the front and back
of filter maintenance, it is recommended that a
with rails, the air handler only needs to be sus-
properly sized remote filter grille be installed
pended at both ends. See Figure 10.
for horizontal applications. Airflow should not
exceed the face velocity of the filter being used.
SCREWS TO
REMOVE COIL
7/8" GASKET
X
7/8" GASKET
X
1/2" GASKET SCREWS TO
INSIDE SURFACE REMOVE COIL
OF BAFFLE
SECT. X-X
(TYP. BOTH SIDES)
WATER
BLOW-OFF WATER
BAFFLES DIVERTER
BAFFLES
ATTACH WITH (5TON ONLY)
2 SCREWS
EACH SIDE
FILL WITH SEALANT
6 18-GE08D1-9
Installer’s Guide
k. Openings where field wiring enters the
0 cabinet must be completely sealed. Location
of power entry is shown on the outline drawing.
Use 2.5" clear stickers provided to seal all un-
used electrical knockouts. See Figure 11.
l. After ductwork connections are made, seal air-
tight and per Local codes.
Horizontal Right
Rail a. For maximum efficiency and Customer ease
of filter maintenance, it is recommended that a
properly sized remote filter grille be installed
for horizontal applications. Airflow should not
exceed the face velocity of the filter being used.
The factory installed filter should then be
removed from the unit.
b. Unit is shipped from the factory in the upflow or
horizontal right configuration. Unit conversion
is not required.
c. If the unit is suspended, it must be supported
from the bottom near both ends as well as the
middle to prevent sagging. The service access
must remain unobstructed. If the unit is sup-
ported along the length of the front and back
with rails, the air handler only needs to be sus-
pended at both ends. See Figure 10.
q
If the unit is not suspended it must be support-
ed as mentioned above and isolated carefully
to prevent sound transmission. Vibration isola-
tors (purchased locally) must be placed under
the unit.
e. It is always recommended that an auxiliary
drain pan be installed under a horizontal air
handler (See Condensate Piping) to prevent
possible damage to ceilings.
f. Isolate the auxiliary drain pan from the unit or
from the structure.
g. Connect the auxiliary drain line to a separate
drain line (no trap is needed in this line) and
terminate according to National and Local
codes.
h. If a return duct is connected to the air handler,
eet
it must be the same dimensions as the return Sh
er
opening shown in the outline drawing. tick
tS
ou
i. On units with sheetmetal returns: Return n ock
plenum should be flanged. Sheetmetal screws ical K
ctr
must be 1/2" in length or shorter. Ele
j. No sheetmetal screws may be used to attach
return ductwork on the side of the unit.
18-GE08D1-9 7
Installer’s Guide
Convertible duct flanges are provided on the discharge
w Flange Attachment opening to provide a “flush fit” for 3/4" or 1‑1/2" duct
board applications. See the Outline drawing for sizes
of the duct connections. After the duct is secured, seal
around the supply duct to prevent air leakage.
NOTE: No sheetmetal screws may be used to attach re-
turn ductwork on the side.
8 18-GE08D1-9
Installer’s Guide
3. Run refrigerant tubing into the stub sockets of in- The use of Field fabricated or manufactured traps
door unit coil. Refrigerant line openings must as shown in Figures 15 & 16 is acceptable. The
be completely sealed. manufactured trap shown in Figure 15 allows for a
4. Braze and evacuate according to indoor and out- float switch option to be added. Refer to the manu-
door installation instructions. facturer’s data and instructions for details.
2. The trap must be located within 4 feet of the air
5. Seal around refrigerant lines. handler drain outlet connection.
PAINTED AREAS OF UNIT MUST BE SHIELDED 3. It is recommended that a clean-out tee or cross be
DURING BRAZING. installed in the primary drain line for future main-
tenance (See Figures 15 & 16)
BRAZE SHIELD
e
r
3/4" NPT
Secondary
drain con-
nection
18-GE08D1-9 9
Installer’s Guide
2. The selection of wire and fuse sizes should be made
t MANUFACTURED TRAPS according to the Minimum Branch Circuit Ampac-
ity and the Maximum Overcurrent Device listed on
the unit nameplate.
3. Field wiring diagrams for electric heaters and unit
accessories are shipped with the accessory.
4. Wiring must conform to National and Local codes.
2" MINIMUM Ground unit per Local codes with good safety pro-
cedures.
If an electric heater is not installed, the Knockout
Plate provided in the Accessory Kit MUST be in-
stalled on the air handler and the conduit termi-
2" MINIMUM nated to it. The electrical connections are made
using the two power leads and ground wire con-
nections which are located near the discharge of
the blower. Openings where field wiring en-
EZT-105 ters the cabinet must be completely sealed.
Location of power entry is shown on the outline
drawing. Use 2.5" clear stickers to seal all unused
electrical knockouts.
y FIELD FABRICATED TRAP NOTE: If air handler is used with or without a heater,
the 7/8" electrical entry hole as well as any other cabi-
net penetrations must be sealed air tight.
CAP OR PLUG I. Control Wiring
1. Connect wiring between indoor unit, outdoor unit
and Comfort Control. The use of color-coded low-
voltage wires is recommended.
2" mIn.
2. A low voltage terminal board is provided for con-
trol wiring, and is located on the left side of the
cross brace in the center of the unit.
3. Field wiring diagrams are provided which show
2" mIn. the low voltage wiring hook-up for a single speed
cooling only system (with supplementary heaters)
and a heat pump system (with supplementary
heaters). Plug in type electrical connectors are
provided for use with supplementary heaters.
Close as possible
Trap must be within 4' IMPORTANT:
of air handler condensate When supplementary heaters are installed, inspect to
drain connection.
insure that all packaging material has been removed.
NOTE: Direct drive motors have bearings which are
! WARnInG permanently lubricated and under normal use lubrica-
ELECTRICAL SHOCK HAZARD tion is not recommended.
LOCK OUT UNIT DISCONNECT SWITCH IN OPEN PO-
SITION BEFORE SERVICING UNIT. FAILURE TO FOL-
LOW THIS WARNING COULD RESULT IN PROPERTY
DAMAGE, PERSONAL INJURY, OR DEATH.
10 18-GE08D1-9
Hook-up Diagrams
Installer’s Guide
18-GE08D1-9 11
Installer’s Guide
2/4TEC AIR HANDLERS WITH SINGLE SPEED COOLING UNIT, 1 STAGE HEAT
12 18-GE08D1-9
Installer’s Guide
2/4TEC AIR HANDLER WITH SINGLE SPEED COOLING UNIT, 2 STAGE HEAT
18-GE08D1-9 13
Installer’s Guide
Outline Drawing For 2/4TEC3F18-60B
14 18-GE08D1-9
Installer’s Guide
2/4TEC Air Handler DIMENSIONAL DATA
18-GE08D1-9 15
Installer’s Guide
J.Checkout Procedure The following warning complies with State of California law, Proposition 65.
1. Check the Air Handler operation and installation ▲WARnInG: this product contains
in accordance with these instructions below. fiberglass wool insulation! Fiberglass dust and ceramic
fibers are believed by the State of California to cause
cancer through inhalation. Glasswool fibers may also
2. “Operational Procedure” for the system instal- cause respiratory, skin, or eye irritation.
lation can be found in the outdoor unit installer PRECAUtIOnARY mEASURES
guide and will be compatible with this Air Han-
Avoid breathing fiberglass dust.
dler.
●
DAMAGE, PERSONAL INJURY, OR DEATH. Skin Contact - Wash affected areas gently with soap
and warm water after handling.
Checkout Procedures
After installation has been completed, it is recommended that the Air Handler be checked against the following
checklist.
1. Make sure power is “OFF” at power 6. Make sure secondary drain pan is installed....... [ ]
disconnect switch.................................................. [ ] 7. Check power supply for correct requirements
2. Check all field wiring for tight connections. See per unit nameplate............................................... [ ]
that grounding of unit is in accord with code..... [ ] 8. Check filters for proper size. Inform owner
3. Make sure unit suspension (if used) is secure of proper procedure for removal and
and that there are no tools or loose debris in, reinstallation........................................................ [ ]
around or on top of the unit................................. [ ] 9. Energize the system and carefully observe its
4. Check all duct outlets; they must be open and operation; make any necessary adjustment........ [ ]
unrestricted.......................................................... [ ] 10. Instruct owner, engineer (if possible) on proper
5. Check drain lines and be sure all joints are tight operating procedure and leave Use and Care
............................................................................... [ ] Manual with owner.............................................. [ ]
1. Be sure the disconnect switch is “OFF”, and safety label (if any) is attached........................................ [ ]
2. Check on field wiring for tight connections and grounding according to codes...................................... [ ]
3. Check circuit protection for proper size per nameplate specifications.................................................... [ ]
4. Check control box panel — in place and secured..................................................................................... [ ]
NOTE: OPERATION OF HEATERS MUST BE CHECKED DURING THE OPERATION CHECK OF THE TOTAL
SYSTEM.
Trane
6200 Troup Highway
Tyler, TX 75707
www.trane.com
The manufacturer has a policy of continuous product and product data improvement, and it reserves the right
For more information contact
to change design and specifications without notice.
your local dealer (distributor)