Series HMI Connection Manual

Mitsubishi FX5U Ethernet


HMI Factory Setting:

Controller IP Address: 192.168.0.1


Controller Ethernet Port: 1025
Controller Station Number: 0
Control Area / Status Area: D-0 / D-10
Applicable models: DOP-B / DOP-W / DOP-H / HMC series、DOP-100

Connection

Standard jumper Cable/ Network Cable without jumper (Auto-detected by HMI)

Definition of PLC Read/Write Address

a. Registers
Format
Type Read/Write Range Data Length Note
Word No. (n)
Input X-n X-0 – X-1777 Word Octal, 2
Output Y-n Y-0 – Y-1777 Word Octal, 2
Latch Relay L-n L-0 – L-32767 Word 2
Annunciator F-n F-0 – F-32767 Word 2
Step Relay S-n S-0 – S-8191 Word 2
Link Relay B-n B-0 – B-7FFF Word Hexadecimal,2
Special Link Relay SB-n SB-0 – SB-7FF Word Hexadecimal,2
Internal Relay M-n M-0 – M-32767 Word 2
Special Internal Relay SM-n SM-0 – SM-2047 Word 2
Timer Value TN-n TN-0 – TN-23087 Word
Retentive Timer Value SN-n SN-0 – SN-23087 Word
Counter Value CN-n CN-0 – CN-23087 Word
Data Register D-n D-0 – D-4212735 Word
Special Data Register SD-n SD-0 – SD-2047 Word
Index Register Z-n Z-0 – Z-19 Word
File Register R-n R-0 – R-32767 Word
Link Register W-n W-0 – W-4047FF Word Hexadecimal
Special Link Register SW-n SW-0 – SW-7FF Word Hexadecimal

b. Contacts
Type Format Read/Write Range Note

V1.00 Revision August, 2017


Series HMI Connection Manual

Bit No. (b)


Input Xb X-0 – X-1777 Hexadecimal
Output Yb Y-0 – Y-1777 Hexadecimal
Latch Relay L-b L-0 – L-32767
Annunciator F-b F-0 – F-32767
Step Relay S-b S-0 – S-8191
Link Relay B-b B-0 – B-7FFF Hexadecimal
Special Link Relay SB-b SB-0 – SB-7FF Hexadecimal
Internal Relay M-b M-0 – M-32767
Special Internal Relay SM-b SM-0 – SM-2047
Timer Contact TS-b TS-0 – TS-23087
Timer Coil TC-b TC-0 – TC-23087
Retentive Timer Contact SS-b SS-0 – SS-23087
Retentive Timer Coil SC-b SC-0 – SC-23087
Counter Contact CS-b CS-0 – CS-23087
Counter Coil CC-b CC-0 – CC-23087
Data Register D-n.b D-0.0 – D-4212735.15
File Register R-n.b R-0.0 – R-32767.15
Link Register W-n.b W-0.0 – W-4047FF.F Hexadecimal

N
OT
E

1) Before using this communication protocol, the user needs to set communication module
via GX Developer programming tools. For more detailed information regarding the
setting method, please refers to Mitsubishi PLC User Manual.
2) The device address must be the multiple of 16.