Ufgs 08 51 13
Ufgs 08 51 13
------------------------------------
Preparing Activity: NAVFAC Superseding
UFGS-08 51 13 (May 2011)
DIVISION 08 - OPENINGS
SECTION 08 51 13
ALUMINUM WINDOWS
05/19
PART 1 GENERAL
1.1 REFERENCES
1.2 SUBMITTALS
1.3 QUALITY ASSURANCE
1.3.1 Qualification of Manufacturer
1.3.2 Shop Drawing Requirements
1.3.3 Engineer's Qualifications for Blast Design
1.3.4 Sample Requirements
1.3.4.1 Finish Sample Requirements
1.3.4.2 Window Sample Requirements
1.3.4.3 Mock-Ups
1.3.5 Design Data Requirements
1.3.6 Test Report Requirements
1.3.7 Certification
1.4 DELIVERY AND STORAGE
1.5 PLASTIC IDENTIFICATION
1.6 PERFORMANCE REQUIREMENTS
1.6.1 Wind Loading Design Pressure
1.6.2 Tests
1.7 DRAWINGS
1.8 WINDOW PERFORMANCE
1.8.1 Structural Performance
1.8.2 Antiterrorism Performance Requirements
1.8.2.1 Computational Design Analysis Method
1.8.2.2 Dynamic Design Analysis Method
1.8.2.3 Standard Airblast Test Method
1.8.3 Air Infiltration
1.8.4 Water Penetration
1.8.5 Thermal Performance
1.8.5.1 Southern Climate
1.8.5.2 South-Central Climate
1.8.5.3 North-Central Climate
1.8.5.4 Northern Climate
SECTION 08 51 13 Page 1
1.8.5.5 Subarctic Climate
1.8.6 Life Safety Criteria
1.8.7 Sound Attenuation
1.8.8 Windborne-Debris-Impact Performance
1.9 WARRANTY
PART 2 PRODUCTS
2.1 WINDOWS
2.1.1 Awning Windows (AP)
2.1.2 Casement Windows (C)
2.1.3 Hung Windows (H)
2.1.4 Horizontal Sliding Windows (HS)
2.1.5 Projected Windows (AP)
2.1.6 Top-Hinged Windows (TH)
2.1.7 Vertically Pivoted Windows (VP)
2.1.8 Fixed Windows (F)
2.1.9 Forced Entry Resistant Windows
2.1.10 Glass and Glazing
2.1.11 Caulking and Sealing
2.1.12 Weatherstripping
2.1.13 Sash Poles
2.2 FABRICATION
2.2.1 Provisions for Glazing
2.2.2 Fasteners
2.2.3 Adhesives
2.2.4 Drips and Weep Holes
2.2.5 Combination Windows
2.2.6 Mullions and Transom Bars
2.2.7 Accessories
2.2.7.1 Hardware
2.2.7.2 Fasteners
2.2.7.3 Window-Cleaner Anchors
2.2.7.4 Window Anchors
2.2.8 Finishes
2.2.8.1 Anodic Coating
2.2.8.2 Organic Coating
2.2.9 Screens
2.2.9.1 Insect Screen
2.3 SPECIAL OPERATORS
2.3.1 Pole Operators
2.3.2 Extension Crank Operators
2.3.3 Mechanical Operators
2.4 THERMAL-BARRIER WINDOWS
2.5 MULLIONS
2.6 WINDOW CLEANERS' BOLTS
PART 3 EXECUTION
3.1 SCHEDULE
3.2 INSTALLATION
3.2.1 Method of Installation
3.2.2 Dissimilar Materials
3.2.3 Anchors and Fastenings
3.2.4 Adjustments After Installation
3.3 CLEANING
SECTION 08 51 13 Page 2
**************************************************************************
USACE / NAVFAC / AFCEC UFGS-08 51 13 (May 2019)
------------------------------------
Preparing Activity: NAVFAC Superseding
UFGS-08 51 13 (May 2011)
SECTION 08 51 13
ALUMINUM WINDOWS
05/19
**************************************************************************
NOTE: This guide specification covers the
requirements for R, LC, CW and AW performance class
aluminum windows.
**************************************************************************
1. Windows requiring UL fire rating must be steel,
and may occur in conjunction with aluminum windows
which cannot be approved for this use. When steel
windows are used in conjunction with aluminum,
specify finish matching aluminum windows. Steel
SECTION 08 51 13 Page 3
windows should be specified in Section 08 51 23
STEEL WINDOWS.
**************************************************************************
NOTE: On the drawings, show:
SECTION 08 51 13 Page 4
4. Method of anchoring windows to adjoining
construction; size and types of clips, anchors,
screws, or other fasteners.
PART 1 GENERAL
1.1 REFERENCES
**************************************************************************
NOTE: This paragraph is used to list the
publications cited in the text of the guide
specification. The publications are referred to in
the text by basic designation only and listed in
this paragraph by organization, designation, date,
and title.
SECTION 08 51 13 Page 5
AAMA 701/702 (2011) Voluntary Specification for Pile
Weatherstripping and Replaceable
Fenestration Weatherseals
SECTION 08 51 13 Page 6
ASTM E413 (2022) Classification for Rating Sound
Insulation
SECTION 08 51 13 Page 7
Performance
1.2 SUBMITTALS
**************************************************************************
NOTE: Review Submittal Description (SD) definitions
in Section 01 33 00 SUBMITTAL PROCEDURES and edit
the following list, and corresponding submittal
items in the text, to reflect only the submittals
required for the project. The Guide Specification
technical editors have classified those items that
require Government approval, due to their complexity
or criticality, with a "G." Generally, other
submittal items can be reviewed by the Contractor's
Quality Control System. Only add a "G" to an item
if the submittal is sufficiently important or
complex in context of the project.
SECTION 08 51 13 Page 8
as proof of compliance for sustainability Guiding
Principles Validation or Third Party Certification
and as described in Section 01 33 00 SUBMITTAL
PROCEDURES.
**************************************************************************
Windows; G, [_____]
Fabrication Drawings
Windows; G, [_____]
] Hardware; G, [_____]
Fasteners; G, [_____]
Mullions; G, [_____]
Screens; G, [_____]
Weatherstripping; G, [_____]
Accessories; G, [_____]
Adhesives
SD-04 Samples
Finish Sample
Window Sample
SECTION 08 51 13 Page 9
Structural Calculations for Deflection; G, [_____]
][ Windborne-Debris-Impact Performance
] SD-07 Certificates
**************************************************************************
NOTE: Provide engineer's qualifications when
required to show conformance to UFC 4-010-01, DoD
Minimum Antiterrorism Requirements for Buildings.
**************************************************************************
[ Engineer's Qualifications
Plastic Identification
**************************************************************************
SECTION 08 51 13 Page 10
NOTE: Provide engineer's qualifications when
required to show conformance to UFC 4-010-01, DoD
Minimum Antiterrorism Requirements for Buildings.
**************************************************************************
**************************************************************************
NOTE: Choose one of the following options. Include
the first choice for projects requiring a large
number of windows. Include the second choice for
projects requiring a limited number of windows.
**************************************************************************
[ Submit one full-size window of each type proposed for use, complete with
AAMA Label, glazing, hardware, anchors, and other accessories. Where
screens or weatherstripping is required, fit sample windows with such
items that are to be used. After approval, install each sample in work,
clearly identified, and record its location.
][Submit one full-size corner of each window type proposed for use. Where
screens or weatherstripping is required, fit sample with such items that
are to be used.
][1.3.4.3 Mock-Ups
**************************************************************************
NOTE: Requesting mock-up samples of aluminum
windows is not required for most projects. Size of
project and scope of quality control should be
carefully evaluated before requiring Contractor to
provide a costly mock-up. Delete paragraph if
mock-ups are not required.
**************************************************************************
SECTION 08 51 13 Page 11
Submit design analysis with calculations showing that the design of each
different size and type of aluminum window unit and its anchorage to the
structure[.] [meets the requirements of paragraph ANTITERRORISM
PERFORMANCE REQUIREMENTS.] Calculations verifying the structural
performance of each window proposed for use, under the given loads, must
be prepared and signed by a registered professional engineer. Reflect the
window components and anchorage devices to the structure, as determined by
the design analysis, in the shop drawings.
**************************************************************************
NOTE: Include bracketed wording when windows are
required to resist blast loads all required by UFC
4-010-01, DoD Minimum Antiterrorism Requirements for
Buildings.
**************************************************************************
Submit test reports for each type of window attesting that identical
windows have been tested and meet the requirements specified herein for
conformance to AAMA/WDMA/CSA 101/I.S.2/A440 including test size, [and]
minimum condensation resistance factor (CRF)[, and resistance to forced
entry][, and, for Antiterrorism windows, in lieu of a Design Analysis,
results of a Standard Airblast Test].[ For Antiterrorism windows, in lieu
of a Design Analysis, results of airblast testing, whether by arena test
or shock tube, must be included in a test report, providing information in
accordance with ASTM F1642/F1642M, as prepared by the independent testing
agency performing the test. The test results must demonstrate the ability
of each window proposed for use to withstand the airblast loading
parameters and achieve the hazard level rating specified in paragraph
STANDARD AIRBLAST TEST METHOD.]
1.3.7 Certification
**************************************************************************
NOTE: Energy Star Certification is required for
residential windows. FEMP Designation, Passivhaus,
and PHIUS Certifications are methods to ensure
compliance with thermal performance.
**************************************************************************
Each prime window unit must bear the AAMA Label warranting that the
product complies with AAMA/WDMA/CSA 101/I.S.2/A440. Certified test
reports attesting that the prime window units meet the requirements of
AAMA/WDMA/CSA 101/I.S.2/A440, including test size, will be acceptable in
lieu of product labeling.
SECTION 08 51 13 Page 12
damaging the windows. Repair damaged windows to an "as new" condition as
approved. If windows can not be repaired, provide a new unit.
**************************************************************************
NOTE: The marking system indicated below is
intended to provide assistance in identification of
products for making subsequent decisions as to
handling, recycling, or disposal.
**************************************************************************
[1.6.2 Tests
Minimum design load for a uniform-load structural test must be 2400 pascal
50 psf.
SECTION 08 51 13 Page 13
][Test double-hung windows in accordance with the applicable portions of the
AAMA WSG.1 for air infiltration, water resistance, uniform-load
deflection, and uniform-load structural test.
]]1.7 DRAWINGS
Submit the Fabrication Drawings for aluminum window units showing complete
window assembly including hardware, weatherstripping, and subframe
assembly details.
**************************************************************************
NOTE: Structural performance, air infiltration and
water penetration are standard performance
requirements for all aluminum window types.
SECTION 08 51 13 Page 14
Aluminum windows must meet the following performance requirements.
Perform testing requirements by an independent testing laboratory or
agency.
Design window frames, mullions, sashes, and glazing to the criteria listed
herein. Include computational design analysis calculations verifying the
structural performance of each window system proposed for use, under the
given static equivalent loads.
**************************************************************************
NOTE: The blanks in the following paragraph should
be the value of the equivalent 3-second duration
design loading obtained from Figure 1 of ASTM F2248
for the explosive weight and standoff distance
combination (based on the established DBT/LOP) that
is being designed for in this project. This section
must be completed by an engineer experienced in
blast-resistant design.
**************************************************************************
**************************************************************************
NOTE: Connection Design: For mullion and framing
members designed using dynamic analysis or shown to
work through airblast testing, all connections
SECTION 08 51 13 Page 15
between mullions and/or framing members and all
connections of storefront systems to the supporting
structure must be designed for the full dynamic
capacity of the attached member or the maximum
calculated dynamic reaction with a load factor equal
to 1.0. Use ultimate capacity of fasteners as
recommended by the fastener manufacturer with a
capacity reduction factor of 0.75. Use Load and
Resistance Factor Design (LRFD) with appropriate
reduction (phi) factors per material specific code
for design of connections components into supporting
structure. All dynamic and static material strength
increase factors for the connection components must
be equal to 1.0. All connection designs must be
performed checking all conventional failure
mechanisms. See Engineering Technical Report (PDC
TR-10-02) titled Blast Resistant Design Methodology
for Window Systems Designed Statically and
Dynamically at USACE Protective Design Center
(Website link:
https://pdc.usace.army.mil/library/tr/10-02) for
additional information. Calculations/Design
Analysis for the connection design as stated above
must be completed by an engineer experienced in
blast-resistant design.
**************************************************************************
**************************************************************************
NOTE: Use the first bracketed requirement below if
the maximum air blast pressure is greater than
one-half the magnitude of the load resistance of the
blast resistant glazing.
**************************************************************************
NOTE: The blanks in the following paragraph should
be the value of the peak positive pressure and
impulse for the explosive weight and standoff
distance combination (based on the established
DBT/LOP) that is being designed for in this
project. Choose the first bracketed items, low
hazard rating/very low level of protection for
inhabited building occupancy as defined in UFC
4-010-01 (Table B-1). Choose the second bracketed
items, very low hazard rating/low level of
protection for primary gathering/billeting building
occupancy as defined in UFC 4-010-01 (Table B-1).
Dynamic analysis is preferred because it typically
SECTION 08 51 13 Page 16
yields a more appropriate and economical / efficient
design. The values for input into the blanks in the
following paragraph related to ‘ductility ratio’ and
‘maximum support rotation’ (for the appropriate
level of protection – very low, low) for steel and
aluminum framing/mullions can be found in
Engineering Technical Report (PDC TR-10-02) titled
Blast Resistant Design Methodology for Window
Systems Designed Statically and Dynamically at USACE
Protective Design Center (Website link:
https://pdc.usace.army.mil/library/tr/10-02). This
section must be completed by an engineer experienced
in blast-resistant design.
**************************************************************************
Design window assembly using a dynamic analysis to prove the system will
provide performance equivalent to or better than a [low];[very low];
[_____] hazard rating in accordance with ASTM F2912 for the peak positive
pressure of [_____] kilopascals (kPa) [_____]pounds per square inch (psi)
and peak positive phase impulse of [_____] kilopascal-millisecond
(kPa-msec) [_____] pounds per square inch - millisecond (psi-msec). Use a
triangular blast load using the applicable pressure and impulse indicated
above. The allowable response limits of [aluminum] [steel] frame elements
are as follows: Maximum ductility ratio of [_____] and maximum support
rotation of [_____] degrees.
**************************************************************************
NOTE: The blanks in the following paragraph should
be the value of the peak positive pressure and
impulse for the explosive weight and standoff
distance combination (based on the established
DBT/LOP) that is being designed for in this
project. Choose the first bracketed items, low
hazard rating/very low level of protection for
inhabited building occupancy as defined in UFC
4-010-01. Choose the second bracketed items, very
low hazard rating/low level of protection for
primary gathering building occupancy as defined in
UFC 4-010-01. This section must be completed by an
engineer experienced in blast-resistant design.
**************************************************************************
SECTION 08 51 13 Page 17
replicate anchorage of the window support system with the method of
installation to be used for the project. The minimum airblast loading
parameters for the test will be as follows: peak positive pressure of
[_____] kilopascals (kPa) [_____] pounds per square inch (psi) and peak
positive phase impulse of [_____] kilopascal-millisecond (kPa-msec)
[_____] pounds per square inch - millisecond (psi-msec). The hazard
rating for the proposed window systems, as determined by the rating
criteria of ASTM F2912, to provide performance equivalent to or better
than a [low];[very low]; [_____] hazard rating (i.e. the "No Break", "No
Hazard", "Minimal Hazard", "Very Low Hazard" and “Low Hazard” ratings are
acceptable. "High Hazard" ratings are unacceptable. Results of window
systems previously tested by test protocols other than ASTM F1642/F1642M
may be accepted provided the required loading, hazard level rating, and
size limitations stated herein are met.
**************************************************************************
NOTE: Window properties are critical to energy
performance and comfort. Specify low U value (rate
of heat transfer) to reduce winter heat loss and
summer heat gain.
SECTION 08 51 13 Page 18
residential aluminum window products.
Windows installed in Climate Zone [1] [2] will have a U-Factor of [1.3]
[1.25] [_____] W/m2.degrees C [0.40][_____] BTU/h.ft2.degrees F or less and
a SHGC of [0.25] [_____] or less.
Windows installed within Climate Zone [5] [6] [7] will have a U-Factor of
[0.65] [1.25][_____] W/m2.degrees C [0.27] [_____] BTU/h.ft2.degrees F or
less and a SHGC of [0.36] [0.41] [_____] or less.
**************************************************************************
NOTE: Designer must indicate on the drawings which
windows serve as rescue and/or secondary means of
escape.
**************************************************************************
Provide windows that conform to NFPA 101 Life Safety Code when rescue
and/or second means of escape are indicated.
**************************************************************************
NOTE: Aluminum environmental control windows have a
"built-in" sound attenuation. This paragraph will
be used only when sound attenuation is a design
parameter. Use outside-indoor transmission class
(OITC) when exterior source noise is a concern.
**************************************************************************
SECTION 08 51 13 Page 19
space between two pieces of 6 mm 1/4 inch.
**************************************************************************
NOTE: Retain WINDBORNE-DEBRIS-IMPACT RESISTANCE
Paragraph if required by Project. The UFC 1-200-01
DoD Building Code cited IBC defines windborne debris
regions. Enhanced protection applies to essential
facilities. Verify site specific requirements with
the AHJ. Delete items not required.
**************************************************************************
Exterior window system including glazing must comply with indicated basis
or enhanced protection testing requirements in ASTM E1996 for [Wind Zone
1] [Wind Zone 2] [Wind Zone 3] [Wind Zone 4] when tested according to
ASTM E1886. Test specimens must be no smaller in width and length than
glazing indicated for use on Project and must be installed in same manner
as glazing indicated for use on Project.
][c. Small-Missile Test: For glazing located more than 9.1 m 30 feet above
grade.
]]1.9 WARRANTY
PART 2 PRODUCTS
2.1 WINDOWS
**************************************************************************
NOTE: AAMA/WDMA/CSA 101/I.S.2/A440 includes a
designation system with a four part code, which
includes Product Type, Performance Class,
Performance Grade (design pressure) and maximum size
tested to achieve desired rating (example Double
Hung or H, CW30 760 by 1520 (30 by 60)). Product
Type is an abbreviation for window type (AP for
awning, hopper, projected window, C for casement, H
for hung, etc.). Performance classes represent the
level of performance (R, LC, CW and AW).
Performance Grade represents the design pressure to
which the window is constructed.
SECTION 08 51 13 Page 20
AAMA/WDMA/CSA 101/I.S.2/A440 also includes criteria
for specifying windows required to meet higher
design pressures if minimum pressure is inadequate.
These windows are designated as Optional Performance
Grade and should be specified in increments of 240 Pa
5 psf above the minimum Performance Grade.
**************************************************************************
**************************************************************************
NOTE: Consult AAMA 1503 "Voluntary Test Method for
Transmittance and Condensation Resistance of
Windows, Doors and Glazed Wall Sections" and select
the minimum Condensation Resistance Factor (CRF)
required for the particular project conditions.
**************************************************************************
**************************************************************************
NOTE: Consult AAMA/WDMA/CSA 101/I.S.2/A440 to
calculate design pressure(s) applicable to the
project. Adjust "design factors" because naval
facilities are typically less than 100 miles from
hurricane ocean line.
**************************************************************************
**************************************************************************
NOTE: Use materials with recycled content where
appropriate for use. Verify suitability,
availability within the region, cost effectiveness
and adequate competition before specifying product
recycled content requirements.
**************************************************************************
**************************************************************************
NOTE: Performance Grades represent design pressure
values for which products have been tested. Specify
SECTION 08 51 13 Page 21
an Optional Performance Grade where a higher than
minimum Performance Grade is desired due to severe
weather conditions and wind loadings. Optional
Performance Grade windows must be tested in
compliance with AAMA/WDMA/CSA 101/I.S.2/A440.
Testing must substantiate requirements for uniform
loading (structural), water resistance, and air
infiltration.
**************************************************************************
Type AP-[R15] [LC25] [CW30] [AW40] [ [R] [LC] [CW] [AW]- [_____] (Optional
Performance Grade)]. Conceal operating mechanism within the frame members
or enclose within a metal casing not less than 1.59 mm 0.0625 inch thick
sheet aluminum.
Type C-[R15] [LC25] [CW30] [AW40] [ [R] [LC] [CW] [AW]- [_____] (Optional
Performance Grade)]. Ventilators must be[ rotary crank][ handle]
operated. Provide ventilators over 1650 millimeters 65 inches high with
two separate locking devices or a two-point locking device operated by
rods from a single lever handle. Conceal rods where possible.[ Provide
casement windows in combination with [fixed][projected] windows specified
below.]
**************************************************************************
NOTE: Tilt-in windows most likely will not meet
ATFP pressure requirements and should not be
specified if force protection is required.
**************************************************************************
[Double][_____] Hung, Type H-[R15] [LC25] [CW30 ][AW40] [ [R] [LC] [CW]
[AW]- [_____] (Optional Performance Grade)]. Test and rate sash balance
to conform with AAMA 902.
Type HS-[R15] [LC25] [CW30] [AW40] [ [R] [LC] [CW] [AW]- [_____] (Optional
Performance Grade)].
Type AP-[R15] [LC25] [CW30] [AW40] [ [R] [LC] [CW] [AW]- [_____] (Optional
Performance Grade)]. Provide projected windows with concealed four bar
friction hinges only. Gear-type rotary hardware to comply with AAMA 901.
Provide operators that function without requiring the removal of interior
screens.
SECTION 08 51 13 Page 22
2.1.7 Vertically Pivoted Windows (VP)
**************************************************************************
NOTE: Pivoting windows most likely will not meet
ATFP pressure requirements and should not be
specified if force protection is required.
**************************************************************************
Type VP-[R15] [LC25] [CW30] [AW40] [ [R] [LC] [CW] [AW]-[_____] (Optional
Performance Grade)].[ Provide window with remotely operated venetian
blind mounted between an access sash and the main sash.]
Type F-[R15] [LC25] [CW30] [AW40] [ [R] [LC] [CW] [AW]- [_____] (Optional
Performance Grade)].
**************************************************************************
NOTE: Conventional aluminum windows offer nominal
resistance to forced entry by unskilled or
opportunistic intruders. While there is no way to
make a window absolutely "burglar proof," windows
complying with AAMA 1302 can provide reasonable
assurance that entry, or attempted entry, will leave
ample evidence of "forced entry." It establishes
only a pass/fail condition when specific
concentrated loads are applied to sash or ventilator
in attempt to open or remove sash or ventilator from
window frame and specifies no measured time delay.
It provides moderate degree of security against
unskilled or opportunistic intruder at little or no
additional cost. When forced entry resistant
windows are specified, coordinate glazing
requirements and specify impact resistant glass and
glazing materials in Section 08 81 00 GLAZING.
SECTION 08 51 13 Page 23
2.1.12 Weatherstripping
2.2 FABRICATION
**************************************************************************
NOTE: Specify glass thickness and vinyl gaskets in
Section 08 81 00 GLAZING. Inside glazing is
preferred, especially for windows above first floor
and other locations where access is difficult.
Windows designed for inside glazing may not be
available in double-hung type; check manufacturers'
literature. Where project requires insulating
glass, show sash members, glazing beads, and
hardware of sufficient size and weight to receive
and support glass of thickness specified. Allow 3 mm
1/8 inch minimum between each side of insulating
glass and metal frame and between edges of glass and
frame for glazing compound and expansion. Drawings
must clearly indicate method for securing insulating
glass in place.
**************************************************************************
**************************************************************************
NOTE: Include the bracket option for minimum
glazing frame bite requirements when personnel
density is greater than one person per 40 square
meters 430 square feet and minimum ATFP standoff
distances are met. This does not include guard type
facilities, single and duplex detached family
housing. These requirements are specified in
Department of Defense Antiterrorism Standards for
Buildings.
**************************************************************************
Design windows and rabbets suitable for glass thickness shown [or
specified].[ For minimum antiterrorism windows, attach glazing to its
supporting frame using structural silicone sealant or adhesive glazing
tape in accordance with ASTM F2248.] Design sash for[ inside][ outside][
single][ double] glazing and for securing glass with[ metal beads,][
glazing clips,][ glazing channels,] or glazing compound.
SECTION 08 51 13 Page 24
2.2.2 Fasteners
2.2.3 Adhesives
**************************************************************************
NOTE: Specify the design pressure used to specify
the Performance Grade or the Optional Performance
Grade for the adjoining windows.
**************************************************************************
**************************************************************************
NOTE: Include the bracketed paragraph included
under the "WINDOWS" heading for static loads when
minimum measures of antiterrorism/force protection
(ATFP) are required and delete the first bracketed
sentence in the following paragraph.
**************************************************************************
[Provide mullions between multiple window units to resist two times (2X)
glazing resistance in accordance with ASTM F2248 and ASTM E1300. ]Provide
mullions with a thermal break. Secure mullions and transom bars to
adjoining construction and window units in such a manner as to permit
expansion and contraction and to form a weathertight joint.[ Where window
cleaner anchors are required, reinforce mullions and anchor to adjoining
construction so as to provide safe and adequate support.] Provide mullion
covers on the interior and exterior to completely close exposed joints and
recesses between window units and to present a neat appearance.[ Provide
special covers over structural support at mullions as indicated.]
2.2.7 Accessories
SECTION 08 51 13 Page 25
receptors[ and subsill] with each window unit.]
2.2.7.1 Hardware
**************************************************************************
NOTE: Use stainless steel hardware in humid
locations or project locations with Environmental
Severity Classifications (ESC) of C3 thru C5. Humid
locations are those in ASHRAE climate zones 0A, 1A,
2A, 3A, 3C, 4C and 5C (as identified in ASHRAE
90.1). See UFC 1-200-01 for determination of ESC
for project locations.
**************************************************************************
2.2.7.2 Fasteners
**************************************************************************
NOTE: Window-cleaner anchors should be shown and
specified for windows having sills more than 1800 mm
6 feet above grade, adjoining balconies, or
adjoining roofs, unless window cleaning methods at
activity make use of anchors unnecessary.
Coordinate window cleaning procedures and
requirements with using activity. When requested by
using activity, removable or tilting-type sash may
be provided instead of anchors. Removable or
tilting-type sash may be specified as Contractor
option when these units are desired by using
activity and are economically competitive with
double-hung sash equipped with anchors. When
appropriate, add the following at end of paragraph
WINDOW-CLEANER ANCHORS:
SECTION 08 51 13 Page 26
must be stainless steel of size and design required for the window type
and application, conforming to ASTM A276/A276M. Provide two anchors for
each single window[ and each adjacent fixed glass window unit]. Fasten
anchors 1120 mm 44 inches above the window sill utilizing appropriate
methods for the window type and application in accordance with industry
safety standards.
2.2.8 Finishes
**************************************************************************
NOTE: Specify anodic and organic coatings as
Contractor's option when these finishes are
determined to be economically competitive in the
project area, unless the project requires use of one
or the other to match an existing condition.
**************************************************************************
Comply with NAAMM's "Metal Finishes Manual" for applying and designating
finishes. Exposed aluminum surfaces must be factory finished with an[
anodic coating][ or][ organic coating].[ Color must be [_____][ as
indicated].] All windows[ for each building] must have the same finish.
**************************************************************************
NOTE: Specify Architectural Class I in locations
with an Environmental Severity Classification (ESC)
of C3 through C5, locations where microenvironments
may create a locally corrosive environment
regardless of ESC (e.g., prevailing winds,
ventilation, waterfront environments, and
penetrations of the building envelope), high
humidity interior areas (bathrooms, locker rooms,
pools, trainers), areas open to the exterior
(mechanical rooms and hangars), and spaces that are
not conditioned by design or may not be conditioned
during prolonged periods due to deployment or
non-occupancy. See UFC 1-200-01 for determination
of ESC for project locations. Specify Architectural
Class II for all atmospheric conditions not
requiring Class I.
**************************************************************************
SECTION 08 51 13 Page 27
]2.2.8.2 Organic Coating
**************************************************************************
NOTE: When anodic and organic coatings are
determined to be economically competitive in the
project area, specify baked enamel finish (AAMA
2603) as an option to Architectural Class II, anodic
coating or high-performance finish (AAMA 2604 or
AAMA 2605) as an option to Architectural Class I,
anodic coating.
**************************************************************************
Clean and prime exposed aluminum surfaces. Provide a[ baked enamel finish
in accordance with AAMA 2603 with total dry film thickness not less than
0.02 mm 0.8 mil][ high-performance finish in accordance with [AAMA 2604][
AAMA 2605] with total dry film thickness of not less than 0.03 mm 1.2 mils
].
2.2.9 Screens
**************************************************************************
NOTE: Remote and group operated windows will
require special operators. Identify these windows
on the drawings and show method of operation.
**************************************************************************
SECTION 08 51 13 Page 28
for each room.
**************************************************************************
NOTE: When motor driven operators are specified,
specify electrical characteristics in Section
26 20 00, INTERIOR DISTRIBUTION SYSTEM.
**************************************************************************
e. Operating and storm sash must be factory-glazed with the type of glass
indicated and of the quality specified in Section 08 81 00 GLAZING.
2.5 MULLIONS
**************************************************************************
NOTE: Drawings must indicate the profile and
dimensions of mullions, anchorage and reinforcing
members as required for wind loading, and the type,
profile, and fastening system for the mullion cover
(screw-fastened or snap-on).
**************************************************************************
SECTION 08 51 13 Page 29
receive weatherstripping, sealant, or tape at the point of contact with
each window flange.
Provide window cleaners' bolts for all windows 2100 millimeter 7 feet or
higher above finished grade, except for windows that can be removed and
cleaned from the ground or from a lower roof level without the use of an
extension ladder. Provide two bolts for each single window unit and each
fixed glass unit. Locate bolts 1120 millimeter 44 inches above the window
sill.
PART 3 EXECUTION
3.1 SCHEDULE
1 inch 25 mm
3.2 INSTALLATION
SECTION 08 51 13 Page 30
materials by keeping ventilators tightly closed and locked to frame. Bed
screws or bolts in sill members, joints at mullions, contacts of windows
with sills, built-in fins, and subframes in mastic sealant of a type
recommended by the window manufacturer. Install and caulk windows in a
manner that will prevent entrance of water and wind. Fasten insect
screens securely in place.
Any materials that show visual evidence of biological growth due to the
presence of moisture must not be installed on the building project.
Make provision for securing units to each other, to masonry, and to other
adjoining construction. Windows installed in masonry walls must have head
and jamb members designed to recess into masonry wall not less than 11 mm
7/16 inch.
3.3 CLEANING
-- End of Section --
SECTION 08 51 13 Page 31