CV Technical Data OLTC HUAMING
CV Technical Data OLTC HUAMING
Contents
1. General----------------------------------------------------------------------------------------------------------------------------- 2
2. Main specifications-------------------------------------------------------------------------------------------------------------- 6
3. Special design-------------------------------------------------------------------------------------------------------------------- 11
4. Construction and installation-------------------------------------------------------------------------------------------------- 12
5. Accessories------------------------------------------------------------------------------------------------------------------------13
6. Appendix--------------------------------------------------------------------------------------------------------------------------- 20
Overall dimensions of CV 350 (with change-over selector) ---------------------------------------------------------- 21
Overall dimensions of CV 350 (without change-over selector) ------------------------------------------------------ 22
Overall dimensions of CV 350 (bridging connection) ------------------------------------------------------------------ 23
Overall dimensions of SV 500 (with change-over selector) ---------------------------------------------------------- 24
Overall dimensions of SV 500 (without change-over selector) ------------------------------------------------------ 25
Overall dimensions of CV I 700 (with change-over selector) ---------------------------------------------------------26
Overall dimensions of CV I 700 (without change-over selector) ---------------------------------------------------- 27
On-load tap changer type CV head (for mounting on standard tank cover) ------------------------------------- 28
On-load tap changer type CV head (for mounting on bell-type cover) ---------------------------------------------29
Sketch of connection flange of the transformer-------------------------------------------------------------------------- 30
Overall dimensions of CMA9 motor drive unit--------------------------------------------------------------------------- 31
CMA9 motor drive unit circuit diagram--------------------------------------------------------------------------------------32
Overall dimensions of CMA7 motor drive unit---------------------------------------------------------------------------- 33
CMA7 motor drive unit circuit diagram--------------------------------------------------------------------------------------34
Overall dimensions of SHM-1 motor drive unit--------------------------------------------------------------------------- 35
Overall dimensions of HMK7 controller-------------------------------------------------------------------------------------36
External connection diagram of SHM-1 motor drive unit and HMK7 controller---------------------------------- 36
Connection diagram of HMK7 controller and SHM-1 motor drive unit----------------------------------------------37
Overall dimensions of bevel gear unit of CV------------------------------------------------------------------------------ 38
Overall dimensions and installation of the protective relay------------------------------------------------------------ 39
Operating key for CV on-load tap changer insert------------------------------------------------------------------------ 40
Swiveling range of the CV on-load tap changer head gear unit, drive shaft left side--------------------------- 41
CV on-load tap changer horizontal drive shaft arrangement----------------------------------------------------------42
1
2/!Hfofsbm
2/2!!Dpotusvdujpo
Type CV on load tap changer is suitable to be used on oil immersed transformer. The design of the tap changer
contact system is of the rolling type dual resistance transition composite type construction. The OLTC comprising
either of a tap selector with or without reverser or coarse tap selector and a diverter switch, as a selector switch combining
the function of the tap selector and diverter switch in one device.
a, b: main arc contacts
al, bl.: transition arc contacts
R: transition resistors
A.B.: main contacts
: indicates the contact closed
!!!!It can be seen from the sequence that the load current
transits from one tap change contact to the adjacent one is
accomplished by the transition arc contact and the main
arc contact.
2/3!!Uif!dibsbdufsjtujd!boe!sbohf!pg!bqqmjdbujpo!pg!uif!cbtjd!wpmubhf!sfhvmbujpo!djsdvju!)Ubcmf!2*/
Designation circuit diagram main characteristic range of application
basic coil The basic coil is added linearly to the turns of the voltage Suitable for power
regulation coil. The range of regulation is not large. Percent transformer with the range of
regulating of voltage regulation is Ġ 3 ġ 2.5%, that is the range of regulation 15% and less.
linear winding regulation of 15%(max. 20%) and less can be utilized.
regulation This is because when the range of regulation is increased,
selecter the scope of increase of the impulse gradient of the voltage
switch regulation coil increases in even greater scale, when the
voltage is not high, optimum range of regulation can be
achieved.
single-pole
The basic coil can be connected in direct and reverse To b e u s e d o n p o w e r
change-over
manner to the turns of the voltage regulation coils, this transformer with wide
selector
is also called direct and reverse excitation voltage range of voltage regulation.
regulation. With the same voltage regulation coil, the But the best way is to use the
reversing range of regulation can be doubled. But with the least
selecter double pole voltage
voltage switch effective turns, the current passes through the entire coil, regulation circuit in the right
regulation the resistance loss will be large. Within the same range figure. This makes the
of voltage regulation, the impulse gradient on the voltage
single-pole
voltage regulation coil
regulation coil is low. The single phase voltage regulation
change-over always connected to the
circuit leads to a bias voltage between the voltage
selector regulation coil and the basic coil. basic coil.
coarse tap On the minimum tap turns position, the resistance loss is The insulation construction
selector relatively small. From the stand point of the insulation, is rather complex and is
coarse and
the construction of the coil is rather complex. seldom employed by
fine
ordinary transformers. Most
voltage
of them can be used on
regulation
selecter industrial transformers with
switch large range of voltage
regulation.
2
IN1/265/112
2/4!!PMUDt!jo!bvup.dpoofdufe!usbotgpsnfst
Designation circuit diagram Main characteristic rage of application
For the circuit shown in the left diagram, the range Frequently used in
of medium voltage regulation ļ15%. For the rest high voltage inter-
of the circuit, the scope of voltage regulation can connecting power
regulation be increased to 30%.The diagram on the right shows transformer.
through the voltage regulation is performed simultaneously
medium on the high and medium voltage side, the high
voltage coil voltage side has even larger scope of voltage
regulation, this time the current through the voltage
regulation coil and the on load tap changer is rather
small.
2/5!!Uisff!qibtf!wpmubhf!sfhvmbujpo!djsdvju-!jut!dibsbdufsjtujd!boe!tdpqf!pg!bqqmjdbujpo/
3
Delta When the voltage İ 60kV and the tap change current Delta connected 3
connected İ350A, one on load tap changer can be used. phase transformer
3-pole When the voltage is 110-220kV, 3 single phase
line-end on load tap changer must be used.
arrangement
Delta connected For voltages Um=123kV and higher this High voltage delta
arrangement is advantageous. connected power
2-pole , 1-pole
transformer.
line-end
arrangement
2/6!!Eftjhobujpo!pg!uif!ubq!dibohfs!npefm!ovncfs
DW!!ŕ!!ŕ!!ŕ!!0!!ŕ!!Ċ!!ŕ!!ŕ!!ŕ!!ŕ
Example CV Ʊ 350Y/72.5-10193W
Type CV on-load tap changer, 3 phases, maximum rated through current 350A, highest voltage for equipment 72.5kV,
Y connection,19 service positions, 3 mid-position, with reversing change-over selector.
highest voltage for the equipment: 40.5kV, 72.5kV.
number of contacts of tap changer: with 10, 12, 14 point of contacts in circuit.
number of service position: up to 19, 23 and 27 when change-over selector is provided.
mode of voltage regulation: divided to linear regulation, reversing regulation and coarse and fine regulation.
0-for linear regulation
W-for reversing regulation
G-for coarse and fine regulation
Mid-position: 1 and 3
4
IN1/265/112
2/7!!Cbtjd!dpoofdujpo!ejbhsbn
5
2. Main specifications
Note: 1) If the operating postion less than 10, the step voltage can reach between 1500V-2000V at reduced current
2) The max through current should decreased to 350A and 300A, when the switching capacity are 525KVA and 420KVA
6
IN1/265/112
3/3!!Sbufe!txjudijoh!dbqbdjujdt!)sbufe!tufq!wpmubhft!Vj-!wt!sbufe!uispvhi.dvssfout!Jv*
1600 10
Ui (V)
1400 12 10
1200
12
1000 14
800
600 CVIII 350Y/D SVIII 500Y/D
400
200
1600 10 10
Ui (V)
12 12
1400
1200
14 14
1000
800
600 CVI 350 CVI 700
400
200
7
3/4!!Csfbljoh!dbqbdjuz
The breaking capacity Pstmax refers to the maximum switching capacity under safe change over load. According to the
stipulation on IEC 60214-1:2003 the breaking capacity should at least equal to 2 times the rated switching capacity Pstn,
that is, under the associated step voltage (Ui), it should be capable of interrupting 2 times the maximum rated through
current (Ium).
3/5!!!Dpoubdu!mjgf
The main expect contact life of the tap changer arcing contacts can be estimated based on the relative load(=(Iu/I um)as
shown in fig6.
The contact life of a selector switch depends on many influencing factors, particularly the condition of switching.
Therefore,only average data are given in the figure (not applicable to constant current service condition).
n ĊĊ number of operations
Iu ĊĊ Actual through-current
Ium ĊĊ max. rated through-current
Jv0Jvn
Fig.6 Estimated mean contact life under average load conditions
3/6!!Tipsu.djsdvju!tusfohui
The short circuit strength of the tap changer is determined by the dynamic stability and by the thermal short-circuit.
Actually, the short circuit intensity of Type CV tap changer is higher than the requirements of IEC60214-1:2003.
3/7!!Ufnqpsbsz!pwfsmpbe
The OLTCs can be used in oil with temperature from -25ņċ105ņ. If the oil temperature may drop to below -25ņ,
please specify during ordering.
3/8!!Jotvmbujpo
2.7.1 Insulation to earth
The insulation to earth of the on load tap changer depends upon the system rated voltage withstand value.
The rated voltage withstand value of the insulation is applicable to new and well drying insulation material and immersed
in transformer oil (temperature about 20ņ) after impregnation. The insulation to earth is determined by the rated
voltage endurance as stipulated in the IEC Standards.
The withstand voltage corresponds to the maximum voltage
Um of the equipment. See the table in right. insulation level 35 63
highest voltage Um for equipment 40.5 72.5
power frequency test voltage (1 min) 85 140
impulse test voltage 225 350
8
IN1/265/112
d
f
b
b
k b
k k
k
a
a
a
f
f b
b b
without change-over selector with reversing switch with coarse tap selector
Note:
a: between the min. and max. tap of the same phase
b: between any two taps of different phase
c: between the beginning of coarse tap of different phase
d: between the beginning and the end of coarse tap of the same phase.
f: to ground
9
3/9!Uif!wpmubhf!hsbejfou!cfuxffo!uif!ufsnjobmt!pg!dibohf!pwfs!tfmfdups!boe!uif!vqqfs!ufsnjobmt
pg!uif!tfmfdups!gps!uif!dpbstf!sfhvmbujpo!dpjm!)Gjh/8*
b b W a c1
c1
a
K
Gjh/8
Note: Because of the practical arrangement of the change over selector, the voltage gradient between the terminal 0 of
the change over selector and the upper terminal of the selector corresponds to the insulation distance a (same phase) or
the insulation distance b (phase to phase). the insulation distance between the fine regulation selector and the change
over selector is principally not to be considered.
10
IN1/265/112
4/!Tqfdjbm!eftjho!
Potential Resistance of the tap winding
During the operation of the chang-over selector the tap winding is disconnected
momentarily from the main winding, the regulation section will be broken from the main
coil. Then it will be subjected to a bias voltage. The magnitude of which depends upon the
voltage of the adjacent windings as well as the coupling capacities to them and to grounded
parts. This bias voltage is produced at the breaking point of the separating contacts during
the operation of change over selector. If these differential voltages exceed a certain limit
value, measures regarding potentied connection of the winding must be taken.
The limiting value of the bias voltage for the Type CV tap changer is 15kV . If it is
expected that the bias voltage will be higher than this value, the regulation section should
be permanently connected to a fixed potential through a resistance (potential resistance).
See Fig.8.
For calculating the change-over selector stress and for dimensioning the tie-in resistors,
the following details of the transformer specificaton must be known:
Ċ Design of the winding, that is the relative position of the regulation section to the
adjacent coil.
Ċ Capactity between tap winding and adjacent windings or winding parts. Gjh9!Dpoujopvt
ĊCapacity between tap winding and ground or, if existing, grounded adjacent winding. dpoofdujpo!pg
The potential resistance may be installed between the terminals of the oil chamber (Fig. uif!ubq!xjoejoh
9), or in the insulation cylinder at the bottom of the oil chamber (Fig.10).
B-B
D - +
0
W
- +
U
0
W dimensions V
Model
U h1 D
W
V CV Ʊ350Y/SVIII500Y 418 395
B B
CV Ư350 244 342
W
h1
Fig.9 potential resistance installed on the Fig.10 Potential resistance installed at the bottom of the
oil chamber, when number of resistors İ2 oil chamber, when number of resistors ˚2
(not applicable to CV Ʊ350D/SVIII500 D)
11
5/!Dpotusvdujpo!boe!jotubmmbujpo
5/2!!Pjm!gjmmjoh!rvboujuz!pg!uif!ubq!dibohfs.njojnvn!wpmvnf!pg!uif!pjm!ubol.njojnvn!pddvqjfe!wpmvnf
pg!uif!ubq!dibohfs
(See paragraph 2.1 technical data)
The size of the oil tank of the tap changer is determined according to the oil filling quantity after inserting the core of
the selector switch into the oil chamber as shown in theparagraph 2.1 technical data.
We recommend the minimum volume of the conservater will be 10% of the oil filling quantity plus 4 dm3. Consideration
has been taken for the variation of oil quantity under the temperature of!.41ņċ211ņ/
Ensure that no pressure differential (max 0.03MPa) exists between the oil tank of the tap changer and oil of the
transformer conservator.
The quantity of oil filling of transformer oil tank must take into account the volume occupied by the tap changer.
5/3!!Jotubmmbujpo!joup!b!cfmm.uzqf!pjm!ubol
Before installing the on-load tap changer into a transformer with bell-type tank, first,remove the tap changer head.
spring energy accumualator and flange, then fix the tap changer on the mounted supporting structures.
Check:
It is advantageous to put spacer blocks temporarily between supporting structure and supporting flange, the
thickness of spacer blocks should be of 5~20mm to make the OLTC mounitng flange at the same level of the
bell-type oil tank cover, and to remove them before setting up the bell-type cover.
! The connection of the tap changer must be carried out at that position. .
This will ensure that there will be no dragging during the installation of the tap changer
After covering of the bell type oil tank, the tap changer is lifted up by means of a hoist, and installed on the mounting
flange on the cover of the bell type oil tank.
5/4!!Jotubmmbujpo
The installation of the tap changer should be done according to instruction HM0.460.001. Observe the following
during installion:
The connected leads must not exert any force on the tap changer. If necessary, the last section of the lead wire can be
curved to give a cushion.
After drying of the tap changer, it is not permitted to operate before oil filling. If operation is necessary, the oil chamber
must be filled with oil.
If the conservator is removed for shipping, attention should be given to reduce the chamber oil level for the
accommodation of oil expansion.
If the transformer is transported without oil, then the oil in the tap changer must be fully drained, and connected the
internal of the oil chamber to the transformer main oil tank. This time the oil chamber is subject to the same pressure on
the transformer.
During installation of motor-drive unit, following instruction book should be consulted for the installation of driving
shaft and the protective relay:
12
IN1/265/112
5/5!!Eszjoh!boe!pjm!gjmmjoh
To ensure the electrical performance of the tap changer, it must be fully dried and filled with oil according to our
On-Load Tap Changer type CV Operation Instructions HM0.460.001.
4.4.1 Vacuum drying
Heating up: the temperature of the tap changer is raised at a rate of 20ņ per hour in ambient atmosphere until up to
110ņ.
Preparatory: in circulating air at 110ņ!nby!bqqmjfe!up!uif!ubq!dibohfs!gps!b!evsbujpo!pg!21!ipvst.
Vacuum drying: with a temperature of 110ņ!nby, applied to the tap changer and the same drying time as for the
transfornner, at least 10 hours.
4.4.2 Vapor phase drying:
Heating up: enter a kerosene vapor of 90ņ, and keep this temperature constant for 3 to 4 hours.
Drying: the temperature of the vapor is increased at a rate of 10ņ per hour up to the specified and temperature, but
must not exceed 125ņ. The time required for drying is usually the same as the transformer.
4.4.3 Oil filling
After drying, oil filling should be performed immediately under vacuum.
The main oil tank of the transformer and the oil chamber of the tap changer must be commented together with a bypass
pipe so that they can be drawn vacuum at the same time and oil filled up to tank top.
6/!Bddfttpsjft
6/2!!Qspufdujwf!sfmbz!(Please refer to attachment for the types)
The protective relay is installed directly on the connection flange of head cover, and connected to the conservator by pipe.
This pipe should have a slope of at least 2ǁ. When the oil flow in the relay exceeds a critical value, the flap of the relay will
operate, thus operates the NO and NC contacts. There contacts should be connected to the tripping circuit of the
transformer circuit breaker. The transformer will be cut off at once if the relay operates.
For the set composed of 3 single phase on load tap changer, one protective relay should be installed for each single
phase tap changer.
6/3!!Esjwjoh!tibgu!boe!cfwfm!hfbs!cpy
Driving shaft is to realize a mechanical connection between the motor drive unit and the head of the on load tap changer
The function of the bevel gear box is convert the vertical drive into horizontal drive.Installation and assembly of vertical
and horizontal shaft must be performed in accordance with CV operation instruction HM0.460.001.
Number of rotation of the vertical driving shaft per step ns, speed reducing ratio of the bevel gear box i1, speed reducing
ratio of the gear box on the tap changer head cover i2 are listed in the following table.
ns i1 i2
CMA7 33 1ģ1 33ģ1
CMA9 2 2ģ1 1ģ1
SHM-1 16.5 1ģ2 33ģ1
13
6/4!!Npups!esjwf!voju
The motor drive unit is used to drive the on load tap changer for selecting the service position. Within the cabinet of
the motor drive unit, there are all electrical and mechanical features required for driving the on load tap changer.
The control is based on step-by-step principle, that is, the on load tap changer will be changed over from one operating
position to the adjacent one, then it will stop. The operation of the motor drive unit is actuated by a single control
signal and working unintermittently until the work has been done, then it stops. For the Type CV on-load tap changer,
CMA9 and CMA7 or SHM-1 motor drive unit can be selected, please refer to the Appendix for their overall
dimensions.
Data
CMA9 CMA7 SHM-1
Specification
Running time per switching operation (s) About 4.4 About 5 About 4
Voltage for control circuit and heater (V) 220V AC 220V AC 220V AC
52 when energized
Power consumption of heater (W)
24 during running time
Weight (kg) 70 90 73
Note: In order to meet certain service requirements the standard design of motor drive unit may be altered.
14
IN1/265/112
6/5!!Pqfsbujpo!dpouspm!tztufn!pg!uif!po!mpbe!ubq!dibohfs
5.4.1 Type HMC-3C position indicator for the on load tap changer
On-load tap changer position indicator type HMC-3C is a support fitting for CV, CM on-load tap changer, it can be used
to indicate the step of on-load tap changer, it has operation function and indication lamp of “ 1-N ” “stop” “ N-1” of tap changer,
as well as remote control indicator lamp, it’s input is decimal code and output is BCD code.
HMC-3C 74 +10
On-load tap changer position indicator
150 +10
Remote Control 1-N stop N-1 Power
Front panel
CX1
3 1 Front
1 2 3 4 5
7 4 Panel of
12 8
6 7 8 9 16
control cabinet
19
13 Rear
17
160
Power Supply Operation Command CX2
220V 1 2 3 4 5 6
(0.5A)
Connect terminals 1,2,3,4,5 and 6 on rear panel of HMC-3C to X1 of MDU according to the following table.
1 8 1-N
2 12 stop
3 9 N-1
4 11 common
5 23 "remote control"
6 24 indication
15
5.4.2 HMK-2A on-load tap changer automatic voltage regulator
HMK-2A automatic voltage regulator for on-load tap changer (hereinafter is referred to as HMK-2A), combined with
CMA7 and CMA9 motor drive unit, is used for remote automatic voltage regulating.
HMK-2A has two display screens. One for the display of tap position, the other for the display of upper limit voltage,
lower limit voltage, under voltage, over voltage, over current, delay time, signal current value and signal voltage
value.
HMK-2A has the interlocking functions of over voltage, under voltage and over current. Once the signal voltage or
signal current exceeds the setting range, HMK-2A interlocks the function of automatic voltage regulation, setting off
alarms with sound and indicating light.
Through HMK-2A, the upper limit voltage, lower limit voltage, over voltage, over current, delay time can be preset.
HMK-2A also has BCD code position signal output, over voltage, under voltage and over current alarming signal
output terminals. G G G G
b
!,
7
wv~ly h|{v
Ę
mXOWUXhP mYOWUXhP
jY
uva
jX
t[G
`]
G G otrTYh
YXW YYW
XWX
G G
YYW G G a
G
16
IN1/265/112
9 Stop command
12 Over-voltage alarming
14 Over-current alarming
CX1-16
CX1-17
CX1-18
CX1-19
17
HMK-2A CX2 BCD code connection diagram
G G
ikj
jY
G ]G \G [G ZG YG XG
G G G
WXG WG WG WG WG WG XG
WYG WG WG WG WG XG WG
WZG WG WG WG WG XG XG
W[G WG WG WG XG WG WG
W\G WG WG WG XG WG XG
W]G WG WG WG XG XG WG
W^G WG WG WG XG XG XG
W_G WG WG XG WG WG WG
W`G WG WG XG WG WG XG
XWG WG XG WG WG WG WG
XXG WG XG WG WG WG XG
XYG WG XG WG WG XG WG
XZG WG XG WG WG XG XG
X[G WG XG WG XG WG WG
X\G WG XG WG XG WG XG
X]G WG XG WG XG XG WG
X^G WG XG WG XG XG XG
X_G WG XG XG WG WG WG
X`G WG XG XG WG WG XG
YWG XG WG WG WG WG WG
YXG XG WG WG WG WG XG
YYG XG WG WG WG XG WG
YZG XG WG WG WG XG XG
Y[G XG WG WG XG WG WG
Y\G XG WG WG XG WG XG
Y]G XG WG WG XG XG WG
Y^G XG WG WG XG XG XG
Y_G XG WG XG WG WG WG
Y`G XG WG XG WG WG XG
ZWG XG XG WG WG WG WG
ZXG XG XG WG WG WG XG
ZYG XG XG WG WG XG WG
ZZG XG XG WG WG XG XG
Z[G XG XG WG XG WG WG
Z\G XG XG WG XG WG XG
Z]G XG XG WG XG XG WG
Z^G XG XG WG XG XG XG
Z_G XG XG XG WG WG WG
Z`G XG XG XG WG WG XG
u aGj Y G Gi j k G G G SGG G GGk j GY _ } VX h SGj Y T ` GG
i j k G G G UG
18
IN1/265/112
Adopting the large LCD on the interface, on which it can display position, operation counter, signal voltage,
and time delay, etc.
Providing functions of manual, automatic and remote control. Under the manual control mode, the
operation of 1-N, N-1, stop of OLTC can be achieved locally
Being capable of communicating with RS-485 or RS-232 serial ports so as to take control of action of 1-N,
N-1, stop of OLTC.
Being available for either one or maximum three pieces of controllers, which are connected in parallel, with
serial ports under the same communication protocol, identifying by addresses without interfering each
other.
Input mode˖Decimal line encoded input. (for details see 6.4 Connection Diagram)
1 2 3 4 5 6 7
1- Position display
2- LCD
3- The information character
Parallel of parallel control
00033 Manual
4- Operation counter
Step Auto
MLK 5- Time delay
Overflow
010
Signal 1 N 6- Indicator light
Voltage 110.0V N 1
STOP 7- Function keys
9 8
SIGNAL POWER
CX1
LOCK OUT GND SIGNAL POWER
AC 110V AC220V
19
rear panel
209 95 Control screen
210 GG
Controller
242
227
G
98
Fastener
220 101
front panel
Overall dimensions of ET-SZ6 Installation schematice diagram of ET-SZ6
GG
Suggest to use ZXJY-1 oil filter plant for on-load tap changer in below operation status:
1. On-load tap changer is used for rectification transformer and furnace transformer with frequent daily operations,
full capacity operation and frequent overload.
2. Operation surround is with high humidity such as in tropical and subtropical region, in which the oil of on-load
tap changer will be getting much moisture.
! Type CV, universal number of annual tap changing operation ǚ 15000 recommended
CV Ʊ 350D
operating in tropical and subtropical districts with
severe variation of temperature recommended
SV Ʊ 500D
CV Ʊ 350D-72.5 !
The voltage regulating section is arranged at the
starting end of the coil compulsory
SV Ʊ 500D-72.5
Following table shows condition of moisture content and breakdown voltage in OLTC oil during operation.
6. Appendix
20
IN1/265/112
(14XXX)
Connecting flange Q. S. R
E1 Bleeding of tap changer head Type CVIII 350Y CVIII 350D CVI 350
E2 Bleeding of transformer tank Highest voltage
for equipment 40.5kV 72.5kV 40.5kV 72.5kV 40.5kV 72.5kV
Q Connecting flange for oil retune h 1381 1381 1621 1735 901 901
Dimension in
R Connecting flange for protective relay i 346 346 346 346 346 346
mm
21
Overall dimensions of CV 350 (without change-over selector)
(10XXX) (12XXX)
(14XXX)
Connecting flange Q. S. R
E1 Bleeding of tap changer head Type CVIII 350Y CVIII 350D CVI 350
Highest voltage
E2 Bleeding of transformer tank for equipment 40.5kV 72.5kV 40.5kV 72.5kV 40.5kV 72.5kV
Q Connecting flange for oil retune h 1150 1190 1390 1510 670 710
Dimension in
22
IN1/265/112
(1406)
(1405)
(1406)
Connecting flange Q. S. R
23
Overall dimensions of SV 500 (with change-over selector)
A-A Change-over selector terminals
Connecting flange Q. S. R
24
IN1/265/112
(1007A) (1007B)
(10XXX)
(12XXX)
Connecting flange Q. S. R
25
Overall dimensions of CV I 700 (with change-over selector)
(10XXX) (12XXX)
(14XXX)
Connecting flange Q. S. R
26
IN1/265/112
(1007A)
(1007B)
(10XXX) (12XXX)
(14XXX)
Connecting flange Q. S. R
27
On-load tap changer type CV head (for mounting on standard tank cover)
Gasket
Transformer flange
Transformer cover
Connecting flange
Q. S. R
28
IN1/265/112
Transformer bracket
Support flange
29
Sketch of connection flange of the transformer
Transformer flange
30
IN1/265/112
Hinge pin
Washer
fixation of cabinet
319
cover opened by 90
31
CMA9 motor drive unit circuit diagram
32
IN1/265/112
450
2- 25 25 2- 13
62
136
473
972
flange for
cable socket 557
170
327
295 295
30
500
A B
M16
33
CMA7 motor drive unit circuit diagram
34
IN1/265/112
35
Overall dimensions of HMK7 controller
HMK7 CONTROLLER
ė1 1ė
I COMMAND
LOCAL
External connection diagram of SHM-1 motor driver unit and HMK7 controller
X2 motor cable
X1 controlling cable
HMK7 controller
Local
Mode Remate Stop
Site
36
IN1/265/112
(Noter: The digital in brackets represents the number of SHM-1 motor driver unit CX cable)
37
Overall dimensions of bevel gear unit of CV
38
39
Pwfsbmm!ejnfotjpot!boe!jotubmmbujpo!ejnfotjpot!pg!uif!qspufdujwf!sfmbz
H1
15° 15°
H2
85
115
115
Oil conservator is
Connected to this side Oil conservator is
Oil conservator is Connected to this side
15 200
200 Connected to this side
15
25
25
4-14
QJ4-25 QJ4G-25 QJ6-25
Sensor Sensor
Sensor
Type H1 H2 Notice
QJ4-25 215 153 4 terminals, 1 pair of signal contact, 1 pair of trip contact
40
IN1/265/112
Swiveing range of the CV on-load tap changer head gear unit, drive shaft left side
Swiveling range
41
CV on-load tap changer horizontal drive shaft arrangement
arrangement 1 arrangement 2
arrangement 3
arrangement 4
arrangement 5
arrangement I2 I3 I4-I5
2 Ľ 511 .
3 Ľ 511 Ľ 511 dimensions will be decided by
4/5 . Ľ 511 the insulation between phases
6 Ľ 631 Ľ 511
42